256819-YTG-C-0506
DESCRIPTION
The new deluxe Affinity fan coil line offers the ultimate in
comfort, sound and application flexibility. The Affinity line of
fan coils utilize a whisper quiet variable speed motor that provides humidity control and the lowest operating cost in the
industry. The air handler is shipped ready to be installed in all
positions, upflow, downflow, horizontal left or right will, with
minor adjustments. No special kits are required to install this
deluxe product in any position. This top of the line product
was designed with the installer and homeowner in mind, easy
to install and quiet, efficient and unsurpassed comfort for the
end user.
TECHNICAL GUIDE
SINGLE PIECE VARIABLE SPEED
AIR HANDLERS
FOR USE WITH SPLIT-SYSTEM
COOLING & HEAT PUMPS
HEAT PUMP MODELS: AVY24 THRU 60 AND SVY48 THRU 60
All UPG air handlers and coils utilize a TXV to provide our
customers with the optimum performance and refrigerant
control required for 13+ systems. Air handlers can be ordered
with a R22 TXV factory installed that can be easily converted
to R410A by changing the bolt-on TXV. Air handlers are also
available with “Flex-coils” without a factory installed metering
device. For added flexibility a R22 or R410A TXV can be field
installed to meet your refrigerant choice.
FEATURES
Thermal Expansion Valve - Provides the ultimate refrigerant
control required for today’s high efficient product. The UPG
bolt-on TXV provides the added flexibility to convert the air
handler to the required refrigerant. The UPG TXV is a true
bolt-on which does not require brazing to replace or install.
MicroBlueTM Coated Fins - All air handler coils are treated
with the MicroBlueTM hydrophilic coating to enhance the
removal of condensate during the refrigeration cycle and
reduce the possibility of water blow-off. The MicroBlueTM
coating also reduces the growth of germ causing microbes
for a healthier home environment.
Insulated Cabinet - All air handler cabinets are thermally
insulated with 1” foil faced insulation (R-4.2) to prevent
sweating. For applications in extreme humidity conditions an
optional, field installed, external insulating wrap kit is also
available.
Durable Finish Inside and Out - Air handler casings are
made of pre-painted galvanized steel which provides a better
paint to steel bond that resists corrosion and rust creep. All
internal coil sheet metal parts are made of G90 pre-painted
steel i.e. triangular plates, top plates, horizontal supports etc.
Coil header plates are not painted due to the brazing process
during production. The coil header plates are treated after the
brazing process with a corrosion resistant spray to reduce the
probability of rust.
New 4 HK Heat Kit - Installation friendly, easy service, more
robust, unique to new design.
ISO 9001
Certified Quality
Management System
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at www.york.com
Additional rating information can be found at
www.ari.org/aridirectory.
ECM Variable Speed Motor - Designed for efficient, quiet
operation with added indoor comfort control. With the use of a
humidistat the motor will monitor the humidity in the home
and automatically keep the desired humidity level in both winter and summer seasons. The ECM motor utilizes only 24%
of the energy used by standard blower motors which will
reduce your overall heating and cooling costs.
ClimaTrak - Installers can set an operating cycle for the ECM
motor that works best in a particular climate. Homeowners
benefit from an operating cycle that maximizes their indoor
comfort level regardless of whether they live in a dry, temperate, or humid climate.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
256819-YTG-C-0506
DIMENSIONS
F
10-3/8”
J
K
TOP OUTLET
DIMENSIONS
CIRCUIT
BREAKER
PANEL
18-9/32”
BLOWER
COMPARTMENT
E
BOTTOM INLET
DIMENSIONS
A
DRAIN CONNECTIONS
FOR UPFLOW AND
DOWNFLOW APPLICATIONS
D
REFRIGERANT
CONNECTIONS
7-11/32”
1-1/2”
C
B
FILTER
ACCESS
DRAIN PAN CONNECTIONS
FOR HORIZONTAL APPLICATIONS
Dimensions
MODELS
A
B
C
Height
Width
Depth
AVY24B**H21
46
17.5
AVY36C**H21
52
21
AVY48D**H21
57
24.5
SVY48D**N21
52
24.5
AVY60D**H21
57
24.5
SVY60D**N21
52
24.5
D
22
(w/o cladding)
23
(with cladding)
Refrigerant
Connections
Line Size
Wiring Knockouts1
Dimensions (Inches)
E
J
K
Power
Control
F
Liquid
Vapor
12-3/8
13-29/32
14-19/32
3/4”
17-1/8
17-13/32
18-3/32
7/8”
22-1/8
20-29/32
17-1/8
20-29/32
22-1/8
20-29/32
7/8” (1/2”)
7/8” (1/2”)
1 3/8” (1”)
21-19/32
1 23/32” (1 1/4”)
21-19/32
17-1/8
20-29/32
21-19/32
21-19/32
3/8”
7/8”
7/8”
7/8’
7/8”
1. Actual size (Conduit size).
COIL TECHNICAL DATA
Model
Application
Refrig.
Face Area
Conn. Types (Sq. Ft.)
Rows
Deep
Fin
Per In.
AVY24B3XH21
3.89
2
14
AVY24B2AH21
3.89
2
14
AVY36C3XH21
4.86
3
12
AVY36C2AH21
4.86
3
12
AVY48D3XH21
5.83
3
11
5.83
3
11
5.83
3
11
SVY48D2CN21
5.83
3
11
AVY60D3XH21
5.83
3
11
AVY60D2CH2
5.83
3
11
SVY60D3XN21
5.83
3
11
SVY60D2CN21
5.83
3
11
AVY48D2CH21
SVY48D3XN21
Cooling /
Heat Pump
Sweat
Coil Size
Tube
Geometry
Tube
Dia.
Fin
Type
None
(2) 16 x 17.5
2A
None
(2) 20 x 17.5
2A
None
(2) 24 x 17.5
1 x 0.866
(2) 24 x 17.5
(2) 24 x 17.5
(2) 24 x 17.5
TXV
3/8
Enhanced
2C
None
2C
None
2C
None
2C
Note: H models are available with a factory installed horizontal drain pan.
2
Unitary Products Group
256819-YTG-C-0506
COOLING CAPACITY
Model Coil
Rated CFM
Entering Air °F
(Dry / Wet Bulb)
MBH@ Evaporator Temperature and Corresponding Pressure °F / PSIG
35 / 61.5
40 / 68.5
45 / 76.0
50 / 84.0
25.2
22.9
18.0
13.8
33.8
25.8
23.9
19.0
72.0
55.0
40.7
40.7
82.0
62.6
46.2
46.2
21.9
19.8
15.1
10.8
29.8
21.9
17.8
17.8
56.8
42.1
34.0
34.0
62.2
45.8
37.0
37.0
FULL-CASED “A” TYPE MULTI-POSITION
AVY24B2AH21
800
AVY36C2AH21
1200
AVY48D2CH21
SVY48D2CN21
1600
AVY60D2CH21
SVY60D2CN21
1850
85/72
80/67
75/62
70/57
85/72
80/67
75/62
70/57
85/72
80/67
75/62
70/57
85/72
80/67
75/62
70/57
31.1
28.6
23.5
19.1
41.6
33.3
26.0
22.3
100.5
80.4
62.7
53.9
119.9
96.0
74.8
64.3
28.3
25.9
20.8
16.5
37.8
29.4
21.9
20.6
86.4
67.5
49.9
47.2
101.0
79.2
58.6
55.4
Cooling Air Flow Data
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM
AVY24B**H21
CFM
High
1010
816
933
706
926
594
706
505
524
448
519
447
AVY36C**H21
CFM
Low
662
534
620
460
615
393
459
380
373
380
378
380
AVY48D**H21, SVY48D**N21
CFM
High
Low
2020
1333
1759
1194
1989
1307
1607
1079
1790
1209
1502
1038
1439
1000
1306
951
1368
973
1218
885
1246
902
1090
834
High
1230
1007
1202
903
1076
965
814
714
868
646
799
604
JUMPER SETTINGS
Low
873
810
811
640
736
688
599
552
626
520
588
523
AVY60D**H21, SVY60D**N21
CFM
High
Low
2166
1354
1970
1242
2134
1343
1769
1082
1895
1184
1826
1167
1526
978
1654
1037
1596
1025
1434
928
1397
934
1283
861
COOL Tap
A
B
A
B
A
C
B
D
C
D
C
D
ADJ Tap*
B
B
A
A
C
B
C
B
A
A
C
C
JUMPER SETTINGS
COOL Tap
A
B
A
B
A
C
B
D
C
D
C
D
ADJ Tap*
B
B
A
A
C
B
C
B
A
A
C
C
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to
0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c.
external static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air
cleaners. Consult the instructions for the electronic air cleaner for further details.
* The ADJ “D” tap should not be used.
Unitary Products Group
3
256819-YTG-C-0506
Heating Air Flow Data
HIGH / LOW HEAT CFM
24B Air Handler
36C Air Handler
CFM
CFM
High
933
JUMPER SETTINGS
CFM
CFM
Low
High
Low
HEAT Tap
ADJ Tap
681
1202
724
A
A
706
607
903
657
B
A
524
523
868
593
C
A
389
646
520
D
A
448
48D Air Handler
CFM
60D Air Handler
CFM
CFM
JUMPER SETTINGS
CFM
High
Low
High
Low
HEAT Tap
ADJ Tap
1942
1318
2134
1212
A
A
1607
1142
1769
1021
B
A
1358
927
1596
713
C
A
1305
673
1434
522
D
A
All CFM’s are shown at 0.5” w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0” to
0.6” w.c. static pressure. From 0.6” to 1.0” static pressure, CFM is reduced by 2% per 0.1” increase in static. Operation on duct systems with greater than 1.0” w.c.
external static pressure is not recommended.
NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower than what is required to operate an airflow switch on certain models of electronic air
cleaners. Consult the instructions for the electronic air cleaner for further details.
* The ADJ “D” tap should not be used.
APPLICATION FACTORS - Related CFM VS. Actual CFM
% Of Rated Airflow
80%
90%
Rated CFM
110%
120%
Capacity Factor
0.96
0.98
1.00
1.02
1.03
Physical and Electrical Data - Cooling Only (60 Hz)
Models
Blower - Diameter x Width
HP
Motor
Nominal RPM
Voltage
Amps
Full Load (230)
Type
Size
Filter1
Permanent Type Kit
Shipping / Operating Weight (lbs.)
AVY24B**H21
AVY36C**H21
10 x 7
1/3
1200
10 x 7
1/2
1200
2.8
16 x 20 x1
1PF0601BK
140/134
AVY48D**H21
SVY48D**N21
10 x 10
3/4
1200
AVY60D**H21
SVY60D**N21
10 x 10
1
1200
230
4.3
5.5
DISPOSABLE OR PERMANENT
20 x 20 x1
22 x 20 x1
1PF0602BK
1PF0603BK
170/164
196/185
7.0
22 x 20 x1
1PF0603BK
199/188
1. Field supplied.
Electrical Data - Cooling Only (60 Hz)
Models
AVY24B**H21
AVY36C**H21
AVY48D**H21
SVY48D**N21
AVY60D**H21
SVY60D**N21
Total Motor Amps
60 Hertz
208V
230V
3.2
2.8
4.7
4.3
6.1
5.0
6.1
5.0
7.8
7.0
7.8
7.0
Minimum Circuit Ampacity
60 Hertz
208V
230V
4.0
3.5
5.9
5.4
7.6
6.9
7.6
6.9
9.7
8.8
9.7
8.8
Max. O.C.P.
Amps/Type1
Minimum Wire
Size A.W.G.
15
15
15
15
15
15
14
14
14
14
14
14
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
4
Unitary Products Group
256819-YTG-C-0506
Electrical Data - 1 Ø - 208/230-1-60
Models
AVY24B**H21
AVY36C**H21
AVY48D**H21
SVY48D**N21
AVY60D**H21
SVY60D**N21
Heat Kits*
Max.
Static
Min.
Speed Tap
4HK*6500206
4HK*6500506
4HK*6500806
4HK*6501006
4HK165N1506
4HK*6500506
4HK*6500806
4HK*6501006
4HK16501506
4HK16501806
4HK*6500506
4HK*6500806
4HK*6501006
4HK16501506
4HK16501806
4HK16502006
4HK16502506
4HK*6500506
4HK*6500806
4HK*6501006
4HK16501506
4HK16501806
4HK16502006
4HK16502506
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Heat-D
Total Heat1
KW
MBH
208v 240v 208v 240v
1.9
2.5
6.4
8.5
3.6
4.8
12.3
16.4
5.6
7.5
19.2
25.6
7.2
9.6
24.6
32.8
10.8
14.4
36.9
49.1
3.6
4.8
12.3
16.4
5.6
7.5
19.2
25.6
7.2
9.6
24.6
32.8
10.8
14.4
36.9
49.1
13.2
17.6
45.1
60.1
3.6
4.8
12.3
16.4
5.6
7.5
19.2
25.6
7.2
9.6
24.6
32.8
10.8
14.4
36.9
49.1
13.2
17.6
45.1
60.1
14.4
19.2
49.2
65.5
18.0
24.0
61.5
81.9
3.6
4.8
12.3
16.4
5.6
7.5
19.2
25.6
7.2
9.6
24.6
32.8
10.8
14.4
36.9
49.1
13.2
17.6
45.1
60.1
14.4
19.2
49.2
65.5
18.0
24.0
61.5
81.9
kW Staging
W1 Only
208v 240v
1.9
2.5
3.6
4.8
2.8
3.75
3.6
4.8
3.6
4.8
3.6
4.8
2.8
3.75
3.6
4.8
3.6
4.8
3.3
4.4
3.6
4.8
2.8
3.75
3.6
4.8
3.6
4.8
3.3
4.4
3.6
4.8
3.6
4.8
3.6
4.8
2.8
3.75
3.6
4.8
3.6
4.8
3.3
4.4
3.6
4.8
3.6
4.8
W2 Only
208v 240v
1.9
2.5
3.6
4.8
5.6
7.5
7.2
9.6
7.2
9.6
3.6
4.8
5.6
7.5
7.2
9.6
7.2
9.6
6.6
8.8
3.6
4.8
5.6
7.5
7.2
9.6
7.2
9.6
6.6
8.8
7.2
9.6
10.8
14.4
3.6
4.8
5.6
7.5
7.2
9.6
7.2
9.6
6.6
8.8
7.2
9.6
10.8
14.4
W1 & W2
208v 240v
1.9
2.5
3.6
4.8
5.6
7.5
7.2
9.6
10.8
14.4
3.6
4.8
5.6
7.5
7.2
9.6
10.8
14.4
13.2
17.6
3.6
4.8
5.6
7.5
7.2
9.6
10.8
14.4
13.2
17.6
14.4
19.2
18.0
24
3.6
4.8
5.6
7.5
7.2
9.6
10.8
14.4
13.2
17.6
14.4
19.2
18.0
24
1. See conversion Table 10.
* May be 0 (no breaker) or 1 (with breaker).
KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
FOR
Unitary Products Group
208V
230V
220V
OPERATION MULTIPLY
240V
240V
240V
TABULATED KW & MBH BY
.751
.918
.840
5
256819-YTG-C-0506
Electrical Data - (For Single Source Power Supply) - Copper Wire 1 Ø - 208/230-1-60
Models
AVY24B**H21
AVY36C**H21
AVY48D**H21
SVY48D**N21
AVY60D**H21
SVY60D**N21
Heater
Amps
240V
Heat Kit Single Phase*
Field Wiring
Min. Circuit Ampacity
Max. O.C.P. Amps/Type1
75°C Wire Size - AWG
208V
240V
208V
240V
208V
240V
4HK*6500206
10.4
15.28
16.53
20
20
12
12
4HK*6500506
20.0
25.67
28.50
30
30
10
10
4HK*6500806
31.3
37.85
42.63
45
45
8
8
4HK*6501006
40.0
47.33
53.50
50
60
8
6
4HK165N1506
60.0
69.00
78.50
70
90
4
3
4HK*6500506
20.0
27.54
30.38
30
35
10
10
4HK*6500806
31.3
39.73
44.50
45
45
8
8
4HK*6501006
40.0
49.21
55.38
50
60
8
6
4HK16501506
60.0
70.88
80.38
70
90
4
3
4HK16501806
73.3
85.32
97.00
90
100
4
3
4HK*6500506
20.0
29.29
31.88
35
35
8
8
4HK*6500806
31.3
41.48
46.00
45
50
8
8
4HK*6501006
40.0
50.96
56.88
60
60
6
6
4HK16501506
60.0
72.63
81.88
90
90
3
3
4HK16501806
73.3
87.07
98.50
90
100
3
2
4HK16502006
80.0
94.29
106.88
100
125
3
1
4HK16502506
100.0
115.96
131.88
125
150
1
1/0
4HK*6500506
20.0
31.42
33.75
35
35
8
8
4HK*6500806
31.3
43.60
47.88
45
50
8
8
4HK*6501006
40.0
53.08
58.75
60
60
6
6
4HK16501506
60.0
74.75
83.75
90
90
3
3
4HK16501806
73.3
89.19
100.38
90
110
3
2
4HK16502006
80.0
96.42
108.75
100
125
3
1
4HK16502506
100.0
118.08
133.75
125
150
1
1/0
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
* May be 0 (no breaker) or 1 (with breaker).
Electrical Data - (For Multi-Source Power Supply) - Copper Wire 1 Ø - 208/230-1-60
Max. O.C.P. Amps/Type1
Min. Circuit Ampacity
Models
AVY24B**H21
AVY36C**H21
AVY48D**H21
SVY48D**N21
AVY60D**H21
SVY60D**N21
Circuit
Heater
Model
1st
4HK165N1506
4HK16501506
75°C Wire Size - AWG
Circuit
1st
2nd
Circuit
2nd
3rd
3rd
1st
2nd
3rd
208/240
208/240
208/240
47.5 / 53.5
21.7 / 25.0
—
50 / 60
25 / 25
—
8/6
10 / 10
—
48.5 / 55.4
21.7 / 25.0
—
50 / 60
25 / 25
—
8/6
10 / 10
—
4HK16501806
44.9 / 51.2
39.8 / 45.8
—
45 / 60
40 / 50
—
8/8
8/8
—
4HK16501506
51.0 / 56.9
21.7 / 25.0
—
60 / 60
25 / 25
—
6/6
10 / 10
—
4HK16501806
47.4 / 52.7
39.8 / 45.8
—
50 / 60
40 / 60
—
6/6
8/6
—
4HK16502006
51.0 / 56.9
43.4 / 50.0
—
60 / 60
45 / 50
—
6/6
8/8
—
4HK16502506
51.0 / 56.9
43.4 / 50.0
21.7 / 25.0
60 / 60
45 / 50
25 / 25
6/6
8/8
10 / 10
4HK16501506
53.1 / 58.8
21.7 / 25.0
—
60 / 60
25 / 25
—
6/6
10 / 10
—
4HK16501806
49.5 / 54.6
39.8 / 45.8
—
50 / 60
40 / 60
—
6/6
8/6
—
4HK16502006
53.1 / 58.8
43.4 / 50.0
—
60 / 60
45 / 50
—
6/6
8/8
—
4HK16502506
53.1 / 58.8
43.4 / 50.0
21.7 / 25.0
60 / 60
45 / 50
25 / 25
6/6
8/8
10 / 10
208/240 208/240 208/240 208/240 208/240 208/240
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
6
Unitary Products Group
256819-YTG-C-0506
ACCESSORIES
LIMITATIONS
Refer to Price Manual for specific model numbers.
TXV Kits - TXV kits are available for “Flex-coil” applications
and converting R22 to R410A or as a service replacement.
All kits are bolt-on and require no brazing to install.
Non-Combustible Bases - A combustible floor base accessory is available, if required by local codes, when the air handler is installed, in the down flow position, on a combustible
material.
Electric Heaters - 4HK models shown under electrical data
include sequential operation and temperature dual limit
switches for safe, efficient operation. Circuit breakers are provided where shown.
External Insulating Wrap Kit - Provides a vinyl covered
thermal insulation wrap, providing additional thermal insulation protection to prevent sweating in applications where
extreme high humidity is present. Air Handler cover (or wrap)
has Velcro edges for easy installation and access.
These units must be wired and installed in accordance with all
national and local safety codes.
Voltage limits are as follows:
1
Air Handler Voltage
Voltage code
Normal Operating
Voltage Range
208/230-1-60
06
187-253
220/240-1-50
93
198-264
1. Rated in accordance with ARI Standard 110, utilization range “A”.
Airflow must be within the minimum and maximum limits approved for
electric heat, evaporator coils and outdoor units.
Entering Air Temperature Limits
Wet Bulb Temp.°F
Dry Bulb Temp. °F
Min.
Max.
Min.
Max.
57
72
65
95
COOLING MODELS WITH ELECTRIC HEAT WIRING
Air Handler Control Wiring
Typical A/C - Cooling only Applications
THERMOSTAT
AIR HANDLER
BOARD
1 - STAGE
AIR CONDITIONING
Air Handler Control Wiring
Typical A/C with Electric Heat Applications
THERMOSTAT
AIR HANDLER
BOARD
R
R
R
R
G
G
G
G
Y
Y / Y2
Y
Y / Y2
W1
Y1
W2
W2
C
W1
Y
Y
Y1
HUMIDISTAT *
O
W2
W2
W1
W1
C
O
HUM
HUM
X/L
X/L
COM
1 - STAGE
AIR CONDITIONING
C
COM
HUMIDISTAT *
C
* Optional dehumidification humidistat switch contacts open on humidity rise.
NOTES:
1. “Y/Y2” Terminal on air handler control board must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.
2. Remove humidistat jumper on air handler control board.
3. For heat pump applications - set MODE jumper on air handler control board to the HP position.
4. To change quantity of heat during HP defrost cycle - reverse connections at W1 and W2 on air handler control board.
Unitary Products Group
7
TWO-STAGE COOLING WIRING
CONTROL WIRING - Air Handler & New UPG HP Systems
Two Stage H/P with York Guard VI Board & Copeland “Ultra Tech”
Conventional Application - Not Hot Heat Pump
AIR HANDLER
BOARD
2 - STAGE SCROLL
HEAT PUMP
R
R
R
G
G
THERMOSTAT
Y2
Y2
Y / Y2
Y1
E
Y2 OUT
Y1
Y1
W2
W2 OUT
W1
W1 OUT
W
O
W
O
O
HUMIDISTAT *
HUM
BS
X/L
X/L
X/L
C
COM
C
* Optional dehumidification humidistat switch contacts open on humidity rise.
NOTES:
1. “Y/Y2” Terminal on air handler control board must be connected for full CFM and applications requiring 60 second blower off delay for SEER enhancement.
2. Remove humidistat jumper on air handler control board.
3. For heat pump applications - set MODE jumper on air handler control board to the HP position.
4. To change quantity of heat during HP defrost cycle - reverse connections at W1 and W2 on air handler control board.
TYPICAL APPLICATIONS
HORIZONTAL RIGHT
UPFLOW
DOWNFLOW
HORIZONTAL LEFT
Subject to change without notice. Printed in U.S.A.
Copyright © by York International Corp. 2006. All rights reserved.
Unitary
Products
Group
256819-YTG-C-0506
Supersedes: 256819-YTG-B-0506
5005
York
Drive
Norman
OK
73069