Model:
PURY-P240TSKMU-A
(Consists of One PURY-P120TKMU-A, One PURY-P120TKMU-E and One CMY-R100XLCBK Twinning Kit)
Job Name:
Location:
Engineer Name:
Contractor:
System No.:
Date:
OUTDOOR VRF HEAT RECOVERY SYSTEM FEATURES
• 3-phase, 208/230V
• Modular variable refrigerant flow (VRF) systems;
smaller capacity units can be piped together to form a
single, large-capacity two-pipe system
• Required Twinning Kit allows for easy field piping connection
• Selectable fan static, 0.12 or 0.24"WG external static
pressure; factory set to 0"WG
• Connects to CITY MULTI indoor units; controlled via
CITY MULTI Controls Network (CMCN)
• External finish: Pre-coated Galvanized-steel Sheets
• Operating Temperature Range
Cooling (Outdoor): 23° ~ 115°F (-5° ~ +46°C) DB
Heating (Outdoor): -4° ~ +60°F (-20° ~ +16°C) WB
Specifications
Unit Type
PURY-P120TKMU-A
□ Twinning Kit*.…………………………………...….CMY-R100XLCBK
□ Branch Joint (T-Branch: ≤ 72,000 Btu/h).…………CMY-Y102SS-G2
□ Branch Joint (T-Branch: 73,000-144,000 Btu/h).………CMY-Y102LS-G2
□ Branch Joint (T-Branch: 145,000-234,000 Btu/h).………CMY-Y202S-G2
□ Joint Adapter (Port Connector > 54,000 Btu/h).………….CMY-R160C-J
□ Main BC Controller.…CMB-P108/1010/1013/1016NU-GA/1016NU-HA
□ Sub BC Controller.………………….CMB-P104/108NU-GB/1016NU-HB
* Twinning Kit is necessary to combine the refrigerant flows of the
modules and is sold separately.
System
PURY-P216TSKMU-A
Nominal Cooling Capacity
Nominal Heating Capacity
Btu/h
Btu/h
External Dimensions (H x W x D)
In. / mm
Refer to Module Data
Net Weight
Lbs. / kg
Electrical Power Requirements
Voltage, Phase, Hertz
1,430 / 648
Refer to Module Data**
Cooling Power Input
kW
Heating Power Input
Cooling Current (208/230V)
Heating Current (208/230V)
Minimum Circuit Ampacity
(MCA)**
kW
R.L.A.
R.L.A.
PURY-P120TKMU-A
OPTIONAL PARTS
240,000
270,000
Module 1
PURY-P120TKMU-A
Module 2
PURY-P120TKMU-A
120,000
120,000
135,000
135,000
65 x 68-29/32 x 29-5/23 /
65 x 68-29/32 x 29-5/23 /
1,650 x 1,750 x 740
1,650 x 1,750 x 740
715 / 324
715 / 324
208 / 230V, 3-phase, 60Hz
21.11
Refer to System Data
22.73
65.1 / 58.8
70.1 / 63.3
Refer to System Data
A
Refer to Module Data**
A
Refer to Module Data**
50**
50**
Maximum Overcurrent Protection** A
Refer to Module Data**
74 / 68**
74 / 68**
Maximum Breaker Size**
45 / 42**
45 / 42**
Piping Diameter
From Twinning Kit to Indoor Units
(Brazed) (In. / mm)
From Modules to Twinning Kit
(Brazed) (In. / mm)
Indoor Unit
Liquid (High Pressure)
Gas (Low Pressure)
Liquid (High Pressure)
Gas (Low Pressure)
Total Capacity
Model / Quantity
Refer to System Data
1-1/8 / 28.58
1-3/8 / 34.93
Refer to Module Data
50 to 150% of ODUs
P06 ~ P96 / 2 to 50
(Max. No. Connectable
Branches: 48)
63.0
3/4 / 19.05
1-1/8 / 28.58
3/4 / 19.05
1-1/8 / 28.58
Refer to System Data
Sound Pressure Levels
dB(A)
60.0
60.0
Fan
Type x Quantity
Propeller Fan x 2
Propeller Fan x 2
Refer to Module Data
Airflow Rate
CFM
11,300
11,300
Direct-drive Inverter Motor Output kW
0.92 + 0.92
0.92 + 0.92
Compressor Operating Range
7 to 100%
Refer to System Data
Compressor Type x Quantity
Inverter-driven Scroll Hermetic x 1 Inverter-driven Scroll Hermetic x 1
Refer to Module Data
Compressor Motor Output
kW
8.2
8.2
Compressor Crankcase Heater
kW
Refrigerant
R410A
Refer to Module Data
Lubricant
MEL32
High-pressure Protection Device
601 psi / 4.15 MPa
601 psi / 4.15 MPa
Refer to Module Data Overheat Protection / Thermal Switch Overheat Protection / Thermal Switch
Compressor / Fan Protection Device
Inverter Protection Device
Overheat / Overcurrent Protection Overheat / Overcurrent Protection
Blue Fin Anti-corrosion Protection: Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants;
≥1μm thick; Salt Spray Test Method - no unusual rust development to 480 hours.
** Each individual module requires a separate electrical connection. Reference electrical data for each individual module.
Left view
a
b
1650(64-31/32)
d
PURY-P240TSKMU-A(-BS) PURY-P264TSKMU-A(-BS) PURY-P288TSKMU-A(-BS)
PURY-P120TKMU-A(-BS) PURY-P144TKMU-A(-BS) PURY-P144TKMU-A(-BS)
PURY-P120TKMU-A(-BS) PURY-P120TKMU-A(-BS) PURY-P144TKMU-A(-BS)
CMY-R100XLCBK
ø28.58(1-1/8)
ø34.93(1-3/8)
Intake
air
Twinning Kit
~Outdoor unit
c
f
Component
P120
P120
unit model
High pressure c ø19.05(3/4) e ø19.05(3/4) c
Low pressure d
- (Note 5) f ø28.58(1-1/8) d
P240
Front view
30(1-3/16)
Unit model
Twinning pipe(Low pressure)
<optional parts>
Outdoor unit 1
1750(68-29/32)
P264
P120
P288
P144
Intake
air
ø22.2(7/8) e ø22.2(7/8)
- (Note 5) f ø28.58(1-1/8)
P144
a
To BC controller
Twinning pipe(High pressure)
<optional parts>
b
To BC controller
ø22.2(7/8) e ø19.05(3/4) c
- (Note 5) f ø28.58(1-1/8) d
P144
e
Outdoor unit 2
1750(68-29/32)
PURY-P240,264,288TSKMU-A(-BS)
Note 1.Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2.Twinning pipe (High pressure) should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3.The pipe section before the Twinning pipe (section "a" in the figure) must have at least 500mm(19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4.Only use the Twinning pipe by Mitsubishi (optional parts).
5.Connect the outdoor unit 1 with the Twinning pipe (Low pressure) (section "d" in the figure).
Component unit name
Package unit name
Outdoor unit 1
Outdoor unit 2
Outdoor Twinning Kit(optional parts)
High pressure
BC controller~Twinning pipe Low pressure
Twinning pipe connection size
Intake
air
Discharge air
740(29-5/32)
Module :
PURY-P240TSKMU-A – DIMENSIONS
Unit : mm(in.)
57
(2-1/4)
Left side view
20
20
(13/16) (13/16)
586(23-3/32)
Discharge air
57
(2-1/4)
262
Service panel
Intake
air
Control box
19.5
(25/32)
Refrigerant service valve
<Low pressure>
Refrigerant service valve
<High pressure>
2X7-ø4.6(3/16) Hole
(Make hole at the plastic fan guard
for snow hood attachment)
<Snow hood attachment hole>
(10-11/32)
Intake
air
54(2-5/32)
(23-5/8)
(2-25/32) =(5-29/32)X4
70
600=150X4
(8-9/16) 217
(5-23/32) 145
2
4
7
5
3
Front view
1
75(2-31/32)
58(2-5/16)
140(5-17/32)
8
Top view
795(31-5/16)
(Mounting pitch)
Refrigerant service valve
<Low pressure>
Bottom view
795(31-5/16)
(Mounting pitch)
Refrigerant service valve
<High pressure>
6
561(22-3/32)
590(23-1/4)
516(20-11/32)
49(1-15/16)
831(32-23/32)
1750(68-29/32)
150(5-29/32)
83
(3-9/32)
831(32-23/32)
526(20-23/32)
541(21-5/16)
562(22-5/32)
80
(3-5/32)
196 (7-23/32)
146 (5-3/4)
121 (4-25/32)
77
(3-1/16)
89
(3-17/32)
145
(5-23/32)
84
(3-5/16)
2X3-14(9/16)X20(13/16) Oval hole
80
(3-5/32)
ø25.4
(1)
ø25.4
(1)
ø28.58 Brazed
(1-1/8) *1
ø28.58 Brazed
(1-1/8) *1
ø19.05 Brazed
(3/4) *2
ø22.2 Brazed
(7/8) *2
ø28.58
(1-1/8)
ø28.58
(1-1/8)
Low
pressure
Service valve
High
pressure
Low
pressure
High
pressure
Diameter
8
7
6
5
4
3
2
1
NO.
Front through hole
Specifications
140 × 77 Knockout hole
(5-17/32)(3-1/16)
Front through hole
(Uses when twinning
ø45 Knockout hole
kit (optional parts)
(1-25/32)
is mounted.)
150 × 94 Knockout hole
Bottom through hole
(5-29/32)(3-23/32)
Front through hole ø62.7 or ø34.5 Knockout hole
(2-15/32) (1-3/8)
Front through hole ø43.7 or ø22.2 Knockout hole
(7/8)
(1-3/4)
For wires
Bottom through hole ø65 Knockout hole
(2-9/16)
Bottom through hole ø52 Knockout hole
(2-1/16)
ø34 Knockout hole
For transmission cables Front through hole
(1-11/32)
For pipes
Usage
*1 Expand the on-site piping and connect to the refrigerant service valve piping.
*2 Use the pipe joint(field supply) and connect to the refrigerant service valve piping.
PURY-P144TKMU
PURY-P120TKMU
Model
Refrigerant pipe
Connecting pipe specifications
2X2-80(3-5/32)X35(1-13/32) Oval hole
<Sling hole>
Fan box
Service
panel
Intake
air
19.5
(25/32)
740(29-5/32)
29.5
(1-3/16)
(26-13/16)
681(678~684)
(26-23/32~26-15/16)
(Mounting pitch)
(740)(29-5/32)
Note 1.Please refer to the next page for information
regarding necessary spacing around the
unit and foundation work.
2.At brazing of pipes,wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120°C(248°F).
PURY-P120,144TKMU-A(-BS)
29.5
(1-3/16)
94
(3-23/32)
1347(53-1/16)
303
(11-15/16)
1650(64-31/32)
Module :
PURY-P120TKMU-A – DIMENSIONS
Unit : mm(in.)
CMY-R100XLCBK
Twinning Kit:
CMY-R100XLCBK
unit : inch
Low-pressure pipe twinning kit
1-9/32”
2-15/32”
6-15/16”
OD 1-1/4”
ID 1-5/32”
1-1/32”
1”
4-9/32”
16-13/16”
1-13/32”
5-3/8”
OD 1-5/32”
<Elbow pipe(Accessory)>
ID 1-1/4”
<Deformed pipe(Accessory)>
OD 1-5/32”
ID 1-13/32”
OD 1-1/4”
ID 7/8”
2-3/32”
ID 1-1/4”
2-15/32”
6-5/16”
2-3/32”
OD 1-1/4”
ID 1-5/32”
ID 1-5/32”
1-31/32”
ID 1-5/32”
OD 7/8”
ID 1-5/32”
2-15/32”
2-23/32”
1-31/32”
High-pressure twinning pipe
<Deformed pipe (Accessory)>
1-31/32”
ID 3/4”
ID 1-5/32”
ID 7/8”
OD 3/4”
OD 7/8”
ID 3/4”
(3Pcs.)
<Pipe for routing through the front (Accessory)>
ID 1”
8-7/16”
ID 1”
ID 3/4”
21/32”
OD 3/4”
2-15/32”
2-15/32”
ID 3/4”
4-17/32”
7-17/32”
2-5/16”
3-5/32”
<Pipe for routing through the bottom (Accessory)>
Note 1. Reference the attitude angle of the branch pipe below the fig.
15
Distributer
The angle of the branch pipe for hign pressure is within 15 against the horizontal plane.
2. Use the attached pipe to braze the port-opening of the distributer.
3. Pipe diameter is indicated by inside diameter.
4. Only use the Twinning pipe by Mitsubishi (optional parts) .
Notes:
Mitsubishi Electric Air Conditioning & Refrigeration Systems Wo rks acquired ISO
based on a review of quality warranties for the production of refrigeration and air
conditioning equipment.
ISO Authorization System
The ISO 9000 series is a plant authorization system relating to quality warranties as
development, production, installation and auxiliary services" for products built at
an authorized plant.
Mitsubishi Electric Sales Canada Inc.
www.MitsubishiElectric.ca
Mitsubishi Electric Air Conditioning & Refrigeration Systems Works acquired environmental
The ISO 14000 series is a set of standards applying to environmental protection set by the
International Standard Organization (ISO).
Specifications are subject to change without notice.
SB_PURY-P240TSKMU-A_201206