I-2533 Quick Start 1. Introduction

I-2533 Quick Start  1.  Introduction
I-2533 Quick Start
1. Introduction
This quick start helps users to apply the I-2533 in users’ applications
quickly. If users need the details of I-2533, please refer to the I-2533 user
manual. Users can free download it from the web site as follows or get it
from product CD (path: CAN/Converter/I-2533).
http://www.icpdas.com/products/Remote_IO/can_bus/i-2533.htm
2. Hardware Installation
Before using I-2533, some things must be done.
1. Prepare one pair of I-2533.
2. Set the CAN baud rate of each I-2533 by using rotary switch. You
can refer to the following table for details. (If you set the rotary
switch to “A”, please use utility tool to do the configuration before.)
Switch Value
F0 1 2
6
E
7 8 9A
BC D
Rotary switch for
CAN baud rate
Description
0
Set baud rate to 10 kbps
1
Set baud rate to 20 kbps
2
Set baud rate to 50 kbps
3
Set baud rate to 80 kbps
4
Set baud rate to 100 kbps
5
Set baud rate to 125 kbps
6
Set baud rate to 250 kbps
7
Set baud rate to 500 kbps
8
Set baud rate to 800 kbps
9
Set baud rate to 1 Mbps
A
Set baud rate to user-defined baud rate
which is configured by I-2533 utility.
B~D
Not-available
E
Update firmware
F
Set I-2533 into configuration mode.
I-2533 Quick Start (ver. 1.1, 2013/05/31) -----1
345
3. Check the application structure, and determine if the terminator
resistor is needed or not. You can find it at the position as follows.
F0 1 2
6
E
7 8 9A
BC D
On
(Enable)
(Default)
345
DIP switch for
terminator resistor
OFF
(Disable)
Generally, if your application is as follows, we recommend you to
enable the terminator resistor.
Device 1
Device 2
...
...
Device N-1
Device N
120Ω
120Ω
CAN_H
Fiber
CAN_L
I-2533
I-2533
If your application is like the structure as follows, the terminator
resistor is not needed.
120Ω
120Ω
CAN_H
CAN_L
Device 1
Device 2
...
I-2533
Device N
Fiber
Device 2
...
I-2533
Device N
CAN_H
CAN_L
I-2533 Quick Start (ver. 1.1, 2013/05/31) -----2
120Ω
120Ω
Device 1
4. Connect the fiber port of these I-2533, CAN port, power line and
frame ground. The pin assignment and wire connection are as
follows. When finished, run your application with these I-2533.
Pin No.
TxD
RxD
1
2
3
4
5
6
7
8
Description
Fiber TxD port
Fiber RxD port
TxD pin of the RS-232 port for configuration
RxD pin of the RS-232 port for configuration
GND pin of the RS-232 port for configuration
Non-available
Non-available
CAN_L pin of CAN bus
CAN_H pin of CAN bus
CAN_GND pin of CAN bus
Fiber Port
Tx
Tx
Rx
Rx
+10VDC ~ +30VDC
CAN_GND
CAN_GND
Power GND
CAN_H
CAN_H
Power GND
CAN_L
CAN_L
Earth
Earth
CAN Port
(ISO 11898-2)
Power Port
F.G.
Interconnecting
Metallic Board
(F.G.)
F.G.
I-2533 Quick Start (ver. 1.1, 2013/05/31) -----3
+10VDC ~ +30VDC
3. Utility Tool
When users want to use user-defined baud rate or set the message
filter, I-2533 utility tool may be needed. It can be free downloaded from the
following web site or get it in the product CD (path: CAN/Converter/I-2533
/Software):
http://www.icpdas.com/products/Remote_IO/can_bus/i-2533.htm
After getting the utility tool, please follow the following steps to set the
baud rate and message filter.
67
BCD
01
EF 2
8 9A
Step0: Power off the I-2533. Set the rotary switch to “F”, and connect the
PC available COM port with the COM port of the I-2533. Users can
find the communication cable in the product box. When connecting
to the COM port of I-2533, the TxD pin of the cable is connected to
the TXD pin of the COM port, RXD pin of the cable is connected to
the RXD pin of the COM port, and GND pin of the cable is
connected to the GND pin of the COM port. Then, power on the I2533.
COM
TXD
TXD
RXD
RXD
GND
GND
34 5
N/A
N/A
CAN_L
CAN_H
CAN_GND
Step1: Execute the I2533_Utility.exe, the dialog of the I-2533 Utility will be
poped up. Select the PC COM port which is connected with the
COM port of the I-2533. Then, click “Connect” button.
I-2533 Quick Start (ver. 1.1, 2013/05/31) -----4
Step2: Users can set the baud rate on the “User-defined Baud Rate” field.
Here, fill “250000” for 250 kbps. Then, set the filter by using the
“from” field, “to” field, and “Add” button. For example, If users want
to pass the CAN message with ID 0x4 and 0x5 in the CAN 2.0A
specification. Fill the value “4” in the “from” field of CAN 2.0A, and
the value “5” in the “to” field of CAN 2.0A.
Step3: Click “Add” button to add this configuration. The configuration is
shown on the “Pass List” field. If the “Pass List” is not empty, only
the messages matched with the “Pass List” will be passed. If the
“Pass List” filed is empty, it means all-pass. If users want to pass
the message with ID 0x0 in the CAN 2.0A specification, fill the
value “0” in both of “from” and “to” field and click “Add” button.
I-2533 Quick Start (ver. 1.1, 2013/05/31) -----5
Step4:.The method of configuring the message filter of the CAN 2.0B
messages is similar with the configuration steps of the message
filter of the CAN 2.0A messages. After finishing all of the
configurations, click “Save all configuration” to store the
configuration in the I-2533.
Step5: When the procedure is successful, the following message will be
shown.
Step6. After finishing the configuration, set the rotary switch value to “0” ~
“A” and reboot the I-2533. The CAN message filter will be applied
automatically in the value “0” ~ “A” of the rotary switch. The CAN
baud rate set by utility is only appled when the rotary switch is set
to “A”.
I-2533 Quick Start (ver. 1.1, 2013/05/31) -----6