MODEL PAX - 1/8 DIN DIGITAL INPUT PANEL METERS
COUNT, DUAL COUNTER, RATE AND SLAVE DISPLAY
0.56" RED SUNLIGHT READABLE DISPLAY
VARIABLE INTENSITY DISPLAY
10 POINT SCALING FOR NON-LINEAR PROCESSES (PAXI)
FOUR SETPOINT ALARM OUTPUTS (W/Option Card)
RETRANSMITTED ANALOG OUTPUT (W/Option Card) (PAXI)
COMMUNICATION AND BUS CAPABILITIES (W/Option Card) (PAXI)
BUS CAPABILITIES; DEVICENET, MODBUS, AND PROFIBUS-DP
CRIMSON PROGRAMMING SOFTWARE (PAXI)
ETHERNET(W/ External Gateway) (PAXI)
NEMA 4X/IP65 SEALED FRONT BEZEL
CC
R
UL
US LISTED
IND. CONT. EQ.
51EB
GENERAL DESCRIPTION
The PAX Digital Input Panel Meters offer many features and performance capabilities to suit a wide range of industrial applications. Available in three different models, PAXC Counter/Dual Counter, PAXR Rate Meter and the PAXI which offers both counting and rate in the same package. Refer to pages 4 - 5 for the details on the specific models. The PAXC and PAXR offer only the Setpoint
Option, while the PAXI is the fully featured version offering all the capabilities as outlined in this bulletin as well as a slave display feature. The optional plug-in output cards allow the opportunity to configure the meter for present applications, while providing easy upgrades for future needs.
The meters employ a bright 0.56" LED display. The meters are available with a red sunlight readable or standard green LED display. The intensity of the display can be adjusted from dark room applications up to sunlight readable, making it ideal for viewing in bright light applications.
The meters accept digital inputs from a variety of sources including switch contacts, outputs from CMOS or TTL circuits, magnetic pickups and all standard RLC sensors. The meter can accept directional, uni-directional or
Quadrature signals simultaneously. The maximum input signal varies up to 34
KHz depending on the count mode and function configurations programmed.
Each input signal can be independently scaled to various process values.
The Rate Meters provide a MAX and MIN reading memory with programmable capture time. The capture time is used to prevent detection of false max or min readings which may occur during start-up or unusual process events.
The meters have four setpoint outputs, implemented on Plug-in option cards.
The Plug-in cards provide dual FORM-C relays (5A), quad FORM-A (3A), or either quad sinking or quad sourcing open collector logic outputs. The setpoint alarms can be configured to suit a variety of control and alarm requirements.
Communication and Bus Capabilities are also available as option cards for the PAXI only. These include RS232, RS485, Modbus, DeviceNet, and
Profibus-DP. Readout values and setpoint alarm values can be controlled through the bus. Additionally, the meters have a feature that allows a remote computer to directly control the outputs of the meter. With an RS232 or RS485 card installed, it is possible to configure the meter using Red Lion’s Crimson software. The configuration data can be saved to a file for later recall.
A linear DC output signal is available as an optional Plug-in card for the PAXI only. The card provides either 20 mA or 10 V signals. The output can be scaled independent of the input range and can track any of the counter or rate displays.
Once the meters have been initially configured, the parameter list may be locked out from further modification in its entirety or only the setpoint values can be made accessible.
The meters have been specifically designed for harsh industrial environments.
With NEMA 4X/IP65 sealed bezel and extensive testing of noise effects to CE requirements, the meter provides a tough yet reliable application solution.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do not use this meter to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the meter.
CAUTION: Risk of Danger.
Read complete instructions prior to installation and operation of the unit.
CAUTION: Risk of electric shock.
DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for
mounting clip installation is 2.1" (53.4) H x 5" (127) W.
A
B
C
8.8.8.8.8.8
SP1 SP2 SP3 SP4
DSP PAR F1 F2 RST
1.95
(49.5)
3.80
(96.5)
.10
(2.5)
4.10
(104.1)
1
1.75
(44.5)
12
13
14
15
16
17
18
19
1 2 3 4 5 6 7 8 9 10 11
20
21
22
23
24
25
3.60 (91.4)
1.75
(44.5)
T
ABLE
O
F
C
ONTENTS
Ordering Information . . . . . . . . . . . . . . . . . . . . 2
General Meter Specifications . . . . . . . . . . . . . 3
PAXC Counter . . . . . . . . . . . . . . . . . . . . . . . . . 4
PAXR Rate Meter . . . . . . . . . . . . . . . . . . . . . . 4
PAXI Counter/Rate Meter . . . . . . . . . . . . . . . . 5
Optional Plug-In Output Cards . . . . . . . . . . . . 6
Installing the Meter . . . . . . . . . . . . . . . . . . . . . 7
Setting the Jumper and DIP Switches . . . . . . 7
O
RDERING
I
NFORMATION
Installing Plug-In Cards . . . . . . . . . . . . . . . . . . 8
Wiring the Meter . . . . . . . . . . . . . . . . . . . . . . . 9
Reviewing the Front Buttons and Display . . . 11
Programming the Meter. . . . . . . . . . . . . . . . . 12
Factory Service Operations . . . . . . . . . . . . . . 28
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . 29
Parameter Value Chart . . . . . . . . . . . . . . . . . 30
Programming Overview . . . . . . . . . . . . . . . . . 32
Meter Part Numbers
PAX 0 0
C - Counter/Dual Counter
R - Rate Meter
I - Counter/Dual Counter/
Rate Meter/Slave Display
0 - Red, Sunlight Readable Display
1 - Green Display
0 - 85 to 250 VAC
1 - 11 to 36 VDC, 24 VAC
Option Card and Accessories Part Numbers
TYPE MODEL NO.
DESCRIPTION
Optional
Plug-In
Cards
Accessories
PAXCDS
PAXCDC
PAXUSB
PAXCDL
SFCRD*
ICM8
Dual Setpoint Relay Output Card
Quad Setpoint Relay Output Card
Quad Setpoint Sinking Open Collector Output Card
Quad Setpoint Sourcing Open Collector Output Card
RS485 Serial Communications Card with Terminal Block
Extended RS485 Serial Communications Card with Dual RJ11 Connector
RS232 Serial Communications Card with Terminal Block
Extended RS232 Serial Communications Card with 9 Pin D Connector
DeviceNet Communications Card
Modbus Communications Card
Extended Modbus Communications Card with Dual RJ11 Connector
Profibus-DP Communications Card
PAX USB Programming Card (Not included in PAX product UL E179259 file).
Analog Output Card
Crimson PC Configuration Software for Windows 98, ME, 2000 and XP
Communication Gateway
*Crimson software is available for free download from http://www.redlion.net/
Shaded areas are only available for the PAXI
2
PART NUMBER
PAXCDS10
PAXCDS20
PAXCDS30
PAXCDS40
PAXCDC10
PAXCDC1C
PAXCDC20
PAXCDC2C
PAXCDC30
PAXCDC40
PAXCDC4C
PAXCDC50
PAXUSB00
PAXCDL10
SFCRD200
ICM80000
G
ENERAL
M
ETER
S
PECIFICATIONS
1. DISPLAY: 6 digit, 0.56" (14.2 mm) red sunlight readable or standard green
LED
2. POWER:
AC Versions:
AC Power: 85 to 250 VAC, 50/60 Hz, 18 VA
Isolation: 2300 Vrms for 1 min. to all inputs and outputs. (300 V working)
DC Versions:
DC Power: 11 to 36 VDC, 14 W
(derate operating temperature to 40° C if operating <15 VDC and three plug-in option cards are installed)
AC Power: 24 VAC, ± 10%, 50/60 Hz, 15 VA
Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working).
3. SENSOR POWER: 12 VDC, ±10%, 100 mA max. Short circuit protected
4. KEYPAD: 3 programmable function keys, 5 keys total
5. USER INPUTS: Three programmable user inputs
Max. Continuous Input: 30 VDC
Isolation To Sensor Input Commons: Not isolated
Logic State: Jumper selectable for sink/source logic
INPUT STATE
Active
Inactive
SINKING INPUTS
5.1 K
pull-up to +12 V
V
IN
< 0.9 VDC
V
IN
> 3.6 VDC
SOURCING INPUTS
5.1 K
pull-down
V
IN
> 3.6 VDC
V
IN
< 0.9 VDC
Response Time: 6 msec. typical; function dependent. Certain resets, stores and inhibits respond within 25 μsec if an edge occurs with the associated counter or within 6 msec if no count edge occurs with the associated counter. These functions include , , , ,
, , and . Once activated, all functions are latched for
50 msec min. to 100 msec max. After that period, another edge/level may be recognized.
6. MEMORY: Nonvolatile E 2 PROM retains all programmable parameters and display values.
7. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File #E179259, UL61010A-1, CSA C22.2
No. 61010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File #E137808, UL508, CSA C22.2 No. 14-M95
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Report #04ME11209-20041018
Issued by Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
IP20 Enclosure rating (Rear of unit), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326:2006: Electrical Equipment for
Measurement, Control and Laboratory use.
Immunity to Industrial Locations:
Electrostatic discharge EN 61000-4-2 Criterion A
4 kV contact discharge
8 kV air discharge
Electromagnetic RF fields EN 61000-4-3 Criterion A
10 V/m (80 MHz to 1 GHz)
3 V/m (1.4 GHz to 2 GHz)
Fast transients (burst)
1 V/m (2 GHz to 2.7 GHz)
EN 61000-4-4 Criterion A
2 kV power
1 kV I/O signal
Surge
2 kV I/O signal connected to power
EN 61000-4-5 Criterion A power 1 kV L to L, 2 kV L to G signal 1 kV
RF conducted interference EN 61000-4-6 Criterion A
3 Vrms
AC power EN 61000-4-11
Voltage dip Criterion A
0% during 1 cycle
40% during 10/12 cycle
Short interruptions
70% during 25/30 cycle
Criterion C
0% during 250/300 cycles
Emissions:
Emissions EN 55011 Class A
Notes:
1. Criterion A: Normal operation within specified limits.
2. Criterion C: Temporary loss of function where system reset occurs.
Refer to EMC Installation Guidelines section of the bulletin for additional information.
8. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50°C (0 to 45°C with all three plug-in cards installed)
Storage Temperature Range: -40 to 60°C
Operating and Storage Humidity: 0 to 85% max. relative humidity noncondensing
Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z direction for 1.5 hours, 2 g.
Shock According to IEC 68-2-27: Operational 25 g (10 g relay), 11 msec in 3 directions.
Altitude: Up to 2000 meters
9. CONNECTIONS: High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 4.5 inch-lbs (0.51 N-m) max.
10. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use.
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and mounting clip included.
11. WEIGHT: 10.1 oz. (286 g)
3
M
ODEL
PAXC - 1/8 DIN C
OUNTER
6-DIGIT LED DISPLAY (Alternating 8 digits for counting)
DUAL COUNT QUAD INPUTS
UP TO 3 COUNT DISPLAYS
SETPOINT ALARM OUTPUTS (W/Plug-in card)
PAXC SPECIFICATIONS
MAXIMUM SIGNAL FREQUENCIES:
To determine the maximum frequency for the input(s), first answer the questions with a yes (Y) or no (N). Next determine the Count Mode to be used for the counter(s). If dual counters are used with different Count Modes, then the lowest frequency applies to both counters.
FUNCTION QUESTIONS Single: Counter A or B Dual: Counter A & B
Are any setpoints used?
N
Is Counter C used?
N
COUNT MODE
Count x1
Count x2
N
Y
Y
N
Y
Y
N
N
N
Y
Y
N
Y
Y
(Values are in KHz) (Values are in KHz)
34 25 18 15 13 12 9 7.5
17 13 9 7 9 7 5 4
Quadrature x1
Quadrature x2
Quadrature x4
22 19 12 10 7 6 4 3.5
17 13 9 7 7 6 4 3.5
8 6 4 3
Notes:
1. Counter Modes are explained in the Module 1 programming section.
2. Listed values are with frequency DIP switch set on HI frequency.
ANNUNCIATORS:
A - Counter A
B - Counter B
C - Counter C
- Upper significant digit display of counter
SP1 - setpoint 1 output state
SP2 - setpoint 2 output state
SP3 - setpoint 3 output state
SP4 - setpoint 4 output state
COUNTER DISPLAYS:
Maximum display: 8 digits: ± 99999999 (greater than 6 digits display
Alternates between high order and low order.)
INPUTS A and B:
DIP switch selectable to accept pulses from a variety of sources including switch contacts, TTL outputs, magnetic pickups and all standard RLC sensors.
LOGIC: Input trigger levels V
IL
= 1.5 V max.; V
IH
= 3.75 V min.
Current sinking: Internal 7.8 K pull-up to +12 VDC, I
MAX
= 1.9 mA.
Current sourcing: Internal 3.9 K pull-down, 7.3 mA max. @ 28 VDC,
V
MAX
= 30 VDC.
Filter: Damping capacitor provided for switch contact bounce. Limits input frequency to 50 Hz and input pulse widths to 10 msec. minimum.
DUAL COUNT MODES:
When any dual count mode is used, then User Inputs 1 and/or 2 will accept the second signal of each signal pair. The user inputs do not have the Logic/Mag, HI/LO Freq, and Sink/Source input setup switches. The user inputs are inherently a logic input with no low frequency filtering.
Any mechanical contacts used for these inputs in a dual count mode must be debounced externally. The user input may only be selected for sink/source by the User Jumper placement.
M
ODEL
PAXR - 1/8 DIN R
ATE
M
ETER
5-DIGIT LED DISPLAY
RATE INDICATION
MINIMUM/MAXIMUM RATE DISPLAYS
SETPOINT ALARM OUTPUTS (W/Plug-in card)
PAXR SPECIFICATIONS
ANNUNCIATORS:
- Rate
- Maximum (High) Rate
- Minimum (Low) Rate
SP1 - setpoint 1 output state
SP2 - setpoint 2 output state
SP3 - setpoint 3 output state
SP4 - setpoint 4 output state
RATE DISPLAY:
Accuracy: ±0.01%
Minimum Frequency: 0.01 Hz
Maximum Frequency: 34 KHz
Maximum Display: 5 Digits: 99999
Adjustable Display (low) Update: 0.1 to 99.9 seconds
Over Range Display: “ ”
INPUT A:
DIP switch selectable to accept pulses from a variety of sources including
TTL outputs, magnetic pickups and all standard RLC sensors.
LOGIC: Input trigger levels V
IL
= 1.5 V max.; V
IH
= 3.75 V min.
Current sinking: Internal 7.8 K pull-up to +12 VDC, I
MAX
= 1.9 mA.
Current sourcing: Internal 3.9 K pull-down, 7.3 mA max. @ 28 VDC,
V
MAX
= 30 VDC.
MAGNETIC PICKUP:
Sensitivity: 200 mV peak
Hysteresis: 100 mV
Input impedance: 3.9 K @ 60 Hz
Maximum input voltage: ±40 V peak, 30 Vrms
4
M
ODEL
PAXI - 1/8 DIN C
OUNTER
/R
ATE
M
ETER
COUNT, RATE AND SLAVE DISPLAY
6-DIGIT 0.56" RED SUNLIGHT READABLE DISPLAY
VARIABLE INTENSITY DISPLAY
10 POINT SCALING (FOR NON-LINEAR PROCESSES)
FOUR SETPOINT ALARM OUTPUTS (W/OPTION CARD)
RETRANSMITTED ANALOG OUTPUT (W/OPTION CARD)
COMMUNICATION AND BUS CAPABILITIES (W/OPTION CARD)
BUS CAPABILITIES; DEVICENET, MODBUS, AND PROFIBUS-DP
CRIMSON PROGRAMMING SOFTWARE
PAXI SPECIFICATIONS
MAXIMUM SIGNAL FREQUENCIES TABLE
To determine the maximum frequency for the input(s), first answer the questions with a yes (Y) or no (N). Next determine the Count Mode to be used for the counter(s). If dual counters are used with different Count Modes, then the lowest frequency applies to both counters.
FUNCTION QUESTIONS Single: Counter A or B (with/without rate) or Rate only Dual: Counter A & B or Rate not assigned to active single counter
Are any setpoints used?
Is Prescaler Output used?
Is Counter C used?
COUNT MODE
Count x1
Count x2
Quadrature x1
Quadrature x2
Quadrature x4
Rate Only
34
17
22
17
8
34
N
N
N
N
N
Y
N Y N
(Values are in KHz)
Y
N
Y
25
13
19
13
6
N/A
21
16
20
16
8
21
17
12
17
12
6
N/A
18
9
12
9
4
34
Y
N
Y
N
Y
Y
N Y N
(Values are in KHz)
Y
Y
Y
15
7
10
7
3
N/A
13
8
11
8
4
21
11
7
10
6
3
N/A
13
9 *
7 *
7 *
N
N
N
N
N
Y
N Y N
(Values are in KHz)
N
Y
Y
12
7 *
6 *
6 *
13
9 *
6 *
6 *
11
7 *
5 *
5 *
9
5 *
4 *
4 *
Y
N
Y
N
Y
Y
N Y N
(Values are in KHz)
Y
Y
Y
7.5
4 *
3.5 *
3.5 *
9
5 *
3.5 *
3.5 *
7
4 *
3 *
3 *
Notes:
1. Counter Modes are explained in the Module 1 programming section.
2. If using Rate with single counter with direction or quadrature, assign it to Input A for the listed frequency.
3. * Double the listed value for Rate frequency.
4. Listed values are with frequency DIP switch set on HI frequency.
5. Derate listed frequencies by 20% during serial communications. (Placing a 5 msec. delay between serial characters will eliminate the derating.)
ANNUNCIATORS:
A - Counter A
B - Counter B
C - Counter C
- Rate
- Maximum (High) Rate
- Minimum (Low) Rate
- Upper significant digit display of counter
SP1 - setpoint 1 output state
SP2 - setpoint 2 output state
SP3 - setpoint 3 output state
SP4 - setpoint 4 output state
RATE DISPLAY:
Accuracy: ±0.01%
Minimum Frequency: 0.01 Hz
Maximum Frequency: see Max Signal Frequencies Table.
Maximum Display: 5 Digits: 99999
Adjustable Display (low) Update: 0.1 to 99.9 seconds
Over Range Display: “
”
COUNTER DISPLAYS:
Maximum display: 8 digits: ± 99999999 (greater than 6 digits display
Alternates between high order and low order.)
INPUTS A and B:
DIP switch selectable to accept pulses from a variety of sources including switch contacts, TTL outputs, magnetic pickups and all standard RLC sensors.
LOGIC: Input trigger levels V
IL
= 1.5 V max.; V
IH
= 3.75 V min.
Current sinking: Internal 7.8 K pull-up to +12 VDC, I
MAX
= 1.9 mA.
Current sourcing: Internal 3.9 K pull-down, 7.3 mA max. @ 28 VDC,
V
MAX
= 30 VDC.
Filter: Damping capacitor provided for switch contact bounce. Limits input frequency to 50 Hz and input pulse widths to 10 msec. minimum.
MAGNETIC PICKUP:
Sensitivity: 200 mV peak
Hysteresis: 100 mV
Input impedance: 3.9 K @ 60 Hz
Maximum input voltage: ±40 V peak, 30 Vrms
DUAL COUNT MODES:
When any dual count mode is used, then User Inputs 1 and/or 2 will accept the second signal of each signal pair. The user inputs do not have the Logic/Mag, HI/LO Freq, and Sink/Source input setup switches. The user inputs are inherently a logic input with no low frequency filtering.
Any mechanical contacts used for these inputs in a dual count mode must be debounced externally. The user input may only be selected for sink/source by the User Jumper placement.
PRESCALER OUTPUT:
NPN Open Collector: I
SNK
= 100 mA max. @ V
OL
= 1 VDC max. V
VDC max. With duty cycle of 25% min. and 50 % max.
OH
= 30
5
O
PTIONAL
P
LUG
-
IN
O
UTPUT
C
ARDS
WARNING: Disconnect all power to the unit before installing Plug-in cards.
Adding Option Cards
The PAX and MPAX series meters can be fitted with up to three optional plugin cards. The details for each plug-in card can be reviewed in the specification section below. Only one card from each function type can be installed at one time.
The function types include Setpoint Alarms (PAXCDS), Communications
(PAXCDC), and Analog Output (PAXCDL). The plug-in cards can be installed initially or at a later date.
PAXI COMMUNICATION CARDS (PAXCDC)
A variety of communication protocols are available for the PAX and MPAX series. Only one of these cards can be installed at a time. When programming the unit via Crimson, a Windows ® based program, the RS232 or RS485 Cards must be used.
PAXCDC10 - RS485 Serial (Terminal)
PAXCDC1C - RS485 Serial (Connector)
PAXCDC20 - RS232 Serial (Terminal)
PAXCDC2C - RS232 Serial (Connector)
PAXCDC30 - DeviceNet
PAXCDC40 - Modbus (Terminal)
PAXCDC4C - Modbus (Connector)
PAXCDC50 - Profibus-DP
SERIAL COMMUNICATIONS CARD
Type: RS485 or RS232
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V. Not Isolated from all other commons.
Data: 7/8 bits
Baud: 300 to 19,200
Parity: no, odd or even
Bus Address: Selectable 0 to 99, Max. 32 meters per line (RS485)
Transmit Delay: Selectable for 2 to 50 msec or 50 to 100 msec (RS485)
DEVICENET™ CARD
Compatibility: Group 2 Server Only, not UCMM capable
Baud Rates: 125 Kbaud, 250 Kbaud, and 500 Kbaud
Bus Interface: Phillips 82C250 or equivalent with MIS wiring protection per
DeviceNet™ Volume I Section 10.2.2.
Node Isolation: Bus powered, isolated node
Host Isolation: 500 Vrms for 1 minute (50 V working) between DeviceNet™ and meter input common.
MODBUS CARD
Type: RS485; RTU and ASCII MODBUS modes
Isolation To Sensor & User Input Commons: 500 Vrms for 1 minute.
Working Voltage: 50 V. Not isolated from all other commons.
Baud Rates: 300 to 38400.
Data: 7/8 bits
Parity: No, Odd, or Even
Addresses: 1 to 247.
Transmit Delay: Programmable; See Transmit Delay explanation.
PROFIBUS-DP CARD
Fieldbus Type: Profibus-DP as per EN 50170, implemented with Siemens
SPC3 ASIC
Conformance: PNO Certified Profibus-DP Slave Device
Baud Rates: Automatic baud rate detection in the range 9.6 Kbaud to 12 Mbaud
Station Address: 0 to 125, set by rotary switches.
Connection: 9-pin Female D-Sub connector
Network Isolation: 500 Vrms for 1 minute (50 V working) between Profibus network and sensor and user input commons. Not isolated from all other commons.
PROGRAMMING SOFTWARE
Crimson is a Windows ® based program that allows configuration of the PAX meter from a PC. Crimson offers standard drop-down menu commands, that make it easy to program the PAX meter. The PAX program can then be saved in a PC file for future use. A PAX serial plug-in card or PAX USB programming card is required to program the meter using the software.
SETPOINT CARDS (PAXCDS)
The PAX and MPAX series has 4 available setpoint alarm output plug-in cards. Only one of these cards can be installed at a time. (Logic state of the outputs can be reversed in the programming.) These plug-in cards include:
PAXCDS10 - Dual Relay, FORM-C, Normally open & closed
PAXCDS20 - Quad Relay, FORM-A, Normally open only
PAXCDS30 - Isolated quad sinking NPN open collector
PAXCDS40 - Isolated quad sourcing PNP open collector
DUAL RELAY CARD
Type: Two FORM-C relays
Isolation To Sensor & User Input Commons: 2000 Vrms for 1 min.
Working Voltage: 240 Vrms
Contact Rating:
One Relay Energized: 5 amps @ 120/240 VAC or 28 VDC (resistive load),
1/8 HP @120 VAC, inductive load
Total current with both relays energized not to exceed 5 amps
Life Expectancy: 100 K cycles min. at full load rating. External RC snubber extends relay life for operation with inductive loads
Response Time: 5 msec. nominal pull-in with 3 msec. nominal release
Timed Output Accuracy: Counter = ± 0.01% + 10 msec.
Rate = ± 0.01% + 20 msec.
QUAD RELAY CARD
Type: Four FORM-A relays
Isolation To Sensor & User Input Commons: 2300 Vrms for 1 min.
Working Voltage: 250 Vrms
Contact Rating:
One Relay Energized: 3 amps @ 250 VAC or 30 VDC (resistive load), 1/10
HP @120 VAC, inductive load
Total current with all four relays energized not to exceed 4 amps
Life Expectancy: 100K cycles min. at full load rating. External RC snubber extends relay life for operation with inductive loads
Response Time: 5 msec. nominal pull-in with 3 msec. nominal release
Timed Output Accuracy: Counter = ± 0.01% + 10 msec.
Rate = ± 0.01% + 20 msec.
QUAD SINKING OPEN COLLECTOR CARD
Type: Four isolated sinking NPN transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V. Not Isolated from all other commons.
Rating: 100 mA max @ V
SAT
= 0.7 V max. V
MAX
= 30 V
Response Time: Counter = 25 μsec; Rate = Low Update time
Timed Output Accuracy: Counter = ± 0.01% + 10 msec.
Rate = ± 0.01% + 20 msec.
QUAD SOURCING OPEN COLLECTOR CARD
Type: Four isolated sourcing PNP transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V. Not Isolated from all other commons.
Rating: Internal supply: 24 VDC ± 10% , 30 mA max. total
External supply: 30 VDC max., 100 mA max. each output
Response Time: Counter = 25 μsec; Rate = Low Update time
Timed Output Accuracy: Counter = ± 0.01% + 10 msec.
Rate = ± 0.01% + 20 msec.
PAXI ANALOG OUTPUT CARD (PAXCDL)
Either a 0(4)-20 mA or 0-10 V retransmitted linear DC output is available from the analog output plug-in card. The programmable output low and high scaling can be based on various display values. Reverse slope output is possible by reversing the scaling point positions.
PAXCDL10 - Retransmitted Analog Output Card
ANALOG OUTPUT CARD
Types: 0 to 20 mA, 4 to 20 mA or 0 to 10 VDC
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V. Not Isolated from all other commons.
Accuracy: 0.17% of FS (18 to 28°C); 0.4% of FS (0 to 50°C)
Resolution: 1/3500
Compliance: 10 VDC: 10 K
load min., 20 mA: 500 load max.
Response Time: 50 msec. max., 10 msec. typ.
6
1.0 I
NSTALLING THE
M
ETER
Installation
The PAX meets NEMA 4X/IP65 requirements when properly installed. The unit is intended to be mounted into an enclosed panel. Prepare the panel cutout to the dimensions shown. Remove the panel latch from the unit. Slide the panel gasket over the rear of the unit to the back of the bezel. The unit should be installed fully assembled. Insert the unit into the panel cutout.
While holding the unit in place, push the panel latch over the rear of the unit so that the tabs of the panel latch engage in the slots on the case. The panel latch should be engaged in the farthest forward slot possible. To achieve a proper seal, tighten the latch screws evenly until the unit is snug in the panel
(Torque to approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.
BEZEL
LATCHING
SLOTS
PANEL
PANEL
LATCH
LATCHING
TABS
Installation Environment
The unit should be installed in a location that does not exceed the operating temperature and provides good air circulation. Placing the unit near devices that generate excessive heat should be avoided.
The bezel should only be cleaned with a soft cloth and neutral soap product.
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the keypad of the unit.
PANEL CUT-OUT
PANEL
GASKET
PANEL
MOUNTING
SCREWS
2.0 S
ETTING THE
J
UMPER AND
DIP S
WITCHES
To access the jumper and switches, remove the meter base from the meter case by firmly squeezing and pulling back on the side rear finger tabs. This should lower the latch below the case slot (which is located just in front of the finger tabs). It is recommended to release the latch on one side, then start the other side latch.
Warning: Exposed line voltage exists on the circuit boards. Remove all power to the meter and load circuits before accessing inside of the meter.
2.1 SETTING THE JUMPER
The meter has one jumper for user input logic. When using the user inputs this jumper must be set before applying power. The Main Circuit Board figure shows the location of the jumper and DIP switch.
The user input jumper determines signal logic for the user inputs, when they are used with user functions or for input signal direction. All user inputs are set by this jumper.
Main
Circuit
Board
2.2 SETTING THE INPUT DIP SWITCHES
The meter has six DIP switches for Input A and Input B terminal set-up that must be set before applying power. NOTE: The PAXR only uses switches 1-3.
Input B LO Freq.
Input B SRC.
Input B MAG.
Input A LO Freq.
Input A SRC.
Input A MAG.
ON
4
3
6
5
2
1
HI Freq.
SNK.
Logic
HI Freq.
SNK.
Logic
Factory Setting
INPUT SET-UP
DIP SWITCHES
SRC
SNK
USER
INPUT
JUMPER
SWITCHES 3 and 6
HI Frequency: Removes damping capacitor and allows max. frequency.
LO Frequency: Adds a damping capacitor for switch contact bounce. Also limits input frequency to 50 Hz and input pulse widths to 10 msec.
SWITCHES 2 and 5
SRC.: Adds internal 3.9 K
pull-down resistor, 7.3 mA max. @ 28 VDC,
V
MAX
= 30 VDC.
SNK.: Adds internal 7.8 K
pull-up resistor to +12 VDC, I
MAX
= 1.9 mA.
SWITCHES 1 and 4
LOGIC: Input trigger levels V
IL
= 1.5 V max.; V
IH
= 3.75 V min.
MAG: 200 mV peak input (must also have SRC on). Not recommended with counting applications.
7
3.0 I
NSTALLING
P
LUG
-I
N
C
ARDS
The Plug-in cards are separately purchased optional cards that perform specific functions. These cards plug into the main circuit board of the meter. The
Plug-in cards have many unique functions when used with the PAX. The literature that comes with these cards should be discarded, unless it specifically states in the Plug-in Card literature that the information applies to the PAX.
Note: The PAXC and PAXR only use the setpoint option card.
CAUTION: The Plug-in card and main circuit board contain static sensitive components. Before handling the cards, discharge static charges from your body by touching a grounded bare metal object. Ideally, handle the cards at a static controlled clean workstation. Also, only handle the cards by the edges. Dirt, oil or other contaminants that may contact the cards can adversely affect circuit operation.
To Install:
1. With the case open, locate the Plug-in card connector for the card type to be installed. The types are keyed by position with different main circuit board connector locations. When installing the card, hold the meter by the rear terminals and not by the front display board.*
2. Install the Plug-in card by aligning the card terminals with the slot bay in the rear cover. Be sure the connector is fully engaged and the tab on the Plug-in card rests in the alignment slot on the display board.
3. Slide the meter base back into the case. Be sure the rear cover latches fully into the case.
4. Apply the Plug-in card label to the bottom side of the meter in the designated area. Do Not Cover the vents on the top surface of the meter. The surface of the case must be clean for the label to adhere properly.
Alignment
Slots
TOP VIEW
Main
Circuit
Board
Connectors
Serial
Communications
Card
Finger
Hold
Analog Output
Card
Setpoint
Output
Card
Finger
Hold
Quad Sourcing Open Collector Output Card Supply Select
* If installing the Quad sourcing Plug-in Card (PAXCDS40), set the jumper for internal or external supply operation before continuing.
Internal Supply
(18 V unregulated)
External Supply
8
4.0 W
IRING THE
M
ETER
WIRING OVERVIEW
Electrical connections are made via screw-clamp terminals located on the back of the meter. All conductors should conform to the meter’s voltage and current ratings. All cabling should conform to appropriate standards of good installation, local codes and regulations. It is recommended that the power supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.
When wiring the meter, compare the numbers embossed on the back of the meter case against those shown in wiring drawings for proper wire position.
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed (stranded wires should be tinned with solder.) Insert the lead under the correct screwclamp terminal and tighten until the wire is secure. (Pull wire to verify tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).
EMC INSTALLATION GUIDELINES
Although this meter is designed with a high degree of immunity to Electro-
Magnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into the meter may be different for various installations. The meter becomes more immune to EMI with fewer I/O connections. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation.
Listed below are some EMC guidelines for successful installation in an industrial environment.
1. The meter should be mounted in a metal enclosure, which is properly connected to protective earth.
2. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually when the noise source frequency is above 1 MHz.
c. Connect the shield to common of the meter and leave the other end of the shield unconnected and insulated from earth ground.
3. Never run Signal or Control cables in the same conduit or raceway with AC power lines, conductors feeding motors, solenoids, SCR controls, and heaters, etc. The cables should be ran in metal conduit that is properly grounded. This is especially useful in applications where cable runs are long and portable two-way radios are used in close proximity or if the installation is near a commercial radio transmitter.
4. Signal or Control cables within an enclosure should be routed as far as possible from contactors, control relays, transformers, and other noisy components.
5. In extremely high EMI environments, the use of external EMI suppression devices, such as ferrite suppression cores, is effective. Install them on Signal and Control cables as close to the unit as possible. Loop the cable through the core several times or use multiple cores on each cable for additional protection. Install line filters on the power input cable to the unit to suppress power line interference. Install them near the power entry point of the enclosure. The following EMI suppression devices (or equivalent) are recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC# FCOR0000)
TDK # ZCAT3035-1330A
Steward # 28B2029-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC# LFIL0000)
Schaffner # FN670-1.8/07
Corcom # 1 VR3
Note: Reference manufacturer’s instructions when installing a line filter.
6. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
7. Switching of inductive loads produces high EMI. Use of snubbers across inductive loads suppresses EMI.
Snubber: RLC# SNUB0000.
4.1 POWER WIRING
AC Power
Terminal 1: VAC
Terminal 2: VAC
1 2
DC Power
Terminal 1: +VDC
Terminal 2: -VDC
1 2
+ -
4.2 USER INPUT WIRING
Before connecting the wires, the User Input Logic Jumper should be verified for proper position. If User Input 1 and/ or 2 are wired for quadrature or directional counting, an additional switching device should not be connected to that User
Input terminal. Only the appropriate User Input terminal has to be wired.
Sinking Logic
Terminals 7-9
Terminal 10
} Connect external switching device between the appropriate User Input terminal and User Comm.
The user inputs of the meter are internally pulled up to +12 V with 5.1 K resistance. The input is active when it is pulled low (<0 .9 V).
USER INPUTS
Sourcing Logic
Terminals 7-9:
+ VDC through external switching device
Terminal 10:
-VDC through external switching device
The user inputs of the meter are internally pulled down to 0 V with 5.1 K resistance.
The input is active when a voltage greater than 3.6 VDC is applied.
7 8 9 10 7
USER INPUTS
8 9 10
+
V
SUPPLY
-
(30V max.)
9
4.3 INPUT WIRING
CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safety of the meter application, the sensor input common must be suitably isolated from hazardous live earth referenced voltage; or input common must be at protective earth ground potential. If not, hazardous voltage may be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the potential of the user input common with respect to earth ground; and the common of the isolated plug-in cards with respect to input common.
If you are wiring Input B, connect signal to Terminal 6 instead of 5, and set DIP switches 4, 5, and 6 to the positions shown for 1, 2, and 3.
Magnetic Pickup AC Inputs From Tach Generators, Etc.
Input A
Two Wire Proximity, Current Source
Input A
Input A
Current Sinking Output
Input A
Current Sourcing Output
Input A
Interfacing With TTL
Input A
Switch or Isolated Transistor; Current Sink
Input A
Switch or Isolated Transistor; Current Source
Input A
Emitter Follower; Current Source
Input A
Current Sink Output; Quad/Direction
Single Counter A
Current Sink Output; Quad/Direction
Counter A
& Rate B
Current Sink Output; Quad/Direction
Counter A &
Counter B
If using single Counter B, then wire signal to 6, and Quad/Direction to 8. Set switch positions
4, 5, and 6 as shown for 1, 2, and 3.
Switch position is application dependent.
User Input Jumper in Sink Position
4.4 SETPOINT (ALARMS) WIRING
SETPOINT PLUG-IN CARD TERMINALS
User Input Jumper in Sink Position
Shaded areas not recommended for counting applications.
SOURCING OUTPUT LOGIC CARD
SINKING OUTPUT LOGIC CARD
10
4.5 PAXI SERIAL COMMUNICATION WIRING
RS232 Communications
PAX METER (DTE)
12
TXD RXD
RECEIVING DEVICE
DB25
DCE
2
DB25
DTE
3
DB9
DTE
2
RS485 Communications
The RS485 communication standard allows the connection of up to 32 devices on a single pair of wires, distances up to 4,000 ft. and data rates as high as 10M baud (the PAX is limited to 19.2k baud). The same pair of wires is used to both transmit and receive data. RS485 is therefore always half-duplex, that is, data cannot be received and transmitted simultaneously.
13
RXD TXD
3 2 3
14
COMM.
5 7 5
15 NC
Terminal Block Connection Figure
Transmit
Enable B( )
5
9
6
1
PIN 2 TXD
PIN 3 RXD
PIN 5 COMMON
FEMALE
Extended Comms Connection Figure
RS232 is intended to allow two devices to communicate over distances up to
50 feet. Data Terminal Equipment (DTE) transmits data on the Transmitted Data
(TXD) line and receives data on the Received Data (RXD) line. Data Computer
Equipment (DCE) receives data on the TXD line and transmits data on the RXD line. The PAX emulates a DTE. If the other device connected to the meter also emulates a DTE, the TXD and RXD lines must be interchanged for communications to take place. This is known as a null modem connection. Most printers emulate a DCE device while most computers emulate a DTE device.
Some devices cannot accept more than two or three characters in succession without a pause in between. In these cases, the meter employs a busy function.
As the meter begins to transmit data, the RXD line (RS232) is monitored to determine if the receiving device is “busy”. The receiving device asserts that it is busy by setting the RXD line to a space condition (logic 0). The meter then suspends transmission until the RXD line is released by the receiving device.
COMM.
*
* OPTIONAL
Terminal Block Connection Figure
2 3 4 5
PAX CONNECTOR
Extended Comms Connection Figure
4.6 PAXI ANALOG OUTPUT WIRING
ANALOG OPTION CARD FIELD TERMINALS
16 +
0-10V
ANALOG
OUTPUT
17 -
18 +
19 -
0-20mA
ANALOG
OUTPUT
4.7 PAXI PRESCALER OUTPUT WIRING
5.0 R
EVIEWING THE
F
RONT
B
UTTONS AND
D
ISPLAY
Counter
Readout
Legends*
A
B
C
8.8.8.8.8.8
SP1 SP2 SP3 SP4
DSP PAR F1 F2 RST
Setpoint Alarm
Annunciators
KEY
DSP
PAR
F1
F2
RST
DISPLAY MODE OPERATION
Index display through the selected displays.
Access Programming Mode
Function key 1; hold for 3 seconds for Second Function 1 **
Function key 2; hold for 3 seconds for Second Function 2 **
Reset (Function key) ***
* Counters B, and C are locked out in Factory Settings (PAXC and PAXI only).
** Factory setting for the F1, and F2 keys is NO mode.
*** Factory setting for the RST key is (Reset Display).
11
PROGRAMMING MODE OPERATION
Quit programming and return to Display Mode
Store selected parameter and index to next parameter
Increment selected parameter value or selections
Decrement selected parameter value or selections
Advances digit location in parameter values
6.0 P
ROGRAMMING THE
M
ETER
OVERVIEW
PROGRAMMING MENU
Shaded areas represent program access that is model dependent.
PROGRAMMING MODE ENTRY (PAR KEY)
The meter normally operates in the Display Mode. No parameters can be programmed in this mode. The Programming Mode is entered by pressing the
PAR
key. If it is not accessible then it is locked by either a security code, or a hardware lock.
Two types of programming modes are available. Quick Programming Mode permits only certain parameters to be viewed and/or modified. All meter functions continue to operate except the front panel keys change to Programming
Mode Operations. Quick Programming Mode is configured in Module 3. Full
Programming Mode permits all parameters to be viewed and modified. In this mode, incoming counts may not be recognized correctly, the front panel keys change to Programming Mode Operations and certain user input functions are disabled. Throughout this document, Programming Mode (without Quick in front) always refers to “Full” Programming.
MODULE ENTRY (ARROW & PAR KEYS)
The Programming Menu is organized into nine modules. These modules group together parameters that are related in function. The display will alternate between
and the present module. The arrow keys (
F1 and
F2 ) are used to select the desired module. The displayed module is entered by pressing the
PAR
key.
MODULE MENU (PAR KEY)
Each module has a separate module menu (which is shown at the start of each module discussion). The
PAR key is pressed to advance to a particular parameter to be changed, without changing the programming of preceding parameters.
After completing a module, the display will return to
. Programming may continue by accessing additional modules.
SELECTION / VALUE ENTRY (ARROW & PAR KEYS)
For each parameter, the display alternates between the present parameter and the selections/value for that parameter. The arrow keys (
F1 and
F2 ) are used to move through the selections/values for that parameter. Pressing the
PAR
key, stores and activates the displayed selection/value. This also advances the meter to the next parameter.
For numeric values, the
RST
key may be used to select a specific digit to be changed. Once a digit is selected, the arrow keys are used to increment or decrement that digit to the desired number.
PROGRAMMING MODE EXIT (DSP KEY or at
PAR KEY)
The Programming Mode is exited by pressing the
DSP
key (from anywhere in the Programming Mode) or the
PAR
key (with displayed). This will commit any stored parameter changes to memory and return the meter to the
Display Mode. If a parameter was just changed, the
PAR
key should be pressed to store the change before pressing the
DSP
key. (If power loss occurs before returning to the Display Mode, verify recent parameter changes.)
PROGRAMMING TIPS
It is recommended to start with Module 1 for counting and Module 4 for rate.
If lost or confused while programming, press the
DSP
key and start over. When programming is complete, it is recommended to record the parameter programming on the Parameter User Chart and lock out parameter programming with a user input or lock-out code.
FACTORY SETTINGS
Factory Settings may be completely restored in Module 9. This is a good starting point for programming problems. Most parameters can be left at their
Factory Settings without affecting basic start-up. These parameters are identified throughout the module explanations.
ALTERNATING SELECTION DISPLAY
In the explanation of the modules, the following dual display with arrows will appear. This is used to illustrate the display alternating between the parameter on top and the parameter’s Factory Setting on the bottom. In most cases, selections and values for the parameter will be listed on the right.
Indicates Program Mode Alternating Display
Parameter
Selection/Value
Factory Settings are shown.
6.1 MODULE 1 - C
OUNT
A & B I
NPUT
P
ARAMETERS
(
)
PAXC & I
PARAMETER MENU
x = Counter A or Counter B
Module 1 is the programming for Counter A, Counter B and the Prescaler Output. Counter B parameters follow the Prescaler parameters. For maximum input frequency, the counters should be set to mode NONE and the Prescaler to NO when they are not in use. When set to NONE or NO, the remaining related parameters are not accessible. A corresponding annunciator indicates the counter being shown in the Display
Mode. An Exchange Parameter Lists feature for scale factors and count load values is explained in Module 2.
12
COUNTER A OPERATING MODE
Select the operating mode for Counter A.
SELECTION
MODE
Count X1
Count X1 w/direction
Count X1 w/direction
Quad X1
Quad X2
Quad X4
Quad X1
Quad X2
Count X2
Count X2 w/direction
Count X2 w/direction
DESCRIPTION
Does not count.
Adds Input A falling edge.
Adds Input A falling edge if Input B is high.
Subtracts Input A falling edge if Input B is low.
Adds Input A falling edge if User 1 is high. Subtracts
Input A falling edge if User 1 is low.
Adds Input A rising edge when Input B is high.
Subtracts Input A falling edge when Input B is high.
Adds Input A rising edge when Input B is high and
Input A falling edge when Input B is low. Subtracts
Input A falling edge when Input B is high and Input A rising edge when Input B is low.
Adds Input A rising edge when Input B is high, Input
A falling edge when Input B is low, Input B rising edge when Input A is low, and Input B falling edge when Input A is high. Subtracts Input A falling edge when Input B is high, Input A rising edge when Input
B is low, Input B rising edge when Input A is high, and Input B falling edge when Input A is low.
Adds Input A rising edge when User 1 is high.
Subtracts Input A falling edge when User 1 is high.
Adds Input A rising edge when User 1 is high and
Input A falling edge when User 1 is low. Subtracts
Input A falling edge when User 1 is high and Input A rising edge when User 1 is low.
Adds Input A rising and falling edges.
Adds Input A rising and falling edges if Input B is high. Subtracts Input A rising and falling edge if
Input B is low.
Adds Input A rising and falling edges if User 1 is high. Subtracts Input A rising and falling edge if User
1 is low.
COUNTER A SCALE MULTIPLIER *
The number of input counts is multiplied by the scale multiplier and the scale factor to obtain the desired process value. A scale multiplier of 1 will result in only the scale factor affecting the display. (Details on scaling calculations are explained at the end of this section.)
COUNTER A COUNT LOAD VALUE *
to
When reset to count load action is selected, Counter A will reset to this value.
COUNTER A RESET POWER-UP *
Counter A may be programmed to reset at each meter power-up.
PAXI: PRESCALER OUTPUT ENABLE *
This enables the prescaler output. The prescaler output is useful for providing a lower frequency scaled pulse train to a PLC or another external counter. On each falling edge of Input A, the prescaler output register increments by the prescaler scale value ( ). When the register equals or exceeds 1.0000, a pulse is output and the register is lowered by 1.0000. The prescaler register is reset to zero whenever Counter A is reset (except for Setpoint Counter Auto
Reset). (See Prescaler Output Figure.)
COUNTER A RESET ACTION
When Counter A is reset, it returns to zero or Counter A count load value.
This reset action affects all Counter A resets, except the Setpoint Counter Auto
Reset in Module 6.
PAXI: PRESCALER SCALE VALUE *
to
The prescaler output frequency is the Input A frequency times the prescaler scale value.
COUNTER A DECIMAL POSITION
This selects the decimal point position for Counter A and any setpoint value assigned to Counter A. The selection will also affect Counter A scale factor calculations.
COUNTER A SCALE FACTOR
to
The number of input counts is multiplied by the scale factor and the scale multiplier to obtain the desired process value. A scale factor of 1.00000 will result in the display of the actual number of input counts. (Details on scaling calculations are explained at the end of this section.)
*
Factory Setting can be used without affecting basic start-up.
13
COUNTER B OPERATING MODE
Select the operating mode for Counter B.
SELECTION
MODE
Count X1
Count X1 w/direction
Quad X1
Quad X2
Count X2
Count X2 w/direction
DESCRIPTION
Does not count.
Adds Input B falling edge.
Adds Input B falling edge if User 2 is high. Subtracts
Input B falling edge if User 2 is low.
Adds Input B rising edge when User 2 is high.
Subtracts Input B falling edge when User 2 is high.
Adds Input B rising edge when User 2 is high and
Input B falling edge when User 2 is low. Subtracts
Input B falling edge when User 2 is high and Input B rising edge when User 2 is low.
Adds Input B rising and falling edges.
Adds Input B rising and falling edges if User 2 is high. Subtracts Input B rising and falling edge if
User 2 is low.
COUNTER B RESET POWER-UP *
Counter B may be programmed to reset at each meter power-up.
*
Factory Setting can be used without affecting basic start-up.
8 DIGIT COUNT VALUES
Any counter display value below -99999 or above 999999 (less decimal point) will consist of a two part display. This display alternates between the least 6 significant digits and the remaining most significant digits beginning with “ ” in the display. If the display exceeds ± 99999999 the display will roll to zero and continue counting. Outputs cannot be set to counter values above 6 digits. The annunciator, indicating the counter being displayed, will flash when the value is above 6 digits.
COUNTER B RESET ACTION
When Counter B is reset, it returns to zero or Counter B count load value.
This reset action affects all Counter B resets, except the Setpoint Counter Auto
Reset Action in Module 6.
COUNTER B DECIMAL POSITION
This selects the decimal point position for Counter B and any setpoint value assigned to Counter B. The selection will also affect Counter B scale factor calculations.
COUNTER B SCALE FACTOR
to
The number of input counts is multiplied by the scale factor and the scale multiplier to obtain the desired process value. A scale factor of 1.00000 will result in the display of the actual number of input counts. (Details on scaling calculations are explained at the end of this section.)
COUNTER B SCALE MULTIPLIER *
The number of input counts is multiplied by the scale multiplier and the scale factor to obtain the desired process value. A scale multiplier of 1 will result in only the scale factor affecting the display. (Details on scaling calculations are explained at the end of this section.)
COUNTER B COUNT LOAD VALUE *
to
When reset to count load action is selected, Counter B will reset to this value.
SCALING CALCULATIONS
Each counter has the ability to scale an input signal to a desired display value. This is accomplished by the counter mode (x-
), scale factor (x
), scale multiplier (x ) and decimal point (x ). The scale factor is calculated using:
SF (x ) = Desired Display Decimal DDD
(Number of pulses per ‘single’ unit x CM x SM)
Where:
Desired
Display
Decimal DDD
1
10
100
1000
10000
100000 x
0
0.0
0.00
0.000
0.0000
0.00000
Counter Decimal Selection
None
Tenths
Hundredths
Thousandths
Ten Thousandths
Hundred Thousandths
Number of pulses per ‘single’ unit: pulses per unit generated by the process (i.e. # of pulses per foot)
CM: Counter Mode(x ) times factor of the mode 1,2 or 4.
SM: Scale Multiplier (x ) selection of 1, 0.1 or 0.01.
Example:
1. Show feet to the hundredths (0.00) with 100 pulses per foot:
Scale Factor would be 100 / (100 x 1 x 1) = 1
(In this case, the scale multiplier and counter mode factor are 1)
2. Show feet with 120 pulses per foot: Scale Factor would be 1 / (120 x 1 x 1)
= 0.0083333. (In this case, the scale multiplier of 0.01 could be used: 1 / (120 x 1 x 0.01) = 0.83333 or show to hundredths (0.00): 100 / (120 x 1 x 1) =
0.8333.)
General Rules on Scaling
1. It is recommended that, the scale factor be as close as possible to, but not exceeding 1.00000. This can be accomplished by increasing or decreasing the counter decimal point position, using the scale multiplier, or selecting a different count mode.
2. To double the number of pulses per unit, use counter modes direction X2 or quad X2. To increase it by four times, use counter mode quad X4. Using these modes will decrease the maximum input frequency.
3. A scale factor greater than 1.00000 will cause Counter display rounding. In this case, digit jumps could be caused by the internal count register rounding the display. The precision of a counter application cannot be improved by using a scale factor greater than 1. 00000.
4. The number of pulses per single unit must be greater than or equal to the
DDD value for the scale factor to be less than or equal to one.
5. Lowering the scale factor can be accomplished by lowering the counter decimal position. (Example: 100 (Hundredths)/10 pulses = 10.000 lowering to 10 (Tenths)/10 = 1.000.)
14
6.2 MODULE 2 - U
SER
I
NPUT AND
F
RONT
P
ANEL
F
UNCTION
K
EY
P
ARAMETERS
(
)
PARAMETER MENU
Module 2 is the programming for rear terminal user inputs and front panel function keys.
Three rear terminal user inputs are individually programmable to perform specific meter control functions. While in the Display Mode, the function is executed when the user input transitions to the active state. (Refer to the user input specifications for active state response times.) Certain user input functions are disabled in “full” Programming Mode.
Three front panel function F1, F2 and RST keys are also individually programmable to perform specific meter control functions. While in the Display
Mode, the primary function is executed when the key is pressed. Holding the
F1 and F2 function keys for three seconds executes a secondary function. It is possible to program a secondary function without a primary function. The front panel key functions are disabled in both Programming Modes.
In most cases, if more than one user input and/or function key is programmed for the same function, the maintained (level trigger) actions will be performed while at least one of those user inputs or function keys are activated. The momentary (edge trigger) actions are performed every time any of those user inputs or function keys transition to the active state. All functions are available to both user inputs and function keys.
Some of the user functions have a sublist of parameters. The sublist is accessed when PAR is pressed at the listed function. The function will only be performed for the parameters entered as
. If a user input or function key is configured for a function with a sublist, then that sublist will need to be scrolled through each time to access the following user inputs or function keys parameters.
NO FUNCTION
With this selection, NO function is performed. This is the factory setting for all user inputs and function keys except the Reset (RST) Key.
NOTE: When a user input is used to accept a quad or directional input signal, then that user input should be programmed for NO function.
EXCHANGE PARAMETER LISTS
Two lists of values are available for , , , , , ,
, , , . The two lists are named and .
If a user input is used to select the list then
is selected when the user input is not active and and
is selected when the user input is active,
(maintained action). If a front panel key is used to select the list then the list will toggle for each key press, (momentary action). The meter will suspend ALL operations for approximately 1 msec. while the new values are loaded. The display will only indicate which list is active when the list is changed or when entering any Programming Mode.
To program the values for and , first complete the programming of all the parameters. Exit programming and switch to the other list. Re-enter programming and enter the values for
,
,
,
,
,
,
, , , . If any other parameters are changed then the other list values must be reprogrammed.
Shaded parameters do not apply to the PAXR.
PAXI: PRINT REQUEST
The meter issues a block print through the serial port when activated. The data transmitted during the print request is configured in Module 7. If the user input is still active after the transmission is complete (about 100 msec.), an additional transmission will occur. Only one transmission will take place with each function key depression. This selection will only function when a serial communications Plug-in card is installed in the meter.
PROGRAMMING MODE LOCK-OUT
Programming Mode is locked-out, as long as activated
(maintained action). In Module 3, certain parameters can be setup where they are still accessible during
Programming Mode Lockout. A security code can be configured to allow complete programming access during user input lockout.
Function keys should not be programmed for
.
ADVANCE DISPLAY
When activated (momentary action), the display advances to the next display that is not locked out from the Display Mode.
RESET DISPLAY
When activated (momentary action), the shown display is reset. This is the factory setting for the Reset (RST) Key.
15
PAXI: PRINT REQUEST AND RESET DISPLAYS
The meter issues a block print through the serial port when activated just like the Print Request function. In addition, when activated (momentary action), the meter performs a reset of the displays configured as . The print aspect of this action only functions when a serial communication plug-in card is installed.
The reset action functions regardless.
DISPLAY DESCRIPTION
Counter A
Counter B
Counter C
Maximum
Minimum
FACTORY
MAINTAINED (LEVEL) RESET AND INHIBIT
The meter performs a reset and inhibits the displays configured as long as activated (maintained action).
, as
DISPLAY
DESCRIPTION
Counter A
Counter B
Counter C
Maximum
Minimum
FACTORY
PAXR: MAINTAINED (LEVEL) RESET AND INHIBIT
The meter performs a reset and inhibits the displays configured as long as activated (maintained action).
, as
DISPLAY
DESCRIPTION
Maximum
Minimum
FACTORY
DEACTIVATE SETPOINT MAINTAINED (LEVEL)
The meter deactivates the setpoints configured as , as long as activated
(maintained action). This action only functions with a Setpoint card installed.
DISPLAY
DESCRIPTION
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
FACTORY
DEACTIVATE SETPOINT MOMENTARY (EDGE)
When activated (momentary action), the meter deactivates the setpoints configured as
. This action only functions with a Setpoint card installed.
DISPLAY
DESCRIPTION
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
FACTORY
MOMENTARY (EDGE) RESET
When activated (momentary action), the meter resets the displays configured as
. (Momentary resets improve max. input frequencies over maintained resets.)
DISPLAY
DESCRIPTION
Counter A
Counter B
Counter C
Maximum
Minimum
FACTORY
HOLD SETPOINT STATE
The meter holds the state of the setpoints configured as
, as long as activated (maintained action). This action only functions with a Setpoint plug-in card installed.
DISPLAY DESCRIPTION FACTORY
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
PAXR: MOMENTARY (EDGE) RESET
When activated (momentary action), the meter resets the displays configured as
. (Momentary resets improve max. input frequencies over maintained resets.)
DISPLAY DESCRIPTION
Maximum
Minimum
FACTORY
ACTIVATE SETPOINT MAINTAINED (LEVEL)
The meter activates the setpoints configured as , as long as activated
(maintained action). This action only functions with a Setpoint card installed.
DISPLAY
DESCRIPTION
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
FACTORY
DISPLAY
INHIBIT
The meter inhibits the displays configured as
(maintained action).
, as long as activated
DESCRIPTION
Counter A
Counter B
Counter C
Maximum
Minimum
FACTORY
ACTIVATE SETPOINT MOMENTARY (EDGE)
When activated (momentary action), the meter activates the setpoints configured as
. This action only functions with a Setpoint card installed.
DISPLAY
DESCRIPTION
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
FACTORY
STORE DISPLAY
The meter holds (freeze) the displays configured as , as long as activated
(maintained action). Internally the counters and max. and min. values continue to update.
DISPLAY DESCRIPTION FACTORY
Counter A
Counter B
Counter C
Maximum
Minimum
16
CHANGE DISPLAY INTENSITY LEVEL
When activated (momentary action), the display intensity changes to the next intensity level (of 4). The four levels correspond to Display Intensity Level
(
) settings of 0, 3, 8 & 15. The intensity level, when changed via the User
Input/ Function Key, is not retained at power-down, unless Quick Programming or Full Programming mode is entered and exited. The meter will power-up at the last saved intensity level.
6.3 MODULE 3 - D
ISPLAY AND
P
ROGRAM
L
OCK
-
OUT
P
ARAMETERS
(
)
3-LOC
PAR
x CNt
Counter x
Display
Lock-out
rAtE
Rate Display
Lock-out
HI
Max Display
Lock-out x = Counter A , Counter B, and then Counter C n = Setpoints 1 to 4
PARAMETER MENU
Pro
LO
Min Display
Lock-out
SP-n
Setpoint 1-4
Access
Counter x
Count Load
Access
x SCFAC
Scale
Factor x
Access
COdE
Security
Code
Shaded areas represent program access that is model dependent.
Module 3 is the programming for Display lock-out and “Full” and “Quick”
Program lock-out.
When in the Display Mode, the available displays can be read consecutively by repeatedly pressing the DSP key. An annunciator indicates the display being shown. These displays can be locked from being visible. It is recommended that the display be set to when the corresponding function is not used.
SELECTION
DESCRIPTION
Visible in Display Mode
Not visible in Display Mode
“Full” Programming Mode permits all parameters to be viewed and modified. This Programming Mode can be locked with a security code and/or user input. When locked and the PAR key is pressed, the meter enters a Quick
Programming Mode. In this mode, setpoint, count load and scale factor values can still be read and/or changed per the selections below. The Display Intensity
Level () parameter also appears whenever Quick Programming Mode is enabled, and the security code is greater than zero.
SELECTION
DESCRIPTION
Visible but not changeable in Quick Programming Mode
Visible and changeable in Quick Programming Mode
Not visible in Quick Programming Mode
SETPOINT 1 to 4 ACCESS LOCK-OUT *
The setpoint displays can be programmed for , , or (See the following table). Accessible only with the Setpoint Plug-in card installed.
COUNT LOAD A B C ACCESS LOCK-OUT *
These displays can be programmed for , , or .
SCALE FACTOR A B C ACCESS LOCK-OUT *
The Scale Factor values can be programmed for , , or .
COUNTER A B C DISPLAY LOCK-OUT *
RATE DISPLAY LOCK-OUT *
MAX. MIN. DISPLAY LOCK-OUT *
SECURITY CODE *
to
Entry of a non-zero value will cause the prompt to appear when trying to access the “Full” Programming Mode. Access will only be allowed after entering a matching security code or universal code of . With this lock-out, a user input would not have to be configured for Program Lock-out. However, this lock-out is overridden by an inactive user input configured for Program Lock-out.
These displays can be programmed for or .
*
Factory Setting can be used without affecting basic start-up.
Shaded areas are model dependent.
PROGRAMMING MODE ACCESS
SECURITY
CODE
USER INPUT
CONFIGURED
0
>0 not not
USER INPUT
STATE
————
————
WHEN PAR KEY IS
PRESSED
“FULL” PROGRAMMING MODE ACCESS
“Full” Programming Immediate access.
Quick Programming w/Display Intensity After Quick Programming with correct code # at prompt.
>0
Active Quick Programming w/Display Intensity After Quick Programming with correct code # at prompt.
>0
0
Not Active
Active
“Full” Programming
Quick Programming
Immediate access.
No access
0 Not Active “Full” Programming Immediate access.
Throughout this document, Programming Mode (without Quick in front) always refers to “Full” Programming (all meter parameters are accessible).
17
6.4 MODULE 4 - R
ATE
I
NPUT
P
ARAMETERS
(
)
-
PAXR & I
PARAMETER MENU
Module 4 is the programming for the Rate parameters. For maximum input frequency, Rate assignment should be set to when not in use. When set to
, the remaining related parameters are not accessible. The Rate value is shown with an annunciator of ‘ ’ in the Display Mode.
Note: For PAXR, is actually on the unit’s display and is actually on the unit’s display.
PAXI: RATE ASSIGNMENT
For measuring the rate (speed) of pulses on Input A, select . For Input
B select . This assignment is independent of the counting modes.
LOW UPDATE TIME (DISPLAY UPDATE) *
to seconds
The Low Update Time is the minimum amount of time between display updates for the Rate display. Values of 0.1 and 0.2 seconds will update the display correctly but may cause the display to appear unsteady. The factory setting of 1.0 will update the display every second minimum.
HIGH UPDATE TIME (DISPLAY ZERO) *
to seconds
The High Update Time is the maximum amount of time before the Rate display is forced to zero. (For more explanation, refer to Input Frequency
Calculation.) The High Update Time must be higher than the Low Update Time and higher than the desired slowest readable speed (one divided by pulses per second). The factory setting of 2.0, will force the display to zero for speeds below 0.5 Hz or a pulse every 2 seconds.
RATE DECIMAL POSITION
This selects the decimal point position for Rate, Minimum and Maximum rate displays and any setpoint value assigned to these displays. This parameter does not affect rate scaling calculations.
PAXI: LINEARIZER SEGMENTS
to
This parameter specifies the number of linear segments used for the Rate
Scaling function. Each linear segment has two scaling points which define the upper and lower endpoints of the segment. The number of segments used depends on the linearity of the process and the display accuracy required as described below.
Linear Application – 2 Scaling Points
Linear processes use a single segment (two scaling points) to provide a linear
Rate display from 0 up to the maximum input frequency. For typical zero based frequency measurements (0 Hz = 0 on display), leave
(factory setting).
For non-zero based 2 scaling point applications, set , to enter both the zero segment ( & ) and segment 1 ( & ).
18
Non-linear Application – Up to 10 Scaling Points
Non-linear processes may utilize up to nine segments (ten scaling points) to provide a piece-wise linear approximation representing the non-linear function.
The Rate display will be linear throughout each individual segment (i.e. between sequential scaling points). Thus, the greater the number of segments, the greater the conformity accuracy. Several linearization equations are available in the software.
About Scaling Points
Each Scaling Point is specified by two programmable parameters: A desired
Rate Display Value ( ) and a corresponding Rate Input Value ( ).
Scaling points are entered sequentially in ascending order of Rate Input Value.
Two scaling points must be programmed to define the upper and lower endpoints of the first linear segment. Setting , automatically factory sets the first scaling point to 0.0 for typical single segment, zero based applications.
When multiple segments are used, the upper scaling point for a given segment becomes the lower scaling point for the next sequential segment. Thus, for each additional segment used, only one additional scaling point must be programmed.
The following chart shows the Scaling Points, the corresponding Parameter mnemonics, and the Factory Default Settings for each point.
SEGMENT
1
2
3
4
5
6
7
8
9
SCALING
POINT
1
2
3
4
5
6
7
8
9
10
DISPLAY
PARAMETER
DISPLAY
DEFAULT
000000
001000
002000
003000
004000
005000
006000
007000
008000
009000
INPUT
PARAMETER
INPUT
DEFAULT
00000.0
01000.0
02000.0
03000.0
04000.0
05000.0
06000.0
07000.0
08000.0
09000.0
PAXI: RATE DISPLAY VALUE FOR SCALING POINT 1
to
Confirm the Rate Display Value for the first Scaling Point is 0. This parameter is automatically set to 0 and does not appear when
. (See Note)
PAXI: RATE INPUT VALUE FOR SCALING POINT 1
to
Confirm the Rate Input Value for the first Scaling Point is 0.0. (See Note)
Note: For all linear and most non-linear applications, the Scaling Point 1 parameters ( and ) should be set to 0 and 0.0 respectively.
Consult the factory before using any non-zero values for Scaling Point 1. These parameters are automatically set to 0 and do not appear when .
RATE DISPLAY VALUE FOR SCALING POINT 2
to
Enter the desired Rate Display Value for the second Scaling Point by using the arrow keys.
*
Factory Setting can be used without affecting basic start-up.
RATE INPUT VALUE FOR SCALING POINT 2
to
Enter the corresponding Rate Input Value for the second Scaling Point by using the arrow keys. Rate Input values for scaling points can be entered by using the Key-in or the Applied method described below.
Key-in Method:
Enter the Rate Input value (
) that corresponds to the entered Rate
Display value (
) by pressing the F1 or F2 keys. This value is always in pulses per second (Hz).
Applied Method:
Apply an external rate signal to the appropriate input terminals. At the Rate
Input Value ( ) press and hold the F1 and F2 keys at the same time. The applied input frequency (in Hz) will appear on the display. (To verify correct reading wait for at least the length of the Low Update Time. Then press and hold the F1 and F2 keys at the same time again. The new value should be ±
0.1% of the previous entered value.) Press PAR to enter the displayed frequency as the Rate Input value. To prevent the displayed value from being entered, press DSP. This will take the meter out of Programming Mode and the previous Rate Input value will remain.
RATE DISPLAY ROUND *
Rounding values other than one round the Rate display to the nearest increment selected (e.g. rounding of ‘5’ causes 122 to round to 120 and 123 to round to 125). Rounding starts at the least significant digit of the Rate display.
LOW CUT OUT *
to
The Low Cut Out value forces the Rate display to zero when the Rate display falls below the value entered.
MAXIMUM CAPTURE DELAY TIME *
to seconds
When the Rate value is above the present Maximum rate value for the entered amount of time, the meter will capture that Rate value as the new
Maximum value. A delay time helps to avoid false captures of sudden short spikes. Maximum detection will only function if Rate is assigned to Input A or
B. The Maximum rate value is shown with an annunciator of ‘
’ in the display and will continue to function independent of being displayed.
MINIMUM CAPTURE DELAY TIME *
to seconds
When the Rate value is below the present Minimum rate value for the entered amount of time, the meter will capture that Rate value as the new Minimum value. A delay time helps to avoid false captures of sudden short spikes.
Minimum detection will only function if Rate is assigned to Input A or B. The
Minimum rate value is shown with an annunciator of ‘ ’ in the display and will continue to function independent of being displayed.
RATE SCALING
To scale the Rate, enter a Scaling Display value with a corresponding Scaling
Input value. (The Display and Input values can be entered by Key-in or Applied
Methods.) These values are internally plotted to a Display value of 0 and Input value of 0 Hz. A linear relationship is formed between these points to yield a rate display value that corresponds to the incoming input signal rate. The PAXI and PAXR are capable of showing a rate display value for any linear process.
KEY-IN SCALING METHOD CALCULATION
If a display value versus input signal (in pulses per second) is known, then those values can be entered into Scaling Display ( x
) and Scaling Input
(
x
). No further calculations are needed.
If only the number of pulses per ‘single’ unit (i.e. # of pulses per foot) is known, then it can be entered as the Scaling Input value and the Scaling Display value will be entered as the following:
RATE PER
Second
Minute
Hour
DISPLAY (
1
60
3600
x ) INPUT ( x )
# of pulses per unit
# of pulses per unit
# of pulses per unit
NOTES:
1. If # of pulse per unit is less than 10, then multiply both Input and Display values by 10.
2. If # of pulse per unit is less than 1, then multiply both Input and Display values by 100.
3. If the Display value is raised or lowered, then Input value must be raised or lowered by the same proportion (i.e. Display value for per hour is entered by a third less (1200) then Input value is a third less of # of pulses per unit). The same is true if the Input value is raised or lowered, then
Display value must be raised or lowered by the same proportion.
4. Both values must be greater than 0.0.
EXAMPLE:
1. With 15.1 pulses per foot, show feet per minute in tenths. Scaling Display
= 60.0 Scaling Input = 15.1.
2. With 0.25 pulses per gallon, show whole gallons per hour. (To have greater accuracy, multiply both Input and Display values by 10.) Scaling Display
= 36000 Scaling Input = 2.5.
INPUT FREQUENCY CALCULATION
The meter determines the input frequency by summing the number of falling edges received during a sample period of time. The sample period begins on the first falling edge. At this falling edge, the meter starts accumulating time towards Low Update and High Update values. Also, the meter starts accumulating the number of falling edges. When the time reaches the Low
Update Time value, the meter looks for one more falling edge to end the sample period. If a falling edge occurs (before the High Update Time value is reached), the Rate display will update to the new value and the next sample period will start on the same edge. If the High Update Time value is reached (without receiving a falling edge after reaching Low Update Time), then the sample period will end but the Rate display will be forced to zero. The High Update
Time value must be greater than the Low Update Time value. Both values must be greater than 0.0. The input frequency calculated during the sample period, is then shown as a Rate value determined by either scaling method.
RATE DISPLAY EXCEEDED
If the rate of the input signal causes a display that exceeds the capacity of the
Rate display (5 digits, 99999), then the display will indicate an overflow condition by showing “
”. During this overflow condition, the Minimum and Maximum rate values will stay at their values even during resets.
*
Factory Setting can be used without affecting basic start-up.
19
6.5 MODULE 5 - C
OUNTER
C I
NPUT
P
ARAMETERS
(
)
PAXC & I
PARAMETER MENU
Module 5 is the programming for Counter C. For maximum input frequency, the counter operating mode should be set to
when not in use. When set to
the remaining related parameters are not accessible. The C annunciator indicates that Counter C is being shown in the Display Mode. An Exchange
Parameter List feature for scale factor and count load values is explained in
Module 2.
COUNTER C OPERATING MODE *
Select the operating mode for Counter C.
Does not count.
Counter C counts the incoming pulses from Counter A input as per Counter A mode of operation. The signal is scaled only according to Counter C parameters.
Counter C counts the incoming pulses from Counter A and B inputs as per Counter A and B modes of operation. The result is scaled only according to Counter C parameters. (Example:
If Counter A is set for Count X1 mode and Counter B is set for Count X2 mode, then Counter C will increment by 1 for each pulse received on Input A and increment by 2 for each pulse received on Input B less any effects of scaling.)
Counter C counts the incoming pulses from Counter A and B inputs as per Counter A and B modes of operation and subtracts the B counts from the A counts. The result is scaled only according to Counter C parameters. (Example: If
Counter A is set for Count X1 mode and Counter B is set for
Count X2 mode, then Counter C will increment by 1 for each pulse received on Input A and decrement by 2 for each pulse received on Input B less any effects of scaling.)
Note: When using Add Ab or Sub Ab, Counter A, B and C must all be reset at the same time for the math to be performed on the display values.
(PAXI only)
See Serial Communications for details.
COUNTER C SCALE FACTOR
to
The number of input counts is multiplied by the scale factor and the scale multiplier to obtain the desired process value. A scale factor of 1.00000 will result in the display of the actual number of input counts. For (Numeric transmissions) modes of operation, the input signal is scaled directly. For
and modes of operation, the math is performed on the input signals and then the result is scaled. To achieve correct results, both Input A and Input
B must provide the same amount of pulses per unit of measurement. (Details on scaling calculations are explained at the end of Module 1 section.)
COUNTER C SCALE MULTIPLIER
The number of input counts is multiplied by the scale multiplier and the scale factor to obtain the desired process value. A scale multiplier of 1 will result in only the scale factor affecting the display. (Details on scaling calculations are explained at the end of Module 1 section.)
COUNTER C COUNT LOAD VALUE
to
When reset to count load action is selected, Counter C will reset to this value.
COUNTER C RESET POWER-UP *
Counter C may be programmed to reset at each meter power-up.
COUNTER C RESET ACTION
When Counter C is reset, it returns to zero or Counter C count load value.
This reset action affects all Counter C resets, except the Setpoint Counter Auto
Reset Action in Module 6.
COUNTER C DECIMAL POSITION
This selects the decimal point position for Counter C and any setpoint value assigned to Counter C. The selection will also affect Counter C scale factor calculations.
20
*
Factory Setting can be used without affecting basic start-up.
6.6 MODULE 6 - S
ETPOINT
(A
LARM
) P
ARAMETERS
(
)
6-SPt
PAR
SPSEL
Setpoint
Select
Lit-n
Setpoint
Annunciators
OUt-n
Output
Logic
SUP-n
Power-up
State
PARAMETER MENU
ACt-n
Setpoint
Action
ASN-n
Setpoint
Assignment
SP-n
Setpoint
Value
trC-n
Setpoint
Tracking
tYP-n
Boundary
Type
PAR
Stb-n
Standby
Operation
HYS-n
Setpoint
Hysteresis
tOFF-n
Off Time
Delay
tON-n
On Time
Delay
tOUt-n
Time-out
Value
AUtO-n
Counter
Auto Reset
rSd-n rSAS-n
Reset
W/Display
Reset
Reset w/SPn+1
Activates
rSAE-n
Reset w/SPn+1
Deactivates
Module 6 is the programming for the setpoint (alarms) output parameters. To have setpoint outputs, a setpoint Plug-in card needs to be installed into the PAX (see Ordering Information). Depending on the card installed, there will be two or four setpoint outputs available. This section replaces the bulletin that comes with the setpoint plug-in card. Please discard the separate literature when using the Plug-in card with the Digital PAX. For maximum input frequency, unused Setpoints should be configured for action.
The setpoint assignment and the setpoint action determine certain setpoint feature availability. The chart below illustrates this.
Pro
PARAMETER DESCRIPTION
SETPOINT PARAMETER AVAILABILITY
Annunciators
Output Logic
Power Up State
Setpoint Value
Setpoint Tracking
Boundary Type
Standby Operation
Setpoint Hysteresis
Setpoint Off Delay
Setpoint On Delay
Setpoint Time Out
Counter Auto Reset
Reset With Display Reset
Reset When SPn+1 Activates
Reset When SPn+1 Deactivates
TIMED OUT
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
No
No
No
No
RATE
BOUNDARY
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
LATCH
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
Yes
No
No
TIMED OUT
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
COUNTER
BOUNDARY
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
Yes
Yes
No
No
No
No
No
No
Yes
Yes
Yes
Yes
LATCH
Yes
Yes
Yes
SETPOINT SELECT
Select a setpoint (alarm output) to open the remaining module menu. (The
“ ” in the following parameters will reflect the chosen setpoint number.) After the chosen setpoint is programmed, the display will default to
. Select the next setpoint to be programmed and continue the sequence for each setpoint.
Pressing PAR at will exit Module 6.
SETPOINT OUTPUT LOGIC *
Normal (
) turns the output “on” when activated and “off” when deactivated. Reverse (
) turns the output “off” when activated and “on” when deactivated.
SETPOINT ANNUNCIATORS*
disables the display of the setpoint annunciator. Normal ( ) displays the corresponding setpoint annunciator of an “on” alarm output. Reverse (
) displays the corresponding setpoint annunciator of an “off” alarm output.
flashes the display and the corresponding setpoint annunciator of an
“on” alarm output.
21
SETPOINT POWER UP STATE *
will restore the output to the same state it was at before the meter was powered down. will activate the output at power up. will deactivate the output at power up.
*
Factory Setting can be used without affecting basic start-up.
SETPOINT ACTION
: When not using a setpoint, it should be set to (no action).
For Counter Assignments:
With Latch action, the setpoint output activates when the count value equals the setpoint value. The output remains active until reset. This action is not associated with Boundary types.
With boundary action, the setpoint output activates when the count value is greater than or equal to (for = ) or less than or equal to (for = ) the setpoint value. The setpoint output will deactivate when the count value is less than (for = ) or greater than (for = ) the setpoint value.
With Timed Out action, the setpoint output activates when the count value equals the setpoint value and deactivates after the
Time Out value. This action is not associated with Boundary types.
For Rate Assignments:
With Latch action, the setpoint output activates when the rate value is equal to the setpoint value. The setpoint output remains active until reset. If after reset, the rate value is greater than or equal to (for = ) or less than or equal to (for = ) the setpoint value, the output will reactivate.
With Boundary action, the setpoint output activates when the rate value is greater than or equal to (for = ) or less than or equal to (for = ) the setpoint value. The setpoint output will deactivate (Auto reset) as determined by the hysteresis value.
With Timed Out action, the setpoint output cycles when the rate value is greater than or equal to (for = ) or less than or equal to (for = ) the setpoint value. The Setpoint Time Out
( ) and Setpoint On Delay ( ) values determine the cycling times.
PAXC & I: SETPOINT ASSIGNMENT
Select the display that the setpoint is to be assigned.
SETPOINT STANDBY OPERATION *
Selecting
will disable low acting setpoints at a power up until the display value crosses into the alarm “off” area. Once in the alarm “off” area, the setpoint will function according to the configured setpoint parameters.
PAXI & R: SETPOINT HYSTERESIS *
to
The hysteresis value is added to (for
=
), or subtracted from (for
=
), the setpoint value to determine at what value to deactivate the associated setpoint output. Hysteresis is only available for setpoints assigned to the Rate with boundary action.
PAXI & R: SETPOINT OFF DELAY *
to seconds
This is the amount of time the Rate display must meet the setpoint deactivation requirements (below hysteresis for high acting and above hysteresis for low acting) before the setpoint’s output deactivates.
PAXI & R: SETPOINT ON DELAY *
to seconds
This is the amount of time the Rate display must meet the setpoint activation requirements (below setpoint for
=
and above setpoint for
=
) before the setpoint’s output activates. If the Rate Setpoint Action is Timed Out, this is the amount of time the output is off during the on / off output cycling.
SETPOINT VALUE
to
Enter the desired setpoint value. Setpoint values can also be entered in the
Quick Programming Mode when the setpoint is configured as in Module 3.
(See Module 2 for Exchange Parameter Lists explanation.)
SETPOINT TIME OUT *
to seconds
If the setpoint action is Timed Out and the setpoint is assigned to Rate, then this is the amount of time the output is on during the on / off output cycling. If the setpoint action is Timed Out and the setpoint is assigned to Count, then this is the amount of time the output will activate once the count value equals the setpoint value.
SETPOINT TRACKING *
If a selection other than NO is chosen, then the value of the setpoint being programmed (“n”) will track the entered selection’s value. Tracking means that when the selection’s value is changed (in the Quick Programming Mode), the
“n” setpoint value will also change (or follow) by the same amount.
SETPOINT BOUNDARY TYPE
activates the output when the assigned display value ( ) equals or exceeds the setpoint value. activates the setpoint when the assigned display value is less than or equal to the setpoint.
PAXC & I: COUNTER AUTO RESET *
This automatically resets the display value of the Setpoint Assignment
( ) counter each time the setpoint value is reached. This reset may be different than the Counter’s Reset Action (x
) in Module 1 or 5.
SELECTION ACTION
No auto reset.
Reset to zero at the start of output activation.
Reset to count load value at the start of output activation.
Reset to zero at the end of output activation. ( action only).
Reset to count load value at the end of output activation. ( action only).
*
Factory Setting can be used without affecting basic start-up.
22
PAXC & I: SETPOINT RESET WITH DISPLAY RESET *
Select
, so the setpoint output will deactivate (reset) when the Setpoint
Assignment (
) counter display resets. The only exception is if the assigned counter is reset by a Counter Auto reset generated by another setpoint.
PAXC & I: SETPOINT RESET WHEN SPn+1 DEACTIVATES *
Select
, so the setpoint output will deactivate (reset) when SPn +1 activates and then times out (deactivates). This function may only be used if the
SPn+1 is programmed for Setpoint Action of . (Example SP1 deactivates when SP2 is activated and then times out.) The last setpoint will wrap around to the first.
PAXC & I: SETPOINT RESET WHEN SPn+1 ACTIVATES *
Select
, so the setpoint output will deactivate (reset) when SPn +1 activates. (Example: SP1 deactivates when SP2 activates and SP4 when SP1 activates.) The last setpoint will wrap around to the first.
*
Factory Setting can be used without affecting basic start-up.
PAXR & I: SETPOINT (ALARM) FIGURES FOR RATE
(For Reverse Action, The Alarm state is opposite.)
LOW ACTING WITH NO DELAY LOW ACTING WITH DELAY
HIGH ACTING WITH NO DELAY HIGH ACTING WITH DELAY
HIGH ACTING WITH TIMEOUT LOW ACTING WITH TIMEOUT
23
6.7 MODULE 7 - S
ERIAL
C
OMMUNICATIONS
P
ARAMETERS
(
)
PAXI O
NLY PARAMETER MENU
Module 7 is the programming module for the Serial Communications
Parameters. These parameters are used to match the serial settings of the PAXI with those of the host computer or other serial device, such as a terminal or printer. This programming module can only be accessed if an RS232 or RS485
Serial Communications card is installed.
This section also includes an explanation of the commands and formatting required for communicating with the PAXI. In order to establish serial communications, the user must have host software that can send and receive
ASCII characters. Red Lion's SFPAX software can be used for configuring the
PAXI (See Ordering Information). For serial hardware and wiring details, refer to section 4.5 Serial Communication Wiring.
This section replaces the bulletin shipped with the RS232 and RS485 serial communications plug-in cards. Discard the separate bulletin when using those serial plug-in cards with the PAXI. Also, this section does NOT apply to the
DeviceNet, Modbus, or Profibus-DP communication cards. For details on the operation of the Fieldbus cards, refer to the bulletin shipped with each card.
METER UNIT ADDRESS
to
Enter the serial meter (node) address. With a single unit, an address is not needed and a value of zero can be used. With multiple units (RS485 applications), a unique 2 digit address number must be assigned to each meter.
ABBREVIATED PRINTING
Select
for full print or Command T transmissions (meter address, parameter data and mnemonics) or for abbreviated print transmissions
(parameter data only). This will affect all the parameters selected in the print options. (If the meter address is 00, it will not be sent during a full transmission.)
BAUD RATE
Set the baud rate to match the other serial communications equipment on the serial link. Normally, the baud rate is set to the highest value that all the serial equipment are capable of transmitting and receiving.
DATA BIT
Select either 7 or 8 bit data word lengths. Set the word length to match the other serial communications equipment on the serial link.
PARITY BIT
Set the parity bit to match that of the other serial communications equipment on the serial link. The meter ignores the parity when receiving data and sets the parity bit for outgoing data. If no parity is selected with 7 bit word length, an additional stop bit is used to force the frame size to 10 bits.
PRINT OPTIONS
- Enters the sub-menu to select the meter parameters to appear during a print request. For each parameter in the sub-menu, select
for that parameter information to be sent during a print request or for that parameter information not to be sent. A print request is sometimes referred to as a block print because more than one parameter information (meter address, parameter data and mnemonics) can be sent to a printer or computer as a block.
PARAMETER DESCRIPTION
Counter A
Counter B
Counter C
Rate
Max. & Min.
A B C Scale Factors
A B C Count Load
1 2 3 4 Setpoints *
*Setpoints are plug-in card dependent.
FACTORY MNEMONIC
CTA
CTB
CTC
RTE
MIN MAX
SFA SFB SFC
LDA LDB LDC
SP1 SP2 SP3 SP4
24
SENDING SERIAL COMMANDS AND DATA
When sending commands to the meter, a string containing at least one command character must be constructed. A command string consists of a command character, a value identifier, numerical data (if writing data to the meter) followed by a the command terminator character * or $. The <CR> is also available as a terminator when Counter C is in the SLAVE mode.
Command Chart
Command Description
N
T
V
R
P
Notes
Node (Meter) Address
Specifier
Transmit Value (read)
Address a specific meter. Must be followed by two digit node address. Not required when address = 00.
Read a register from the meter. Must be followed by register ID character.
Value change (write)
Reset
Write to register of the meter. Must be followed by register ID character and numeric data.
Reset a register or output. Must be followed by register ID character
Block Print Request
(read)
Initiates a block print output. Registers are defined in programming.
Command String Construction
The command string must be constructed in a specific sequence. The meter does not respond with an error message to invalid commands. The following procedure details construction of a command string:
1. The first characters consist of the Node Address Specifier (N) followed by a
2 character address number. The address number of the meter is programmable.
If the node address is 0, this command and the node address itself may be omitted. This is the only command that may be used in conjunction with other commands.
2. After the optional address specifier, the next character is the command character.
3. The next character is the Register ID. This identifies the register that the command affects. The P command does not require a Register ID character.
It prints according to the selections made in print options.
4. If constructing a value change command (writing data), the numeric data is sent next.
5. All command strings must be terminated with the string termination characters *, $ or when Counter C is set for slave mode <CR>. The meter does not begin processing the command string until this character is received.
See Timing Diagram figure for differences between terminating characters.
Q
S
L
M
O
J
K
U
W
X
F
G
H
I
C
D
E
Register Identification Chart
ID VALUE DESCRIPTION
REGISTER
NAME 1
COMMAND 2
A Count A
B Count B
CTA
CTB
T, V, R
T, V, R
TRANSMIT DETAILS 3
6 digit (V), 8 digit (T)
6 digit (V), 8 digit (T)
Count C
Rate
Min
Max
Scale Factor A
Scale Factor B
Scale Factor C
Count Load A
Count Load B
Count Load C
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
Auto/Manual Register
Analog Output Register
Setpoint Register
T, V
T, V
T, V
T, V, R
T, V, R
T, V, R
T, V, R
T, V
T, V
T, V
T, V, R
T, V
T, V, R
T, V, R
T, V
T, V
T, V
LDA
LDB
LDC
SP1
SP2
SP3
SP4
MMR
AOR
SOR
CTC
RTE
MIN
MAX
SFA
SFB
SFC
6 digit (V), 8 digit (T)
5 digit, positive only
5 digit, positive only
5 digit, positive only
6 digit, positive only
6 digit, positive only
6 digit, positive only
5 negative / 6 positive
5 negative / 6 positive
5 negative / 6 positive
5 negative / 6 positive
5 negative / 6 positive
5 negative / 6 positive
5 negative / 6 positive
0 - auto, 1 - manual
0 - 4095 normalized
0 - not active, 1 - active
1. Register Names are also used as Register Mnemonics during full transmission.
2. The registers associated with the P command are set up in Print Options (Module 7).
3. Unless otherwise specified, the Transmit Details apply to both T and V
Commands.
25
Command String Examples:
1. Address = 17, Write 350 to Setpoint 1
String: N17VM350$
2. Address = 5, Read Count A value, response time of 50 - 100 msec. min.
String: N05TA*
3. Address = 0, Reset Setpoint 4 output
String: RS*
Transmitting Data To the Meter
Numeric data sent to the meter must be limited to Transmit Details listed in the Register Identification Chart. Leading zeros are ignored. Negative numbers must have a minus sign. The meter ignores any decimal point and conforms the number to the scaled resolution. (ie. The meter’s scaled decimal point position is set for 0.0 and 25 is written to a register. The value of the register is now 2.5.
In this case, write a value of 250 to equal 25.0).
Note: Since the meter does not issue a reply to value change commands, follow with a transmit value command for readback verification.
Transmitting Data From the Meter
Data is transmitted from the meter in response to either a transmit command
(T), a print block command (P) or User Function print request. The response from the meter is either a full field transmission or an abbreviated transmission.
The meter response is established in Module 7.
Full Transmission
Byte
1, 2
3
4-6
7-18
19
20
21
22
23
Description
2 byte Node (Meter) Address field [00-99]
<SP> (Space)
3 byte Register Mnemonic field
12 byte numeric data field: 10 bytes for number, one byte for sign, one byte for decimal point
<CR> (Carriage return)
<LF> (Line feed)
<SP> (Space)
<CR> (Carriage return)
<LF> (Line feed)
These characters only appear in the last line of a block print.
The first two characters transmitted (bytes 1 and 2) are the unit address. If the address assigned is 00, two spaces are substituted. A space (byte 3) follows the unit address field. The next three characters (bytes 4 to 6) are the register mnemonic. The numeric data is transmitted next.
The numeric field (bytes 7 to 18) is 12 characters long. When the requested value exceeds eight digits for count values or five digits for rate values, an *
(used as an overflow character) replaces the space in byte 7. Byte 8 is always a space. The remaining ten positions of this field (bytes 9 to 18) consist of a minus sign (for negative values), a floating decimal point (if applicable), and eight positions for the requested value. The data within bytes 9 to 18 is right-aligned with leading spaces for any unfilled positions.
The end of the response string is terminated with <CR> (byte 19), and <LF>
(byte 20). When a block print is finished, an extra <SP> (byte 21), <CR> (byte
22), and <LF> (byte 23) are used to provide separation between the transmissions.
Abbreviated Transmission
These characters only appear in the last line of a block print.
13
14
15
16
17
Byte Description
1-12
12 byte data field, 10 bytes for number, one byte for sign, one byte for decimal point
<CR> (Carriage return)
<LF> (Line feed)
<SP> (Space)
<CR> (Carriage return)
<LF> (Line feed)
The abbreviated response suppresses the address and register mnemonics, leaving only the numeric part of the response.
Meter Response Examples:
1. Address = 17, full field response, Count A = 875
17 CTA 875 <CR><LF>
2. Address = 0, full field response, Setpoint 2 = -250.5
SP2 -250.5<CR><LF>
3. Address = 0, abbreviated response, Setpoint 2 = 250, last line of block print
250<CR><LF><SP><CR><LF>
Auto/Manual Mode Register (MMR) ID: U
This register sets the controlling mode for the outputs. In Auto Mode (0) the meter controls the setpoint and analog output. In Manual Mode (1) the outputs are defined by the registers SOR and AOR. When transferring from auto mode to manual mode, the meter holds the last output value (until the register is changed by a write). Each output may be independently changed to auto or manual. In a write command string (VU), any character besides 0 or 1 in a field will not change the corresponding output mode.
U abcde e = Analog Output d = SP4 c = SP3 b = SP2 a = SP1
Example: VU00011 places SP4 and Analog in manual.
Analog Output Register (AOR) ID: W
This register stores the present signal value of the analog output. The range of values of this register is 0 to 4095, which corresponds to the analog output range per the following chart:
Register Value
0
1
2047
4094
4095
0-20 mA
0.000
0.005
10.000
19.995
20.000
Output Signal*
4-20 mA
4.000
4.004
12.000
19.996
20.000
0-10V
0.000
0.0025
5.000
9.9975
10.000
*Due to the absolute accuracy rating and resolution of the output card, the actual output signal may differ 0.15% FS from the table values. The output signal corresponds to the range selected (0-20 mA, 4-20 mA or 0-10 V).
Writing to this register (VW) while the analog output is in the Manual Mode causes the output signal level to update immediately to the value sent. While in the Automatic Mode, this register may be written to, but it has no effect until the analog output is placed in the manual mode. When in the Automatic Mode, the meter controls the analog output signal level. Reading from this register (TW) will show the present value of the analog output signal.
Example: VW2047 will result in an output of 10.000 mA, 12.000 mA or
5.000V depending on the range selected.
Setpoint Output Register (SOR) ID: X
This register stores the states of the setpoint outputs. Reading from this register (TX) will show the present state of all the setpoint outputs. A “0” in the setpoint location means the output is off and a “1” means the output is on.
X abcd d = SP4 c = SP3 b = SP2 a = SP1
In Automatic Mode, the meter controls the setpoint output state. In Manual
Mode, writing to this register (VX) will change the output state. Sending any character besides 0 or 1 in a field or if the corresponding output was not first in manual mode, the corresponding output value will not change. (It is not necessary to send least significant 0s.)
Example: VX10 will result in output 1 on and output 2 off.
COUNTER C SLAVE COMMUNICATIONS
Counter C may be programmed for
, to act as a serial slave display. By doing this, the carriage return <CR> is added as a valid command terminator character for all serial command strings. The <CR> as a terminator may be very useful for standard serial commands, even if Counter C is never displayed or sent a slave message. The $ terminator should not be used in the slave mode. If numeric values are not to be saved to EPROM then send the value as a literal transmission with <CR> terminator.
The Counter C slave display is right aligned. It has a capacity of displaying six characters. When less than six characters are received, blank spaces will be placed in front of the characters. If more than six characters are sent, then only the last six are displayed. The meter has a 192 character buffer for the slave display. If more than 192 characters are sent, the additional characters are discarded until a terminator is received. Counter C processes numeric and literal transmissions differently.
Numeric Transmissions
When a string that does not begin with #, T, V, P or R is received, the meter processes it as a Numeric transmission. In this case, only the recognized numbers and punctuation are displayed. All other characters in the string are discarded. If a negative sign appears anywhere in the string the resulting number will be negative. Only the most significant decimal point is retained. If no numerical characters are received, then the numeric value will be zero. The numeric display can be used for setpoint (boundary action only) and analog output functions.
When using this display for setpoint and analog output values, the decimal point position must match the programming entered through the front panel. The numeric value is retained in Counter C memory until another Numeric transmission is received.
Recognized Numbers = 0, 1, 2, 3, 4, 5, 6, 7, 8, 9
Recognized Punctuation = period, comma, minus
Literal Transmissions
When a string that begins with # is received, the meter processes it as a Literal transmission. In this case, any unrecognized characters will be replaced with a space. A Literal display will replace a Numeric value in the Counter C display.
However, it will not remove a previous Numeric value from Counter C memory or prevent the Counter C outputs from functioning with the Numeric value.
Literal transmissions are only possible when using RS232 or RS485 cards.
Recognized Characters = a, b, c, d, e, f, g, h, i, j, l, n, o, p, q, r, s, t, u, y, z (in upper or lower case)
Recognized Numbers = 0, 1, 2, 3, 4, 5, 6, 7, 8, 9
Recognized Punctuation = period, comma, minus, blank
26
COMMAND RESPONSE TIME
The meter can only receive data or transmit data at any one time (half-duplex operation). During RS232 transmissions, the meter ignores commands while transmitting data, but instead uses RXD as a busy signal. When sending commands and data to the meter, a delay must be imposed before sending another command. This allows enough time for the meter to process the command and prepare for the next command.
At the start of the time interval t
1
, the computer program prints or writes the string to the com port, thus initiating a transmission. During t
1
, the command characters are under transmission and at the end of this period, the command terminating character (*, $ or slave only <CR>) is received by the meter. The time duration of t
1 the channel.
is dependent on the number of characters and baud rate of t
1
= (10 times the # of characters) / baud rate
At the start of time interval t
2
, the meter starts the interpretation of the command and when complete, performs the command function. This time interval t
2
varies (See Timing Diagrams). If no response from the meter is expected, the meter is ready to accept another command.
If the meter is to reply with data, the time interval t
2
is controlled by the use of the command terminating character. The ‘*’ or ‘<CR>’ terminating character results in a response time window of 50 msec. minimum and 100 msec. maximum. This allows sufficient time for the release of the sending driver on the RS485 bus. Terminating the command line with ‘$’ results in a response time window (t
2
) of 2 msec. minimum and 50 msec. maximum. The faster response time of this terminating character requires that sending drivers release within 2 msec. after the terminating character is received.
At the beginning of time interval t
3
, the meter responds with the first character of the reply. As with t
1
, the time duration of t
3
is dependent on the number of characters and baud rate of the channel. At the end of t
3 ready to receive the next command.
, the meter is
t
3
= (10 times the # of characters) / baud rate
The maximum serial throughput of the meter is limited to the sum of the times t
1
, t
2
and t
3
.
SERIAL TIMING
COMMAND
R
#
V
T
P
COMMENT PROCESS TIME (t
2
)
Numeric Slave 2-50 msec.
Reset
Literal
Write
Transmit
2-50 msec.
2-50 msec.
100-200 msec.
2-50 msec. for $
50-100 msec. for * and <CR>
2-50 msec. for $
50-100 msec. for * and <CR>
Timing Diagrams
NO REPLY FROM METER
RESPONSE FROM METER
COMMUNICATION FORMAT
Data is transferred from the meter through a serial communication channel.
In serial communications, the voltage is switched between a high and low level at a predetermined rate (baud rate) using ASCII encoding. The receiving device reads the voltage levels at the same intervals and then translates the switched levels back to a character.
The voltage level conventions depend on the interface standard. The table lists the voltage levels for each standard.
LOGIC INTERFACE STATE RS232*
1
0 mark (idle) space (active)
* Voltage levels at the Receiver
TXD,RXD; -3 to -15 V
TXD,RXD; +3 to +15 V
RS485* a-b < -200 mV a-b > +200 mV
Data is transmitted one byte at a time with a variable idle period between characters (0 to ). Each ASCII character is “framed” with a beginning start bit, an optional parity bit and one or more ending stop bits. The data format and baud rate must match that of other equipment in order for communication to take place. The figures list the data formats employed by the meter.
Start bit and Data bits
Data transmission always begins with the start bit. The start bit signals the receiving device to prepare for reception of data. One bit period later, the least significant bit of the ASCII encoded character is transmitted, followed by the remaining data bits. The receiving device then reads each bit position as they are transmitted.
Character Frame Figure
Parity bit
After the data bits, the parity bit is sent. The transmitter sets the parity bit to a zero or a one, so that the total number of ones contained in the transmission
(including the parity bit) is either even or odd. This bit is used by the receiver to detect errors that may occur to an odd number of bits in the transmission.
However, a single parity bit cannot detect errors that may occur to an even number of bits. Given this limitation, the parity bit is often ignored by the receiving device. The PAX meter ignores the parity bit of incoming data and sets the parity bit to odd, even or none (mark parity) for outgoing data.
Stop bit
The last character transmitted is the stop bit. The stop bit provides a single bit period pause to allow the receiver to prepare to re-synchronize to the start of a new transmission (start bit of next byte). The receiver then continuously looks for the occurrence of the start bit. If 7 data bits and no parity is selected, then 2 stop bits are sent from the PAXI.
27
6.8 MODULE 8 - A
NALOG
O
UTPUT
P
ARAMETERS
(
)
PAXI O
NLY
PARAMETER MENU
Pro 8-AnA
PAR
tYPE
Analog
Type
ASIN
Analog
Assignment
AN-LO
Analog Low
Scale Value
AN-HI
Analog High
Scale Value
Module 8 is the programming for the analog output parameters. To have an analog output signal, an analog output plug-in card needs to be installed (See
Ordering Information). This section replaces the bulletin that comes with the analog plug-in card. Please discard the separate literature when using the plugin card with the PAXI.
ANALOG TYPE
SELECTION RANGE
0 to 20 mA
4 to 20 mA
0 to 10 V
Enter the analog output type. For voltage output use terminals 16 and 17. For current output use terminals 18 and 19. Only one range can be used at a time.
ANALOG LOW SCALE VALUE
to
Enter the display value within the selected Analog Assignment that corresponds to the low limit of the type selected.
The decimal point is determined by the decimal point setting of the assigned counter or rate. The scale value can not be set to read values with more than 6 digits. Reverse acting output is possible by reversing the scaling values.
ANALOG ASSIGNMENT
Select the display that the analog output is to follow:
= Counter A Value
= Counter B Value
= Counter C Value
= Rate Value
= Minimum Value
= Maximum Value
ANALOG HIGH SCALE VALUE
to
Enter the display value within the selected Analog Assignment that corresponds to the high limit of the type selected.
The decimal point is determined by the decimal point setting of the assigned counter or rate. The scale value can not be set to read values with more than 6 digits. Reverse acting output is possible by reversing the scaling values.
6.9 MODULE 9 - F
ACTORY
S
ERVICE
O
PERATIONS
(
)
Pro 9-FCS
PAR
d-LEV
Display
Intensity Level
COdE
Factory
Service Code
PARAMETER MENU
DISPLAY INTENSITY LEVEL
Enter the desired Display Intensity Level (0-15) by using the arrow keys. The display will actively dim or brighten as the levels are changed. This parameter also appears in Quick Programming Mode when enabled.
RESTORE FACTORY DEFAULTS
Use the arrow keys to display and press PAR.
The meter will display and then returns to .
Press DSP key to return to the Display Mode. This will overwrite all user settings with the factory settings.
Pressing the PAR and DSP keys at the same time on power-up will load the factory settings and display . This allows operation in the event of a memory failure or corrupted data. Immediately press RST key and reprogram the meter. If the meter is powered down again before pressing the RST key, the existing dynamic data will not be overwritten.
28
PAXI: CALIBRATION
The only item in the PAXI meter that can be calibrated
is the Analog Output. The Count A and B values are scaled using the parameters in Module 1, Counter C value is scaled using Module 5 and the Rate value is scaled using Module
4. If the meter appears to be indicating incorrectly or inaccurately, refer to the
Troubleshooting section.
When Analog Out recalibration is required (generally every 2 years), it should be performed by qualified technicians using appropriate equipment.
Calibration does not change any user programmed parameters.
Calibration may be aborted by disconnecting power to the meter before exiting Module 9. In this case, the existing calibration settings remain in effect.
Note: Allow a 30 minute warm-up period before staring calibration.
Analog Output Card Calibration
Before starting, verify that a precision meter with an accuracy of 0.05% or better (voltmeter for voltage output and/or current meter for current output) is connected and ready. Then perform the following procedure:
1. Use the arrow keys to display and press PAR.
2.
is displayed. Use the arrow keys to select
and press PAR.
3. Using the chart below, step through the five selections to be calibrated. At each prompt, use the PAXI arrow keys to adjust the output so that the external meter display matches the selection being calibrated. When the external reading matches, or if the range is not being calibrated, press PAR.
SELECTION EXTERNAL METER ACTION
0.00
4.00
20.00
0.00
Adjust if necessary, press PAR
Adjust if necessary, press PAR
Adjust if necessary, press PAR
Adjust if necessary, press PAR
10.00
Adjust if necessary, press PAR
4. When
appears, press PAR twice and remove the external meters.
TROUBLESHOOTING
For further assistance, contact technical support at the appropriate company numbers listed.
PROBLEM
NO DISPLAY
PROGRAM LOCKED-OUT
CERTAIN DISPLAYS ARE LOCKED OUT
INCORRECT DISPLAY VALUE or NOT
COUNTING
USER INPUT NOT WORKING CORRECTLY
REMEDIES
CHECK: Power level, power connections
CHECK: Active (lock-out) user input
ENTER: Security code requested
CHECK: Module 3 programming
CHECK: Input wiring, DIP switch setting, input programming, scale factor calculation,
input signal level, user input jumper, lower input signal frequency
CHECK: User input wiring, user input jumper, user input being used for signal, Module 2
OUTPUT DOES NOT WORK
JITTERY DISPLAY
“ ” RATE
CHECK: Corresponding plug-in card installation, output configuration, output wiring
CHECK: Wiring is per EMC installation guidelines, input signal frequency, signal quality,
scaling, update time, DIP switch setting
CHECK: Lower input signal frequency, reduce rate scaling
MODULES or PARAMETERS NOT ACCESSIBLE CHECK: Corresponding plug-in card installation, related controlling parameter selected
ERROR CODE ( )
SERIAL COMMUNICATIONS
PRESS: Reset key (if unable to clear contact factory.)
CHECK: Wiring, connections, meter and host settings
Shaded areas are model dependent.
29
PARAMETER VALUE CHART Programmer ________________ Date ________
PAX Model Number _________ Meter# _____________ Security Code __________
Counter A & B Input Parameters - PAXC & I only
DISPLAY PARAMETER
FACTORY
SETTING
COUNTER A OPERATING MODE
COUNTER A RESET ACTION
COUNTER A DECIMAL POSITION
COUNTER A SCALE FACTOR (A)
COUNTER A SCALE FACTOR (B) *
COUNTER A SCALE MULTIPLIER
COUNTER A COUNT LOAD VALUE (A)
COUNTER A COUNT LOAD VALUE (B)*
COUNTER A RESET POWER-UP
PRESCALER OUTPUT ENABLE
PRESCALER SCALE VALUE
COUNTER B OPERATING MODE
COUNTER B RESET ACTION
COUNTER B DECIMAL POSITION
COUNTER B SCALE FACTOR (A)
COUNTER B SCALE FACTOR (B)*
COUNTER B SCALE MULTIPLIER
COUNTER B COUNT LOAD VALUE (A)
COUNTER B COUNT LOAD VALUE (B)*
COUNTER B RESET POWER-UP
USER SETTING
* See Module 2, Exchanging Parameter Lists, for details on programming this value.
Shaded areas are model dependent.
DISPLAY
User Input and Function Key Parameters
PARAMETER
USER INPUT 1
USER INPUT 2
USER INPUT 3
FUNCTION KEY 1
FUNCTION KEY 2
RESET KEY
2nd FUNCTION KEY 1
2nd FUNCTION KEY 2
FACTORY
SETTING
USER SETTING
Rate Input Parameters - PAXI & R only
DISPLAY
PARAMETER
RATE ASSIGNMENT
LOW UPDATE TIME
HIGH UPDATE TIME
RATE DECIMAL POINT
LINEARIZER SEGMENTS
SCALING PT. 1 - DISPLAY VALUE
SCALING PT. 1 - INPUT VALUE
SCALING PT. 2 - DISPLAY VALUE
SCALING PT. 2 - INPUT VALUE
SCALING PT. 3 - DISPLAY VALUE
SCALING PT. 3 - INPUT VALUE
SCALING PT. 4 - DISPLAY VALUE
SCALING PT. 4 - INPUT VALUE
SCALING PT. 5 - DISPLAY VALUE
SCALING PT. 5 - INPUT VALUE
SCALING PT. 6 - DISPLAY VALUE
SCALING PT. 6 - INPUT VALUE
SCALING PT. 7 - DISPLAY VALUE
SCALING PT. 7 - INPUT VALUE
SCALING PT. 8 - DISPLAY VALUE
SCALING PT. 8 - INPUT VALUE
SCALING PT. 9 - DISPLAY VALUE
SCALING PT. 9 - INPUT VALUE
SCALING PT. 10 - DISPLAY VALUE
SCALING PT. 10 - INPUT VALUE
RATE DISPLAY ROUNDING
MINIMUM LOW CUT OUT
MAX CAPTURE DELAY TIME
MIN CAPTURE DELAY TIME
Shaded areas are model dependent.
FACTORY
SETTING
USER SETTING
Display and Program Lockout Parameters
DISPLAY PARAMETER
COUNTER A DISPLAY LOCK-OUT
COUNTER B DISPLAY LOCK-OUT
COUNTER C DISPLAY LOCK-OUT
RATE DISPLAY LOCK-OUT
MAX DISPLAY LOCK-OUT
MIN DISPLAY LOCK-OUT
SETPOINT 1 ACCESS LOCK-OUT
SETPOINT 2 ACCESS LOCK-OUT
SETPOINT 3 ACCESS LOCK-OUT
SETPOINT 4 ACCESS LOCK-OUT
COUNT LOAD A ACCESS
COUNT LOAD B ACCESS
COUNT LOAD C ACCESS
SCALE FACTOR A ACCESS
SCALE FACTOR B ACCESS
SCALE FACTOR C ACCESS
SECURITY CODE
Shaded areas are model dependent.
FACTORY
SETTING
USER SETTING
Counter C Input Parameters - PAXC & I only
DISPLAY PARAMETER
FACTORY
SETTING
COUNTER C OPERATING MODE
COUNTER C RESET ACTION
COUNTER C DECIMAL POSITION
COUNTER C SCALE FACTOR (A)
COUNTER C SCALE FACTOR (B)*
COUNTER C SCALE MULTIPLIER
COUNTER C COUNT LOAD VALUE (A)
COUNTER C COUNT LOAD VALUE (B)*
COUNTER C RESET POWER-UP
USER SETTING
* See Module 2, Exchanging Parameter Lists, for details on programming this value.
30
Setpoint (Alarm) Parameters
PARAMETER DISPLAY
SETPOINT ANNUNCIATORS
SETPOINT OUTPUT LOGIC
SETPOINT POWER UP STATE
SETPOINT ACTION
SETPOINT ASSIGNMENT
SETPOINT VALUE (A)
SETPOINT VALUE (B)*
SETPOINT TRACKING
SETPOINT BOUNDARY TYPE
STANDBY OPERATION
SETPOINT HYSTERESIS (rate)
SETPOINT OFF DELAY
SETPOINT ON DELAY
SETPOINT TIME OUT
COUNTER AUTO RESET ACTION
SETPOINT RESET WITH DISPLAY
RESET WHEN SPn+1 ACTIVATES
RESET WHEN SPn+1 DEACTIVATES
FACTORY
SETTING
USER SETTING
FACTORY
SETTING
USER SETTING
FACTORY
SETTING
USER SETTING
FACTORY
SETTING
USER SETTING
* See Module 2, Exchanging Parameter Lists, for details on programming this value.
Shaded areas are model dependent.
Serial Communication Parameters - PAXI only
DISPLAY PARAMETER
BAUD RATE
DATA BIT
PARITY BIT
METER ADDRESS
ABBREVIATED PRINTING
PRINT COUNTER A
PRINT COUNTER B
PRINT COUNTER C
PRINT RATE
PRINT MAX & MIN
PRINT SCALE FACTORS
PRINT COUNT LOAD VALUES
PRINT SETPOINT VALUES
FACTORY
SETTING
USER SETTING
Analog Output Parameters - PAXI only
DISPLAY PARAMETER
FACTORY
SETTING
ANALOG TYPE
ANALOG ASSIGNMENT
ANALOG LOW SCALE VALUE
ANALOG HIGH SCALE VALUE
USER SETTING
Factory Service Parameters
DISPLAY
PARAMETER
DISPLAY INTENSITY LEVEL
FACTORY
SETTING
USER SETTING
LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and workmanship for a period limited to two years from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L.
92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L.
93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations.
31
PROGRAMMING QUICK OVERVIEW
32
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 Ordering Information
- 3 General Meter Specifications
- 4 PAXC Counter
- 4 PAXR Rate Meter
- 5 PAXI Counter/Rate Meter
- 6 Optional Plug-In Output Cards
- 7 Installing the Meter
- 7 Setting the Jumper and DIP Switches
- 8 Installing Plug-In Cards
- 9 Wiring the Meter
- 11 Reviewing the Front Buttons and Display
- 12 Programming the Meter
- 28 Factory Service Operations
- 29 Troubleshooting
- 30 Parameter Value Chart
- 32 Programming Overview