Accessories and Spare Parts For 3RT, 3RH Contactors and Contactor Relays ■

Accessories and Spare Parts For 3RT, 3RH Contactors and Contactor Relays ■
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
■ Overview
The auxiliary switch blocks and the maximum number of blocks
that can be mounted are described in the sections "Motor Contactors" and "Contactor Relays".
With the OFF-delay variant of the timing relay, the contactor coil
is contacted directly through the relay; terminals A1 and A2 of
the contactor coil must not be connected.
The timing relays are suitable for both AC and DC operation.
Solid-state time-delay auxiliary switch block
Size S00
The timer module, which is available in the "ON-DELAY" and
"OFF-DELAY" versions, allows time-delayed functions up to
100 s (3 distinct delay ranges).
The version for size S00 contactors is fitted onto the front of the
contactor (with the supply voltage switched off) and then slid
into its latched position; at the same time, the timing relay is connected by means of plug-in contacts to coil terminals A1 and A2
of the contactor. Any contactor coil terminals which are not required are sealed off by means of covers on the enclosure of the
time-delay block, to prevent them from being connected
inadvertently.
It contains a relay with one NO contact and one NC contact; depending on the version, the relay is switched either after an ONdelay or after an OFF-delay.
The timer module with "WYE-DELTA FUNCTION" is equipped
with one delayed and one instantaneous NO contact, with a
dead time of 50 ms between the two. The delay time of the NO
contact can be adjusted between 1.5 s and 30 s.
A varistor is integrated in the timer module in order to damp
opening surges in the contactor coil.
The solid-state, time-delay block cannot be mounted on size S00
coupling relays.
Wye-delta function:
Sizes S0 to S3
N S B 0 _ 0 0 4 5 3 b
A 1 /A 2
Y 2 7 /2 8
3 7 /3 8
t
5 0 m s
The time-delay block for size S0 to S3 contactors is plugged into
coil terminals A1 and A2 on top of each contactor; the timing relay is connected both electrically and mechanically by means of
pins.
The contactor on which the solid-state, time-delay auxiliary
switch block is mounted operates without a delay.
A varistor is integrated in the timer module in order to damp
opening surges in the contactor coil.
Size S00
Configuring note:
The solid-state, time-delay auxiliary switch block is fitted onto the
front side of the contactor. The timer module is supplied with
power directly by plug-in contacts through the coil terminals of
the contactor, in parallel with A1/A2. The timing function is activated by closing the contactor on which the auxiliary switch
block is mounted. The OFF-delay version operates without an
auxiliary voltage; minimum ON period: 200 ms.
A varistor is integrated in the timer module in order to damp
opening surges in the contactor coil.
The solid-state, time-delay auxiliary switch block cannot be
mounted on size S00 coupling relays.
Sizes S0 to S12
The solid-state, time-delay auxiliary switch block is fitted onto the
front side of the contactor.
The timer module is supplied with power through two terminals
(A1/A2); the time delay of the auxiliary switch block can be activated either by a parallel link to any contactor coil or by any
power source.
The OFF-delay version operates without an auxiliary voltage;
minimum ON period: 200 ms.
A single-pole auxiliary switch block can be snapped onto the
front of the contactor in addition to the timer module.
The timer module has no integrated components for overvoltage
damping.
Solid-state time-delay block with semiconductor output
The timer module in the "ON-DELAY" and "OFF-DELAY with auxiliary voltage" versions allows time-delayed functions up to 100 s
(3 distinct delay ranges). Contactors fitted with a time-delay
block close or open after a delay according to the set time.
The ON-delay variant of the timing relay is connected in series
with the contactor coil; terminal A1 of this coil must not be
connected.
a)
L1
NSB0_00454b
b)
NSB0_00455b
L1
K3
S1
A1 B1 A2
K3
S1
A1 B1 A2
K3
1
1
2
A1
A2
N
2
A1
A2
N
$ Timing relay block
% Contactor
The activation of loads parallel to the start input is not permissible when using AC control voltage (see (a) in the circuit
diagram).
The 3RT19 16-2D. . . / 3RT19 26-2D. . . OFF-delay timing relay
blocks have a zero potential start input B1. This means that if
there is a parallel load on terminal B1, activation can be simulated with AC voltage. In this case, the additional load
(e. g. contactor K3) must be wired according to (b).
OFF-delay device for size S00 to S3 contactors
AC and DC operation
IEC 60947, EN 60947.
For screw and snap-on mounting onto 35 mm standard mounting rail. The OFF-delay devices have screw terminals.
The OFF-delay device prevents a contactor from dropping out
unintentionally when there is a short-time voltage dip or voltage
failure. It supplies a downstream, DC-operated contactor with
the necessary energy during a voltage dip, ensuring that the
contactor does not trip. The 3RT19 16 OFF-delay devices are
specifically designed for operation with the 3RT contactors and
3RH contactor relays of the SIRIUS series.
The OFF-delay device operates without external voltage on a capacitive basis, and can be energized with either AC or DC (24 V
version only for DC operation). Voltage matching, which is only
necessary with AC operation, is performed using a rectifier
bridge.
Siemens LV 1 · 2009
3/97
3
Snap-on auxiliary switch blocks
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
If the command devices are upstream of the OFF-delay device
in the circuit, the OFF-delay takes effect with every opening operation. If the opening operation is downstream of the OFF-delay
device, an OFF-delay only applies in the event of failure of the
mains voltage.
A so-called counter-e.m.f. (electromotive force) is produced
when motors or various inductive loads are turned off. Voltage
peaks of up to 4000 V may occur as a result, with a frequency
spectrum from 1 kHz to 10 MHz and a rate of voltage variation
from 0.1 to 20 V/ns.
4000 V
NSB0_00456c
A contactor opens after a delay when the capacitors of the solenoid coil, built into the OFF-delay device, are switched in parallel. In the event of voltage failures, the capacitors are discharged
via the solenoid coil and thereby delay the opening of the
contactor.
V
3
Operation
In the case of the versions for rated control supply voltages of
110 V and 230 V, either AC voltage or DC voltage can be applied
on the line side, whereas the variant for 24 V is designed for DC
operation only.
A DC-operated contactor is connected to the output in accordance with the input voltage that is applied.
The mean value of the OFF-delay is approximately 1.5 times the
specified minimum time.
Surge suppressors
• Without LED (also for Cage Clamp terminals)
size S00, S0, S2, S3, S6 to S12
• With LED (also for Cage Clamp terminals)
size S00
All 3RT1 contactors and 3RH1 contactor relays can be retrofitted
with RC elements or varistors for damping opening surges in the
coil. Diodes or diode assemblies (comprising noise suppression
diodes and Zener diodes for rapid switch-off) can be used.
The surge suppressors are plugged onto the front of size S00
contactors. Space is provided for them next to a snap-on auxiliary switch block.
With all size S0 to S3 contactors, varistors, RC elements and diode assemblies can be plugged on directly at the coil terminals,
either on the top or underneath.
The plug-in direction of the diodes and diode assemblies is determined by a coding device.
Coupling relays are supplied either without surge suppression or
with a varistor or diode connected as standard, according to the
version.
Note:
The OFF-delay times of the NO contacts and the ON-delay times
of the NC contacts increase if the contactor coils are damped
against voltage peaks (noise suppression diode 6 to 10 times;
diode assemblies 2 to 6 times, varistor +2 to 5 ms).
Electromagnetic interference suppression module, 3-phase
for size S00 contactors
3/98
Siemens LV 1 · 2009
400 V
500 ms
t
Capacitive input to various analog and digital signals makes it
necessary to suppress interference in the load circuit.
Reducing contact arcing
The connection between the main current path and the EMC
suppression module enables contact arcing, which is responsible for contact erosion and the majority of clicking noises, to be
reduced; this in turn is conducive to an electromagnetically compatible design.
Higher operational reliability
Since the EMC suppression module achieves a significant reduction in radio-frequency components and the voltage level in
three phases, the contact endurance is also improved considerably. This makes an important contribution towards enhancing
the reliability and availability of the system as a whole.
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
Dispensing with fine graduations
Coupling links for mounting on contactors of sizes S0 to S3
There is no need for fine graduations within each performance
class, as smaller motors inherently have a higher inductance, so
that one solution for all fixed-speed operating mechanisms up to
5.5 kW is adequate.
DC operation
NSB0_00457c
V
The coupling link is suitable for use in any climate. It is fingersafe according to EN 50274. The terminal designations comply
with EN 50005.
System-compatible operation with 24 V DC,
operating range 17 to 30 V.
Low power consumption in conformity with the technical specifications of the solid-state systems. An LED indicates the switching state.
Surge suppression
The 3RH19 24-1GP11 coupling link has an integrated surge
suppressor (varistor) for the contactor coil being switched.
Mounting
The 3RH19 24-1GP11 coupling link is mounted directly on the
contactor coil.
930 V
Solder pin adapters
400 V
500 ms
t
• The varistor circuit can absorb a high energy level and can
also be used for frequencies ranging from 10 to 400 Hz
(closed-loop controlled operating mechanisms). There is no
limiting below the knee-point voltage, however.
The solder pin adapters for the size S00 contactors are available
in two versions:
• Solder pin adapter for contactors with one integrated auxiliary
contact
• Solder pin adapter for contactors with mounted 4-pole auxiliary switch block
NSB0_00458c
Screw adapters
V
Plug-on adapters improve the accessibility of the screw fixing for
size S0 contactors. As a result it is possible to position the screwdriver vertically even when using insulated screwdrivers or
power screwdrivers.
Optionally the adapters can be rotated through 90° before
mounting.
Sealable covers for sizes S00 to S12
950 V
400 V
500 ms
t
Additional load module
• Size S00 for plugging onto the front of the contactors with and
without auxiliary switch block
When contactors and contactor relays are used in safetyoriented applications, it must be ensured that it is impossible to
operate the contactors manually.
For SIRIUS contactors there are sealable covers available for
this purpose as accessories; these prevent accidental manual
operation. These are transparent molded-plastic caps with a
bracket that enables the contactor to be sealed.
Siemens LV 1 · 2009
3/99
3
Two electrical versions are available:
• The advantages of the RC circuit lie mainly in the reduction in
the rate of rise and in its RF damping ability. The selected values ensure effective interference suppression over a wide
range.
IEC 60947 and EN 60947.
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
■ Selection and ordering data
3
PU (UNIT, SET, M) = 1
PS*
= 1 unit
PG
= 101
3RH19 11-1HA. .
3RH19 11-1FA. .
For contactors
3RH19 11-2HA. .
3RH19 21-1HA. .
Auxiliary contacts
Ident. No.
Type
3RH19 21-2HA. .
3RH19 21-2FA. .
DT Screw terminals
Version
Order No.
3RH19 11-1AA. .
3RH19 11-1LA. .
Weight DT Cage Clamp terminals
per PU
approx.
Price
per PU
NO NC NO NC
Order No.
kg
Weight
per PU
approx.
Price
per PU
kg
Auxiliary switch blocks for snapping onto the front
according to EN 50012
Size S00
For assembling contactors with 2, 4 or 5 auxiliary contacts
3RT10 1.-1. . .1,
3RT10 1.-2. . .1
Ident. No. 10 E
11 E
22 E
23 E
32 E
-1
1
2
1
2
3
2
-----
-----
}
}
}
}
3RH19 11-1HA01
3RH19 11-1HA12
3RH19 11-1HA13
3RH19 11-1HA22
0.060
0.060
0.060
0.060
}
}
}
}
3RH19 11-2HA01
3RH19 11-2HA12
3RH19 11-2HA13
3RH19 11-2HA22
0.060
0.060
0.060
0.060
3
2
1
2
1
2
3
2
-----
-----
}
}
}
B
3RH19 21-1HA31
3RH19 21-1HA22
3RH19 21-1HA13
3RH19 21-1XA22-0MA0
0.075
0.075
0.075
0.075
}
}
}
D
3RH19 21-2HA31
3RH19 21-2HA22
3RH19 21-2HA13
3RH19 21-2XA22-0MA0
0.075
0.075
0.075
0.075
Sizes S0 ... S121)
4-pole
3RT10 2,
3RT1. 3 ... 3RT1. 7
31
22
13
22 2)
Auxiliary switch blocks for snapping onto the front
according to EN 50005
Size S00
2 or 4-pole auxiliary switch blocks for assembling contactors with 3 or 5 auxiliary contacts
3RT1. 1,
3RH11,
3RH14
20
11
02
11 U
2
1
---
-1
2
--
---1
---1
}
}
}
}
3RH19 11-1FA20
3RH19 11-1FA11
3RH19 11-1FA02
3RH19 11-1FB11
0.050
0.050
0.050
0.050
}
}
}
A
3RH19 11-2FA20
3RH19 11-2FA11
3RH19 11-2FA02
3RH19 11-2FB11
0.050
0.050
0.050
0.050
40
31
22
22 U
11, 11 U
4
3
2
-1
-1
2
-1
---2
1
---2
1
}
}
}
}
}
3RH19 11-1FA40
3RH19 11-1FA31
3RH19 11-1FA22
3RH19 11-1FC22
3RH19 11-1FB22
0.060
0.060
0.060
0.060
0.060
}
}
}
}
B
3RH19 11-2FA40
3RH19 11-2FA31
3RH19 11-2FA22
3RH19 11-2FC22
3RH19 11-2FB22
0.060
0.060
0.060
0.060
0.060
1- and 2-pole auxiliary switch blocks with cable entry from one side
• Cable entry from above
3RT1. 1,
3RH11,
3RH14
-----
1
-1
2
-1
1
--
-----
-----
}
}
}
}
3RH19 11-1AA10
3RH19 11-1AA01
3RH19 11-1LA11
3RH19 11-1LA20
0.015
0.015
0.045
0.045
-----
-----
}
}
}
}
3RH19 11-1BA10
3RH19 11-1BA01
3RH19 11-1MA11
3RH19 11-1MA20
0.015
0.015
0.045
0.045
-----
• Cable entry from below
3RT1. 1,
3RH11,
3RH14
-----
1
-1
2
-1
1
--
-----
For multi-unit packing and reusable packaging, see "Appendix --> Order information".
1)
Exception: 3RT12, 3RT16.
2)
With identification numbers 5, 6, 7, 8.
* You can order this quantity or a multiple thereof.
3/100
Siemens LV 1 · 2009
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
PU (UNIT, SET, M) = 1
PS*
= 1 unit
PG
= 101
2RH19 21-2F. .
For contactors
Auxiliary contacts
Ident. No.
Type
3RH19 21-1C. .
3RH19 21-2C. .
DT Screw terminals
Version
Order No.
3RH19 21-1LA. .
3RH19 21-1MA. .
Weight DT Cage Clamp terminals
per PU
approx.
Price
per PU
NO NC NO NC
Order No.
Weight
per PU
approx.
Price
per PU
kg
kg
Auxiliary switch blocks for snapping onto the front
according to EN 50005
Sizes S0 to S121)
4-pole auxiliary switch blocks
3RT10 2,
3RT1. 3
...
3RT1. 7
40
31
22
04
22 U
4
3
2
---
-1
2
4
--
----2
----2
}
}
}
}
}
3RH19 21-1FA40
3RH19 21-1FA31
3RH19 21-1FA22
3RH19 21-1FA04
3RH19 21-1FC22
}
}
}
A
A
3RH19 21-2FA40
3RH19 21-2FA31
3RH19 21-2FA22
3RH19 21-2FA04
3RH19 21-2FC22
0.075
0.075
0.075
0.075
0.075
0.020 }
0.020 }
0.020
0.020
3RH19 21-2CA10
3RH19 21-2CA01
---
0.020
0.020
0.075
0.075
0.075
0.075
0.075
1-pole auxiliary switch blocks to EN 50005 and EN 50012
3RT1. 2
...
3RT1. 7
-----
1
----
-1
---
--1
--
---1
}
}
}
}
3RH19 21-1CA10
3RH19 21-1CA01
3RH19 21-1CD10
3RH19 21-1CD01
2-pole auxiliary switch blocks with cable entry from one side
• Cable entry from above
3RT1. 2,
3RT1. 3
...
3RT1. 7
----
1
2
--
1
-2
----
----
}
}
}
3RH19 21-1LA11
3RH19 21-1LA20
3RH19 21-1LA02
0.075
0.075
0.075
----
----
}
}
}
3RH19 21-1MA11
3RH19 21-1MA20
3RH19 21-1MA02
0.075
0.075
0.075
----
• Cable entry from below
3RT1. 2,
3RT1. 3
...
3RT1. 7
1)
----
1
2
--
1
-2
----
Exception: 3RT16.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
3/101
3
3RH19 21-1F. .
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
3
PU (UNIT, SET, M) = 1
PS*
= 1 unit
PG
= 101
3RH19 11-1GA. .
For contactor relays
Contacts
DT
Ident. No. Version
NO
3RH19 11-2GA. .
Weight
per PU
approx.
Screw terminals
Order No.
NC
DT
Price
per PU
Weight
per PU
approx.
Cage Clamp
terminals
Order No.
kg
Price
per PU
kg
Snap-on auxiliary switch blocks
according to EN 50011
For assembling contactor relays with 8 contacts
3RH11 40,
3RH14 40
(Ident. No. 40E)
80E
71E
62E
53E
44E
4
3
2
1
--
-1
2
3
4
}
}
}
}
}
3RH19 11-1GA40
3RH19 11-1GA31
3RH19 11-1GA22
3RH19 11-1GA13
3RH19 11-1GA04
0.060
0.060
0.060
0.060
0.060
}
}
}
}
}
3RH19 11-2GA40
3RH19 11-2GA31
3RH19 11-2GA22
3RH19 11-2GA13
3RH19 11-2GA04
0.060
0.060
0.060
0.060
0.060
For multi-unit packing and reusable packaging, see
"Appendix --> Order information".
* You can order this quantity or a multiple thereof.
3/102
Siemens LV 1 · 2009
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
3RH19 21-1DA11
3RH19 21-1JA11
3RH19 21-2DA11
3RH19 21-2JA11
For contactors
Auxiliary contacts
DT
Version
Type
NO
3RH19 21-1EA. .
3RH19 21-1KA. .
3RH19 21-2EA. .
3RH19 21-2KA..
Screw terminals
Weight
per PU
approx.
Order No.
NC
DT
Price
per PU
3
PU (UNIT, SET, M) = 1
PS*
= 1 unit
PG
= 101
Weight
per PU
approx.
Cage Clamp
terminals
Order No.
Price
per PU
kg
kg
Laterally mountable auxiliary switch blocks
according to EN 50012
Sizes S0 ... S12
First laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 2 ... 3RT1. 7
1
1
}
3RH19 21-1DA11
0.050 }
3RH19 21-2DA11
0.050
3RH19 21-2JA11
0.050
3RH19 21-2EA20
-3RH19 21-2EA02
0.050
3RH19 21-2KA20
-3RH19 21-2KA02
0.050
Sizes S3 ... S12
Second laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 4 ... 3RT1. 7
1
1
}
3RH19 21-1JA11
0.050 }
Laterally mountable auxiliary switch blocks
according to EN 50005
Sizes S0 ... S12
First laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 2 ... 3RT1. 7
2
1
--
-1
2
}
}
}
3RH19 21-1EA20
3RH19 21-1EA11
3RH19 21-1EA02
0.050 }
0.050
0.050 }
0.050
Sizes S3 ... S12
Second laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 4 ... 3RT1. 7
2
1
--
-1
2
}
}
}
3RH19 21-1KA20
3RH19 21-1KA11
3RH19 21-1KA02
0.050 D
0.050
0.050 D
0.050
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
3/103
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
3
PU (UNIT, SET, M) = 1
PS*
= 1 unit
PG
= 101
3RH19 11-1NF. .
3RH19 11-2NF. .
For
Version
contactors
3RH19 21-1FE22
Contacts
DT Screw terminals
Version
Type
NO
3RH19 21-2JE22
Order No.
NO1) NC1) NC
3RH19 21-2DE11
3RH19 21-2JE11
Weight DT Cage Clamp
per PU
terminals
approx.
Price
per PU
Order No.
kg
Weight
per PU
approx.
Price
per PU
kg
Solid-state compatible auxiliary switch blocks for snapping onto the front,
according to EN 50005
Size S00
3RT1. 1,
3RH11,
3RH14
For operation in dusty atmo1
sphere and solid-state circuits 2
with rated operational currents -Ie/AC-14 and DC-13 from 1 mA
to 300 mA at 3 V to 60 V.
Hard gold-plated contacts.
No mirror contacts.
----
----
1
-2
}
}
A
3RH19 11-1NF11
3RH19 11-1NF20
3RH19 11-1NF02
0.045 A
0.045 A
0.045 A
3RH19 11-2NF11
3RH19 11-2NF20
3RH19 11-2NF02
0.045
0.045
0.045
1
1
1
}
3RH19 21-1FE22
0.070 B
3RH19 21-2FE22
0.070
}
3RH19 21-2DE11
0.050
}
3RH19 21-2JE11
0.050
Sizes S0 ... S12
3RT1. 2
...
3RT1. 7
For operation in dusty atmo1
sphere and solid-state circuits
with rated operational currents
Ie/AC-14 and DC-13 from 1 mA
to 300 mA at 3 V to 60 V.
Hard gold-plated contacts.
Mirror contacts acc.
to EN 60947-4-1, Appendix F
Solid-state compatible auxiliary switch blocks, laterally mountable,
according to EN 50012
Sizes S0 ... S12
First laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 2
...
3RT1. 7
1
1 NO + 1 NC solid-state
compatible auxiliary switches
For operation in dusty atmosphere and solid-state circuits
with rated operational currents
Ie/AC-14 and DC-13 from 1 mA
to 300 mA at 3 V to 60 V.
Hard gold-plated contacts.
Mirror contacts acc.
to EN 60947-4-1, Appendix F
--
--
1
--
Sizes S3 ... S12
Second laterally mountable auxiliary switch block (right or left), 2-pole
3RT1. 4
...
3RT1. 7
1)
1
1 NO + 1 NC solid-state
compatible auxiliary switches
For operation in dusty atmosphere and solid-state circuits
with rated operational currents
Ie/AC-14 and DC-13 from 1 mA
to 300 mA at 3 V to 60 V.
Hard gold-plated contacts.
Mirror contacts acc.
to EN 60947-4-1, Appendix F
--
--
1
--
1 NO + 1 NC standard auxiliary switches:
see Technical Information LV 1 T –> "Technical specifications".
* You can order this quantity or a multiple thereof.
3/104
Siemens LV 1 · 2009
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
For
Auxiliary
contactors contacts
Rated control
supply voltage
Us1)
Time setDT
ting range t
Type
V
s
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Solid-state time-delay auxiliary switch blocks for snapping onto
the front, terminal designations according to DIN 46199-5
Size S00
1 NO + 1 NC 24 AC/DC3)
0.05 ... 1
0.5 ... 10
5 ... 100
}
}
B
3RT19 16-2EJ11
3RT19 16-2EJ21
3RT19 16-2EJ31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
100 ... 127 AC3)
0.05 ... 1
0.5 ... 10
5 ... 100
C
}
}
3RT19 16-2EC11
3RT19 16-2EC21
3RT19 16-2EC31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
200 ... 240 AC3)
0.05 ... 1
0.5 ... 10
5 ... 100
D
}
}
3RT19 16-2ED11
3RT19 16-2ED21
3RT19 16-2ED31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
OFF-delay without auxiliary voltage (varistor integrated)4)
3RT19 16-2. . . .
3RT1. 1,
3RH112)
3RH14
1 NO + 1 NC 24 AC/DC3)
0.05 ... 1
0.5 ... 10
5 ... 100
}
}
}
3RT19 16-2FJ11
3RT19 16-2FJ21
3RT19 16-2FJ31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
100 ... 127
AC/DC3)
0.05 ... 1
0.5 ... 10
5 ... 100
C
}
B
3RT19 16-2FK11
3RT19 16-2FK21
3RT19 16-2FK31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
200 ... 240
AC/DC3)
0.05 ... 1
0.5 ... 10
5 ... 100
D
}
}
3RT19 16-2FL11
3RT19 16-2FL21
3RT19 16-2FL31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
0.5 ... 10
0.5 ... 10
0.5 ... 10
B
B
C
3RT19 16-2LJ21
3RT19 16-2LC21
3RT19 16-2LD21
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
1.5 ... 30
1.5 ... 30
1.5 ... 30
}
D
}
3RT19 16-2GJ51
3RT19 16-2GC51
3RT19 16-2GD51
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
0.05 ... 1
0.5 ... 10
5 ... 100
D
}
A
3RT19 26-2EJ11
3RT19 26-2EJ21
3RT19 26-2EJ31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
100 ... 127 AC5)
0.05 ... 1
0.5 ... 10
5 ... 100
C
}
D
3RT19 26-2EC11
3RT19 26-2EC21
3RT19 26-2EC31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
200 ... 240 AC5)
0.05 ... 1
0.5 ... 10
5 ... 100
D
}
B
3RT19 26-2ED11
3RT19 26-2ED21
3RT19 26-2ED31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
0.05 ... 1
0.5 ... 10
5 ... 100
}
}
}
3RT19 26-2FJ11
3RT19 26-2FJ21
3RT19 26-2FJ31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
100 ... 127 AC5)
0.05 ... 1
0.5 ... 10
5 ... 100
D
}
C
3RT19 26-2FK11
3RT19 26-2FK21
3RT19 26-2FK31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
200 ... 240 AC5)
0.05 ... 1
0.5 ... 10
5 ... 100
D
A
A
3RT19 26-2FL11
3RT19 26-2FL21
3RT19 26-2FL31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
1.5 ... 30
}
3RT19 26-2GJ51
1
1 unit
101
0.090
1.5 ... 30
}
3RT19 26-2GC51
1
1 unit
101
0.090
1.5 ... 30
}
3RT19 26-2GD51
1
1 unit
101
0.090
OFF-delay with auxiliary voltage
3RT10 1
3RH11
1 CO
24 AC/DC
100 ... 127 AC
200 ... 240 AC
Wye-delta function (varistor integrated)
3RT10 12)
1 NO
24 AC/DC3)
delayed +
100 ... 127 AC3)
1 NO instan- 200 ... 240 AC3)
taneous,
dead time
50 ms
Sizes S0 ... S12
With ON-delay
3RT10,
3RT13,
3RT14,
3RT15
1 NO + 1 NC 24 AC/DC5)
3RT19 26-2. . . .
OFF-delay without auxiliary voltage4)
3RT10,
3RT13,
3RT14,
3RT15
1 NO + 1 NC 24 AC/DC5)
Wye-delta function
3RT10,
3RT13,
3RT14,
3RT15
1 NO,
24 AC/DC5)
delayed +
100 ... 127 AC5)
1 NO, instan200 ... 240 AC5)
taneous,
dead time
50 ms
1)
The AC voltages are valid for 50 Hz and 60 Hz.
2)
Cannot be fitted onto coupling relays.
3)
The terminals for the control supply voltage are connected to the contactor
by the integrated spring contacts of the solid-state time-delay auxiliary
switch above it when this switch is mounted.
4) Setting of output contacts in as-supplied state not defined (bistable relay).
Application of the control supply voltage once results in contact
changeover to the correct setting.
5)
Terminals A1 and A2 for the control supply voltage of the solid-state timedelay auxiliary switch must be connected to the associated contactor by
means of connecting cables.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
3/105
3
ON-delay (varistor integrated)
3RT1. 1,
3RH112)
3RH14
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
For contactors
Rated control
supply voltage Us
Time setting
range t
Type
V
s
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Solid-state time-delay blocks with semiconductor output
Size S00
For mounting onto the front of contactors
• ON-delay (varistor integrated)
3
3RT1. 1,
3RH111)
3RH14
3RT19 16-2C. . .
24 ... 66 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
B
}
B
3RT19 16-2CG11
3RT19 16-2CG21
3RT19 16-2CG31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.050
0.050
0.050
90 ... 240 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
D
}
}
3RT19 16-2CH11
3RT19 16-2CH21
3RT19 16-2CH31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.050
0.050
0.050
• OFF-delay with auxiliary voltage (varistor integrated)
3RT1. 1,
3RH111)
3RH14
3RT19 16-2D. . .
24 ... 66 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
C
B
B
3RT19 16-2DG11
3RT19 16-2DG21
3RT19 16-2DG31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.060
0.060
0.060
90 ... 240 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
D
}
B
3RT19 16-2DH11
3RT19 16-2DH21
3RT19 16-2DH31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.060
0.060
0.060
Sizes S0 ... S3
For mounting onto coil terminals on top of the contactors
Only for devices with screw terminals
• ON-delay (varistor integrated)
3RT10 2,
3RT10 3,
3RT10 4,
3RT132)
3RT15
24 ... 66 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
D
B
D
3RT19 26-2CG11
3RT19 26-2CG21
3RT19 26-2CG31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.050
0.050
0.050
90 ... 240 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
}
}
}
3RT19 26-2CH11
3RT19 26-2CH21
3RT19 26-2CH31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.050
0.050
0.050
3RT19 26-2C. . .
• OFF-delay with auxiliary voltage (varistor integrated)
3RT10 2,
3RT10 3,
3RT10 4,
3RT132)
3RT15
24 ... 66 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
D
D
D
3RT19 26-2DG11
3RT19 26-2DG21
3RT19 26-2DG31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.050
0.050
0.050
90 ... 240 AC/DC
0.05 ... 1
0.5 ... 10
5 ... 100
C
D
C
3RT19 26-2DH11
3RT19 26-2DH21
3RT19 26-2DH31
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.050
0.050
0.050
3RT19 26-2D. . .
OFF-delay devices
3RT1. 1,
3RT1. 2,
3RH1. . .-1BF40
110 AC/DC
D
3RT19 16-2BK01
1
1 unit
101
0.150
3RT1. 1,
3RT1. 2,
3RH1. . .-1BM40
220/230 AC/DC
D
3RT19 16-2BL01
1
1 unit
101
0.150
}
3RT19 16-2BE01
1
1 unit
101
0.150
3RT1. 1 ... 3RT1. 4, 24 DC
3RH1. . .-1BB40
3RT19 16-2B.01
Pneumatic delay blocks,
terminal designation according to EN 50005
3RT1. 2
For mounting onto the front side of size S0 contactors3)4)
Auxiliary contacts 1 NO and 1 NC
• ON-delay
0.1 ... 30
1 ... 60
C
C
3RT19 26-2PA01
3RT19 26-2PA11
1
1
1 unit
1 unit
101
101
0.080
0.080
0.1 ... 30
1 ... 60
C
C
3RT19 26-2PR01
3RT19 26-2PR11
1
1
1 unit
1 unit
101
101
0.080
0.080
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.130
0.130
0.130
• OFF-delay
3RT19 26-2P. . .
Mechanical latching blocks
Sizes S0 and S2
For mounting on 1 contactor,
contactor remains in the energized state even after a voltage failure
3RT1. 2,
3RT1. 3
24 AC/DC
110 AC/DC
230 AC/DC
A
B
B
3RT19 26-3AB31
3RT19 26-3AF31
3RT19 26-3AP31
3RT19 26-3A.31
1)
Cannot be fitted onto coupling relays.
2)
Not to be used for 3RT10 4. and 3RT13 4. contactors with Us ≤ 42 V.
3)
In addition to these, no other auxiliary contacts are permitted.
4)
Versions according to DIN VDE 0116 on request.
* You can order this quantity or a multiple thereof.
3/106
Siemens LV 1 · 2009
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
For con- Version
tactors
Type
Rated control
supply voltage Us1)
AC
operation
DC
operation
V AC
V DC
DT
Order No.2)
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Surge suppressors without LED
(also for Cage Clamp terminals)
Size S00
Varistors
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
}
}
A
}
A
3RT19 16-1BB00
3RT19 16-1BC00
3RT19 16-1BD00
3RT19 16-1BE00
3RT19 16-1BF00
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.010
0.010
0.010
0.010
0.010
3RT1.,
3RH1
RC elements
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
}
}
}
}
}
3RT19 16-1CB00
3RT19 16-1CC00
3RT19 16-1CD00
3RT19 16-1CE00
3RT19 16-1CF00
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.010
0.010
0.010
0.010
0.010
3RT1.,
3RH1
Noise suppression
diodes
--
12 ... 250
}
3RT19 16-1DG00
1
1 unit
101
0.010
3RT1.,
3RH1
Diode assemblies
(diode and Zener
diode) for DC operation
--
12 ... 250
}
3RT19 16-1EH00
1
1 unit
101
0.010
3RT19 16-1DG00
Size S0
For fitting onto the coil terminals at top or bottom
3RT1. 2 Varistors
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
}
}
}
}
B
3RT19 26-1BB00
3RT19 26-1BC00
3RT19 26-1BD00
3RT19 26-1BE00
3RT19 26-1BF00
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.025
0.025
0.025
0.025
0.025
3RT1. 2 RC elements
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
}
}
}
}
B
3RT19 26-1CB00
3RT19 26-1CC00
3RT19 26-1CD00
3RT19 26-1CE00
3RT19 26-1CF00
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.025
0.025
0.025
0.025
0.025
• Connectable at the -top (e. g. for contac- -tor with overload relay)
24
30 ... 250
}
}
3RT19 26-1ER00
3RT19 26-1ES00
1
1
1 unit
1 unit
101
101
0.025
0.025
• Connectable at the -bottom (e. g. for fuse- -less load feeders)
24
30 ... 250
}
A
3RT19 26-1TR00
3RT19 26-1TS00
1
1
1 unit
1 unit
101
101
0.025
0.025
3RT19 26-1B.00
3RT1. 2 Diode assemblies
For DC operation
1)
Can be used for AC operation for 50/60 Hz. Please inquire about further
voltages.
2)
For packs of 10 units, the Order No. must be supplemented with "-Z" and
the order code "X90".
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
3/107
3
For plugging onto the front side of the contactors with and without auxiliary switch blocks
3RT1.,
3RH1
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
For contactors
Version
Rated control supply
voltage Us1)
Type
AC
operation
DC
operation
V AC
V DC
DT
Order No.2)
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Surge suppressors without LED
(also for Cage Clamp terminals)
Sizes S2 and S3
For fitting onto the coil terminals at top or bottom
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
--
}
}
}
}
B
3RT19 26-1BB00
3RT19 26-1BC00
3RT19 26-1BD00
3RT19 26-1BE00
3RT19 26-1BF00
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.025
0.025
0.025
0.025
0.025
3RT1. 33) RC elements
,
3RT1. 4
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
---
}
}
}
}
B
3RT19 36-1CB00
3RT19 36-1CC00
3RT19 36-1CD00
3RT19 36-1CE00
3RT19 36-1CF00
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.040
0.040
0.040
0.040
0.040
• Connectable at the top
(e. g. for contactor with
overload relay)
24
30 ... 250
}
}
3RT19 36-1ER00
3RT19 36-1ES00
1
1
1 unit
1 unit
101
101
0.025
0.025
• Connectable at the bottom (e. g. for fuseless
load feeders)
24
30 ... 250
}
B
3RT19 36-1TR00
3RT19 36-1TS00
1
1
1 unit
1 unit
101
101
0.025
0.025
1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
1 unit
101
101
101
101
101
0.035
0.035
0.035
0.035
0.035
3
3RT1. 3, Varistors
3RT1. 4
3RT19 26-1B.00
3RT19 36-1C.00
3RT1. 3, Diode assemblies
3RT1. 4 For DC operation
Sizes S6 ... S12
For connecting to withdrawable coil with screw terminals with contactors with
• 3RT1. ..-.A... conventional operating mechanism
• 3RT1. ..-.N... conventional operating mechanism
3RT1. 5, RC elements
3RT1. 6,
3RT19 56-1C.00 3RT1. 7
24 ... 48
48 ... 127
127 ... 240
240 ... 400
400 ... 600
24 ... 70
70 ... 150
150 ... 250
--
1)
Can be used for AC operation for 50/60 Hz. Please inquire about further
voltages.
2)
For packs of 10 or 5 units "-Z" and order code "X90" must be added to the
Order No.
3)
Mountable only at the top for 3RT1. 3/AC operating mechanism.
For
Version
contactors
Type
Rated control
supply voltage Us1)
AC
operation
DC
operation
V AC
V DC
Power consumption
of LED
at Us
}
}
}
}
C
3RT19 56-1CB00
3RT19 56-1CC00
3RT19 56-1CD00
3RT19 56-1CE00
3RT19 56-1CF00
DT
Order No.2)
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Surge suppressors with LED
(also for Cage Clamp terminals)
Size S00
For plugging onto the front side of the contactors with and without auxiliary switch blocks
24 ... 48
48 ... 127
127 ... 240
--
3RT1,
3RH1.
Varistors
3RT1,
3RH1.
Noise sup- -pression
-diodes
--
12 ... 24
24 ... 70
70 ... 150
150 ... 250
10 ... 120
20 ... 470
50 ... 700
160 ... 950
}
}
}
A
3RT19 16-1JJ00
3RT19 16-1JK00
3RT19 16-1JL00
3RT19 16-1JP00
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.010
0.010
0.010
0.010
24 ... 70
50 ... 150
150 ... 250
20 ... 470
50 ... 700
160 ... 950
}
}
}
3RT19 16-1LM00
3RT19 16-1LN00
3RT19 16-1LP00
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.010
0.010
0.010
3RT19 16-1L.00
1)
Can be used for AC operation for 50/60 Hz. Please inquire about further
voltages.
2)
For packs of 10 or 5 units "-Z" and order code "X90" must be added to the
Order No.
* You can order this quantity or a multiple thereof.
3/108
Siemens LV 1 · 2009
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
For contactors Version
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Type
kg
EMC suppression modules; 3-phase ≤ 5.5 kW
Size S00 (for contactors with AC or DC operation)1)
RC elements (3 x 220 Ω/0.22 µF)
}
A
C
3RT19 16-1PA1
3RT19 16-1PA2
3RT19 16-1PA3
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.080
0.080
0.080
A
B
D
3RT19 16-1PB1
3RT19 16-1PB2
3RT19 16-1PB3
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.090
0.090
0.090
C
3RT19 66-1PV3
1
1 unit
101
0.400
Rated operational voltage
C
Ue = 1000 V AC
For damping overvoltages and protecting motor windings against multiple reignition when switching off induction
motors. For connection on the contactor
feeder side (2-T1/4-T2/6-T3). For separate installation.
3RT19 66-1PV4
1
1 unit
101
0.780
For increasing the permissible residual }
current and for limiting the residual voltage. Ensures safe opening of contactors
with direct control via 230 V AC semiconductor outputs of SIMATIC controllers.
Also performs the function of an overvoltage damping circuit.
Rated voltage: 50/60 Hz,
180 V to 255 V AC.
Operating range: 0.8 to 1.1 x Us
3RT19 16-1GA00
1
1 unit
101
0.010
For manual operation of the contactor
contacts for start-up and service3)
3RK1 903-0CA00
1
1 unit
121
0.015
Up to 400 V
Up to 575 V
Up to 690 V
3RT10 1
Varistors
Up to 400 V
Up to 575 V
Up to 690 V
3RT19 16-1PA.
Main current path surge suppression modules
for 3RT12 vacuum contactors
Size S10 and S12
3RT12
Rated operational voltage
Ue = 690 V AC
Additional load modules
Size S00 (also for Cage Clamp terminals)
For plugging onto the front side of the
contactors with and without auxiliary
switch blocks 2)
3RT1. 1,
3RH1.
3RT19 16-1GA00
Control kits
Size S00
3RT1. 1,
3RH1.
A
3RK1 903-0CA00
1)
See also description on page 3/98.
2)
For packs of 10 units, the Order No. must be supplemented with "-Z" and
the order code "X90".
3)
See "Load Feeders, Motor Starters and Soft Starters --> ET 200S Motor
Starters, 3RK1 903-0CA00".
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
3/109
3
3RT10 1
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
For contactors
Version
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Type
kg
Coupling links for control by PLC
Sizes S0 ... S3
For mounting onto the coil terminals of the contactors
3
3RT1. 2,
3RT1. 3,
3RT1. 4
3RH19 24-1GP11
}
Operating range 17 to 30 V DC
Power consumption: 0.5 W at 24 V DC
Permissible residual current of the electronics (for 0 signal): 2.5 mA
Rated operational current Ie:
AC-15/AC-14 at 230 V: 3 A, DC-13
at 230 V: 0.1 A
With LED for indicating switching state.
With integrated varistor for damping opening surges.
3RH19 24-1GP11
1
1 unit
101
0.060
3RT19 26-1QT00
1
5 units
101
0.010
B
3RT19 46-4F
1
1 unit
101
0.035
A
3RT19 16-4KA1
1
4 units
101
0.030
LED modules for indicating the contactor function
(also for Cage Clamp terminals)
Sizes S0 ... S121)
3RT1. 2,
3RT1. 3,
3RT1. 4
For snapping into the location hole of an
B
inscription label on the front of a contactor
either directly on the contactor or on the
front auxiliary switch.
The LED module is connected to coil terminals A1 and A2 of the contactor and indicates its energized state. Yellow LED.
Rated voltage: 24 to 240 V AC/DC,
polarized.
(1 pack = 5 units)
3RT19 26-1QT00
mounted to contactor
Auxiliary terminals, 3-pole
Size S3
3RT10 4.
For connection of auxiliary and control
cables (0.5 to 2.5 mm2) to the main conductor connections (for one side)
3RT19 46-4F
Solder pin adapters for contactors
Size S00
3RT1. 1,
3RH11
Assembly kit for soldering contactors onto
a printed circuit board.
For 1 contactor, 1 set is required.
3RT19 16-4KA1
Connection modules for contactors with screw terminals
Size S00, S0
3RT1 . 1,
3RT1. 2,
3RH1.
3RT19 26-4RD01
Adapters for contactors
Screw terminals
Ambient temperature Tu max. = 60 °C
Size S00,
rated operational current Ie at
AC-3/400 V: 20 A
B
3RT19 16-4RD01
1
1 unit
101
0.020
Size S0,
rated operational current Ie at
AC-3/400 V: 25 A
B
3RT19 26-4RD01
1
1 unit
101
0.200
Plugs for contactors
Size S00, S0
B
3RT19 00-4RE01
1
1 unit
101
0.025
3RT19 00-4RE01
1)
For sizes S6 ... S12 the connecting leads have to be extended.
* You can order this quantity or a multiple thereof.
3/110
Siemens LV 1 · 2009
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
For contactors Version
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Type
kg
Solder pin adapters for contactors with
mounted 4-pole auxiliary switch block
Size S00
Assembly kit for soldering contactors B
with an auxiliary switch block onto a
printed circuit board.
For 1 contactor, 1 set is required.
3RT19 16-4KA2
1
4 units
101
0.070
3RT19 26-4P
1 10 units
101
0.010
3
3RT1. 1,
3RH11
3RT19 16-4KA2
Screw adapters with screw or Cage Clamp terminals
Size S0
3RT1. 2
NSB0_01470
Screw adapters for easy screw fixing C
2 units required per contactor
(1 pack contains 10 sets for 10 contactors)
3RT19 26-4P
3RT19 16-4BB31
3RT19 16-4BB41
3RT19 36-4BB31
Size
For contactors
Max. conductor cross-sections
Type
mm2
3RT19 56-4BA31
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Links for paralleling
3-pole, with connection terminal1)2)
S00
3RT10 1
25
}
3RT19 16-4BB31
1
1 unit
101
0.015
S0
3RT10 2
35, stranded
}
3RT19 26-4BB31
1
1 unit
101
0.020
S2
3RT10 3
95
}
3RT19 36-4BB31
1
1 unit
101
0.100
3-pole, with through-hole (star jumpers)1)2)
3RT10 4
3RT14 4
185
}
3RT19 46-4BB31
1
1 unit
101
0.200
S6
3RT1. 5
--
}
3RT19 56-4BA31
1
1 unit
101
0.160
S10/S12
3RT1. 6,
3RT1. 7
--
}
3RT19 66-4BA31
1
1 unit
101
0.500
C
3RT19 16-4BB41
1
1 unit
101
0.015
S3
4-pole, with connection terminal1)2)
S00
3RT1. 1
25
1)
The links for paralleling can be reduced by one pole.
2)
Sizes S00 to S2: The links for paralleling are insulated.
Size S3: A cover plate is included for touch protection.
(Can only be used when the box terminal is removed.)
Sizes S6 to S12: The 3RT19 56-4EA1 (for S6) or 3RT19 66-4EA1
(for S10 and S12) cover can be used for touch protection.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
3/111
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
For contactors
Version
Size
Type
S6
3RT1. 5
Up to 70 mm² 2)
(3RB20 5) Up to 120 mm²
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Box terminal blocks
3
For round and ribbon cables1)
}
3RT19 55-4G
1
1 unit
101
0.230
}
3RT19 56-4G
1
1 unit
101
0.260
Auxiliary conductor connec- B
tion for box terminals
3TX7 500-0A
1
1 unit
101
0.010
}
3RT19 66-4G
1
1 unit
101
0.676
S10/S12
3RT1. 6, Up to 240 mm²
3RT1. 7
With auxiliary conductor con(3RB20 6, nection
3RB21 6)
S2
3RT10 3
3RT19 5.-4G
Covers
Terminal covers for box terminals
3RT13 3,
3RT15 3
S3
3RT19 36-4EA2
Additional touch protection to
be fitted at the box terminals
(2 units required per contactor)
4-pole contactors
3RT10 4,
3RT14 4
}
3RT19 36-4EA2
1
1 unit
101
0.020
B
3RT19 36-4EA4
1
1 unit
101
0.020
}
3RT19 46-4EA2
1
1 unit
101
0.025
B
3RT19 46-4EA4
1
1 unit
101
0.025
S6
3RT1. 5
Length: 25 mm
}
3RT19 56-4EA2
1
1 unit
101
0.030
S10/S12
3RT1. 6,
3RT1. 7
Length: 30 mm
}
3RT19 66-4EA2
1
1 unit
101
0.040
S3
3RT10 4,
3RT14 4
3RT13 4
Terminal covers for cable lugs and busbar connection3)
3RT19 46-4EA1
For complying with the voltage }
clearances and as touch protection if box terminal is
removed4)
(2 units required per contactor)
3RT19 46-4EA1
1
1 unit
101
0.040
S6
3RT1. 5
Length: 100 mm
}
3RT19 56-4EA1
1
1 unit
101
0.070
S10/S12
3RT1. 6,
3RT1. 7
Length: 120 mm
}
3RT19 66-4EA1
1
1 unit
101
0.130
For busbar cover between
contactor and 3RB2. overload
relay or wiring module for contactor assemblies
3RT1. 5
Length: 27 mm
}
3RT19 56-4EA3
1
1 unit
101
0.020
S10/S12 5) 3RT1. 6,
3RT1. 7
Length: 42 mm
}
3RT19 66-4EA3
1
1 unit
101
0.060
S6
For busbar cover of the flat line
connectors for reversing and
wye-delta assemblies
S6
3RT1. 5
Length: 38 mm
}
3RT19 56-4EA4
1
1 unit
101
0.030
S00
3RT1. 1,
3RH1. 6)
Sealable cover for preventing
manual operation
A
3RT19 16-4MA10
1
5 units
101
0.010
B
3RT19 26-4MA10
1
5 units
101
0.010
Sealable covers
S0 ... S12 3RT1. 2 ... 1 unit required per contactor
3RT1. 7 6)
NSB0_01471
3RT19 .6-4MA10
1)
For connectable cross-sections of the contactors see Technical Information LV 1 T –> "Technical specifications".
4)
Observe the note in Technical Information LV 1 T, "Technical specifications", "Conductor Cross-Sections".
2)
As standard for 3RT10 54-1 contactor (55 kW).
5)
3)
Also fits on contactors S6 ... S12 with box terminals.
The 3RT19 66-4EA3 cover is required in addition for use in contactor
assemblies (reversing/wye-delta).
6)
Exception: contactors and contactor relays auxiliary switch block mounted
onto the front.
* You can order this quantity or a multiple thereof.
3/112
Siemens LV 1 · 2009
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Accessories for 3RT, 3RH contactors
and contactor relays
Version
DT
Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
kg
Insulation stop for securely holding back
the conductor insulation on conductors up to 1 mm2
for contactors with Cage Clamp terminals
3RT19 16-4JA02
100
20 unit
101 1000.000
3
3RT19 16-4JA02
Insulation stop strip can be inserted in cable entry of B
Cage Clamp (2 strips per contactor required, can be
removed in pairs) Fits into cable entries of all SIRIUS
devices with Cage Clamp terminals of conductor
cross-section up to 2.5 mm2.
Tools for opening Cage Clamp terminals
For all SIRIUS devices with Cage Clamp terminals, up
to max. 2.5 mm² conductor cross-section
(not suitable for devices with removable terminal)
8WA2 880
Length: approx. 175 mm; 3.5 x 0.5, green; partially
insulated
C
8WA2 880
1
1 unit
041
0.034
Length: approx. 175 mm; 3.5 x 0.5; green
C
8WA2 803
1
1 unit
041
0.024
• 10 mm × 7 mm, pastel turquoise
D
3RT19 00-1SB10
100
816
units
101
24.000
• 20 mm × 7 mm, pastel turquoise
C
3RT19 00-1SB20
100
340
units
101
0.200
• 19 mm × 6 mm, pastel turquoise
D
3RT19 00-1SB60
100
3060
units
101
15.000
• 19 mm × 6 mm, zinc/yellow
C
3RT19 00-1SD60
100
3060
units
101
12.000
Blank labels
Unit labeling plates for "SIRIUS"
Labels for sticking for "SIRIUS"
3RT19 00-1SB10
Computer labeling system
Obtainable from:
For individual inscription of
unit labeling plates
murrplastik
Systemtechnik GmbH
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
3/113
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Spare parts for 3RT, 3RH
contactors and contactor relays
■ Selection and ordering data
3
PU (UNIT, SET, M) = 1
PS*
= 1 unit
PG
= 101
3RT19 24-5A.01
For contactors
3RT19 34-5A.01
Rated control
supply voltage Us
DT
Order No.
Size
Type
3RT19 24-5A.02
Weight
per PU
approx.
Screw terminals
DT
Price
per PU
Weight
per PU
approx.
Cage Clamp
terminals
Order No.
Price
per PU
50 Hz
50/60 Hz 60 Hz
V
V
V
24
42
48
110
-----
-----
}
B
A
}
3RT19 24-5AB01
3RT19 24-5AD01
3RT19 24-5AH01
3RT19 24-5AF01
0.100
0.100
0.100
0.100
B
C
B
B
3RT19 24-5AB02
3RT19 24-5AD02
3RT19 24-5AH02
3RT19 24-5AF02
0.100
0.100
0.100
0.100
230
400
---
---
}
}
3RT19 24-5AP01
3RT19 24-5AV01
0.100 B
0.100 C
3RT19 24-5AP02
3RT19 24-5AV02
0.100
0.100
-----
24
42
48
110
-----
}
B
B
}
3RT19 24-5AC21
3RT19 24-5AD21
3RT19 24-5AH21
3RT19 24-5AG21
0.100
0.100
0.100
0.100
B
C
C
B
3RT19 24-5AC22
3RT19 24-5AD22
3RT19 24-5AH22
3RT19 24-5AG22
0.100
0.100
0.100
0.100
---
220
230
---
B
B
3RT19 24-5AN21
3RT19 24-5AL21
0.100 B
0.100 B
3RT19 24-5AN22
3RT19 24-5AL22
0.100
0.100
110
220
---
--100
200
120
240
110
220
B
B
B
B
3RT19 24-5AK61
3RT19 24-5AP61
3RT19 24-5AG61
3RT19 24-5AN61
0.100
0.100
0.100
0.100
B
C
C
C
3RT19 24-5AK62
3RT19 24-5AP62
3RT19 24-5AG62
3RT19 24-5AN62
0.100
0.100
0.100
0.100
kg
kg
Solenoid coils ⋅ AC operation
S0
S2
3RT10 2.,
3RT13 2.,
3RT15 2.
3RT10 34
3RT10 35,
3RT10 36,
3RT13 3.,
3RT15 3.
--
400
440
B
3RT19 24-5AR61
0.100 C
3RT19 24-5AR62
0.100
24
42
48
110
-----
-----
B
B
B
B
3RT19 34-5AB01
3RT19 34-5AD01
3RT19 34-5AH01
3RT19 34-5AF01
0.120
0.120
0.120
0.120
B
B
B
B
3RT19 34-5AB02
3RT19 34-5AD02
3RT19 34-5AH02
3RT19 34-5AF02
0.120
0.120
0.120
0.120
230
400
---
---
A
C
3RT19 34-5AP01
3RT19 34-5AV01
0.120 B
0.120 B
3RT19 34-5AP02
3RT19 34-5AV02
0.120
0.120
-----
24
42
48
110
-----
B
B
B
C
3RT19 34-5AC21
3RT19 34-5AD21
3RT19 34-5AH21
3RT19 34-5AG21
0.120
0.120
0.120
0.120
B
B
B
B
3RT19 34-5AC22
3RT19 34-5AD22
3RT19 34-5AH22
3RT19 34-5AG22
0.120
0.120
0.120
0.120
---
220
230
---
C
C
3RT19 34-5AN21
3RT19 34-5AL21
0.120 B
0.120 B
3RT19 34-5AN22
3RT19 34-5AL22
0.120
0.120
110
220
---
--100
200
120
240
110
220
B
B
B
B
3RT19 34-5AK61
3RT19 34-5AP61
3RT19 34-5AG61
3RT19 34-5AN61
0.120
0.120
0.120
0.120
B
B
B
B
3RT19 34-5AK62
3RT19 34-5AP62
3RT19 34-5AG62
3RT19 34-5AN62
0.120
0.120
0.120
0.120
--
400
440
B
3RT19 34-5AR61
0.120 B
3RT19 34-5AR62
0.120
24
42
48
110
-----
-----
B
B
B
}
3RT19 35-5AB01
3RT19 35-5AD01
3RT19 35-5AH01
3RT19 35-5AF01
0.120
0.120
0.120
0.120
B
B
B
B
3RT19 35-5AB02
3RT19 35-5AD02
3RT19 35-5AH02
3RT19 35-5AF02
0.120
0.120
0.120
0.120
230
400
---
---
}
C
3RT19 35-5AP01
3RT19 35-5AV01
0.120 B
0.120 B
3RT19 35-5AP02
3RT19 35-5AV02
0.120
0.120
-----
24
42
48
110
-----
B
B
B
B
3RT19 35-5AC21
3RT19 35-5AD21
3RT19 35-5AH21
3RT19 35-5AG21
0.120
0.120
0.120
0.120
B
B
B
B
3RT19 35-5AC22
3RT19 35-5AD22
3RT19 35-5AH22
3RT19 35-5AG22
0.120
0.120
0.120
0.120
---
220
230
---
B
B
3RT19 35-5AN21
3RT19 35-5AL21
0.120 B
0.120 B
3RT19 35-5AN22
3RT19 35-5AL22
0.120
0.120
110
220
---
--100
200
120
240
110
220
B
B
B
B
3RT19 35-5AK61
3RT19 35-5AP61
3RT19 35-5AG61
3RT19 35-5AN61
0.120
0.120
0.120
0.120
B
B
B
B
3RT19 35-5AK62
3RT19 35-5AP62
3RT19 35-5AG62
3RT19 35-5AN62
0.120
0.120
0.120
0.120
--
400
440
C
3RT19 35-5AR61
0.120 B
3RT19 35-5AR62
0.120
* You can order this quantity or a multiple thereof.
3/114
Siemens LV 1 · 2009
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Spare parts for 3RT, 3RH
contactors and contactor relays
3
PU (UNIT, SET, M) = 1
PS*
= 1 unit
PG
= 101
3RT19 44-5A.01
For contactors
3RT19 45-5A.01
3RT19 45-5A.02
Rated control
supply voltage Us
DT
AC
DC
Order No.
50 Hz 50/60 Hz 60 Hz
Size
Type
V
V
V
V
3RT19 44-5B.42
Weight
per PU
approx.
Screw terminals
DT
Price
per PU
Weight
per PU
approx.
Cage Clamp
terminals
Order No.
Price
per PU
kg
kg
Solenoid coils ⋅ AC operation
S3
3RT10 44
3RT10 45,
3RT10 46,
3RT13 4.,
3RT14 46,
3RT15 4.
24
42
48
110
-----
-----
-----
B
B
B
B
3RT19 44-5AB01
3RT19 44-5AD01
3RT19 44-5AH01
3RT19 44-5AF01
0.190
0.190
0.190
0.190
B
B
B
B
3RT19 44-5AB02
3RT19 44-5AD02
3RT19 44-5AH02
3RT19 44-5AF02
0.190
0.190
0.190
0.190
230
400
---
---
---
B
B
3RT19 44-5AP01
3RT19 44-5AV01
0.190 B
0.190 B
3RT19 44-5AP02
3RT19 44-5AV02
0.190
0.190
-----
24
42
48
110
-----
-----
B
B
B
B
3RT19 44-5AC21
3RT19 44-5AD21
3RT19 44-5AH21
3RT19 44-5AG21
0.190
0.190
0.190
0.190
B
B
B
B
3RT19 44-5AC22
3RT19 44-5AD22
3RT19 44-5AH22
3RT19 44-5AG22
0.190
0.190
0.190
0.190
---
220
230
---
---
B
B
3RT19 44-5AN21
3RT19 44-5AL21
0.190 B
0.190 B
3RT19 44-5AN22
3RT19 44-5AL22
0.190
0.190
110
220
---
--100
200
120
240
110
220
-----
C
B
B
B
3RT19 44-5AK61
3RT19 44-5AP61
3RT19 44-5AG61
3RT19 44-5AN61
0.190
0.190
0.190
0.190
B
B
B
B
3RT19 44-5AK62
3RT19 44-5AP62
3RT19 44-5AG62
3RT19 44-5AN62
0.190
0.190
0.190
0.190
--
400
440
--
B
3RT19 44-5AR61
0.190 B
3RT19 44-5AR62
0.190
24
42
48
110
-----
-----
-----
B
B
B
B
3RT19 45-5AB01
3RT19 45-5AD01
3RT19 45-5AH01
3RT19 45-5AF01
0.190
0.190
0.190
0.190
B
B
B
B
3RT19 45-5AB02
3RT19 45-5AD02
3RT19 45-5AH02
3RT19 45-5AF02
0.190
0.190
0.190
0.190
230
400
---
---
---
}
C
3RT19 45-5AP01
3RT19 45-5AV01
0.190 B
0.190 B
3RT19 45-5AP02
3RT19 45-5AV02
0.190
0.190
-----
24
42
48
110
-----
-----
B
B
B
B
3RT19 45-5AC21
3RT19 45-5AD21
3RT19 45-5AH21
3RT19 45-5AG21
0.190
0.190
0.190
0.190
B
B
B
B
3RT19 45-5AC22
3RT19 45-5AD22
3RT19 45-5AH22
3RT19 45-5AG22
0.190
0.190
0.190
0.190
---
220
230
---
---
B
B
3RT19 45-5AN21
3RT19 45-5AL21
0.190 B
0.190 B
3RT19 45-5AN22
3RT19 45-5AL22
0.190
0.190
110
220
---
--100
200
120
240
110
220
-----
B
B
B
C
3RT19 45-5AK61
3RT19 45-5AP61
3RT19 45-5AG61
3RT19 45-5AN61
0.190
0.190
0.190
0.190
B
B
B
B
3RT19 45-5AK62
3RT19 45-5AP62
3RT19 45-5AG62
3RT19 45-5AN62
0.190
0.190
0.190
0.190
--
400
440
--
B
3RT19 45-5AR61
0.190 B
3RT19 45-5AR62
0.190
Solenoid coils ⋅ DC operation
S2
S3
3RT10 3.,
3RT13 3.,
3RT15 3.
3RT10 4.,
3RT13 4.,
3RT14 4.,
3RT15 4.
-----
-----
-----
24
42
48
60
B
B
B
B
3RT19 34-5BB41
3RT19 34-5BD41
3RT19 34-5BW41
3RT19 34-5BE41
0.650
0.650
0.650
0.650
B
C
B
B
3RT19 34-5BB42
3RT19 34-5BD42
3RT19 34-5BW42
3RT19 34-5BE42
0.650
0.650
0.650
0.650
-----
-----
-----
110
125
220
230
B
B
B
B
3RT19 34-5BF41
3RT19 34-5BG41
3RT19 34-5BM41
3RT19 34-5BP41
0.650
0.650
0.650
0.650
B
C
B
B
3RT19 34-5BF42
3RT19 34-5BG42
3RT19 34-5BM42
3RT19 34-5BP42
0.650
0.650
0.650
0.650
-----
-----
-----
24
42
48
60
B
C
B
B
3RT19 44-5BB41
3RT19 44-5BD41
3RT19 44-5BW41
3RT19 44-5BE41
1.000
1.000
1.000
1.000
B
B
B
B
3RT19 44-5BB42
3RT19 44-5BD42
3RT19 44-5BW42
3RT19 44-5BE42
1.000
1.000
1.000
1.000
-----
-----
-----
110
125
220
230
B
B
B
B
3RT19 44-5BF41
3RT19 44-5BG41
3RT19 44-5BM41
3RT19 44-5BP41
1.000
1.000
1.000
1.000
B
B
B
B
3RT19 44-5BF42
3RT19 44-5BG42
3RT19 44-5BM42
3RT19 44-5BP42
1.000
1.000
1.000
1.000
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
3/115
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Spare parts for 3RT, 3RH
contactors and contactor relays
3
PU (UNIT, SET, M) = 1
PS*
= 1 unit
PG
= 101
3RT19 55-5A. . .
For contactors
Rated control
supply voltage
Us min ... Us max
Size
V AC/DC
DT
Order No.
Type
Weight
per PU
approx.
Screw terminals
Price
per PU
DT
Weight
per PU
approx.
Cage Clamp
terminals
Order No.
kg
Price
per PU
kg
Withdrawable coils
Conventional operating mechanism
S6
S10
S10
S12
3RT10 5,
3RT14 5
3RT10 6,
3RT14 6
3RT12 6
vacuum
contactors
3RT10 7,
3RT14 7,
3RT12 7
vacuum
contactors
23 ... 26
42 ... 48
110 ... 127
200 ... 220
B
B
B
B
3RT19 55-5AB31
3RT19 55-5AD31
3RT19 55-5AF31
3RT19 55-5AM31
0.650
0.650
0.650
0.650
B
B
B
B
3RT19 55-5AB32
3RT19 55-5AD32
3RT19 55-5AF32
3RT19 55-5AM32
0.650
0.650
0.650
0.650
220 ... 240
240 ... 277
380 ... 420
440 ... 480
B
B
B
B
3RT19 55-5AP31
3RT19 55-5AU31
3RT19 55-5AV31
3RT19 55-5AR31
0.650
0.650
0.650
0.650
B
B
B
B
3RT19 55-5AP32
3RT19 55-5AU32
3RT19 55-5AV32
3RT19 55-5AR32
0.650
0.650
0.650
0.650
500 ... 550
575 ... 600
B
B
3RT19 55-5AS31
3RT19 55-5AT31
0.650 B
0.650 B
3RT19 55-5AS32
3RT19 55-5AT32
0.650
0.650
23 ... 26
42 ... 48
110 ... 127
200 ... 220
B
B
B
C
3RT19 65-5AB31
3RT19 65-5AD31
3RT19 65-5AF31
3RT19 65-5AM31
0.850
0.850
0.850
0.850
B
B
B
B
3RT19 65-5AB32
3RT19 65-5AD32
3RT19 65-5AF32
3RT19 65-5AM32
0.850
0.850
0.850
0.850
220 ... 240
240 ... 277
380 ... 420
440 ... 480
B
B
B
B
3RT19 65-5AP31
3RT19 65-5AU31
3RT19 65-5AV31
3RT19 65-5AR31
0.850
0.850
0.850
0.850
B
B
B
B
3RT19 65-5AP32
3RT19 65-5AU32
3RT19 65-5AV32
3RT19 65-5AR32
0.850
0.850
0.850
0.850
500 ... 550
575 ... 600
C
C
3RT19 65-5AS31
3RT19 65-5AT31
0.850 B
0.850 B
3RT19 65-5AS32
3RT19 65-5AT32
0.850
0.850
23 ... 26
42 ... 48
110 ... 127
200 ... 220
B
B
A
C
3RT19 66-5AB31
3RT19 66-5AD31
3RT19 66-5AF31
3RT19 66-5AM31
1.000
1.000
1.000
1.000
-----
220 ... 240
240 ... 277
380 ... 420
440 ... 480
A
C
B
C
3RT19 66-5AP31
3RT19 66-5AU31
3RT19 66-5AV31
3RT19 66-5AR31
1.000
1.000
1.000
1.000
-----
500 ... 550
575 ... 600
C
C
3RT19 66-5AS31
3RT19 66-5AT31
1.000
1.000
---
23 ... 26
42 ... 48
110 ... 127
200 ... 220
B
B
B
C
3RT19 75-5AB31
3RT19 75-5AD31
3RT19 75-5AF31
3RT19 75-5AM31
1.300
1.300
1.300
1.300
B
B
B
B
3RT19 75-5AB32
3RT19 75-5AD32
3RT19 75-5AF32
3RT19 75-5AM32
1.300
1.300
1.300
1.300
220 ... 240
240 ... 277
380 ... 420
440 ... 480
B
B
B
B
3RT19 75-5AP31
3RT19 75-5AU31
3RT19 75-5AV31
3RT19 75-5AR31
1.300
1.300
1.300
1.300
B
B
B
B
3RT19 75-5AP32
3RT19 75-5AU32
3RT19 75-5AV32
3RT19 75-5AR32
1.300
1.300
1.300
1.300
500 ... 550
575 ... 600
C
C
3RT19 75-5AS31
3RT19 75-5AT31
1.300 B
1.300 B
3RT19 75-5AS32
3RT19 75-5AT32
1.300
1.300
* You can order this quantity or a multiple thereof.
3/116
Siemens LV 1 · 2009
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Spare parts for 3RT, 3RH
contactors and contactor relays
3
PU (UNIT, SET, M) = 1
PS*
= 1 unit
PG
= 101
3RT19 55-5N. . .
For contactors
Rated control
supply voltage Us
Size
V AC/DC
DT
Order No.
Type
Weight
per PU
approx.
Screw terminals
Price
per PU
DT
Weight
per PU
approx.
Cage Clamp
terminals
Order No.
kg
Price
per PU
kg
Withdrawable coils
Solid-state operating mechanisms
For 24 V DC PLC output
S6
3RT10 5,
3RT14 5
S10
S12
21 ... 27.3
96 ... 127
200 ... 277
C
B
B
3RT19 55-5NB31
3RT19 55-5NF31
3RT19 55-5NP31
0.650 B
0.650 B
0.650 B
3RT19 55-5NB32
3RT19 55-5NF32
3RT19 55-5NP32
0.650
0.650
0.650
21 ... 27.3
96 ... 127
200 ... 277
B
B
B
3RT19 65-5NB31
3RT19 65-5NF31
3RT19 65-5NP31
0.900 B
0.900 B
0.900 B
3RT19 65-5NB32
3RT19 65-5NF32
3RT19 65-5NP32
0.900
0.900
0.900
3RT12 6
21 ... 27.3
vacuum contac- 96 ... 127
tors
200 ... 277
B
C
C
3RT19 66-5NB31
3RT19 66-5NF31
3RT19 66-5NP31
0.650
0.650
0.650
----
3RT10 7,
21 ... 27.3
3RT14 7,
96 ... 127
3RT12 7
200 ... 277
vacuum contactors
B
B
B
3RT19 75-5NB31
3RT19 75-5NF31
3RT19 75-5NP31
1.100 B
1.100 B
1.100 B
3RT19 75-5NB32
3RT19 75-5NF32
3RT19 75-5NP32
3RT10 6,
3RT14 6
1.100
1.100
1.100
For 24 V DC PLC output/PLC relay output, with remaining lifetime indicator (RLT)
(Withdrawable coil with lateral solid-state module)
S6
3RT10 5,
3RT14 5
96 ... 127
200 ... 277
B
B
3RT19 55-5PF31
3RT19 55-5PP31
0.650
0.650
---
S10
3RT10 6,
3RT14 6
96 ... 127
200 ... 277
B
B
3RT19 65-5PF31
3RT19 65-5PP31
1.300
1.300
---
S12
3RT10 7,
3RT14 7
96 ... 127
200 ... 277
B
B
3RT19 75-5PF31
3RT19 75-5PP31
1.300
1.300
---
With AS-Interface and remaining lifetime indicator (RLT)
(Withdrawable coil with lateral solid-state module)
S6
3RT10 5,
3RT14 5
96 ... 127
200 ... 277
B
B
3RT19 55-5QF31
3RT19 55-5QP31
0.650
0.650
---
S10
3RT10 6,
3RT14 6
96 ... 127
200 ... 277
B
B
3RT19 65-5QF31
3RT19 65-5QP31
1.300
1.300
---
S12
3RT10 7,
3RT14 7
96 ... 127
200 ... 277
B
B
3RT19 75-5QF31
3RT19 75-5QP31
1.300
1.300
---
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
3/117
© Siemens AG 2009
Accessories and Spare Parts
For 3RT, 3RH Contactors and Contactor Relays
Spare parts for 3RT, 3RH
contactors and contactor relays
For contactors
Size
Version
DT Order No.
Price
per PU
PU
PS*
(UNIT,
SET, M)
PG
Weight
per PU
approx.
Type
kg
3
Arc chutes
S2
3RT10 3.
C
3RT19 36-7A
1
1 unit
101
0.110
S3
3RT10 4.,
3RT14 46
Arc chutes, 3-pole
C
3RT19 46-7A
1
1 unit
101
0.300
S6
3RT10 54
3RT10 55
3RT10 56
B
B
B
3RT19 54-7A
3RT19 55-7A
3RT19 56-7A
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.760
0.760
0.760
S10
3RT10 64
3RT10 65
3RT10 66
B
B
B
3RT19 64-7A
3RT19 65-7A
3RT19 66-7A
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.350
1.350
1.350
S12
3RT10 75
3RT10 76
B
B
3RT19 75-7A
3RT19 76-7A
1
1
1 unit
1 unit
101
101
1.650
1.650
S6
3RT14 56
B
3RT19 56-7B
1
1 unit
101
0.720
S10
3RT14 66
B
3RT19 66-7B
1
1 unit
101
1.350
S12
3RT14 76
B
3RT19 76-7B
1
1 unit
101
1.400
}
}
}
3RT19 34-6A
3RT19 35-6A
3RT19 36-6A
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.050
0.050
0.050
}
}
}
3RT19 44-6A
3RT19 45-6A
3RT19 46-6A
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.110
0.110
0.110
Contacts with fixing parts
For contactors with 3 main contacts
S2
3RT10 34
3RT10 35
3RT10 36
Main contacts (3 NO contacts) for
utilization category AC-3
(1 set = 3 movable and 6 fixed switching
elements with fixing parts)
S3
3RT10 44
3RT10 45
3RT10 46
S6
3RT10 54
3RT10 55
3RT10 56
}
}
}
3RT19 54-6A
3RT19 55-6A
3RT19 56-6A
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.280
0.280
0.280
S10
3RT10 64
3RT10 65
3RT10 66
}
}
}
3RT19 64-6A
3RT19 65-6A
3RT19 66-6A
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.550
0.550
0.550
S12
3RT10 75
3RT10 76
}
A
3RT19 75-6A
3RT19 76-6A
1
1
1 unit
1 unit
101
101
0.900
0.100
S3
3RT14 46
B
3RT19 46-6D
1
1 unit
101
0.900
S6
3RT14 56
B
3RT19 56-6D
1
1 unit
101
0.280
S10
3RT14 66
B
3RT19 66-6D
1
1 unit
101
0.550
S12
3RT14 76
A
3RT19 76-6D
1
1 unit
101
0.900
B
B
B
3RT19 64-6V
3RT19 65-6V
3RT19 66-6V
1
1
1
1 unit
1 unit
1 unit
101
101
101
1.530
1.530
1.530
B
B
3RT19 75-6V
3RT19 76-6V
1
1
1 unit
1 unit
101
101
1.780
1.780
C
3RT19 36-6E
1
1 unit
101
0.060
C
C
3RT19 44-6E
3RT19 46-6E
1
1
1 unit
1 unit
101
101
0.150
0.150
Main contacts (3 NO contacts) for
utilization category AC-1
(1 set = 3 movable and 6 fixed switching
elements with fixing parts)
For 3RT12 vacuum contactors
S10
3RT12 64
3RT12 65
3RT12 66
S12
3RT12 75
3RT12 76
3 vacuum interrupters with fixing parts
For contactors with 4 main contacts
S2
3RT13 36
S3
3RT13 44
3RT13 46
Main contacts (4 NO contacts) for
utilization category AC-1
(1 set = 4 movable and 8 fixed switching
elements with fixing parts)
* You can order this quantity or a multiple thereof.
3/118
Siemens LV 1 · 2009
Was this manual useful for you? yes no