- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Samsung
- MC26AC2X
- Service manual
advertisement
DB98_11868A(1)_cover 3/3/03 11:16 AM Page 3
ROOM AIR CONDITIONER
INDOOR UNIT
MC26AC2-07
MC26AC2-12
OUTDOOR UNIT
MC26AC2X
SERVICE Manual
AIR CONDITIONER
1. Precautions
CONTENTS
2. Product Specifications
3. Operating Instructions and
Installation
4. Disassembly and Reassembly
5. Troubleshooting
6. Exploded Views and Parts List
7. Block Diagrams
8. PCB Diagrams
9. Wiring Diagrams
10. Schematic Diagrams
DB98_11868A(1)_1 3/3/03 11:17 AM Page 1-1
1. Precautions
1. Warning: Prior to repair, disconnect the power cord from the circuit breaker.
2. Use proper parts: Use only exact replacement parts. (Also, we recommend replacing parts rather than repairing them.)
3. Use the proper tools: Use the proper tools and test equipment, and know how to use them.
Using defective tools or test equipment may cause problems later-intermittent contact, for example.
4. Power Cord: Prior to repair, check the power cord and replace it if necessary.
5. Avoid using an extension cord, and avoid tapping into a power cord. This practice may result in malfunction or fire.
6. After completing repairs and reassembly, check the insulation resistance.
Procedure: Prior to applying power, measure the resistance between the power cord and the ground terminal. The resistance must be greater than 30 megaohms.
7. Make sure that the grounds are adequate.
8. Make sure that the installation conditions are satisfactory.
Relocate the unit if necessary.
9. Keep children away from the unit while it is being repaired.
10. Be sure to clean the unit and its surrounding area.
Fig. 1-1 Avoid Dangerous Contact
Fig. 1-2 No Tapping and No Extension Cords
Fig. 1-3 No Kids Nearby!
Samsung Electronics
Fig. 1-4 Clean the Unit
1-1
DB98_11868A(1)_1 3/3/03 11:17 AM Page 1-2
M E M O
1-2 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-1
2. Product Specifications
2-1 Table
Model
Item
Type
Cooling
Performance
Power
Dehumidifying
Air volume
Noise
Power
Power Consumption
Operating Current
Starting Current
Power Cord (Option)
Connection Cable (Option)
Fuse Capacity
Outer
Dimension
Weight
W x H x D
Refrigerant pipe
Liquid
Gas
Drain hose
Type
A mm inch kg
OD(mm)xL(m)
OD(mm)xL(m)
OD(mm)xL(m) kW
BTU/h
Kcal/h
\ /h m 3 /min dB
ø-V-Hz
W
A
A
Size Model name
Compressor
Capacitor
Blower
Motor
Type
Rated output
Type
Motor
Type
Rated output
Heat exchanger
Refrigerant control unit
Freezer oil capacity
W
W cc
Refrigerant to charge(R410A)
Protection device
Cooling test condition
Maximum operation condition
INDOOR UNIT
MC26AC2-07
2.05 x 2
6,995 x 2
1,763x2
0.9
6
39
1,250
5.5
3.15
790 x 245 x 165
31.1 x 9.64 x 6.50
7.7
ø6.35 x 5
MC26AC2
INDOOR UNIT
MC26AC2-12
Wall-Mounting Multi Split
3.5
11,942
3,009
1.5
8
42
1-220-240V~, 50Hz
1,210
5.4
30
2.5 x 3core
1.0 x 4core
3.15
790 x 245 x 165
31.1 x 9.64 x 6.50
7.7
ø6.35 x 5
OUTDOOR UNIT
MC26AC2X
7.6
25,932
6,535
-
-
60
2,460
10.9
-
880 x 638 x 310
34.65 x 25.1 x 12.2
60
-
ø9.52 x 5
ø18.0 x 2
-
-
-
ø9.52 x 5
ø18.0 x 2
-
-
-
-
-
Rotary
A : G8C124JU1EL
B : G8C124JU1EL
A : 35µF 450VAC
B : 35µF 450VAC
-
-
Resin
Cross-flow
22
2Row 12Step
-
-
Resin
Cross-flow
22
2Row 12Step
A/B-Unit : Capillary tube
A : 1,060, B : 1,060
Steel
Propeller
74
2Row 36Step
-
A : 500
B : 500
A-Unit : 920g, B-Unit : 970g
-
A : RAC12128-9622
B : RAC12128-9622
Indoor unit : DB27˚C WB19˚C Outdoor unit : DB35˚C WB24˚C
Indoor unit : DB32˚C WB23˚C Outdoor unit : DB43˚C WB26˚C
Samsung Electronics 2-1
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-2
2-2 Dimensions
2-2-1 Indoor Unit
(Unit : mm)
Air out
Air in
(Front view)
790
165
(Remote control)
45 22
Installation plate
2-2 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-3
2-2-2 Outdoor Unit
(Front view)
660
1000 340
(Rear view)
Product Specifications
(Unit : mm)
Samsung Electronics 2-3
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-4
2-3 Pressure Graph
■ MC26AC2-07
■
11
10
9
8
7
20 30
Outdoor drybulb temperature [deg C]
30.6/22.5
27/19
21.5/14.6
40
■ MC26AC2-12
■
10
9
8
7
6
20
30.6/22.5
27/19
21.5/14.6
30
Outdoor drybulb temperature [deg C]
40
2-4 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-5
3. Operating Instructions and Installation
3-1 Operating Instructions
3-1-1 The Feature of Key in remote controller
NO
1
NAMED OF KEY
FUNCTION OF KEY
Power On/Off button to start and stop airconditioner or timer set up.
2
3
(UP)
(DOWN)
Temp. up button. To increase the temperatute by the pressing the temperature button.
Temp. down button. To decrease the temperature by the pressing the temperature button.
Each time you press this button
Mode is changed in the following order : Auto Mode
: Cool Mode
: Dry Mode
: Fan Only
4
Press until the appearance. The air condition cools the room as quickly as possible. After 30minutes, the air, the airconditioner is reset automatically to the previous mode.
Press until the appearance. The sleep timer can be used when you are cooling your room to switch the air conditioner off automatically after a period of six hours.
Each time you press this button,
FAN SPEED is changed in the following order.
5
6
7
8
Adjust air flow vertically.
The ON Timer enables you to switch on the air conditioner automatically after a given period of time that is from 30 minutes to 24 hours.
To cancel the On Time, press the (Set/Cancel) button.
The Off Timer enables you to switch off the air conditioner automatically after a given period of time that is from 30 minutes to 24 hours.
To cancel the Off Time, press the (Set/Cancel) button.
To select the 5 way function with the remote control, press the 5 way button one or more times until the desired mode is selected.
Each time you press the 5 way button.
9
Each 5 way indicator on the indoor unit comes on in order.
Samsung Electronics 3-1
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-6
Operating Instructions and Installation
3-1-2 Name & Function of Key in remote controller
1. AUTO MODE : In this mode, operation
COOL mode is selected automatically by the room temperature of initial operation.
Operation Type
Cool Operation
Room Temp
Tr
≥
25°C+
∆
T
Tr<24°C+
∆
T
Compressor ON
Compressor OFF
∆
T= -1°C, -2°C, 0°C+1°C+2°C
∆
T is controlled by setting temperature up/down key of remote controller
* FAN SPEED : AUTO
2. COOL MODE : The unit operates according to the difference between the setting and room temperature.
(18°C~30°C)
3. DRY MODE : Has 3 states, each determined by room temperature.
The unit operates in DRY mode.
*Compressor ON/OFF Time is controlled compulsorily(can not set up the fan speed, always breeze).
*Protective function : Low temperature release. (Prevention against freeze)
4. TURBO MODE : This mode is available in
AUTO, COOL, DRY, FAN MODE.
When this button is pressed at first, the air conditioner is operated “powerful” state for 30 minutes regardless of the set temperature, room temperature.
When this button is pressed again, or when the operating time is 30 minutes, turbo operation mode is canceled and returned to the previous mode.
*But, if you pressed the TURBO button in
DRY or FAN mode that is changed with
AUTO mode automatically.
5. SLEEP MODE : Sleep mode is available only in COOL mode.
The operation will stop after 6 hours.
*The setting temperature is automatically raised by 1°C each 1hour When the temperature has been raised by total of
2°C, that temperature is maintained.
6. FAN SPEED : Manual (3 step), Auto (4 step)
Fan speed automatically varies depending on both the difference between setting and the room temperature.
7. COMPULSORY OPERATION :
For operating the air conditioner without the remote controller.
*AUTO : The operating is the same function that AUTO MODE in the remote controller. And each time you press the button the 5WAY function is changed as follow. STD ➝ NATURE ➝ POWER ➝
SAVING ➝ SILENCE ➝ POWER OFF
❊ STD(standard)( ) : General operation Mode
❊ NATURE( ) : The unit is operated according to health pattern control
❊ POWER( ) : The unit is operated in powerful state
❊ SAVING( ) : The unit is operated in power saving state
❊ SILENCE( ) : The unit is operated quietly
Each mode has Auto, Cool and SLEEP operation designed in advance.
3-2 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-7
Operating Instructions and Installation
8. SWING : BLADE-H is rotated vertically by the stepping motor.
*Memory louver : When ON/OFF button is pressed at stop state, the BLADE-H returns to its original location which is operating state before stop
*Swing Set : Press the button under the remote control is displayed on LCD the and the blades move up and down. If the one more time press the button, blades location is stop.
9. 24-Hour ON/OFF Real Setting Timer. :
The air conditioner is turned ON at a specified time using .
OFF TIMER : The air Conditioner is turned OFF at a specified time using .
*ON TIMER : Only timer LED lights on.
*OFF TIMER : Both timer and operation
LED lights on.
10. SELF Diagnosis
Check Point
LED DISPLAY
STD NATURE POWER SAVING SILENCE TIMER
Indoor unit room temperature sensor error(open or short)
Indoor unit heat exchanger temperature sensor error(open or short)
Indoor fan mal function
EEPROM error
Option error(option wasn’t set up or option data error)
: LED blinking : LED off
11. BUZZER SOUND : Whenever the
ON/OFF button is pressed or whenever change occurs to the condition which is set up or select, the compulsory operation mode, buzzer is sounded "beep".
Samsung Electronics 3-3
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-8
3-2 Installation
3-2-1 Selecting Area for Installation
Select an area for installation that is suitable to the customer's needs.
3-2-1(a) Indoor Unit
1. Make sure that you install the indoor unit in an area providing good ventilation. It must not be blocked by an obstacle affecting the airflow near the air inlet and the air outlet.
2. Make sure that you install the indoor unit in an area allowing good air handling and endurance of vibration of the indoor unit.
3. Make sure that you install the indoor unit in an area where there is no source of heat or vapor nearby.
4. Make sure that you install the indoor unit in an area from which hot or cool air is spread evenly in a room.
5. Make sure that you install the indoor unit in an area away from TVs, audio units, cordless phones, fluorescent lighting fixtures and other electrical appliances
(at least 1 meter).
6. Make sure that you install the indoor unit in an area which provides easy pipe connection with the outdoor unit, and easy drainage for condensed water.
7. Make sure that you install the indoor unit in an area which is large enough to accommodate the measurements shown in figure on the next page.
3-2-1(b) Outdoor Unit
1. Make sure that you install the outdoor unit in area not exposed to the rain or direct sun light.
(Install a separate sunblind if exposed to direct sun light.)
2. Make sure that you install the outdoor unit in area allowing good air moment, not amplifying noise or vibration, especially to avoid disturbing neighbours.
(Fix the unit firmly if it is mounted in a high place.)
3. Make sure that you install the outdoor unit in area providing good ventilation and which is not dusty. It must not be blocked by any obstacle affecting the airflow near the air inlet and the air outlet.
4. Make sure that you install the outdoor unit in area free from animals or plants.
5. Make sure that you install the outdoor unit in area not blocking the traffic.
6. Make sure that you install the outdoor unit in area easy to drain condensed water from the indoor unit.
7. Make sure that you install the outdoor unit in area which provides easy connection within the maximum allowable length of a coolant pipe(10 meters).
Note
1. Add 10 grams of refrigerant (R410A) for every
1 meter if the pipe length exceeds the standard pipe length of 5 meters.
2. Maintain a height between the indoor and outdoor units of less than 3 meters.
8. Make sure that you install the outdoor unit in an area which is large enough to accommodate the measurements shown in figure on the next page.
3-2-1(c) Remote Control Unit
1. Make sure that you install the remote control unit in an area free from obstacles such as curtains etc, which may block signals from the remote control unit.
2. Make sure that you install the remote control unit in an area not exposed to direct sunlight, and where there is no source of heat.
3. Make sure that you install the remote control unit in an area away from TVs, audio units, cordless phones, fluorescent lighting fixtures and other electrical appliances (at least 1 meter).
Caution :
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines), salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice.
3-4 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-9
B Drain hose installation
Operating Instructions and Installation
3-2-2 Installation diagram of indoor unit and outdoor unit
A Indoor unit gas leak test check point
Indoor unit
Piping
1
3
2
Tape vinyl
Piping may be laid to the rear, left, right or down .
Right
Rear
Down Rear
Left
125mm or more
Cut the piping hole sloped slightly
6
5
125mm or more
B
A 7
Remote control
100mm or more
600mm or more
4
100mm or more
Outdoor unit check point
A-UNIT
B-UNIT
10
Samsung Electronics
1
2
3
4
5
Piping (Liquid) 1/4"
Piping (Gas) 3/8"
Installation tube
Vinyl tape
Putty
6
7
8
9
10
Clamper tube
Installation plate
Pipe-connection
Screw
Drain hose
3-5
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-10
Operating Instructions and Installation
3-2-2(a) Fixing the Installation Plate
(Unit : mm)
252
Installation plate
Pipe hole
(ø65mm)
275
1. Determine the position of the pipe and drain hose hole using the right figure and drill the hole with an inner diameter of 65mm so that it slants slightly downwards.
2. If you are fixing the indoor unit to a… Then follow
Steps…
Wall
Window frame
3.
4 to 6.
3. Fix the installation plate to the wall in a manner appropriate to the weight of the indoor unit.
If you are mounting the plate on a concrete wall with anchor bolts, the anchor bolts must not project by more than 20mm.
90 140
(Unit : mm)
4. Determine the positions of the wooden uprights to be attached to the window frame.
5. Attach the wooden uprights to the window frame in a manner appropriate to the weight of the indoor unit.
6. Using tapped screws, attach the installation plate to the wooden uprights, as illustrated in the last figure opposite.
3-2-2(b) Purging the Unit
On delivery, the indoor unit is loaded with an inert gas. All this gas must therefore be purged before connecting the assembly piping. To purge the inert gas, proceed as follows.
Unscrew the caps at the end of each pipe.
Result : All inert gas escapes from the indoor unit.
• To prevent dirt or foreign objects from getting into the pipes during installation, do NOT remove the caps completely until you are ready to connect the piping.
3-6 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-11
Operating Instructions and Installation
3-2-2(c) Connecting the Assembly Cable.
Indoor unit
1 2 3 E Earth terminal
Outdoor unit
1
1
(L)
2 3
2
(N)
3
COM
Earth terminal
E
E
The outdoor unit is powered from the indoor unit via the assembly cable. If the outdoor unit is more than five metres away from the indoor unit, the cable must first be extended to a maximum of ten metres.
1. Extend the assembly cable if necessary.
2. Open the front grille by pulling on the tabs on the lower right and left sides of the indoor unit.
3. Remove the screw securing the connector cover.
4. Pass the assembly cable through the rear of the indoor unit and connect the assembly cable to terminals N1 to 1.
• Each wire is labelled with the corresponding terminal number.
5. Firmly fix the ass’y cable with clamp wire holder.
6. Pass the other end of the cable through the 65mm hole in the wall.
7. Replace the connector cover, carefully tightening the screw.
8. Close the front grille.
9. For further details on how to plug the other end of the assembly cable into the outdoor unit, refer to page 3-8.
3-2-2(d) Installing and Connecting the Indoor Unit Drain Hose
Care must be taken when installing the drain hose for the indoor unit to ensure that any condensation water is correctly drained outside. When passing the drain hose through the 65mm hole drilled in the wall, check that none of the following situations occur.
The hose must
NOT slope upwards.
The end of the drain hose must NOT be placed in water.
Do NOT bend the hose in different directions.
To install the drain hose, proceed as follows.
5cm less
Keep a clearance of at least 5cm between the end of the hose and the ground.
Do NOT place the end of the drain hose in a hollow.
1. If necessary, connect the 2-metre extension to the drain hose.
2. If you are using the extension, insulate the inside part of the extension drain hose with a shield.
3. Pass the drain hose under the refrigerant piping, taking care to keep the drain hose tight.
4. Pass the drain hose through the hole in the wall, making sure that it is sloping downwards, as shown in the illustrations above.
Shield
The hose will be fixed permanently into position once the whole installation has been tested for gas leaks;
Drain hose Extension drain hose
Samsung Electronics 3-7
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-12
Operating Instructions and Installation
3-2-2(e) Outdoor unit installation
GAS LEAK TEST
Outdoor unit check point
Indoor unit check point
Check for gas leak from the flare nut connections with leak detector.
WIRING CONNECTION
Two electric cables must be connected to the outdoor unit:
• The assembly cable connecting the indoor unit to the outdoor unit.
• The power cable connecting the auxiliary circuit breaker to the outdoor unit.
1 Remove the terminal board cover on the side of the outdoor unit.
2 Connect the assembly cable to terminals 1 to 5 and connect the power cable to therminals A to B.
√ Each wire is labelled with the corresponding terminal number.
√ Ensure the wire number of the indoor unit and the terminal number of the outdoor unit.
3 Connect the earth wires to the earth terminals.
√ Refer to the page opposite for further details on how to check that earthing is correct.
4 Replace the terminal board cover, carefully tightening the screw.
5 Connect the power cable to the auxiliary circuit breaker.
Outdoor unit
Terminal Block
3
COM
1
(L)
2
(N)
3
COM
3
COM
2
(N)
1
(L)
2
(N)
Indoor Unit
MC26AC2-12
MC26AC2-07
A B
E
Earth terminal
Circuit Breaker
(Main Power cable)
Outdoor Unit
MC26AC2X
1 2 3 5
Earth terminal
1 2 3
Assembly cable
1 2 3
Indoor unit 1 2 3
A-unit
MC26AC2-12
5 1 2 3
Earth terminal
1 2 3
B-unit
MC26AC2-07
5
Earth terminal
1 2 3 5
Earth terminal
5 1 2 3
Earth terminal
1 2 3
C-unit
MC26AC2-07
5
Earth terminal
3-8 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-13
Operating Instructions and Installation
Grounding
(The parts for this work are optional)
• A grounding terminal can be found on the outdoor unit as illustrated.
1. When an existing grounding terminal is avilable.
(Grounding wire of ø1.6mm or larger<solid wire>or 2mm 2 or larger <standard wire>)
Terminal used exclusively for grounding
Grounding resistance: less than 100 ohms
(existing grounding electrode)
Grounding screw hole
2. Use of a grounding electrode.
• Specifications of grounding electrode.
Carbon plastic Steel core
PVC-insulated wire(2mm 2 x3.5m), green Terminal, M4
Samsung Electronics 3-9
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-14
Operating Instructions and Installation
3-2-2(f) Air-Purge Procedure
1. Connect each assembly pipe to the appropriate valve on the outdoor unit and tighten the flare nut.
Outdoor unit
A
B
2. Connect the charging hose of low pressure side of manifold gauge to the packed valve having a service port
(3/8” Packed valve) as shown at the figure.
3. Open the valve of the low pressure side of manifold gauge counter-clockwise.
4. Purge the air from the system using vacuum pump for about
30 minutes.
- After that, please recheck that pressure is staloilization.
- Close the valve of the low pressure side of manifold gauge clockwise.
- Remove the hose of the low pressure side of manifold gauge.
5. Set valve cork of both liquid side and gas side of packed valve to the open position.
6. Mount the valve stem nuts to the 2-way and 3-way valve.
6. And mount the service port cap to 3-way valve.
Valve stem
B
(liquid)
A
(gas)
Indoor unit
Gas pipe side C
Liquid pipe side D
Vacuum Pump
Stem cap
3-10
7. Check for gas leakage.
6. - At this time, especially check for gas leakage from the
3-way valve’s stem nuts, and from the service port cap.
Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-15
Operating Instructions and Installation
3-2-2(g) Refrigerant Refill
• Refill an air-conditioner with refrigerant when refrigerant has been leaked at installing or using.
1. Vacuum system with pump (for new installation, leakage).
2. Turn the 3-way valve clockwise to close, connect the pressure gauge(low pressure side) to the service valve, and open the
3-way valve again.
3. Connect the tank to refill with Refrigerant
4. Set the unit to Low pressure checking mode.
* Press the ON/OFF switch for 5 second.
* All lamps blink on the indoor unit.
5. Check the pressure indicated by the pressure gauge(low pressure side).
* Refer to Low pressure graph.
Compound gauge
For mounting other end of hose when not in use
INDOOR
A-UNIT
INDOOR
B-UNIT
INDOOR
C-UNIT
Suspension hook
High pressure gauge
Hand wheel
Finger tight fittings
Connected to high pressure side
Vacuum pump
6. Open the refrigerant tank and fill with refrigerant until the rated pressure is reached.
* It is recommended not to pour the refrigerant in too quickly, but gradually while operating a pressure valve.
R410A
7. Stop operation of the air conditioner.
8. Close the 3-way valve, disconnect the pressure gauge, and open the 3-way valve again.
9. Close the cap of each valve.
Samsung Electronics 3-11
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-16
Operating Instructions and Installation
3-2-2(h) Refrigerant Adjustment
Class
Connection
Pipe Length
Air-Purge
Method
For installation
Refrigerant
Adjustment
5m Max.
5~10m
Refer to the detailed Air-Purge
Procedure
Unnecessary
Add 10g of refrigerant
R410A(Add as liquid state) for every 1m.
Air-Purge
Method
Purge air using a vaccum pump
For service
Refrigerant
Quantity refer to specification sheet
Add 10g of refrigerant
R410A(Add as liquid state) for every 1m.
3-2-2(i) Flare nut fixing torque
Outer diameter
ø 6.35 (Liquid Side)
ø 9.52 (Gas Side)
ø 12.7 (Gas Side)
Torque (kg-cm)
Fixing Torque Final Torque
160 200
300 350
500 550
3-12 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-17
Operating Instructions and Installation
3-2-2(j) "Pump down" Procedure
• Pump down shall be carried out when an evaporator is replaced or when the unit is relocated in another area.
1. Remove the caps from the 2-way valve and the 3-way valve.
2-Way Valve
2. Turn the 3-way valve clockwise to close and connect a pressure gauge(low pressure side) to the service valve, and open the 3-way valve again.
3-Way Valve
3. Set the unit to cool operation mode.
(Check if the compressor is operating.)
4. Turn the 2-way valve clockwise to close.
Valve Stem
(liquid)
5. When the pressure gauge indicates "0" turn the 3-way valve clockwise to close.
(gas)
2-Way Valve
3-Way Valve
Stem cap
6. Stop operation of the air conditioner.
7. Close the cap of each valve.
Relocation of the air conditioner
• Refer to this procedure when the unit is relocated.
1. Carry out the pump down procedure (refer to the details of 'pump down').
2. Remove the power cord.
3. Disconnect the assembly cable from the indoor and outdoor units.
4. Remove the flare nut connecting the indoor unit and the pipe.
At this time, cover the pipe of the indoor unit and the other pipe using a cap or vinyl plug to avoid foreign material entering.
Relocation of the air conditioner
5. Disconnect the pipe connected to the outdoor unit.
At this time, cover the valve of the outdoor unit and the other pipe using a cap or vinyl plug to avoid foreign material entering.
6. Make sure you do not bend the connection pipes in the middle and store together with the cables.
7. Move the indoor and outdoor units to a new locatioon.
8. Remove the mounting plate for the indoor unit and move it to a new location.
Samsung Electronics 3-13
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-18
M E M O
3-14 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-19
4. Disassembly and Reassembly
Stop operation of the air conditioner and remove the power cord before repairing the unit.
4-1 Indoor Unit
No
1
Parts Procedure
Front Grille 1) Stop the air conditioner operation and block the main power.
2) Separate tape of front panel upper.
Remark
3) Contract the second finger to the left, and right handle and pull to open the inlet grille.
4) Take the left and right filter out.
*Taking off the deodorizing filter.
5) Loosen one of the right fixing screw and separate the terminal cover.
6) Loosen three fixing screws of front grille.
7) Pull the upper left and right of discharge softly for the outside cover to be pulled out.
Samsung Electronics
8) Pull softly the lower part of discharge and push it up.
Caution;
Assemble the front panel and fix the hooks of left and right.
4-1
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-20
Disassembly and Reassembly
No
2
3
Parts
Ass’y Tray
Drain.
Electrical Parts
(Main PCB)
Procedure
1) Do “1”above.
2) Take all the connector of PCB upper side out.
(Inclusion Power cord)
3) Separate the outdoor unit connection wire from the terminal block.
4) If pulling the Main PCB up. It will be taken out.
1) Do “1”, “2” above.
Separate the drain hose from the extension drain hose.
2) Pull tray drain out from the back body.
4 Heat
Exchanger
1) Do “1” and “2”, “3” above.
2) Loosen two fixing earth screws of right side.
3) Separate the connection pipe.
4) Separate the holder pipe at the rear side.
5) Loosen the three fixing screws of right and left side.
6) Lifting the heat exchanger up a little to push the up side for separation from the indoor unit.
5 Fan Motor and
Cross Fan
1) Do “1”, “2”, ”3”, “4” above.
2) Loosen the fixing two screws and separate the motor holder.
3) Loosen the fixing screw of fan motor.
(By use of M3 wrench)
4) Separate the fan motor from the fan.
5) Separate the fan from the left holder bearing.
Remark
4-2 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-21
4-2 Outdoor Unit
No
1
Parts
Cabinet
Procedure
1) Turn off the unit and remove the power cable.
2) Remove the top cover.
3) Remove the control box cover.
4) Unplug the ass'y cable.
5) Remove the cabi-side.
6) Remove the cabi-front.
* When you assemble the parts, check if the each parts and electric connectors are fixed firmly.
2 Fan Motor
&
Propeller Fan
1) Do Procedure “1” above.
2) Remove the nut flange.
(Turn to the right to remove as it is a left turned screw)
3) Disassemble the propeller fan.
Remark
Samsung Electronics 4-3
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-22
M E M O
4-4 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-23
5. Troubleshooting
5-1 Items to be checked first
1) The input voltage should be rating voltage
±
10% range.
The airconditioner may not operate properly if the voltage is out of this range.
2) Is the link cable linking the indoor unit and the outdoor unit linked properly?
The indoor unit and the outdoor unit shall be linked by 3 cables.
Check the terminals if the indoor unit and outdoor unit are properly linked by the same number of cables.
Otherwise the airconditioner may not operate properly.
3) When a problem occurs due to the contents illustrated in the table below it is a symptom not related to the malfunction of the airconditioner.
NO Operation of air conditioner
1 The STD operation indication LED blinks when a power plug of the indoor unit is plugged in for the first time.
2 In a COOL operation mode, the compressor does not operate at a room temperature higher than the setting temperature that the IN DOOR FAN should operate.
Explanation
It indicates power is on. The LED stops blinking if the operation
ON/OFF button on the remote control unit is pushed.
In happens after a delay of 3 minutes when the compressor is reoperated. The same phenomenon occurs when a power is on.
As a phenomenon that the compressor is reoperated after a delay of
3 minutes, the indoor fan is adjusted automatically with reference to a temperature of the air blew.
3 Fan speed setting is not allowed in AUTO or DRY mode.
4 Compressor stops operation intermittently in DRY mode.
The speed of the indoor fan is set to LL in DRY mode.
Fan speed is 5 steps is selected automatically in AUTO mode.
Compressor operation is controlled automatically in DRY mode depending on the room temperature and humidity.
5 Timer LED only of the indoor unit lights up and the air conditioner does not operate.
Timer is being activated and the unit is in ready mode.
The unit operates normally if the timer operation is cancelled.
6 The compressor stops intermittently in a COOL mode or DRY mode, and fan speed of the indoor unit decreases.
The compressor stops intermittently or the fan speed of the indoor unit decreases to prevent inside/outside air frozen depending on the inside/outside air temperature.
4) Indoor unit observes operation condition of the air conditioner, and displays self diagnosis details on thedisplay panel.
NO Display
1 STD LED blinking (1Hz)
2 TIMER LED blinking (1Hz)
3 STD and TIMER LED blinking (1Hz)
4 BIO LED blinking (1Hz)
5 STD, BIO and TIMER LED blinking(1HZ)
6 All LED blinking(1HZ)
Self Diagnosis
Restore from power failure (input initial power)
Indoor unit Room sensor Error (open or short)
Indoor unit heat exchanger temperature sensor Error (open or short)
Indoor fan malfunctioning (for speed is Below 450rpm)
EEPROM Error
Option Error (option wasn’t setup or option data error)
Samsung Electronics 5-1
DB98_11868A(1)_1 3/3/03 11:17 AM Page 2-24
5-2 Fault Diagnosis by Symptom
5-2-1 No Power (completely dead)-Initial diagnosis
1) Checklist :
(1) Is input voltage normal?
(2) Is AC power linked correctly?
(3) Is output voltage of DC regulator IC KA78L05 (IC02) normal? (4.5VDC-5.5VDC)
2) Troubleshooting procedure
Remove power cord and plug in again in approx. 5 seconds
Replace
YES
PCB display
•Check linkage between power cord and terminal tap
•Check fuse
Is 325VDC appear in the secondary side (+, -)
NO of “BD71”
YES
NO
Is DC voltage of PCB display normal?
NO
Is rating voltage ±10% range applied to the primary side(~,~) of the “BD71”
NO
NO
Is operation lamp blinking?
YES
Does operation start when
ON/OFF button on the remote controller unit pushed?
NO
Is transmission display of the remote controller unit blinking?
YES
Is "beep"sound heard from the main unit?
YES
Is DC voltage of the PCB module normal?
YES
Are voltages of #33 (compressor), of the micom normal? 5VDC
Is voltage of #32 (indoor fan) of the micom normal?
DC5V
Replace
SMPS PARTS
NO
Is voltage at #10 terminal of the Micom normal?
0VDC
Is voltage at #9 terminal of the Micom normal?
5VDC
YES NO
YES
NO
NO
YES
Normal
Refer to remote control unit fault diagnosis
Replace PCB module.
Are voltages at RY71(Compressor) normal?
DC12V Is voltage at SS71(indoor fan)
YES
Check connections compressor and indoor fan.
NO
Replace
RY71 and SS71
Is voltage at #3 terminal of the micom normal?
Is output voltage of ICO2 normal?
YES NO
Check PCB pattern.
Replace main PCB.
Replace ICO2
10ms
YES NO
Is voltage output terminal of
PC814(PC02) normal?
NO
Are voltage at #11 and #12 of the micom normal?
YES NO
Replace resonator (X301)
YES
Is operation normal?
OK Replace PC814(pc02)
NO Replace micom
YES
250ns
OK
5-2 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 4-1
Troubleshooting
5-2-2 When the power is not applied(Outdoor unit)
(1) Is the voltage of the power normal? (The rating voltage ±10% range)
(2) Is the power line in good contact?
(3) Are the primary (CN71) and secondary (CN11) connectors of the power trans in good contact?
(4) Is the power voltage of the IC01 (KA7812) normal? (DC11.5V~DC12.5V)
2) Troubleshooting procedure
Turn off the power, and then turn on the power in five minutes.
YES
Does the power of the IC01(KA7812) match with the voltage of DC12V?
YES
Is the F701(3.15A) fuse blown?
YES
Is the secondary voltage of the trans normal?
(AC15V~AC25V)
NO
NO
NO
YES
Is the first voltage of the trans normal?
the rating voltage ±10% range
NO
YES
Is the rectifying diode(D101~D104) normal?
YES
Is the voltage at both ends of the C102 electrolytic condenser in the range of DC16~DC25V?
Is the voltage at both ends of the C104 electrolytic condenser DC12V?
NO
NO
YES
Is the IC01(KA7812) normal?
End
YES
NO
Normal operation
Replace the fuse
Replace the trans
Replace the trans
Check and replace the rectifying diode
Replace the C102 and C104.
Replace the IC01
Samsung Electronics 5-3
DB98_11868A(1)_1 3/3/03 11:17 AM Page 4-2
Troubleshooting
5-2-3 When the Indoor Unit Fan Does Not Operate. (Initial Diagnosis)
1) Checklist :
(1) Is the indoor unit fan motor properly connected with the connector (CN72)?
(2) Is the AC voltage correct?
(3) Is HALL IC in indoor fan motor properly connected with the connector (CN42)?
(4) Is the running capacitor (CR71) properly connected with PCB board?
2) Troubleshooting procedure
After unplugging out the power cord should be reconnected within five seconds.
YES
Does the STD lamp(Green) blink?
YES
NO Check as in the procedure “NO power parts”
Refer to page 5-2.
Does the Solid State Relay(SS71) work properly?
Test rod location
Normal
Voltage
+ -
SS71SS71-
YES
12V
NO
Microcomputer is out of order.
Is the supply voltage of the fan motor sufficient?
Test rod location
Normal voltage
PCB CN72 Condition pin #3 and #5 about AC 180V Fan operate
YES
NO PCB is out of order.
MF-C is out of order
PCB should be replaced.
Replace MFC
Fan motor is out of order.
Fan motor should be replaced.
5-4 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 4-3
Troubleshooting
5-2-4 When the Outdoor Unit Does Not Operate. (Initial Diagnosis)
1) Checklist :
(1) Is input voltage normal? (The rating voltage ±10% range)
(2) Is the set temperature of the remote control higher than room temperature in COOL mode?
(3) Is the POWER IN connector (terminal-tab) linked correctly?
(4) Is the outdoor unit properly connected with the TERMINAL BLOCK connector(5P)?
2) Troubleshooting procedure
(1) Checking procedures for the indoor unit.
After unplugging out the power cord should be reconnected within five seconds.
Does the operating lamp blink
YES
Does the timer lamp blink during operation ?
NO
NO
YES
Check as in the procedure "No Power parts"
Refer to page 5-2.
Room temperature sensor is out of order
@ PCB should be checked.
Is the power relay RY71 operated by adjusting the room temperature?
NO !
Test rod location
+ -
Normal
IC1 Pin No.63
IC1 Pin No.62
GND
GND
NO
RY73 ON
RY72 ON
DC 4.8V
DC 4.8V
1) Is the rating voltage ±10% range applied relay between
Terminal Tap(TB71) and RY 71 terminal No #
2) Is the rating voltage ±10% range applied relay between
Terminal Tap(TB71) andCN 71 terminal No !
YES #
YES
Microcomputer is out of order.
Power relay is out of order
PCB should be checked.
Power relay should be replaced.
A Room operation
“A”Compreessor or outdoor fan-motor replaced
! NO
@ NO
Is the room sensor normal register?
10°C
17.96k
Ω
20°C
12.09k
Ω
YES #
30°C
8.3k
Ω
B Room or C Room operating
Proceed to the checking points for the outdoor unit.
Samsung Electronics 5-5
DB98_11868A(1)_1 3/3/03 11:17 AM Page 4-4
Troubleshooting
(2) Procedures for checking the outdoor unit.
Turn off the power, and then turn on the power in 5 seconds.
YES
Does the compressor operate in 2 minutes after the relay (RY71) is activated at the indoor unit after 3 minutes?
YES
Does the photo coupler (IC02, IC03) corresponding to the indoor units (B & C) operate?
YES
NO
NO
Normal
Check and replace the relevant
IC (IC02, IC03).
Is the DC voltage applied to both ends of the C901?
(1) Is the voltage DC6V when either of the indoor units (B & C) is turned on?
(2) Is the voltage DC8V when both of the indoor units are turned on?
YES
NO
• Check and replace the resistance
(R901, R928, R931) and diode (D907, D908).
• Check and replace the electrolytic condenser (C901)
(1) Does the N01 pin output of the IC04 maintain "Low"?
(2) Does the N014 pin output of the IC04 maintain "High"?
When either of the indoor units (B & C) is turned on.
(3) Does the N014 pin output of the IC04 maintain "Low"?
When both of the indoor units (B & C) is turned on.
NO
YES
(1) Is the NO3 pin voltage of the IC04 DC5V?
(2) Is the NO12 pin voltage of the IC04 DC7V?
NO
• Check and replace the
IC04.
• Check and replace the resistance.
(R902, R903,R905, R906)
Does the No7 pin output of the IC04 maintain "Low"?
YES
NO
Is the No.5 pin voltage of the IC04 DC5V?
NO Check and replace the
R913, R915 and IC04.
Is the voltage at both ends of the C903 DC10V?
YES
NO Check and replace the
R911, D901, and C903.
Are the Q901, and 904 in "Turn-off" condition?
Are the Q902, Q903 and Q905 in "Turn-on" condition?
YES
Does the operation of the Q701 lead to activation of the compressor relay (RY71)?
YES
Replace the "B" compressor.
NO
NO
Check and replace each transistor
Check and replace the Q701 and relay.
(Resistance at both ends of the relay: About 150)
5-6 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 4-5
Troubleshooting
5-2-5 When the Outdoor Unit Does Not Operate. (Initial Diagnosis)
1) Checklist :
(1) Is input voltage normal?
(2) Is the set temperature of the remote control higher than room temperature in COOL mode?
(3) Is the POWER IN connector (CN71) linked correctly?
(4) Is the outdoor unit properly connected with the TERMINAL BLOCK connector((N1), 1)?
2) Troubleshooting procedure
After unplugging out the power cord should be reconnected within five seconds.
Does the STD lamp blink
YES
Does the timer lamp blink during operation ?
NO
#
NO
YES !
Check as in the procedure "No Power parts"
Refer to page 5-2.
Room temperature sensor is out of order
@
PCB should be checked.
Is the power relay RY71 operated by adjusting the room temperature?
NO
Test rod location
+ - Condition
Normal
Voltage
IC4 Pin No.33 GND RY71 ON DC 4.8V
NO
Microcomputer is out of order.
PCB should be checked.
Is rating voltage ±10% range applied relay between Terminal block
NO(N1) and No !
YES
Power relay is out of order
10°C
17.96k
Ω
!
YES NO
@
Is the room sensor normal register?
20°C
12.09k
Ω
YES
#
30°C
8.3k
Ω
Outdoor unit is out of order.
Power relay should be replaced.
Samsung Electronics 5-7
DB98_11868A(1)_1 3/3/03 11:17 AM Page 4-6
Troubleshooting
5-2-6 When the UP/DOWN Louver Moter Does Not Operate. (Initial Diagnosis)
1) Checklist :
(1) Is input voltage normal?
(2) Is the UP/DOWN louver motor properly connected with the connector (CN61)?
2) Troubleshooting procedure
Remove power cord and plug in again in approx. 5 seconds.
Is STD lamp blinking?
YES
Does operation start when swing button of the remote control unit pushed?
NO
Voltage at pin #58 ~ #61 of micom (ICO4) change?(Squarewave)
YES
Volatge at pin #13 ~ #16 of IC06 (ULN2003AFW) change?(Squarewave)
YES
UP/DOWN louver motor is faulty.
NO
Check as in the procedure "No Power parts".
Refer to page 5-2.
YES
Normal
NO
NO
Micom (IC04) is faulty.
Driver IC06 (ULN2003AFW) is faulty.
5-2-7 In the mode, When there is no cool air current. Check this first;
(1) Is the set temperature of Remote Control lower than room temperature in Cool mode?
(2) Is the Indoor PCB properly connected with the CN71 connector?
After training on, the Cooling operation should start in five minutes.
NO
Is the number #33 of Micom (IC04) DC 5.0 V?
YES
Is the number checking #10 of IC06 (ULN2003AFW) LOW?
YES
NO
NO
Normal
Abnormal Micom
Abnormal IC06
RY01 or Cable Check.
5-8
PCB should be replaced.
Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 4-7
Troubleshooting
5-2-8 If Operation By Remote Control Unit Is Impossible. (Initial Diagnosis)
Remove power cord and plug in again approx. 5 Seconds
Is operation lamp blinking?
YES
“ “ sound heard from the indoor unit when ON/OFF button on the remote control unit pushed?
NO
Voltage of battery less than 2.5V (Remote Control Unit)?
NO
LCD display status of REMOCON normal?
YES
Transmission display lamp ( ) blinking when
ON/OFF button on the remote control unit pushed?
YES
Voltage at PIN #30 of Remocon Micom change?
YES
Voltage at collecter of Q601 or Q602 change?
YES
NO
Check as in the procedure “NO Power parts”.
Refer to page 5-2.
YES
Normal
YES
NO
NO
NO
Replace battery.
LCD is faulty.
Replace button.
Micom is faulty.
NO
Q601(C4375Y) or Q602(C1623Y) is faulty.
IR LED(CL-1L5EU) is faulty.
NO
Voltage at pin #26 of micom (IC04) change (INDOOR UNIT)?
YES
Micom (IC04) is faulty.
Receiver module is faulty.
Samsung Electronics 5-9
DB98_11868A(1)_1 3/3/03 11:17 AM Page 4-8
Troubleshooting
5-2-9 When the SV-BY is Malfunctioning (Outdoor Unit)
1) Checklist :
(1) Is the SV1 under normal operating condition?
(2) Is the voltage of the power normal? (the rating voltage ±10% range)
(3) Is the connector (CN76) of the SV-BY in good contact?
(4) Is the resistance at both ends of the solenoid about 1.4k
Ω
?
2) Checking procedures
(1) When either of the indoor units (B & C) is turned on
Turn off the outdoor power, and then turn on the power in 5 seconds.
YES
Does the SV-BY operate when either of the indoor units is turned on?
NO
Is the voltage of DC6V applied to both ends of the C901?
YES
(1) Does the No14 pin output of the IC04 maintain "High"?
(2) Does the No1 pin output of the IC04 maintain "Low"?
YES
YES
NO
NO
Normal
• Check and replace the relevant IC (IC02, IC03).
• Check and replace the resistance (R901, R928, R931), and diode (D907, D908).
(1) Is the No12 pin voltage of the IC04 DC7V?
(2) Is the No3 pin voltage of the IC04 DC5V?
YES
NO
• Check and replace the IC04.
• Check and replace the resistance
(R902, R903, R905, R906).
Are the Q906, and Q907 in "turn-on" condition?
Is the Q908 in "turn-off" condition?
YES
Is the No8 pin output of the IC04 in "High" condition?
YES
NO
Check and replace each transistor
NO
Is the No10 pin voltage of the IC04 DC7V?
YES
NO
• Check and replace the IC04.
• Check and replace the resistance (R922, R924).
Does the operation of the Q702 lead to activation of the SV-BY relay (RY72)?
YES
Replace the SV-BY
NO Check and replace the Q702 and relay.
(Resistance at both ends of the relay: 400
Ω
)
5-10 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 5-1
Troubleshooting
(2) When all of the indoor units (B & C) are turned off
Turn off the outdoor power, and then turn on the power in 5 seconds.
YES
Is the SV1 turned off after operating for about 2 minutes when all of the indoor units (B & C) are turned off?
NO
(1) Does the No14 pin output of the IC04 maintain "High"?
(2) Does the No1 pin output of "Low"?
YES
NO
NO
Normal
(1) Is the No.12 pin voltage of the IC04 DC7V?
(2) Is the No.3 pin voltage of the IC04 DC5V?
YES
NO
• Check and replace the IC04.
• Check and replace the IC04 maintain resistance
(R902, R903,R905, R906).
Is the voltage at both ends of the C901 0V?
YES
NO
• Check and replace the
IC02-IC03.
• Check and replace the C901.
Are the Q906 and Q908 in "turn-on" condition?
Is the Q907 in "turn-off" condition?
YES
NO
Check and replace each transistor
Is the No8 pin output of the IC04 in "High" condition?
NO
Is the No10 pin voltage of the IC04 DC7V?
NO
• Check and replace the IC04.
• Check and replace the R922, and R924.
YES
Is the voltage charged to the C904 above DC7V?
YES
The "High" condition should be maintained for about 2 minutes until the voltage of about DC7V or higher is applied to the C904.
NO
Check and replace the R920 and R921.
Check and replace the C904.
Does the No8 pin output of the IC04 change from "High" to "Low"?
NO
IC04 Check and replace
YES
The output is changed from "High" to "Low" when charging to the C904 is completed.
Does the turning on and then turning off of the Q702 lead to turning off of the SV-BY relay (RY72)?
YES
Replace the SV-BY solenoid.
NO Check and replace the Q702 and relay.
(Resistance at both ends of the relay: 400
Ω
)
Samsung Electronics 5-11
DB98_11868A(1)_1 3/3/03 11:17 AM Page 5-2
Troubleshooting
5-2-10 When the SV-B is malfunctioning
1) Checklist :
(1) Is the SV-B under normal operating condition?
(2) Is the voltage of the power normal? (the rating voltage ±10% range)
(3) Is the SV-B connector (CN75) in good contact?
(4) Is the resistance at both ends of the solenoid about 1.4k
Ω
?
2) Checking procedures
Turn off the outdoor power, and then turn it on after 5 seconds
YES
Does the SVA operate when the room B among the indoor unit room B and room C is turned on?
YES
NO
NO
Does the photo-coupler (IC02) for the room B among the indoor unit room B and room C operate?
YES
NO
Is the voltage of about DC5V or above applied to both ends of the C905?
YES
Is the voltage of about DC6V or above applied to both ends of the C901?
YES
! Is the 14th pin output of the IC04 maintained at
"High" level?
@ Is the Ist pin output of the IC04 maintained at
"Low" level?
Normal operation
Check and replace the photo coupler (IC02)
• Check and replace the R929 and R930
• Check and replace the C905
NO
NO
• Check and replace the R901, R928 and D908
• Check and replace the C901
NO
! Is the voltage of the 12th pin for the IC04 about DC7V?
@ Is the voltage of the 3rd pin of the IC04 about DC5V?
NO
•Check and replace the IC04
•Check and replace the resistance(R902,
R903,R905,R906)
YES
YES
Are the Q906, Q907, and Q909 under turn on condition, and is the Q908 under "turn off" condition?
YES
NO
Check and replace the relevant transistor
Is the Q703 turned. on, indicating the operating of the SV-B relay (RY73)?
YES
Replace the SV-B solenoid valve
NO Check and replace the D905, D909, and Q703 relay
(Coil resistance at both ends of the relay:about 400
Ω
)
5-12 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 5-3
Troubleshooting
5-2-11 When the SV-C is malfunctioning
1) Checklist :
(1) Is the SV-C under normal operating condition?
(2) Is the voltage of the power normal? (the rating voltage ±10% range)
(3) Is the SV-C connector (CN74) in good contact?
(4) Is the resistance at both ends of the solenoid about 1.4k
Ω
?
2) Checking procedures
Turn off the outdoor power, and then turn it on after 5 seconds
YES
Does the SVB operate when the room C among the indoor unit room B and room C is turned on?
YES
NO
Does the photo-coupier (IC03) for the room C among the indoor unit rooms B and room C operate?
YES
NO
Normal operation
Check and replace the photo coupler(IC03)
Is the voltage of about DC5V or above applied to both ends of the C906?
YES
NO • Check and replace the R932, and R933
• Check and replace the C906
Is the voltage of about DC6V or above applied to both ends of the C901?
YES
NO • Check and replace the R901, R931, and D907
• Check and replace the C901
! Is the output of the 14th pin of the IC04 maintained a "Hight" level?
@ Is the output of the lst pin of the I04 maintained at "Low" level?
NO
! Is the voltage of the 12th pin of the IC04 about DC7V?
@ Is the voltage of the 3rd pin of the IC04 about DC5V?
YES
YES
Are the Q906, Q907 and Q909 turned on with the Q908 being turned off?
YES
NO
NO
• Check the
IC04
• Check and replace the resistance
(R902, R903,
R905, R906)
Check and replace the relevant transistor
Is the Q704 turned on, indicating the operating condition of the SV-C relay (RY74)?
YES
Replace the SV-C solenoid valve
NO Check and replace the D906, D910, and Q704 relay
(Coil resistance at both ends of the relay : about 400
Ω
)
Samsung Electronics 5-13
DB98_11868A(1)_1 3/3/03 11:17 AM Page 5-4
Troubleshooting
5-2-12 When the SV-B and SV-C are malfunctioning with all of the indoor units
(B & C) turned off
(1) Are the SVA and SVB under normal operating condition?
(2) Is the voltage of the power normal? (the rating voltage ±10% range)
(3) Are the SV-B (CN75) and SV-C (CN74) connectors in good contact?
(4) Is the resistance at both ends of the solenoid about 1.4k
Ω
?
5-14
Turn off the outdoor power, and then turn on the power in 5 seconds.
YES
Are the SVA and SVB operate turned off after operating for about 2 minutes when all of the indoor units (B & C) are turned off?
YES
NO
(1) Does the No14 pin output of the IC04 maintain "High"?
(2) Does the No1 pin output of the IC04 maintain "High"?
YES
NO
Normal
(1) Is the No12 pin voltage of the IC04 DC7V?
(2) Is the No3 pin voltage of the IC04 DC5V?
YES
Is the voltage at both ends of the C901 0V?
YES
NO
NO
• Check and replace the IC04.
• Check and replace the resistance
(R902, R904, R905 R906).
• Check and replace the IC02, and IC03.
• Check and replace the C901.
Are the Q906 and Q908 in "turn-on" condition?
Are the Q907 and Q909 in "turn-off" condition?
YES
Is the No8 pin output of the IC04 in "High" condition?
YES
NO
NO
Check and replace each transistor.
Is the No10 pin voltage of the IC04 DC7V?
YES
NO • Check and replace the IC04.
• Check and replace the R922, and R924.
The "High" condition should be maintained for about 2 minutes until a voltage of above DC7V is charged to the C904.
Do the SVA and SVB operated when the Q703, and Q704 are turned on?
NO • Check and replace the D903, D905, D906 and Q703 Q704.
• Check and replace the SVA and SVB solenoid.
YES
Is the voltage charged to the C904 above DC7V?
YES
NO • Check and replace the R920 and R921.
• Check and replace the C904.
Is the No8 pin output of the
IC04 changed from "High" to "Low"?
NO
IC04 Check and replace
YES The output is changed from "High" to "Low" when the charging to the C904 is completed.
Are the SV-B and SV-C relays (RY73, 74) turned off when the Q703 and Q704 are turned off.
YES
Replace the SV-B and SV-C solenoids.
NO
• Check and replace the Q703, and Q704.
• Check and replace the relay when necessary.
(Resistance at both ends of the relay: About 400
Ω
)
Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 5-5
5-3 PCB Inspection
5-3-1 Cautions for Part Replacement
1. The human body carries much static electricity. Before touching a part for repair, replacement or the similar purpose, be sure to touch a grounded metallic portion by hand to let the static electricity go through the metallic portion to the earth.
Especially when handling any micro computer or IC, carefully remove such static electricity before touching them.
2. When repairing any part on a work bench, be sure to place an insulative sheet on the bench and always keep the sheet surface neat without any metal fragments. If any such fragment touches a part, a secondary trouble will possibly be caused in the part.
3. Before replacing any parts, be sure to turn off the power supply. If such replacement is done with the power supply kept on, an electric shock, short circuit or destruction of a part may result.
4. During replacement or repair of a part, carefully handle it : The printed circuit board has fine lead wires (jumper wires) and glass-made parts (diode) on its substrate.
So if a circuit board is roughly handled, such lead wires and parts will be easily broken or damaged by bending or shock.
5. When soldering the lead wires of any new part, be sure to polish them using an emery paper or the like before solding them.
Since the lead wires of any new part are covered with an oxide film, solder cannot adhere to the lead wires if not polished.
6. When soldering any part, care should be exercised not to apply any high-wattage soldering iron to the part for a long time.
Some parts are of so low a heat resistance that they may be broken or have the properties changed if a soldering iron is so applied (Otherwise, the pattern may possibly be separated and raised).
7. The heat of the soldering iron should be transfered to the entire object to be soldered. If the solder pieces are not well fused due to insufficient transfer of the heat from the soldering iron, no satisfactory electrical continuity can be assured even if the soldered objects appear well connected to each other.
8. The solder used should be limited to a minimum. If excessive solder is used, it will cause inter-pattern contact, which may cause malfunction of the circuit.
5-3-2 Procedure
The parts should be replaced in the following procedure.
Check for any faulty part.
Detach the faulty part.
Replace it with a new part.
Check the operation of the new part.
The repair is completed.
Samsung Electronics 5-15
DB98_11868A(1)_1 3/3/03 11:17 AM Page 5-6
Troubleshooting
5-3-3 Detailed Procedure
No.
1
2
3
Malfunction
Pull out the power plug from the AC terminal and confirm the fuse on the PCB assembly
Checking point (symptoms)
1. Is the broken(open)?
Turn the power on.
Set the TURBO mode
Voltage check
1. AC voltage at BD71(~,~)?
: rating voltage ± 10% range
2. DC voltage at BD71(+,-)?
: about 325[v] ± 10%
3. DC voltage at IC02
: IN-GND ➔ DC12[v]
: OUT-GND ➔ DC5[v]
4. Voltage waveform at Q201
: collector-GND ➔ squarewave
Voltage check
1. check voltage of IC06
(pin#10,pin#8)
: relay on ➔ 0.7[v]
: relay off ➔ 12[v]
2. Voltage at terminal block
((N1) -1) ➔ rating voltage
Voltage over
Causes
Indoor unit fan motor short-circuit
SMPS circuit is faulty
SMPS circuit is faulty
PC02, R202-R205
SMPS circuit is faulty
IC06 is faulty
RY71 is faulty
5-16 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 5-7
5-4 Fault Diagnosis of Major Parts
Parts
Temp.Sensor
Heat ex. Sensor
Indoor Fan Motor
Diagnosis
Measure resistance with a tester.
Normal 8K
Ω
~27K
Ω at ambient temperature (+0°C ~ +30°C)
Abnormal
∞
, O
Ω
… open or short
Measure resistance between terminals (CN72) with a tester
Normal At ambient temperature (10°C ~ 30°C) between
Red, Yellow
Red, Blue
Resistance
190±10 Ω
170±10
Ω
Outdoor Fan Motor
Abnormal
∞
, O
Ω
… open or short
Measure the voltage between ground and signal wire of the fan motor
Normal between
Gray, Orange
Yellow, Orange
Voltage
0.5V~4.5V
5V
Abnormal
Normal
Abnormal if voltage does not change from 0V to 5V.
At ambient temperature (10°C ~ 30°C) between
Red, Blue
Red, White
Resistance
100±10
Ω
130±10
Ω
Stepping Motor
(UP/DOWN swing motor)
Abnormal
∞
, O
Ω
… open or short
Measure resistance between red wire and each terminal.
Abnormal ∞ , O Ω … open or short
Samsung Electronics 5-17
DB98_11868A(1)_1 3/3/03 11:17 AM Page 5-8
5-5 Set up the Model option
The Method for Setting up the model option with remocon
• It is necessary to set up option code after replacing the main-PCB as a service parts.
Make sure that you can set up the option of code the remote controller after you replace the main PBA otherwise, the unit won’t be working properly and all LED lamps on display will be flickering.
Step 1 : Preparing the remocon to main PCB option set
1 st Remove the battery from the remocon.
2 nd Press the temperature raise/down button simultaneously and insert the battery again.
3 rd Make sure the remocon display shown as .
Step 2 : Second stage preparation of the remocon option set.
❈ Note ; In case the wrong letter has been selected, continue to press the button until the correct letter appears.
1 st
2 nd
3 rd
If the first stage number “ ” appears on the display, proceed to the second stage.
Every time the
!
and
& button, “ ” and “ ” each continue to appear.
Whenever pressing the @ , # , $ , % , ^ , * , ( , ) , 1 , 2 button, the number increase from
0~9(0123456789) and A, b, C, d, E, F each time.
! If the first number is , it is correct otherwise press appear.
@ When pressing the select one of them.
button ~ until appear on the display,
# When pressing the select one of them.
$ When pressing the select one of them.
% When pressing the select one of them.
button button button
~
~
~ appear on the display, appear on the display, appear on the display,
^ When pressing the select one of them.
button ~ appear on the display,
5-18 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 5-9
Troubleshooting
! If the first number is , it is correct otherwise press appear.
@ When pressing the select one of them.
# When pressing the select one of them.
$ When pressing the select one of them.
% When pressing the select one of them.
^ When pressing the select one of them.
button button button button button
~
~
~
~
~ until appear on the display, appear on the display, appear on the display, appear on the display, appear on the display,
Step 3 : Reconfirming option set after completion
(in case of ex. 020000-170351)
After pressing
After pressing selector for the mode, the display shown as selector for the mode, the display shown as .
.
Step 4 : Pressing the ON/OFF button ( )
When pressing the operation ON/OFF key with the direction of remote controller for unit, the sound “Ding” or “Diriring” is heard and the first LED lamp on the left side is flickering at the same time, then the input of option is completed. (If the diriring sound isn’t heard, try again pressing the ON/OFF button.)
Step 5 : Unit operation test-run
First, Remove the battery from the remote controller.
Second, Re-insert the battery into the remote controller.
Third, Press ON/OFF key with the direction of remote controller for set.
• Error Mode
1 st If all lamps of indoor unit are flickering, Plug out and plug in again and pressing ON/OFF key to retry.
2 nd If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is set up for it’s model.
Samsung Electronics 5-19
DB98_11868A(1)_1 3/3/03 11:17 AM Page 5-10
Troubleshooting
<Table of the option code>
MODEL
MC26AC2-07
MC26AC2-12
OPTION CODE
020000-1000D9
020000-100340
5-20 Samsung Electronics
DB98_11868A(1)_1 3/3/03 11:17 AM Page 5-11
M E M O
Samsung Electronics 5-21
DB98_11868A(1)_2 3/3/03 11:21 AM Page 1-2
6. Exploded Views and Parts List
6-1 Indoor Unit
20-1
20-5
20-3
20-4
20
20-6
20-6-1
20-2
16
19
14
13
15
10
13-1
11
13-2
13-3
13-4
17 18
12
8
22
24
21
9
6
5
7
23
4
3
25
2
1
6-1
You can search for the updated part code number through the ITSELF.
URL : http://itself.sec.samsung.co.kr
Samsung Electronics
DB98_11868A(1)_2 3/3/03 11:21 AM Page 2-1
Exploded Views and Parts List
■ Parts List
No.
CODE NO Description
24
25
DB93-00927A
DB39-00147A
DB94-00056G
DB94-00104A
DB61-00165A
DB39-00146A
DB39-00147A
DB70-00036A
DB94-00058L
DB94-00062E
DB66-00127A
DB66-00128A
DB66-00128B
DB63-00082A
DB95-20138A
DB31-10129A
DB64-00354A
DB63-00064A
DB95-00287G
DB63-00067A
DB92-00248A
DB67-00051A
DB67-00032A
DB63-00083A
DB94-00040F
DB60-20011A
DB31-00033A
DB32-00020A
DB93-01223C
DB93-01018A
DB65-00078A
DB65-10074E
DB93-00859A
DB61-40251A
DB67-60030A
DB96-01123K
DB96-01441A
DB94-40003A
DB93-00251K
20
20-1
20-2
20-3
20-4
20-5
20-6
20-6-1
20-7
21
22
23
16
17
18
19
13-4
13-5
14
15
13
13-1
13-2
13-3
9
10
11
12
7
8
5
6
3
4
1
2
GRILLE-AIR INLET
GUARD-AIR FILTER
ASS´Y-CLEANER FILTER
COVERTER-TEMINAL
ASSY PANEL-FRONT
SPACER-EVAP LOW
SPACER-EVAP UP
COVER U-BEND
ASSY-CROSS FAN
BOLT-SPECIAL
MOTOR-FAN-IN
THERMISTOR-WIRE ASSY
ASSY CONTROL IN
ASSY PCB MAIN
TERMINAL BLOCK
CLAMP-CABLE
ASSY DISPLAY-SWITCH PCB
CONNECT WIRE-PCB
ASSY BACK BODY
ASSY-HOLDER MOTOR
HOLDER-PIPE
CONNECT WIRE-DISPLAY
CONNECT WIRE-PCB
PLATE-HANGER
ASSY TRAY DRAIN
ASSY DRAIN-HOSE
BLADE-H
BLADE-V,A
BLADE-V,B
SCREEN-SAFETY WIRE
ASSY-MOTOR STEPPING
MOTOR-STEPPING
ASSY DISPLAY
HOLDER-SENSOR
SPRING-SENSOR
ASSY EVAP-UNIT(EVAPORATOR ASSY)
ASSY CYCLE IN(EVAPORATOR ASSY)
RUBBER BEARING
ASSY REMOCON
Samsung Electronics
MC26AC2-12
1
1
6
1
1
3
1
1
1
1
1
1
1
1
1
1
1
-
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
Q’TY
MC26AC2-07
1
1
6
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
-
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
Remark
6-2
DB98_11868A(1)_2 3/3/03 11:21 AM Page 2-2
6-2 Outdoor Unit
6
1
3
10
4
5
7
13(13-1~13-6)
12
18
11
19(19-1~19-7)
14
15
16(16-1)
8
2
9(9-1~9-2)
17(17-1~17-4)
6-3 Samsung Electronics
DB98_11868A(1)_2 3/3/03 11:21 AM Page 2-3
Exploded Views and Parts List
■ Parts List
No.
CODE NO Description Specification
13-6 DB35-00015V
14
15
DB62-01416A
DB62-01417A
16 DB96-02103A
16-1 DB95-00403A
17 DB99-00282A
17-1 DB62-01414A
17-2 DB62-01415A
17-3 DB96-02113A
17-4 DB96-02114A
17-4-1 DB95-00403B
17-4-2 DB95-00403C
18 DB32-10018E
19 DB93-01623A
19-1 2301-001379
19-2 2501-001237
19-3 DB26-10063C
19-4 DB61-00585A
19-5 DB61-00584B
19-6 DB65-40072C
19-7 PE-M3000-02
1
2
3
4
5
DB90-01006A
DB90-20207A
DB67-00140A
DB31-00103A
DB90-00967A
6
7
8
DB63-30027C
DB94-50041E
DB90-10574E
9 DB90-40120B
9-1 DB63-10434B
ASSY CABI FRONT
ASSY BASE OUT
FAN PROPELLER
MOTOR FAN
ASSY BKT MOTOR
ASS'Y
ASS'Y
AS+G/F20%,D460
OSM-606SRC
ASS'Y
GUARD COND
ASSY PARTITION
ASSY CABI SIDE
SC-90073T
ASS'Y
ASS'Y
ASSY COVER ASS'Y
COVER PP
9-2 DB63-10433B
10
11
DB90-00569A
DB96-02273A
COVER CONTROL
ASSY CABI UPPER
ASSY COND
12 DB63-30110J SCREEN GUARD
13 G8C124JU1EL ROTARY COMPRESSOR
13-1 DB60-30018A
13-2 DB60-30028A
13-3 DB63-10165D
13-4 DB63-20002A
13-5 DB73-00067A
NUT FLANGE
NUT WASHER
COVER TERMINAL
GASKET
GROMMET ISOLATOR
PP
ASS'Y
ASS'Y
P.E.H 100%
G8C124JU1EL
PI0.8,M5
HEX,2C,M8
PBT,2.5
EPDM,T0.8
NR 40°
OLP
TUBE DISCHARGE A
TUBE DISCHARGE B
ASSY TUBE BY PASS
ASSY SOLENOIDE COIL
ASSY VALVE
TUBE SUCTION A
TUBE SUCTION B
ASSY TUBE CAPI A
ASSY TUBE CAPI B
ASSY SOLENOIDE COIL
ASSY SOLENOIDE COIL
THERMISTOR OUT
ASSY CONTROL OUT
C-OIL
C-OIL
TRANS POWER
CASE PCB
CASE CONTROL OUT
TERMINAL BLOCK
ASSY PCB PARTS
RAC12128-9622
ASS'Y
ASS'Y
ASS'Y
ASS'Y
ASS'Y
ASS'Y
ASS'Y
ASS'Y
ASS'Y
ASS'Y
ASS'Y
103AT
ASS'Y
4uF,450V
35uF,450V
DC17,AC230,400mA
ABS
SGCC-M,T0.8
ASS'Y
ASS'Y
Samsung Electronics
Q’TY
MC26AC2X
Remark
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
2
6
2
2
6
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
6-4
DB98_11868A(1)_2 3/3/03 11:21 AM Page 2-4
6-3 ASS’Y Remote Control : DB93-00251K
3
7
4
1
2
■ Parts List
No
5
6
7
3
4
1
2
Description
INLAY LCD
CASE TOP
LCD
KEY RUBBER
ASS'Y PCB REMOCON
CASE LOW
BATTERY COVER
5
Q’TY
1
1
1
1
1
1
1
6
Remark
6-5 Samsung Electronics
DB98_11868A(1)_2 3/3/03 11:21 AM Page 2-5
6-4 ASS’Y Control In : DB93-01223C
■ Parts List
No
9
10
7
8
11
5
6
3
4
1
2
Description
HOLDER CONTROL
ASSY MAIN PCB
TERMINAL BLOCK ASSY
ASS'Y DISPLAY PCB
CONNECTOR WIRE PCB U/D
HOLDER CLAMP IN
SEAL CONTROL SIDE
SEAL H/CONTROL FRONT
SCREW MACHINE
CABLE CLAMP
SCREW TAPPING
Samsung Electronics
Specification
DB61-00160A
DB93-01018A
DB65-00078A
DB93-00927A
DB39-00147A
DB61-00219A
DB72-10191T
DB72-00127V
6001-000929
DB65-10074E
6002-000234
Remark
6-6
DB98_11868A(1)_2 3/3/03 11:21 AM Page 2-6
M E M O
6-7 Samsung Electronics
DB98_11868A(1)_2 3/3/03 11:21 AM Page 2-7
7. Block Diagrams
7-1 Refrigerating Cycle Block Diagram
INDOOR UNIT OUTDOOR UNIT
Samsung Electronics 7-1
DB98_11868A(1)_2 3/3/03 11:21 AM Page 2-8
8. PCB Diagrams
8-1 ASS’Y MAIN PCB : DB93-01018A
■ TOP PATTERN
8-1 Samsung Electronics
DB98_11868A(1)_2 3/3/03 11:21 AM Page 2-9
PCB Diagrams
■ Parts List
Description
PCB-MAIN
IC-MCU
IC DRIVE
EEPROM
PHOTO COUPLER
TR SMALL SIGNAL
TR SMALL SIGNAL
TR DIGITAL
DIODE BRIDGE
ZENER
ZENER
SSR
TR SWITCH
IC VOLT REGULATOR
IC
PHOTO COUPLER
FR-DIODE
T.V.S
VARISTOR
RESONATOR CERAM IC
SW TRANS
FILTER NOISE
COIL
RELAY POWER
BUZZER
HOLDER FUSE
FUSE
FUSE
CONNECTOR HEADER
CONNECTOR HEADER
CONNECTOR HEADER
CONNECTOR HEADER
CONNECTOR HEADER
CONNECTOR HEADER
C-FILM
C-AL
C-AL
C-AL
C-ELEC
C-CERAMIC
C-CHIP
C-CHIP
C-CHIP
R-CHIP
R-CHIP
R-CHIP
R-CHIP
R-CHIP
R-CHIP
R-CHIP
R-CHIP
R-CHIP
R-CHIP
R-CHIP
RELAY-MINIATURE
45
46
47
42
43
44
48
49
50
51
52
53
54
55
No
28
29
30
31
23
24
25
26
27
20
21
22
16
17
18
19
13
14
15
9
10
11
12
6
7
4
5
8
1
2
3
35
36
37
38
32
33
34
39
40
41
Specification
120x93
KS88C4632
ULN2003AFW
93LC56B-I/SN
TLP181
MMST2907A
2SC2412K
DTA114EKA
DF06S
BZX84-C11
BZX84-C3V6
G3MB202PL
TNY255P
KA78L05
KA7533Z
PC814
UG2B
ST02D-200
INR14D561K-BS
10MHZ
JT1916
HP1-P10 / NFP-1010
5mH/50mA
UKH-12S
CBE2220BA
FB58
250V, 3.15A
250V, 1A
YW396-05AV WHT
YW396-05AV BLU
SMW200-10 WHT
SMW200-5PWHT
SMW300-3P WHT
SMW200-4P WHT
1.2µF, 450V
SD 1000µF, 25
47µF, 50V
470µF, 16V
SD 6.8µF/450V
SDE 2G 222M
CS2012Y5V104Z500NR
CS2012Y5V103Z500NR
CS2012X7R102K500NR
MCR18EZHJ224
MCR18EZHJ104
MCR10EZHF6801
MCR10EZHJ103
MCR10EZHJ682
MCR10EZHJ472
MCR10EZHJ102
MCR10EZHJ561
MCR10EZHJ471
MCR10EZHJ331
MCR10EZHJ221
F3AA012E
Location No.
L101
RY71
BZ61
F701
F701
F702
CN72
CN71
CN91
PC02
D101
CD11
VA71
X301
ST11
FT71
BD71
ZD12
ZD11
SS71
IC01
IC02
IC03
IC04
IC05, IC06
IC51
PC01
Q603
Q201, Q401, Q601, Q602
Q901, Q902
CN61
CN42
CN41
CR71
C104
C601
C107
C101, C109
C103
C102, C105, C106, C108, C201, C202, C301, C402,
C403, C501, C502, C503, C504, C901
C203, C204, C401
C404
R102, R103, R104
R202, R203, R204, R205
R404, R406
R206, R501, R502, R503, R602, R609, R610, R902
R402
R108, R603, R901
R201, R207, R208, R301, R401, R403, R408, R601,
R607, R608
R606
R105, R604, R605
R405, R407
R106, R107
RY72, RY73
Samsung Electronics 8-2
DB98_11868A(1)_2 3/3/03 11:22 AM Page 2-10
PCB Diagrams
■ BOTTOM PATTERN
8-3 Samsung Electronics
DB98_11868A(1)_2 3/3/03 11:22 AM Page 2-11
8-2 PCB OUTDOOR UNIT : PE-M3000-02
Samsung Electronics 8-4
DB98_11868A(1)_2 3/3/03 11:22 AM Page 2-12
PCB Diagrams
■ Parts List
No.
Description
CN77
CN78
PC31~PC33
X501
C105
C103
C101
VA71~75
DS71
FT71
IC01
IC02
F701
F701
TB71
OPJ2
CN70
RY71
IC04
RY72~74, 77, 78
IC01
IC01
-
J01-J09
OP01
C304~306
C501~505, C201, C301~303,
C401, C404, C102, C403
D101~D104
R510~513, 403
R304-306, R403
R301~R303
R201
R401
R402
R701~R704,R701~R706
PCB BOARD
Q301~303
IC03
IC05
CN11
CN41
CN71
CN72
CN73
CN74
JUMP-WIRE
JUMP-WIRE
C-CERAMIC
C-CERAMIC
C-CERAMIC
DIODE-RECT
R-CARBON
R-CARBON
R-CARBON
R-CARBON
R-CARBON
R-CARBON
R-CARBON
PCB-MAIN
TR
RESET IC
IC-DRIVE
CON-HEAD
CON-HEAD
CONNECTOR-WAFE
CONNECTOR-WAFE
CONNECTOR-WAFE
CONNECTOR-WAFE
CONNECTOR-WAFE
CONNECTOR-WAFE
PHOTO-COUPLER
CERAMIC-RESONATOR
C-ELEC
C-ELEC
C-ELEC
VARISTOR
DISCHARGE
NOISE-FILTER
PIN-HOUSING
POWER-RELAY
IC-MCU
RELAY
HEAT-SINK
SCREW-TAPPING
IV-VOLT REGU
IC-VOLT REGU
FUSE
FUSE-HOLDER
TERMINAL TAP
JUMP-WIRE
8-5
Specification
PI 0.6 SN T 52MM
PI 0.6 SN T 52MM
50V 103Z
50V 104Z
50V 104Z
1N4007
RD 1/8 T 10K-J
RD 1/8 T 10K-J
RD 1/8 T 10K-J
RD 1/8 T 1K-J
RD 1/8 T 330-J
RD 1/8 T 6.8K-F
RS 2 T 51K-J
FR-1 197*330
KSR1002
KA7533Z
KID650003AP
SMW250-03 RED
SMW250-02 WHT
YW396-03AV WHT
YW396-03AV BLU
YW396-03AV YEL
YW396-03AV RED
YW396-05AV WHT
YW396-05AV BLU
PC814A
10.0MHZ
25V 470µF
25V 2200µF
35V 1000µF
14D 471
DSA362MA
HP1-P16
YDW236-01
DI1U(12V)
MB89635PSH-XXXX
JQ1A-12V
25MM
PH 3 L6 AB FEFZY
KA7812
KA7805
AC250V 3.15A 20MM
FH51H 7.5A
YTR-250
PI0.6SM T52MM
Q’TY
9
1
3
13
4
11
Remark
1
1
1
1
1
1
1
1
1
3
1
6
1
1
1
1
1
3
1
5
1
1
1
1
1
1
1
-
1
1
1
1
1
1
1
5
Samsung Electronics
DB98_11868A(1)_2 3/3/03 11:22 AM Page 2-13
8-3 ASS’Y DISPLAY PCB : DB93-00927A
7
8
5
6
9
10
3
4
1
2
■ Parts List
No Descrption
PCB-DISPLAY
MODULE REMOCON
TACT SWITCH
C-CERAMIC
C-CERAMIC
DIODE SWITCHING
R-CARBON
JUMP
CONNECTOR WAFER
CONNECTOR WIRE
Location No.
RM01
SW01
C01
C02
D01
R01, R02, R03
J01
CN02
CN01
Specification
64.5x53
KSM-713TH5
KPT-1105A
102K
104Z
IN4148
470 1/2W 5%
10mm
SMAW200-05
UL1007, AWG#26
Q’TY
3
2
1
1
1
1
1
1
1
1
Remark
8-4 ASS’Y CENTER DISPLAY : DB93-00859A
Samsung Electronics 8-6
DB98_11868A(1)_2 3/3/03 11:22 AM Page 2-14
M E M O
8-7 Samsung Electronics
DB98_11868A(1)_2 3/3/03 11:22 AM Page 2-15
9. Wiring Diagrams
9-1 Indoor Unit
Samsung Electronics 9-1
DB98_11868A(1)_2 3/3/03 11:22 AM Page 2-16
9-2 Outdoor Unit
9-2 Samsung Electronics
DB98_11868A(1)_2 3/3/03 11:22 AM Page 2-17
10. Schematic Diagrams
10-1 Indoor Unit
Samsung Electronics 10-1
DB98_11868A(1)_2 3/3/03 11:22 AM Page 2-18
Application date
UPDATE LOG SHEET
Page Part# Note(Cause & Solution) S/Bulletin#
Use this page to keep any special servicing information. (Service Bulletin, etc.)
If only parts number changes, Just change parts number directly on parts list.
And if you need more information, please see the service website.
Itself Solution
Integrated technology supporting electronic library http://itself.sec.samsung.co.kr
Copyright © 2002
By Samsung Electronics Co., Ltd.
All rights reserved.
This manual may not, in whole or in part, be copied, photocopied, reproduced, translated, or converted to any electronic or machine readable from without prior written permission of
Samsung Electronics Co., Ltd.
Printed in Korea.
DB98_11868A(1)_cover 3/3/03 11:16 AM Page 2
ELECTRONICS
© Samsung Electronics Co., Ltd. Mar. 2003.
Printed in Korea.
Code No. DB98-11868A(1)
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project