48TJ016-028 Single Package Rooftop Units Electric Cooling/Gas Heating Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-14 Step 1 — Provide Unit Support . . . . . . . . . . . . . . . 1 • ROOF CURB • ALTERNATE UNIT SUPPORT Step 2 — Rig and Place Unit . . . . . . . . . . . . . . . . . . 3 • POSITIONING • ROOF MOUNT Step 3 — Field Fabricate Ductwork . . . . . . . . . . . . 9 Step 4 — Make Unit Duct Connections . . . . . . . . 9 Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . 9 Step 6 — Trap Condensate Drain . . . . . . . . . . . . 10 Step 7 — Install Gas Piping . . . . . . . . . . . . . . . . . . 10 Step 8 — Make Electrical Connections . . . . . . . 10 • FIELD POWER SUPPLY • FIELD CONTROL WIRING Step 9 — Make Outdoor-Air Inlet Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 • MANUAL OUTDOOR-AIR DAMPER • OPTIONAL ECONOMIZER Step 10 — Install Outdoor-Air Hood . . . . . . . . . . 13 START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-19 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-28 START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . CL-1 1. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Refer to the User’s Information Manual provided with this unit for more details. 2. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. What to do if you smell gas: 1. DO NOT try to light any appliance. 2. DO NOT touch any electrical switch, or use any phone in your building. 3. IMMEDIATELY call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. 4. If you cannot reach your gas supplier, call the fire department. Disconnect gas piping from unit when pressure testing at pressure greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 0.5 psig or less, a unit connected to such piping must be isolated by closing the manual gas valve(s). SAFETY CONSIDERATIONS Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations. Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury. INSTALLATION Step 1 — Provide Unit Support When handling 48TJE024 and 028 units with a forklift truck, use a minimum of 48-in. long forks and lift ONLY through factory-provided holes in base rail. Otherwise, damage to the unit may result. ROOF CURB — Assemble or install accessory roof curb or horizontal adapter in accordance with instructions shipped with this accessory. See Fig. 1 and 2. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb or horizontal adapter before unit is set in place. Curb or adapter should be level. This is necessary to permit unit drain to function properly. Unit leveling tolerance is ± 1⁄16 in. per linear ft in any direction. Refer to Accessory Roof Curb or Horizontal Adapter Installation Instructions for additional information as required. When accessory roof curb or horizontal adapter is used, unit may be installed on class A, B, or C roof covering material. Instructions continued on page 3. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 111 Catalog No. 564-873 Printed in U.S.A. Form 48TJ-11SI Pg 1 4-96 Replaces: 48TJ-7SI Tab 1a 6a NOTE: To prevent the hazard of stagnant water build-up in the drain pan of the indoor-air section, unit can only be pitched as shown. LEGEND COMPR SECT. — Compressor Section NOTES: 1. Roof curb accessory is shipped unassembled. 2. Insulated panels, 1⁄2-in. thick neoprene-coated, 2 lb density. 3. Dimensions in ( ) are in millimeters. 4. Direction of airflow. 5. Roof curb: 18 gage steel. 6. Attach all ductwork to roof curb. 7. Field installation of sidewall is mandatory. ACCESSORY PACKAGE NO. CURB HEIGHT 50PQ900221 18-29 (355) 50PQ900141 28-09 (610) 50PQ900151 50DP900211 48DP900041* 48DP900051* 48DP900061* 48DP900071* 28-09 (610) 18-119 (584) 18-29 (355) 28-09 (610) 28-09 (610) 18-119 (584) DESCRIPTION ‘‘A’’ ‘‘B’’ ‘‘C’’ ‘‘D’’ ‘‘E’’ Standard Curb — 149 High Standard Curb for Units Requiring High Installation Horizontal Supply and Return Curb Pre-Assembled, High-Static, Horizontal Adapter Standard Curb — 149 High Standard Curb for Units Requiring High Installation Horizontal Supply and Return Curb Pre-Assembled, High-Static, Horizontal Adapter 58-71⁄169 (1703) 18-713⁄169 (503) — — — 58-7 ⁄ 9 (1703) 18-7 ⁄ 9 (503) — — — 58-7 ⁄ 9 (1703) 58-71⁄169 (1703) 78-213⁄169 (2205) 18-7 ⁄ 9 (503) 18-713⁄169 (503) 38-35⁄89 (1006) 58-69 (1676) 68-29 (1880) 08-2 ⁄ 9 (64) 08-61⁄49 (159) 18-69 (457) 18-25⁄89 (371) — — — 78-213⁄169 (2205) 38-35⁄89 (1006) — — — 78-213⁄169 (2205) 78-213⁄169 (2205) 38-35⁄89 (1006) 38-35⁄89 (1006) 58-69 (1676) 68-29 (1880) 08-21⁄29 (64) 08-61⁄49 (159) 18-69 (457) 18-25⁄89 (371) 1 16 1 16 13 16 *For high-heat applications. Fig. 1 — Roof Curb Details 2 13 16 12 POSITIONING — Maintain clearance, per Fig. 4-6, around and above unit to provide minimum distance from combustible materials, proper airflow, and service access. Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute). Although unit is weatherproof, guard against water from higher level runoff and overhangs. Locate mechanical draft system flue assembly at least 4 ft from any opening through which combustion products could enter the building, and at least 4 ft from any adjacent building. When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade. ROOF MOUNT — Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1. Instructions continued on page 9. IMPORTANT: The gasketing of the unit to the roof curb or adapter is critical for a watertight seal. Install gasket with the roof curb or adapter as shown in Fig. 1. Improperly applied gasket can also result in air leaks and poor unit performance. ALTERNATE UNIT SUPPORT — When a curb or adapter cannot be used, install unit on a noncombustible surface. Support unit with sleepers, using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side. Step 2 — Rig and Place Unit — Inspect unit for transportation damage. File any claim with transportation agency. Do not drop unit; keep upright. Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit frame as a reference; leveling tolerance is ± 1⁄16 in. per linear ft in any direction. See Fig. 3 for additional information. Unit operating weight is shown in Table 1. Four lifting holes are provided in ends of unit base rails as shown in Fig. 3. Refer to rigging instructions on unit. NOTE: For preassembled horizontal adapter part no. 50DP900211 and 48DP900071, the accessory kit includes a factory-designed, high-static, regain transition duct. For horizontal curb part no. 50PQ900151 and 48DP900061, a field-supplied transition duct is required. Fig. 2 — Horizontal Adapters and Roof Curbs UNIT 48TJ D016 D020 D024 D028 E016 E024 E028 DIMENSIONS MAXIMUM SHIPPING WEIGHT Lb 1800 2300 2350 2400 1800 2550 2600 Kg 816 1043 1066 1089 816 1156 1179 NOTES: 1. Dimensions in ( ) are in millimeters. 2. Refer to Table 1 for unit operating weights. 3. Remove boards at ends of unit and runners prior to rigging. 4. Rig by inserting hooks into unit base rails as shown. Use corner post from packaging to protect coil from damage. Use bumper boards for spreader bars on all units except 48TJE024 and 028. 5. Weights do not include optional economizer. See Table 1 for economizer weight. 6. Weights given are for aluminum evaporator and condenser coil plate fins. Weights of other metal combinations are listed in Table 1. A Ft-in. 6-111⁄2 6-111⁄2 6-111⁄2 6-111⁄2 6-111⁄2 8- 71⁄4 8- 71⁄4 B mm 2121 2121 2121 2121 2121 2623 2623 Ft-in. 4-0 3-2 3-4 3-4 4-0 4-2 4-2 mm 1219 964 1016 1016 1219 1270 1270 All panels must be in place when rigging. Fig. 3 — Rigging Details 3 UNIT 48TJ X Ft-in. mm D016 3-2 965 D020 3-7 1090 E016 3-2 965 UNIT 48TJ D016 D020 E016 A Lb 384 520 383 Kg 174 235 174 DIMENSIONS Y Ft-in. mm 4-0 1219 3-2 965 4-0 1219 CORNER B Lb Kg 370 168 508 230 369 167 WEIGHT* C Lb Kg 358 162 486 220 360 163 Z Ft-in. 1-10 1- 8 1-10 mm 559 508 559 D Lb 538 636 538 Kg 244 288 244 *Weights are for unit only (aluminum plate fins) and do not include options or crating. NOTES: 1. Dimensions in ( 2. 3. ) are in millimeters. Center of gravity. Direction of airflow. 4. Ductwork to be attached to accessory roof curb or adapter only. 5. Minimum clearance: a. Rear: 7809 (2134) for coil removal. This dimension can be reduced to 4809 (1219) if conditions permit coil removal from the top. b. Left side: 4809 (1219) for proper condenser coil airflow. c. Front: 4809 (1219) for control box access. d. Right side: 4809 (1219) for proper operation of damper and power exhaust (if so equipped). e. Top: 6809 (1829) to assure proper condenser fan operation. f. Local codes or jurisdiction may prevail. 6. With the exception of clearance for the condenser coil and the damper/power exhaust as stated in Note No. 5, a removable fence or barricade requires no clearance. 7. Dimensions are from outside of corner post. Allow 08-5⁄169 (8) on each side for top panel drip edge. Fig. 4 — Base Unit Dimensions; 48TJ016,020 4 NOTES: 1. Dimensions in ( 2. 3. UNIT 48TJD 024 028 CORNER B Lb Kg Lb Kg 520 235 508 230 527 239 545 247 A WEIGHT* DIMENSION X C D Lb Kg Lb Kg Ft-in. mm 532 241 640 290 3-2 965 578 262 600 272 3-7 1092 ) are in millimeters. Center of gravity. Direction of airflow. 4. Ductwork to be attached to accessory roof curb or adapter only. 5. Minimum clearance: a. Rear: 7809 (2134) for coil removal. This dimension can be reduced to 4809 (1219) if conditions permit coil removal from the top. b. 4809 (1219) to combustible surfaces, all four sides (includes between units). c. Left side: 4809 (1219) for proper condenser coil airflow. d. Front: 4809 (1219) for control box access. e. Right side: 4809 (1219) for proper operation of damper and power exhaust (if so equipped). f. Top: 6809 (1829) to assure proper condenser fan operation. g. Bottom: 14 (356) to combustible surfaces (when not using curb or adapter). h. Control box side: 3809 (914) to ungrounded surfaces (noncombustible). i. Control box side, 3869 (1067) to block or concrete walls, or other grounded surfaces. j. Local codes or jurisdiction may prevail. 6. With the exception of clearance for the condenser coil and the damper/power exhaust as stated in Note No. 5, a removable fence or barricade requires no clearance. 7. Dimensions are from outside of corner post. Allow 08-5⁄169 (8) on each side for top panel drip edge. Fig. 5 — Base Unit Dimensions; 48TJD024,028 5 NOTES: 1. Dimensions in ( 2. 3. UNIT 48TJE 024 028 CORNER B Lb Kg Lb Kg 465 211 456 206 472 214 494 224 A ) are in millimeters. Center of gravity. Direction of airflow. 4. Ductwork to be attached to accessory roof curb or adapter only. 5. Minimum clearance: a. Rear: 7809 (2134) for coil removal. This dimension can be reduced to 4809 (1219) if conditions permit coil removal from the top. b. 4809 (1219) to combustible surfaces, all four sides (includes between units). c. Left side: 4809 (1219) for proper condenser coil airflow. d. Front: 4809 (1219) for control box access. e. Right side: 4809 (1219) for proper operation of damper and power exhaust (if so equipped). f. Top: 6809 (1829) to assure proper condenser fan operation. g. Bottom: 14 (356) to combustible surfaces (when not using curb or adapter). h. Control box side: 3809 (914) to ungrounded surfaces (noncombustible). i. Control box side, 3869 (1067) to block or concrete walls, or other grounded surfaces. j. Local codes or jurisdiction may prevail. 6. With the exception of clearance for the condenser coil and the damper/power exhaust as stated in Note No. 5, a removable fence or barricade requires no clearance. 7. Dimensions are from outside of corner post. Allow 08-5⁄169 (8) on each side for top panel drip edge. WEIGHT* DIMENSION X C D Lb Kg Lb Kg Ft-in. mm 644 292 835 378 3-4 1016 736 334 748 339 3-5 1041 *Weights are for unit only (aluminum plate fins) and do not include options or crating. Fig. 6 — Base Unit Dimensions; 48TJE024,028 6 Table 1 — Physical Data UNIT SIZE NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb) Unit Al/Al* Al/Cu* Cu/Cu* Economizer Roof Curb† COMPRESSOR Quantity Oil (oz) REFRIGERANT TYPE Expansion Device Operating Charge (lb-oz) Circuit 1** Circuit 2 CONDENSER COIL Rows...Fins/in. Total Face Area (sq ft) CONDENSER FAN Nominal Cfm Quantity...Diameter (in.) Motor Hp...Rpm Watts Input (Total) EVAPORATOR COIL Rows...Fins/in. Total Face Area (sq ft) EVAPORATOR FAN Quantity...Size (in.) Type Drive Nominal Cfm Motor Hp Maximum Continuous Bhp Motor Frame Size Nominal Rpm High/Low Fan Rpm Range Motor Bearing Type Maximum Allowable Rpm Motor Pulley Pitch Diameter Min/Max (in.) Nominal Motor Shaft Diameter (in.) Fan Pulley Pitch Diameter (in.) Nominal Fan Shaft Diameter (in.) Belt, Quantity...Type...Length (in.) Pulley Center Line Distance (in.) Speed Change per Full Turn of Movable Pulley Flange (rpm) Movable Pulley Maximum Full Turns From Closed Position Factory Setting Factory Speed Setting (rpm) Fan Shaft Diameter at Pulley (in.) 016D/E 208/230,460 v 15 575 v 1650/1650 1800/1800 1930/1930 110 200 020D 024D/E 028D/E 18 20 25 2150 2200/2400 2300 2350/2550 2430 2480/2680 110 110 200 200/213 Semi-Hermetic 2 2 88,115 115 ea R-22 Acutrol™ Refrigerant Metering 1 115 TXV 2250/2450 2400/2600 2530/2730 110 200/213 2 128 ea Device 19-4 13-4 12-13 16-12 — 11-0 12-13 15-12 Enhanced Copper Tubes, Aluminum Lanced or Copper Fins 2...17 3...15 3...15 4...15 22.2 22.2 22.2 22.2 Propeller Type 10,500 10,500 14,200 14,200 3...22 3...22 2...30 2...30 1⁄2...1050 1⁄2...1050 1...1075 1...1075 1100 1100 3400 3400 Copper Tubes, Aluminum or Copper Plate Fins 2...17 3...17 4...15 4...15 17.9 17.9 17.9 17.9 Centrifugal Type 2...10 x 10 2...10 x 10 2...12 x 12 2...12 x 12 2...12 x 12 Belt Belt Belt Belt Belt 6000 6000 7200 8000 10,000 3.7 3.0 5 71⁄2 10 8.7 [208/230,575 v] 10.2 [208/230,575 v] 4.25 3.45 5.90 9.5 [460 v] 11.8 [460 v] 56H 56H 184T 213T 215T — — — — — 1227-1559 1201-1462 1047-1251 1238-1494 1323-1579 Ball Ball Ball Ball Ball 1559 1550 1550 1550 1550 3.7/4.7 4.3/5.3 4.9/5.9 5.4/6.4 5.8/7.0 7 ⁄8 7⁄8 1 1 ⁄8 1 3 ⁄8 13⁄8 5.2 6.4 8.4 7.9 7.9 13⁄16 13⁄16 17⁄16 17⁄16 17⁄16 1...BX...42 1...BX...45 1...BX...50 1...BX...50 1...BX...51 13.5-15.5 13.5-15.5 13.3-14.8 14.6-15.4 14.6-15.4 66 52 34 43 43 4 3.5 1294 13⁄16 5 3.5 1279 13⁄16 6 3 1149 7 1 ⁄16 6 3 1366 7 1 ⁄16 6 3 1451 7 1 ⁄16 LEGEND ††Rollout switch is manual reset. \The 48TJ028 unit requires 2-in. industrial-grade filters capable of handling face velocities of up to 625 ft/min (such as American Air Filter no. 5700 or equivalent). Al — Aluminum Bhp — Brake Horsepower Cu — Copper TXV — Thermostatic Expansion Valve *Evaporator coil fin material/condenser coil fin material. †Weight of 14-in. roof curb. **Circuit 1 consists of lower portion of condenser coil and lower portion of evaporator coil, and Circuit 2 is the upper portion of both coils. NOTE: Units have a low-pressure switch (standard) located on the suction side. 7 Table 1 — Physical Data (cont) UNIT SIZE FURNACE SECTION Rollout Switch Cutout Temp (F)†† Burner Orifice Diameter (in. ...drill size) Natural Gas Pilot Orifice Diameter (Quantity) in. ...drill size Natural Gas Thermostat Heat Anticipator Setting (amps) 208/230,575 v Stage 1 Stage 2 460 v Stage 1 Stage 2 Gas Input (Btuh) Stage 1 Stage 2 Efficiency (Steady State) (%) Temperature Rise Range Manifold Pressure (in. wg) Natural Gas Gas Valve Quantity Field Gas Connection Size (in.) HIGH-PRESSURE SWITCH (psig) Standard Compressor Internal Relief (Differential) Cutout Reset (Auto.) LOW-PRESSURE SWITCH (psig) Cutout Reset (Auto.) FREEZE PROTECTION THERMOSTAT (F) Opens Closes OUTDOOR-AIR INLET SCREENS Quantity...Size (in.) 016D/E 020D 024D/E 028D/E 190 190 190 190 .113...33 .113...33 .113...33 .113...33 (1) .055...54/ (1) .055...54, (1) .041...59 (1) .055...54 (1) .041...59 (1) .055...54, (1) .041...59/ (2) .070...50 0.98 0.44 0.80 0.44 115,500/115,500 231,000/270,000 0.98 0.44 0.80 0.44 115,500 270,000 0.98 0.44 0.80 0.44 115,500/242,500 270,000/485,000 0.98 0.44 0.80 0.44 115,500/242,500 270,000/485,000 80 25-55/25-55 80 15-45 80 15-45/35-65 80 15-45/35-65 3.5 2 3.5 2 3.5 2 3.5 2 ⁄ 34 ⁄ 34 ⁄ 34 34 (1) .055...54, (1) .041...59/ (2) .070...50 ⁄ — 426 320 7 22 30 ± 5 45 ± 5 Cleanable 2...20 x 25 x 1 1...20 x 20 x 1 Throwaway \ 4...20 x 20 x 2 4...16 x 20 x 2 RETURN-AIR FILTERS Quantity...Size (in.) LEGEND ††Rollout switch is manual reset. \The 48TJ028 unit requires 2-in. industrial-grade filters capable of handling face velocities of up to 625 ft/min (such as American Air Filter no. 5700 or equivalent). Al — Aluminum Bhp — Brake Horsepower Cu — Copper TXV — Thermostatic Expansion Valve *Evaporator coil fin material/condenser coil fin material. †Weight of 14-in. roof curb. **Circuit 1 consists of lower portion of condenser coil and lower portion of evaporator coil, and Circuit 2 is the upper portion of both coils. NOTE: Units have a low-pressure switch (standard) located on the suction side. 8 Ductwork openings are shown in Fig. 1 and 4-6. Duct connections are shown in Fig. 7. Field-fabricated concentric ductwork may be connected as shown in Fig. 8 and 9. Attach all ductwork to roof curb and roof curb basepans. Step 3 — Field Fabricate Ductwork — Secure all ducts to building structure. Use flexible duct connectors between unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. Step 5 — Install Flue Hood — Flue hood is shipped Step 4 — Make Unit Duct Connections — Unit is shipped for through-the-bottom duct connections. secured under main control box. To install, secure flue hood to access panel. See Fig. 10 and 11. NOTE: When properly installed, flue hood will line up with combustion fan housing. See Fig. 12 and 13. NOTE: Do not drill in this area; damage to basepan may result in water leak. NOTE: Dimensions A, A8, B, and B8 are obtained from field-supplied ceiling diffuser. Shaded areas indicate block-off pans. Fig. 7 — Air Distribution — Through-the-Bottom (48TJ028-028 Shown) Fig. 9 — Concentric Duct Details NOTE: Do not drill in this area; damage to basepan may result in water leak. Fig. 8 — Concentric Duct Air Distribution (48TJ020-028 Shown) Fig. 10 — Flue Hood Location, 48TJD Low-Heat and 48TJE016 High-Heat Units 9 Fig. 11 — Flue Hood Locations, 48TJE024 and 028 High-Heat Units Fig. 13 — Combustion Fan Housing Location, 48TJE024 and 028 High-Heat Units Step 6 — Trap Condensate Drain — See Fig. 14 for drain location. One 3⁄4-in. half coupling is provided inside unit evaporator section for condensate drain connection. An 81⁄2 in. x 3⁄4-in. diameter and 2-in. x 3⁄4-in. diameter pipe nipple, coupled to standard 3⁄4-in. diameter elbows, provides a straight path down through hole in unit base rail (see Fig. 15). A trap at least 4-in. deep must be used. PRESSURE SWITCH Step 7 — Install Gas Piping — Unit is equipped for use with natural gas. Installation must conform with local building codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1. Install manual gas shutoff valve with a 1⁄8-in. NPT pressure tap for test gage connection at unit. Field gas piping must include sediment trap and union. See Fig. 16. COMBUSTION FAN HOUSING Do not pressure test gas supply while connected to unit. Always disconnect union before servicing. Natural gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13.5 in. wg. Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection. HEAT EXCHANGER SECTION Step 8 — Make Electrical Connections FIELD POWER SUPPLY — Unit is factory wired for voltage shown on unit nameplate. When installing units, provide a disconnect per NEC (National Electrical Code) of adequate size (Table 2). Fig. 12 — Combustion Fan Housing Location, 48TJD Low-Heat Units and 48TJE016 High-Heat Units 10 All field wiring must comply with NEC and local requirements. Route power and ground lines through control box end panel or unit basepan (see Fig. 4-6) to connections as shown on unit wiring diagram and Fig. 17. The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (National Fire Protection Association). 3/4" FPT DRAIN CONNECTION Field wiring must conform to temperature limitations for type ‘‘T’’ wire. All field wiring must comply with NEC and local requirements. Transformer no. 1 is wired for 230-v unit. If 208/230-v unit is to be run with 208-v power supply, the transformer must be rewired as follows: 1. Remove cap from red (208 v) wire. 2. Remove cap from orange (230 v) spliced wire. 3. Replace orange wire with red wire. 4. Recap both wires. 1-3/8" DRAIN HOLE Fig. 14 — Condensate Drain Details (48TJ016 Shown) IMPORTANT: BE CERTAIN UNUSED WIRES ARE CAPPED. Failure to do so may damage the transformers. Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2%. Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation instructions included with accessory. Locate thermostat assembly on a solid interior wall in the conditioned space to sense average temperature. Fig. 15 — Condensate Drain Piping Details NOTE: The maximum wire size for TB1 is 2/0. LEGEND EQUIP GND NEC TB Fig. 16 — Field Gas Piping — — — — Equipment Ground National Electrical Code Terminal Board Fig. 17 — Field Power Wiring Connections 11 Table 2 — Electrical Data COMPRESSOR VOLTAGE OFM NOMINAL RANGE UNIT NO. 1 NO. 2 48TJ (60 VOLTAGE Hz, 3 Phase) Min Max RLA LRA RLA LRA Qty Hp FLA (ea) 016 020 024 028 IFM POWER COMBUSTIONEXHAUST FAN MOTOR* POWER SUPPLY FLA FLA LRA FLA MCA MOCP† — 4.6 — 2.3 — 2.1 — 4.6 — 2.3 — 2.1 — 4.6 — 2.3 — 2.1 — 4.6 — 2.3 — 2.1 0.57 0.57 0.30 0.30 0.57 0.57 0.57 0.57 0.30 0.30 0.57 0.57 0.57 0.57 0.30 0.30 0.57 0.57 0.57 0.57 0.30 0.30 0.57 0.57 92/92 96/96 42 45 35 37 94/94 98/98 47 49 37 40 116/116 121/121 59 61 49 51 137/137 142/142 70 72 60 62 150/150 150/150 70 70 50 60 125/125 125/125 60 60 50 50 150/150 150/150 70 70 60 60 175/175 175/175 90 90 70 80 ⁄ 1.70 10.5/10.5 12 ⁄ 0.80 4.8 ⁄ 0.75 3.9 ⁄ 1.70 15.8/15.8 12 ⁄ 0.80 7.9 ⁄ 0.75 6.0 2 1 5.50 25.0/25.0 99 2 1 2.80 13.0 14.3 79 2 1 3.40 10.0 228 43.6 228 2 1 5.50 28.0/28.0 22.1 114 22.1 114 2 1 2.80 14.6 17.9 91 17.9 91 2 1 3.40 13.0 208/230 187 254 61.0 266 — — 3 12 460 414 508 28.0 120 — — 3 575 518 632 23.0 96 — — 3 12 208/230 187 254 35.6 198 28.2 160 3 12 460 414 508 17.8 99 14.1 80 3 575 518 632 14.3 79 11.3 64 3 12 208/230 187 254 35.6 198 35.6 198 460 414 508 17.8 99 17.8 575 518 632 14.3 79 208/230 187 254 43.6 460 414 508 575 518 632 LEGEND — 18.8 — 6.0 — 4.8 — 18.8 — 6.0 — 4.8 — 18.8 — 6.0 — 4.8 — 18.8 — 6.0 — 4.8 % Voltage Imbalance = 100 x max voltage deviation from average voltage average voltage FLA — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC — National Electrical Code OFM — Outdoor (Condenser) Fan Motor RLA — Rated Load Amps *The 48TJ024 and 028 high-heat units have 2 combustion-fan motors. †Fuse or HACR circuit breaker. EXAMPLE: Supply voltage is 460-3-60. AB = 452 v BC = 464 v AC = 455 v 452 + 464 + 455 3 1371 = 3 = 457 Average Voltage = Determine maximum deviation from average voltage. (AB) 457 - 452 = 5 v (BC) 464 - 457 = 7 v (AC) 457 - 455 = 2 v Maximum deviation is 7 v. Determine percent voltage imbalance. 7 % Voltage Imbalance = 100 x 457 = 1.53% NOTES: 1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker. 2. Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent voltage imbalance. This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%. IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately. 12 Route thermostat cable or equivalent single leads of colored wire from subbase terminals through conduit in unit to low-voltage connections as shown on unit label wiring diagram and in Fig. 18. NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C Minimum). All wire larger than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat. Set heat anticipator settings as follows: VOLTAGE 208/230,575 460 W1 0.98 0.80 W2 0.44 0.44 Settings may be changed slightly to provide a greater degree of comfort for a particular installation. Refer to Accessory Remote Control Panel instructions if required. Step 9 — Make Outdoor-Air Inlet Adjustments Fig. 20 — Economizer Damper Assembly-End View MANUAL OUTDOOR-AIR DAMPER — All units (except those equipped with a factory-installed economizer) have a manual outdoor-air damper to provide ventilation air. Damper can be preset to admit up to 25% outdoor air into return-air compartment. To adjust, loosen securing screws and move damper to desired setting, then retighten screws to secure damper (Fig. 19). OPTIONAL ECONOMIZER Economizer Motor Control Module (See Fig. 20-22) — Set economizer motor to the D setting (Fig. 21). Damper Vent Position Setting 1. Set fan switch at ON position (continuous fan operation) and close night switch if used. 2. Set system selector switch at OFF position. 3. Turn damper adjustment knob located on control module clockwise slowly until dampers assume desired vent position. Do not manually operate economizer motor. Damage to motor will result. LED — Light-Emitting Diode Fig. 21 — Economizer Motor Control Module Step 10 — Install Outdoor-Air Hood — The outdoorair hood is common to 25% air ventilation and economizer. If economizer is used, all electrical connections have been made and adjusted at the factory. Assemble and install hood in the field. NOTE: The hood top panel, upper and lower filter retainers, hood drain pan, baffle (020-028), and filter support bracket are secured opposite the condenser end of the unit. The screens, hood side panels, remaining section of filter support bracket, seal strip, and hardware are in a package located inside the return-air filter access panel (Fig. 23). 1. Attach seal strip to upper filter retainer. See Fig. 24. 2. Assemble hood top panel, side panels, upper filter retainer, and drain pan (see Fig. 25). 3. Secure lower filter retainer and support bracket to unit. See Fig. 25. Leave screws loose on 020-028 units. 4. Slide baffle (020-028) behind lower filter retainer and tighten screws. Fig. 18 — Field Control Thermostat Wiring Fig. 19 — 25% Outdoor-Air Section Details 13 Fig. 25 — Outdoor-Air Hood Details 5. Loosen sheet metal screws for top panel of base unit located above outdoor-air inlet opening, and remove screws for hood side panels located on the sides of the outdoorair inlet opening. 6. Match notches in hood top panel with unit top panel screws. Insert hood flange between top panel flange and unit. Tighten screws. 7. Hold hood side panel flanges flat against unit, and install screws removed in Step 5. 8. Insert outdoor-air inlet screens and spacer in channel created by lower filter retainer and filter support bracket. 9. Attach remaining section of filter support bracket. Fig. 22 — Economizer Motor Control Module Location START-UP Use the following information and Start-Up Checklist on page CL-1 to check out unit PRIOR to start-up. Unit Preparation — Check that unit has been installed in accordance with these installation instructions and applicable codes. Compressor Mounting — Loosen the compressor holddown bolts until sidewise movement of the washer under each holddown bolt head can be obtained. Do not loosen completely as bolts are self-locking and will maintain adjustment. Fig. 23 — Outdoor-Air Hood Component Location Internal Wiring — Check all electrical connections in unit control boxes; tighten as required. Refrigerant Service Ports — Each refrigerant system has 1 suction port located in the top of the compressor motor casing. All units also have one service port on the liquid line and one on either the compressor discharge flange or discharge line. Be sure that caps on the ports are tight. Crankcase Heater(s) — Crankcase heater(s) is energized as long as there is power to the unit. IMPORTANT: Unit power must be on for 24 hours prior to start-up. Otherwise, damage to compressor may result. Evaporator Fan — Fan belt and variable pulleys are factory-installed. See Tables 3-7 for Fan Performance Data. Remove tape from fan pulley, and be sure that fans rotate in the proper direction. See Table 8 for air quantity limits. See Tables 9 and 10 for static pressure information for accessories and options. See Table 11 for fan rpm at various motor pulley settings. To alter fan performance, see Evaporator Fan Performance Adjustment section on page 20. Fig. 24 — Seal Strip Location 14 Condenser-Fans and Motors — Condenser fans and Gas Heat — Verify gas pressures before turning on heat as follows: 1. Turn off manual gas stop. 2. Connect pressure gage to supply gas pressure tap (See Fig. 16). 3. Connect pressure gage to manifold pressure tap on gas valve. 4. Turn on manual gas stop and set thermostat to HEAT position. After the unit has run for several minutes, verify that incoming pressure is 5.0 in. wg or greater, and that the manifold pressure is 3.5 in. wg. If manifold pressure must be adjusted, refer to Gas Valve Adjustment section on page 24. 5. After unit has been in operation for 5 minutes, check temperature rise across the heat exchangers. See unit informative plate for correct rise limits of the heat supplied. Air quantities may need to be adjusted to bring the actual rise to within the allowable limits. motors are factory set. Refer to Condenser-Fan Adjustment section on page 21 as required. Be sure that fans rotate in the proper direction. Return-Air Filters — Check that correct filters are installed in filter tracks (see Table 1). Do not operate unit without return-air filters. Outdoor-Air Inlet Screens — Outdoor-air inlet screens must be in place before operating unit. Accessory Economizer Adjustment — Remove filter access panel. Check that outdoor-air damper is closed and return-air damper is open. Economizer operation and adjustment are described in Base Unit Operation section on page 18, and in Economizer Adjustment section on page 22. Table 3 — Fan Performance Data, 48TJ016 — 208/230-V and 460-V Units AIRFLOW (Cfm) 4500 4800 5100 5400 5700 6000 6300 6600 6900 7200 7500 AIRFLOW (Cfm) 4500 4800 5100 5400 5700 6000 6300 6600 6900 7200 7500 Rpm 801 843 885 927 971 1016 1059 1104 1150 1194 1238 EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1.05 933 890 1.26 1119 971 1.46 1297 1050 1.67 1483 1.25 1110 928 1.47 1306 1006 1.68 1492 1081 1.90 1687 1.47 1306 968 1.70 1510 1043 1.93 1714 1114 2.16 1918 1.71 1519 1008 1.95 1732 1080 2.20 1954 1148 2.44 2167 1.98 1758 1049 2.24 1989 1118 2.50 2220 1134 2.75 2442 2.28 2025 1091 2.55 2265 1158 2.83 2513 1222 3.10 2753 2.60 2309 1133 2.89 2567 1198 3.17 2815 1259 3.46 3073 2.96 2629 1174 3.26 2895 1239 3.56 3162 1297 3.86 3428 3.35 2975 1218 3.67 3259 1281 3.98 3535 — — — 3.77 3348 1260 4.10 3641 — — — — — — 4.23 3758 — — — — — — — — — Rpm 1275 1293 1316 1342 1370 1401 — — — — — EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2.39 2123 1349 2.70 2398 1421 3.03 2691 2.62 2327 1364 2.92 2593 1433 3.24 2877 2.90 2575 1382 3.18 2824 1448 3.49 3099 3.20 2842 1403 3.47 3082 1466 3.77 3348 3.54 3144 1429 3.81 3384 1487 4.11 3650 3.92 3481 1458 4.20 3730 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — LEGEND Bhp — Brake Horsepower Input to Fan FIOP — Factory Installed Option Watts — Input Watts to Motor NOTES: 1. Factory shipped motor drive range is 1227 to 1559 rpm. Other rpms require a field-supplied drive. 2. Static pressure losses (i.e., economizer) must be added to external static pressure before entering Fan Performance table. See Table 9 for accessory/FIOP static pressure information. Rpm 1490 1501 1514 1529 — — — — — — — Rpm 1125 1153 1183 1214 1247 1282 1318 1355 — — — 1.0 1.2 Bhp Watts Rpm Bhp Watts 1.88 1670 1200 2.12 1883 2.13 1892 1223 2.36 2096 2.40 2131 1250 2.64 2345 2.69 2389 1279 2.94 2611 3.01 2673 1309 3.28 2913 3.36 2984 1342 3.64 3233 3.74 3321 1375 4.02 3570 4.15 3686 — — — — — — — — — — — — — — — — — — 2.0 Bhp Watts 3.39 3011 3.59 3188 3.86 3428 4.16 3694 — — — — — — — — — — — — — — 3. Interpolation is permissible. Do not extrapolate. 4. Maximum continuous bhp is 4.25 and the maximum continuous watts are 3775. Extensive motor and drive testing on these units ensures that the full horsepower range of the motor can be utilized with confidence. Using your fan motors up to the watts rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 15 Table 4 — Fan Performance Data, 48TJ016 — 575-V Units AIRFLOW (Cfm) 4500 4800 5100 5400 5700 6000 6300 6600 6900 7200 7500 AIRFLOW (Cfm) 4500 4800 5100 5400 5700 6000 6300 6600 6900 7200 7500 Rpm 801 843 885 927 971 1016 1059 1104 1150 — — EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1.05 933 890 1.26 1119 971 1.46 1297 1050 1.67 1483 1.25 1110 928 1.47 1306 1006 1.68 1492 1081 1.90 1687 1.47 1306 968 1.70 1510 1043 1.93 1714 1114 2.16 1918 1.71 1519 1008 1.95 1732 1080 2.20 1954 1148 2.44 2167 1.98 1758 1049 2.24 1989 1118 2.50 2220 1134 2.75 2442 2.28 2025 1091 2.55 2265 1158 2.83 2513 1222 3.10 2753 2.60 2309 1133 2.89 2567 1198 3.17 2815 — — — 2.96 2629 1174 3.26 2895 — — — — — — 3.35 2975 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — Rpm 1275 1293 1316 1342 — — — — — — — EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 2.0 Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 2.39 2123 1349 2.70 2398 1421 3.03 2691 1490 3.39 3011 2.62 2327 1364 2.92 2593 1433 3.24 2877 — — — 2.90 2575 1382 3.18 2824 — — — — — — 3.20 2842 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — LEGEND Bhp — Brake Horsepower Input to Fan FIOP — Factory-Installed Option Watts — Input Watts to Motor NOTES: 1. Factory shipped motor drive range is 1201 to 1462 rpm. Other rpms require a field-supplied drive. 2. Static pressure losses (i.e., economizer) must be added to external static pressure before entering Fan Performance table. See Table 9 for accessory/FIOP static pressure information. Rpm 1125 1153 1183 1214 1247 1282 — — — — — 1.0 1.2 Bhp Watts Rpm Bhp Watts 1.88 1670 1200 2.12 1883 2.13 1892 1223 2.36 2096 2.40 2131 1250 2.64 2345 2.69 2389 1279 2.94 2611 3.01 2673 1309 3.28 2913 3.36 2984 — — — — — — — — — — — — — — — — — — — — — — — — — — — — 3. Interpolation is permissible. Do not extrapolate. 4. Maximum continuous bhp is 3.45 and the maximum continuous watts are 3065. Extensive motor and drive testing on these units ensures that the full horsepower range of the motor can be utilized with confidence. Using your fan motors up to the watts rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. Table 5 — Fan Performance Data, 48TJ020 AIRFLOW (CFM) 5000 5500 6000 6500 7000 7200 7500 8000 8500 9000 AIRFLOW (Cfm) 5000 5500 6000 6500 7000 7200 7500 8000 8500 9000 Rpm 669 717 767 817 869 889 920 973 1026 1079 EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1.10 1019 772 1.40 1291 870 1.80 1582 963 2.10 1903 1.40 1292 813 1.80 1585 905 2.10 1892 992 2.50 2223 1.80 1617 858 2.20 1932 944 2.50 2256 1026 2.90 2600 2.20 1992 903 2.60 2329 985 3.00 2673 1062 3.40 3031 2.70 2427 950 3.10 2787 1028 3.50 3151 1102 3.90 3527 2.94 2624 969 3.34 2993 1046 3.74 3366 1118 4.18 3749 3.30 2919 998 3.70 3303 1073 4.10 3689 1143 4.60 4083 3.90 3476 1047 4.30 3886 1119 4.80 4294 1186 5.30 4708 4.60 4102 1097 5.10 4635 1166 5.60 4967 — — — 5.40 4800 — — — — — — — — — Rpm 1178 1196 1218 1244 1275 1288 1307 — — — EXTERNAL STATIC PRESSURE (in. wg) 1.3 1.4 1.6 Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3.15 2820 1218 3.40 3016 1295 3.80 3425 3.55 3164 1234 3.80 3366 1309 4.20 3789 4.00 3565 1251 4.20 3772 1327 4.70 4206 4.50 4022 1279 4.70 4233 1348 5.20 4677 5.05 4547 1308 5.30 4762 — — — 5.33 4783 — — — — — — 5.75 5135 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — LEGEND Rpm 1369 1381 1396 1415 — — — — — — Rpm 1052 1076 1104 1136 1172 1187 1210 1250 — — 1.0 1.2 Bhp Watts Rpm Bhp Watts 2.50 2251 1137 2.90 2623 2.90 2680 1157 3.30 2962 3.30 2967 1181 3.80 3358 3.80 3410 1209 4.30 3811 4.40 3919 1241 4.80 4331 4.64 4147 1255 5.08 4564 5.00 4490 1275 5.50 4914 5.70 5131 — — — — — — — — — — — — — 1.8 Bhp Watts 4.30 3849 4.70 4229 5.20 4658 5.80 5139 — — — — — — — — — — — — 3. Interpolation is permissible. Do not extrapolate. 4. Maximum continuous bhp is 5.9 and the maximum continuous watts are 5180. Extensive motor and drive testing on these units ensures that the full horsepower range of the motor can be utilized with confidence. Using your fan motors up to the watts rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. Bhp — Brake Horsepower Input to Fan FIOP — Factory-Installed Option Watts — Input Watts to Motor NOTES: 1. Factory shipped motor drive range is 1047 to 1251 rpm. Other rpms require a field-supplied drive. 2. Static pressure losses (i.e., economizer) must be added to external static pressure before entering Fan Performance table. See Table 10 for accessory/FIOP static pressure information. 16 Table 6 — Fan Performance Data, 48TJ024 AIRFLOW (CFM) 6000 6500 7000 7500 8000 8500 9000 9500 10,000 AIRFLOW (Cfm) 6000 6500 7000 7500 8000 8500 9000 9500 10,000 Rpm 767 817 869 920 973 1026 1079 1133 1188 EXTERNAL STATIC PRESSURE (in. wg) 0.2 0.4 0.6 0.8 Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 1.80 1617 858 2.20 1932 944 2.50 2256 1026 2.90 2600 2.20 1992 903 2.60 2329 985 3.00 2673 1062 3.40 3031 2.70 2427 950 3.10 2787 1028 3.50 3151 1102 3.90 3527 3.30 2919 998 3.70 3303 1073 4.10 3689 1143 4.60 4083 3.90 3476 1047 4.30 3886 1119 4.80 4294 1186 5.30 4708 4.60 4102 1097 5.10 4635 1166 5.60 4967 1231 6.00 5401 5.40 4800 1147 5.90 5257 1214 6.40 5714 1276 6.90 6171 6.20 5576 1199 6.80 6058 1263 7.30 6540 1323 7.90 7018 7.20 6432 1250 7.80 6939 1313 8.30 7444 1371 8.90 7946 Rpm 1255 1279 1308 1339 1373 1410 1449 1488 — EXTERNAL STATIC PRESSURE (in. wg) 1.4 1.6 1.8 1.9 2.0 Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 4.20 3772 1327 4.70 4206 1396 5.20 4658 1431 5.45 4884 1465 5.70 5110 4.70 4233 1348 5.20 4677 1415 5.80 5139 1449 6.10 5370 1482 6.40 5601 5.30 4762 1373 5.80 5215 1437 6.40 5686 1469 6.70 5922 1501 7.00 6157 6.00 5356 1401 6.50 5818 1462 7.00 6298 1493 7.25 6538 1523 7.50 6778 6.70 6024 1433 7.30 6495 1493 7.80 6966 1523 8.05 7202 — — — 7.60 6765 1467 8.10 7248 1524 8.70 7731 — — — — — — 8.50 7584 1503 9.00 8033 — — — — — — — — — 9.40 8403 — — — — — — — — — — — — — — — — — — — — — — — — — — Rpm 1104 1136 1172 1210 1250 1292 1336 1381 1426 1.0 1.2 Bhp Watts Rpm Bhp Watts 3.30 2967 1181 3.80 3358 3.80 3410 1209 4.30 3811 4.40 3919 1241 4.80 4331 5.00 4490 1275 5.50 4914 5.70 5131 1313 6.20 5569 6.50 5843 1352 7.00 6297 7.40 6632 1393 7.90 7102 8.40 7500 1436 8.90 7988 9.50 8449 — — — 4. Interpolation is permissible. Do not extrapolate. 5. Maximum continuous bhp is 8.7 for 208/230 and 575-v units and 9.5 for 460-v units. The maximum continuous watts are 7915 for the 208/230 and 575-v units and 8640 for the 460-v units. Extensive motor and drive testing on these units ensures that the full horsepower range of the motor can be utilized with confidence. Using your fan motors up to the watts rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. LEGEND Bhp — Brake Horsepower Input to Fan FIOP — Factory-Installed Option Watts — Input Watts to Motor NOTES: 1. Boldface indicates additional capability of the 460-v motor. 2. Factory shipped motor drive range is 1238 to 1494 rpm. Other rpms require a field-supplied drive. 3. Static pressure losses (i.e., economizer) must be added to external static pressure before entering Fan Performance table. See Table 10 for accessory/FIOP static pressure information. Table 7 — Fan Performance Data, 48TJ028 AIRFLOW (CFM) 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,250 AIRFLOW (Cfm) 7,500 8,000 8,500 9,000 9,500 10,000 10,500 11,000 11,250 Rpm 962 1017 1072 1128 1185 1241 1298 1355 1384 Rpm 1309 1349 1390 1433 1478 1524 — — — 0.2 Bhp 3.39 4.04 4.76 5.57 6.47 7.45 8.54 9.72 10.36 Watts 3123 3717 4385 5129 5955 6865 7865 8956 9540 Rpm 1039 1091 1143 1196 1250 1304 1359 1414 1441 EXTERNAL STATIC PRESSURE (in. wg) 0.4 0.6 0.8 Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 3.81 3507 1111 4.23 3895 1179 4.66 4295 4.48 4126 1160 4.93 4536 1225 5.38 4954 5.23 4818 1209 5.70 5250 1271 6.18 5688 6.07 5587 1260 6.56 6042 1320 7.06 6501 6.99 6437 1311 7.51 6915 1369 8.03 7395 8.00 7372 1363 8.55 7873 1419 9.09 8376 9.12 8396 1415 9.69 8921 1469 10.26 9446 10.33 9512 1469 10.93 10,062 1521 11.52 10,609 10.97 10,107 1495 11.58 10,668 — — — 0.9 Rpm Bhp 1212 4.89 1256 5.62 1302 6.42 1348 7.32 1396 8.30 1445 9.37 1495 10.55 — — — — Watts 4503 5170 5913 6735 7638 8629 9710 — — 1.0 Rpm Bhp 1245 5.11 1287 5.85 1332 6.66 1377 7.57 1424 8.56 1472 9.64 1521 10.83 — — — — Watts 4710 5386 6137 6968 7881 8882 9973 — — EXTERNAL STATIC PRESSURE (in. wg) 1.2 1.3 1.4 1.6 1.8 Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 5.58 5143 1341 5.83 5370 1372 6.08 5597 1434 6.59 6067 1494 7.12 6558 6.33 5833 1379 6.59 6065 1409 6.84 6297 1467 7.36 6779 — — — 7.17 6600 1419 7.43 6839 1447 7.68 7077 1504 8.22 7571 — — — 8.08 7446 1461 8.35 7692 1488 8.62 7938 — — — — — — 9.10 8378 1505 9.37 8626 — — — — — — — — — 10.20 9396 1550 10.48 9653 — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — LEGEND Bhp — Brake Horsepower Input to Fan FIOP — Factory-Installed Option Watts — Input Watts to Motor NOTES: 1. Boldface indicates additional capability of the 460-v motor. 2. Factory shipped motor drive range is 1323 to 1579 rpm. Other rpms require a field-supplied drive. 3. Static pressure losses (i.e., economizer) must be added to external static pressure before entering Fan Performance table. See Table 10 for accessory/FIOP static pressure information. 4. Interpolation is permissible. Do not extrapolate. 5. Fan performance is based on wet coils, clean filters, and casing losses. 6. Maximum continuous bhp is 10.2 for 208/230 and 575-v units and 11.8 for 460-v units. The maximum continuous watts are 9510 for the 208/230 and 575-v units and 11,000 for the 460-v units. Extensive motor and drive testing on these units ensures that the full horsepower range of the motor can be utilized with confidence. Using your fan motors up to the watts rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. 17 Table 8 — Air Quantity Limits UNIT 48TJ 016 020 024 028 MINIMUM CFM 4500 5400 6000 7500 MAXIMUM CFM 7,500 9,000 10,000 11,250 Table 9 — Accessory/FIOP Static Pressure* (in. wg) — 48TJ016 COMPONENT 4500 0.04 Economizer CFM 6000 0.07 5000 0.05 7200 0.09 7500 0.10 LEGEND FIOP — Factory-Installed Option *The static pressure must be added to external static pressure. The sum and the evaporator enteringair cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts. Table 10 — Accessory/FIOP Static Pressure* (in. wg) — 48TJ020-028 COMPONENT Economizer 5000 0.06 6000 0.07 7200 0.09 CFM 9000 0.11 10,000 0.12 11,250 0.14 LEGEND FIOP — Factory-Installed Option *The static pressure must be added to external static pressure. The sum and the evaporator enteringair cfm should then be used in conjunction with the Fan Performance tables to determine blower rpm and watts. Table 11 — Fan Rpm at Motor Pulley Settings* UNIT 48TJ 016 (208/230,460 v) 016 (575 v) 020 024 028 0 1559 1462 1251 1494 † ⁄ 1524 1436 1234 1472 † 12 1 1491 1410 1217 1451 1536 11⁄2 1458 1384 1200 1430 1515 MOTOR PULLEY TURNS OPEN 2 21⁄2 3 31⁄2 4 1425 1392 1359 1326 1293 1358 1332 1305 1279 1253 1183 1166 1149 1132 1115 1408 1387 1366 1345 1323 1493 1472 1451 1430 1408 41⁄2 1260 1227 1098 1302 1387 5 1227 1201 1081 1281 1366 51⁄2 — — 1064 1259 1344 6 — — 1047 1238 1323 *Approximate fan rpm shown. †Do not run this fan at less than 1 full turn open, as it will exceed the maximum allowable rpm of 1550. When sequence is complete, time-delay relay closes and evaporator fans start. Second-Stage — 48TJD016-028 Low-Heat and 48TJE016 High Heat Units — With an additional heating call, the secondstage thermostat closes. (The control relay [HR2] closes during the first stage of operation.) Pilot valve no. 2 opens, and the spark ignitor ignites pilot. The sensor detects a flame and energizes main gas valve coil no. 2, opening main gas valve no. 2. Gas flows to the main burners, and the second-stage burners ignite. The spark ignitor turns off. When the second-stage thermostat is satisfied, the secondstage gas valve closes. When the first-stage thermostat is satisfied, the first-stage gas valve closes. The induced-draft motor turns off, the time delay relay opens, and the timer sequence begins. When the sequence is complete, the evaporator-fan motor turns off. Second-Stage — 48TJE024,028 High-Heat Units — With an additional heating call, the second-stage thermostat closes. (The control relay [HR2] closes during the first stage of operation.) The second-stage induced-draft relay closes, and the second-stage induced-draft motor starts. The second-stage pressure switch closes and pilot valve no. 2 opens, allowing gas to flow to the second-stage pilot. Spark ignitor ignites pilot flame. The sensor detects the flame, and main gas valve no. 2 opens. Gas flows to main burners and second-stage burners ignite. Spark ignitor turns off. Base Unit Operation COOLING, UNITS WITHOUT ECONOMIZER — When thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC) and compressor contactor no. 1 (C1) are energized and evaporatorfan motor (IFM), compressor no. 1 (48TJ020-028) or unloaded compressor (48TJ016), and condenser fan start. The condenser-fan motors run continuously while unit is cooling. If the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is energized and compressor no. 2 starts (48TJ020-028), or compressor no. 1 runs fully loaded (48TJ016). HEATING, UNITS WITHOUT ECONOMIZER NOTE: The 48TJ016-028 units have 2 stages of heat. First Stage — All Units — Turn unit power on. Open manual gas line valve. Set thermostat system switch at HEAT or AUTO. position and set fan switch to AUTO. position for heating. First-stage thermostat calls for heat. Time-delay relay for evaporator fan begins timer sequence. Induced-draft relay closes, and induced-draft motor starts. Pressure switch closes and pilot valve no. 1 opens, allowing gas to flow to the first-stage pilot. Spark ignitor ignites pilot flame. Sensor detects flame and the main gas valve no. 1 opens. Gas flows to main burners and first-stage burners ignite. Spark ignitor turns off. 18 removing screws holding motor mounting plate to top of combustion fan housing (Fig. 26 and 27). The motor and wheel assembly will slide up and out of the fan housing. Remove the blower wheel from the motor shaft and clean with a detergent or solvent. Replace motor and wheel assembly. EVAPORATOR COIL — Clean as required with commercial coil cleaner. CONDENSER COIL — Clean condenser coil annually and as required by location and outdoor-air conditions. Inspect coil monthly; clean as required. CONDENSATE DRAIN — Check and clean each year at start of cooling season. In winter, keep drains and traps dry. FILTERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions require. Refer to Table 1 for type and size. NOTE: The 48TJ028 unit requires industrial grade throwaway filters capable of withstanding face velocities up to 625 fpm. Ensure that replacement filters for the 48TJ028 units are rated for 625 fpm. When the second-stage thermostat is satisfied, the secondstage gas valve closes and the second-stage induced-draft motor turns off. When the first-stage thermostat is satisfied, the first-stage gas valve closes. The first-stage induced-draft motor turns off, the time relay opens, and the timer sequence begins. When the sequence is complete, the evaporator-fan motor turns off. COOLING, UNITS WITH ECONOMIZER — Upon a call for cooling, when outdoor ambient is above the changeover control setting, the economizer damper moves to VENT position. The compressors and evaporator and condenser fans energize and operate as per Cooling, Units Without Economizer section above. Upon a first call for cooling, when outdoor ambient is below the changeover control setting, the evaporator fan starts and the economizer is fully open. The compressors remain off. Upon a second-stage call for cooling, compressor no. 1 (48TJ020-028) or unloaded compressor (48TJ016) is energized and mechanical cooling is integrated with economizer cooling. If the outdoor-air temperature drops below 50 F, a cooling lockout switch prevents the compressors from running. When supply-air temperature drops below a fixed set point, the economizer damper modulates to maintain the temperature at the fixed set point. A freeze protection thermostat (FPT) is located on the evaporator coil. It detects frost build-up and locks out the compressors, allowing the coil to clear. Once frost has melted, the compressors can be reenergized by resetting the thermostat. HEATING, UNITS WITH ECONOMIZER — Outdoor-air damper stays at VENT position while evaporator fan is operating. SERVICE Fig. 26 — Typical Gas Heating Section, 2-Stage Units (48TJD Units Shown) Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury. Cleaning — Inspect unit interior at beginning of each heating and cooling season and as operating conditions require. Remove unit top panel and/or side panels for access to unit interior. MAIN AND PILOT BURNERS — At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the pilot and main burner flames through view port (in condenser section), and adjust if necessary. Refer to Pilot Adjustment or Main Burners sections on page 24. FLUE GAS PASSAGEWAYS — The flue collector box and heat exchanger cells may be inspected by removing heat exchanger access panel (Fig. 4-6), flue box cover, and main burner assembly (Fig. 26). Refer to Main Burners section on page 24 for burner removal sequence. If cleaning is required, remove heat exchanger turbulators (Fig. 27) and clean all parts with a wire brush. COMBUSTION-AIR BLOWER — Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bi-monthly to determine proper cleaning frequency. To inspect blower wheel, remove heat exchanger access panel. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove motor and wheel assembly by Fig. 27 — Typical Heating Section with Main Burners Removed (48TJD Units Shown) 19 4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. Increasing fan speed increases load on motor. Do not exceed maximum speed specified in Table 1. See Table 8 for air quantity limits. 5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.) 6. Replace and tighten belts (see Belt Tension Adjustment section on page 21). OUTDOOR-AIR INLET SCREENS — Clean screens with steam or hot water and a mild detergent. Do not use throwaway filters in place of screens. Lubrication COMPRESSORS — Each compressor is charged with the correct amount of oil at the factory. The 48TJ016 compressor runs with a slightly low sight glass oil level. Oil level with compressor off should be about 1⁄4 of sight glass as shown in Fig. 28. If oil charge is above 1⁄4 sight glass, do not remove any oil until the compressor crankcase heater has been energized for at least 24 hours. FAN SHAFT BEARINGS — For 016 units, bearings are permanently lubricated. No field lubrication is required. For 020028 units, lubricate bearings at least every 6 months with suitable bearing grease. Extended grease line is provided for far side fan bearing (opposite drive side). Typical lubricants are given below: MANUFACTURER Texaco Mobil Sunoco Texaco To align fan and motor pulleys: 1. Loosen fan pulley setscrews. 2. Slide fan pulley along fan shaft. 3. Make angular alignment by loosening motor from mounting plate. LUBRICANT Regal AFB-2* Mobilplex EP No. 1 Prestige 42 Multifak 2 *Preferred lubricant because it contains rust and oxidation inhibitors. CONDENSER AND EVAPORATOR-FAN MOTOR BEARINGS — The condenser- and evaporator-fan motors have permanently-sealed bearings, so no field lubrication is necessary. Evaporator Fan Performance Adjustment (Fig. 29-31) — Fan motor pulleys are factory set for speed shown in Table 1. To change fan speeds: 1. Shut off unit power supply. 2. a. 016 only: Loosen belt by loosening carriage nuts holding motor mount assembly to fan scroll side plates (A and B). b. 020-028 only: Loosen nuts on the 2 carriage bolts in the mounting base. Install jacking bolt and plate under motor base (bolt and plate are shipped in installer’s packet). Using bolt and plate, raise motor to top of slide and remove belt. Secure motor in this position by tightening the nuts on the carriage bolts. 3. Loosen movable-pulley flange setscrew (see Fig. 29). Fig. 29 — Evaporator-Fan Alignment and Adjustment Evaporator Fan Service and Replacement 48TJ016 UNITS (See Fig. 30) NOTE: To remove belts only, follow Steps 1-6. 1. Remove filter and supply-air section panels. 2. Remove unit top panel. 3. Loosen carriage nuts A and B holding motor mount assembly to fan scroll side plates. 4. Loosen screw C. 5. Rotate motor mount assembly (with motor attached) as far as possible away from evaporator coil. 6. Remove belt. 7. Rotate motor mount assembly back past original position toward evaporator coil. 8. Remove motor mounting nuts D and E (both sides). 9. Lift motor up through top of unit. 10. Reverse above procedure to reinstall motor. 11. Check and adjust belt tension as necessary. Fig. 28 — 48TJ016 Compressor Sight Glass Oil Level 20 NOTE: A 31⁄2-in. bolt and threaded plate are included in the installer’s packet. They can be added to the motor support channel below the motor mounting plate to aid in raising the motor. Fig. 31 — 48TJ020-028 Evaporator-Fan Motor Section Belt Tension Adjustment — To adjust belt tension: Fig. 30 — 48TJ016 Evaporator-Fan Motor Adjustment 1. Loosen fan motor bolts. 2. a. 016 Units: Move motor mounting plate up or down for proper belt tension (1⁄2 in. deflection with one finger). 48TJ020-028 UNITS (See Fig. 31) — The 48TJ020-028 units use a fan motor mounting system that features a slide-out motor mounting plate. To replace or service the motor, slide out the bracket. 1. Remove the evaporator-fan access panel and the heating control access panel. b. 020-028 Units: Turn motor jacking bolt to move motor mounting plate up or down for proper belt tension (3⁄8 in. deflection at midspan with one finger [9 lb force]). 3. Tighten nuts. 4. Adjust bolts and nut on mounting plate to secure motor in fixed position. Condenser-Fan Adjustment 2. Remove the center post (located between the evaporator fan and heating control access panels) and all screws securing it. 3. Loosen nuts on the 2 carriage bolts in the motor mounting base. 4. Using jacking bolt under motor base, raise motor to top of slide and remove belt. Secure motor in this position by tightening the nuts on the carriage bolts. 5. Remove the belt drive. 6. Remove jacking bolt and tapped jacking bolt plate. 7. Remove the 2 screws that secure the motor mounting plate to the motor support channel. 8. Remove the 3 screws from the end of the motor support channel that interfere with the motor slide path. 9. Slide out the motor and motor mounting plate. 10. Disconnect wiring connections and remove the 4 mounting bolts. 11. Remove the motor. 12. To install the new motor, reverse Steps 1-11. 48TJ016,020 UNITS (Fig. 32) 1. Shut off unit power supply. 2. Remove access panel(s) closest to the fan to be adjusted. 3. Loosen fan hub setscrews. 4. Adjust fan height on shaft using a straightedge placed across the fan orifice. 5. Tighten setscrews and replace panel(s). 6. Turn on unit power. 48TJ024,028 UNITS (Fig. 33) 1. Shut off unit power supply. 2. Remove fan top-grille assembly and loosen fan hub screws. 3. Adjust fan height on unit, using a straightedge placed across the fan orifice. 4. Tighten setscrews and replace rubber hubcap to prevent hub from rusting to motor shaft. 5. Fill hub recess with permagum if rubber hubcap is missing. 21 Power Failure — Dampers have a spring return. In event of power failure, dampers will return to fully closed position until power is restored. Do not manually operate damper motor. Table 12 — Economizer Checkout Procedures TEST PROCEDURE A. Disconnect power at TR and TR1. Disconnect jumper between P and P1. See Fig. 21. B. Jumper TR to 1. C. Jumper T1 to T. D. Disconnect outdoor-air thermostat connections from SO and +. Factory-installed 800 ohm resistor should remain connected to SR and +. E. Reconnect power to terminals TR and TR1. Fig. 32 — Condenser Fan Adjustment, 48TJ016,020 RESULTS 1. LED (light-emitting diode) should be off. 2. Motor is in closed position. Fig. 33 — Condenser-Fan Adjustment, 48TJ024,028 TEST PROCEDURE Disconnect factory-installed resistor from terminals SR and +. Economizer Adjustment — See Tables 12 and 13 for checkout and enthalpy simulation. Make certain the outdoor-air damper is fully closed and the return-air damper is fully open before completing the following steps: 1. Turn on power to the unit. 2. Turn the thermostat fan switch to the ON position. The damper will go to the vent position. 3. Adjust the vent position with the minimum damper position adjustment on the economizer motor control module. See Fig. 21. 4. Set the system selector switch to COOL position and set the cooling temperature selector to its lowest setting. NOTE: The cooling mode may also be simulated by removing the thermostat wires from terminals Y1 and Y2 and installing a jumper between terminals R and Y1. Refer to unit label diagram for terminal locations. 5. Set the outdoor-air thermostat (OAT), located in the economizer section of the unit (see Fig. 20) to 75 F. 6. If the outdoor temperature is below 75 F, the economizer will control the mixed air with the mixed-air sensor. If the outdoor air is above 75 F, place a jumper around the contacts of the OAT. 7. Jumper terminal T to terminal T1 on the module (see Fig. 21). The economizer will go to the full open position. The outdoor-air damper will go to the full open position, and the return-air damper will go to the full closed position. 8. Adjust mechanical linkage, if necessary, for correct positioning. If may be necessary to remove the filters to adjust the linkage. 9. Remove the jumper from around the contacts of the OAT if installed in Step 6. Remove the jumper from terminals T and T1 installed in Step 7. 10. If the cooling mode was simulated to operate the unit in Step 4, remove the jumper and reconnect the thermostat wires to terminals Y1 and Y2. RESULTS 1 LED (light-emitting diode) should be on. 2. Motor drives toward open. Table 13 — High and Low Outdoor-Air Simulation TEST PROCEDURE A. Reconnect factory-installed 800 ohm resistor between terminals SR and +. B. Connect 1200 ohm checkout resistor between terminals SO and +. C. Turn set point potentiometer to position A. RESULTS Low outdoor-air test results: 1. LED (light-emitting diode) should be on. 2. Motor drives toward open. D. Turn set point potentiometer to position D. E. Disconnect 1200 ohm checkout resistor. High outdoor-air test results: 1. LED should be off. 2. Motor drives toward closed. Refrigerant Charge — Amount of refrigerant charge is listed on unit nameplate and in Table 1. Refer to Carrier GTAC II; Module 5; Charging, Recovery, Recycling, and Reclamation section for charging methods and procedures. Unit panels must be in place when unit is operating during charging procedure. NO CHARGE — Use standard evacuating techniques. After evacuating system, weigh in the specified amount of refrigerant (refer to Table 1). 22 3. Check that ICP is securely grounded. 4. Check that high-voltage lead is securely connected between ICP and electrode body. 5. Restore power to ICP. Check that 24 v is supplied LOW CHARGE COOLING — Using appropriate cooling charging chart (see Fig. 34-37), add refrigerant until conditions of the appropriate chart are met. Note that 48TJ020028 charging charts are different from those normally used. All charts are based on charging units to correct superheat for various operating conditions. An accurate pressure gage and temperature sensing device are required for all units. Connect temperature sensing device to service port on suction line and insulate it so that outdoor ambient temperature does not affect reading. Indoor-air cfm must be within normal operating range of unit. TO USE COOLING CHARGING CHART, 48TJ016 UNITS — The TXV is set to maintain between 10 and 13° F superheat leaving the evaporator coil. It controls the flow of refrigerant to the evaporator coil. Take the outdoor ambient temperature, and read the suction pressure gage. Refer to Fig. 34 to determine correct discharge pressure. If discharge pressure is low, add refrigerant. If discharge pressure is high, carefully recover some of the charge. Recheck discharge pressure as charge is adjusted. TO USE COOLING CHARGING CHART, 48TJ020-028 UNITS — Take outdoor ambient temperature and read the suction pressure gage. Refer to appropriate chart to determine correct suction temperature. If suction temperature is high, add refrigerant. If suction temperature is low, carefully recover some of the charge. Recheck suction pressure as charge is adjusted. Example (Fig. 36) Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . 85 F Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 psig Suction Temperature (should be) . . . . . . . . . . . . . . . . . 60 F (Suction temperature may vary ± 5 F) to terminal TH of ICP. 6. Check unit label diagram for correct terminal usage if any wires are removed. Fig. 34 — Cooling Charging Chart — 48TJ016 Fig. 35 — Cooling Charging Chart — 48TJ020 Pilot Light — If pilots do not light as described in StartUp, Gas Heat section on page 15, be sure that pilot orifice is not obstructed, then check for spark ignitor malfunctions as follows: 1. Shut off control supply power to ignitor control pack (ICP). 2. Check that spark gap is 1⁄8 in. 6 1⁄32 inch. 23 Pilot Adjustment 1. Set system selector switch at OFF position to shut off unit. Turn off power to unit. 2. Remove screw cap cover on pilot gas valve to expose pilot adjustment screw (See Fig. 38). 3. Turn valve knobs to pilot position. 4. Turn on power to unit. Set system selector switch to HEAT position and set thermostat to a setting that will call for heat. Pilot ignites. 5. With a small screwdriver, turn pilot adjustment screw until flame fully engulfs sensor. Flame can be observed through view port (Fig. 39). 6. Replace cap on pilot gas valve. Turn off power to unit. Return valve(s) to original position. 7. Check for proper burner operation by cycling the burners. Wait 30 seconds between burner cycles. 8. Check that all unit panels are in place before leaving unit. Gas Valve Adjustment NATURAL GAS — The gas valve opens and closes in response to the thermostat or limit control. When power is supplied to valve terminals 3 and 4, the pilot valve opens to the preset position. When power is supplied to terminals 1 and 2, the main valve opens to its preset position. The regular factory setting is stamped on the valve body (3.5 in. wg). To adjust regulator: 1. Set thermostat at setting for no call for heat. 2. Turn main gas valve to OFF position. 3. Remove 1⁄8-in. pipe plug from manifold or gas valve pressure tap connection. Install a suitable pressure-measuring device. 4. Set main gas valve to ON position. 5. Set thermostat at setting to call for heat. 6. Remove screw cap covering regulator adjustment screw (See Fig. 38). 7. Turn adjustment screw clockwise to increase pressure or counterclockwise to decrease pressure. 8. Once desired pressure is established, set thermostat setting for no call for heat, turn off main gas valve, remove pressure-measuring device, and replace 1⁄8-in. pipe plug and screw cap. Fig. 36 — Cooling Charging Chart — 48TJ024 Main Burners — For most applications, main burners are factory set and should require no adjustment. However, if burner adjustment is necessary: 1. Perform pilot adjustment. 2. Turn gas valve to ON position. Allow unit to operate at least 15 minutes with burner access panel in place. 3. Remove access panel. 4. Loosen primary air shutter (Fig. 39) and adjust to a minimum opening of 5⁄8 inch. 5. Retighten primary air shutter and reinstall access panel. To check ignition of main burners and fan switch operation, move thermostat dial above and below room temperature several times, pausing at least one minute between cycles. Fig. 37 — Cooling Charging Chart — 48TJ028 24 Protective Devices COMPRESSOR PROTECTION Overcurrent — Each compressor has one manual reset, calibrated trip, magnetic circuit breaker. Do not bypass connections or increase the size of the circuit breaker to correct trouble. Determine the cause and correct it before resetting the breaker. Overtemperature — Each compressor has an internal protector to protect it against excessively high discharge gas temperatures. Crankcase Heater — Each compressor has a 125-watt crankcase heater to prevent absorption of liquid refrigerant by oil in the crankcase when the compressor is idle. Since power for the crankcase heaters is drawn from the unit incoming power, main unit power must be on for the heaters to be energized. Fig. 38 — Gas Valve VIEW PORT IMPORTANT: After a prolonged shutdown or service job, energize the crankcase heaters for 24 hours before starting the compressors. FLUE BOX COVER PRIMARY AIR SHUTTER Compressor Lockout — If any of the safeties (high-pressure, low-pressure, freeze protection thermostat, compressor internal thermostat) trip, or if there is loss of power to the compressors, the cooling lockout (CLO) will lock the compressors off. To reset, manually move the thermostat setting. EVAPORATOR FAN MOTOR PROTECTION — A manual reset, calibrated trip, magnetic circuit breaker protects against overcurrent. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the cause and correct it before resetting the breaker. CONDENSER-FAN MOTOR PROTECTION — Each condenser-fan motor is internally protected against overtemperature. HIGH- AND LOW-PRESSURE SWITCHES — If either switch trips, or if the compressor overtemperature switch activates, that refrigerant circuit will be automatically locked out by the CLO. To reset, manually move the thermostat setting. FREEZE PROTECTION THERMOSTAT (FPT) — An FPT is located on the evaporator coil. It detects frost build-up and turns off the compressor, allowing the coil to clear. Once the frost has melted, the compressor can be reenergized. MAIN BURNER SECTION Fig. 39 — Typical Heating Section MAIN BURNER REMOVAL 1. Shut off (field-supplied) manual main gas valve. 2. Shut off power to unit. 3. Remove unit control box access panel, burner section access panel, and center post (Fig. 4-6). 4. Disconnect pilot ignitor and pilot proving sensor leads at ICP, rollout switch leads at switch, and pilot tube gas connection(s) at the pilot orifice. 5. Disconnect gas connection(s) from between gas valve(s) and main burners. 6. Remove 2 screws securing burner assembly to base unit. NOTE: For 48TJE024 and 028 units only: Remove access plate from base rail. 7. Slide burner assembly out of unit. Relief Devices — All units have relief devices to protect against damage from excessive pressures (i.e., fire). These devices protect the high and low side. Control Circuit, 24-V — This control circuit is protected against overcurrent by a 3.2 amp circuit breaker. Breaker can be reset. If it trips, determine cause of trouble before resetting. Replacement Parts — A complete list of replacement parts may be obtained from any Carrier distributor upon request. Filter Drier — Replace whenever refrigerant system is exposed to atmosphere. 25 LEGEND Fig. 40 — Typical Wiring Schematic Fig. 41 — Typical Component Arrangement AHA BKR W/AT C CB CC CH CLO CLS COMP CR CT DM DU EQUIP FPT — — — — — — — — — — — — — — — FU GND HPS HR HV I ICP IDM IDR IFC — — — — — — — — — — IFCB — Adjustable Heat Anticipator Breaks with Amp Turns Contactor, Compressor Circuit Breaker Cooling Compensator Crankcase Heater Compressor Lockout Compressor Lockout Switch Compressor Motor Control Relay Current Transformer Damper Motor Dummy Terminal Equipment Freeze Protection Thermostat Fuse Ground High-Pressure Switch Heat Relay High Voltage Ignitor Ignitor Control Pack Induced-Draft Motor Induced-Draft Relay Indoor (Evaporator) Fan Contactor Indoor (Evaporator) Fan Circuit Breaker IFM IFR IP L LOR LPS LS MAT MGV NEC OAT OFC OFM PGV PL PRI PS QT R RS SN SW TB TC TDR — Indoor (Evaporator) Fan Motor — Indoor (Evaporator) Fan Relay — Internal Protector — Light — Lockout Relay — Low-Pressure Switch — Limit Switch — Mixed-Air Thermostat — Main Gas Valve — National Electrical Code — Outdoor-Air Thermostat — Outdoor (Condenser) Fan Contactor — Outdoor (Condenser) Fan Motor — Pilot Gas Valve — Plug Assembly — Primary — Pressure Switch — Quadruple Terminal — Relay — Rollout Switch — Sensor — Switch — Terminal Block — Thermostat Cooling — Time Delay Relay NOTES: 1. Compressor and fan motors thermally protected; 3-phase motors protected against primary single-phasing conditions. 2. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent. 3. Jumpers are omitted when unit is equipped with economizer. 4. Set thermostat heat anticipator(s): VOLTAGE 208/230, 575 460 W1 0.98 0.80 TH — Thermostat Heating TRAN — Transformer Terminal (Marked) Terminal (Unmarked) Terminal Block Splice Splice (Marked) Splice (Field Supplied) Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential Only, Not To Represent Wiring 5. CB must-trip amps are equal to or less than 140% full load amps. 6. Number(s) indicates the line location of used contacts. A bracket over (2) numbers signifies a single-pole, double-throw contact. An underlined number signifies a normally-closed contact. A plain (no line) number signifies a normally-open contact. 7. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices. Before replacing CLO, check these devices. W2 0.44 0.44 Fig. 40 — Typical Wiring Schematic (48TJ020-028 Shown) 26 Fig. 40 — Typical Wiring Schematic (48TJ020-028 Shown) (cont) 27 Fig. 41 — Typical Component Arrangement (48TJ020-028 Shown) 28 PACKAGED SERVICE TRAINING Our packaged service training programs provide an excellent way to increase your knowledge of the equipment discussed in this manual. Product programs cover: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available. All programs include a video cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training sessions. For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are included. Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 111 Catalog No. 564-873 Printed in U.S.A. Form 48TJ-11SI Pg 30 4-96 Replaces: 48TJ-7SI Tab 1a 6a DATE: TECHNICIAN: PRE-START-UP: M VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT M LOOSEN ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTRUCTIONS M VERIFY INSTALLATION OF ECONOMIZER HOOD M VERIFY INSTALLATION OF EXHAUST HOOD M VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS M VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT M CHECK GAS PIPING FOR LEAKS M CHECK THAT INDOOR-AIR FILTER IS CLEAN AND IN PLACE M VERIFY THAT UNIT IS LEVEL M CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SETSCREW IS TIGHT M VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED START-UP ELECTRICAL SUPPLY VOLTAGE L1-L2 L2-L3 L3-L1 COMPRESSOR AMPS — COMPRESSOR NO. 1 L1 L2 L3 — COMPRESSOR NO. 2 (020-028 ONLY) L1 L2 L3 SUPPLY FAN AMPS EXHAUST FAN AMPS TEMPERATURES OUTDOOR-AIR TEMPERATURE F DB (Dry Bulb) RETURN-AIR TEMPERATURE F DB COOLING SUPPLY AIR F GAS HEAT SUPPLY AIR F F WB (Wet Bulb) PRESSURES IN. WG GAS INLET PRESSURE IN. WG STAGE NO. 2 IN. WG GAS MANIFOLD PRESSURE STAGE NO. 1 REFRIGERANT SUCTION CIRCUIT NO. 1 PSIG CIRCUIT NO. 2 (020-028 ONLY) PSIG REFRIGERANT DISCHARGE CIRCUIT NO. 1 PSIG CIRCUIT NO. 2 (020-028 ONLY) PSIG M VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGES 23 AND 24 GENERAL M ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 111 Catalog No. 564-873 Printed in U.S.A. Form 48TJ-11SI Pg CL-1 4-96 Replaces: 48TJ-7SI Tab 1a 6a CUT ALONG DOTTED LINE SERIAL NO.: CUT ALONG DOTTED LINE MODEL NO.: - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - START-UP CHECKLIST
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement