DILM115(RAC240) 239548 Contactor,55kW/400V,AC operated Connection technique

DILM115(RAC240) 239548 Contactor,55kW/400V,AC operated Connection technique
Type: DILM115(RAC240)
Article No.: 239548
Sales text Contactor,55kW/400V,AC operated
Ordering information
Connection technique
Screw terminals
Description
3 pole
Description
Springloaded terminals on the
auxiliary and control circuit
terminals
Rated operational current
AC−3 380 V 400 V
Ie
A
115
AC−3 220 V 230 V
P
kW
37
AC−3 380 V 400 V
P
kW
55
AC−3 660 V 690 V
P
kW
90
AC−4 220 V 230 V
P
kW
17
AC−4 380 V 400 V
P
kW
28
AC−4 660 V 690 V
P
kW
43
Ith = Ie
A
130
Max. rating for three−phase motors, 50
– 60 Hz
Conventional free air thermal current I th
= I e AC−1 at 60 °C
Open
Contacts
Can be combined with auxiliary contact
1
DILM150−XHI(V)..
DILM1000−XHI(V)..
Actuating voltage
RAC 240
Contact sequence
Notes concerning the product group
Accessories
1 Overload relay
278442
2 Suppressor
281199
3 Auxiliary contact module
277376
Further actuating voltages
277379
Accessories
281227
The DC operated contactors have
integral suppressor circuits (DILM7 −
DILM15: Varistor).
Contactors DILM115, DILM150 and
DILM170 have a built−in suppressor
circuit.
Mirror contact for DILM7−01 to
DILM32−01
Contactor contact according to EN
50012
General
Standards
Lifespan, mechanical
2
IEC/EN 60947, VDE 0660,
UL, CSA
AC operated
Operations
× 106 10
DC operated
Operations
× 106 10
Operating frequency, mechanical
AC operated
Operations/h
3600
DC operated
Operations/h
3600
Damp heat, constant, to IEC
60068−2−78
Damp heat, cyclical, to IEC
60068−2−30
Climatic proofing
Ambient temperature
Open
°C
–25...60
Enclosed
°C
–25...40
Storage
°C
... 40...+80
Mechanical shock resistance
(IEC/EN 60068−2−27)
Half−sinusoidal shock, 10 ms
Main contacts
N/O contact
g
10
N/O contact
g
7
N/C contact
g
5
g
10
Min. rated current = rated
uninterrupted current
g
7
N/C contact
g
5
Auxiliary contacts
Mechanical shock resistance
(IEC/EN 60068−2−27) when
tabletop−mounted
Half−sinusoidal shock, 10 ms
Main contacts
Thickness of material for busbar
max.
Auxiliary contacts
Protection type
IP00
Protection against direct contact
when actuated from front (IEC 536)
Finger− and back−of−hand
proof
Weight
AC operated
kg
2
DC operated
kg
2,1
Terminal capacity main cable
Flexible with ferrule
3
mm2
1 × (10 – 95)
2 × (10 – 70)
1 × (16 – 95)
2 × (16 – 70)
Stranded
mm2
Solid or stranded
AWG 8...3/0
Flat conductor
Number of
segments ×
width ×
thickness
mm
Main cable connection screw/bolt
2 × (6 × 16 × 0.8)
M10
Tightening torque
Nm
14
Solid
mm2
1 × (0.75 – 4)
2 × (0.75 – 4)
Flexible with ferrule
mm2
1 × (0.75 – 2.5)
2 × (0.75 – 2.5)
Solid or stranded
AWG 18 – 14
Terminal capacity control circuit
cables
Control circuit cable connection
screw/bolt
M3.5
Tightening torque
Nm
1.2
mm
5
Tool
Main cable
Hexagon socket−head spanner
SW
Control circuit cables
Pozidriv screwdriver
Size 2
Standard screwdriver
mm
0.8 × 5.5
1×6
Solid
mm2
1 × (0.75 – 2.5)
2 × (0.75 – 2.5)
Flexible
mm2
1 × (0.75 – 2.5)
2 × (0.75 – 2.5)
Flexible with ferrule
mm2
1 × (0.75 – 1.5)
2 × (0.75 – 1.5)
Solid or stranded
AWG 18 – 14
Terminal capacity control circuit
cables
Tool
Stripping length
mm
10
Screwdriver blade width
mm
3,5
Main conducting paths
Rated impulse withstand voltage
Overvoltage category/pollution
degree
4
Uimp
V AC 8000
III/3
Rated insulation voltage
Ui
V AC 1000
Rated operational voltage
Ue
V AC 1000
Safe isolation to VDE 0106 Part 101
and Part 101/A1
between coil and contacts
V AC 690
between the contacts
V AC 690
Making capacity (p.f. to IEC/EN
60947)
Up to 690 V
A
1610
220/230 V
A
1150
380/400 V
A
1150
500 V
A
1150
660/690 V
A
1100
Breaking capacity
Short−circuit rating
Short−circuit protection maximum
fuse
Type “2” coordination
400 V
gG/gL 500 V
A
250
690 V
gG/gL 690 V
A
250
400 V
gG/gL 500 V
A
250
690 V
gG/gL 690 V
A
250
at 40 °C
Ith
A
160
at 50 °C
Ith
A
142
at 55 °C
Ith
A
135
at 60 °C
Ith
A
130
enclosed
Ith
A
115
open
Ith
A
325
enclosed
Ith
A
285
Type “1” coordination
AC
AC−1 duty
conv. therm. current 3 pole 50 – 60
Hz
open
Conventional free air thermal current,
1 pole
AC−3 duty
Rated operational current AC−3
open, 50 – 60 Hz, 3 pole
5
220/230 V
Ie
A
115
240 V
Ie
A
115
380/400 V
Ie
A
115
415 V
Ie
A
115
440V
Ie
A
115
500 V
Ie
A
115
660/690 V
Ie
A
93
220/230 V
P
kW
37
240V
P
kW
40
380/400 V
P
kW
55
415 V
P
kW
70
440 V
P
kW
75
500 V
P
kW
85
660/690 V
P
kW
90
220/230 V
Ie
A
55
240 V
Ie
A
55
380/400 V
Ie
A
55
415 V
Ie
A
55
440 V
Ie
A
55
500 V
Ie
A
55
660/690 V
Ie
A
45
220/230 V
P
kW
17
240 V
P
kW
19
380/400 V
P
kW
28
415 V
P
kW
33
440 V
P
kW
35
500 V
P
kW
40
660/690 V
P
kW
43
60 V
Ie
A
160
110 V
Ie
A
160
220 V
Ie
A
90
Motor rating
AC−4 duty
Rated operational current AC−4
open, 50 – 60 Hz, 3 pole
Motor rating
DC
of three−phase capacitors open
DC−1 operation
6
440 V
Ie
A
4,5
60 V
Ie
A
160
110 V
Ie
A
160
220 V
Ie
A
40
440 V
Ie
A
1
60 V
Ie
A
160
110 V
Ie
A
160
220 V
Ie
A
40
440 V
Ie
A
1
Current heat loss at Ith
W
20,3
Current heat loss at Ie to AC−3/400 V
W
15,9
Impedance per pole
m
0,4
DC−3 operation
DC−5 operation
Current heat loss (3 pole)
Magnet systems
Voltage tolerance
AC operated
Pick−up
× Uc 0,8...1,15
Drop−out voltage AC operated
Drop−out
× Uc 0,25...0,6
DC operated
Pick−up
× Uc 0,7...1,2
DC operated
Drop−out
× Uc 0,15...0,6
Power consumption of the coil in a
cold state and 1.0 × Uc
50 Hz
Pick−up
VA
180
50 Hz
Sealing
VA
3,1
50 Hz
Sealing
W
2,1
60 Hz
Pick−up
VA
170
60 Hz
Sealing
VA
3,1
60 Hz
Sealing
W
2,1
50/60 Hz
Pick−up
VA
170
170
50/60 Hz
Sealing
VA
3,1
3,1
50/60 Hz
Sealing
W
2,1
2,1
DC operated
Pick−up
W
149
DC operated
Sealing
W
2.1
Duty factor
Switching times at 100 % Uc
(approximate values)
7
% DF 100
Main contacts
AC operated
Closing delay
ms
28...33
Opening delay
ms
35...41
Closing delay
ms
35
Opening delay
ms
30
Arcing time
ms
15
Permissible residual current with
actuation of A1 – A2 by the
electronics (with 0 signal).
mA
1
DC operated
Electromagnetic compatibility (EMC)
Emitted interference
to EN 60947−1
Interference immunity
to EN 60947−1
Notes
Notes
Mounting position, AC− and DC operated
8
The following applies to
magnet systems, voltage
tolerance, pickup voltage
DC−operated DILM17 –
DILM32:
RDC 24 (Umin 24 V
DC/Umax 27 V DC)
RDC 60 (Umin 48 V
DC/Umax 60 V DC)
RDC 130 (Umin 110 V
DC/Umax 130 V DC)
RDC 240 (Umin 200 V
DC/Umax 240 V DC)
Example:
Uc = 0.7 x Umin − 1.2 x
Umax
Uc = 0.7 x 24 V − 1.2 x 27 V
DC
With voltage tolerance and
DC operated power
consumption the following
applies: At least smoothed
double−pulse bridge
rectification or a three−phase
current rectifier is necessary
Dimensions
Dimensions
9
distance at side to earthed parts: 10 mm
Basic unit with auxiliary contact module
Characteristic curve
10
Squirrel−cage motor
Operating characteristics
Starting:from rest
Stopping:after attaining full running speed
Electrical characteristics
Make: up to 6 × rated motor current
Break: up to 1 × rated motor current
Utilization category
100 % AC−3
Typical applications
Compressors
Lifts
Mixers
Pumps
Escalators
Agitators
Fans
Conveyor belts
Centrifuges
Hinged flaps
Bucket−elevators
Air conditioning system
General drives in manufacturing and processing machines
Characteristic curve
11
Extreme switching duty
Squirrel−cage motor
Operating characteristics
Inching, plugging, reversing
Electrical characteristics
Make: up to 6 × rated motor current
Break: up to 6 × rated motor current
Utilization category
100 % AC−4
Typical applications
Printing presses
Wire−drawing machines
Centrifuges
Special drives for manufacturing and processing machines
Moeller GmbH, Hein−Moeller−Str. 7−11, D−53115 Bonn
E−Mail: [email protected], Internet: www.moeller.net, http://catalog.moeller.net
Copyright 2006 by Moeller GmbH. HPL−C2007G V2.1
12
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project