Emergency-stop�key-release�mushroom,�1N/O+1N/C,�surface�mounting Part�no.  M22-PV/KC11/IY Article�no. 

Emergency-stop�key-release�mushroom,�1N/O+1N/C,�surface�mounting Part�no.  M22-PV/KC11/IY Article�no. 
Emergency-stop�key-release�mushroom,�1N/O+1N/C,�surface�mounting
Part�no. Article�no. Catalog�No. Delivery�programme
M22-PV/KC11/IY
216525
M22-PV-KC11-IYQ
Approval
Product range
RMQ-Titan (drilling dimensions 22.5 mm)
Basic function
Emergency stop buttons
Single unit/Complete unit
Complete unit
Description
Tamper-proof according to ISO 13850/EN 418
Pull to release
Colour of enclosure top
Yellow
Colour of enclosure top
Function
Pull-release
Contacts
N/O = Normally open
1 N/O
N/C = Normally closed
Notes
Contact sequence
RAL Value
RAL 1004
Front ring
None
Connection to SmartWire-DT
no
Standards
IEC/EN 60947
VDE 0660
Lifespan, mechanical
Operations
x 10
Operating frequency
Operations/h Actuating force
n
50
Degree of Protection
IP66, IP69K
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
°C
1 NC
= safety function, by positive opening to IEC/EN 60947-5-1
Technical�data
General
Open
6
> 0.1
600
°C
- 25 - + 70
Mounting position
As required
Mechanical shock resistance
g
50
Shock duration 11 ms
02/13/2015
216525 - HPL-ED2014 V9.0 EN
1/4
Sinusoidal
according to IEC 60068-2-27
Data�for�design�verification�according�to�IEC/EN�61439
Technical data for design verification
Rated operational current for specified heat dissipation
In
A
6
Heat dissipation per pole, current-dependent
Pvid
W
0.11
Equipment heat dissipation, current-dependent
Pvid
W
0
Static heat dissipation, non-current-dependent
Pvs
W
0
Heat dissipation capacity
Pdiss
W
0
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
IEC/EN 61439 design verification
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical�data�ETIM�5.0
Low-voltage industrial components (EG000017) / Control circuit devices combination in enclosure (EC000225)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Command and alarm device / Command and alarm device combination in housing
([email protected] [AKF034010])
Number of command positions
1
Number of push buttons
1
Number of indicator lights
0
Number of key switches
0
Number of selector switches
0
Number of mushroom-shaped push-buttons
0
Suitable for emergency stop
Yes
Rated control supply voltage Us at AC 50HZ
V
115 - 500
Rated control supply voltage Us at AC 60HZ
V
115 - 500
Rated control supply voltage Us at DC
V
24 - 220
Colour housing cover
Yellow
Material housing
Plastic
Degree of protection (IP)
IP66
Number of contacts as normally open contact
1
02/13/2015
216525 - HPL-ED2014 V9.0 EN
2/4
Number of contacts as normally closed contact
1
Number of contacts as change-over contact
0
Product Standards
IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14-05; CSA-C22.2 No. 94-91; CE marking
UL File No.
E29184
UL Category Control No.
NKCR
CSA File No.
012528
CSA Class No.
3211-03
North America Certification
UL listed, CSA certified
Degree of Protection
UL/CSA Type 3R, 4X, 12, 13
Approvals
Dimensions
02/13/2015
216525 - HPL-ED2014 V9.0 EN
3/4
Additional�product�information�(links)
IL04716002Z�(AWA1160-1745)�RMQ-Titan�System
IL04716002Z (AWA1160-1745) RMQ-Titan
System
02/13/2015
ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL04716002Z2013_08.pdf
Eaton Industries GmbH
http://www.eaton.eu
© 12/2014 by Eaton Industries GmbH
216525 - HPL-ED2014 V9.0 EN
4/4
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement