• Indoor Units • R-410A • FUQ-BVV1B
1
A t i y nk BU S 1 V r tAV o0B io 1- ld4Q pn-U SR•FI
1
1
Features
Compact&stylish
•
Extremely quiet in operation
•
Ideal for shops, restaurants or offices requiring maximum floor space
for furniture, decorations and fittings
•
Easy to install
•
Daikin remote controls give you easy control at your fingertips.
•
Can be installed in both new and existing buildings.
•
•
Flexible installation: can be installed in the middle of a room or in a
corner.
The wired remote control provides you with a schedule timer,
enabling to program the air conditioning daily or weekly.
•
•
Air can be discharged in any of 4 directions
•
Possibility to shut 1 or 2 flaps for easy installation in corners
The optional remote ON/OFF enables you to start/stop the air
conditioning from a mobile phone via a telephone remote control
(field supply).
•
Air flow distribution for ceiling heights up to 3.5m without loss of
capacity.
•
The optional forced OFF enables you to switch off the unit
automatically. E.g. when a window is opened, the unit switches off.
•
Air filter, drain pan and heat exchanger fin are mildew proof and antibacterial treated.
•
•
Drain-up pump with 500mm lift fitted as standard
The ’home leave’ operation button prevents large temperature
differences by continuously operating at a minimum (heating mode)
or maximum (cooling mode) preset level while you’re out or sleeping.
It also allows the indoor temperature to return quickly to your
favourite comfort level.
heat pump
2 steps
1
optional
standard
optional
optional
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FUQ-BVV1B
2
2-1
Specifications
FOR INDOOR UNITS ONLY
Nominal Input
2-2
Cooling
Heating
kW
kW
TECHNICAL SPECIFICATIONS
Casing
Dimensions
Colour
Material
Packing
Unit
Weight
Heat
Exchanger
Fan
Air Flow Rate
Unit
Packed Unit
Dimensions
Tube type
Fin
Type
Quantity
Cooling
Heating
Fan
Motor
Cooling
Sound Power
Sound
Pr essure
Heating
Sound Power
Sound
Pr essure
Refrigerant
Piping
connections
Type
Liquid ( OD)
Gas
Drain
Height
Width
Depth
Height
Width
Depth
mm
mm
mm
mm
mm
mm
kg
kg
mm
Length
Nr of Rows
Fin Pitch mm
Nr of Passes
Face
m²
Area
Nr of Stages
Empty Tubeplate
Hole
FUQ71 BVV1 B
FUQ1 00BVV1B
FUQ12 5BVV1B
0.180
0.160
0.289
0.269
0.289
0.269
FUQ71 BVV1 B
FUQ1 00BVV1B
FUQ12 5BVV1B
230
960
960
165
895
895
25.0
31.0
2101
3
1.50
8
0.265
W hite
Resin
295
960
960
230
895
895
31.0
38.0
2101
3
1.50
8
0.353
295
960
960
230
895
895
31.0
38.0
2101
3
1.50
12
0.353
6
Type
High
m³/min
Low
m³/min
High
m³/min
Low
m³/min
Quantity
Model
Number of steps
Output
W
(high)
High
dBA
Low
dBA
High
dBA
Low
dBA
High
dBA
Low
dBA
High
dBA
Low
dBA
Type
Diameter
(OD)
Type
Diameter
(OD)
Diameter
(OD)
1
19.0
14.0
19.0
14.0
1
QTS48A10M
2
45
56.0
51.0
40.0
35.0
56.0
51.0
40.0
35.0
8
4
N-Hix
Cross fin coil (Multi louver fins and N-hix tubes)
Tur bo fan
1
29.0
21.0
29.0
21.0
1
QTS50B15M
2
90
mm
9.5
59.0
54.0
43.0
38.0
59.0
54.0
43.0
38.0
R- 410A
Flare connection
9.5
mm
15.9
Flare connection
15.9
mm
Heat Insulation
3
1
2
8
1
32.0
23.0
32.0
23.0
1
QTS50B15M
2
90
60.0
55.0
44.0
39.0
60.0
55.0
44.0
39.0
9.5
15.9
I.D. 20/O.D. 26
Heat resistant foamed polyethylene, regular foamed polyethylene
Resin net with mold resistance
Fan motor thermal protector
Air Filter
Safety Devices
• Split Sky Air • Indoor Units
2
• Indoor Units • R-410A • FUQ-BVV1B
2
Specifications
2-2 TECHNICAL SPECIFICATIONS
Standard
Accessories
1
Item
Quantity
Item
FUQ7 1BVV1 B
1
2
2-3 ELECTRICAL SPECIFICATIONS
Name
Phase
Frequency
Voltage
Power Supply Intake
FUQ7 1BVV1 B
Power Supply
3
Hz
V
1
50
• Split Sky Air • Indoor Units
FUQ100BVV1B
Installation and oper ation manual
1
Drain hose
Clamp metal
Insulation for fitting
Sealing pad
Clamps
Screws
Washer
Joint
Holding plate
FUQ100BVV1B
V1
1
50
220-240
Outdoor unit only
FUQ1 25BVV1B
1
FUQ1 25BVV1B
1
50
• Indoor Units • R-410A • FUQ-BVV1B
3
Safety device settings
3
FUQ71-100-125B
Model
FUQ-B
FUQ71BUV1B
FUQ100BUV1B
FUQ125BUV1B
Fuse
Safety devices
−
−
−
Fan motor thermal fuse (°C)
−
−
−
Off: 130±5
Off: 130±5
Off: 130±5
Fan motor thermal protector (°C)
1
3
4D013856E
• Split Sky Air • Indoor Units
4
• Indoor Units • R-410A • FUQ-BVV1B
4
Options
Name of option
1
4
Remark
100
125
Sealing member of air discharge outlet
KDBH49FA80
KDBH49FA140
Decoration panel for air discharge
KDBT49FA80
KDBT49FA140
Vertical flap kit
KDGJ49FA80
Replacement long-life filter
Remote control
KDGJ49FA140
KAF495FA140
L connection piping kit
KHFP49MA140
Wired type
Infrared type
BRC1D528
Heat pump
BRC7CA528W
Cooling only
BRC7CA529W
Central remote control
DCS302CA51
Unified ON/OFF control
DCS301BA51
Schedule timer
DST301BA51
Wiring adapter for electrical appendices
KRP4AA53 *1
Interface adapter for Sky Air series
DTA112BA51
Installation box for adapter PCB
KRP1BA97
Remote sensor
KRCS01-1A
Connector for forced on, forced off
EKROROA
Electrical box with earth terminal (3 blocks)
KJB311AA
Electrical box with earth terminal (2 blocks)
KJB212AA
NOTE: *1: Installation box for adapter PCB (KRP1BA97) is necessary
5
FUQ∼B
71
• Split Sky Air • Indoor Units
3D044484A
• Indoor Units • R-410A • FUQ-BVV1B
5
Control systems
3
BRC1D52
1
5 x 10 (Round end slit)
5
6.5 x 9 (Round end slit)
5 x 7 (Round end slit)
HoleJ5
Cover closed
Cover open
• Split Sky Air • Indoor Units
3TW23651-2
6
• Indoor Units • R-410A • FUQ-BVV1B
6
Dimensional drawing & centre of gravity
6-1
Dimensional drawing
unit (mm)
FUQ71B
1
Drain connection
location for upper
piping
Drain connection
location for rear piping
z 1500 mm or
more
Required space
6
z 1500 mm or
more
z 1500 mm
or more
z 1500 mm or more
790 Suspension position
z Drain pipe can be raised up to 350mm from the top surface of the product.
z When closing the discharge grill, the required space is
30mm or more. (Note 3)
790 (Suspension position)
Brand name plate (note 2)
Suspension bolt
1
2
3
4
5
6
7
8
9
10
Height of suspension bracket
Liquid pipe connection - J9.5 flare
Gas pipe connection J15.9 flare
Drain pipe connection V.P.20
Air outlet
Air suction grille
Corner decoration cover
Right pipe / wiring connection
Rear pipe / wiring connection
Pipe through cover
Accessory drain elbow
Note:
1. Location for manufacture’s label: on bell mouth.
2. This is where the signal of infrared remote control
is received. Refer to the drawing of infrared
remote control in detail.
3. When closing the discharge grill (2 or 3 way
discharge), direction of pipe connection will be
limited, please refer to installation manual.
1000mm or more
(required space)
3D013860D
unit (mm)
FUQ100-125B
Drain connection
location for upper
piping
Drain connection
location for rear
piping
z 1500 mm or
more
Required space
z 1500 mm or
more
z 1500 mm
or more
z 1500 mm or more
z Drain pipe can be raised up to 350mm from the top surface of the product.
790 (Suspension position)
Brand name plate (note 2)
z When closing the discharge grill, the required space is
30mm or more. (Note 3)
790 Suspension position
Suspension bolt
1
2
3
4
5
6
7
8
9
10
7
Height of suspension bracket
Liquid pipe connection - J9.5 flare
Gas pipe connection J15.9 flare
Drain pipe connection V.P.20
Air outlet
Air suction grille
Corner decoration cover
Right pipe / wiring connection
Rear pipe / wiring connection
Pipe through cover
Accessory drain elbow
Note:
1000mm or more
(required space)
1. Location for manufacture’s label: on bell mouth.
2. This is where the signal of infrared remote control
is received. Refer to the drawing of infrared
remote control in detail.
3. When closing the discharge grill (2 or 3 way
discharge), direction of pipe connection will be
limited, please refer to installation manual.
3D044898B
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FUQ-BVV1B
7
Piping diagram
3
FUQ71-100-125B
1
Refrigerant pipe connection port diameters
Indoor heat exchanger
Model
FUQ71, 100, 125B
A
J9.5
7
B
J15.9
Field piping JA C1220T-0
Field piping JB C1220T-0
To outdoor unit
Indoor unit
O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe
• Split Sky Air • Indoor Units
4D037995F
8
• Indoor Units • R-410A • FUQ-BVV1B
8
Wiring diagram
8-1
Wiring diagram
FUQ71∼125B
8
Notes
b : Protective earth (screw)
1. D : Terminal
F : Connector
Wired remote
control
Note) 4
: Field wiring
2.
3. In case using central remote control, connect it to the unit in
accordance with the attached instruction manual.
4. X24A is connected when the infrared remote control kit is
being used.
5. Remote control model varies according to the combination
system, confirm technical materials and catalogs, etc. before
connecting.
6. Symbols show as follows Red:red, Blk:black, Ylw:yellow,
Org:orange, Gry:gray, Prp:purple, Blu:blue
7. Confirm the method of setting the selector switch (SS1, SS2)
by installation manual and engeneering materials, etc.
Norm. Emerg.
To outdoor unit
1
In case of simultaneous
operation system.
To outdoor
unit
Indoor unit
(master)
Indoor unit
(slave)
Infrared remote
control
Note) 4
Receiver / display unit
Control box
A1P
C1R
HAP
KAR
KPR
M1F
M1P
M1S
Q1M
R1T
R2T
Printed circuit board
Capacitor (M1F)
Light emitting diode (service monitor green)
Magnetic relay (M1S)
Magnetic relay ((M1P)
Motor (indoor fan)
Motor (drain pump)
Motor (swing flap)
Thermo switch (M1F embedded)
Thermistor (air)
Thermistor (coil)
S1L
Float switch (M1A)
S1Q
Limit switch (swing flap)
SS1
Selector switch (emergency)
T1R
Transformer (220-240V/22V)
V1TR
Phase control circuit
X1M
Terminal strip
X2M
Terminal strip
? Signal receiver circuit
. Signal transmission circuit
Wired remote control
R1T
Thermistor (air)
SS1
Selector switch (main/sub)
Receiver / display unit (attached to infrared remote controller)
A2P
Printed circuit board
A3P
Printed circuit board
BS1
Push button (on/off)
H1P
Light emitting diode (service monitor red)
H2P
Light emitting diode (service monitor green)
H3P
Light emitting diode (service monitor red)
H4P
Light emitting diode (service monitor orange)
SS1
Selector switch (main/sub)
SS2
Selector switch (wireless address set)
Connector for optional parts
X35A
Connector (group control adapter)
X60A
Connector (interface adapter for sky air series)
X61A
3D043746A
9
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FUQ-BVV1B
8
Wiring diagram
8-2
External connection diagram
FUQ71∼125B
V1, Model
Power supply
1∼50Hz
220V-240V
V3, Model
Power supply
1∼50Hz
230V
Main switch
Main switch
Fuse
Fuse
3
Y1, Model
Power supply
3N∼50Hz
400V
1
Main switch
8
Fuse
NOTES
1
2
3
4
5
6
7
8
9
Line voltage wiring
Control circuit wiring
All wiring, components and materials to be produced on the site must comply with the applicable local and national codes.
Use copper conductors only.
See wiring diagrams for details.
Install fuse and mainswitch for safety.
All field wiring and components must be provided by a licensed electrician.
The unit shall be grounded in compilance with the applicable local and national codes.
Wiring shown are general points-of-connection guides only and are not intended for or to include all details for a specific
installation.
Never share a common power supply with other equipment.
• Split Sky Air • Indoor Units
4D013833C
10
• Indoor Units • R-410A • FUQ-BVV1B
9
Sound data
9-1
Sound level data
Sound pressure level
230V
1
9
11
Sound power level
50Hz
Model
Cooling
(H/L)
Heating
(H/L)
FUQ71B
40/35
40/35
FUQ100B
43/38
43/38
FUQ125B
44/39
44/39
• Split Sky Air • Indoor Units
Measuring location
Location of
microphone
Cooling
(H/L)
Heating
(H/L)
56/51
56/51
59/54
59/54
60/55
60/55
• Indoor Units • R-410A • FUQ-BVV1B
9
Sound data
9-2
Sound pressure spectrum
3
FUQ71B
1
Octave band sound pressure level
Octave band sound pressure level
FUQ100B
H (230V)
9
H (230V)
L (230V)
L (230V)
approximate
threshold hearing
for continuous
noise
4D014037D
approximate
threshold hearing
for continuous
noise
4D014038D
Octave band center frequency (Hz)
NOTES
1
NOTES
Sound pressure levels are measured in an anechoic
room.
Operation sound levels are valid at nominal
operation condition
Operation sound level differs with operation and
ambient conditions.
2
3
Octave band center frequency (Hz)
1
2
3
Sound pressure levels are measured in an anechoic
room.
Operation sound levels are valid at nominal
operation condition
Operation sound level differs with operation and
ambient conditions.
Octave band sound pressure level
FUQ125B
H (230V)
L (230V)
approximate
threshold hearing
for continuous
noise
4D014039D
Octave band center frequency (Hz)
NOTES
1
2
3
Sound pressure levels are measured in an anechoic
room.
Operation sound levels are valid at nominal
operation condition
Operation sound level differs with operation and
ambient conditions.
• Split Sky Air • Indoor Units
12
• Indoor Units • R-410A • FUQ-BVV1B
10
Air flow pattern
FUQ71B
Cooling - air velocity distribution
1
4-way discharge air flow direction: horizontal
10
FUQ71B
Cooling - air temperature distribution
4-way discharge air flow direction: horizontal
4D028396C
13
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FUQ-BVV1B
10
Air flow pattern
3
FUQ100B
Cooling - air velocity distribution
1
4-way discharge air flow direction: horizontal
10
FUQ100B
Cooling - air temperature distribution
4-way discharge air flow direction: horizontal
4D028397C
• Split Sky Air • Indoor Units
14
• Indoor Units • R-410A • FUQ-BVV1B
10
Air flow pattern
FUQ125B
Cooling - air velocity distribution
1
4-way discharge air flow direction: horizontal
10
FUQ125B
Cooling - air temperature distribution
4-way discharge air flow direction: horizontal
4D028398C
15
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FUQ-BVV1B
10
Air flow pattern
3
FUQ71B
Heating - air velocity distribution
1
4-way discharge, air flow direction: down
10
FUQ71B
Heating - air temperature distribution
4-way discharge, air flow direction: down
4D013863D
• Split Sky Air • Indoor Units
16
• Indoor Units • R-410A • FUQ-BVV1B
10
Air flow pattern
FUQ100B
Heating - air velocity distribution
1
4-way discharge, air flow direction: down
10
FUQ100B
Heating - air temperature distribution
4-way discharge, air flow direction: down
4D014054D
17
• Split Sky Air • Indoor Units
• Indoor Units • R-410A • FUQ-BVV1B
10
Air flow pattern
3
FUQ125B
Heating - air velocity distribution
1
4-way discharge, air flow direction: down
10
FUQ125B
Heating - air temperature distribution
4-way discharge, air flow direction: down
4D014055D
• Split Sky Air • Indoor Units
18
• Indoor Units • R-410A • FUQ-BVV1B
11
Installation
11 - 1 Installation method
1
Names and functions of parts
j
a Indoor unit
j
b Outdoor unit
j
c Infrared remote control
j
d Inlet air
j
e Discharged air
j
f Air outlet
j
g Air flow flap (at air outlet)
j
h Refrigerant piping, connection electric wire
j
i Drain pipe
j
j Air inlet
The built-in air filter removes dust and dirt.
j
k Ground wire
Wire to ground from the outdoor unit to prevent electrical
shocks.
j
l Drain pumping out device (built-in)
Drains water removed from the room during cooling
11
19
• Split Sky Air • Indoor Units