Overload Relays ■ General data

Overload Relays ■ General data
© Siemens AG 2009
Overload Relays
General data
■ Overview
Features
Benefits
3RU11
3RB20/3RB21
3RB22/3RB23
S00 ... S12
S00 ... S12
0.1 ... 630 A
0.3 ... 630 A
( ... 820 A)1)
General data
Sizes
• Are coordinated with the dimensions, connections S00 ...S3
and technical characteristics of the other devices
in the SIRIUS modular system (contactors, soft
starters, ...)
• Permit the mounting of slim and compact load
feeders in widths of 45 mm (S00), 45 mm (S0),
55 mm (S2), 70 mm (S3), 120 mm (S6) and
145 mm (S10/S12)
• Simplify configuration
Seamless current range
• Allows easy and consistent configuration with one 0.11 ... 100 A
series of overload relays (for small to large loads)
Protection functions
• Provides optimum inverse-time delayed protection
of loads against excessive temperature rises due
to overload
✔
✔
✔
Tripping in the event of phase
unbalance
• Provides optimum inverse-time delayed protection
of loads against excessive temperature rises due
to phase unbalance
(✔)
✔
✔
Tripping in the event of phase failure
• Minimizes heating of induction motors during
phase failure
✔
✔
✔
Protection of single-phase loads
• Enables the protection of single-phase loads
✔
--
✔
Tripping in the event of overheating
• Provides optimum temperature-dependent protection of loads against excessive temperature
rises, e. g. for stator-critical motors or in the event
of insufficient coolant flow, contamination of the
motor surface or for long starting or braking operations
--2)
--2)
✔
--
✔
(only 3RB21)
✔
✔
✔
✔
✔
(by means of
separate module)
✔
(only 3RB21 with
24 V DC)
✔
✔
by
Integrated thermistor motor
protection function
5
Tripping in the event of overload
• Eliminates the need for additional special equipment
• Saves space in the control cabinet
• Reduces wiring outlay and costs
Tripping in the event of a ground fault • Provides optimum protection of loads against
high-resistance short-circuits or ground faults due
by
to moisture, condensed water, damage to the
insulation material, etc.
Internal ground-fault detection
• Eliminates the need for additional special equip(activatable)
ment.
• Saves space in the control cabinet
• Reduces wiring outlay and costs
Features
RESET function
• Allows manual or automatic resetting of the relay
Remote RESET function
• Allows the remote resetting of the relay
TEST function for auxiliary contacts
• Allows easy checking of the function and wiring
✔
✔
TEST function for electronics
• Allows checking of the electronics
--
✔
✔
Status display
• Displays the current operating state
✔
✔
✔
Large current adjustment button
• Makes it easier to set the relay exactly to the
correct current value
✔
✔
✔
Integrated auxiliary contacts
(1 NO + 1 NC)
• Allows the load to be switched off if necessary
✔
✔
✔
(2 ×)
• Can be used to output signals
1)
Motor currents up to 820 A can be recorded and evaluated by a current
measuring module, e. g. 3RB29 06-2BG1 (0.3 ... 3 A), in combination with
a 3UF18 68-3GA00 (820 A / 1 A) series transformer.
For 3UF18 transformers, see Chapter 7, section "SIMOCODE".
2)
The SIRIUS 3RN thermistor motor protection devices can be used to provide additional temperature-dependent protection.
Siemens LV 1 · 2009
5/39
© Siemens AG 2009
Overload Relays
General data
Features
Benefits
3RU11
3RB20/3RB21
3RB22/3RB23
Design of load feeders
Short-circuit strength up to 100 kA
• Provides optimum protection of the loads and opat 690 V
erating personnel in the event of short-circuits due
(in conjunction with the corresponding
to insulation faults or faulty switching operations
fuses or the corresponding motor starter
protector)
Electrical and mechanical matching
to 3RT1 contactors
• Simplifies configuration
✔
✔
✔
✔
✔
✔1)
--
✔
(S2 ... S6)
✔
(S00 ... S6)
✔
(S00)
--
--
✔
✔
✔
✔
✔
✔
(✔)
✔
✔
--
✔
(1:4)
✔
(1:10)
• Reduces wiring outlay and costs
5
• Enables stand-alone installation as well as spacesaving direct mounting
Straight-through transformers for
main circuit2)
(in this case the cables are routed
through the feed-through openings of
the overload relay and connected
directly to the box terminals of the contactor)
• Reduces the contact resistance
(only one point of contact)
Spring-loaded terminal connection
system for main circuit2)
• Enables fast connections
• Saves wiring costs
(easy, no need for tools, and fast)
• Saves material costs
• Reduces installation costs
• Permits vibration-resistant connections
• Enables maintenance-free connections
Spring-loaded terminal connection
system for auxiliary circuits2)
• Enables fast connections
• Permits vibration-resistant connections
• Enables maintenance-free connections
Other features
Temperature compensation
• Allows the use of the relays at high temperatures
without derating
• Prevents premature tripping
• Allows compact installation of the control cabinet
without distance between the devices/load feeders
• Simplifies configuration
• Enables space to be saved in the control cabinet
Very high long-term stability
• Provides safe protection for the loads even after
years of use in severe operating conditions
Wide setting ranges
• Reduce the number of variants
• Minimize the engineering outlay and costs
• Minimize storage overhead, storage costs, tied-up
capital
Trip class CLASS 5
• Enables solutions for very fast starting motors requiring special protection (e. g. Ex motors)
--
✔
(only 3RB21)
✔
Trip classes > CLASS 10
• Enables heavy starting solutions
--
✔
✔
Low power loss
• Reduces power consumption and energy costs
(up 98 % less power is used than for thermal overload relays).
--
✔
✔
• Minimizes temperature rises of the contactor and
control cabinet – in some cases this may eliminate
the need for controlgear cabinet cooling.
• Direct mounting to contactor saves space, even
for high motor currents ( i. e. no heat decoupling is
required).
1)
Exception: up to size S3, only stand-alone installation is possible.
2)
Alternatively available for screw terminals.
5/40
Siemens LV 1 · 2009
© Siemens AG 2009
Overload Relays
General data
Features
Benefits
3RU11
3RB20/3RB21
3RB22/3RB23
Other features
Internal power supply
• Eliminates the need for configuration and connecting an additional control circuit
Variable adjustment of the trip
classes
• Reduces the number of variants
--1)
✔
--
--
✔
(only 3RB21)
✔
--
--
✔
--
--
✔
• Minimizes the configuring outlay and costs
(The required trip class can be adjusted • Minimizes storage overhead, storage costs, and
by means of a rotary switch depending
tied-up capital
on the current start-up condition.)
Overload warning
• Indicates imminent tripping of the relay directly on
the device due to overload, phase unbalance or
phase failure
• Allows the imminent tripping of the relay to be signaled
• Allows measures to be taken in time in the event of
continuous inverse-time delayed overloads
• Eliminates the need for an additional device
5
• Saves space in the control cabinet
• Reduces wiring outlay and costs
Analog output
• Allows the output of an analog output signal for actuating moving-coil instruments, feeding programmable logic controllers or transfer to bus systems
• Eliminates the need for an additional measuring
transducer and signal converter
• Saves space in the control cabinet
• Reduces wiring outlay and costs
1)
The SIRIUS 3RU11 thermal overload relays use a bimetal contactor and
therefore do not require a control supply voltage.
Siemens LV 1 · 2009
5/41
© Siemens AG 2009
Overload Relays
General data
Overload relays Current
measurement
Type
Type
Current
range
A
Contactors (type, size, rating in kW)
3RT10 1
3RT10 2
3RT10 3
3RT10 4
3RT10 5
3RT10 6
3RT10 7
S00
S0
S2
S3
S6
S10
S12
3/4/5.5
5.5/7.5/11 15/18.5/22 30/37/45
55/75/90
110/132/160 200/250
3TF68/69
Size 14
375/450
3RU11 thermal overload relays
3RU11 1
Integrated
0.11 … 12
✔
--
--
--
--
--
--
3RU11 2
Integrated
1.8 … 25
--
✔
--
--
--
--
--
--
3RU11 3
Integrated
5.5 … 50
--
--
✔
--
--
--
--
--
3RU11 4
Integrated
18 … 100
--
--
--
✔
--
--
--
--
--
--
3RB201) solid-state overload relays
3RB20 1
Integrated
0.1 … 12
✔
--
--
--
--
--
--
3RB20 2
Integrated
0.1 … 25
--
✔
--
--
--
--
--
--
3RB20 3
Integrated
6 … 50
--
--
✔
--
--
--
--
--
3RB20 4
Integrated
12.5 … 100
--
--
--
✔
--
--
--
--
3RB20 5
Integrated
50 ... 200
--
--
--
--
✔
--
--
--
3RB20 6
Integrated
55 ... 630
--
--
--
--
--
✔
✔
✔
3RB20 1 +
3UF18
Integrated
630 ... 820
--
--
--
--
--
--
--
✔
--
5
3RB211) solid-state overload relays
3RB21 1
Integrated
0.1 … 12
✔
--
--
--
--
--
--
3RB21 2
Integrated
0.1 … 25
--
✔
--
--
--
--
--
--
3RB21 3
Integrated
6 … 50
--
--
✔
--
--
--
--
--
3RB21 4
Integrated
12.5 … 100
--
--
--
✔
--
--
--
--
3RB21 5
Integrated
50 ... 200
--
--
--
--
✔
--
--
--
3RB21 6
Integrated
55 ... 630
--
--
--
--
--
✔
✔
✔
3RB21 1 +
3UF18
Integrated
630 ... 820
--
--
--
--
--
--
--
✔
3RB29 0
0.3 … 25
✔
✔
--
--
--
--
--
--
3RB29 0
10 ... 100
--
--
✔
✔
--
--
--
--
3RB22/3RB23 + 3RB29 5
20 … 200
--
--
--
--
✔
--
--
--
3RB29 6
63 ... 630
--
--
--
--
--
✔
✔
✔
3RB29 0 +
3UF18
630 ... 820
--
--
--
--
--
--
--
✔
3RB22/3RB231) solid-state overload relays
1)
When using the overload relays with trip class ≥ CLASS 20, see Technical
Information LV 1 T "Technical specifications", "Short-Circuit Protection with
Fuses for Motor Feeders", and the project planning aid "Configuring SIRIUS Fuseless Load Feeders".
Connection methods
The 3RB20 and 3RB21 relays are available with screw terminals
(box terminals) or spring-loaded terminals on the auxiliary current side; the same applies for the evaluation modules of the
3RB22/3RB23 relays. The 3RU11 relays come with screw
terminals.
Screw terminals
Spring-type terminals or Cage Clamp terminals
The terminals are indicated in the selection and
ordering data by orange backgrounds.
5/42
Siemens LV 1 · 2009
© Siemens AG 2009
Overload Relays
3RU1 Thermal Overload Relays
3RU11 for standard applications
"Increased safety" type of protection EEx e according to
ATEX directive 94/9/EC
■ Overview
3
The 3RU11 thermal overload relays are suitable for the overload
protection of explosion-proof motors with "increased safety" type
of protection EEx e. The relays meet the requirements of
EN 60079-7 (Electrical apparatus for areas subject to explosion
hazards – Increased safety "e");
see Chapter 20 "Appendix" --> "Standards and approvals" -->
"Type overview of approved devices for potentially explosive
areas (ATEX explosion protection)".
4
EC type test certificate for Category (2) G/D exists. It has the
number DMT 98 ATEX G 001.
1
2
5
7
6
■ Benefits
The most important features and benefits of the 3RU11 thermal
overload relays are listed in the overview table (see "Overload
Relays", --> "General data").
The 3RU11 thermal overload relays up to 100 A have been designed for inverse-time delayed protection of loads with normal
starting (see Technical Information LV 1 T, "Function") against excessive temperature rises due to overload or phase failure. An
overload or phase failure results in an increase of the motor current beyond the set rated motor current. Via heating elements,
this current rise heats up the bimetal strips inside the device
which then bend and as a result trigger the auxiliary contacts by
means of a tripping mechanism. The auxiliary contacts then
switch off the load by means of a contactor. The break time depends on the ratio between the tripping current and current
setting Ie and is stored in the form of a long-term stable tripping
characteristic (see Technical Information LV 1 T, "Characteristic
Curves").
■ Application
Industries
The 3RU11 thermal overload relays are suitable for customers
from all industries who want to guarantee optimum inverse-time
delayed protection of their electrical loads (e. g. motors) under
normal starting conditions (CLASS 10).
5
(1) Connection for mounting onto contactors:
Optimally adapted in electrical, mechanical and design terms to the
contactors, these connecting pins can be used for direct mounting of
the overload relays. Stand-alone installation is possible as an alternative (in some cases in conjunction with a stand-alone installation
module).
(2) Selector switch for manual/automatic RESET and RESET button:
With this switch you can choose between manual and automatic
RESET. A device set to manual RESET can be reset locally by pressing
the RESET button. A remote RESET is possible using the RESET modules (accessories), which are independent of size.
(3) Switch position indicator and TEST function of the wiring:
Indicates a trip and enables the wiring test.
(4) Motor current setting:
Setting the device to the rated motor current is easy with the large rotary knob.
(5) STOP button:
If the STOP button is pressed, the NC contact is opened. This switches
off the contactor downstream. The NC contact is closed again when
the button is released.
(6) Transparent, sealable cover:
Secures the motor current setting and the TEST function against
adjustment.
(7) Supply terminals:
The generously sized terminals permit connection of two conductors
with different cross-sections for the main and auxiliary circuits. The
auxiliary circuit can be connected with screw terminals and alternatively with spring-loaded terminals.
Application
The 3RU11 thermal overload relays have been designed for the
protection of three-phase and single-phase AC and DC motors.
If single-phase AC or DC loads are to be protected by the 3RU11
thermal overload relays, all three bimetal strips must be heated.
For this purpose, all main current paths of the relay must be connected in series.
Ambient conditions
The 3RU11 thermal overload relays have temperature compensation in accordance with IEC 60947-4-1 for the temperature
range of –20 to +60 °C. For temperatures from +60 to +80 °C the
upper set value of the setting range must be reduced by the factor listed in the table below.
Ambient temperature in °C
Derating factor for the upper set
value
+60
1.0
+65
0.94
+70
0.87
+75
0.81
+80
0.73
The "tripped" status is signaled by means of a switch position indicator. Resetting takes place either manually or automatically
after a recovery time has elapsed (see Technical Information
LV 1 T, "Function").
The devices are manufactured in accordance with environmental guidelines and contain environmentally friendly and reusable
materials.
They comply with all important worldwide standards and
approvals.
Siemens LV 1 · 2009
5/43
© Siemens AG 2009
Overload Relays
3RU1 Thermal Overload Relays
3RU11 for standard applications
■ Selection and ordering data
3RU11 thermal overload relays with screw terminals on the auxiliary current side1) for direct mounting, CLASS 10
•
•
•
•
Features and technical specifications:
• Overload and phase failure protection
• Auxiliary contacts 1 NO + 1 NC
• Manual and automatic RESET
Size
Rating
contactor2) for induction
motor
Rated value3)
Switch position indicators
TEST function
STOP button
Integrated, sealable cover
Current setting of
the inverse-time
delayed overload release
Short-circuit DT Screw terminals
(on auxiliary
protection
current side)
with fuse,
type of coorOrder No.
dination 2,
gL/gG operational class4)
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kW
A
A
0.04
0.06
0.06
0.09
0.11 ... 0.16
0.14 ... 0.2
0.18 ... 0.25
0.22 ... 0.32
0.5
1
1
1.6
}
}
}
}
3RU11 16-0AB0
3RU11 16-0BB0
3RU11 16-0CB0
3RU11 16-0DB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.150
0.150
0.150
0.150
0.09
0.12
0.18
0.18
0.28 ... 0.4
0.35 ... 0.5
0.45 ... 0.63
0.55 ... 0.8
2
2
2
4
}
}
}
}
3RU11 16-0EB0
3RU11 16-0FB0
3RU11 16-0GB0
3RU11 16-0HB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.150
0.150
0.150
0.150
0.25
0.37
0.55
0.75
0.7 ... 1
0.9 ... 1.25
1.1 ... 1.6
1.4 ... 2
4
4
6
6
}
}
}
}
3RU11 16-0JB0
3RU11 16-0KB0
3RU11 16-1AB0
3RU11 16-1BB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.150
0.150
0.150
0.150
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
10
10
16
20
}
}
}
}
3RU11 16-1CB0
3RU11 16-1DB0
3RU11 16-1EB0
3RU11 16-1FB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.150
0.150
0.150
0.150
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12
20
25
35
35
}
}
}
}
3RU11 16-1GB0
3RU11 16-1HB0
3RU11 16-1JB0
3RU11 16-1KB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.150
0.150
0.150
0.150
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
10
10
16
20
}
}
}
}
3RU11 26-1CB0
3RU11 26-1DB0
3RU11 26-1EB0
3RU11 26-1FB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12.5
20
25
35
35
}
}
}
}
3RU11 26-1GB0
3RU11 26-1HB0
3RU11 26-1JB0
3RU11 26-1KB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
7.5
7.5
11
11
11 ... 16
14 ... 20
17 ... 22
20 ... 25
40
50
63
63
}
}
}
}
3RU11 26-4AB0
3RU11 26-4BB0
3RU11 26-4CB0
3RU11 26-4DB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
3
4
5.5
5.5 ... 8
7 ... 10
9 ... 12.5
25
35
35
}
}
}
3RU11 36-1HB0
3RU11 36-1JB0
3RU11 36-1KB0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.320
0.320
0.320
7.5
7.5
11
15
11 ... 16
14 ... 20
18 ... 25
22 ... 32
40
50
63
80
}
}
}
}
3RU11 36-4AB0
3RU11 36-4BB0
3RU11 36-4DB0
3RU11 36-4EB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.320
0.320
0.320
0.320
18.5
22
22
28 ... 40
36 ... 45
40 ... 50
80
100
100
}
}
}
3RU11 36-4FB0
3RU11 36-4GB0
3RU11 36-4HB0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.320
0.320
0.320
11
15
18 ... 25
22 ... 32
63
80
}
}
3RU11 46-4DB0
3RU11 46-4EB0
1
1
1 unit
1 unit
101
101
0.550
0.550
18.5
22
30
37
28 ... 40
36 ... 50
45 ... 63
57 ... 75
80
125
125
160
}
}
}
}
3RU11 46-4FB0
3RU11 46-4HB0
3RU11 46-4JB0
3RU11 46-4KB0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.550
0.550
0.550
0.550
45
45
70 ... 90
80 ... 1005)
160
200
}
}
3RU11 46-4LB0
3RU11 46-4MB0
1
1
1 unit
1 unit
101
101
0.550
0.550
Price
per PU
kg
Size S00
S00
5
3RU11 16-..B0
Size S0
S0
3RU11 26-..B0
Size S2
S2
3RU11 36-..B0
Size S3
S3
3RU11 46-..B0
1)
With the suitable terminal brackets (see "Accessories", page 5/47), the
3RU11 overload relays for direct mounting can also be installed as standalone units.
2)
Observe maximum rated operational current of the devices.
3)
Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
4)
Maximum protection by fuse for overload relay, type of coordination 2.
For fuse values in conjunction with contactors, see Technical Information
LV 1 T "Technical specifications" --> "Short-circuit protection with
fuses/motor starter protectors for motor feeders".
5)
For overload relays > 100 A, see 3RB2.
* You can order this quantity or a multiple thereof.
5/44
Siemens LV 1 · 2009
© Siemens AG 2009
Overload Relays
3RU1 Thermal Overload Relays
3RU11 for standard applications
3RU11 thermal overload relays with screw terminals on the auxiliary current side for stand-alone installation1), CLASS 10
•
•
•
•
Features and technical specifications:
• Overload and phase failure protection
• Auxiliary contacts 1 NO + 1 NC
• Manual and automatic RESET
Size
Rating
contactor2) for induction
motor
Rated value3)
Switch position indicators
TEST function
STOP button
Integrated, sealable cover
Current setting of
the inverse-time
delayed overload release
Short-circuit DT Screw terminals
(on auxiliary
protection
current side)
with fuse,
type of coorOrder No.
dination 2,
gL/gG operational class4)
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kW
A
A
0.04
0.06
0.06
0.09
0.11 ... 0.16
0.14 ... 0.2
0.18 ... 0.25
0.22 ... 0.32
0.5
1
1
1.6
B
B
B
B
3RU11 16-0AB1
3RU11 16-0BB1
3RU11 16-0CB1
3RU11 16-0DB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.180
0.180
0.180
0.180
0.09
0.12
0.18
0.18
0.28 ... 0.4
0.35 ... 0.5
0.45 ... 0.63
0.55 ... 0.8
2
2
2
4
}
}
}
}
3RU11 16-0EB1
3RU11 16-0FB1
3RU11 16-0GB1
3RU11 16-0HB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.180
0.180
0.180
0.180
0.25
0.37
0.55
0.75
0.7 ... 1
0.9 ... 1.25
1.1 ... 1.6
1.4 ... 2
4
4
6
6
}
}
}
}
3RU11 16-0JB1
3RU11 16-0KB1
3RU11 16-1AB1
3RU11 16-1BB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.180
0.180
0.180
0.180
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
10
10
16
20
}
}
}
}
3RU11 16-1CB1
3RU11 16-1DB1
3RU11 16-1EB1
3RU11 16-1FB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.180
0.180
0.180
0.180
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12
20
25
35
35
}
}
}
}
3RU11 16-1GB1
3RU11 16-1HB1
3RU11 16-1JB1
3RU11 16-1KB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.180
0.180
0.180
0.180
S0
7.5
7.5
11
11
11 ... 16
14 ... 20
17 ... 22
20 ... 25
40
50
63
63
}
}
}
}
3RU11 26-4AB1
3RU11 26-4BB1
3RU11 26-4CB1
3RU11 26-4DB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.240
0.240
0.240
0.240
S2
15
18.5
22
22
22 ... 32
28 ... 40
36 ... 45
40 ... 50
80
80
100
100
}
}
}
}
3RU11 36-4EB1
3RU11 36-4FB1
3RU11 36-4GB1
3RU11 36-4HB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.480
0.480
0.480
0.480
S3
30
37
45
45
45 ... 63
57 ... 75
70 ... 90
80 ... 1005)
125
160
160
200
}
}
}
}
3RU11 46-4JB1
3RU11 46-4KB1
3RU11 46-4LB1
3RU11 46-4MB1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.810
0.810
0.810
0.810
Price
per PU
kg
S00
Size S0
Size S2
Size S3
1)
Sizes S00 to S3 for screw and snap-on mounting onto TH 35 standard
mounting rails, size S3 also for TH 75 standard mounting rails.
2)
Observe maximum rated operational current of the devices.
3)
Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
4)
Maximum protection by fuse for overload relay, type of coordination 2.
For fuse values in conjunction with contactors, see Technical Information
LV 1 T "Technical specifications" --> "Short-circuit protection with
fuses/motor starter protectors for motor feeders".
5)
For overload relays > 100 A, see 3RB2.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
5/45
5
Size S00
© Siemens AG 2009
Overload Relays
3RU1 Thermal Overload Relays
3RU11 for standard applications
3RU11 thermal overload relays with Cage Clamp terminals for direct mounting1) and stand-alone installation2), CLASS 10
•
•
•
•
Features and technical specifications:
• Overload and phase failure protection
• Auxiliary contacts 1 NO + 1 NC
• Manual and automatic RESET
Size of
Rating
contactor3) for induction
motor
Rated value4)
kW
Current setting
of the inversetime delayed
overload release
Switch position indicators
TEST function
STOP button
Integrated, sealable cover
Short-circuit DT Cage Clamp
protection
terminals
(on auxiliary
with fuse,
current side)
type of coordination 2,
Order No.
gL/gG operational class5)
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
Price
per PU
kg
A
A
0.04
0.06
0.06
0.09
0.11 ... 0.16
0.14 ... 0.2
0.18 ... 0.25
0.22 ... 0.32
0.5
1
1
1.6
B
B
B
B
3RU11 16-0AC1
3RU11 16-0BC1
3RU11 16-0CC1
3RU11 16-0DC1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
0.09
0.12
0.18
0.18
0.28 ... 0.4
0.35 ... 0.5
0.45 ... 0.63
0.55 ... 0.8
2
2
2
4
B
B
}
}
3RU11 16-0EC1
3RU11 16-0FC1
3RU11 16-0GC1
3RU11 16-0HC1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
0.25
0.37
0.55
0.75
0.7 ... 1
0.9 ... 1.25
1.1 ... 1.6
1.4 ... 2
4
4
6
6
}
}
}
}
3RU11 16-0JC1
3RU11 16-0KC1
3RU11 16-1AC1
3RU11 16-1BC1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
10
10
16
20
C
}
B
}
3RU11 16-1CC1
3RU11 16-1DC1
3RU11 16-1EC1
3RU11 16-1FC1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12
20
25
35
35
}
}
}
}
3RU11 16-1GC1
3RU11 16-1HC1
3RU11 16-1JC1
3RU11 16-1KC1
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
0.75
1.1
1.5
1.5
1.8 ... 2.5
2.2 ... 3.2
2.8 ... 4
3.5 ... 5
10
10
16
20
B
B
B
B
3RU11 26-1CD0
3RU11 26-1DD0
3RU11 26-1ED0
3RU11 26-1FD0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
2.2
3
4
5.5
4.5 ... 6.3
5.5 ... 8
7 ... 10
9 ... 12.5
20
25
35
35
B
B
B
B
3RU11 26-1GD0
3RU11 26-1HD0
3RU11 26-1JD0
3RU11 26-1KD0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
7.5
7.5
11
11
11 ... 16
14 ... 20
17 ... 22
20 ... 25
40
50
63
63
}
}
}
}
3RU11 26-4AD0
3RU11 26-4BD0
3RU11 26-4CD0
3RU11 26-4DD0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.190
0.190
0.190
0.190
3
4
5.5
7.5
5.5 ... 8
7 ... 10
9 ... 12.5
11 ... 16
25
35
35
40
B
B
B
B
3RU11 36-1HD0
3RU11 36-1JD0
3RU11 36-1KD0
3RU11 36-4AD0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.320
0.320
0.320
0.320
7.5
11
15
14 ... 20
18 ... 25
22 ... 32
50
63
80
B
B
}
3RU11 36-4BD0
3RU11 36-4DD0
3RU11 36-4ED0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.320
0.320
0.320
18.5
22
22
28 ... 40
36 ... 45
40 ... 50
80
100
100
}
}
}
3RU11 36-4FD0
3RU11 36-4GD0
3RU11 36-4HD0
1
1
1
1 unit
1 unit
1 unit
101
101
101
0.320
0.320
0.320
11
15
18.5
22
18 ... 25
22 ... 32
28 ... 40
36 ... 50
63
80
80
125
B
B
B
B
3RU11 46-4DD0
3RU11 46-4ED0
3RU11 46-4FD0
3RU11 46-4HD0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.550
0.550
0.550
0.550
30
37
45
45
45 ... 63
57 ... 75
70 ... 90
80 ... 100
125
160
160
200
}
}
}
}
3RU11 46-4JD0
3RU11 46-4KD0
3RU11 46-4LD0
3RU11 46-4MD0
1
1
1
1
1 unit
1 unit
1 unit
1 unit
101
101
101
101
0.550
0.550
0.550
0.550
Size S00 for stand-alone installation6)
S00
5
3RU11 16-..C1
Size S0 for direct mounting1)7)
S0
3RU11 16-..D0
Size S2 for direct mounting1)7)
S2
3RU11 36-..D0
Size S3 for direct mounting1)7)
S3
3RU11 46-..D0
1)
With the suitable terminal brackets (see "Accessories", page 5/47), the
3RU11 overload relays for direct mounting can also be installed as standalone units.
5)
Size S00 for screw and snap-on mounting onto TH 35 standard mounting
rail.
Maximum protection by fuse for overload relay, type of coordination 2.
For fuse values in conjunction with contactors, see Technical Information
LV 1 T "Technical specifications" --> "Short-circuit protection with
fuses/motor starter protectors for motor feeders".
2)
3)
6)
Auxiliary and main conductor connections with Cage Clamp terminal.
Observe maximum rated operational current of the devices.
7)
4)
Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
Auxiliary conductor connections with Cage Clamp terminals and main conductor connections with screw terminals.
* You can order this quantity or a multiple thereof.
5/46
Siemens LV 1 · 2009
© Siemens AG 2009
Overload Relays
3RU1 Thermal Overload Relays
Accessories
■ Overview
The following optional accessories are available for the 3RU11
thermal overload relays:
• For the four overload relay sizes S00 to S3 one terminal
bracket each for stand-alone installation
• One electrical remote RESET module in three voltage variants
for all sizes
• One mechanical RESET module for all sizes
• One cable release for resetting devices which are difficult to
access (for all sizes)
• Terminal covers
■ Selection and ordering data
Version
Size
DT Order No.
Price
per PU
PU
(UNIT,
SET, M)
PS*
PG
Weight
per PU
approx.
kg
Terminal brackets for stand-alone installation
S00
}
3RU19 16-3AA01
1
1 unit
101
0.060
S0
}
3RU19 26-3AA01
1
1 unit
101
0.080
S2
}
3RU19 36-3AA01
1
1 unit
101
0.180
S3
}
3RU19 46-3AA01
1
1 unit
101
0.280
Resetting plungers, holders and formers S00 ...S3
}
3RU19 00-1A
1
1 unit
101
0.038
Pushbuttons with extended stroke
(12 mm), IP65, Ø 22 mm
B
3SB30 00-0EA11
1
1 unit
102
0.020
Extension plungers
For compensation of the distance between
the pushbutton and the unlatching button of
the relay
A
3SX1 335
1
1 unit
102
0.004
• Length 400 mm
}
3RU19 00-1B
1
1 unit
101
0.063
• Length 600 mm
}
3RU19 00-1C
1
1 unit
101
0.073
}
3RU19 00-2AB71
1
1 unit
101
0.066
}
3RU19 00-2AF71
1
1 unit
101
0.067
}
3RU19 00-2AM71
1
1 unit
101
0.066
S3
}
3RT19 46-4EA1
1
1 unit
101
0.040
• Length 20.6 mm
S2
}
3RT19 36-4EA2
1
1 unit
101
0.020
• Length 20.8 mm
S3
}
3RT19 46-4EA2
1
1 unit
101
0.025
For separate mounting of overload relays;
screw and snap-on mounting onto TH 35
standard mounting rail; size S3 also for
TH 75 standard mounting rail
3RU19 .6-3AA01
3RU19 00-1A
with pushbutton and
extension plunger
Cable releases with holder for RESET1)
For Ø 6.5 mm holes in the control panel;
max. control panel thickness 8 mm
S00 ...S3
3RU19 00-1.
Modules for remote RESET, electrical
Operating range
24 ... 30 V
0.85 ... 1.1 x Us;
110 ... 127 V
power consumption
AC: 80 VA, DC: 70 W; 220 ... 250 V
ON period 0.2 ... 4 s;
switching frequency
60/h
S00 ...S3
3RU19 00-2A.71
Terminal covers1)
Covers for cable lugs and busbar
connections
• Length 55 mm
Covers for box terminals
For more accessories (screwdrivers and labeling plates),
see page 5/62.
1)
The accessories are identical to those of the 3RB2 solid-state overload
relays.
* You can order this quantity or a multiple thereof.
Siemens LV 1 · 2009
5/47
5
Mechanical RESET1)