Autronica | AutroFlame X33AF | Autronica Fire and Security AS

Autronica Fire and Security AS ■ ID:
1 1
Autronica Fire and Security AS
 A leading innovator,
pp
manufacturer and supplier
of fire & gas detection
equipment
 Founded in 1957 in
Trondheim, Norway
 “Protecting life, environment
and property”
Autronica Fire and Security AS ■ ID:
2
Fire & Gas Detection Challenges
 Building Fire Detection System

95% of Critical Faults caused by electronics faults,
faults human mistakes
mistakes, or manual testing
Autronica Fire and Security AS ■ ID:
3
AutroSafe – Automatic Addressing
 Each detector has a unique ID,
and therefore automatic addressing
 When powering up, the system will
automatically find all units’ “IDs”,
register
and “remember”...
 and simultaneously register
each detectors place in the
loop
 Built-in Short Circuit Isolators
 100% Operational with Wiring Fault
 Specific Location of Fault Provided
Autronica Fire and Security AS ■ ID:
ID
IDENTITETSKORT
Multi
SENSOR
Sensor
MULTI
14 05 17
NRR <123 004 567 8<
246
DES 00
1
001199828000346
7
2
004199828001125
008199827600125
3
006199828001025
KNUS GLASSET
TRYKKBREAK
HER
PRESS
HERE
GLASS
4
BN- 35
BRANNALARM
Tilpasningsenhet
FIRE ALARM
007199828000725
Interface unit
6
Nr.
No
No.
5
001199828000025
008199827600126
4
AutroSafe SelfVerify®
Power supply
All L
Loop U
Units
it
Automatically Tested
Every 24 Hours
SVcontrol
CommunicationC
i i
interface
Smoke detector
Fault warning
Fault signal
ALARM!
SelfVerify®
stimulator
Fire Alarm
Fire Alarm Signal
STOP!
Operating
p
g
Detection
chamber
AlarmAl
signal
Test smoke
Autronica Fire and Security AS ■ ID:
5
Fire & Gas Detection Challenges
 Building Fire Detection System

95% of Critical Faults caused by electronics faults,
faults human mistakes
mistakes, or manual testing
 Communication Failures – Flame & Gas Detectors



Between Engineering & Procurement
Between Engineering & Maintenance/Operations
Recognizing Need for Revising Procedures
Autronica Fire and Security AS ■ ID:
6
AutroFlame X33AF – Technology

Multispectrum IR



Maximum False Alarm Rejection
Solar Resistance
Single Detector for Multiple Fuels

Automatic Optical Integrity (OI) Test


Autronica Fire and Security AS ■ ID:
Built-in lamps test all sensors every 60
seconds
No external test lamp required
7
X33AF – Cone of Vision

Autronica Fire and Security AS ■ ID:
N t All Fl
Not
Flame D
Detectors
t t
“S
“See”” E
Equally
ll

Coverage Areas are different for each
model & manufacturer

Smaller coverage areas lead to a
higher quantity of detectors required
8
AutroPoint HC200 – Technology

A diffusion-based, infrared combustible gas detector
(point-IR) that provides continuous, fixed monitoring
of flammable hydrocarbon gases from 0 to 100%
Lower Explosive Limit (LEL)

Methane (default)
(default), ethane
ethane, propane,
propane butane
butane, ethylene
and propylene (100 flammable Hydrocarbon vapours)

Calibration Not Required!

21 Years MTBF
Autronica Fire and Security AS ■ ID:
9
AutroPath HC-600 Open Path Gas Detector
Autronica Fire and Security AS ■ ID:

5 – 120 meter Separation

Redundant Xenon IR lamps

Same detector model (spares) for
entire range of separation distance
10
Acoustic Gas Leak Detector
•Stainless Steel
•4-20mA w/ HART
• SIL-2
SIL 2 R
Rated
t d
• Range of 12-20m (at 58dB)
• Analyzes 24 discrete ultrasonic frequency bands
• Data Logging w/ Removable Storage
Autronica Fire and Security AS ■ ID:
11
AutroTox Gas Detectors

Local Display with Relay, Alarm, and Fault
Outputs Combined with isolated 4-20mA
4 20mA

4-20 mA output with HART

Nonintrusive Calibration

Fully Explosion-Proof Housing

316SS or coated aluminum

Easy-to-Set
Easy
to Set Alarm Levels

Access to Alarm and Fault History

Multiple Conduit Access Points
Autronica Fire and Security AS ■ ID:












H2S 0-20 pp
ppm
H2S 0-50 ppm
H2S 0-100 ppm
CL2 0-10 ppm
NH3 0-100 ppm
NH3 0-500 ppm
H2 0-1000 ppm
O2 0-25% by Vol
CO 0-100 ppm
CO 0-500 ppm
SO2 0-20
0 20 ppm
SO2 0-100 ppm
12
Fire & Gas Detection Challenges
 Building Fire Detection System

95% of Critical Faults caused by electronics faults,
faults human mistakes
mistakes, or manual testing
 Communication Failures – Flame & Gas Detectors



Between Engineering & Procurement
Between Engineering & Maintenance/Operations
Recognizing Need for Revising Procedures
 Industry Misconceptions

SIL
Autronica Fire and Security AS ■ ID:
13
What is SIL?
 Safety Integrity Level (SIL) is a measure of safety for a given
protective function.
 Specifically, the extent to which the end user can expect the
protective function to perform, and in the case of a failure, fail
in a safe manner
manner.
 This protective function is known as the Safety Instrumented
Function (SIF).
(SIF)
 A Safety Instrumented System (SIS) is a collection of
components (field devices and logic solver) that execute one or
more SIFs.
Autronica Fire and Security AS ■ ID:
14 14
SIL Misconceptions
 SIL Applies to Individual Devices
 Connecting “SIL
SIL Devices”
Devices Creates a SIL Approved System
 Redundancy is Required to Meet a SIL Rating
Autronica Fire and Security AS ■ ID:
15 15
Misconception: - SIL Applies to Individual Devices

IEC-61508 states that a SIL number applies to a complete function (SIF), i.e.
the field sensor, the logic solver and the final element. It is therefore incorrect
to refer to any individual item or equipment having a safety integrity level.

An individual component can be certified for use in a particular SIL application
application,
but such a certificate constitutes only part of the verification effort, since the
target SIL must be verified for the complete SIF.
SIF
Detector
Autronica Fire and Security AS ■ ID:
Loop driver
module
d l
F&G alarm
panell
Output
16
Misconception: – SIL Requires Redundancy
 SIL ratings do not require redundancy.
 SIL Ensures that a safety related system adequately performs the
required safety functions under all stated conditions within a defined
period of time.
 SIL assesses th
the risk
i k reduction
d ti required
i d ffor a ttolerable
l bl llevell off risk.
i k
 Redundancy
y is used to raise the availabilityy of unreliable equipment.
q p
 How likely is it that the function in question will perform its
assigned
i
d task
t k when
h needed?
d d?
Autronica Fire and Security AS ■ ID:
17 17
Autronica – The Only Fire Detection System
SIL 2 Approved by TUV

Autronica is safe and reliable. SelfVerify function tests field devices and
reports
p
system
y
as if newly
y installed every
y day.
y

Autronica AutroSafe system’s SIF & SIS have been tested and approved
byy third party
p y TUV - World leader in SIL assessment.
AutroSafe SIF SIL 2 Approved from Input to Output
Sensor
Autronica Fire and Security AS ■ ID:
Loop driver
module
F&G alarm
panel
Output
18 18
Fire & Gas Detection Challenges
 Building Fire Detection System

95% of Critical Faults caused by electronics faults,
faults human mistakes
mistakes, or manual testing
 Communication Failures – Flame & Gas Detectors



Between Engineering & Procurement
Between Engineering & Maintenance/Operations
Recognizing Need for Revising Procedures
 Industry Misconceptions

SIL
 Compliance with Different Worldwide Regulations
Autronica Fire and Security AS ■ ID:
19
Autronica – Always a Safe Choice
 Designed and approved according to international standards
g
and regulations
 ISO 9001
Approval Certificates Available for Download
 EX certification
 IEC61508 SIL 2
NAN
Autronica Fire and Security AS ■ ID:
YANG
20
Fire & Gas Detection Challenges
 Building Fire Detection System

95% of Critical Faults caused by electronics faults,
faults human mistakes
mistakes, or manual testing
 Communication Failures – Flame & Gas Detectors



Between Engineering & Procurement
Between Engineering & Maintenance/Operations
Recognizing Need for Revising Procedures
 Industry Misconceptions

SIL
 Compliance with Different Worldwide Regulations
 Communicating with PLC/DCS/ICSS/SIS/insert-your-own-initialism
PLC/DCS/ICSS/SIS/insert your own initialism
Autronica Fire and Security AS ■ ID:
21
AutroSafe – Communication
Safety PLC
Modbus RTU, Modbus TCP, and OPC
{or AutroCom}
AutroSafe – BS-420 / BC-420 panels
A t S f panels
AutroSafe
l h
have iintegrated
t
t d Modbus
M db converters
t
Autronica Fire and Security AS ■ ID:
22
AutroCom - direct link to DCS vendors





ABB AC400
ABB AC800 (SIL2)
Siemens S7
Kongsberg (SIL2)
Emerson Delta V
The Serial Port on the Multifunction Connection List can be used for one of these communication
types:

Serial – VDR

Serial – ESPA
Serial - MODBUS Master


Serial - MODBUS Slave

Serial - Autrocom:

SERIAL

SERIAL SLIDING WINDOW
SERIAL SLIDING WINDOW HIGH INTEGRITY
INTEGRITY*

(For example for SIL2 connections)
Two TCP/IP ports on the main board (BSA-400) in different subnet, can be connected to switches with
multiple ports, and can be used for up to six of these communication types:

TCP - MODBUS Master

TCP - MODBUS Slave

TCP - Autrocom:

TCP/IP

TCP/IP HIGH INTEGRITY*
(For example for SIL2 connections)

Autronica Fire and Security AS ■ ID:
TCP – Web server with Secure LogOn and Automatically shutdown. For uploading and
downloading software, logs, etc.
23
Truly Redundant Communication Architecture
Safety PLC/DCS
BS-420
BS 420
Autronica Fire and Security AS ■ ID:
24
AutroSafe IFG – Architecture Overview
Autronica Fire and Security AS ■ ID:
25
Thank You for Your Time
Are There Any
Autronica Fire and Security AS ■ ID:
Questions
26 26