Concepts Serving Systems Use & Care Manual

Concepts Serving Systems Use & Care Manual
Concepts Serving Systems
Use & Care Manual
Please read this manual completely before attempting to install or operate this equipment!
Notify carrier of damage! Inspect all components immediately. See page 2.
ATION
M
R
O
F
NT IN
A
T
R
O
P
USE
IM
E
R
O
F
E
NS!
O
I
T
C
U
READ B
INSTR
E
S
E
H
VE T
A
S
E
S
PLEA
March 2011
Concepts Use & Care Manual
Important Warning And Safety Information
WARNING Read This Manual Thoroughly Before Operating, Installing, Or Performing
Maintenance On The Equipment.
WARNING Failure To Follow Instructions In This Manual Can Cause Property Damage,
Injury Or Death.
WARNING Do Not Store Or Use Gasoline Or Other Flammable Vapors Or Liquids In The
Vicinity Of This Or Any Other Appliance.
WARNING Unless All Cover And Access Panels Are In Place And Properly Secured, Do
Not Operate This Equipment.
WARNING Do Not Clean With Water Jet.
CAUTION Observe the following:
• Minimum clearances must be maintained from all walls and combustible
materials.
• Keep the equipment area free and clear of combustible material.
• Adequate clearance for air openings.
• Operate equipment only on the type of electricity indicated on the
specification plate.
• Retain this manual for future reference.
2
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Concepts Use & Care Manual
Contents
Serial Number Information
Receiving & Inspecting The Equipment...............................................4
Specifications..................................................................................... 5-9
If your unit is heated, the serial tag is located above the louvered panel
near the on/off switch.
Refrigerated units have the serial tag located in the compressor
area near the on/off switch.
Operation
Heated Units....................................................................................10
Mechanically Cooled Serving Counters..........................................10
LiquiTec Units...................................................................................11
Frost Top Serving Counters.............................................................11
Mobile Hand Sink.............................................................................12
Tower Module...................................................................................12
Maintenance........................................................................................13
Understorage units often have the serial tag located on the left
inside the storage area.
All purpose counters, utility equipment or delivery carts do not
require serial numbers but a model tag is placed at the top of the
pylon on the back of the unit.
Always have the serial number of your unit available when
calling for parts or service.
This manual covers standard units only. If you have a custom unit,
consult the customer service department at the number listed below.
Wiring Diagrams
Heated Serving Counter..................................................................14
Mechanically Cooled Serving Counter............................................15
LiquiTec Units...................................................................................15
Frost Top Serving Counters.............................................................15
Tower Module...................................................................................16
Mobile Hand Sink.............................................................................16
Replacement Parts List................................................................. 17-19
Standard Labor Guidelines.................................................................20
Standard Warranty........................................................................ 21-22
Notes....................................................................................................23
©2011 The Delfield Company. All rights reserved. Reproduction without written
permission is prohibited.
“Delfield” is a registered trademarks of The Delfield Company.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
3
Concepts Use & Care Manual
Receiving And Inspecting The Equipment
Even though most equipment is shipped crated, care should be
taken during unloading so the equipment is not damaged while
being moved into the building.
1. Visually inspect the exterior of the package and skid or
container. Any damage should be noted and reported to the
delivering carrier immediately.
The units with LiquiTec technology cold pans contain a
non-toxic eutectic fluid within a sealed inner liner. This
fluid may leak if the tank is punctured so care must be
taken when uncrating and setting in place. The eutectic
fluid is non-toxic and may be flushed down a disposal
drain. If the LiquiTec unit cold pans leak, immediately
call the Delfield service department directly at 1-800-7338821 not your local service agent.
2. If damaged, open and inspect the contents with the carrier.
3. In the event that the exterior is not damaged, yet upon
opening, there is concealed damage to the equipment notify
the carrier. Notification should be made verbally as well as
in written form.
4. Request an inspection by the shipping company of the
damaged equipment. This should be done within 10 days
from receipt of the equipment.
Uncrating the Equipment
First cut and remove the banding from around the crate. Remove
the front of the crate material, use of some tools will be required. If
the unit is on legs remove the top of the crate as well and lift the unit
off the skid. If the unit is on casters it can be "rolled" off the skid.
5. Check the lower portion of the unit to be sure legs or casters
are not bent.
6. Also open the compressor compartment housing and visually
inspect the refrigeration package. Be sure lines are secure
and base is still intact.
7. Freight carriers can supply the necessary damage forms upon
request.
8. Retain all crating material until an inspection has been made
or waived.
4
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Concepts Use & Care Manual
Specifications
This manual covers standard units only. If you have a custom unit, consult the customer service department at the number listed below.
Cashier Counter
Model
Length
Width
Height
Ship Weight
DCCS-SD
45.00”
36.00”
36.00”
270lbs/122kg
DCCS-SDW
45.00”
54.00”
36.00”
320lbs/145kg
DCCS-SDWL
45.00”
54.00”
36.00”
295lbs/134kg
DCCS-SDWR
45.00”
54.00”
36.00”
295lbs/134kg
DCCS-DD
72.00”
36.00”
36.00”
540lbs/245kg
DCCS-DDW
72.00”
54.00”
36.00”
590lbs/268kg
DCCS-DDWL
72.00”
54.00”
36.00”
565lbs/256kg
DCCS-DDWR
72.00”
54.00”
36.00”
565lbs/256kg
FlexiShield™ Food Shields
Radial Glass Front, Single Tier with Glass Shelf, Single Service, Inside & Outside
L
W
H
Ship Weight
L
W
H
Ship Weight
DCFSRIG-2
Model
38.47”
18.00”
18.00”
Contact Factory
DCFSROG-2
Model
43.09”
18.00”
18.00”
Contact Factory
DCFSRIG-3
53.43”
18.00”
18.00”
Contact Factory
DCFSROG-3
59.85”
18.00”
18.00”
Contact Factory
DCFSRIG-4
68.17”
18.00”
18.00”
Contact Factory
DCFSROG-4
76.35”
18.00”
18.00”
Contact Factory
DCFSRIG-5
82.61”
18.00”
18.00”
Contact Factory
DCFSROG-5
92.53”
18.00”
18.00”
Contact Factory
FlexiShield™ Food Shields
Radial Single Tier, Fixed Sneeze Guard Front, Dual Service
Model
L
W
H
Ship Weight
DCFSRKD-2
40.78”
35.50”
14.75”
Contact Factory
DCFSRKD-3
56.64”
35.50”
14.75”
Contact Factory
DCFSRKD-4
72.26”
35.50”
14.75”
Contact Factory
DCFSRKD-5
87.57”
35.50”
14.75”
Contact Factory
FlexiShield™ Food Shields
Radial Single Tier, Fixed Sneeze Guard Front, Single Service, Inside & Outside
Model
DCFSRIKS-2
L
W
H
Ship Weight
38.47”
18.00”
14.75”
Contact Factory
Model
DCFSROKS-2
L
W
H
Ship Weight
43.09”
18.00”
14.75”
Contact Factory
DCFSRIKS-3
53.43”
18.00”
14.75”
Contact Factory
DCFSROKS-3
59.85”
18.00”
14.75”
Contact Factory
DCFSRIKS-4
68.17”
18.00”
14.75”
Contact Factory
DCFSROKS-4
76.35”
18.00”
14.75”
Contact Factory
DCFSRIKS-5
82.61”
18.00”
14.75”
Contact Factory
DCFSROKS-5
92.53”
18.00”
14.75”
Contact Factory
Utility Serving Counter Specifications
Model
Length
Depth
Height
Ship Weight
Model
Length
Depth
Height
Ship Weight
DCBU-38
38.00”
36.00”
36.00”
171lbs/78kg
DCBU-T38
38.00”
36.00”
36.00”
171lbs/78kg
DCBU-52
52.00”
36.00”
36.00”
234lbs/106kg
DCBU-T52
52.00”
36.00”
36.00”
234lbs/106kg
DCBU-66
66.00”
36.00”
36.00”
297lbs/135kg
DCBU-T66
66.00”
36.00”
36.00”
297lbs/135kg
DCBU-80
80.00”
36.00”
36.00”
360lbs/163kg
DCBU-T80
80.00”
36.00”
36.00”
360lbs/163kg
DCBU-94
94.00”
36.00”
36.00”
423lbs/192kg
DCBU-T94
94.00”
36.00”
36.00”
423lbs/192kg
DCBU-120
120.00”
36.00”
36.00”
540lbs/245kg
DCBU-T120
120.00”
36.00”
36.00”
540lbs/245kg
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
5
Concepts Use & Care Manual
Specifications, continued
Self-Contained Frost Top Serving Counter
Model
Length
Depth
Height
h.p.
V/Hz/Ph
Amps
Ship Weight
DC-FT2
38.00”
36.00”
36.00”
1/4
115/60/1
7.5
399lbs/181kg
DC-FT3
52.00”
36.00”
36.00”
1/4
115/60/1
7.5
546lbs/248kg
DC-FT4
66.00”
36.00”
36.00”
1/4
115/60/1
7.5
693lbs/314kg
DC-FT5
80.00”
36.00”
36.00”
1/4
115/60/1
7.5
840lbs/381kg
DC-FT6
94.00”
36.00”
36.00”
1/3
115/60/1
8.0
987lbs/448kg
Heated Serving Counter
Model
Length
Depth
Height
Watts
# of 12x20
Pans Held
V/Hz/Ph
Amps
Ship Weight
DC-H2
38.00”
36.00”
36.00”
2000
2
115/60/1
16.6
228lbs/103kg
DC-H3
52.00”
36.00”
36.00”
3000/4000
3
208-230/60/1
15.0/16.0
312lbs/142kg
DC-H4
66.00”
36.00”
36.00”
4000/4800
4
208-230/60/1
20.0/22.0
396lbs/180kg
DC-H5
80.00”
36.00”
36.00”
5000/6000
5
208-230/60/1
24.0/27.0
480lbs/218kg
DC-H6
94.00”
36.00”
36.00”
6000/7200
6
208-230/60/1
29.0/32.0
564lbs/256kg
Ice Cooled Serving Counter
Model
Length
Depth
Height
# of 12x20
Pans Held
Ship Weight
DC-IC2
38.00”
36.00”
36.00”
2
209lbs/95kg
DC-IC3
52.00”
36.00”
36.00”
3
286lbs/130kg
DC-IC4
66.00”
36.00”
36.00”
4
363lbs/165kg
DC-IC5
80.00”
36.00”
36.00”
5
440lbs/200kg
DC-IC6
94.00”
36.00”
36.00”
6
517lbs/235kg
Self-Contained LiquiTec® Cold Pan Serving Counter
Model
Length
Depth
Height
# of 12x20
Pans Held
H.P.
V/Hz/Ph
Amps
BTU
Ship Weight
DC-L2
38.00”
36.00”
36.00”
2
1/4
115/60/1
7.5
379
342lbs/155kg
DC-L3
52.00”
36.00”
36.00”
3
1/4
115/60/1
7.5
569
468lbs/212kg
DC-L4
66.00”
36.00”
36.00”
4
1/4
115/60/1
7.5
758
594lbs/269kg
DC-L5
80.00”
36.00”
36.00”
5
1/4
115/60/1
7.5
948
720lbs/327kg
DC-L6
94.00”
36.00”
36.00”
6
1/4
115/60/1
7.5
1138
846lbs/384kg
Self-Contained Mechanically Cooled Serving Counter
Model
Length
Depth
Height
# of 12x20
Pans Held
h.p.
V/Hz/Ph
Amps
BTU Load
Ship Weight
DC-MC2
38.00”
36.00”
36.00”
2
1/4
115/60/1
7.5
379
323lbs/147kg
DC-MC3
52.00”
36.00”
36.00”
3
1/4
115/60/1
7.5
569
442lbs/200kg
DC-MC4
66.00”
36.00”
36.00”
4
1/4
115/60/1
7.5
758
561lbs/254kg
DC-MC5
80.00”
36.00”
36.00”
5
1/4
115/60/1
7.5
948
680lbs/308kg
DC-MC6
94.00”
36.00”
36.00”
6
1/3
115/60/1
8.0
1138
799lbs/362kg
6
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Concepts Use & Care Manual
Specifications, continued
Radial Utility Serving Counter
Model
Length
DCRU-O
103.32”
DCRU-I
103.32”
DCRU-OT
103.32”
DCRU-IT
103.32”
Depth
36.00”
36.00”
36.00”
36.00”
Height
36.00”
36.00”
36.00”
36.00”
Ship Weight
464lbs/210kg
464lbs/210kg
464lbs/210kg
464lbs/210kg
Radial Heated Serving Counter
Model
Length
Depth
Height
Watts
DCRU-H225
DCRU-H332
DCRU-H440
DCRU-H2
DCRU-H3
DCRU-H4
DCRU-H5
58.44”
75.55”
92.35”
103.32”
103.32”
103.32”
103.32”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
2000
3000/4000
4000/4800
2000
3000/4000
4000/4800
5000/6000
# of 12x20
Pans Held
2
3
4
2
3
4
5
V/Hz/Ph
Amps
Ship Weight
115/60/1
208-230/60/1
208-230/60/1
115/60/1
208-230/60/1
208-230/60/1
208-230/60/1
16.6
15.0/16.0
20.0/22.0
16.6
15.0/16.0
20.0/22.0
24.0/27.0
369lbs/167kg
485lbs/220kg
601lbs/273kg
563lbs/255kg
604lbs/274kg
645lbs/293kg
685lbs/311kg
Radial Ice Cooled Serving Counter
Model
Length
Depth
Height
DCRU-IC225
DCRU-IC332
DCRU-IC440
DCRU-IC2
DCRU-IC3
DCRU-IC4
DCRU-IC5
58.44”
75.55”
92.35”
103.32”
103.32”
103.32”
103.32”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
# of 12x20
Pans Held
2
3
4
2
3
4
5
Radial Self-Contained LiquiTec® Cold Pan Serving Counter
# of 12x20
Model
Length
Depth
Height
Pans Held
DCRU-L1
103.32”
36.00”
36.00”
1
DCRU-L2
103.32”
36.00”
36.00”
2
DCRU-L3
103.32”
36.00”
36.00”
3
DCRU-L4
103.32”
36.00”
36.00”
4
Radial Self-Contained Mechanically Cooled Serving Counter
# of 12x20
Model
Length
Depth
Height
Pans Held
DCRU-MC225
58.44”
36.00”
36.00”
2
DCRU-MC332
75.55”
36.00”
36.00”
3
DCRU-MC440
92.35”
36.00”
36.00”
4
DCRU-MC2
103.32”
36.00”
36.00”
2
DCRU-MC3
103.32”
36.00”
36.00”
3
DCRU-MC4
103.32”
36.00”
36.00”
4
DCRU-MC5
103.32”
36.00”
36.00”
5
Ship Weight
369lbs/167kg
485lbs/220kg
601lbs/273kg
540lbs/245kg
578lbs/262kg
616lbs/279kg
654lbs/297kg
H.P.
V/Hz/Ph
Amps
BTU
Ship Weight
1/4
1/4
1/4, 1/4
1/4, 1/4
115/60/1
115/60/1
115/60/1
115/60/1
7.5
7.5
7.5/7.5
7.5/7.5
292
379
292/379
379/379
633lbs/287kg
679lbs/308kg
848lbs/385kg
894lbs/406kg
h.p.
V/Hz/Ph
Amps
BTU Load
Ship Weight
1/4
1/4
1/4
1/4
1/4
1/4
1/4
115/60/1
115/60/1
115/60/1
115/60/1
115/60/1
115/60/1
115/60/1
7.5
7.5
7.5
7.5
7.5
7.5
7.5
379
569
758
379
569
758
948
410lbs/186kg
525lbs/238kg
640lbs/290kg
604lbs/274kg
644lbs/292kg
684lbs/310kg
724lbs/328kg
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
7
Concepts Use & Care Manual
Specifications, continued
Transition Counters
Model
DC-T22
DC-T45
DC-T90
DC-TT45
DC-TT90
DCRU-T22
DCRU-T45
DCRU-T90
DCRU-TT45
DCRU-TT90
Length
25.81”
38.64”
59.40”
38.64”
59.40”
18.92”
37.12”
68.59”
37.12”
68.59”
Depth
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
Height
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
36.00”
Ship Weight
86lbs/39kg
171lbs/78kg
315lbs/143kg
171lbs/78kg
315lbs/143kg
86lbs/39kg
171lbs/78kg
315lbs/143kg
171lbs/78kg
315lbs/143kg
Beverage Bar Specifications
Model
DCBC-48R
Length
Depth
Height
Ship Weight
48”
44”
36”
397lbs/180kg
DCBC-72R
72”
44”
36”
460lbs/209kg
DCBC-96R
96”
44”
36”
523lbs/237kg
DCBC-120R
120”
44”
36”
640lbs/290kg
Curved Utility Counter Specifications
Model
Length
Depth
Height
Ship Weight
DCBU-48R
48.00”
44”
36.00”
297lbs/135kg
DCBU-72R
72.00”
44”
36.00”
360lbs/163kg
DCBU-96R
96.00”
44”
36.00”
423lbs/192kg
DCBU-120R
120.00”
44”
36.00”
540lbs/245kg
Radial Cashier Station Specifications
Model
Length
Depth
Height
Ship Weight
DCCS-SDR
45.00”
44.00”
36.00”
310lbs/141kg
DCCS-SDRW
45.00”
54.00”
36.00”
390lbs/177kg
DCCS-SDRWL
45.00”
54.00”
36.00”
350lbs/159kg
DCCS-SDRWR
45.00”
54.00”
36.00”
350lbs/159kg
DCCS-DDR
72.00”
44.00”
36.00”
580lbs/263kg
DCCS-DDRW
72.00”
54.00”
36.00”
660lbs/299kg
DCCS-DDRWL
72.00”
54.00”
36.00”
620lbs/281kg
DCCS-DDRWR
72.00”
54.00”
36.00”
620lbs/281kg
Display Merchandiser Specifications
Model
Length
Depth
Height
Ship Weight
DCDM-24
24.00”
20.00”
36.00”
150lbs/68kg
DCDM-36
36.00”
20.00”
36.00”
125lbs/57kg
8
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Concepts Use & Care Manual
Specifications, continued
Overshelf, Radial Front Specifications
Model
L
W
H
Ship Weight
DCFSCR
24.00” (61cm)
24.00” (61cm)
16.00” (41cm)
Contact factory
DCFSCRD
24.00” (61cm)
24.00” (61cm)
26.00” (66cm)
Contact factory
DCFSOS-XX
XX”
18.00” (46cm)
16.00” (41cm)
Contact factory
DCFSOS2-XX
XX”
18.00” (46cm)
26.00” (66cm)
Contact factory
Handsink Modules Specifications
Model
Length
Depth
Height
V/Hz/Ph
Amps
Ship Weight
DCHS-DI
51.00”
36.00”
36.00”
120/60/1
15
220lbs/100kg
DCHS-51
36.13”
28.00”
22.00”
120/60/1
15
454lbs/206kg
Radial Counters Specifications
Model
Length
Depth
Height
Ship Weight
DCRU-T25
58.44”
36.00”
36.00”
270lbs/122kg
DCRU-T32
75.55”
36.00”
36.00”
345lbs/156kg
DCRU-T40
92.35”
36.00”
36.00”
420lbs/191kg
DCRUO-TT25
58.44”
36.00”
36.00”
270lbs/122kg
DCRUO-TT32
75.55”
36.00”
36.00”
345lbs/156kg
DCRUO-TT40
92.35”
36.00”
36.00”
420lbs/191kg
DCRUI-TT25
58.44”
36.00”
36.00”
270lbs/122kg
DCRUI-TT32
75.55”
36.00”
36.00”
345lbs/156kg
DCRUI-TT40
92.35”
36.00”
36.00”
420lbs/191kg
Tower Module Specifications
Model
Length
Depth
Height
Ship Weight
DCTM-38RI
38.00”
36.00”
83.62”
516lbs/234kg
DCTM-66RI
66.00”
36.00”
83.62”
774lbs/351kg
DCTM-RI
30”-72”
36.00”
83.62”
Contact factory
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
9
Concepts Use & Care Manual
Operation: Heated Units
After plugging in the power supply cord, select desired temperature
by rotating the knob on the temperature control panel. Indicator light
will come on when the switch is activated. Individual temperature
control knobs and indicator lights are provided for each heated food
well.
Before the unit is used the first time for serving:
•
Turn the temperature knob to “10” and heat the well for 15
minutes. Do not be alarmed if smoke appears; this preheat
should burn off any residue or dust that has adhered to the
food well element
If the same temperature settings for each well are used every day,
the temperature knobs can be left in their set position and the wells
can be turned off using the ON/OFF switch at the end of the control
panel.
When serving thick sauces always use the hot food well in “wet”
operation. This provides more uniform temperature for the sauce.
Product temperature should range from 140˚F to 160˚F
Never place food directly in well. Always use pans.
For most efficient operation, keep empty inset pans empty and
covered during preheating and when the well is not in use.
Always place covers on pans when not serving to prevent food from
drying out and to reduce your operating costs.
Wet operation
Fill the food well with about two inches of hot water and cover
with lid or empty pan. To bring water to highest temperature, set
temperature control at “High”. With pans in place, wells will boil
water. Food temperature will vary depending on type and amount of
product. To minimize steam and water usage, set control to lowest
setting that will maintain proper food temperature.
team can cause serious burns. Always wear some
S
type of protective covering on your hands and arms
when removing lids from the unit. Lift the lid in a way
that will direct escaping steam away from your face
and body. Water temperature will average 180˚F.
Dry operation
Wet operation is usually much more efficient and is usually
preferred. However, these units may be operated without water with
no damage to the unit.
he dry well should never be preheated longer than
T
15 minutes. Only 6” deep pans should be used with
dry food wells.
hen operated dry, the well bottoms become very
W
hot. Do not allow unprotected skin to contact any
well surface.
When operated dry, the bottom of the well will discolor. To clean, use
a stainless steel cleaner or mild abrasive.
Operation of optional heated understorage
Preheat the heated understorage to desired temperature.
Temperature range of understorage is 80°F to 190°F. The
temperature control knob is always the far left knob on the panel.
Indicator light is also at the far left.
Operation: Mechanically Cooled Serving Counters
Mechanically cooled cold pans are adjusted at the factory to provide
proper operation without any further adjustments. However, if it is
necessary to adjust the temperature, the control is located in the
machine compartment. Turn the knob clockwise as indicated on the
control. Settings are from 1 thru 7, 7 being the coldest. Adjustments
should be made gradually. Several small adjustments will be more
effective than one large adjustment. It may take an hour or longer
to realize the temperature change depending on the application and
location of the unit.
Warming of food product can occur very quickly outside of the unit.
When loading or rotating product, avoid leaving food items in a nonrefrigerated location for any length of time to prevent warming or
spoilage.
Turn the cold pan on an hour or longer before loading product to
achieve the desired temperature.
These units are not designed to be used with ice. If the cold pan is
to be used with ice, it is recommended that the optional perforated
bottoms be used. These will allow ice to melt properly.
These units are not designed to cool warm food products. Items
should be placed in the unit pre-cooled at least to the desired holding
temperature, if not slightly colder. In some applications, a gradual
warming of product may occur, particularly at the exposed top of
the product. Stirring or rotation of the product may be necessary to
maintain overall temperature.
10
The temperature control is used to turn the unit on and off as well as
control the temperature of the cold pan. The settings range from 1
through 7, 7 being the coldest. To turn the cold pan off, turn the knob
to the off position.
The unit must be turned off when not in use or overnight for defrosting
and cleaning.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Concepts Use & Care Manual
Operation: LiquiTec Units
There is a switch on the compressor housing front to turn the units
on and off. LiquiTec Series cold pans are adjusted at the factory to
provide proper operation without any further adjustments. However,
if it is necessary to adjust the temperature, the control is located in
the machine compartment. Turn the knob clockwise as indicated on
the control to adjust it colder. Adjustments should be made gradually.
Several small adjustments will be more effective than one large
adjustment. It may take an hour or longer to realize the temperature
change depending on the application and location of the unit.
Turn the cold pan on an hour or longer before loading product to
achieve the desired temperature.
The cold pan is not intended to be used with ice.
The unit must be turned off when not in use or overnight for defrosting
and cleaning.
Temperature Control Settings:
17°F (8ºC) differential
25°F (-4ºC) cut-in
8°F (-13ºC) cut-out
These units are not designed to cool warm food products. Items
should be placed in the unit pre-cooled at least to the desired holding
temperature, if not slightly colder. In some applications, a gradual
warming of product may occur, particularly at the exposed top of the
products. Stirring or rotation of the product may be necessary to
maintain overall temperature. Warming of food product can occur very
quickly outside of the unit. When loading or rotating the product, avoid
leaving food items in a non-refrigerated location for any length of time
to prevent warming or spoilage.
Operation: Frost Top Serving Counters
Frost tops are designed to maintain an even layer of frost to
pleasantly display product. Once turned on, the compressor will run
continuously. The unit should be turned off overnight or when not in
use. There is no temperature control on the frost top series. The
ON/OFF switch is the only means available to cycle the unit.
Product should not be placed on the frost top prior to turning the unit
on, because it may freeze to the surface of the unit.
The unit must be turned off when not in use or overnight for defrosting
and cleaning.
Since it takes time for the frost to accumulate initially, the unit should
be turned on approximately one hour before it is actually required.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
11
Concepts Use & Care Manual
Operation: Mobile Hand Sink
The hand sink is to be used for hand washing only,
not for consumption.
Hot water heater MUST be filled with water before
connecting the water heater to power to prevent
damage to the heater.
The fresh water and waste water containers are located in the base
of the sink compartment on the right. The fresh water containers are
on the left with clear vinyl tubing and waste water tanks are on the
right with a rigid drain tube. Two fresh water and two waste water
containers are provided with each unit.
To add water to the fresh water container, remove the cap the vinyl
tubing is connected to on the container by pressing the button on the
cap and pull out the cap from the container. Pull the container out
of the sink base and unscrew the cap of the fill access hole at the
back of the container. Fill the container with water and screw the cap
back on at the back of the container and push the cap with the vinyl
tubing back into place at the front. Make sure there are no kinks in
the clear vinyl tubing.
To fill the water heater with water, turn on the hot water handle on the
faucet until water flows. When water flows into the sink, the water
heater is filled with water. The water heater can now be plugged
into the GFCI. Verify the water heater power switch on the front of
the heater is ON. The red light on the switch will stay on until it has
reached the set temperature.
Changing containers:
To switch out the waste water containers, get as much residual water
out of the drain into the container before removing. Lift the black
elbow out of the container and pull part of the drain line through the
hole in the compartment center divider to create an elbow in the
drain line to prevent water from draining out while switching out the
containers. When the empty container is in place, pull the drain line
back through the center divider and put the black elbow into the hole
in the container.
To prevent waste water overflow:
• Switch the fresh water and waste water containers at the same
time.
• Do not pour excess liquids into the sink
Verify the black waste arm at the end of the drain line is in the hole
on the waste container.
To adjust the water temperature, refer to the water heater
manufacturer’s manual provided with the unit.
Before Operating The Sink:
The hot water heater and the water pump is on a sliding shelf. Use
the handle provided in the shelf slide it out to access the heater and
other components.
Water heater MUST be filled with water before connecting the water
heater to power to prevent damage to the heater.
Before plugging the sink into a wall receptacle, verify the water pump
only is plugged into the GFCI receptacle in the base of the unit. If the
water heater is plugged in, unplug it until the heater has been filled
with water. Put the switch and the breaker to the “ON” position in the
base of the unit. Make sure the GFCI receptacle is ON.
The soap dispenser container is located in the base of the unit. The
container is threaded into the soap dispenser pump. Liquid soap
only is to be used in the soap dispenser.
Operation: Tower Module
Verify the module is plugged into a receptacle and the Reach-In is
plugged into the GFCI receptacle. If lights were provided, turn on the
on /off switch on the back of the tower.
The flanged feet must be bolted to the floor.
12
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Concepts Use & Care Manual
Maintenance
Drain Maintenance - Base
Each unit has a drain located inside the unit that removes the
condensation from the evaporator coil and routes it to an external
condensate evaporator pan. Each drain can become loose or
disconnected during normal use. If you notice water accumulation
on the inside of the unit be sure the drain tube is connected to the
evaporator drain pan. If water is collecting underneath the unit make
sure the end of the drain tube is in the condensate evaporator in the
machine compartment. The leveling of the unit is important as the
units are designed to drain properly when level. Be sure all drain
lines are free of obstructions.
Caster Maintenance
Wipe casters with a damp cloth monthly to prevent corrosion.
The power switch must be turned to OFF and the
unit disconnected from the power source whenever
performing service, maintenance functions or cleaning
the refrigerated area.
Refrigerators and Freezers
The interior and exterior can be cleaned using soap and warm water.
If this isn’t sufficient, try ammonia and water or a nonabrasive liquid
cleaner. When cleaning the exterior, always rub with the “grain” of
the stainless steel to avoid marring the finish. Do not use an abrasive
cleaner because it will scratch the stainless steel and can damage
the breaker strips and gaskets.
Stainless Steel Care and Cleaning
To prevent discoloration or rust on stainless steel several important
steps need to be taken. First, we need to understand the properties
of stainless steel. Stainless steel contains 70- 80% iron, which will
rust. It also contains 12-30% chromium, which forms an invisible
passive film over the steel’s surface, which acts as a shield against
corrosion. As long as the protective layer is intact, the metal is still
stainless. If the film is broken or contaminated, outside elements
can begin to breakdown the steel and begin to form discoloration or
rust. Proper cleaning of stainless steel requires soft cloths or plastic
scouring pads.
NEVER USE STEEL PADS, WIRE BRUSHES OR SCRAPERS!
Cleaning solutions need to be alkaline based or non-chloride
cleaners. Any cleaner containing chlorides will damage the protective
film of the stainless steel. Chlorides are also commonly found in
hard water, salts, and household and industrial cleaners. If cleaners
containing chlorides are used be sure to rinse repeatedly and dry
thoroughly. Routine cleaning of stainless steel can be done with
soap and water. Extreme stains or grease should be cleaned with
a non-abrasive cleaner and plastic scrub pad. Always rub with the
grain of the steel. There are stainless steel cleaners available which
can restore and preserve the finish of the steels protective layer.
Early signs of stainless steel breakdown are small pits and cracks.
If this has begun, clean thoroughly and start to apply stainless steel
cleaners in attempt to restore the passivity of the steel.
Never use an acid based cleaning solution! Many
food products have an acidic content, which can
deteriorate the finish. Be sure to clean the stainless
steel surfaces of ALL food products. Common items
include, tomatoes, peppers and other vegetables.
Cleaning the Condenser Coil
In order to maintain proper refrigeration performance, the
condenser fins must be cleaned of dust, dirt and grease regularly.
It is recommended that this be done at least every three months.
If conditions are such that the condenser is totally blocked in three
months, the frequency of cleaning should be increased. Clean the
condenser with a vacuum cleaner or stiff brush. If extremely dirty, a
commercially available condenser cleaner may be required.
Failure to maintain a clean condenser coil can initially cause high
temperatures and excessive run times. Continuous operation with
a dirty or clogged condenser coil can result in compressor failure.
Neglecting the condenser coil cleaning procedures will void any
warranties associated with the compressor and cost to replace the
compressor.
Never use a high-pressure water wash for this
cleaning procedure as water can damage the electrical
components located near or at the condenser coil.
Preventing blower coil corrosion
To help prevent corrosion of the blower coil, store all acidic items,
such as pickles and tomatoes, in sealable containers. Immediately
wipe up all spills.
Units with pans should be operated with pans in place.
Operating the unit without all pans in place will lower
efficiency and may damage the unit.
Defrosting
Refrigerated cold pans and frost tops should be defrosted daily. On/
Off switch located above louver panel.
Never use sharp objects or tools to clean or scrape ice/frost
build up from the refrigerated cold pans or frost tops. A
puncture to the pan could cause irreparable damage to the
refrigeration system.
Units with a Eutectic Fluid Cold Pan require the same
precautions. The fluid is NOT refillable and loss of fluid due to
a puncture would cause irreparable damage.
Over shelves and other items mounted to the top of the counters
should never be installed in the field due to the potential damage to
the refrigeration system.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
13
Concepts Use & Care Manual
Wiring Diagram, Heated Serving Counter
PILOT LIGHT
(FURNISHED)
H1
1000 W - 120V
OR 1000/1222 W 208-230 V
HEATING ELEMENT
P
L1
L2
H2
LINE
WIRES
TO ADDITIONAL
FOOD WARMERS
INFINITE CONTROL
WITH “OFF”
POSITION
AMPERES IN LINE WIRES
# OF
WARMERS
1
120V,
1 PHASE
8.3
2
3
4
208V,
1 PHASE
4.8
230V,
1 PHASE
5.3
16.7
9.6
10.6
25
33.3
14.4
19.2
15.9
21.3
14.4/15.9
14.4/15.9
14.4/15.9
19.2/21.3
19.2/21.3
14.4/15.9
5
24
26.6
19.2/21.3
28.8
31.3
24/26.1
28.8/31.3
19.2/21.3
6
28.8/31.3
28.8/31.3
L1
G
L1
208-230V, 3 PHASE
L2
L3
L2
30A SWITCH
(OPTIONAL)
L1
L2
G
L3
20A, 3–POLE SWITCH
(OPTIONAL)
HA–1
HA–1
HA–2
HA–2
ALL WIRING
MINIMUM 14 AWG
250C
HA–3
HA–3
HA–4
HA–4
HA–5
HA–5
HA–6
HA–6
HA = HEATER ASSEMBLY
Standard Single Phase
14
HA = HEATER ASSEMBLY
Optional Three Phase
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Concepts Use & Care Manual
Wiring Diagram, Self-Contained Mechanically Cooled Serving Counter
CONDENSER FAN
S
C
L1
COOLING T'STAT
R
COMPRESSOR
115V
N
G
Wiring Diagram, Self-Contained LiquiTec® Cold Pan Serving Counter
CONDENSER FAN
S
C
ON/OFF SWITCH
L1
COOLING T'STAT
R
COMPRESSOR
120V
N
G
Wiring Diagram, Self-Contained Frost Top Serving Counter
ON/OFF SWITCH
L1
CONDENSER FAN
S
C
R
COMPRESSOR
115V
N
G
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
15
Concepts Use & Care Manual
Wiring Diagram, Tower Module
Wiring Diagram, Mobile Hand Sink
16
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Concepts Use & Care Manual
Replacement Parts
Sink Assembly
Key Part No.
1
2194099
2
3235056
3
1701410
4
1701413
5
9324097
6
1701411
7
1702078
8
1701418
9
1701417
10
3235051
11
3235050
12
1701416
13
1701415
14
2194328
15
1701414
16
3545340
17
3235053
18
3545343
19
3545341
20
1701412
21
3545344
3235054
3235500
3234902
3234783
3234156
2183348
2193450
3234077
3234067
2194443
3235555
3235052
1
Description
Switch, SPST, 15 Amp
Soap Dispenser, Tough Guy
Waste Arm, Black ABS
Coupling, Colder
Clamp, Oetiker
Hose, NewFlex, 1.5”ID
Tubing, Vinyl, 1/2”ID x 3/4”OD
Container, Water, Waste
Container, Water, Fresh, 5
Pump, Water, Shurflo*
Heater, Water, Ariston*
Pipe, PVC, 3/4”
Elbow, PVC, 3/4”
Breaker
Adaptor, 3/4” MPT
Line, Supply, Water, 30” LG
Hammer, Water, 1/2M STR
Tee, Brass, 1/2” x 1/2” x 1/2”
Line, Supply, Water, 20”LG
Fitting, Elbow, Nylon
Elbow, Brass, 3/8”NPT-3/8”BPT
Aerator
Cap, Threaded, 1”, DC
Caster, 5”, Plate, swivel
Caster, 5”, Plate, swivel w/ brake
Catch, Magnetic, Snap-In
Cord, Lead, 16/3 W Nema 5-15P
Cover, Weather Proof
Faucet, Deck, FSHR#3510
Hinge, Flag
Receptacle, GFCI, 15Amp
Spacer, PNL Bolt Washer
Strainer, Sink, 2-1/2”
2
3
4
5
6
7
3
14
8
9
13
12
11
10
15
16
17
16
18
19
5
21
20
10
*Heater and pump warranty will be covered by
Delfield instead of OEM.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
17
Concepts Use & Care Manual
Replacement Parts, continued
Tower Module
3235500
Cap, Threaded, 1”
3234452
Flanged Food
2195286
Gooseneck light
2194444
Receptacle, GFCI 5-20R
2190154
Switch, Rocker 20A/125V, 15A, 250V
Beverage Module
3235500
Cap, Threaded, 1”
3234243
Door Hinge
3234272
Door Hinge Mounting Plate
3234645
Leg
DC-FT Frost Tops
3234156
*000-BN5-0030
3234067
3234645
000-585-0032
2194099
3516225
Catch, magnetic, snap-in
Condensing unit 1/4 hp
Hinge, flag
Leg
Louver assy, 18" Left hand
Switch, SPST 15A, Brown
Valve, expansion, 1/4, low
DC-IC Ice Cooled Counter
3234645
Leg
3234242
Plastic Drain, 1PS, 2.87Long
DC-L Liquitech
3234156
*000-BN5-0030
3234645
000-585-0032
2190154
000-282-0051
3516225
Catch, magnetic, snap-in
Condensing unit 1/4 hp
Leg
Louver access door Assy, 18", Left
Switch, rocker, 20A/125V,15A/250V
Tstat Assy, Danfoss
Valve, expansion, 1/4, low
DC-MC Mechanically cooled cold pan
*000-BN5-0030 Condensing unit 1/4 hp
3234645
Leg
000-585-0032
Louver access door Assy, 18", Left
2190154
Switch, rocker, 20A/125V, 15A/250V
2194201
Thermostat
3516225
Valve, expansion, 1/4, low
DC-H Heated Serving Counter
3234156
Catch, magnetic snap-in
3234572
3234075
3234645
2194095
000-585-0034
2194212
*0160193
Drain Screen
Faucet, hot food table
Leg
Light, pilot, 250V Amber
Louver assy, 18 x 11.75, left hand
Switch, 30A, 120/277V, DPST
Warmer, food, 208V, Infinite
Control, w/ drain
* Exploded view on next page.
18
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Concepts Use & Care Manual
Replacement Parts, continued
Key
1
2
3
4
5
6
7
8
1
2
Part No.
0160193
026-103-Z0006
3434663
2194335
3234557
2194110
0160014
2194007
026-061-0001-S
Description
Complete assembly, 208V, w/drain
Bottom cover
Insulation
Thermostat non-adjustable
Knob
Infinite control, 230V
Food well, with drain
Element, 208V
Deflector plate
8
3
7
2
3
4
1
6
5
5
4
6
7
Key
1
2
3
4
5
5
6
7
Part No.
000-BN5-0030
3516457
2160020
2162717
3526999
3516444
2194787
3516322
3516454
Description
Condensing Unit, 1/4HP
Fan Blade
Fan Guard
Fan Motor
Danfoss Compressor
Compressor Relay
Start Capacitor
Filter Drier
Condenser Coil
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
19
Concepts Use & Care Manual
Standard Labor Guidelines To Repair Or Replace Parts On Delfield Equipment
Advice and recommendations given by Delfield Service Technicians do not constitute or guarantee any special coverage.
•A maximum of 1-hour is allowed to diagnose a defective component.
•A maximum of 1-hour is allowed for retrieval of parts not in stock.
•A maximum travel distance of 100 miles round trip and 2-hours will be reimbursed.
•Overtime, installation/start-up, normal control adjustments, general maintenance, glass breakage, freight damage, and/or correcting and
end-user installation error will not be reimbursed under warranty unless pre-approved with a Service Work Authorization from Delfield.
You must submit the number with the service claim.
LABOR OF 1-HOUR IS ALLOWED TO REPLACE:
•Thermostat
•Infinite Switch
•Door Jamb Switch
•Solenoid Coil
•Hi-limit/Thermal Protector Switch
•Compressor Start Components and Overload Protector
•Defrost Timer
•Thermometer
•
•
•
•
•
•
•
•
Contactor/Relay
Transformer
Evaporator/Condenser Fan Motor and Blade
Circulating Fan Motor and Blade
Fan Delay/Defrost Termination Switch
Door Hinges, Locks, and Gaskets
Condensate Element
Springs/Lowerator
LABOR OF 2 HOURS TO REPLACE:
•Drawer Tracks/Cartridges
• Defrost Element
•Pressure Control
• Heating Element
•Solenoid Valve
• Locate/Repair Leak
LABOR OF 3 HOURS TO REPLACE:
•EPR or CPR Valve
• Condenser or Evaporator Coil
•Expansion Valve
LABOR OF 4 HOURS TO REPLACE
•Compressor
This includes recovery of refrigerant and leak check.
$55.00 maximum reimbursement for refrigerant recovery (includes recovery machine, pump, torch, oil, flux, minor fittings, solder, brazing
rod, nitrogen, or similar fees.)
REFRIGERANTS
•R22 A maximum of $4.00/lb. or 25¢/oz. will be reimbursed.
•R134A A maximum of $5.00/lb. or 31¢/oz. will be reimbursed.
•R404A A maximum of $15.00/lb. or $1.00/oz. will be reimbursed.
20
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Concepts Use & Care Manual
Standard One Year Warranty (One year parts and labor.)
The Delfield Company (“Delfield”) warrants to the Original
Purchaser of the Delfield product (herein called the “Unit”)
that such Unit, and all parts thereof, will be free from defects
in material and workmanship under normal use and service
for a period of one (1) year from the date of shipment of the
Unit to the Original Purchaser or, if the Original Purchaser
returns the warranty card completely filled out including the
date of installation within thirty (30) days of receipt of the
Unit, one (1) year from the date of installation. During this
one year warranty period, Delfield will repair or replace any
defective part or portion there of returned to Delfield by the
Original Purchaser which Delfield determines was defective
due to faulty material or workmanship. During this one year
warranty period, Delfield will pay labor, crating, and freight
incurred in the removal of the Unit of defective component
and shipment to Delfield. A maximum of 1-hour is allowed
to diagnose a defective component. A maximum of 1-hour
is allowed for retrieval of parts not in stock. A maximum
travel distance of 100 miles round trip and 2-hours will be
reimbursed. Overtime, installation/start-up, normal control
adjustments, general maintenance, glass breakage, freight
damage, and/or correcting and end-user installation error will
not be reimbursed under warranty unless pre-approved with a
Service Work Authorization from Delfield. Delfield will pay the
return costs if the Unit or part thereof was defective.
The term “Original Purchaser” as used herein means that
person, firm, association, or corporation for whom the Unit was
originally installed.
This warranty does not apply to any Unit or part thereof that
has been subjected to misuse, neglect, alteration, or accident,
such as accidental damage to the exterior finish, operated
contrary to the recommendations specified by Delfield; or
repaired or altered by anyone other than Delfield in any way
so as to, in Delfield’s sole judgement, affect its quality or
efficiency. This warranty does not apply to any Unit that has
been moved from the location where it was originally installed.
This warranty also does not cover the refrigerator drier or the
light bulbs used in the Unit. The warranty is subject to the
user’s normal maintenance and care responsibility as set forth
in the Service and Installation Manual, such as cleaning the
condenser coil, and is in lieu of all other obligations of Delfield.
Delfield neither assumes, nor authorizes any other person
to assume for Delfield, any other liability in connection with
Delfield’s products.
Removal or defacement of the original Serial Number or Model
Number from any Unit shall be deemed to release Delfield from
all obligations hereunder or any other obligations, express or
implied.
Parts furnished by suppliers to Delfield are guaranteed by
Delfield only to the extent of the original manufacturer’s
express warranty to Delfield. Failure of the Original Purchaser
to receive such manufacturer’s express warranty to Delfield.
Failure of the Original Purchaser to receive such manufacturers
warranty shall in no way create any warranty, expressed or
implied, or any other obligation or liability on Delfield’s part in
respect thereof.
If shipment of a replacement part is requested prior to the
arrival in the Delfield factory of the part claimed to be defective,
the Original Purchaser must accept delivery of the replacement
part of a C.O.D. basis, with credit being issued after the part
has been received and inspected at Delfield’s plant and
determined by Delfield to be within this warranty.
Under no condition does this warranty give the Original
Purchaser the right to replace the defective Unit with a complete
Unit of the same manufacturer or of another make. Unless
authorized by Delfield in writing, this warranty does not permit
the replacement of any part, including the motor-compressor,
to be made with the part of another make or manufacturer.
No claims can be made under this warranty for spoilage of any
products for any reason, including system failure.
The installation contractor shall be responsible for building
access, entrance and field conditions to insure sufficient
clearance to allow any hood(s), vent(s), or Unit(s) if necessary,
to be brought into the building. Delfield will not be responsible
for structural changes or damages incurred during installation
of the Unit or any exhaust system.
Delfield shall not be liable in any manner for any default or
delay in performance hereunder caused by or resulting from
any contingency beyond Delfield’s control, including, but not
limited to, war, governmental restrictions or restraints, strike,
lockouts, injunctions, fire, flood, acts of nature, short or reduced
supply of raw materials, or discontinuance of the parts by the
original part manufacturer.
Except as provided in any Additional Four Year Protection
Plan, if applicable, and the Service Labor Contract, if
applicable, the foregoing is exclusive and in lieu of all other
warranties, whether written or oral, express or implied. This
warranty supersedes and excludes any prior oral or written
representations or warranties. Delfield expressly disclaims any
implied warranties of merchantability, fitness for a particular
purpose of compliance with any law, treaty, rule or regulation
relating to the discharge of substances into the environment.
The sole and exclusive remedies of any person relating to
the Unit, and the full liability of Delfield for any breach of this
warranty, will be as provided in this warranty.
Other than this Delfield Standard One Year Limited Warranty,
any applicable Delfield Additional Four Year Protection Plan
or applicable Delfield Service Labor Contract, the Original
Purchaser agrees and acknowledges that no other warranties
are offered or provided in connection with or for the unit or any
other part thereof.
In no event will Delfield be liable for special, incidental or
consequential damages, or for damages in the nature of
penalties.
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
21
Concepts Use & Care Manual
Additional Four Year Protection Plan
(for Motor-Compressor only)
Delfield Model#
Serial #
Installation
Date
In addition to the Standard One Year Warranty on the Motor-Compressor
contained in the above listed Delfield product (the “Unit”), The Delfield
Company (“Delfield”) also agrees to repair, or exchange with similar or
interchangeable parts in design and capacity at Delfield’s option, the
defective Motor-Compressor contained in the Unit (the “Motor-Compressor),
or any part thereof, for the Original Purchaser only, at any time during the four
(4) years following the initial one (1) year period commencing on the date of
installation for the Original Purchaser. Failure of the Original Purchaser to
register the registration card containing the Original Purchasers name,
address, date of installation, model number and serial number of the
Unit containing the Motor-Compressor within 30 days from the date
of installation shall void this warranty. This additional warranty is only
available if the Motor-Compressor is inoperative due to defects in material
or factory workmanship, as determined by Delfield in its sole judgement
and discretion. The Original Purchaser shall be responsible for returning
the defective Motor-Compressor to Delfield prepaid, F.O.B. at the address
shown on the back cover of this manual.
The term “Original Purchaser” as used herein means that person, firm,
association, or corporation for whom the Unit was originally installed.
The term “Motor-Compressor” as used herein does not include unit base,
air or water cooled condenser, receiver, electrical accessories such as relay,
capacitors, refrigerant controls, or condenser fan/motor assembly. This
warranty does not cover labor charges incidental to the replacement of
parts. This warranty further does not include any equipment to which said
condensing unit is connected, such as cooling coils, temperature controls
or refrigerant metering devices. This warranty shall be void if the MotorCompressor, in Delfield’s sole judgement, has been subjected to misuse,
neglect, alteration or accident, operated contrary to the recommendations
specified by the Unit manufacturer, repaired or altered by anyone other than
Delfield in any way so as, in Delfield’s sole judgment, to affect its quality
or efficiency or if the serial number has been altered, defaced or removed. This Warranty does not apply to a Motor-Compressor in any Unit that has
been moved from the location where it was originally installed. The addition
of methyl chloride to the condensing unit or refrigeration system shall void
this warranty.
General Conditions
Delfield shall not be liable in any manner for any default or delay in
performance hereunder caused by or resulting from any contingency beyond
Delfield’s control, including, but not limited to, war, governmental restrictions
or restraints, strike, lockouts, injunctions, fire, flood, acts of nature, short or
reduced supply of raw materials, or discontinuance of any part or the MotorCompressor by the unit manufacturer.
Replacement of a defective Motor-Compressor is limited to one (1) MotorCompressor by us during the four (4) year period. Delfield shall replace the
Motor-Compressor at no charge.
This warranty does not give the Original Purchaser of the Motor-Compressor
the right to purchase a complete replacement Motor-Compressor of the
same make or of another make. It further does not permit the replacement
to be made with a Motor-Compressor of another kind unless authorized by
Delfield. In the event Delfield authorizes the Original Purchaser to purchase
a replacement Motor-Compressor locally, only the wholesale cost of the
Motor-Compressor is refundable.
Expressly excluded from this warranty are damages resulting from spoilage
of goods.
Except as provided in any applicable Standard One Year Limited
Warranty or applicable Service Labor Contract, the foregoing is
exclusive and in lieu of all other warranties, whether written or oral,
express or implied. This Warranty supersedes and excludes any
prior oral or written representations or warranties. Delfield expressly
disclaims any implied warranties of merchantability, fitness for a
particular purpose or compliance with any law, treaty, rule or regulation
relating to the Motor-Compressor, and the full liability of Delfield for
any breach of this warranty, will be as provided in this warranty.
Other than any applicable Delfield Standard One year Limited Warranty, this
Delfield Additional Four Year Protection Plan and any applicable Delfield
Service Labor Contract, the Original Purchaser agrees and acknowledges
that no other warranties are offered or provided in connection with or for the
Motor-Compressor or any part thereof.
In no event will Delfield be liable for special, incidental or consequential
damages, or for damages in the nature of penalties.
22
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
Concepts Use & Care Manual
Notes
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
23
Mt. Pleasant, MI
Covington, TN
Thank you for choosing Delfield!
Help is a phone call away. Help our team of professional, courteous
customer service reps by having your model number and serial number
available at the time of your call (800) 733-8829
Model:______________________________ S/N: ____________________________
Installation Date:______________________________
For a list of Delfield’s authorized parts depots,
visit our website at www.delfield.com
980 S. Isabella Rd., Mt. Pleasant, MI 48858, U.S.A. • (989) 773-7981 or (800) 733-8829 • Fax (989) 773-3210 • www.delfield.com
Delfield reserves the right to make changes in design or specifications without prior notice. ©2011 The Delfield Company. All rights reserved. Printed in the U.S.A.
DMConcepts 03/11
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement