48TJ016-028 single Package Rooftop Units Electric Cooling/Gas Heating Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERATIONS ................. 1 INSTALLATION ............................ 1-14 Step 1 — Provide Unit Support .............. 1 ® ROOF CURB e ALTERNATE UNIT SUPPORT Step 2 — Rig and Place Unit ................ 3 ® POSITIONING ® ROOF MOUNT Step 3 — Field Fabricate Ductwork .......... 9 Step 4 — Make Unit Duct Connections ...... 9 Step 5 — Install Flue Hood .................. 9 Step 6 — Trap Condensate Drain ........... 10 Step 7 — Install Gas Piping ................ 10 Step 8 — Make Electrical Connections ...... 11 e FIELD POWER SUPPLY e FIELD CONTROL WIRING Step 9 — Make Outdoor-Air Inlet Adjustments ............................. 13 ® MANUAL OUTDOOR-AIR DAMPER e OPTIONAL ECONOMIZER Step 10 — Install Outdoor-Air Hood ........ 14 START-UP .......... ii, 14-19 SERVICE ............. i, 19-26 START-UP CHECKLIST ..................... CL-1 SAFETY CONSIDERATIONS Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical com- ponents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment. Untrained personnel can perform the basic maintenance, functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels at- tached to the unit, and other safety precautions that may apply. Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations. A WARNING Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury. A WARNING 1. Improper installation, adjustment, alteration, serv- ice, or maintenance can cause property damage, per- sonal injury, or loss of life. Refer to the User's Information Manual provided with this unit for more details. 2. Do not store or use gasoline or other flammable va- pors and liquids in the vicinity of this or any other appliance. What to do if you smell gas: 1. DO NOT try to light any appliance. 2. DO NOT touch any electrical switch, or use any phone in your building. 3. IMMEDIATELY call your gas supplier from a neigh- bor’s phone. Follow the gas supplier’s instructions. 4. If you cannot reach your gas supplier, call the fire department. A WARNING Disconnect gas piping from unit when pressure testing at pressure greater than 0.5 psig. Pressures greater than 0.5 psig will cause gas valve damage resulting in haz- ardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pres- sures of 0.5 psig or less, a unit connected to such pip- ing must be isolated by closing the manual gas valve(s). INSTALLATION Step 1 — Provide Unit Support A CAUTION и When handling 48TJE024 and 028 units with a forklifi truck, use a minimum of 48-in. long forks and lift ONLY through factory-provided holes in base rail. Otherwise, damage to the unit may result. ROOF CURB — Assemble or install accessory roof curb in accordance With instructions shipped with this accessory. See Fig. 1 and 2. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb before unit is set in place. Curb should be level. This is necessary to permit unit drain to function prop- erly. Unit leveling tolerance is + V6 in. per linear ft in any direction. Refer to Accessory Roof Curb Installation Instructions for additional information as required. When accessory roof curb is used, unit may be installed on class A, B, or C roof covering material. Instructions continued on page 3. Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 564-836 Book |1 PC 111 Tab Ia Printed in USA Form 48TJ-7SI Pg 1 4-94 Replaces: 48TJ-2SI M| TERED CORNERS (TOP ONLY) INSULATED PANEL FOR SIDE PLAN VIEW OF ROOF CURB SUPPLY AND RETURN - —— OUTLINE (48DP900061, 48DP900071, al La OFUNIT 50DP900211, AND om 50PQ300151 ONLY) TT TT | + | ° un FROM TABLE | COMPR SUPPLY RETURN | | M, 5/47 X 4° OPEN ING OPENING | | | “ag Xe 2 CURB CURB | ° UTA | И 753) (48DF90008 1. 48DP900071, | 50DP900211, AND | 50PQ900151 ONLY) | =—— LE (1 133 316 > 1-1 15/18 N KEEP THIS AREA "E [y (349) NEE ans Ea, VER 1 -3/167 == o—1"-10 3/47 310) (578) { CONDE RSE ALL UNITS EXCEPT ( COMPRESSOR (reas = 54 IN CASKET . } UNIT OPENINGS WITH CURE) [ y 8 NAIL \ *-4 5/16" ? CONDENSATE CONDENSER Tard — 17-4 9/16” DRAIN AND SUPPLY RETURN (421) COMPRESSOR 28 DEG qu OPTIONAL — — — — > COUNTER FLASHING + END À 43 IN a RETURN , (FIELD SUPPL IED . . — ; Е ИЕ, ROOF ING FELT ? 1 м — 7 fe Lon DUCT- | (FIELD SUPPLIED) == CANT STRIP a AIR вето ия SIDE SUPPLY | ЗРРСТЕО ED OF ING. MATER AL ай A 7 (FIELD SUPPLIED) SECTION A-A 7 NOTE: To prevent the hazard of stagnant water build-up in the drain pan of the indoor-air sec- GIO INSULATION tion, unit can only be pitched as shown. LEGEND COMPR SECT. — Compressor Section O NOTES: 1. Roof curb accessory is shipped unassembied. 2. Insulated panels, %-in. thick neoprene-coated, 2 Ib density. 3. Dimensions in ( ) are in millimeters. 4 2 Direction of airflow. ) 5 Roof curb: 18 gage steel. a 6. Attach all ductwork to roof curb. 7. Field installation of sidewall is mandatory © ACCESSORY CURB PACKAGE HEIGHT DESCRIPTION “A” В’ “up” “Dj” “e” a NO. Td 1-2" Standard Curb — 5-76" 1-71%6" SOPQ900221 (355) 14" High (1703) (503) — — — a Standard Curb for 4 2-0" Ч 8-76" 1-76" 1 50PQ900141 Units Requiring — — — » (610) High Installation (1703) (503) 2'-0" Horizontal Supply and 5-716" 17-7196" 5-6” 0'-2%%” 1'-6" SoPQ900151 (610) Return Curb (1703) (503) (1676) (64) (457) 50DP90021 1 1 1 1 Pre-Assembiled, High-Static, 5'-71 в” 1 -7 % в” 6'-2" 0-64" 1 25" (584) Horizontal Adapter Curb (1703) (503) (1880) (159) (371) A 1°-2" Standard Curb — 7'-2196" 3'-3%" A8DP900041 (355) 14” High (2205) (1006) — - = Standard Curb 2-0” es 721%" 3°-3%" 48DP900051* for Units Requiring — — — (610) High Installation (2205) (1006) 2'-0" Horizontal Supply 7'-213hg" 3'-356” 5-6" 0'-21/" 1'-6" 48DP900061* (610) and Return Curb (2205) (1006) (1676) (64) (457) 48DP900071* 1-11” Pre-Assembled, High-Static, 7-21%16" 3-356" 6-2" 0-61" 1-27” (584) Horizontal Adapter Curb (2205) (1006) (1880) (159) (371) *For high-heat applications. Fig. 1 — Roof Curb Details O EVAPORATOR-FAN MOTOR 48TJ016 25% VENT AIR/ ECONOMIZER HOOD AIR IN BLOCK-OFF PAN 4 1/2" AIR OUT HORIZONTAL SUPPLY CURB (50PQ900151, 48DP900061, 50DP900211, OR 48DP900071) EVAPORATOR-FAN MOTOR 48TJ020-028 -7 — | | 1-9 1/2" ! / и Pi DUCT NOTE: For preassembled horizontal adapter curb part no. 50DP900211 and 48DP900071, the accessory kit includes a factory-designed, high-static, regain transition duct. For horizontal adapter curb part no. 50PQ800151 and 48DP900061, a field-supplied transition duct is required. Fig. 2 — Horizontal Adapter Curbs IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket with the roof curb as shown in Fig. 1. Improperly applied gasket can also result in air leaks and poor unit performance. ALTERNATE UNIT SUPPORT — When the curb cannot be used, install unit on a noncombustible surface. Support unit with sleepers, using unit curb support area. If sleepers cannot be used, support long sides of unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side. Step 2 — Rig and Place Unit — Inspect unit for transportation damage. File any claim with transportation agency. Do not drop unit; keep upright. Use spreader bars over unit to prevent sling or cable damage. Rollers may be used to move unit across a roof. Level by using unit frame as a reference; leveling tolerance is + Vie in. per linear ft in any direction. See Fig. 3 for additional information. Unit operating weight is shown in Table 1. Four lifting holes are provided in ends of unit base rails as shown in Fig. 3. Refer to rigging instructions on unit. POSITIONING — Maintain clearance, per Fig. 4 and 5, around and above unit to provide minimum distance from combustible materials, proper airflow, and service access. Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of con- taminated air. For proper unit operation, adequate combus- tion and ventilation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute). Although unit is weatherproof, guard against water from higher level runoff and overhangs. Locate mechanical draft system flue assembly at least 4 ft from any opening through which combustion products could enter the building, and at least 4 ft from any adjacent building. When unit is located adjacent to public walk- ways, flue assembly must be at least 7 ft above grade. ROOF MOUNT — Check building codes for weight dis- tribution requirements. Unit weight is shown in Table 1. Instructions continued on page 9. 1 0'-0" (3048) SPREADER BARS и DETAIL A" 4 RIGGING HOOK UNIT BASE RAIL SEE "DETAIL A" NOTES: MAXIMUM SHIPPING DIMENSIONS 1. Dimensions in ( ) are in millimeters BT WEIGHT A B 2. Refer to Table 1 for unit operating weights. ~ 1 ji 3. Remove boards at ends of unit and runners prior to rigging. Lb Kg Ftin. | mm | Ft-in. | mm 4. Rig by inserting hooks into unit base rails as shown. Use corner D016 1834 832 6-11% | 2121 | 3-2 965 post from packaging to protect coil from damage. Use bumper D020 2131 967 6-111 | 2121 | 3-3 991 boards for spreader bars on all units except 48TJE024 and 028. 0024 2131 967 6-11 | 2121 | 3-3 991 5. Weights sio not include optional economizer. See Table 1 for econo- D028 2514 1140 6-11 | 2121 | 3-3 991 6. Weights given are for aluminum evaporator coil plate fins and 411 . copper condenser coil plate fins Weights of other metal combi- E016 1854 841 6-112 | 2121 | 3-2 965 nations are listed in Table 1. E024 2441 1094 B- 774 | 2623 | 4-2 | 1270 E028 2793 1267 8- 774 | 2623 | 4-2 | 1270 A CAUTION All panels must be in place when rigging Fig. 3 — Rigging Details at CORNER D 1 3/8” DIA. DRAIN HOLE IE … ‚ 2121) CORNER € -3 778% я 6°-11 1/2 (99) 1-7 13/16” *-4 5/16 00e-1”-4 9/16 /10-0/-3 15/16" _/-0°-1 5/16” 0-5 15/16” ‘ “= (504) (415) (421) (108 (151) p°-8 1/8 an ; (206) | — re = (SN) UN: Ï (109) г | | O — DT fra, | | | | | | ! | 3-2 | 28 15/16*-— 6 | (986) 2-1 5/8” OUTDOOR! [SUPPLY (651) | AIR SECTION | i LL (T3 RETURN S°-11 7/8” a | AIR (1825) do he=1 “-6 5/16 5’-7 3/16” 5 pa (1707) VIEW 7-Z 2-2 1/18" (662) > \ | POWER EXHAUST \ (ACCESSORY ONLY) | | | | | | | bo (1753) | т 7-2 1/8" POWER EXHAUST | ( 2187) CACCESSORY ONLY) | | | | | — | i | | | { | | | ! | | | i | i | I | a — | 1 i | i | | | | | | | | 1 | | | | ! | | | | | | ! | | | | ! | | | + 0-10 hans MN > PETT 2-8 ori de" 274) 0 Y 7 Z 0-7 3/4" a 1 pd | 6097) (965) +, ‘ le DIA HOLE OR ; 0°-5 OUT OL 2 DIA K.O. 0-52 e 7 10 (22) (51) (127) — 07-11 15/167 (303 CORNER A 3° 2 1 3/8" DIA CONCENTRIC K.O. 78) 95) 06 y CONTROL BOX ILTERS 25% ALR OR || TOP Veces FAR s10€/ = -10 ape y Eonia KooD > = y e ESP Eo LEFT SIDE + SECTION A-A 3°-9° 0°-3 7/16" (1143) — 1 en o = —Ñ Tamer + 0 | = | 210% | o" 1°-6 3/8 (559) ТУР \ (467) | 01 1/7" } ОЙ TN ge CORNER WEIGHT* ! or J | 020 ou” pd т es UNIT A B С D D y INDOOR Cott ALTERNATE RETURN 4874 ib | Ka | Lb T Ka | Lb T Ka | Lb TK HEAT EXCHANGER ACCESS PANEL, prRONT . 9 9 9 9 3/4” FPT DRAIN CONNECTION AÑO CENTER POST EOS PANEL (27) FAR SIDE ONLY Do16 | 348 | 158 | 360 | 163 | 373 | 169 | 523 | 237 D020 | 362 | 164 | 483 | 219 | 495 | 225 | 511 | 232 E016 | 355 | 161 | 363 | 164 | 377 | 171 | 530 | 240 07 420m *Weights are for unit only and do not include options or (102) — Lo 3” 8 7/9 DIA CONCENTRIC K.O. crating. 0-3 1/48 fe | SD (76) & (22) (FIELD POWER) (79) NOTES: 1 Dimensions in ( ) are in millimeters == , 2, 4, Center of gravity 3, Direction of airflow | 4. Ductwork to be attached to accessory roof curb only 5. Minimum clearance: a Rear: 7'0" (2134) for coil removal This dimension can be re- 0-3" / duced to 4'0” (1219) if conditions permit coil removal from the (76) top. $ Ф b. Left side: 4'0” (1219) for proper condenser coil airflow , 1 . ; N c. Front: 4'0” (1219) for control box access A to A < | d Right side: 4'0” (1219) for proper operation of damper and т UE power exhaust if so equipped 3 5/8” 2 1 3/8 OIA CONCENTRIC K.O. TE ge e Top: 6/0” (1829) to assure proper condenser fan operation 0-2 7/8" (92) 8 (35) (FIELD POWER) 076 f. Local codes or jurisdiction may prevail (73) ._3 2/07 |L- 748 DIA K.0. (CONTROL) 1 1/4 DIA Hoe © With the exception of clearance for the condenser coil and the es) Na 1/2” DIA K.O. (GAS ENTRY) 3/4” NPT (32) damper/power exhaust as stated in Note No. 5, a removable fence Vas + (38) or barricade requires no clearance. , so 5-6” 7. Dimensions are from outside of corner post. Allow 0'-%1s” (8) on 0-2 VA = (1676) each side for top cover drip edge Fig. 4 — Base Unit Dimensions, 48TJ016,020 CORNER WEIGHT" DIMENSIONS 1 A B С D A B С р Е Lb Kg Lb Kg Lb Kg Lb Kg | Ft-in. mm Ft-in. mm Ft-in. | mm Ft-in. mm Ft-in. mm D024 | 495 | 225 | 483 | 219 | 362 | 164 | 511 | 232 3-3 991 3-7 1092 0-3 76 | 611% | 2121 | 1-71%e 504 E024 | 431 | 196 | 421 | 191 | 494 | 224 | 685 | 311 4-2 1270 3-4 1016 | 0-4% | 114 | 8- 7% | 2623 3-3% 1006 ® D028 | 523 | 237 | 541 245 | 574 | 260 | 596 | 270 3-3 991 3-7 1092 0-3 76 | 6-11% | 2121 1-71%es 504 E028 | 465 | 211 486 | 220 | 725 | 329 | 737 | 334 4-2 1270 3-5 1041 0-42 114 | 8- 7% | 2623 3-3% 1006 “Weights are for unit only and do not include options or crating CORNER D 1 3/97 DIA DRAIN HOLE TYP (4) PLCS CORNER A 0-3 7/6” D (2121) es (99) re E ——opel -4 5/16%qe1 -4 9/16% 072 15/16" __/ 9". 5/16" 0-5 15/16” 0 -8 1/8 REAR (415) > (421) [ace | (33) (151) (206) | E 0-4 5/16” + OS { (109) - zz —3 — , | | ; — -6 15/16 re (786) } RETURN} | ame | 5-7 3/16" (466) (1707) > POWER EXHAUST (ACCESSORY ONLY) —— 4 $011 1/8” . (283) 0*-10 13/16” > 7 aa 270 E 0 iQ Ts | / roar] ~~ i Ï DD T A OUTDOOR *_e” 7/8" DIA HOLE COIL 2” DIAKO cod Tle O An (22) (51) Fe —l 0-11 15/16” (303) CORNER B CORNER C 3° 8 1 3/8” DIA CONCENTRIC K © (76) (35) Me ELIMINATOR Î FILTERS ACCESS - ACCESO 0-2 1/4" TOP (567) 25% 62} AR SIDE TA _ : ÉCONOMIZER Soon 0-3" 7 , a , > N 1-10 ak A 1 (76) O 5/16” FIELD- ——— 0 -a" (339) (102) LAPT SIDE { SUPPLIED | 3-8 1/4 0 -3 72/16" SECTION A-A (1124) Zen => —4 “ans Y RIGHT | es SIDE - 1'-6 3/8" 69 IN (467) | E ——— | Lo + 1 ÿ I | JLo 0 Л + 1 01 178" sh) INDOOR COIL (38) ALTERNATE RETURN NOTES: en FAR DE ORLY N 1 Dimensions in ( )are in millimeters 2 < Center of gravity vo „Г { — *-2° 3° & 7/8 DIA CONCENTRIC K i i i 0-3 18% tal | re (76) 8 (22) (FIELD POWER) | 3 Direction of airflow Ш 4 Ductwork to be attached to accessory roof curb only 5 Minimum clearance: r a Rear: 7'0” (2134) for coil removal This dimension can be reduced to 4'0” (1219) if conditions permit coil removal from e top b 4'0" (1219) to combustible surfaces, all four sides (in- cludes between units). / с Left side: 4'0" (1219) for proper condenser coil airflow о -3° / d Front: 4'0” (1219) for contro! box access | ve 4 e Right side: 4°0” (1219) for proper operation of damper and 5 ie ower exhaust (if so equipped) 0:4 14° — | — f Top: 6'0" (1829) to assure proper condenser fan (108) I operation ! g. Bottom: 14 (356) to combustible surfaces (when not using | R= 3.508 a 3/8 „DIA CONCENTRIC K O curb) 0°-2 7/8" (FIELD POWER) h Control box side: 3'0" (914) to ungrounded surfaces Tora 7/8" N 192, 4 K 9 (CONTROL 1 1/4" DIA HOLE (non-combustible). DIMENSIONS 98) 1 eid DIA KO (GAS ENTRY) 3/4” NPT (32) i Control box side: 3'6” (1067) to block or concrete walls, or EDGE OF ' 316 (38) , other grounded surfaces UNIT CABNET 0-2 5 = 5 -6 j. Local codes or jurisdiction may prevail (1676) 6. With the exception of clearance for the condenser coil and the damper/power exhaust as stated in Note No. 5, a removable fence or barricade requires no clearance 7 Dimensions are from outside of corner post Allow 0'-516” (8) on each side for top cover drip edge Fig. 5 — Base Unit Dimensions, 48TJ024-028 Table 1 — Physical Data 016D/E UNIT SIZE 208/230,460 v | 575 v 020D 024D/E 028D/E PA NOMINAL CAPACITY (tons) 15 18 20 25 e OPERATING WEIGHT (ib) nit Al/Al* 1604/1624 1850 1850/2031 2234/2413 Al/Cu* 1684/1704 1980 1980/2161 2364/2543 Cu/Cu* 1754/1774 2090 2090/2271 2474/2653 Economizer 110 110 110 110 Roof Curbt 200 200 200/213 200/213 COMPRESSOR Semi-Hermetic Hermetic Semi-Hermetic Quantity 1 2 2 2 Oil (02) 130 65 ea 65 ea 152 ea REFRIGERANT TYPE R-22 Operating Charge (ib-02) Circuit 1** 19-4 15-4 15-8 16-12 Circuit 2 — 12-6 15-8 15-12 CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced or Copper Fins Rows...Fins/in. 2.17 3..15 4.15 4.15 Total Face Area (sq ft) 22 2 22.2 22.2 22.2 CONDENSER FAN Propeller Type Nominal Cfm 10,500 10,500 14,200 14,200 Quantity...Diameter (in.) 3...22 3...22 2.. 30 2...30 Motor Hp...Rpm Y...1050 7. .1050 1.. 1075 1..1075 Watts Input (Total) 1100 1100 3400 3400 EVAPORATOR COIL Copper Tubes, Aluminum or Copper Plate Fins Rows...Fins/in. 2...17 3...17 4 15 4..15 Total Face Area (sq ft) 17.9 17.9 17.9 17.9 EVAPORATOR FAN Centrifugal Type Quantity...Size (in.) 2.10x10 2..10x 10 | 2...12 х 12 2...12 х 12 2 12x12 Type Drive Belt Belt Belt Belt Belt Nominal Cfm 6000 6000 7200 8000 10,000 Motor Hp 37 3.0 5 7% 10 Maximum Continuous Bhp 4.25 3.45 5.90 8.7 4601 SV] 10€ F8 [460 4] SV] Motor Frame Size 56H 56H 184T 213T 215T Nominal Rpm High/Low — — — — — Fan Rpm Range 1194-1526 1201-1462 | 1047-1251 1238-1494 1323-1579 Motor Bearing Type Ball Ball Ball Ball Ball Maximum Allowable Rpm 1550 1550 1550 1550 1550 Motor Pulley Pitch Diameter Min/Max (in.) 3.4/4.4 4.3/5.3 4.9/5.9 5.4/6.4 58/7.0 Nominal Motor Shaft Diameter (in.) И 7% 1% 1% 1% Fan Pulley Pitch Diameter (in.) 5.0 6.4 8.4 79 7.9 Nominal Fan Shaft Diameter (in.) 1%s 13/16 17/16 176 176 Belt, Quantity... Type...Length (in.) 1...AX...42 1...BX...45 | 1...BX...50 1.. BX...50 1...BX...51 Pulley Center Line Distance (in.) 13.5-15.5 13.5-15.5 13.3-14.8 14.6-15 4 14.6-15.4 Speed Change per Full Turn of Movable Pulley Flange (rpm) 66 52 34 43 43 Movable Pulley Maximum Full Turns From Closed Position 5 5 6 6 6 Factory Setting 35 3.5 3 3 3 Factory Speed Setting (rpm) 1293 1279 1149 1366 1451 Fan Shaft Diameter at Pulley (in.) 13/6 1%6 1716 17/16 176 Table 1 — Physical Data (cont) UNIT SIZE 016D/E 020D 024D/E 028D/E FURNACE SECTION Rollout Switch Cutout Temp (F)tt 190 Burner Orifice Diameter (in. ...drill size) Natural Gas 113..33 Pilot Orifice Diameter (Quantity) in. ...drill size Natural Gas (1) 055...54/ (1) .055 54, (1) 041 59 Thermostat Heat Anticipator Setting (amps) 208/230,575 v Stage 1 98 Stage 2 44 460 v Stage 1 1.20 Stage 2 44 Gas Input (Btuh) Stage 1 115,500/115,500 Stage 2 231,000/270,000 Efficiency (Steady State) (%) 80 Temperature Rise Range 25-55/25-55 Manifold Pressure (in. wg) Natural Gas 3.5 Gas Valve Quantity 2 Field Gas Connection Size (in.) Ya 190 190 190 113 33 113 ..33 ‚113 33 (1) .055 ..54 (1) 055.. 54, (1) .055 54, (1) 041 ..59 (1) .041. 59/ (1) 041 .59/ (2) 070 .50 (2) .070. 50 98 98 98 44 44 44 120 120 120 44 44 44 115,500 115,500/242,500 115,500/242,500 270,000 270,000/485,000 270,000/485,000 80 80 80 15-45 15-45/35-65 15-45/35-65 35 35 3.5 2 2 2 Y Ya Ya HIGH-PRESSURE SWITCH (psig) Standard Compressor Internal Relief (Differential) Cutout Reset (Auto.) LOW-PRESSURE SWITCH (psig) Cutout Reset (Auto.) FREEZE PROTECTION THERMOSTAT (F) Opens Closes OUTDOOR-AIR INLET SCREENS Quantity...Size (in.) 426 320 7 22 30 +5 45 + 5 Cleanable 2 20x25x1 1..20 x 20 x 1 RETURN-AIR FILTERS Quantity...Size (in.) Throwaway | 4.20 x 20 x 2 4 16x20x2 LEGEND Al — Aluminum Bhp — Brake Horsepower Cu — Copper *Evaporator coil fin material/condenser coil fin material. {Weight of 14-in. roof curb **On 48TJ020-028 units, Circuit 1 consists of lower portion of con- denser coil and lower portion of evaporator coil, and Circuit 2 is the upper portion of both coils. wu’ {tRollout switch is manual reset The 48TJ028 unit requires 2-in. industrial-grade filters capable of handling face velocities of up to 625 ft/Min (such as American Air Filter no 5700 or equivalent) NOTE: The 48TJ016-028 units have a low-pressure switch (stand- ard) located on the suction side Step 3 — Field Fabricate Ductwork — Secure all ducts to building structure. Use flexible duct connectors be- tween unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes. Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier. Step 4 — Make Unit Duct Connections — Unit is shipped for through-the-bottom duct connections. Duct ху НЕАТ „—ЕХСНАМСЕВ DL Na SEE SEE NOTE “E \_ 5 ODE NOTE: Do not drill in this area; damage to basepan may result in water leak Fig. 6 — Air Distribution — Through-the-Bottom HEAT *~ EXCHANGER CIN SEE | SEE NOTE —\ `` ALS { ] МИ AIR OUT AIR IN AIR OUT NOTE: Do not drill in this area; damage to basepan may result in water leak Fig. 7 — Concentric Duct Air Distribution work openings are shown in Fig. 1, 4, and 5. Duct connec- tions are shown in Fig. 6. Field-fabricated concentricduct- work may be connected as shown in Fig. 7 and 8. Attach all ductwork to roof curb and roof curb basepans. Step 5 — Install Flue Hood — Flue hood is shipped secured under main control box. To install, secure flue hood to access panel. See Fig. 9 and 10. NOTE: When properly installed, flue hood will line up with combustion fan housing. See Fig. 11 and 12. —— 6-23 Max nO 74 57 e _ Eee Pre see RE pese ee e y EE — BAFFLE NOTE: Dimensions A, A’, B, and B' are obtained from field- supplied ceiling diffuser. EEES: areas indicate block-off pans Fig. 8 — Concentric Duct Details COMBUSTION FAN HOUSING (INSIDE) SE SE ca ee en ee ms = чи sc Were e SS О у mi me uh pe as . " cen о ii De . e BE о qe x | . " a 5 e О о o ENT DT Fig. 9 — Flue Hood Location, 48TJD Low- Heat and 48TJE016 High-Heat Units FLUE HOODS “ sue Eu ола ея naa eee ad PERA ae ah a a + латы xan A A NE . a a a ee ae n en CAN ETES $ as анны A = a , Sins AS ко x A a кл aa ; кА = xr Aap a wn uk = 4 pe Li E = NF К pS Lo EE Fig. 10 — Flue Hood Locations, 48TJE024 and 028 High-Heat Units TE ee nas de EE RE ss NN NI EAU VO ORLEANS PON OU A OT o o PRESSURE — 5255 or SWITCH Meza OZ. + СОНЯ a oles Li ‘oy a A, nn “ete A EE "oy CL Naa ay) FL) CEL) TA nro A RS EAE DE AI ee AN COMBUSTION 224 Br FAN HOUSING 25 ón Галича на. rea ace CC С Гира НЕАТ EXCHANGER SECTION г - die я Lo fa AN a арий rel ани IC ла Re - pn Cos Fig. 11 — Combustion Fan Housing Location, 48TJD Low-Heat Units and A48TJE016 High-Heat Units et 10 mm mh NR ME AA nn ото еее в Во eee Cla] NAO “= лы = + EE EE NC E ; LR he Bye WF a A A a CALA AA a - au vs Ca an at к ot E =. . = ENSUE O mas COMBUSTION FAN HEAT EXCHANGER HOUSINGS SECTIONS Fig. 12 — Combustion Fan Housing Location, 48TJE024 and 028 High-Heat Units Step 6 — Trap Condensate Drain — See Fig. 13 for drain location. One %4-in. half coupling is provided inside unit evaporator section for condensate drain connec- tion. An 8% in. x %4-in. diameter and 2-in. x %4-in. diam- eter pipe nipple, coupled to standard %4-in. diameter elbows, provides a straight path down through hole in unit base rail (see Fig. 14). À trap at least 4-in. deep must be used. Step 7 — Install Gas Piping — Unit is equipped for use with natural gas. Installation must conform with local building codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1. Install manual gas shutoff valve with a /4-in. NPT pres- sure tap for test gage connection at unit. Field gas piping must include sediment trap and union. See Fig. 15. A WARNING Do not pressure test gas supply while connected to unit. Always disconnect union before servicing. Natural gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13.5 in. wg. Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection. 3/4-IN. FPT 1-3/8 IN. DRAIN CONNECTION DRAIN HOLE 8 IN Fig. 13 — Condensate Drain Details (48TJ016 Shown) 3/4" FPT DRAIN CONNECTION (HALF COUPLING) BASE RAIL — 8 1/2-IN (FIELD- —™] SUPPLIED) NIPPLE 2-IN. (FIELD-SUPPLIED) NIPPLE Fig. 14 — Condensate Drain Piping Details MANUAL SHUTOFF GAS X N | SUPPLY 7 \ PRESSURE TAP (1/8" NPT PLUG) TO — UNIT 3 UNION SEDIMENT TRAP Fig. 15 — Field Gas Piping Step 8 — Make Electrical Connections FIELD POWER SUPPLY — Unit is factory wired for volt- age shown on unit nameplate. When installing units, provide a disconnect per NEC (National Electrical Code) of adequate size (Table 2). All field wiring must comply with NEC and local requirements. Route power and ground lines through control box end panel or unit basepan (see Fig. 4 and 5) to connections as shown on unit wiring diagram and Fig. 16. A WARNING The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (National Fire Protection Association). Field wiring must conform to temperature limitations for type “T” wire, All field wiring must comply with NEC and local requirements. 3 | ! - | | TBI | | FIELD m 2] POWER | 50 ——— La e] = SUPPLY | Sa | | Ba l La | | | | | [Um == e= que UT Cana ques eu ———{ [7] | | EQUIP GND Lo TB1 MAXIMUM WIRE SIZES UNIT VOLTAGE 48TJ 208/230 460 575 016 2/0 2/0 2/0 020,024 2/0 2/0 2/0 028 2/0 2/0 2/0 LEGEND EQUIP — Equipment GND — Ground NEC — National Electrical Code TB — Terminal Board Fig. 16 — Field Power Wiring Connections Transformer no. 1 is wired for 230-v unit. If 208/230-v unit is to be run with 208-v power supply, the transformer must be rewired as follows: 1. Remove cap from red (208 v) wire. 2. Remove cap from orange (230 v) spliced wire. 3. Replace orange wire with red wire. 4. Recap both wires. IMPORTANT: BE CERTAIN UNUSED WIRES ARE CAPPED. Failure to do so may damage the transformers. Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, volt- ages between phases must be balanced within 2%. Table 2 — Electrical Data VOLTAGE COMPRESSOR COMBUSTION UNIT NOMINAL EM RANGE NO. 1 NO 2 OFM IFM FAN MOTOR* POWER SUPPLY 48TJ (60 Hz) Min | Max | RLA | LRA | RLA | LRA | Qty | Hp (ea) Hp | FLA FLA MCA | MOCPI 208/230 (3 phase) Std 187 | 254 | 610 | 266 — — 3 % | 170 | 37 | 12.0120 0 57 93/93 150/150 016 460 (15 Tons) | (3 phase) Std 414 | 508 | 28.0 | 120 — — 3 % | 0.80 | 3.7 54 0.30 43 70 575 (3 phase) Std 518 | 632 | 230 96 — — 3 Y | 0.75 | 3 38 0.57 35 50 @ phase) Std | 187 | 254 | 28.3 | 205 | 250 | 185 | 3 | % | 1701 5 | 1671152 057 82/81 | 110/100 020 460 (18 Tons) | (3 phase) Std 414 | 508 | 14.4 | 104 | 12.4 89 3 2 | 080 | 5 7.6 030 40 50 575 (3 phase) Std 518 | 632 | 11.4 78 | 104 78 3 Ya | 075 | 5 61 057 33 40 208/230 | Std | 187 | 254 | 345 | 239 | 283 | 205 | 2 | 1 | 550 | 7% | 242/220 057 107/104 | 125/125 (3 phase) 024 460 (20 Tons) | (3 phase) Std 414 | 508 | 17.0 | 119 | 144 | 104 2 1 280 | 71% 110 030 52 60 575 (3 phase) Std 518 | 632 | 15.2 | 111 | 114 78 2 1 3.40 | 7% 90 057 46 60 @ phase) Std | 187 | 254 | 43.6 | 228 | 436 | 228 | 2 | 1 | 550 | 10 | 308/280 057 140/137 | 175/175 028 460 (25 Tons) | (3 phase) Std 414 | 508 | 221 | 114 | 221 | 114 2 1 280 | 10 14.0 0.30 69 90 575 (3 phase) Std 518 632 | 179 91 | 179 91 2 1 3.40 | 10 11.0 0.57 57 70 LEGEND 2 Unbalanced 3-Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater FLA — Full Load Amps i im- HACR — Heating, Air Conditioning and Refrigeration (han 2% Use the following formula to determine the percent voltage im IFM — Indoor (Evaporator) Fan Motor LRA — Locked Rotor Am $ % Voltage Imbalance — Minimum Circuit Amps ati MOCP _ Maximum Overcurrent Protection _ 400 x max voltage deviation from average voltage — National Electrical Code OFM %+T— Outdoor (Condenser) Fan Motor average voltage RLA — Rated Load Amps Example: Supply voltage is 460-3-60 *The 48TJ024 and 028 high-heat units have 2 combustion-fan motors AB = 452 v TFuse or HACR circuit breaker A BC BC = 464 v AC = 455v Warnock Hersey Average Voltage = _— = _ 1871 Eu 3 Ш Ш ER © = 457 Determine maximum deviation from average voltage NOTES: (AB) 457 - 452 = 5v 1 In compliance with NEC requirements for multimotor and combination load (BC) 464 - 457 = 7 у equipment (refer to NEC Articles 430 and 440), the overcurrent protective (AC) 457 - 455 = 2v device for the unit shall be fuse or HACR breaker Canadian units may be Maximum deviation is 7 v use or circuit breaker. Determine percent voltage imbalance % Voltage Imbalance = 100 x 457 = 153% , | This amount of phase imbalance is satisfactory as it is below the maximum # allowable 2% IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately 12 Settings may be changed slightly to provide a greater de- gree of comfort for a particular installation. Refer to Accessory Remote Control Panel instructions if required. Step 9 — Make Outdoor-Air Inlet Adjustments MANUAL OUTDOOR-AIR DAMPER — All units (ex- cept those equipped with a factory-installed economizer) have a manual outdoor-air damper to provide ventilation air. THERMOSTAT ASSEMBLY REMOVABLE JUMPER n № в 9 GE р панно a g 2 É Xx ÉS Fig. 17 — Field Control Thermostat Wiring me 25% ADJUSTABLE AIR DAMPER / I R 4 À L [À / BASE ° \ “$T UNIT \ Ан LI Y J SECURING SCREWS Fig. 18 — 25% Outdoor-Air Section Details aa 8 me EE a a a Teta TT a aa ea eta tt a at AÑ A ET a ae te a Te a a te et Te a hea РЕЯ „же ож TT a "a a a a TS О Cat TR COOLING LOCKOUT SWITCH ECONOMIZER BER de HR I ECONOMIZER LAN CN o MOTOR RE ES Pes ERE CONTROL in oe > : os MODULE E Cee В FILTERS OUTDOOR AIR THERMOSTAT ECONOMIZER. E К DAMPER м в о: 2 rs esd ee E Es ASSEMBLY EA . Fig. 19 — Economizer Damper Assembly-End View Damper can be preset to admit up to 25% outdoor air into return-air compartment. To adjust, loosen securing screws and move damper to desired setting, then retighten screws to secure damper (Fig. 18). OPTIONAL ECONOMIZER Economizer Motor Control Module (See Fig. 19-21) — Set economizer motor to the D setting (Fig. 20). Damper Vent Position Setting 1. Set fan switch at ON position (continuous fan operation) and close night switch if used. 2. Set system selector switch at OFF position. 3. Turn damper adjustment knob located on control mod- ule clockwise slowly until dampers assume desired vent position. Do not manually operate economizer motor. Damage to motor will result. ” ) = "0-0 Ok] Г so + A D ____ CHANGEOVER | | + | SET POINT 5 © — 1: Г MINIMUM DAMPER мммим ° _ Y — POSITION CIE — SETTING =z | LED LIGHTS UP OPEN TO INDICATE P PI OUTDOOR AIR IS SUITABLE FOR 1 FREE COOLING LED — Light-Emitting Diode Fig. 20 — Economizer Motor Control Module ECONOMIZER MOTOR y ; OI N > СО © SER >” Callao Calla Loa `Е au _ / ECONOMIZER ASS EEE ne Fig. 21 — Economizer Motor Control Module Location Step 10 — Install Outdoor-Air Hood — The outdoor-air hood is common to 25% air ventilation and econo- mizer. If economizer is used, all electrical connections have been made and adjusted at the factory. Assemble and in- stall hood in the field. NOTE: The hood top cover, upper and lower filter retain- ers, hood drain pan, baffle (020-028), and filter support bracket are secured opposite the condenser end of the unit. The screens, hood side panels, remaining section of filter support bracket, seal strip, and hardware are in a package located inside the return-air filter access panel (Fig. 22). 1. Attach seal strip to upper filter retainer. See Fig. 23. 2. Assemble hood top cover, side panels, upper filter retainer, and drain pan (see Fig. 24). 3. Secure lower filter retainer and support bracket to unit. See Fig. 24. Leave screws loose on 020-028 units. 4. Slide baffle (020-028) behind lower filter retainer and tighten screws. 5. Loosen sheet metal screws for top cover of base unit located above outdoor-air inlet opening. 6. Match notches in hood top cover with unit top cover screws. Insert hood flange between top cover flange and unit. Tighten screws. 7. Insert outdoor-air inlet screens and spacer in channel created by lower filter retainer and filter support bracket. 8. Attach remaining section of filter support bracket. START-UP Use the following information and Start-Up Checklist on page CL-1 to check out unit PRIOR to start-up. Unit Preparation — Check that unit has been installed in accordance with these installation instructions and appli- cable codes. Compressor Mounting — Loosen the compressor hold- down bolts on 48TJO16 and 028 units until sidewise move- ment of the washer under each holddown bolt head can be obtained. Do not loosen completely as bolts are self- locking and will maintain adjustment. NOTE: DO NOT loosen holddown bolts on 48TJ020 and 024 units with hermetic compressors. Internal Wiring — Check all electrical connections in unit control boxes; tighten as required. Refrigerant Service Ports — Each refrigerant sys- tem has 1 suction port located in the top of the compressor motor casing (semi-hermetic compressors) or on the suc- tion line (hermetic compressors). All units also have one service port on the liquid line and one on either the com- pressor discharge flange or discharge line. Be sure that caps on the ports are tight. N Crankcase Heater(s) (48TJ016 and 028 Only) — Crankcase heater(s) is energized as long as there is power to the unit. ; IMPORTANT: Unit power must be on for 24 hours prior to start-up. Otherwise, damage to compressor may result. Evaporator Fan — Fan belt and variable pulleys are factory-installed. See Tables 3-7 for Fan Performance Data. Remove tape from fan pulley, and be sure that fans rotate in the proper direction. See Table 8 for air quantity limits. See Table 9 for static pressure information for accessories В 14 wt OUTDOOR-AIR HOOD AND MOUNTING BRACKETS A > y >< @ I e Pe te | „” ~~ | E > > “=. J re XG | PACKAGE AND HOOD COMPONENTS > RETURN-AIR FILTER ACCESS PANEL Fig. 22 — Outdoor-Air Hood Component Location HOOD TOP PANEL HOOD DRAIN и РАМ Fig. 23 — Seal Strip Location UPPER FILTER RETAINER SEAL STRIP HOOD SIDE PANELS (2) HOOD TOP PANEL LOWER FILTER RETAINER FILTER SUPPORT BRACKET HOOD DRAIN PAN UPPER FILTER RETAINER Fig. 24 — Outdoor-Air Hood Details and options. To alter fan performance, see Evaporator Fan Performance Adjustment section on page 20. Condenser-Fans and Motors — Condenser fans and motors are factory set. Refer to Condenser-Fan Adjustment section on page 21 as required. Be sure that fans rotate in the proper direction. e Return-Air Filters — Check that correct filters are in- stalled in filter tracks (see Table 1). Do not operate unit without return-air filters. Outdoor-Air Inlet Screens — Outdoor-air inlet screens must be in place before operating unit. Accessory Economizer Adjustment — Remove filter access panel. Check that outdoor-air damper is closed and return-air damper is open. Economizer operation and adjustment are described in Base Unit Operation section on page 18; and Economizer Adjustment section on page 22. Gas Heat — Verify gas pressures before turning on heat as follows: I. Turn off manual gas stop. Connect pressure gage to supply gas tap (See Fig. 15 on page 11). Connect pressure gage to manifold pressure tap on gas valve. Turn on manual gas stop and set thermostat to HEAT position. After the unit has run for several minutes, ver- ify that incoming pressure is 5.0 in. wg or greater, and that the manifold pressure is 3.5 in. wg. If manifold pres- sure must be adjusted, refer to Gas Valve Adjustment section on page 25. . After unit has been in operation for 5 minutes, check temperature rise across the heat exchangers. See unit in- formative plate for correct rise limits of the heat sup- plied. Air quantities may need to be adjusted to bring the actual rise to within the allowable limits. Table 3 — Fan Performance Data, 48TJ016 — 208/230-V and 460-V Units EXTERNAL STATIC PRESSURE (in. wg) em 0.2 0.4 0.6 0.8 1.0 1.2 Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rom | Bhp | Watts 4500 8011105 | 933 | 890 | 1.26 | 1119 | 971 | 1.46 | 1297 | 1050 | 1 67 | 1483 | 1125 | 188 | 1670 | 1200 | 2.12 | 1883 4800 843 | 1.25 | 1110 | 928 | 1.47 | 1306 | 1006 | 168 | 1492 | 1081 | 1.90 | 1687 | 1153 | 2.13 | 1892 | 1223 | 2.36 | 2096 5100 885 | 147 | 1306 | 968 | 1.70 | 1510 | 1043 | 1.93 | 1714 | 1114 | 2 16 | 1918 | 1183 | 2.40 | 2131 | 1250 | 2.64 | 2345 5400 927 | 1.71 | 1519 | 1008 | 1.95 | 1732 | 1080 | 2.20 | 1954 | 1148 | 2.44 | 2167 | 1214 | 2.69 | 2389 | 1279 | 2.94 1 2611 5700 971 | 198 | 1758 | 1049 | 2.24 | 1989 | 1118 | 2.50 | 2220 | 1134 | 2 75 | 2442 | 1247 | 301 | 2673 | 1309 | 3.28 | 2913 6000 1016 | 2 28 | 2025 | 1091 | 2.55 | 2265 | 1158 | 2.83 | 2513 | 1222 | 3 10 | 2753 | 1282 | 336 | 2984 | 1342 | 3.64 | 3233 6300 1059 | 2.60 | 2309 | 1133 | 2 89 | 2567 | 1198 | 3.17 | 2815 | 1259 | 3.46 | 3073 | 1318 | 374 | 3321 | 1375 | 4.02 | 3570 6600 1104 | 2.96 | 2629 | 1174 | 3 26 | 2895 | 1239 | 3.56 | 3162 | 1297 | 386 | 3428 | 1355 | 4.15 } 3686 — — — 6900 1150 | 3.35 | 2975 | 1218 | 3.67 | 3259 | 1281 | 398 | 3535 — — — — — — — — — 7200 1194 | 377 | 3348 | 1260 | 4.10 | 3641 — — — — — — — — — — — — 7500 1238 | 4 23 | 3758 — — — — — — — — — — — — — — — EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW 14 1.6 1.8 2.0 (Cfm) . . . . Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts 4500 1275 | 2.39 | 2123 | 1349 | 2.70 | 2398 | 1421 | 303 | 2691 | 1490 | 3.39 | 3011 4800 1293 | 2.62 | 2327 | 1364 | 2 92 | 2593 | 1433 | 3.24 | 2877 | 1501 | 359 | 3188 5100 1316 | 290 | 2575 | 1382 | 3.18 | 2824 | 1448 | 3.49 | 3099 | 1514 | 3.86 | 3428 5400 1342 | 320 | 2842 | 1403 | 3.47 | 3082 | 1466 | 3.77 | 3348 | 1529 | 4.16 | 3694 5700 1370 | 354 | 3144 | 1429 | 3.81 | 3384 | 1487 | 411 | 3650 — — — 6000 1401 | 3.92 | 3481 | 1458 | 4.20 | 3730 — — — — — — 6300 — — — — — — — — — — — — 6600 — — — — — — — — — — — — 6900 — — — — — — — — — — — — 7200 — — — — — — — — — — — — 7500 — — — — — — — — — — — — LEGEND mance table. See Table 9 for accessory/FIOP static pressure information Bhp — Brake Horsepower Input to Fan 3 inter n os polation is permissible. Do not extrapolate. Watts — Input Watts to Motor 4. Maximum continuous bhp is 4.25 and the maximum continuous NOTES: 1. Factory shipped motor drive range is 1194 to 1526 rpm Other roms require a field-supplied drive. 2 Static pressure losses (i e , economizer, electric heater) must be added to external static pressure before entering Fan Perfor- 15 watts are 3775. Extensive motor and drive testing on these units ensures that the full horsepower range of the motor can be uti- lized with confidence. Using your fan motors up to the watts rat- ing shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. Table 4 — Fan Performance Data, 48TJ016 — 575-V Units EXTERNAL STATIC PRESSURE (in. wg) A 0.2 0.4 0.6 0.8 1.0 1.2 Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts 4500 801 | 1.05 | 933 | 8901.26 | 1119 | 971 | 146 | 1297 | 1050 | 1 67 | 1483 | 1125 | 188 | 1670 | 1200 | 2 12 | 1883 4800 843 | 125 | 1110 | 928 | 1.47 | 1306 | 1006 | 1 68 | 1492 | 1081 | 190 | 1687 | 1153 | 213 | 1892 | 1223 | 2.36 | 2096 5100 885 | 147 | 1306 | 968 | 1.70 | 1510 | 1043 | 1 93 | 1714 | 1114 | 216 | 1918 | 1183 | 2 40 | 2131 | 1250 | 2.64 | 2345 5400 927 | 171 | 1519 | 1008 | 1.95 | 1732 | 1080 | 2 20 | 1954 | 1148 | 2 44 | 2167 | 1214 | 2.69 | 2389 | 1279 | 2.94 | 2611 5700 971 | 198 | 1758 | 1049 | 2.24 | 1989 | 1118 | 2.50 | 2220 | 1134 | 2 75 | 2442 | 1247 | 301 | 2673 | 1309 | 3.28 | 2913 6000 1016 | 2.28 | 2025 | 1091 | 2.55 | 2265 | 1158 | 2.83 | 2513 | 1222 | 310 | 2753 | 1282 | 3.36 | 2984 — — — 6300 1059 | 260 | 2309 | 1133 | 2.89 | 2567 | 1198 | 3.17 | 2815 — — — — — — — — — 6600 1104 | 2.96 | 2629 | 1174 | 3.26 | 2895 — — — — — — — — — — — — 6900 1150 | 3.35 | 2975 — — — — — — — — — — — — — — — 7200 — — — — — — — — — — — — — — — — — — 7500 — — — — — — — — — — — — — — — — — — EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW 14 16 1.8 2.0 (Cfm) = - - = Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts 4500 1275 | 2.39 | 2123 | 1349 | 270 | 2398 | 1421 | 3.03 | 2691 | 1490 | 3.39 | 3011 4800 1293 | 262 | 2327 | 1364 | 292 | 2593 | 1433 | 3.24 | 2877 — — — 5100 1316 | 290 | 2575 | 1382 | 3.18 | 2824 — — — — — — 5400 1342 | 320 | 2842 — — — — — — — — — 5700 — — — — — — — — — — — — 6000 — — — — — — — — — — — — 6300 — — — — — — — — — — — — 6600 — — — — — — — — — — — — 6900 — — — — — — — — — — — — 7200 — — — — — — — — — — — — 7500 — — — — — — — — — — — — LEGEND mance table. See Table 9 for accessory/FIOP static pressure information Bhp — Brake Horsepower Input to Fan q Inter n Let polation is permissible. Do not extrapolate. Watts — Input Watts to Motor 4. Maximum continuous bhp is 3 45 and the maximum continuous NOTES: watts are 3065. Extensive motor and drive testing on these units 1 Factory shipped motor drive range is 1201 to 1462 rpm. Other ensures that the full horsepower range of the motor can be uti- 2. rpms require a field-supplied drive Static pressure losses (i.e , economizer, electric heater) must be added to external static pressure before entering Fan Perfor- lized with confidence. Using your fan motors up to the watts rat- ing shown will not result in nuisance tripping or premature motor failure Unit warranty will not be affected Table 5 — Fan Performance Data, 48TJ020 EXTERNAL STATIC PRESSURE (in. wg) Aer 0.2 0.4 0.6 0.8 1.0 1.2 Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rom | Bhp | Watts | Rpm | Bhp | Watts {| Rpm | Bhp | Watts | Rpm | Bhp | Watts 5000 669 | 110 | 1019 772 | 1.40 | 1291 870 | 1 80 | 1582 963 | 2.10 | 1903 | 1052 | 2.50 | 2251 | 1137 | 2.90 | 2623 5500 717 | +40 | 1292 813 | 1.80 | 1585 905 | 210 | 1892 992 | 250 | 2223 | 1076 | 290 | 2680 | 1157 | 3.30 | 2962 6000 767 | 180 | 1617 858 | 2.20 | 1932 944 | 2 50 | 2256 | 1026 | 2.90 | 2600 | 1104 | 330 | 2967 | 1181 | 3.80 | 3358 6500 817 | 220 | 1992 903 | 2.60 | 2329 985 | 3 00 | 2673 | 1062 | 3 40 | 3031 | 1136 | 380 | 3410 | 1209 | 4.30 | 3811 7000 869 | 2 70 | 2427 950 | 3 10 | 2787 | 1028 | 3.50 | 3151 | 1102 | 3.90 | 3527 | 1172 | 4.40 | 3919 | 1241 | 4.80 | 4331 7200 889 | 2 94 | 2624 969 | 3.34 | 2993 | 1046 | 3 74 | 3366 | 1118 | 4 18 | 3749 | 1187 | 4.64 | 4147 | 1255 | 5.08 | 4564 7500 920 | 330 | 2919 998 | 3 70 | 3303 | 1073 | 4.10 | 3689 | 1143 | 4.60 | 4083 | 1210 | 5.00 | 4490 | 1275 | 5.50 | 4914 8000 973 | 390 | 3476 | 1047 | 4 30 | 3886 | 1119 | 4.80 | 4294 | 1186 | 5.30 | 4708 | 1250 | 5 70 | 5131 — — — 8500 1026 | 460 | 4102 | 1097 | 5 10 | 4635 | 1166 | 5.60 | 4967 — — — — — — — — — 9000 1079 | 540 | 4800 — — — — — — — — — — — — — — — EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW 1.3 1.4 1.6 © 1.8 (Cfm) - "“ " - Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts 5000 1178 | 3.15 | 2820 | 1218 | 3.40 | 3016 | 1295 | 3 80 | 3425 | 1369 | 4 30 | 3849 5500 1196 | 355 | 3164 | 1234 1 3.80 | 3366 1 1309 | 420 | 3789 | 1381 | 470 | 4229 6000 1218 | 400 | 3565 | 1251 | 4.20 | 3772 | 1327 | 4.70 1 4206 | 1396 | 5.20 | 4658 6500 1244 | 450 | 4022 | 1279 | 4.70 | 4233 | 1348 | 5.20 | 4677 | 1415 | 5 80 | 5139 7000 1275 | 505 | 4547 | 1308 | 5.30 | 4762 — — — — — — 7200 1288 | 5 33 | 4783 — — — — — — — — — 7500 1307 | 5 75 | 5135 — — — — — — — — — 8000 — — — — — — — — — — — — 8500 — — — — — — — — — — — — 9000 — — — — — — — — — — — — LEGEND mance table. See Table 9 for accessory/FIOP static pressure information. Bhp - Brake Horsepower Input to Fan 3 Inter n. o _ polation is permissible Do not extrapolate. Watts Input Watts to Motor 4. Maximum continuous bhp is 5 9 and the maximum continuous NOTES: 1. 2, Factory shipped motor drive range is 1047 to 1251 rpm. Other rpms require a field-supplied drive. Static pressure losses (i.e., economizer, electric heater) must be added to external static pressure before entering Fan Perfor- 16 watts are 5180. Extensive motor and drive testing on these units ensures that the full horsepower range of the motor can be uti- lized with confidence Using your fan motors up to the watts rat- ing shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected. кое Table 6 — Fan Performance Data, 48TJ024 EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW 0.2 0.4 0.6 0.8 1.0 1.2 (CFM) > " = = = в — Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts e 6000 767 | 1.80 | 1617 | 858 | 2.20 | 1932 | 944 | 250 | 2256 | 1026 | 290 | 2600 | 1104 | 3.30 | 2967 | 1181 | 380 | 3358 6500 817 | 2.20 | 1992 | 903 | 2.60 | 2329 | 985 | 300 | 2673 | 1062 | 340 | 3031 | 1136 | 3.80 | 3410 | 1209 | 430 | 3811 7000 869 | 2.70 | 2427 | 950 | 3.10 | 2787 | 1028 | 350 | 3151 | 1102 | 390 | 3527 | 1172 | 4.40 | 3919 | 1241 | 4.80 | 4331 7500 920 | 3.30 | 2919 | 998 | 370 | 3303 | 1073 | 4.10 | 3689 | 1143 | 4 60 | 4083 | 1210 | 5.00 | 4490 | 1275 | 5.50 | 4914 8000 973 | 3.90 | 3476 | 1047 | 430 | 3886 | 1119 | 4 80 | 4294 | 1186 | 530 | 4708 | 1250 | 5 70 | 5131 | 1313 | 6.20 | 5569 8500 | 1026 | 460 | 4102 | 1097 | 510 | 4635 | 1166 | 560 | 4967 | 1231 | 600 | 5401 | 1292 |6 50 | 5843 | 1352 | 7.00 | 6297 9000 | 1079 | 540 | 4800 | 1147 | 590 | 5257 | 1214 | 6.40 | 5714 | 1276 | 6.90 | 6171 | 1336 | 7 40 | 6632 | 1393 | 7.90 | 7102 9500 | 1133 | 6.20 | 5576 | 1199 | 6.80 | 6058 | 1263 | 7.30 | 6540 | 1323 | 7.90 | 7018 | 1381 | 840 | 7500 | 1436 | 8.90 | 7988 10,000 | 1188 | 7.20 | 6432 | 1250 | 7.80 | 6939 | 1313 | 8.30 | 7444 | 1371 | 8.90 | 7946 | 1426 | 9.50 | 8449 | — — — EXTERNAL STATIC PRESSURE (in. wg) Amo 1.4 16 1.8 1.9 2.0 Rpm | Bhp | Watts | Rom | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts 6000 | 1255 | 4.20 | 3772 | 1327 | 4 70 | 4206 | 1396 | 520 | 4658 | 1431 | 5.45 | 4884 | 1465 | 5 70 | 5110 6500 | 1279 | 4.70 | 4233 | 1348 | 5.20 | 4677 | 1415 | 580 | 5139 | 1449 | 6.10 | 5370 | 1482 | 6 40 | 5601 7000 | 1308 | 5.30 | 4762 | 1373 | 5 80 | 5215 | 1437 | 6.40 | 5686 | 1469 | 6.70 | 5922 | 1501 | 7.00 | 6157 7500 | 1339 | 6.00 | 5356 | 1401 | 6 50 | 5818 | 1462 | 7.00 | 6298 | 1493 | 7.25 | 6538 | 1523 | 7 50 | 6778 8000 1 1373 | 6.70 | 6024 | 1433 | 7 30 | 6495 | 1493 | 7.80 | 6966 | 1523 | 8.05 | 7202 | — — — 8500 | 1410 | 7.60 | 6765 | 1467 | 810 | 7248 | 1524 | 8.70 | 7731 — — — — — — 9000 | 1449 | 8.50 | 7584 | 1503 | 9.00 | 8033 | — — — — — — — — — 9500 | 1488 | 9.40 | 8403 | — — — — — — — — — — — — 10,000 — — — — — — — — — — — — — — — LEGEND 4. Interpolation is permissible Do not extrapolate. 5. Maximum continuous bhp is 8.7 for 208/230 and 575-v units and Watts — Input Watts to Motor pui fo Fan 9.5 for 460-v units. The maximum continuous watts are 7915 for p the 208/230 and 575-v units and 8640 for the 460-v units. Exten- NOTES: sive motor and drive testing on these units ensures that the full 1. Boldface indicates additional capability of the 460-v motor. 2. Factory shipped motor drive range is 1238 to 1494 rpm. Other rpms require a field-supplied drive 3 Static pressure losses (i.e , economizer) must be added to exter- nal static pressure before entering Fan Performance table See Table 9 for accessory/FIOP static pressure information horsepower range of the motor can be utilized with confidence. Using your fan motors up to the watts rating shown will not result in nuisance tripping or premature motor failure Unit warranty will not be affected. Table 7 — Fan Performance Data — 48TJ028 EXTERNAL STATIC PRESSURE (in. wg) “cm 0.2 0.4 0.6 0.8 0.9 1.0 Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rom | Bhp | Watts | Rpm | Bhp | Watts 7,500 962 | 3.39 | 3123 | 1039 | 381 | 3507 (1111 | 4.23| 3895 |1179| 466 | 4295 | 1212| 4.89 | 4503 | 1245 511 | 4710 8,000 |1017| 4.04 | 3717 |1091 | 4.48 | 4126 | 1160 | 493| 4536 | 1225| 538| 4954 |1256| 5.62 | 5170 | 1287 | 5.85 | 5386 8,500 |1072| 4.76 | 4385 |1143 | 5.23 | 4818 | 1209 | 5.70 | 5250 |1271| 618| 5688 | 1302 | 6.42 | 5913 |1332| 6.66 | 6137 9,000 |1128| 5.57 | 5129 [1196 | 6.07 | 5587 |1260 | 6 56| 6042 | 1320 | 7.06 | 6501 | 1348 | 7.32 | 6735 | 1377 | 757 | 6968 9,500 |1185| 6.47 | 5955 |1250 | 6.99 | 6437 [13111 7.51 | 6915 | 1369 | 803| 7395 | 1396 | 8.30 | 7638 | 1424 | 8.56 | 7881 10,000 | 1241 | 7.45! 6865 | 1304 | 8.00 | 7372 | 13631 8.55 | 7873 |1419| 909| 8376 |1445 | 9.37 | 86529 | 1472 | 9.64 | 8882 10,500 |1298| 8.54 7865 {1359 | 9121 8396 | 1415| 969| 8921 | 1469 |10.26 | 9446 | 1495 | 10.55 | 9710 | 1521 | 10.83 | 9973 11,000 | 1355| 9.72 | 8956 | 1414 | 10.33 | 9512 | 1469 | 10.93 | 10,062 | 1521 | 11.52 | 10,609 | — — — — — — 11,250 | 1384 | 10.36 | 9540 | 1441 | 10.97 | 10,107 | 1495 | 11.58 | 10,668 | — — — — — — — — — EXTERNAL STATIC PRESSURE (in. wg) Ae 1.2 1.3 1.4 1.6 1.8 Rpm | Bhp | Watts | Rom | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts | Rpm | Bhp | Watts 7,500 | 1309 | 5.58 | 5143 | 1341 | 5.83 | 5370 | 1372 | 6 08 | 5597 | 1434 | 6 59 | 6067 | 1494 | 7.12 | 6558 8,000 | 1349 | 6.33 | 5833 | 1379 | 6.59 | 6065 | 1409 | 6 84 | 6297 | 1467 | 736 | 6779 | — — — 8,500 |1390| 7.17 | 6600 | 1419 | 7.43 | 6839 | 1447 | 7 68 | 7077 | 1504 | 822 | 7571 — — 9,000 | 1433 | 808 | 7446 | 1461 | 8.351 7692 | 1488 | 8 62 | 7938 | — — — — — — 9,500 | 1478 | 910| 8378 | 1505 | 9.37 | 8626 | — — — — — — — — — 10,000 | 1524 | 10.20 | 9396 | 1550 | 10.48 | 9653 | — — — — — — — — — 10,500 — — — — — — — — — — — — — — — 11,000 — — — — — — — — — — — — — — — 11,250 — — — — — — — — — — — — — — — LEGEND 4. Interpolation is permissible. Do not extrapolate. Bhp — Brake Horsepower Input to Fan 5 an performance is based on wet coils, clean filters, and casing Watts — Input Watts to Motor 6. Maximum continuous bhp is 10.2 for 208/230 and 575-v units and OTES: Ш Ш 11 8 for 460-v units. The maximum continuous watts are 9510 for 1. Boldface indicates additional capability of the 460-v motor. the 208/230 and 575-v units and 11,000 for the 460-v units Ex- | 2. Factory shipped motor drive range is 1323 to 1579 rpm. Other tensive motor and drive testing on these units ensures that the \ rpms require a field-supplied drive. full horsepower range of the motor can be utilized with confi- 3 Static pressure losses (i.e , economizer) must be added to exter- nal static pressure before entering Fan Performance table. See Table 9 for accessory/FIOP static pressure information. dence Using your fan motors up to the watts rating shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected 17 Table 8 — Air Quantity Limits UNIT 48TJ MINIMUM CFM MAXIMUM CFM 016 4500 7,500 020 5400 9,000 024 6000 10,000 028 7500 11,250 Table 9 — Accessory/FIOP Static Pressure (in. wg) UNIT UNIT CFM ECONOMIZER HORIZONTAL ADAPTER CURB ABTJ | VOLTAGE PRESSURE DROP* PRESSURE INCREASE} 4.000 03 0.68 5.000 05 0 65 016 All 6.000 07 0.60 7.500 10 0.45 6.000 07 0.60 7.200 09 048 020-028 All 9.000 11 030 10.000 12 0.26 11.250 13 024 FIOP — Factory-installed Option *The static pressure must be added to external static pressure. The result and the evaporator entering- air cfm should then be used with the fan performance table to determine blower rpm, bhp, and watts. +The static pressure must be deducted from external static pressure The result and the evaporator entering-air cfm should then be used with the Fan Performance table to determine blower rpm, bhp, and watts. NOTE: The factory-assembled horizontal adapter curb substantially improves 48TJ016-028 fan performance (by the amount of static pressure listed). Base Unit Operation COOLING, UNITS WITHOUT ECONOMIZER — When thermostat calls for cooling, terminals G and Y1 are ener- gized. The indoor (evaporator) fan contactor (IFC) and compressor contactor no. 1 (C1) are energized and evaporator- fan motor (IFM), compressor no. 1 (48TJ020-028) or un- loaded compressor (48TJ016), and condenser fan start. The condenser-fan motors run continuously while unit is cool- ing. If the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is ener- gized and compressor no. 2 starts (48TJ020-028), or com- pressor no. 1 runs fully loaded (48TJO16). HEATING, UNITS WITHOUT ECONOMIZER NOTE: The 48TJ016-028 units have 2 stages of heat. First Stage — All Units — Turn unit power on. Open man- ual gas line valve. Set thermostat system switch at HEAT or AUTO. position and set fan switch to AUTO. position for heating. First-stage thermostat calls for heat. Time-delay relay for evaporator fan begins timer sequence. Induced-draft relay closes, and induced-draft motor starts. Pressure switch closes and pilot valve no. 1 opens, al- lowing gas to flow to the first-stage pilot. Spark ignitor ignites pilot flame. Sensor detects flame and the main gas valve no. 1 opens. Gas flows to main burners and first- stage burners ignite. Spark igniter turns off. When sequence is complete, time-delay relay closes and evaporator fans start. Second-Stage — 48TJD016-028 Low-Heat and 48TJEO16 High Heat Units — With an additional heating call, the second-stage thermostat closes. (The control relay [HR2] closes during the first stage of operation.) Pilot valve no. 2 opens, and the spark ignitor ignites pilot. The sensor de- tects a flame and energizes main gas valve coil no. 2, open- 18 wt ing main gas valve no. 2. Gas flows to the main burners, and the second-stage burners ignite. The spark ignitor turns off. When the second-stage thermostat is satisfied, the second- stage gas valve closes. When the first-stage thermostat is satisfied, the first- stage gas valve closes. The induced-draft motor turns off, the time delay relay opens, and the timer sequence begins. When the sequence is complete, the evaporator-fan motor turns off. Second-Stage — 48TJE024,028 High-Heat Units — With an additional heating call, the second-stage thermostat closes. (The control relay [HR2] closes during the first stage of op- eration.) The second-stage induced-draft relay closes, and the second-stage induced-draft motor starts. The second-stage pressure switch closes and pilot valve no. 2 opens, allowing gas to flow to the second-stage pilot. Spark ignitor ignites pilot flame. The sensor detects the flame, and main gas valve no. 2 opens. Gas flows to main burners and second-stage burners ignite. Spark ignitor turns off. When the second-stage thermostat is satisfied, the second- stage gas valve closes and the second-stage induced-draft motor turns off. When the first-stage thermostat is satisfied, the first- stage gas valve closes. The first-stage induced-draft motor turns off, the time relay opens, and the timer sequence be- gins. When the sequence is complete, the evaporator-fan motor turns off. COOLING, UNITS WITH ECONOMIZER — Upon a call for cooling, when outdoor ambient is above the changeover control setting, the economizer damper moves to VENT position. The compressors and evaporator and condenser fans energize and operate as per Cooling, Units Without Economizer section above. e Upon a first call for cooling, when outdoor ambient is below the changeover control setting, the evaporator fan starts and the economizer 1s fully open. The compressors remain off. Upon a second-stage call for cooling, compressor no. 1 (48TJ020-028) or unloaded compressor (48TJ016) is ener- gized and mechanical cooling is integrated with econo- mizer cooling. If the outdoor-air temperature drops below 50 F, a cooling lockout switch prevents the compressors from running. When supply-air temperature drops below a fixed set point, the economizer damper modulates to maintain the temper- ature at the fixed set point. A freeze protection thermostat (FPT) is located on the evaporator coil. It detects frost build-up and locks out the compressors, allowing the coil to clear. Once frost has melted, the compressors can be reenergized by resetting the thermostat. HEATING, UNITS WITH ECONOMIZER — Outdoor-air damper stays at VENT position while evaporator fan is operating. SERVICE A WARNING Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury. Cleaning — Inspect unit interior at beginning of each heating and cooling season and as operating conditions re- quire. Remove unit top panel and/or side panels for access to unit interior. MAIN AND PILOT BURNERS — At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the pilot and main burner flames through view port (in condenser section), and adjust if necessary. Refer to Pilot Adjustment or Main Burners sections on pages 24 and 25. FLUE GAS PASSAGEWAYS — The flue collector box and heat exchanger cells may be inspected by removing heat exchanger access panel (Fig. 4 and 5), flue box cover, and main burner assembly (Fig. 25). Refer to Main Burners sec- tion on page 25 for burner removal sequence. If cleaning is required, remove heat exchanger turbulators (Fig. 26) and clean all parts with a wire brush. COMBUSTION-AIR BLOWER — Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bi-monthly to determine proper cleaning frequency. To inspect blower wheel, remove heat exchanger access panel. Shine a flashlight into opening to inspect wheel. If cleaning is required, remove motor and wheel assembly by removing screws holding motor mounting plate to top of combustion fan housing (Fig. 25 and 26). The motor and wheel assembly will slide up and out of the fan housing. Remove the blower wheel from the motor shaft and clean with a detergent or solvent. Replace motor and wheel assembly. EVAPORATOR COIL — Clean as required with commer- cial coil cleaner. 19 CONDENSER COIL — Clean condenser coil annually and as required by location and outdoor-air conditions. Inspect coil monthly; clean as required. CONDENSATE DRAIN — Check and clean each year at start of cooling season. In winter, keep drains and traps dry. FILTERS — Clean or replace at start of each heating and cooling season, or more often if operating conditions re- quire. Refer to Table 1 for type and size. NOTE. The 48TJ028 unit requires industrial grade throw- away filters capable of withstanding face velocities up to 625 fpm. Ensure that replacement filters for the 48TJ028 units are rated for 625 fpm. OUTDOOR-AIR INLET SCREENS — Clean screens with steam or hot water and a mild detergent. Do not use dis- posable filters in place of screens. IGNITOR IGNITOR CONTROL CONTROL PACKNO1 PACKNO 2 INDUCED-DRAFT PRESSURE MOTOR SWITCH - 1... PUE от’. ao A Te © nu mu me a _ COMBUSTION PRIMARY MAIN FAN AIR BURNER BOX VALVE VALVE HOUSING SHUTTER SECTION COVER NO 1 NO 2 Fig. 25 — Typical Gas Heating Section, 2-Stage Units {(48TJD Units Shown) COMBUSTION FAN HOUSING IGNITOR CONTROL PACKS и, № a E y TURBULATORS аа. 3 a "e a Fig. 26 — Typical Heating Section with Main Burners Removed (48TJD Units Shown) Lubrication COMPRESSORS — Each compressor is charged with the correct amount of oil at the factory. The 48TJ016 compres- sor runs with a slightly low sight glass oil level. Oil level with compressor off should be about % of sight glass as shown in Fig. 27. If oil charge is above V4 sight glass, do not remove any oil until the compressor crankcase heater has been ener- gized for at least 24 hours. FAN SHAFT BEARINGS — For 016 units, bearings are permanently lubricated. No field lubrication is required. For 020-028 units, lubricate bearings at least every 6 months with suitable bearing grease. Extended grease line is pro- vided for far side fan bearing (opposite drive side). Typical lubricants are given below: MANUFACTURER LUBRICANT Texaco Regal AFB-2* Mobil Mobilplex EP No 1 Sunoco Prestige 42 Texaco Multifak 2 “Preferred lubricant because it contains rust and oxidation inhibitors. CONDENSER AND EVAPORATOR-FAN MOTOR BEARINGS — The condenser- and evaporator-fan motors have permanently-sealed bearings, so no field lubrication is necessary. Evaporator Fan Performance Adjustment (Fig. 28-30) — Fan motor pulleys are factory set for speed shown in Table 1. To change fan speeds. 1. Shut off unit power supply. 2. a. 016 only: Loosen belt by loosening carriage nuts hold- ing motor mount assembly to fan scroll side plates (A and B). b. 020-028 only: Loosen nuts on the 2 carriage bolts in the mounting base. Install jacking bolt and plate un- der motor base (bolt and plate are shipped in install- er’s packet). Using bolt and plate, raise motor to top of slide and remove belt. Secure motor in this posi- tion by tightening the nuts on the carriage bolts. 3. Loosen movable-pulley flange setscrew (see Fig. 28). COMPRESSOR SIGHT GLASS 1/4 NORMAL COMPRESSOR SIGHT GLASS OIL LEVEL Fig. 27 — 48TJ016 Compressor Sight Glass Oil Level 20 ut 4. Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. In- creasing fan speed increases load on motor. Do not ex- ceed maximum speed specified in Table 1. See Table 8 for air quantity limits. 5. Set movable flange at nearest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.) 6. Tighten belts (see Belt Tension Adjustment section on page 21). To align fan and motor pulleys: 1. Loosen fan pulley setscrews. 2. Slide fan pulley along fan shaft. 3. Make angular alignment by loosening motor from mount- ing plate. 7 MOVABLE STRAIGHTEDGE MUST FLANGES BE PARALLEL WITH BELT =I MOTOR AND FAN SHAFTS MUST BE PARALLEL PULLEYS SETSCREWS FIXED FLANGES SINGLE-GROOVE — Fig. 28 — Evaporator-Fan Alignment and Adjustment Evaporator Fan Service and Replacement 48TJO16 UNITS (See Fig. 29) NOTE: To remove belts only, follow Steps 1-6. 1. Remove filter and supply-air section panels. 2. Remove unit top cover 3. Loosen carriage nuts A and B holding motor mount as- sembly to fan scroll side plates. Loosen screw C. Rotate motor mount assembly (with motor attached) as far as possible away from evaporator coil. Remove belt. 7. Rotate motor mount assembly back past original posi- tion toward evaporator coil. Remove motor mounting nuts D and E (both sides). 9. Lift motor up through top of unit. 10. Reverse above procedure to reinstall motor. 11. Check and adjust belt tension as necessary. > ME oC UNIT TOP COVER MOTOR MOUNT ASSEMBLY PULLEY \ FAN SCROLL SIDE PLATES | o DRAIN U CONNECTION \V Fig. 29 — 48TJ016 Evaporator-Fan Motor Adjustment 48TJ020-028 UNITS (See Fig. 30) — The 48TJ020-028 units use a fan motor mounting system that features a slide- out motor mounting plate. To replace or service the motor, slide out the bracket. 1. Remove the evaporator-fan access panel and the heat- ing control access panel. 2. Remove the center post (located between the evapora- tor fan and heating control access panels) and all screws securing it, 3. Loosen nuts on the 2 carriage bolts in the motor mount- ing base 4. Using jacking bolt under motor base, raise motor to top of slide and remove belt. Secure motor in this po- sitton by tightening the nuts on the carriage bolts. 5. Remove the belt drive. 6. Remove jacking bolt and tapped jacking bolt plate. 7. Remove the 2 screws that secure the motor mounting plate to the motor support channel. 8. Remove the 3 screws from the end of the motor sup- port channel that interfere with the motor slide path. 9. Slide out the motor and motor mounting plate. 10. Disconnect wiring connections and remove the 4 mount- ing bolts. 11. Remove the motor. 12. To install the new motor, reverse Steps 1-10. 21 FAN PULLEY CENTER POST BELT MOTOR PULLEY SLIDING MOTOR MOTOR PLATE MOTOR MOUNTING PLATE ©. % &3 \ MOTOR SUPPORT 7 CHANNEL JACKING BOLT NOTE: A 3%-in bolt and threaded plate are included in the install- er's packet. They can be added to the motor support channel below the motor mounting plate to aid in raising the motor Fig. 30 — 48TJ020-028 Evaporator-Fan Motor Section AWN «== SEE NOTE JACKING PLATE Belt Tension Adjustment — To adjust belt tension: 1. Loosen fan motor bolts. 2. a. 016 Units: Move motor mounting plate up or down for proper belt tension (7 in. deflection with one finger). b. 020-028 Units: Turn motor jacking bolt to move motor mounting plate up or down for proper belt tension (3% in. deflection at midspan with one finger [9 Ib force]). 3. Tighten nuts. 4. Adjust bolts and nut on mounting plate to secure motor in fixed position. Condenser-Fan Adjustment 48TJ016,020 UNITS (Fig. 31) |. Shut off unit power supply. 2. Remove access panel(s) closest to the fan to be adjusted. 3. Loosen fan hub setscrews. 4. Adjust fan height on shaft using a straightedge placed across the fan orifice, 5. Tighten setscrews and replace panel(s). 6. Turn on unit power. 48TJ024,028 UNITS (Fig. 32) 1. Shut off unit power supply. 2. Remove fan top-grille assembly and loosen fan hub screws. 3. Adjust fan height on unit, using a straightedge placed across the fan orifice. 4. Tighten setscrews and replace rubber hubcap to prevent hub from rusting to motor shaft. 5. Fill hub recess with permagum if rubber hubcap is missing. 025 0.62 +8 € Fig. 31 — Condenser Fan Adjustment, 48TJ016,020 00020202 RAIN SHIELD Fig. 32 — Condenser-Fan Adjustment, 48TJ024,028 Economizer Adjustment — See Tables 10 and 11 for checkout and enthalpy simulation. Make certain the outdoor-air damper is fully closed and the return-air damper is fully open before completing the following steps: |. Turn on power to the unit. 2. Turn the thermostat fan switch to the ON position. The damper will go to the vent position. 3. Adjust the vent position with the minimum position ad- justment on the economizer motor control module. See Fig. 20. 4. Set the system selector switch to COOL position and set the cooling temperature selector to its lowest setting. NOTE: The Cooling mode may also be simulated by removing the thermostat wires from terminals Y1 and Y2 and installing a jumper between terminals R and Y1. Refer to unit label diagram for terminal locations. 5. Set the outdoor-air thermostat (OAT), located in the economizer section of the unit to 75 F. 6. If the outdoor temperature is below 75 F, the econo- mizer will control the mixed air with the mixed-air sen- sor. If the outdoor air is above 75 F, place a jumper around the contacts of the OAT. 7. Jumper terminal T to terminal T1 on the module (see Fig. 20). The economizer will go to the full open po- sition. The outdoor-air damper will go to the full open position, and the return-air damper will go to the full closed position. 8. Adjust mechanical linkage, if necessary, for correct po- sitioning. If may be necessary to remove the filters to adjust the linkage. a* 9. Remove the jumper from around the contacts of the OAT if installed in Step 6. Remove the jumper from terminals T and TIL installed in Step 7. 10. If the Cooling mode was simulated to operate the unit in Step 4, remove the jumper and reconnect the ther- mostat wires to terminals Y1 and Y? Power Failure — Dampers have a spring return. In event of power failure, dampers will return to fully closed posi- tion until power is restored. Do not manually operate damper motor. Table 10 — Economizer Checkout Procedures TEST PROCEDURE A. Disconnect power at TR and TR1 Disconnect jumper between P and Pt See Fig. 20. . Jumper TR to 1. . Jumper T1 to T. . Disconnect outdoor-air thermostat connections from So and + Factory-installed 800 ohm resistor should remain connected to Sy and +. E. Reconnect power to terminals TR and TR1. RESULTS oOo 1. LED (light-emitting diode) should be off. 2. Motor is in closed position TEST PROCEDURE Disconnect factory-installed resistor from terminals Sg and + RESULTS 1 LED (light-emitting diode) should be on. 2. Motor drives toward open. Table 11 — High and Low Outdoor-Air Simulation TEST PROCEDURE A. Reconnect factory-installed 800 ohm resistor between terminals Sp and +. B. Connect 1200 ohm checkout resistor between terminals Sg and +. C. Turn set point potentiometer to position A. RESULTS Low outdoor-air test results: 1. LED (light-emitting diode) should be on. 2 Motor drives toward open. D. Turn set point potentiometer to position D E Disconnect 1200 ohm checkout resistor. High outdoor-air test results: 1. LED should be off. 2 Motor drives toward closed Refrigerant Charge — Amount of refrigerant charge is listed on unit nameplate and in Table 1. Refer to Carrier GTAC II; Module 5; Charging, Recovery, Recycling, and Reclamation section for charging methods and procedures. Unit panels must be in place when unit is operating dur- ing charging procedure. NOTE: On 020,024 units, do not adjust charge until after compressors have been running for at least 20 minutes and pressures and temperatures have stabilized. NO CHARGE — Use standard evacuating techniques. Af- ter evacuating system, weigh in the specified amount of refrigerant (refer to Table 1). LOW CHARGE COOLING — Using appropriate cooling charging chart (see Fig. 33-36), add refrigerant until con- ditions of the appropriate chart are met. Note that charging chart is different from those normally used. Chart is based on charging units to correct superheat for various operating conditions. An accurate pressure gage and temperature sens- ing device are required. Connect temperature sensing de- vice to service port on suction line and insulate it so that outdoor ambient temperature does not affect reading. Indoor- air cfm must be within normal operating range of unit. TO USE COOLING CHARGING CHART — Take out- door ambient temperature and read the suction pressure gage. Refer to appropriate chart to determine correct suction tem- perature. If suction temperature is high, add refrigerant. If suction temperature is low, carefully reclaim some of the charge. Recheck suction pressure as charge 1s adjusted. CIRCUIT 1 OUTDOOR TEMP F* -J < (9ISd> 3#NSSI4d 3NIT NOILONS un > 20 30 40 50 60 80 SUCTION LINE TEMPERATURE CF) SUCTION LINE PRESSURE (PSIG) 20 30 40 50 50 70 80 SUCTION LINE TEMPERATURE (CF) Fig. 33 — Cooling Charging Chart — 48TJ016 CIRCUIT 2 un = < - QQ = at = m A Un un < x m m © wm o Sr 30 20 70 80 30 40 50 60 SUCTION LINE TEMPERATURE (F) Fig. 34 — Cooling Charging Chart — 48TJ020 23 SUCTION LINE PRESSURE (PSIG) SUCTION LINE PRESSURE (PSIG) CIRCUIT 1 20 30 40 50 60 80 SUCTION LINE TEMPERATURE (F) SUCTION LINE PRESSURE (PSIG 20 CIRCUIT 2 OUTDOOR TEMP F 30 40 50 60 70 80 SUCTION LINE TEMPERATURE (F) Fig. 35 — Cooling Charging Chart — 48TJ024 CIRCUIT 1 AND 2 20 30 40 50 60 70 80 SUCTION LINE TEMPERATURE (F) Fig. 36 — Cooling Charging Chart — 48TJ028 24 Pilot Light — If pilots do not light as described in Start- Up, Gas Heat section on page 15, be sure that pilot orifice is not obstructed, then check for spark ignitor malfunctions as follows: 1. 2. 3. Shut off control supply power to ignitor control pack (ICP). Check that spark gap is / in. = 132 inch. Check that ICP is securely grounded. Check that high-voltage lead is securely connected be- tween ICP and electrode body. . Restore power to ICP. Check that 24 v is supplied to terminal of ICP. Check unit label diagram for correct terminal usage if any wires are removed. Pilot Adjustment % 1. 2. 3. 4. Set system selector switch at OFF position to shut off unit. Turn off power to unit. Remove screw cap cover on pilot gas valve to expose adjusting screw (See Fig. 37). Turn valve knobs to pilot position. Turn on power to unit. Set system selector switch to HEAT position and set thermostat to a setting that will call for heat. Pilot ignites. . With a small screwdriver, turn adjustment screw until flame fully engulfs sensor. Flame can be observed through view port (Fig. 38). Replace cap on pilot gas valve. Turn off power to unit. Return valve(s) to original position. . Check for proper burner operation by cycling the burn- ers. Wait 30 seconds between burner cycles. Check that all unit panels are in place before leaving unit. Gas Valve Adjustment NATURAL GAS — The gas valve opens and closes in re- sponse to the thermostat or limit control. When power 1s supplied to valve terminals 3 and 4, the pilot valve opens to the preset position. When power 1s sup- plied to terminals 1 and 2, the main valve opens to its pre- set position. The regular factory setting 1s stamped on the valve body (3.5 in. wg). To adjust regulator: 1. Set thermostat at setting for no call for heat. 2. Turn main gas valve to OFF position. 3. Remove %-in pipe plug from manifold or gas valve pres- sure tap connection. Install a suitable pressure-measuring device. 4. Set main gas valve to ON position. Set thermostat at setting to call for heat. 6. Remove screw cap covering regulator adjustment screw (See Fig. 37). 7. Turn adjustment screw clockwise to increase pressure or counterclockwise to decrease pressure. 8. Once desired pressure is established, set thermostat set- ting for no call for heat, turn off main gas valve, re- move pressure-measuring device and replace &-in. pipe plug and screw cap. in Main Burners — For most applications, main burners are factory set and should require no adjustment. However, if burner adjustment is necessary: 1. Perform pilot adjustment. 2. Turn gas valve to ON position. Allow unit to operate at least 15 minutes with burner access panel in place. 3. Remove access panel. 4. Loosen primary air shutter (Fig. 38) and adjust to a min- imum opening of % inch. 5. Retighten primary air shutter and reinstall access panel. To check ignition of main burners and fan switch oper- ation, move thermostat dial above and below room temper- ature several times, pausing at least one minute between cycles. MAIN BURNER REMOVAL 1. Shut off (field-supplied) manual main gas valve. 2. Shut off power to unit. 3. Remove unit control box/gas valve access panel, burner section access panel, and center post (Fig. 4 and 5). REGULATOR ADJUSTMENT SCREW (REMOVE COVER) PILOT ADJUSTMENT SCREW (REMOVE COVER) Fig. 37 — Gas Valve 25 PRIMARY AIR SHUTTER пс e ” adel IT ERI, dl Cuve rw E OE 0 pe FLUE BOX [OVER EE. N BT - a CR er) Cr RC I un a NN NU Mp aa Mea Ha LA oan ra Da EE MAIN BORNER Jad aE te Fig. 38 — Typical Heating Section 4. Disconnect pilot ignitor and pilot proving sensor leads at ICP, rollout switch leads at switch, and pilot tube gas connection(s) at the pilot orifice. 5. Disconnect gas connection(s) from between gas valve(s) and main burners. 6. Remove 2 screws securing burner assembly to base unit. NOTE: For 48TJE024 and 028 units only: Remove ac- cess plate from base rail. 7. Slide burner assembly out of unit. Filter Drier — Replace whenever refrigerant system is exposed to atmosphere. Protective Devices COMPRESSOR PROTECTION Overcurrent (016 and 028) — Each compressor has one man- ual reset, calibrated trip, magnetic circuit breaker. Do not bypass connections or increase the size of the circuit breaker to correct trouble. Determine the cause and correct it before resetting the breaker. NOTE: The 48TJ020 and 024 units have overcurrent pro- tection inherent in the compressor. Overtemperature — Each compressor has an internal pro- tector to protect it against excessively high discharge gas temperatures. Crankcase Heater — Each compressor has a 125-watt crank- case heater to prevent absorption of liquid refrigerant by oil in the crankcase when the compressor is idle. Since power for the crankcase heaters 1s drawn from the unit incoming power, main unit power must be on for the heaters to be energized. IMPORTANT: After a prolonged shutdown or serv- ice job, energize the crankcase heaters for 24 hours before starting the compressors. Compressor Lockout — If any of the safeties (high-, low- pressure, freeze protection thermostat, compressor internal thermostat) trip, or if there is loss of power to the compres- sors, the cooling lockout (CLO) will lock the compressors off. To reset, manually move the thermostat setting. EVAPORATOR FAN MOTOR PROTECTION — A man- ual reset, calibrated trip, magnetic circuit breaker protects against overcurrent. Do not bypass connections or increase the size of the breaker to correct trouble. Determine the cause and correct it before resetting the breaker. CONDENSER-FAN MOTOR PROTECTION — Each condenser-fan motor is internally protected against overtemperature. HIGH- AND LOW-PRESSURE SWITCHES — If either switch trips, or if the compressor overtemperature switch activates, that refrigerant circuit will be automatically locked out by the CLO. To reset, manually move the thermostat setting. FREEZE PROTECTION THERMOSTAT (FPT) — An FPT is located on the evaporator coil. It detects frost buildup and turns off the compressor, allowing the coil to clear. Once the frost has melted, the compressor can be reenergized. Relief Devices — All units have relief devices to pro- tect against damage from excessive pressures (i.e., fire). These devices protect the high and low side. Control Circuit, 24-V — This control circuit is pro- tected against overcurrent by a 3.2 amp circuit breaker. Breaker can be reset. If it trips, determine cause of trouble before resetting. Replacement Parts — A complete list of replace- ment parts may be obtained from any Carrier distributor upon request. LEGEND Fig. 39 — Typical Wiring Schematic Fig. 40 — Typical Component Arrangement AHA — Adjustable Heat Anticipator 1ЕМ — Indoor (Evaporator) TH — Thermostat Heating BKR W/AT — Breaks with Amp Turns Fan Motor TRAN — Transformer С — Contactor, Compressor IFR — Indoor (Evaporator) CB — Circuit Breaker Fan Relay {> Terminal (Marked) CC — Cooling Compensator IP — Internal Protector CH — Crankcase Heater L — Light O) Terminal (Unmarked) ero — Compressor Lockout Switch LOS — Lockout Relay n L — Compressor Lockout Switc — Low-Pressure Switc COMP — Combressor Motor LS — Limit Switch | | Terminal Block CR — Control Relay MAT — Mixed-Air Thermostat CT — Current Transformer MGV — Main Gas Valve o Splice DM — Damper Motor NEC — National Electrical Code DU — Dummy Terminal OAT — Outdoor-Air Thermostat <_>® Splice (Marked) EQUIP — Equipment OFC — Outdoor (Condenser) FPT — Freeze Protection Fan Contactor ZN Splice (Field Supplied) FU Thermostat OFM — Qutdoor (Condenser) - — Fuse an Motor Fa iri GND — Ground PGV — Pilot Gas Valve ciory Wiring HPS — High-Pressure Switch PL — Plug Assembly __ Field Control Wiring HR — Heat Relay PRI — Primary HV — High Voitage PS — Pressure Switch mew Field Power Wiring | — lgnitor QT -— Quadruple Terminal | ICP — lgnitor Control Pack R — Relay ——[ Accessory or Optional Wiring IDM — Induced-Draft Motor RS — Rollout Switch IDR — Induced-Draft Relay SN — Sensor 10 Indicate Common Potential Only, IFC — Indoor (Evaporator) SW — Switch Not To Represent Wiring Fan Contactor TB — Terminal Block IFCB — Indoor (Evaporator) TC — Thermostat Cooling Fan Circuit Breaker TDR — Time Delay Relay NOTES: 1 Compressor and fan motors thermally protected; 3-phase motors protected against primary single-phasing conditions. 2. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent. 3 Jumpers are omitted when unit is equipped with economizer. 4. Set thermostat heat anticipator(s): UNIT 48TJ W1 W2 VOLTAGE 98 ‚44 208/230, 575 016-028 1.20 44 460 26 5. CB must-trip amps are equal to or less than 140% full load amps. 6. Number(s) indicates the line location of used contacts. A bracket over (2) numbers signifies a single-pole, double-throw contact An underlined number signifies a normally-closed contact. A plain (no line) number signifies a normally-open contact 7. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices. Before replacing CLO, check these devices. 15 FIELD _ 208/230-3-60 POWER _ SUPPLY _ Ç1 cLo! nio mae r—BLK BL e YEL a —— ve COMPI 181 au BLU BLU C2 CLO2 - D— —-ZK—=———HELK BLK — 614 KID AYA-—BLK 2 — YEL: YEL — СН YEL COMP2 - 13 PE] BLU- BLU BLU IFCB [FC EQUIP GND LL. NBLK— 0-62 BL HKD BLK «-1 © уе боба YEL —7818 YEL LEN BLU 36 NI BLU BLU «CD BLU—— BLK] EL orc BL SH HID < BLK T YEL EH HI— YEL OFHI BLU BLU BLK YEL OF M2 7 BLU BLU ve 230V , ! oR YEL-9— BLU LOM ORN | BLK YEL ELK— 2H H1)-erN-0—ELk Fig. 39 — Typical Wiring Schematic (48TJ020-028 Shown) 27 L2 3 WIRE COM BUS TO OTHER COMMUNICATING | | | | | | | | | | | THERMOSTATS | | | | | | | | | | | | HR2 GHKD)——— ten PL1-11 Г e FACTORY ONLY | | | | Od TU de CRD 24VAC — ——|— (COMMON) 24 VAC (R) LOAD IS 1 AMP AT 24 VI(SEE NOTE 4) | | | TSR-0t RELAY PACK (MAXIMUM CONTACT | | | (NOTE 3) | (OTE 6) ALI-9 PL16 | — — — a PM ECONOMIZER OPTION/ACCESSORY RESISTOR CLS Oe WT PK Нет » » MIXED AIR SENSOR TOR SEQUENCE CHART 0 0 2 HIN > 30 SEC 90-150 secta | [490-150 SEC | (BLACK DENOTES CLOSED CONTACTS) I | Fig. 39 — Typical Wiring Schematic (48TJ020-028 Shown) (cont) ON y OFF 28 CONTROL BOX ес! | OL 80% Го а] о [об DOS (0) 00| С 0 О DOM CLO 1 cLO 2 DM Do DO DO ( | D © O oD | | ate | | aie ero © o al oca lios D @ Y DI @ QD Y | @ DD a ey a т © (108 e-vEL+—COM — (OH # 4 e-oRN-—230 TRANI| cry @-RED{— 208 YEL —Aikj-460 G9) Ч те! I | ' | , IT EQUIP GND + + Хх Ny 6 i | ORO I ) | ! 1 [FCB ! I Fi | ! 1 TB2 €) SD N pa {R] M1] M2] (61 [3 X | i y LL. ИЕ FIELD POWER WIRING FIELD CONTROL WIRING 1 11 PL1-R CD io! я \ 3 DISCONNECT PER NEC I 6566 Ce enn a {0 © С) GRN-YELY En © MILE) - DO E © COMP e= EAT Ая 1 182 GAS SECTION ey EY @ ® ® D ‘= © æ En ps @O ® {В © & т GRN-YEL кн GRN-YEL | Ey ® © BLU oO LS1 © BLK ? 7 RS E m © o o ECONOMIZER OPTION/ACCESSORY PGV2 6 9, o PLI-R вск PEN ai DM BLU + OD F y L lp À [900] | fura ET DOS о 7 O æ® RESISTOR av+—— YN , La | E UR) PNK, - MAT RA] T1 i 8) = = = co PNK | —_ ми — Г} рн ня 1 Fig. 40 — Typical Component Arrangement (48TJ020-028 Shown) 29 PACKAGED SERVICE TRAINING equipment discussed in this manual. Product programs cover: ® Unit Familiarization e Maintenance e Installation Overview e Operating Sequence Our packaged service training programs provide an excellent way to increase your knowledge of the ® A large selection of product, theory, and skills programs is available. All programs include a video cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training sessions. For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are included. wt Copyright 1994 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book | 1 PC 111 Catalog No. 564-836 Printed in U.S A. Form 48TJ-7SI Pg 30 4-94 Replaces: 48TJ-2SI Tab Ha START-UP CHECKLIST MODEL NO.: SERIAL NO.: DATE: TECHNICIAN: PRE-START-UP: [] VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT [] REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTRUCTIONS [] VERIFY INSTALLATION OF ECONOMIZER HOOD [] VERIFY INSTALLATION OF EXHAUST HOOD [] VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS [] VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT [| CHECK GAS PIPING FOR LEAKS [] CHECK THAT INDOOR-AIR FILTER IS CLEAN AND IN PLACE [] VERIFY THAT UNIT IS LEVEL [] CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SETSCREW IS TIGHT [] VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED START-UP ELECTRICAL SUPPLY VOLTAGE 11-12 L2-L3 L3-L1 COMPRESSOR AMPS — COMPRESSOR NO. 1 Ll L2 L3 — COMPRESSOR NO. 2 LI L2 L3 SUPPLY FAN AMPS EXHAUST FAN AMPS TEMPERATURES OUTDOOR-AIR TEMPERATURE F DB (Dry Bulb) RETURN-AIR TEMPERATURE F DB Е WB (Wet Bulb) COOLING SUPPLY AIR в GAS HEAT SUPPLY AIR LF PRESSURES GAS INLET PRESSURE IN. WG GAS MANIFOLD PRESSURE STAGE NO. | IN. WG STAGE NO. 2 IN. WG REFRIGERANT SUCTION CIRCUIT NO. 1 PSIG CIRCUIT NO. 2 PSIG REFRIGERANT DISCHARGE CIRCUIT NO. 1 PSIG CIRCUIT NO. 2 PSIG [] VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGES 23 AND 24 GENERAL [] ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS Copyright 1994 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book|1 PC 111 Catalog No 564-836 Printed in U.S.A Form 48TJ-7SI CL-1 4-94 Replaces: 48TJ-2S1 Tab a 1 $ 1 1 1 CUT ALO " - - - - - - Г] - - - - = - - = - - - - - - - - - - - - - - - - - - A
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement