- Home
- Domestic appliances
- Large home appliances
- Dishwashers
- 3D Connexion
- mD4000-b
- Installation instructions
3D Connexion mD4000-b Dishwasher Installation instructions
Add to my manuals
23 Pages
3D Connexion mD4000-b is a powerful and versatile 3D mouse that can help you to work more efficiently and accurately in 3D applications. With its advanced features, such as six-degrees-of-freedom (6DoF) control, customizable buttons, and an ergonomic design, the 3D Connexion mD4000-b is the perfect tool for anyone who wants to take their 3D modeling and design skills to the next level.
advertisement
INSTALLATION INSTRUCTIONS
& REpLACEMENT pARTS LIST
MD4000 SERIES SOLID STATE
DUAL UNIT LEAD/LAG CONTROLLER for use with H-Series
Wall Mount Air Conditioners with F & G Spyder™ Economizers only
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
Since 1914...Moving ahead, just as planned.
Manual No.: 2100-574
Supersedes: NEW
File: Vol. III Tab 19
Date: 07-05-12
Manual 2100-574
Page 1 of 23
CONTENTS
Getting Other Information and publications 3
MD4000 General Information
Shipping Damage....................................................4
General ...................................................................4
Theory of Operation ................................................4
Controller Certifications ...........................................4
Specifications/Features for MD4000 Series Controller
MD4000 Controller ..................................................5
Mounting the Controller
Installation Instructions............................................5
Temperature Sensors
Two Optional Sensor Inputs ....................................5
Temperature Sensor Logic
Using Multiple Sensors ...........................................5
Basic MD4000 Controller Input/Output Specs.
MD4000 Controller Connections .............................6
Located in the MD4000 panel Box
Unit #1 & Unit #2 Terminal Block .............................6
Specifications/Features for Alarm Boards
MD4000-B & -BC w/Controller Alarms ....................7
Low Voltage Field Wiring
Circuitry in the MD4000...........................................7
Controller Grounding
Earth ground ...........................................................7
Controller power-Up
Time Delay on Power-Up ........................................7
Fire Suppression Circuit
Disabling the MD4000 .............................................8
Staging Delay periods
Stages 1 - 4 .............................................................8
Blower Operation
Various Blower Options ...........................................8
Advance (Swap) Lead/Lag Unit Feature
Manual Switching of Units .......................................8
Accelerate Timer Feature
Testing the Timer Function ......................................8
General programming Overview
Buttons & Function ..................................................9
Heating Sequence of Operation ............................10
Specifications Opt. Remote Comm. Board
CB4000 Communications Board ......................11-12
Controller Wiring
Refer to Connection Diagram................................13
Security (Locking) Feature
Locking and Unlocking the MD4000 .....................13
Generator Run / Economizer Shutdown Feature
Standby Generator Disable Operation ..................13
Backup DC power Connection
Input Connections Available ..................................13
Economizer Failure Alarm .....................................16
Dirty Filter Alarm ....................................................16
2-Compressor Run Alarm ......................................16
Alarm Wiring ...........................................................16
2nd Stage Cooling Alarm .......................................17
Refrigerant pressure Alarms .................................17
Spyder Economizer Displays ................................17
Emergency Ventilation Sequence .........................17
programming Instructions .....................................20
Figures
— — — MD4000 Flow Chart ................................10
Figure 1 Controller Connections 1-Stage (H**A/L ....
Series) A/C w/ECONWMT Econ. .............14
Figure 2 Controller Connections 1-Stage (H**A/L ...
Series) A/C w/ ECONWMT Econ. & w/Alarm
Board & CB4000 Comm. Board .............15
— — — Alarm LED Display Board ........................16
Figure 3 Alarm Board Connections for Normally ......
Closed "NC" Open-On-Alarm Strategy ....18
Figure 4 Alarm Board Connections for Normally Open
"NO" Close-On-Alarm Strategy ................................19
— — — MD4000 Label .........................................21
Figure 5 Parts List Description Diagram ................22
Tables
Controller Prog. Features & Defaults ........9
Table 1 Hook-Up Diagram Selection ....................14
Table Parts List .................................................23
Manual 2100-574
Page 2 of 23
Getting Other Information and Publications
These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Standard for the Installation ............... ANSI/NFPA 90A of Air Conditioning and
Ventilating Systems
FOr mOre InFOrmatIOn, cOntact these PublIshers:
ACCA Air Conditioning Contractors of America
1712 New Hampshire Avenue, NW
Washington, DC 20009
Standard for Warm Air Heating ......... ANSI/NFPA 90B and Air Conditioning Systems
ANSI
Telephone: (202) 483-9370
Fax: (202) 234-4721
American National Standards Institute
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900
Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigerating, and Air Conditioning Engineers, Inc.
1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305
Telephone: (404) 636-8400
Fax: (404) 321-5478
BARD Bard Manufacturing Company, Inc.
1914 Randolph Drive
Bryan, OH 43506
Telephone: (419) 636-1194
Fax: (419) 636-2640
Manual 2100-574
Page 3 of 23
** ImPOrtant **
The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
Please read entire manual before proceeding.
The MD4000 is equipped with the B alarm board.
Form C dry contact alarm relays are used, offering both NO and NC switching to meet the user’s specific alarm protocol, providing complete flexibility to meet any user's requirements. All alarm actuations are individually indicated on the controller front panel.
There is an Ethernet based remote communication option that can be either factory or field installed. See section on Communication Module.
shIPPInG DamaGe
Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
General
These instructions explain the operation, installation and troubleshooting of the MD4000 Series controller.
All internal wiring is complete. Only attach low voltage field wiring to designated terminal strips.
The MD4000 is for use with units with economizers.
Each unit should be sized to handle the total load of the structure if 100% redundancy is required.
The MD4000 controller is suitable for both 50 and 60
HZ operation. See Controller Programmable Features and Default Settings.
theOrY OF OPeratIOn
The controller is used to control two wall mount air conditioners from one control system. It provides total redundancy for the structure and equal wear on both units. It must be used with units with economizers and both units be equipped alike.
The MD4000 controller is configured for alternative
(lead/lag/lead/lag) sequence, which is default setting.
The MD4000 works in conjunction with the Economizer
Logic Modules to provide room temperature control based on the DC amp load that the building is using.
The Economizer Logic Modules, in the air conditioner, control the cooling stages and functions. The MD4000 controls the heating stages, lead lag operation and alarming operation for the system.
cOntrOller certIFIcatIOns
The MD4000 main controller board, alarm board, optional communication module, and remote sensors have undergone extensive testing for immunity and emissions. This system is FCC-compliant, in accordance with CE requirements, and meets the following standards:
MD4000 Series
Master Controller
This device complies with FCC Rule Part 15, Subpart
B, Class A. Operation is subject to the following two conditions:
1. This device may not cause harmful interference
2. This device must accept any interference received, including that which may cause undesired operation.
This device complies with CE Standards EN55011/
EN50081 and EN55024 for ISM Equipment, Class A.
This ISM device also complies with Canadian ICES – 001.
Bard Manufacturing Company, Inc.
Bryan, OH 43506
Manual 2100-574
Page 4 of 23
sPecIFIcatIOns/Features FOr mD4000-b cOntrOller
MD4000 Basic Controller
•Input power: 18-32 VAC, 60/50Hz, power is supplied from
A/C #1 and/or A/C #2
•Isolation circuitry: no line or low voltage phasing required
•Backup power: connection for -24 VDC or -48 VDC (-20 to
-56V) maintains microprocessor operation, front panel indication
& alarm relay operation during commercial power outages.
•Digital display: 4-character LCD
•Temperature display: F or C
•HVAC outputs: Form A (NO) relays (1A @ 24 VAC)
•Cooling control stages:
2 for each A/C unit (4 total)
•Heating Control stages:
1 for each A/C unit
•Operating temperature range: 0 to 120F (-18 to 49C)
•Storage temperature range: -20 to 140F (-29 to 60C)
•Temperature accuracy: +/- 1F from 60-85F (16-30C)
+/- 1% outside 60-85F
•Lead/lag changeover time: 0 to 30 days
•Timing accuracy: +/- 1%
•Inter-stage time delay: 10 seconds between stages
•On-Off differential: 2F (1C) is standard, 4F (3C) when
“excessive cycling” mode is enabled
•Comfort setting, Heating 68F(20C), for 1 hour
•Dead band (difference between cooling and heating set points): 2F to 40F (1.1C to 22.2C)
•Fire/smoke interface: standard NC circuit jumper, remove for connection to building system control, shuts down both
A/C units immediately
•Memory: EEPROM for set point and changeable parameters (maintains settings on power loss)
•Space temperature sensors: 1 local is standard, will accept up to 2 optional 25' remote sensors, Bard part number 8612-023.
When multiple sensors are used, temperatures are averaged
•Controller Enclosure: 20-gauge pre-painted steel, 9.25"W x 20.875"H x 3.00"D, hinged cover, twenty four (24) .875" diameter electrical knockouts
•LEDs for basic controller: Lead unit, Heating Stages 1 – 4
•Six (6) Push-button controls: On/Off switch-Change lead unit-Increase & Decrease set points-Program/Save-Comfort.
mOuntInG the cOntrOller
Included in the controller carton is the controller and installation instructions.
The controller should be installed on a vertical wall approximately four (4) feet above the floor-away from drafts & outside doors or windows. Four (4) mounting holes are provided for mounting to the wall and 7/8" holes for conduit connections are provided in both the base, sides & top of the controller.
temPerature sensOrs
The standard (local) temperature sensor has 12" leads and comes installed from the factory.
A secondary sensor is located internally on the main controller board and serves as a reference and back-up sensor to the local sensor. Any differential of +/- 12F between the on-board and local sensor will cause the controller to use the local sensor as its point of reference.
If the differential is greater than 12F then the controller will check to determine the on-board sensor is reading a temperature that is between the SP (set-point) plus 12F and the SP minus the DB (dead-band) minus 12F. If it is the on-board sensor will become the valid sensor reading and the controller will ignore the local sensor reading. If it is not then the controller will still use the local sensor reading. This is to add additional level of operational capability in the rare event the local sensor fails. If the controller is operating in this mode it is indicated by the lower left decimal point flashing in the display. Note: for purposes of testing when the local sensor is manually driven higher or lower by applying warm or cool water to the probe the on-board sensor is inhibited for the first
30-minutes following power up, or when power is cycled off and back on.
The controller is designed to accept 1 or 2 additional sensors and those have 25-foot leads. The Bard part number for the optional sensor with 25-foot leads is
8612-023. These can be installed as required in the structure to address hot spots, barriers to airflow, etc.
It is recommended that the sensor lead wires be installed in conduit for protective purposes.
The highest reading of any connected sensor will be used for high temperature alarm and the lowest reading sensor will be used for low temperature alarm.
Note: All sensors are polarity sensitive. the copper lead must connect to terminal CU, and the silver lead to AG. Sensors are solid state, not RtD. Use only sensors supplied by Bard. Sensor leads can be extended up to 200 feet. Use 18-gauge twisted pair with soldered connections.
temPerature sensOr lOGIc
The standard local (LSEn) sensor monitors the temperature at the controller location. If this is the only sensor connected, it will control the temperature read-out, the space (building) temperature, and also be used for
Low and High Temperature alarm functions.
If one or more REMOtE sensors are installed and connected (Rem 1 or Rem 2), the temperature read-out will display and the building will be controlled to an
average of all connected sensors. If there is more than
10F difference from the highest to the lowest connected sensor, the actual control will be governed by the hottest sensor for cooling and the coldest sensor for heating.
If multiple temperature sensors are used, the High and
Low temperature alarms will be governed by the average of the connected sensors.
Manual 2100-574
Page 5 of 23
basIc mD4000 cOntrOller
InPut/OutPut sPecIFIcatIOns mD4000 cOntrOller cOnnectIOns
Located on Main Controller Board
Unit #1
Unit #2
C – 24VAC common
R – 24VAC hot
G – fan (Form A, NO)
W – heat (Form A, NO)
C – 24VAC common
R – 24VAC hot
G – fan (Form A, NO)
W – heat (Form A, NO)
F1-F2 Fire/smoke interface
Shipped with jumper installed (a)
48Vdc Back-up power input
-24Vdc or –48Vdc
-20V to –56V range
Local Main sensor, 12-inch leads
CU – copper, AG – silver
Polarity sensitive
Rem 1 Optional remote indoor sensor
CU – copper, AG – silver
Polarity sensitive
Rem 2 Optional remote indoor sensor
CU – copper, AG – silver
Polarity sensitive
H1-H2 Humidity controller input
NOTE:
Sensors are solid state, not RTD.
Use Bard sensors only.
Requires optional controller
Field installed
Advance Input used to remotely toggle lead/lag change
(a) These connections require either jumper or Normally
Closed (NC) relay contact at the Fire/Smoke and Generator interface for Controller to function.
Note: All alarm and output relays are dry contacts rated
1A @ 24 VAC.
Note: All alarm relay outputs have 10-second delay before issuing to protect against nuisance alarm signals.
lOcateD In the mD4000 Panel bOx
Unit #1 terminal Block
R – 24VAC hot from Unit
C – 24VAC common from Unit
Y – Compressor Signal to Unit
F – Economizer Shutdown Output to Economizer
A – Compressor Signal from Economizer
4 – Dirty Filter Alarm from Unit
5 – Dirty Filter Alarm from Unit
6 – Signal Common for F
8 – Economizer Fail from Unit
9 – Economizer Fail from Unit
41 – To Unit 2, 43
42 – To Unit 2, 44
43 – To Unit 2, 41
44 – To Unit 2, 42
45 – To Unit 2, 45 DCA Input
46 – To Unit 2, 46 DCA Input
47 – To Unit 1 Display
48 – To Unit 1 Display
Unit #2 terminal Block
R – 24VAC hot from Unit
C – 24VAC common from Unit
Y – Compressor Signal to Unit
F – Economizer Shutdown Output to Economizer
A – Compressor Signal from Economizer
4 – Dirty Filter Alarm from Unit
5 – Dirty Filter Alarm from Unit
6 – Signal Common for F
8 – Economizer Fail from Unit
9 – Economizer Fail from Unit
41 – To Unit 1, 43
42 – To Unit 1, 44
43 – To Unit 1, 41
44 – To Unit 1, 42
45 – To Unit 1, 45 DCA Input
46 – To Unit 1, 46 DCA Input
47 – To Unit 2 Display
48 – To Unit 2 Display
Gen Run/Econ Shutdown terminal Block(a)
Gen Run Input
Economizer Fail terminal Block
Alarm Output
Alarm relays can be wired for NO (close on alarm) or NC (open on alarm) strategy. Alarm relays can be used individually if there are enough available building alarm points, or can be arranged into smaller groups or even a single group so that all alarm capabilities can be utilized. When multiple alarms are grouped together and issued as a single alarm there will be no off-site indication of which specific problem may have occurred, only that one of the alarms in the group has been triggered.
The individual alarm problem will be displayed on the LED display on face of the controller.
Manual 2100-574
Page 6 of 23
sPecIFIcatIOns/Features FOr mD4000-b & -bc cOntrOller alarms
Inputs
Lockout 1
Lockout 2
2, 3 – input from HVAC #1
2, 3 – input from HVAC #2
Outputs
Smoke/Fire
Lockout 1
Lockout 2
Power Loss 1
Power Loss 2
Low Temp
High Temp 1
High Temp 2
Controller
Form C (SPDT)
Form C (SPDT)
Refrigerant alarm HVAC #1
Form C (SPDT)
Refrigerant alarm HVAC #2
Form C (SPDT)
Power loss HVAC #1
Form C (SPDT)
Power loss HVAC #2
Form C (SPDT)
Low temperature alarm
Form C (SPDT)
High temperature alarm #1
Form C (SPDT)
High temperature alarm #2
Form C (SPDT)
Controller failure alarm
Econ 1
Econ 2
E, F - Form A (NO)
See note (b)
E, F - Form A (NO)
See note (b)
2 nd Stage (c) Form C (SPDT)
2 nd -stage cooling alarm
(b) Make these connections to terminals E & F in HVAC 1 and 2 respectively if desired to have economizers open for emergency ventilation at High Temp Alarm #2 setpoint
condition.
(c) For units with 2-stage compressors, 2nd stage cooling alarm activates on cooling Stage 3 initiation.
2nd Compressor Form A (NC)
Dirty Filter Form A (NC)
4, 5 – Input from Unit
Economizer Fail Form A (NC)
8, 9 – Input from Unit
lOW vOltaGe FIelD WIrInG
The MD4000 is powered from the air conditioners that it is controlling, 24 VAC (18-32V) low voltage only.
Circuitry in the MD4000 isolates the power supplies of the two air conditioners so that no back feeds or phasing problems can occur. Additionally, if one air conditioner loses power, the MD4000 and the other air conditioner are unaffected and will continue to operate normally.
Connect the low voltage field wiring from each unit per the low voltage field wiring diagrams in Section on
“Controller Wiring”. NOTE: Maximum of 18-gauge control wiring should be used. Using heavier gauge wiring can create excessive stress on the control board as door is opened and closed. Create a wiring loop so the door can open and close without stressing terminal blocks.
cOntrOller GrOunDInG
A reliable earth ground must be connected in addition to any grounding from conduit. Grounding lugs are supplied for this purpose.
cOntrOller POWer-uP
Whenever power is first applied to the controller, there is a twenty (20) second time-delay prior to any function
(other than display) becoming active. This time-delay is in effect if the controller On/Off button is used when
24VAC from air conditioners is present, and also if controller is in “ON” position and 24VAC from air conditioners is removed and then restored.
Manual 2100-574
Page 7 of 23
FIre suPPressIOn cIrcuIt
To disable the MD4000 and shut down both air conditioners, terminals F1 and F2 may be used. The F1 and F2 terminals must be jumpered together for normal operation. A normally closed (nc) set of dry contacts may be connected across the terminals and the factory jumper removed for use with a field-installed fire suppression system. The contacts must open if a fire is detected. See appropriate connection diagram - Figures
1, 2 or 3 for this connection. Contacts should be rated for pilot duty operation at 2 amp 24VAC minimum.
Shielded wire (22-gauge minimum) must be used, and the shield must be grounded to the controller enclosure.
staGInG DelaY PerIODs
The following delays are built in for both cooling & heating:
Stage 1 – 0 seconds for blower (if not already on as
continuous)
10 seconds for cooling or heating output
Stage 2 – 10 seconds after Stage 1 for blower
10 additional seconds for cooling or heating
output
Stage 3 – 10 seconds after Stage 2
Stage 4 – 10 seconds after Stage 3
Note: For cooling Stages 1 and 2, the stage LED will blink for 10 seconds while the cooling output is delayed after that stage is called for. There is also a delay after the stage is satisfied, and after the LED stops blinking, the stage will turn off. There is a minimum 10-second delay between stages 2 & 3, and 3 & 4, but no delayed output when stage is turned on or off, and LED for those stages will not blink.
blOWer OPeratIOn
The controller can be configured to have main HVAC blowers cycle on and off on demand; have all blowers run continuously; or have the lead unit blower run continuously with the lag unit blower cycling on demand. Default setting is the blower on the lead unit operates continuously. There is also an option to have all blowers cycle on if one remote sensor is connected, and a temperature difference of more than 5F between any two sensors is observed. This helps to redistribute the heat load within the structure and should reduce compressor operating time.
When any of the stages are satisfied, the stage LED will blink for ten (10) seconds before the stage is actually turned off.
aDvance (sWaP) leaD/laG unIt
Feature
Pressing the Advance button for one (1) second will cause the lead and lag units to change positions.
This may be useful during service and maintenance procedures. This function can also be done remotely by closing a contact across the Advance terminals on the main board.
accelerate tImer Feature
Pressing the UP arrow button for five (5) seconds will activate an accelerate (speed-up) mode, causing the normal changeover time increments of days to be reduced to seconds. Example: 7 days becomes
7 seconds. When “ACC” displays, release button.
Whichever LED is on, indicating lead unit will blink over for each second until the controller switches. This is a check for the timer functionality.
Manual 2100-574
Page 8 of 23
General PrOGrammInG OvervIeW
mD4000 cOntrOller buttOns anD FunctIOn
On/Off Button
1. Press and release the On/Off button to turn On controller, 4-character display will illuminate and Lead unit LED will light.
2. Press and release the On/Off button to turn Off controller. Controller will go dark and A/C units will stop.
Comfort Button
1. Press and release the Comfort button to change the Cooling Set Point to 72F and the Heating Set Point to 68F for a period of 1 hour.
2. Set Points will return to the programmed settings automatically after 1 hour.
3. Pressing the Comfort button during the 1 hour period will deactivate the Set Point change.
4. The temperature display will flash the current temperature while in override mode.
Program Button
1. Press the Program button and release it when the message “Prog” appears on the display.
2. Refer to Programming Instructions and follow these commands to change from Default settings.
Advance/Change/Save Button
1. Press and release the Advance button to swap lead and lag unit positions.
2. When in Program mode the Down and Up buttons are used to scroll through the programming steps.
3. A flashing display means that the particular function of that programming step is “set”, and the display will alternate between the step function and the setting.
4. To change the setting press the Change button and the display will stop flashing, allowing change to the setting.
5. Use Down or Up arrows to change setting as desired, and press the Save button and proceed as desired.
6. When done with programming changes press the Program button until display stops flashing and room temperature is shown.
Up and Down Buttons
These buttons are used to change the settings in conjunction with the Advance/Change/Save button when in programming mode.
cOntrOller PrOGrammable Features anD DeFault settInGs
Order /
Display Description range / choice
LSEn Temperature at local (main) sensor —
SP db r1 r2 cFAn deg
Alt
Cooling set point temperature
Deadband between cooling SP and heating set point
Temperature at remote sensor 1 location, if connected
Temperature at remote sensor 2 location, if connected
Continuous blower operation
Controller system operates in F or C
Alternating Lead-Lag-Lead-Lag sequence or Non-Alternating Lead-Lead-Lag-Lag sequence —
Yes = Alternating
65 to 90F (18 to 32C)
2 to 40F (1 to 24C)
—
—
None, Lead, Both
F or C
Not Used
LLCO Lead-Lag changeover time (Days)
1 - 30 days, or 0 for disabled
HP
Cbd5
OFde crun
LoAL
HAL1
HAL2
Locd
Heat pump logic enabled — only for 1-stage heat pumps and forces Lead-Lag sequence
(overrides a Non-Alt setting)
Unit 1 and 2 blowers automatically both run if delta T >5F between any 2 connected sensors
3-minute lead unit & 4-minute lag unit off-delay enabled
Minimum 3-minute compressor runtime enabled
Low temperature alarm setpoint
High temperature alarm level #1 setpoint
High temperature alarm level #2 setpoint
Controller is locked and no changes can be made. Consult building authority.
Not Used
Yes or No
Not Used
Not Used
Not Used
70F to 120F (21 to 49C)
70F to 120F (21 to 49C)
If locked, display will show
Locd if changes attempted
Inter-Stage Differential
ISd2 From Stage 1 to Stage 2
ISd3 From Stage 2 to Stage 3
ISd4 From Stage 3 to Stage 4
On/Off Differential (Hysterisis)
CSon
CSoF
HSoo
CoPr
Turn "On" above SP for Stage 1 Cooling
Turn "Off" below SP for Stage 1 Cooling
Stage 2, 3 and 4 Cooling automatically set same as Stage 1 decisions
All Heating Stages are equal -/+ on & off differential
1 or 2-stage compressor, if set to 1 the 2nd stage Cooling Alarm activates on Cooling Call 2, if set to 2 the 2nd stage Cooling Alarm activates on Cooling Call 3
Not Used
Not Used
Not Used
Not Used
Not Used
-1/+1 or -2/+2
Not Used
Default
—
77F (25C)
27F (15C)
—
—
Lead
F
Yes
7
No
Yes
No
No
45F (7.2C)
90F (32C)
95F (35C)
Unlocked
4
2
2
2
-4
-2/+2
1
Manual 2100-574
Page 9 of 23
heatInG seQuence OF OPeratIOn
Note: All heating sequences for air conditioners with electric heat or heat pumps will automatically operate in Alternating Lead/Lag/Lead/Lag sequence even if controller is set to Non-Alternating for cooling with or without economizers.
Spyder 1 is lead
Signals Spyder2 as lag.
MD4000 decides Lead unit
1. Air Conditioners with Electric Heat
1 st stage heating set point is the dead-band (db) below the 1 st stage cooling set point (the SP entered into the program). The dead-band is adjustable from 2-40F, and factory default is 27F.
2 nd stage heating set point will operate at same inter stage differential as set for cooling mode.
Spyder 2 is lead
Signals Spyder1 as Lag
MD4000-BCESDC/MD4000-BESDC
W/ AC UNITS W/ DC CONTROL
ECONOMIZERS
If OAT <= SP-MTD and Enthalpy is below curve(if equipped
Is OAT suitable for Cooling
No
Yes
Determine Building
Load
DC Amp load is read and converted to building load with the equation DCA *
106.4-.2455 = BTUH
Calculate adjusted building Load
(BL)
MAT will be adjusted to take into account deviation from setpoint
BL+((RT-SP)*Airflow*1.2)
OAT = Outdoor Air Temperature
BL = Building Load
MDT = Minimum Temperature Differential
RT = Room Temperature
SP = Setpoint
AC = Available Cooling
Calculate
Available Cooling
(AC) for 1 econ
Available cooling =( SP-
MTD-OAT)*1.08*Airflow
If AC > BL
No
Yes
Calculate MAT
Start Econ 1
Stop Econ 2
Stop Blower 2
Calculate
Available cooling for 2 econ
If AC*2 > BL
No
Yes
Calculate MAT
Start Econ 1
Start Econ 2
Start Blower 2
Allow econ operation with
Compressor
No
Stop Econ 1
Stop Econ 2
Stop Blower 2
Yes
Calculate MAT
Start Econ 1
Start Econ 2
Start Blower 2
No Is RT above or below SP
Yes
No
Is RT above SP
Yes
Start Lead
Compressor
Start Lead Blower
Is RT
Below SP
Yes
No
Stop Lead
Compressor
Is 2 nd comp
Allowed
Yes
NO
Manual 2100-574
Page 10 of 23
Is RT
Above ALarn
Setpoint
Yes
No
Start Lag
Compressor
sPecIFIcatIOns FOr OPtIOnal remOte cOmmunIcatIOn bOarD
CB4000 COMMUNICAtION BOARD
Note: If this communication board was not originally factory installed it can be field-installed at anytime. Bard part number is CB4000. It allows remote access via
Ethernet, depending upon level of authority assigned, to all functions of the controller system the same as it one was in the building where the controller system is physically installed.
Required Input Connections to the CB4000 (these are all internal connections from either the alarm board or main controller board):
1. Fire/smoke connection from MD4000 main controller board.
2. Refrigerant lockout inputs.
3. If economizers are used an additional 24V signal wire is required from each air conditioner to the controller system.
4. Communication cable from CB4000 plugs into phone jack connection on main MD4000 controller board.
OPERAtING SYStEM
No special software is required to access the system.
The CB4000 has a default address, simply follow these instructions: tO ACCESS tHE SYStEM
1. Connect CAT 5 or CAT 6 Ethernet cable from computer to Ethernet port on the CB4000.
2. Change your computer’s IP address as shown below to gain initial access to the CB4000.
NOTE 1: Record your computer’s current IP settings
BEFORE making any changes. You will need to reset back to these original settings once you’ve assigned an IP address to the CB4000.
For XP or Windows 2000:
1. Open Control Panel, double click Network
Connections.
2. Double click Local Area Connection on the
General tab and select Properties.
3. Using the General tab, scroll to Internet
Protocol (TCP/IP).
4. Highlight Internet Protocol (TCP/IP) and select
Properties.
5. Change the addresses as follows:
IP 192.168.1.50
Subnet mask: 255.255.255.0
Default gateway:
Preferred DNS server:
192.168.1.1
192.168.1.10
Alternate DNS server: 192.168.1.11
6. Click OK and close all windows.
7. Start your browser, enter the CB4000’s default IP address and hit Enter.
8. The MD4000 log-in page should appear.
For Vista or Windows 7:
1. Open Control Panel, click Network & Internet.
2. Click Network & Sharing Center.
3. Click Local Area Network link.
4. Click Properties.
5. Highlight Internet Protocol Version 4 (TCP/
IPV4) and select Properties.
6. Change the addresses as follows:
Subnet mask: 255.255.255.0
Default gateway:
Preferred DNS server:
192.168.1.1
192.168.1.10
Alternate DNS server: 192.168.1.11
7. Click OK and close all windows.
8. Start your browser, enter the CB4000’s default IP address and hit Enter.
9. The MD4000 log-in page should appear.
LOG IN PAGE
1. Type in “Admin” for the user name and “Bard” for the password. These are case sensitive. Hit “Log In”.
2. Click the “System Setup” button.
SYStEM SEtUP PAGE
Note: If the remote user is on a different subnet than the
CB4000 it is recommended that Static IP Addressing be used rather than DHCP.
IF YOUR NETWORK USES STATIC IP ADDRESSING
1. Enter the correct address information provided by your IT department and click the “Save Config” button.
2. The assumption is that the new IP address has already been configured into the network to get through any firewall(s).
3. Disconnect the Ethernet cable from the computer and plug into your router.
4. Change your computer system’s IP address back to their previous settings from Note 1.
5. Type the new IP address into the browser and make any changes to the MD4000 system before logging out.
IF YOUR NETWORK USES DHCP
1. Check the “Enable DHCP” box.
2. Click “Save Config” box (it will take several seconds before you receive a message that you are now offline. At this point the unit is now running in
DHCP mode).
3. Change your computer system’s IP address back to their previous settings from Note 1. access the CB4000.
NOTE 2: If you need to get back to the CB4000 default
IP setting simply hold the reset button next to the phone jack for 5+ seconds, then release.
Manual 2100-574
Page 11 of 23
USER PAGE
1. The designated Admin person can assign up to 9 additional users and set-up as Admin, Write or
Read authority.
2. User Name and password must be assigned, each must be at least 3 characters long, and are case
sensitive.
3. Only “Admin” can add, change or delete users and has access to all controller pages.
4. “Write” can make changes to the controller settings and operating characteristics, and has access to only Log In, System Status, Setpoints, and Log Out pages.
5. “Read” can only view Status and Setpoints pages and cannot make any changes.
SYStEM StAtUS PAGE
1. This page shows the overall HVAC status of: a. Active cooling or heating stages or
dehumidification mode (requires humidity
sensor) b. Active controller outputs (blower, Stage 1 or
2, heating) to each air conditioner c. Which unit is the Lead unit d. Power loss or refrigerant lock-out for each air
conditioner e. If economizers are used, this will show if the
economizers are on or off.
2. General status of: a. Backup Generator Active or not (if tied to
generator run controls to inhibit lag unit
operation during generator run) b. Alarm board connected or not c. Controller system Locked or Unlocked d. Comfort mode Active or not
3. Temperatures: used, if not will read same as Local sensor) b. Local sensor at controller c. Remote 1 or Remote 2 if connected
4. General Alarm Status: a. Fire/Smoke, Clear or Alarm b. Low Temp, Clear or Alarm c. High Temp #1, Clear or Alarm d. High Temp #2, Clear or Alarm e. Controller Failure, Clear or Alarm
SEtPOINtS PAGE (Note: “Read” level authority can view this screen but cannot make any changes.
“Admin” and “Write” authority can make changes)
1. General Setpoints a. On initial installation and start-up all selectable characteristics are set to factory default
settings. b. Each of these points has a drop-down menu for ease of use.
2. Alarm Board Setpoints a. Low temperature alarm setpoint b. High temperature alarm #1 setpoint c. High temperature alarm #2 setpoint
3. System Overrides a. System 1 Heating Override b. System 2 Heating Override c. Turn Power On to the System (Note: Cannot
remotely turn the controller system Off) d. Lock/Unlock Controller e. Advance Lead to Lag Unit f. Comfort Mode g. Restore System Defaults h. Reset Controller. There are built-in routines to
prevent the controller system from getting
“locked up”, but this also allows a manual
remote reset as a backup before having a
service call to the site.
LOG OUt BUttON
1. Clicking this button will automatically log you off the controller remote access.
2. To log back in will require entering assigned IP address into your browser and entering valid
User Name and Password.
cb4000 cOmmunIcatIOn bOarD
CONNECt tO NEtWORk
1. After initial set-up using laptop computer, disconnect computer cable from the Ethernet port and connect the CAT 5 or CAT 6 network cable.
RESET BUTTON TO RETURN TO DEFAULT CONTROLLER SETTINgS
2. Remote access is now available using the assigned
IP address and valid User Name and Password
(case sensitive).
Manual 2100-574
Page 12 of 23
ETHERNET PORT
PHONE jACk
CONNECTION
TO MAIN
CONTROLLER
BOARD
IP DEFAULT ADDRESS RESET
cOntrOller WIrInG
The MD4000 can be used for controlling two (2) air conditioners with economizers.
securItY (lOckInG) Feature
The MD4000 controller can be locked such that unauthorized persons cannot make any changes to temperature set points or any other selectable parameters of the controller system.
The ON/OFF and Comfort buttons remain fully active for their normal intent. The Advance/Change/
Save button remains active for the Advance feature only, which allows the position of the lead and lag air conditioners to be swapped (reversed). The Program button remains partially active - allowing the review of temperature sensor(s) actual reading of temperature, and the current settings/choices that have been chosen.
However, no changes can be made when the controller is locked, and if the change button is pressed when in the Program mode, the display will come up showing
“Locd” instead of flashing the selectable choices for that parameter. The default (DEF) reset capability is also disabled when the controller is in locked mode.
Locking and Unlocking the MD4000 Controller:
1. Locking the controller requires using 3 buttons
while the controller is in the normal operating (run)
mode.
2. Press and hold the Advance/Change/Save button
and the Up and Down arrow buttons simultaneously
for 20 seconds until the display shows “Locd”.
3. To unlock the controller, press the Change, Up and
Down arrow buttons simultaneously for 20 seconds
until the display reads “uLoc”.
GeneratOr run / ecOnOmIzer shutDOWn Feature
If desired, the MD4000 controller can be signaled from a standby generator system to lockout (disable operation of the) lag air conditioning system and close economizers if active. This is sometimes mandated if the generator size is not sufficient to handle the building load (amperage) and that of both air conditioning systems.
A normally closed (NC) dry contact as part of generator controls is required. These contacts must open when the generator is started, and such action will signal the
MD4000 controller to this condition and disable lag air conditioner run function and close economizers if active.
A wire jumper is factory-installed across the Generator
Run / Economizer Shutdown terminals. To utilize the generator run feature, remove the jumper from
Generator Run / Economizer Shutdown, and connect the generator normally closed (NC) contacts that will open-on-run generator condition to the Generator Run /
Economizer Shutdown terminals.
backuP Dc POWer cOnnectIOn
There are input connections available for -24VDC or
-48VDC (-20 to -56V) backup power connection. Making this connection will maintain microprocessor operation, front panel display, LED signaling, and alarm relay operation during periods of commercial power outages and when no standby generator is available. This circuit is protected by a replaceable .5A (500mA) 250V fuse.
IMPORtANt: The shelter DC battery power must be connected to the controller and wired as shown in controller wiring diagrams.
The backup DC power connection is polarity sensitive. If polarity is reversed, the controller will not function on backup power, no display and no alarm functions will be evident.
Manual 2100-574
Page 13 of 23
table 1 hOOk-uP DIaGram selectIOn table — reFerence FIGure 1 shOWn system type model series
A/C with 1-Stage Compressor H**A / H**L mD4000-b newer ecOnWmt economizer — no communication board
1 mD4000-bc newer ecOnWmt economizer with cb4000 communication board
2
AC UNIT 1
45
44
43
42
41
4
48
47
46
R
C
27
NO
9
26
RED/WHITE
BLACK/WHITE
BLUE
YELLOW
YELLOW/WHITE
PURPLE
28
30
10
15
UNIT 1
SPYDER ECON
BLUE/WHITE
YELLOW/RED
BROWN/WHITE
ORANGE
1
REFRIGERANT PRESSURE LOCKOUT
ALARM - REQUIRES "J" CONTROL MODULE IN
A/C UNITS
2 THE "E" AND "F" CONNECTION FOR EMERGENCY
VENTILATION ARE AVAILABLE
3 USE SHIELDED CABLE OR EQUIVALENT.
CONNECT SHIELD AT SPYDER ONLY
AC UNIT 2
UNIT 2
SPYDER ECON
15
30
ORANGE
YELLOW/RED
BROWN/WHITE 10
28
26
9
NO
27
C
R
41
BLUE/WHITE
PURPLE
YELLOW/WHITE
YELLOW
BLUE
BLACK/WHITE
RED/WHITE
42
43
44
45
46
47
48
4
A
F
Y
C
R
8
7
6
5
4
Y2
Y1
W
9
2
3
10
G
1
E
3
Manual 2100-574
Page 14 of 23
Y
F
A
R
C
4
5
6
7
8
9
Y2
G
E
W
Y1
2
3
10
1
FIGure 1 mD4000-b cOntrOller cOnnectIOns
1-staGe (h**a/h**l serIes) aIr cOnDItIOners
WIth (ecOnWmt) ecOnOmIzers
3
NC CONTACTS
OPEN ON ALARM
NC CONTACTS
OPEN ON ALARM
MD4000 UNIT 1
TERMINAL BLOCK
46
45
44
43
42
41
F
A
4
5
6
R
C
Y
DIRTY FILTER
ALARM (NC)
8
9
ECON FAIL
ALARM (NC)
1
DISPLAY 1
2 3 4 1
DISPLAY 2
2
MD4000
3 4
MD4000
MAIN BOARD
48VDC
W
Y1
Y2
G
R
C
+
_
NOTE: DC BACK-UP POWER
IS POLARITY SENSITIVE AND
MUST BE CONNECTED AS SHOWN
OR CONTROLLER WILL NOT
OPERATE ON DC POWER ONLY
1
LOCKOUT ALARM
1
LOCKOUT ALARM
2
E
F
2
3
E
F
2
3
ALARM
BOARD
GEN RUN ALARM/
ECON SHUTDOWN
FIRE/SMOKE
ALARM CIRCUIT
"NC" CONTACTS -
OPEN ON ALARM
UNIT 1
OPTIONAL
48VDC
FIRE/
SMOKE
2 COMP RUN ALARM
TERMINAL BLOCK
REMOVE
JUMPER
REMOVE
JUMPER
F1
F2
MD4000 UNIT 2
TERMINAL BLOCK
9
8
ECON FAIL
ALARM (NC)
NOTE: ALL SENSORS ARE
POLARITY SENSITIVE. COPPER
LEAD MUST CONNECT TO
CU, AND SILVER MUST
LEAD TO AG
OPTIONAL FIELD INSTALLED
25 FOOT TEMPERATURE
SENSORS, BARD PART
NUMBER 8612-023
R
41
42
43
44
45
46
F
Y
A
4
C
6
5 DIRTY FILTER
ALARM (NC)
OPTIONAL FIELD INSTALLED
HUMIDITY CONTROLLER
"NO" CONTACTS - CLOSE ON RISE
REM 1
REM 2
CU
AG
CU
AG
G2
G1
HUMIDITY
CONTROLLER
H1
H2
ADVANCE
R
G
Y2
Y1
W
C
LOCAL
CU
AG
UNIT 2
COPPER
SILVER
COPPER
SILVER
COPPER
SILVER
MIS-3092 A
AC UNIT 1
4
48
47
46
45
44
43
42
41
C
R
27
NO
9
26
28
30
RED/WHITE
BLACK/WHITE
BLUE
YELLOW
YELLOW/WHITE
PURPLE
BLUE/WHITE
YELLOW/RED
10
15
UNIT 1
SPYDER ECON
BROWN/WHITE
ORANGE
FIGure 2 mD4000-bc cOntrOller cOnnectIOns
1-staGe (h**a/h**l serIes) aIr cOnDItIOners
WIth (ecOnWmt) ecOnOmIzers anD WIth alarm bOarD & cb4000 cOmmunIcatIOn bOarD
3
1
REFRIGERANT PRESSURE LOCKOUT
ALARM - REQUIRES "J" CONTROL MODULE IN
A/C UNITS
2 THE "E" AND "F" CONNECTION FOR EMERGENCY
VENTILATION ARE AVAILABLE
3 USE SHIELDED CABLE OR EQUIVALENT.
CONNECT SHIELD AT SPYDER ONLY
AC UNIT 2
UNIT 2
SPYDER ECON
15
30
10
28
26
9
NO
27
ORANGE
YELLOW/RED
BROWN/WHITE
BLUE/WHITE
PURPLE
YELLOW/WHITE
YELLOW
C
R
41
BLUE
BLACK/WHITE
RED/WHITE
42
43
44
45
46
47
48
4
E
2
1
3
10
G
Y2
9
8
Y1
W
Y
C
A
F
R
5
6
4
7
3
F
A
4
5
8
7
6
9
R
C
Y
W
Y1
Y2
G
2
E
3
10
1
MD4000 UNIT 1
TERMINAL BLOCK
F
A
C
Y
42
41
R
5
4
6
46
45
44
43
DIRTY FILTER
ALARM (NC)
DISPLAY 1
1 2 3 4 1
MD4000
DISPLAY 2
2 3 4
MD4000
MAIN BOARD
9
8
ECON FAIL
ALARM (NC)
W
Y1
Y2
G
R
C
+
_
UNIT 1
NOTE: DC BACK-UP POWER
IS POLARITY SENSITIVE AND
MUST BE CONNECTED AS SHOWN
OR CONTROLLER WILL NOT
OPERATE ON DC POWER ONLY
48VDC
OPTIONAL
48VDC
NC CONTACTS
OPEN ON ALARM
NC CONTACTS
OPEN ON ALARM
1
LOCKOUT ALARM
1
LOCKOUT ALARM
GEN RUN ALARM/
ECON SHUTDOWN
2 COMP RUN ALARM
TERMINAL BLOCK
REMOVE
JUMPER
2
E
F
3
2
E
F
3
2
ALARM
BOARD
CB4000
NO
C
NC
1-3
2-3
3-3
1
2
3
FIRE/SMOKE
ALARM CIRCUIT
"NC" CONTACTS -
OPEN ON ALARM
REMOVE
JUMPER
F1
F2
41
42
43
44
45
46
F
Y
4
A
C
R
MD4000 UNIT 2
TERMINAL BLOCK
8
9
ECON FAIL
ALARM (NC)
NOTE: ALL SENSORS ARE
POLARITY SENSITIVE. COPPER
LEAD MUST CONNECT TO
CU, AND SILVER MUST
LEAD TO AG
OPTIONAL FIELD INSTALLED
25 FOOT TEMPERATURE
SENSORS, BARD PART
NUMBER 8612-023
5
6
DIRTY FILTER
ALARM (NC)
OPTIONAL FIELD INSTALLED
HUMIDITY CONTROLLER
"NO" CONTACTS - CLOSE ON RISE
REM 1
REM 2
CU
AG
CU
AG
G2
G1
HUMIDITY H1
CONTROLLER H2
ADVANCE
Y1
W
C
R
G
Y2
LOCAL
CU
AG
FIRE/
SMOKE
UNIT 2
COPPER
SILVER
COPPER
SILVER
COPPER
SILVER
MIS-3093
Manual 2100-574
Page 15 of 23
ecOnOmIzer FaIlure alarm
Upon failure of either economizer to open on command or close on command, the Economizer Failure Alarm will open normally closed contacts to signal the failure. To utilize this feature, terminals 8 & 9 must be connected to the shelter alarm panel.
A normally closed economizer fail alarm is available on terminals 8 & 9 of the Unit 1 & 2 terminal blocks.
DIrtY FIlter alarm
A normally closed dirty filter alarm is available on terminals 4 & 5 of the Unit 1 & 2 terminal blocks.
2-cOmPressOr run alarm
If both compressors are running at the same time, the
2-Compressor Run Alarm will open indicating this condition.
Note: the alarm LeD display board is shipped uninstalled to protect it from possible damage during installation of the wiring to main controller board and/ or the alarm board. It is polarity sensitive and is keyed so it can only be installed in correct position.
alarm WIrInG
Alarm relays can be wired for NO (close on alarm) or
NC (open on alarm) strategy.
Alarm relays can be used individually if there are enough available building alarm points, or can be arranged into smaller groups or even a single group so that all alarm capabilities can be utilized.
When multiple alarms are grouped together and issued as a single alarm, there will no off-site indication of which specific problem may have occurred, only that one of the alarms in the group has been triggered. The individual alarm problem will be shown on the LED display on the face of the controller.
Note: All alarm and output relays are Form C (SPDT) dry contacts rated 1A @ 24 VAC.
Note: All alarm relay outputs have 10-second delay in acutally issuing to protect against nuisance alarm signals.
The Power Loss 1, Power Loss 2 and controller alarm relays are all “reverse actuated”, which means they are continuously energized (the NO contact is closed) and switched to NC position upon alarm condition.
Therefore, it is important to closely follow the alarm board connection diagrams that follow.
Any alarm feature that is not desired can simply be ignored (not connected).
NOtE: the LED display board can be replaced if needed independently of the alarm board. Bard part number is 8612-022.
alarm leD DIsPlaY bOarD
Manual 2100-574
Page 16 of 23
MIS-2042
Note: The LED display board is polarized and will only fit in one direction as shown. It must be fully inserted in order for the controller to function properly.
2nD staGe cOOlInG alarm
This alarm output is available for use if desired. It is important to note that in some installations, due to A/C system sizing and internal heat load, that the secondary
(lag) air conditioning unit may be called upon to assist the lead air conditioner some of the time. If this is the case, or possibly when additional heat load is added, using the 2nd stage cooling alarm will cause nuisance alarm conditions.
Note: For units with 2-stage compressors, the dual stage cooling alarm activates on cooling Stage 3 initiation. Menu Step 23, CoPr, must be set to “2” for this to occur, otherwise alarm will activate on cooling call Stage 2 causing nuisance alarm.
For installations where it is known that there is 100% redundancy (one air conditioning unit can handle 100% of the load 100% of the time) use of the 2nd Stage Cooling
Alarm is a method to issue an alarm signal that the lead air conditioner is down (or not delivering full capacity) and that the lag air conditioner is now operating.
reFrIGerant Pressure alarms
Air conditioners with “J” control module are equipped with an alarm relay that is activated upon high or low refrigerant pressure lockout conditions. Connecting terminals 2 and 3 from the air conditioner 24V terminal block to the matching terminals 2 and 3 on the alarm board will allow these alarms to function.
sPYDer ecOnOmIzer DIsPlaYs
The two (2) displays on the front of the MD4000 are for remotely monitoring and programming the 100% fresh air Spyder economizers in the units. See Instruction
Manual 2100-576 for details.
emerGencY ventIlatIOn seQuence
For units with economizers, there are two (2) emergency ventilation sequences designed into the controller. Both require the -B alarm board and connection of terminals E and F from the air conditioner
24V terminal block to the matching terminals on the alarm board.
Note: The E and F wiring connections at the 24V terminal block in the A/C units are different for older style EIFM economizers than for newer style
ECONWMT economizers. Refer to the appropriate
Controller Connection diagrams - See Table 1.
Sequence one requires a refrigerant pressure alarm, coupled with high temperature alarm condition No. 1
(HAL 1 set point). If both of these conditions occur, the economizer in the air conditioner that issued the refrigerant alarm will drive open to ventilate the building.
Sequence two (HAL 2 set point) is activated by high temperature alarm No. 2, and will initiate even without a refrigerant pressure alarm signal. Both economizers will be activated to provide emergency ventilation.
This strategy help protect against building overheating if air conditioner(s) are inoperative for non-pressure related reasons (bad compressor, contactor, run capacitor, etc.).
Manual 2100-574
Page 17 of 23
FIGure 3 alarm bOarD cOnnectIOns
FOr nOrmallY clOseD "nc" OPen-On-alarm strateGY
IMPORtANt! LED display board is shipped loose to protect it from possible damage during installation of the wiring to main controller board and/or the alarm board. It is polarity sensitive and is keyed so it can only be installed in correct position.
Manual 2100-574
Page 18 of 23
FIGure 4 alarm bOarD cOnnectIOns
FOr nOrmallY OPen "nO" clOse-On-alarm strateGY
IMPORtANt! LED display board is shipped loose to protect it from possible damage during installation of the wiring to main controller board and/or the alarm board. It is polarity sensitive and is keyed so it can only be installed in correct position.
Manual 2100-574
Page 19 of 23
PrOGrammInG InstructIOns
To swap lead and lag unit positions, press the
ADVANCE button.
To enter the Program mode, press the PROGRAM button and release it when the message PROG appears on the display. When in Program mode, the
DOWN and UP arrows are used to scroll through the programming steps.
A FLASHING display means that the function or choice is “SET”, and the display will alternate between the step function and setting.
To change the setting of any step, press the CHANGE button and the display will stop flashing, allowing change to the setting by using the DOWN or UP arrows. When desired setting is reached, press the
SAVE button, and proceed as desired. When done with programming changes, press the PROGRAM button until display stops flashing and room temperature display is shown. If no buttons are pushed within thirty
(30) seconds, the controller will automatically revert back to “RUN” mode.
To reset all controller settings to the factory default values, press the PROGRAM button for 10 seconds until display reads dEF.
NOTE: When the controller has the security locking feature enabled, no changes to any selectable features can be made, and the default reset feature is also locked out. All of the programmable features/settings can be reviewed using the Program button and Up or Down arrows, but any attempt to change settings using the Change button will result is display showing “Locd” indicating controller is locked. See section on Security (Locking) Feature.
See next page for Programmable Features, Default Settings and MD4000 front panel label layout.
Note: When using the controller buttons to review settings or making changes, push and hold the buttons for approximately 1 second or until the display changes.
Quickly pushing or jabbing the buttons will not allow the controller to respond.
Manual 2100-574
Page 20 of 23
See displays above
D trans red window adhesive die emboss die cut
Material: 10 mil HP92WP lexan
Adhesive: 7952MP
Premask: 4075
Colors: black, spot white, trans red,
spot frosted clear
N/A - See Operating Manual
LEAD
27F/15C
N/A - See Operating Manual
N/A - See Operating Manual
N/A - See Operating Manual
N/A - See Operating Manual
N/A - See Operating Manual
N/A - See Operating Manual
N/A - See Operating Manual
N/A - See Operating Manual
N/A - See Operating Manual
7961-762
8.5” h
Manual 2100-574
Page 21 of 23
11”
6
18
10
FIGure 5
Parts lIst DescrIPtIOn DIaGram
20
8
Manual 2100-574
Page 22 of 23
14
13
17
15
5
12
4
3
19
9
1
7
11
2
SEXP-648
Parts List
Dwg.
no.
13
14
15
16
9
10
11
12
17
18
19
20
7
8
5
6
3
4
1
2
Part no.
127-423-4
8612-038
8612-021
8612-022
113-456-4
152-515-4
8611-099
5400-002
8612-023
7961-762
8611-006
8612-035
8201-015
8201-071
8607-030
113-461-4
8201-062
8611-094
8607-033
8301-043
Description
Control Box
Controller Board
Alarm Board B
Alarm Display
Support Bracket
Control Box Door
LTF Fitting
Hinge
Sensor
Label/keypad ground Lug
Communication Board
Relay
Relay
Terminal Block
Alarm Bracket
Relay
Light
Terminal Block
Display
2
2
2
2
2
1
2
3 mD4000-b mD4000-bc ab3000-b
X
X
X
X
X
X
X
X
X
X
2
X
X
2
2
2
2
X
X
X
X
X
X
X
X
2
1
2
3
2
X
X
X cb4000
X
Manual 2100-574
Page 23 of 23
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Key Features
- 6-degrees-of-freedom (6DoF) control
- Customizable buttons
- Ergonomic design
- Compatible with most 3D modeling and design software
- Plug-and-play installation
- 3Dconnexion's patented 6DoF sensor technology
- Two programmable buttons
- Sculpted shape for a comfortable grip
- Non-slip rubberized surface
- Durable construction
Related manuals
Frequently Answers and Questions
What is the difference between the 3D Connexion mD4000-b and other 3D mice?
What are the benefits of using a 3D mouse like the 3D Connexion mD4000-b?
Is the 3D Connexion mD4000-b compatible with my 3D modeling and design software?
advertisement