- No category
Adjustable Capacitive Prox E2K-C Cylindrical Sensor Offers Adjustable Detecting Distance
Add to my manuals8 Pages
advertisement
E2K-C
Adjustable Capacitive Prox
Cylindrical Sensor Offers
Adjustable Detecting Distance
■
Permits non-contact detection of metallic and non-metallic objects such as glass, wood, water, oil and plastic
■
Allows indirect detection of materials inside non-metallic containers
■
Adjustable detecting distance from 3 to 25 mm
■
Built-in amplifier accepts wide range of supply voltages and switches up to
200 mA
■
Mounting bracket included
Ordering Information
■ SENSORS
Type
Nominal detecting distance
Output type
Part number
AC switching type (SCR)
DC switching type
NPN
PNP
■ REPLACEMENT PARTS
Description
Mounting bracket for E2K-C (supplied with sensor)
Unshielded
3 to 25 mm (0.12 to 0.98 in), adjustable
NO NC
E2K-C25MY1
E2K-C25ME1
E2K-C25MF1
E2K-C25MY2
E2K-C25ME2
E2K-C25MF2
Part number
Y92E-A34
E2K-C
E2K-C
2
E2K-C E2K-C
Specifications
Part number
Sensor type
Body
Supply voltage
Size
Type
Current consumption
Detectable object type
Sensitivity
Effective maximum detecting distance (with standard target)
E2K-C25M ❑❑
Capacitive
34 mm (1.34 in) diameter
Unshielded
10 to 40 VDC, 10% max. permissible ripple peak to peak
10 mA max. at 12 VDC
15 mA max. at 24 VDC
Metallic and non-metallic objects
Adjustable
3 to 25 mm
(0.12 to 0.98 in)
E2K-C25MY ❑
90 to 250 VAC, 50/60 Hz
1 mA max. at 100 VAC
2 mA max. at 200 VAC
Standard target size
(grounded mild steel, L x W x H)
Differential travel
50 x 50 x 1 mm
(2.0 x 2.0 x 0.04 in)
15% max. of detecting distance
Control output
AC solidstate
Type
Max. load
Min. load
Max. off-state leakage current
Max. on-state voltage drop
Type
—
—
—
—
—
DC solidstate
Response frequency
Max. load
Max. on-state voltage drop
Circuit protection
Output shortcircuit
DC power supply reverse polarity
Indicators
Materials
Mounting
Connections
NPN-NO open collector with pull-up
NPN-NC open collector with pull-up
PNP-NO open collector with pull-down
PNP-NC open collector with pull-down
200 mA
See “Residual Load Voltage” graph in
Engineering Data
70 Hz
Not provided
Provided
Weld field immunity Not provided
RFI immunity Not provided
Target Present (red LED)
Housing
Sensing face
Cable sheath
ABS/PC
ABS
PVC
Bracket Y92E-A34 included
Prewired
Weight with cable
Enclosure ratings
Approvals
CSA
Ambient operating temperature
Vibration
Shock
UL
NEMA
IEC 144
UL
IP67
—
SCR-NO (E2K-C25MY1)
SCR-NC (E2K-C25MY2)
200 mA
5 mA
See “Leakage Current Characteristics” graph in Engineering Data
2V max.
Listed, File Number E76675
—
–25
°
to 70
°
C (–13
°
to 158
°
F)
Certified, File Number LR45951
10 to 55 Hz, 1.5 mm (0.06 in) double amplitude
Approx. 50 G's
—
—
10Hz
Not provided
—
Output Operation (red LED)
Three-conductor cable, 2 m (6.56 ft) length Two-conductor cable, 2 m (6.56 ft) length
Approx. 200 g (7.0 oz.)
1
1, 4, 12, 13
3
E2K-C E2K-C
Operation
■ OUTPUT CIRCUIT DIAGRAMS AND TIMING CHARTS
DC Switching Types
E2K-C25ME ❑
The dotted line shows a transistor circuit load.
22
Ω
Brown (Red)
4.7 K
Ω
D
2
D
1
Black (White)
Prox.
switch main circuit
2.2
Ω
Tr
ZD
Blue (Black)
+ V
0 V
Note: IEC colors are shown in parentheses.
E2K-C25ME1
NO
Target
Present
Absent
Load (between red and white)
Operates
Releases
Logic (between white and black)
H
Operation indicator
L
ON
OFF
E2K-C25ME2
NC
E2K-C25MF ❑
The dotted line shows a transistor circuit load.
Prox.
switch main circuit
D
2
4.7 K
Ω
ZD
Black (White)
22
Ω
2.2 Ω
D
1
Target
Present
Absent
Load (between white and black)
Operates
Releases
Logic (between red and white)
Operation indicator
H
L
ON
OFF
Brown (Red)
Blue (Black)
E2K-C25MF1
NO
Tr
+ V
0 V
E2K-C25MF2
NC
AC Switching Types
E2K-C25MY ❑
Prox.
switch main circuit
White (Black)
Load
Black (Blue)
Target
Load
Operation indicator
NO
NC
NO
NC
Present
Absent
Operates
Releases
Operates
Releases
ON
OFF
ON
OFF
Note: IEC colors are shown in parentheses.
4
E2K-C
Engineering Data
Operating Range
E2K-C25MY1
Standard target
X
Detecting
30 head
Y 25
Setting distance
25mm
20
20mm
15
15mm
10
10mm
5
5mm
25 20 15 10 5 0 5 10 15 20
25
Detecting head
Y (mm)
Detecting Distance vs. Size and Material of Target
Detecting Distances of Common Materials
30
25
20
Detecting distance
X
❑
Grounded mild steel t = 1 mm
Ungrounded mild steel t = 1 mm
25
20
15
15
10 10
5
Phenolic resin plate t = 6 mm
0
10 20 30 40 50 60 70 80 90 100
Size of target (mm)
5
0
E2K-C
5
E2K-C E2K-C
Residual Load Voltage Characteristics
DC switching types
E2K-C25M ❑❑
24VDC
AC switching types
E2K-C25MY ❑
100 VAC 200 VAC
2.5
2.0
1.5
1
0.5
0.1
0.05
0.01
ON (V
2
)
OFF (V
1
)
24 VDC
0 50 100 150 200 250
Load current (mA)
R
V
S
10 – i
(k
Ω
) P
>
V
S
R
2
(mW) i
P : Power rating of bleeder resistor
V
S
: Load current (mA)
: Supply voltage (V)
Leakage Current Characteristics
AC switching types
E2K-C25MY ❑
3.0
Residual output voltage
100
90
80
70
60
50
40
30
Residual output voltage
Load
ON
AC
100V
20
Residual
10 load voltage OFF
0
1 5 10 50 100 200
Load current (mA)
200
150
ON
100 Load
50
Residual load voltage
OFF
0
1 5 10 50 100 200
AC
200V
Load current (mA)
Note: When the current rating of the load is less than 10 mA, false operation may occur. This is normal, and the problem can be cured by installing a bleeder resistor in parallel with the load. Use the formulas given here to calculate the power rating and value of the resistor.
1.0
0.5
OFF state
0
0 80 100 120 140 160 180 200 220 240
260
Supply voltage (V)
Dimensions
Unit: mm (inch)
■ SENSORS
E2K-C25M ❑❑
34 (1.34) dia.
20
(0.79)
82
(3.23)
31
(1.22)
Cap screw for sensitivity adjustment
6
(0.24)
Operation indicator
(LED)
0.15
(0.006)
Note: Cable may be extended to 200 m (656 ft).
Cable: 2 m (6.56 ft.) length
6
E2K-C
Unit: mm (inch)
■ MOUNTING BRACKET
Y92E-A34 (supplied with sensor)
45 (1.77)
43 (1.69)
5.2 (0.20)
R2.6
(0.102)
6.3 (0.25)
Two elliptic holes for bracket mounting
(0.08)
23.5 (0.93)
35 (1.38)
15 (0.59)
2
42 (1.65)
Two M4 sensor clamping screws
55 (2.16)
Sensor mounting hole
E2K-C proximity sensor
51 (2.01)
30
(1.18)
14
(0.55)
6 (0.24)
45 (1.77)
58 (2.28)
Two 5.5 (0.22) dia. mounting holes
35
(1.38)
Precautions
■ EFFECTS OF SURROUNDING METALS
When mounting the sensor, be sure to provide the minimum distance shown in the diagram. This prevents the sensor from being affected by metallic objects other than the target. Also, when using the supplied mounting bracket, be sure to allow a distance of 20 mm or more between the detecting face and the mounting bracket.
20 (0.79) mm min.
80 (3.15) mm min.
Surrounding conductive object
Detecting face
Metal
To ground
E2K-C
■ MUTUAL INTERFERENCE
To prevent mutual interference, be sure to space the two sensors at a distance greater than that shown in the diagrams.
Opposed mounting
100 (3.94) mm min.
Parallel mounting
100 (3.94) mm min.
80
(3.15) mm min.
80 (3.15) mm min.
80 (3.15) mm min.
Surrounding conductive object
7
E2K-C
■ SENSITIVITY ADJUSTMENT
NO type (E2K-C25M ❑ 1)
Remove protective rubber plug to gain access to sensitivity adjustment screw. Use the screwdriver provided with each sensor to turn the sensitivity adjustment screw.
1) Remove any targets from in front of the sensor. Turn the sensitivity adjustment screw CLOCKWISE until the sensor turns ON and the indicator illuminates.
Sensitivity adjustment
Stop when the sensor turns ON
2) Place a target in front of the sensor. Turn the sensitivity adjustment screw COUNTERCLOCKWISE until the sensor turns OFF and the indicator goes out. Note the number of revolutions between OFF and ON positions.
Sensitivity adjustment
Stop when the sensor turns OFF
3) If the number of revolutions is greater than one and a half, the sensor will provide stable output. If the number of revolutions is less than one and a half, increase or decrease the distance between the target and the sensing face as necessary to allow at least one and a half revolutions between the ON and OFF positions.
1
ON point
Stable operation if the difference is more than 1.5 turns
2
4) Now turn the sensitivity adjustment screw CLOCKWISE to the midpoint between the ON and OFF points.
1 ON point
1
Set at midpoint between ON and
OFF points
2 OFF point
5) If the distance between the target and the sensor is not constant, perform the first adjustment operation (#1) when the target is at the closest position to the sensor. Then perform the second adjustment operation (#2) when the target is at the farthest position from the sensor.
NC type (E2K-C25M ❑ 2)
The sensitivity adjustment procedure for NC type proximity sensors is the same as for NO type sensors, with the exception that ON and OFF operations of the proximity sensor and ON and OFF points in the adjustment procedure are exactly reversed.
E2K-C
■ USING METAL CONDUIT
If a high voltage of power line runs near the proximity sensor cable, be sure to wire the sensor cable through a metal conduit to protect the sensor from malfunctioning or damage.
■ SURGE PROTECTION
The proximity sensor is provided with a surge suppressor circuit. However, if any large surge generating source (i.e., motor, welding machine, etc.) exists in the vicinity of the proximity sensor, insert a surge suppressor (such as a varistor) into the surge generating source.
8
E2K-C E2K-C
OMRON ELECTRONICS LLC
One East Commerce Drive
Schaumburg, IL 60173
1-800-55-OMRON
Cat. No. CEDSAX4 11/01
OMRON ON-LINE
Global - http://www.omron.com
USA - http://www.omron.com/oei
Canada - http://www.omron.com/oci
Specifications subject to change without notice.
OMRON CANADA, INC.
885 Milner Avenue
Scarborough, Ontario M1B 5V8
416-286-6465
Printed in the U.S.A.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project