K-LINE K109PT1000 E N

K-LINE K109PT1000 E N
CONVERTERS AND INTERFACES
K-LINE
K109PT1000
Temperature converters
K-LINE
PT1000 Converter
► INPUT: PT1000 at 2,3,4 wires with zero and span
►
►
►
►
►
►
►
configurable by dip-switch
OUTPUT: N.1 channel current 0/4..20, 20..4/0 mA or
voltage 0..5/10, 10..0, 1..5 Vdc
Galvanic isolation at 3-way.
Spring-cage terminal block and/or DIN bus connection
system
Power bridging terminal - DIN rail bus connector
Tiny dimensions (102,5 x 93,1 x 6,2 mm)
Resolution @ 14 bit
Precision class 0.1%
TECHNICAL DATA
K109PT – PT100
K109PT1000
– PT1000
converter
Converter
ORDER CODES
K109PT1000
PT1000 converter
Accessories
K-BUS
Expandable power supply connector
K-SUPPLY
Power Supply module with surge protection
GENERAL FEATURES
Power supply
19,2…30 Vdc
Design
Channels
N.1
Filter rejection
Terminal housing for mounting on 35 mm DIN 46277
50-60 Hz (settable)
Accuracy
(20,5 K / temp + 0.05) % (Measurement range)
DIP Switch
-Inputs signal setup
-Output signal setup
Status indicators
Setting error
Wrong connection
Internal improper functioning
Processing
Floating point 32 bit
Dimensions
6,2 x 93,1 x 102,5 mm (w x h x d)
Galvanic Isolation
Power supply // input // output at 1500 Vac, digital
Weight
50 g
Hot swapping
Yes
Operating temperature
-20..+65 °C
Power consumption
500 mW
Connections
Plug-in screw clamp terminal blocks, wires up to 2.5 mm2
A/D Converter
14 bit
IP Protection
IP 20
Current output protection
Approximately 25 mA
Standards
EN50081-2
EN50082-2
EN61010-1
EN60742
Approvals
CE
Security output
- 102.5% of full scale value, in case of over-range
- 105% of full scale value in case of improper functioning
Humidity
30..90% a +40°C (not condensing)
INPUT
OUTPUT
PT1000 probe, EN 60751/A2 (ITS90)
Connection by 2, 3 or 4 wires
Current on sensor: < 900 uA
Cable resistance: Max. 20 Ohm per wire
Measurement Range: -200..210 °C
Min span : 30°C
Current: 0..20 mA, 4..20 mA, 20..0 mA e 20..4 mA
Higher load resistance: 500 Ohm
Voltage: 0..5 Vdc, 1..5 Vdc, 0..10 Vdc and 10..0 Vdc
Lower load resistance: 2 KOhm
DIMENSIONS AND INSTALLATION
Inserting / Extracting module on DIN guide
Power supply
Expandable connector K-BUS
Input
Cage clamp connection
Output