Product data sheet 3RT2017-1BB41 CONTACTOR, AC-3, 5.5KW/400V, 1NO,

Product data sheet 3RT2017-1BB41 CONTACTOR, AC-3, 5.5KW/400V, 1NO,
Product data sheet
3RT2017-1BB41
CONTACTOR, AC-3, 5.5KW/400V, 1NO,
DC 24V, 3-POLE, SZ S00 SCREW TERMINAL .
General technical data:
product brand name
SIRIUS
Size of the contactor
S00
Product extension
• auxiliary switch
Yes
• function module for communication
No
Protection class IP / on the front
IP20
Protection against electrical shock
finger-safe
Degree of pollution
3
Installation altitude / at a height over sea level / maximum
m
2,000
• during storage
°C
-55 … +80
• during operating
°C
-25 … +60
Ambient temperature
Shock resistance
• at rectangular impulse
• at DC
7.3g / 5 ms, 4.7g / 10 ms
• at sine pulse
• at DC
11,4g / 5 ms, 7,3g / 10 ms
Impulse voltage resistance / rated value
kV
6
Insulation voltage / rated value
V
690
3RT2017-1BB41
Page 1/ 9
10/18/2013
subject to modifications
© Copyright Siemens AG 2013
Maximum permissible voltage for protective separation /
between coil and main contacts / in accordance with EN 60947-1
V
400
Mechanical operating cycles as operating time
• of the contactor / typical
30,000,000
• of the contactor with added auxiliary switch block / typical
10,000,000
• of the contactor with added electronics-compatible auxiliary
switch block / typical
5,000,000
Main circuit:
Number of NC contacts / for main contacts
0
Number of NO contacts / for main contacts
3
Connectable conductor cross-section / in main circuit
• at AC-1
• at 40 °C / minimum permissible
m²
4
• at 60 °C / minimum permissible
m²
2.5
A
12
• at 400 V / rated value
A
12
• at 500 V / rated value
A
9.2
• at 690 V / rated value
A
6.7
A
8.5
• at 24 V / rated value
A
20
• at 110 V / rated value
A
2.1
• at 220 V / rated value
A
0.8
• at 440 V / rated value
A
0.6
• at 600 V / rated value
A
0.6
• at 24 V / rated value
A
20
• at 110 V / rated value
A
12
• at 220 V / rated value
A
1.6
• at 440 V / rated value
A
0.8
• at 600 V / rated value
A
0.7
• at 24 V / rated value
A
20
• at 110 V / rated value
A
20
• at 220 V / rated value
A
20
Operating current
• at AC-2
• at 400 V / rated value
• at AC-3
• at AC-4
• at 400 V / rated value
Operating current
• with 1 current path / at DC-1
• with 2 current paths in series / at DC-1
• with 3 current paths in series / at DC-1
3RT2017-1BB41
Page 2/ 9
10/18/2013
subject to modifications
© Copyright Siemens AG 2013
• at 440 V / rated value
A
1.3
• at 600 V / rated value
A
1
• at 24 V / rated value
A
20
• at 110 V / rated value
A
0.1
• at 24 V / rated value
A
20
• at 110 V / rated value
A
0.35
• at 24 V / rated value
A
20
• at 110 V / rated value
A
20
• at 220 V / rated value
A
1.5
• at 440 V / rated value
A
0.2
• at 600 V / rated value
A
0.2
• at 230 V / rated value
kW
7.5
• at 400 V / rated value
kW
13
• at 690 V / rated value
kW
22
kW
5.5
• at 230 V / rated value
kW
3
• at 400 V / rated value
kW
5.5
• at 690 V / rated value
kW
5.5
kW
4
Thermal short-time current / restricted to 10 s
A
90
Active power loss / at AC-3 / at 400 V / with rated Operating
current value / per conductor
W
1.2
1/h
10,000
• at AC-1 / according to IEC 60947-6-2
1/h
1,000
• at AC-2 / according to IEC 60947-6-2
1/h
750
• at AC-3 / according to IEC 60947-6-2
1/h
750
• at AC-4 / according to IEC 60947-6-2
1/h
250
Operating current
• with 1 current path / at DC-3 / at DC-5
• with 2 current paths in series / at DC-3 / at DC-5
• with 3 current paths in series / at DC-3 / at DC-5
Service power
• at AC-1
• at AC-2
• at 400 V / rated value
• at AC-3
• at AC-4
• at 400 V / rated value
Off-load operating frequency
• at DC
Frequency of operation
Control circuit:
3RT2017-1BB41
Page 3/ 9
10/18/2013
subject to modifications
© Copyright Siemens AG 2013
Type of voltage / of the controlled supply voltage
DC
Control supply voltage
• for DC / rated value
V
24
operating range factor control supply voltage rated value / of
the magnet coil
• for DC
0.8 … 1.1
Pull-in power / of the solenoid / for DC
W
4
Holding power / of the solenoid / for DC
W
4
ms
30 … 100
• at DC
ms
7 … 13
Arcing time
ms
10 … 15
• at 230 V / with AC / maximum permissible
mA
4
• at 24 V / with DC / maximum permissible
mA
10
Closing delay
• at DC
Opening delay
Residual current / of electronics / for control with signal <0>
Auxiliary circuit:
Contact reliability / of the auxiliary contacts
1 faulty switching per 100 million (17 V, 1 mA)
Number of NC contacts / for auxiliary contacts / instantaneous
switching
0
Number of NO contacts / for auxiliary contacts / instantaneous
switching
1
Operating current
• at AC-12 / maximum
A
10
• at 230 V / rated value
A
10
• at 400 V / rated value
A
3
• at 500 V / rated value
A
2
• at 690 V / rated value
A
1
• at 24 V / rated value
A
10
• at 48 V / rated value
A
6
• at 60 V / rated value
A
6
• at 110 V / rated value
A
3
• at 125 V / rated value
A
2
• at 220 V / rated value
A
1
• at 440 V / rated value
A
0.3
• at 600 V / rated value
A
0.15
A
10
• at AC-15
Operating current / at DC-12
Operating current / at DC-13
• at 24 V / rated value
3RT2017-1BB41
Page 4/ 9
10/18/2013
subject to modifications
© Copyright Siemens AG 2013
• at 48 V / rated value
A
2
• at 60 V / rated value
A
2
• at 110 V / rated value
A
1
• at 125 V / rated value
A
0.9
• at 220 V / rated value
A
0.3
• at 440 V / rated value
A
0.14
• at 600 V / rated value
A
0.1
• at 110/120 V / rated value
hp
0.5
• at 230 V / rated value
hp
2
• at 200/208 V / rated value
hp
3
• at 220/230 V / rated value
hp
3
• at 460/480 V / rated value
hp
7.5
• at 575/600 V / rated value
hp
10
• at 480 V / rated value
A
11
• at 600 V / rated value
A
11
UL/CSA ratings:
yielded mechanical performance (hp)
• for single-phase squirrel cage motors
• for three-phase squirrel cage motors
Operating current (FLA) / for three-phase squirrel cage motors
Contact rating designation / for auxiliary contacts / according to
UL
A600 / Q600
Short-circuit:
Design of the fuse link
• for short-circuit protection of the auxiliary switch / required
fuse gL/gG: 10 A
• for short-circuit protection of the main circuit
• with type of assignment 1 / required
gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35
A
• at type of coordination 2 / required
gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE:
20A
Installation/mounting/dimensions:
mounting position
+/-180° rotation possible on vertical mounting surface;
can be tilted forward and backward by +/- 22.5° on
vertical mounting surface
Type of mounting
screw and snap-on mounting onto 35 mm standard
mounting rail according to DIN EN 50022
Type of fixing/fixation / series installation
Yes
Width
mm
45
Height
mm
57.5
Depth
mm
73
3RT2017-1BB41
Page 5/ 9
10/18/2013
subject to modifications
© Copyright Siemens AG 2013
Distance, to be maintained, to the ranks assembly / sidewards
mm
0
Connections:
Design of the electrical connection
• for main current circuit
screw-type terminals
• for auxiliary and control current circuit
screw-type terminals
Type of the connectable conductor cross-section
• for main contacts
• finely stranded
• with conductor end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
• for AWG conductors / for main contacts
2x (20 ... 16), 2x (18 ... 14), 2x 12
• for auxiliary contacts
• finely stranded
• with conductor end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
• for AWG conductors / for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14), 2x 12
Sicherheitsrelevante Kenngrößen:
B10 value / with high demand rate
• according to SN 31920
1,000,000
T1 value / for proof test interval or service life
• according to IEC 61508
a
20
• with low demand rate / according to SN 31920
%
40
• with high demand rate / according to SN 31920
%
73
FIT
100
Proportion of dangerous failures
Failure rate (FIT value) / with low demand rate
• according to SN 31920
Product function
• mirror contact to IEC 60947-4-1
Yes
• comment
with 3RH29
• positively driven operation to IEC 60947-5-1
No
Certificates/approvals:
3RT2017-1BB41
Page 6/ 9
10/18/2013
subject to modifications
© Copyright Siemens AG 2013
General Product Approval
Functional Safety /
Safety of
Machinery
Type Examination
Declaration of
Conformity
Test Certificates
other
Special Test
Certificate
Type Test
Certificates/Test
Report
Shipping Approval
Shipping Approval
other
Confirmation
Further information:
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
http://www.siemens.com/industrial-controls/mall
Cax online generator
http://www.siemens.com/cax
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/3RT2017-1BB41/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RT2017-1BB41
3RT2017-1BB41
Page 7/ 9
10/18/2013
subject to modifications
© Copyright Siemens AG 2013
3RT2017-1BB41
Page 8/ 9
10/18/2013
subject to modifications
© Copyright Siemens AG 2013
last change:
3RT2017-1BB41
Page 9/ 9
Oct 14, 2013
10/18/2013
subject to modifications
© Copyright Siemens AG 2013
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project