advertisement
Room Air Conditioner
Service and Parts
Manual
115 Volts CP05N10
ZQ05C10:
Staring with serial number LFMK00059
CP05.Svc(05/07)
CONTENTS
1. PREFACE
...................................................................................................................................................3
1.1 FEATURES.....................................................................................................................................................3
1.2 SPECIFICATIONS .........................................................................................................................................3
1.3 LOCATIONS OF CONTROLS-CP
ATIONS OF CONTROLS-ZQ
1.4 SAFETY PRECAUTIONS ..............................................................................................................................5
1.5 INSULATION RESISTANCE TEST ................................................................................................................5
2. DISASSEMBLY INSTRUCTIONS
................................................................................................6
2.1 MECHANICAL PARTS ..................................................................................................................................6
2.1.1 FRONT GRILLE ....................................................................................................................................6
2.1.2 CABINET................................................................................................................................................6
2.1.3 CONTROL BOARD ................................................................................................................................6
2.2 AIR HANDLING PARTS ................................................................................................................................7
2.2.1 AIR GUIDE UPPER ..............................................................................................................................7
2.2.2 ORIFICE, TURBO FAN AND FAN .........................................................................................................7
2.2.3 MOTOR ..................................................................................................................................................8
2.2.4 AIR GUIDE.............................................................................................................................................8
2.3 ELECTRICAL PARTS ....................................................................................................................................8
2.3.1 OVERLOAD PROTECTOR ...................................................................................................................8
2.3.2 COMPRESSOR .....................................................................................................................................9
2.3.3 CAPACITOR ..........................................................................................................................................9
2.3.4 THERMOSTAT .......................................................................................................................................9
2.3.5 ROTARY SWITCH..................................................................................................................................9
2.3.6 POWER CORD ....................................................................................................................................10
2.4 REFRIGERANT CYCLE ...............................................................................................................................10
2.4.1 CONDENSER ..................................................................................................................................... 10
2.4.2 EVAPORATOR .................................................................................................................................... 11
2.4.3 CAPILLARY TUBE .............................................................................................................................. 11
3. TROUBLESHOOTING GUIDE
....................................................................................................13
3.1 OUTSIDE DIMENSIONS..............................................................................................................................13
3.2 PIPING SYSTEM ........................................................................................................................................14
3.3 TROUBLESHOOTING GUIDE ....................................................................................................................15
4. CIRCUIT DIAGRAM
........................................................................................................................... 20
5. EXPLODED VIEW-CP
.............................................................................................................................. 21
5-1. EXPLODED VIEW-ZQ
.............................................................................................................................. 22
6. SERVICE PARTS LIST
.................................................................................................................... 23
—2—
1. PREFACE
This service manual provides various service information, including the mechanical and electrical parts, etc.
This room air conditioner was manufactured and assembled under a strict quality control system.
The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.
1.1 FEATURES
• DESIGNED FOR COOLING ONLY
• BUILT-IN ADJUSTABLE THERMOSTAT
• WASHABLE ONE-TOUCH FILTER
• COMPACT SIZE
1.2 SPECIFICATIONS
ITEMS
MODELS
COOLING CAPACITY (BTU/h)
POWER SUPPLY (Phase, V, Hz)
ZQ05C10 CP05N10
5,000
1ø, 115V, 60HZ
INPUT (W) 515
OPERATING CURRENT (AMP.)
REFRIGERANT CONTROL
REFRIGERANT CHARGE (R-22)
INSIDE FAN
OUTSIDE FAN
AIR DISCHARGE
CHASSIS
PROTECTOR
4.8
CAPILLARY TUBE
205g (7.05 oz)
TURBO FAN
PROPELLER FAN WITH SLINGER RING
2-WAY (RIGHT AND LEFT)
TOP-DOWN
• OVERLOAD PROTECTOR FOR COMPRESSOR
• INTERNAL PROTECTOR FOR FAN MOTOR
TEMPERATURE CONTROL
FAN MOTOR
Thermostat Thermistor
6 POLES, 21W
—3—
1.3 LOCATIONS OF CONTROLS - CP
1
TEMPERATURE SETTING
• These buttons control the temperature of the room.
The temperature can be set within a range of 60
°
F to 86
°
F, in increments of 1
°
F.
2
MONEY SAVER
The fan stops when the compressor stops cooling.
• Approximately every 3 minutes the fan will turn on and sample the room air to determine if more cooling is needed.
3
OPERATION MODE SELECTOR
• Everytime you push this button, it will rotate between the COOL, FAN and DRY modes.
4
ON/OFF TIMER
ON–When the air conditioner is off, it can be set to automatically come on in 1 to 12 hours from its previous setting. Each touch will increase the timer by 1 hour.
OFF–When the air conditioner is on, it can be set to automatically turn off in 1 to 12 hours. Each touch will increase the timer by 1 hour. After the timer has been on for 30 minutes, the temperature will automatically rise 2
°
F, and after another 30 minutes, it will automatically rise 2
°
F again. The temperature will then stay the same until the timer goes
OFF.
To cancel the timer, press the TIMER pad until the display time disappears.
5
POWER
• To turn the unit ON, push the button. To turn the unit OFF, push the button again.
• This button takes priority over any other buttons.
• When you first turn it on, the unit is on the High cool mode and the temp. at 72
°
F
6
FAN SPEED
• Everytime you push this button it will rotate between the following fan speeds:
High (F3)
→
Low(F1)
→
Medium (F2)
→
High (F3)
—4—
1.3-1 LOCATIONS OF CONTROLS - ZQ
Off
Hi Fan
Lo Fan
Hi Cool
Lo Cool
: Turns air conditioner off.
: High speed fan operation without cooling.
: Low speed fan operation without cooling.
: Cooling with high speed fan operation.
: Cooling with low speed fan operation.
This automatically controls the temperature of the indoor air.
Turn the knob clockwise for greater cooling.
Point the arrow counter-clockwise for more moderate cooling.
CAUTION : After switching the air conditioner from Cool to Off or Fan, wait at least 3 minutes before switching it back to Cool.
1.4 SAFETY PRECAUTIONS
1. When servicing, set the ROTARY SWITCH to
Off and unplug the power cord.
2. Observe the original lead dress.
If a short circuit is found, replace all parts which have been overheated or damaged by the short circuit.
3. After servicing, make an insulation resistance test to prevent the customer from being exposed to shock hazards.
1.5 INSULATION RESISTANCE TEST
1. Unplug the power cord and connect a jumper between 2 pins (black and white).
2. The grounding conductor (green or green and yellow) is to be open.
3. Measure the resistance value with an ohm meter between the jumpered lead and each exposed metallic part on the equipment at all position
[except Off] of the ROTARY SWITCH.
4. The value should be over 1 MΩ.
—5—
2. DISASSEMBLY INSTRUCTIONS
2.1 MECHANICAL PARTS
2.1.1 FRONT GRILLE
1. Pull the inlet grille forward.
2. Remove the screw securing the Front Grille. (Fig. 3)
3. Push the grille up from the bottom and pull the top of the grille away from the case to lift the top tabs out of their slots. (Fig. 4)
4. Carefully position the grille, bottom first, and snap back into place.
5. Reposition the screw that secures the front grille
Figure 1
Figure 2
2.1.2 CABINET
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to section 2.1.1)
3. Remove 9 screws that secure the cabinet to the base pan and condenser. (See Figure 3)
4. Lift the cabinet from the unit.
5. Re-install by referring to the procedures above.
Figure 3
2. Remove the front grille. (Refer to Section 2.1.1)
3. Remove the cabinet. (Refer to Section 2.1.2)
4. Remove 1 screws that secure the control board to base pan and air guide. (See Figure 4)
NOTE : Controls, wires, and capacitor are now accessible for servicing. Discharge the capacitor before servicing. See step
2.3.3 on page 8 for procedures.
the fan motor and compressor. (See Figure 5)
7. Re-install components by referring to procedures above. (Refer to wiring diagram on page 23 in this manual or inside control board.)
Figure 4
Figure 5
—6—
2.2 AIR HANDLING PARTS
2.2.1 AIR GUIDE UPPER
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to Section 2.1.1)
3. Remove the cabinet. (Refer to Section 2.1.2)
4. Remove the control panel.
(Refer to Section 2.1.3)
5. Remove 2 screws that secure the upper air guide to air guide lower. (See Figure 6)
6. Lift upper air guide upward.
7. Re-install by referring to the procedures above.
Figure 6
Figure 7
2.2.2 ORIFICE, TURBO FAN AND FAN
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to Section 2.1.1)
3. Remove the cabinet. (Refer to Section 2.1.2)
4. Remove the control board.
(Refer to Section 2.1.3)
5. Remove the air guide upper.
(Refer to Section 2.2.1)
6. Remove 2 screws that secure the base pan to condenser. (See Figure 7)
7. Remove screw that secures the shroud to channel of condenser.
8. Press the snap area of shroud with your thumbs.
This allows you to remove it from the condenser.
9. Lift the compressor upward with the evaporator and condenser. (See Figure 7)
10. Remove the orfice by pushing the snap area of the air guide blower. (See Figure 8)
11. Remove the clamp springs which are clamped to the shaft of fan and turbo fan by hand plier. (See
Figure 9)
12. Pull the fan and turbo fan outward.
13. Remove the shroud.
14. Re-install by referring to the procedures above.
Figure 8
Figure 9
—7—
2.2.3 MOTOR
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to Section 2.1.1)
3. Remove the cabinet. (Refer to Section 2.1.2)
4. Remove the control panel.
(Refer to Section 2.1.3)
5. Remove the upper air guide.
(Refer to Section 2.2.1)
6. Remove the compressor, turbo fan, fan and shroud. (Refer to Section 2.2.2)
7. Remove 2 screws that secure the motor to the motor mount . (See Figure 10)
8. Remove the motor.
9. Re-install by referring to the procedures above.
Figure 10
2.2.4 AIR GUIDE
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to Section 2.1.1)
3. Remove the cabinet. (Refer to Section 2.1.2)
4. Remove the control panel.
(Refer to Section 2.1.3)
5. Remove the upper air guide .
(Refer to Section 2.2.1)
6. Remove the compressor, turbo fan, fan and shroud. (Refer to Section 2.2.2)
7. Remove the motor. (Refer to Section 2.2.3)
8. Remove 2 screws that secure the air guide to the base pan. (See Figure 11)
9. Push the air guide backward and lift it upward.
(See Figure 11)
10. Re-install by referring to the procedures above.
Figure 11
Figure 12
2.3 ELECTRICAL PARTS
2.3.1 OVERLOAD PROTECTOR
1. Remove the front grille and cabinet.
(Refer to Section 2.1)
2. Remove the nut which fastens the terminal cover.
3. Remove the terminal cover.
4. Remove all the leads from the overload protector.
5. Remove the overload protector.
6. Re-install the components by referring to the removal procedure above.
(See Figure 12 and 13)
—8—
Figure 13
2.3.2 COMPRESSOR
1. Remove the front grille and cabinet.
(Refer to Section 2.1)
2. Discharge the refrigerant by using a refrigerant recovery system.
3. Remove the overload protector.
(Refer to Section 2.3.1)
4. After discharging the unit completely, unbrace the suction and discharge pipes at the compressor connections.
5. Remove 3 nuts which fasten the compressor.
6. Remove the compressor.
7. Re-install by referring to the removal procedure above. (See Figure 14)
2.3.3 CAPACITOR
1. Remove the cabinet. (Refer to Section 2.1.2)
2. Remove the control panel.
(Refer to Section 2.1.3)
3. Discharge the capacitor by placing a 20 K
Ω resistor across the capacitor terminals.
4. Remove the screw which fastens the capacitor clamp.
5. Remove all the leads of capacitor terminals.
6. Re-install the components by referring to the removal procedure above. (See Figure 15)
Figure 14
Figure 15
2.3.4 THERMISTOR
1. Remove the cabinet. (Refer to Section 2.1.2)
2. Remove the control panel.
(Refer to Section 2.1.3)
3. Disconnect the thermistor terminals from main
P.W.B assembly.
4. Remove the thermistor.
5. Re-install the components by referring to the removal procedure above. (See Figure 16)
2.3.5 CONTROL BOARD
1. Remove the cabinet. (Refer to Section 2.1.2)
2. Remove the control panel.
(Refer to Section 2.1.3)
3. Pull the control board forward and pull out it.
4. Remove 2 lead wire terminals.
5. Re-install the components by referring to the removal procedure above. (See Figure 17)
Figure 16
Figure 17
—9—
2.3.6 POWER CORD
1. Disconnect the unit from source of power.
2. Remove the front grille. (Refer to Section 2.1.1)
3. Remove the cabinet. (Refer to Section 2.1.2)
4. Remove a screw that secures control panel to base pan. (Refer to Section 2.1.3)
5. Pulls the control board toward you.
6. Disconnect the 2 receptacles and remove the grounding screw.
7. Remove a screw securing the clip with cord to the control panel.
8. Pull the power cord.
9. Re-install by referring to procedures above.
Figure 18
2.4 REFRIGERANT CYCLE
2.4.1 CONDENSER
1. Remove the cabinet. (Refer to Section 2.1.2)
2. Discharge the refrigerant by using a refrigerant recovery system.
3. Remove the air guide. (Refer to Section 2.2.1)
4. Remove 2 screws which fasten the condenser.
5. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.
6. Remove the condenser.
7. Re-install by referring to the procedures above.
Figure19
—10—
2.4.2 EVAPORATOR
1. Remove the cabinet.
2. Discharge the refrigerant by using a refrigerant recovery system.
3. Remove the upper air guide . (Refer to Section
2.2.1)
4. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.
5. Remove the evaporator.
6. Re-install by referring to the procedures above.
2.4.3 CAPILLARY TUBE
1. Remove the cabinet.
2. Discharge the refrigerant by using a refrigerant recovery system.
3. Remove the upper air guide. (Refer to Section
2.2.1)
4. After discharging the refrigerant completely, unbraze the interconnecting tube of the capillary tube.
5. Remove the capillary tube.
6. Re-install by referring to the procedures above.
NOTES
Replacement of the refrigeration cycle.
1. When replacing the refrigerating cycle, be sure to discharge the refrigerant by using a refrigerant recovery system.
2. After discharging the unit completely, remove the desired components, and unbraze the pinch-off tubes.
3. Solder service valves into the pinch-off tube ports, leaving the valves open.
4. Solder the pinch-off tubes with service valves.
5. After completing the above procedures, the valve must be removed .
6. Evacuate as follows:
6-1. Connect the vacuum pump, as illustrated in figure 21A.
6-2. Start the vacuum pump. Slowly open manifold valves A and B with two full turns counterclockwise and leave the valves closed.
The vacuum pump is now pulling through valves A and B up to valve C by means of manifold and the entire system.
CAUTION : If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counter-clock-
—11— wise. This will keep oil from foaming and being drawn into the vacuum pump.
6-3. Operate the vacuum pump for 20 to 30 minutes, until 600 micron vacuum is obtained.
Close valves A and B and observe vacuum gauge for a few minutes.
A rise in pressure would indicate a possible leak or moisture remaining in the system.
With valves A and B closed, stop the vacuum pump.
6-4. Remove the hose from the vacuum pump and place it on the charging cylinder. See figure
23B. Open valve C.
Discharge the line at the manifold connection.
6-5. The system is now ready for final charging.
7. Recharge as follows:
7-1. Rotary compressor systems are charged from the high-side. If the total charge cannot be put in the high-side, the balance will be put in the suction line through the access valve which is installed as the system is opened.
7-2. Connect the charging cylinder as shown in figure 21B. With valve C open, discharge the hose at the manifold connection.
7-3. Open valve A and allow the proper charge to enter the system. Valve B is still closed.
7-4. If more charge is required, the high-side will not take it. Close valve A.
7-5. With the unit running, open valve B and add the balance of the charge. a. Do not add the liquid refrigerant to the lowside. b. Watch the low-side gauge, allow pressure to rise to 30 lbs. c. Turn off valve B and allow the pressure to drop. d. Repeat steps B and C until the balance of the charge is in the system.
7-6. When the unit is operating correctly, use the pinch-off tool with the unit still running and the clamp on the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder the pinch-off tube closed. Turn off the unit, allow setting for a while and then test the leakage of the pinch-off connection.
Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment, pinch-off tool capable of making a vapor proof seal, leak detector, tubing cutter, hand tools to remove components and service valve.
COMPOUND GAUGE
MANIFOLD
GAUGE
B A
CONDENSER
(HIGH PRESSURE SIDE)
COMPRESSOR
SEE INSETS
BELOW
EVAPORATOR
(LOW PRESSURE SIDE)
CAPILLARY TUBE
B
A
EXTERNAL VACUUM PUMP
B
LO HI CHARGING CYLINDER
A
Figure 21A-Pulling Vacuum Figure 21B-Charging
C
—12—
2.4.4 ELECTRICAL DATA
Line Cord Plug Use Wall Receptacle Power Supply
Do not under any circumstances cut or remove the grounding prong from the plug.
Power supply cord with
3-prong grounding plug
Standard 125V, 3-wire grounding receptacle rated 15A, 125V AC
Use 15 AMP, time delay fuse, or circuit breaker.
USE OF EXTENSION CORDS
Because of potential safety hazards, we strongly discourage the use of an extension cord. However, if you wish to use an extension cord, use a CSA certified/UL-listed 3-wire (grounding) extension cord, rated 15A, 125V.
3. TROUBLESHOOTING GUIDE
3.1 OUTSIDE DIMENSIONS (unit: mm [in])
370 (14
9
/
16
")
42 (1 21 /
32
")
120 (4
3
/
4
")
27.5 (1 3 /
32
")
472 (18
9/16
")
42 (1
21
/
32
")
22.5(0.8
3/32
")
155(6
3/32
")
370 (14
9
/
16
")
472 (18
9
/
16
")
—13—
3.2 PIPING SYSTEM
CAPILLARY
TUBE
CONDENSER COILS
FAN
MOTOR
TURBO FAN
EVAPORATOR
COILS
Following is a brief description of the important components and their function in what is called the refrigeration system. Reference should be made to Figure 32 to follow the refrigerating cycle and the flow of the refrigerant in the cooling cycle.
ROOM AIR CONDITIONER
CYCLE OF REFRIGERATION
EVAPORATOR COILS
COMPLETE LIQUID
BOIL OFF POINT
COOLED
AIR
ROOM AIR HEAT LOAD
SUCTION LINE
COOL LOW PRESSURE VAPOR
VAPOR INLET
CONDENSER COILS
OUTSIDE COOLING
AIR FOR REFRIGERANT
PASS THROUGH
HOT
DISCHARGED
AIR
LIQUID
PRESSURE
DROP
MOTOR
COMPRESSOR
OIL
(LIQUID REFRIGERANT)
CAPILLARY TUBE
Figure 32
DISCHARGE
LINE
NOT HIGH PRESSURE
VAPOR
LIQUID OUTLET
HIGH PRESSURE VAPOR
LIQUID REFRIGERANT
LOW PRESSURE VAPOR
—14—
3.3 TROUBLESHOOTING GUIDE
In general, possible trouble is classified in two kinds.
The one is called Starting Failure which is caused by an electrical defect. The other is Ineffective Air Con-
ditioning caused by a defect in the refrigeration circuit and improper application.
Unit is running but cooling is ineffective.
Ineffective Cooling
Check cold air circulation for smooth flow.
Check outdoor coil
(heat exchanger) and fan operation.
Check heat load increase.
Clean condenser.
Dirty indoor coil
(heat exchanger)
Check for gas leakage.
Not on dedicated circuit.
Repair gas leak.
Malfunction of fan.
Clogging air filter.
Replacement of unit if the unit is beyond repair.
Check inside gas pressure.
Obstruction at air outlet.
Adjust refrigerant charge.
Remove obstruction.
Malfunction of compressor.
Check for restriction in refri geration circuit.
Remove restriction in refrigeration circuit.
Satisfactory operation with temperature difference of inlet & outlet air; 18~26°F.
—15—
Replacement of compressor.
Fails to Start
Check voltage power source.
Check control switch setting.
Compressor fails to start.
Drop of power voltage.
Defect of compressor or capacitor.
Capacitor check.
Replacement.
Irregular motor resistance (
Ω
)
Irregular motor insulation (
Ω
)
Replacement of compressor
(Motor damaged).
Improper thermostat setting
Loose terminal connection
Improper wiring
—16—
Check of circuit breaker and fuse.
Gas leakage of feeler bulb of thermostat.
Check control switch.
Fan fails to start.
Improper wiring.
Defect of fan motor or capacitor.
Irregular motor resistance (
Ω
)
Irregular motor insulation (
Ω
)
Replacement of fan motor.
Regular but fails to start.
Replacement of compressor.
ROOM AIR CONDITIONER VOLTAGE LIMITS
NAME PLATE RATING MINIMUM
115V ± 10% 103.5V
MAXIMUM
126.5V
COMPLAINT CAUSE
Fan motor will not run.
REMEDY
No power Check voltage at outlet. Correct if none.
Power supply cord Check voltage to electronic control board. If none, check power supply cord. Replace cord if circuit is open.
Fan motor runs.
Wire disconnected or connection loose
Capacitor (Discharge capacitor before testing.)
Will not rotate
Revolves on overload
Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal.
Test capacitor.
Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged.
Fan blade hitting shroud or blower wheel hitting scroll. Re-align assembly.
Units using slinger ring condenser fans must have 1/4" inch clearance to the base.
If necessary, shim up the bottom of the fan motor with mounting screw(s).
Check fan motor bearings; if motor shaft will not rotate, replace the motor.
Check voltage. See limits on this page.
If not within limits, call an electrician.
Test capacitor.
Check bearings. Does the fan blade rotate freely?
If not, replace fan motor.
Pay attention to any change from high speed to low speed. If the speed does not change, replace the motor.
—17—
COMPLAINT
Fan motor noise.
Compressor will not run, fan motor runs.
Compressor cycles on overload.
CAUSE REMEDY
Fan blade If cracked, out of balance, or partially missing, replace it.
Blower wheel If cracked, out of balance, or partially missing, replace it.
Loose set screw Tighten it.
Worn bearings
Voltage
If knocking sounds continue when running
replace the motor. If the motor hums or noise appears to be internal while running, replace motor.
Check voltage. See the limits on the preceding page. If not within limits, call an electrician.
Wiring
Thermistor
Check the wire connections; if loose, repair or replace the terminal. If the wires are disconnected, refer to wiring diagram for identification, and replace the wires. Check the wire connections;
If not according to the wiring diagram, correct the connections.
Check the TEMP control. If not at the lowest number, set TEMP control to this setting.
Check the continuity of the thermistor. Replace the control board if the circuit is open.
Capacitor (discharge capacitor before servicing.)
Compressor
Overload
Voltage
Overload
Check the capacitor.
Replace if not within ±10% of manufacturer’s rating, replace if shorted, open, or damaged.
Check the compressor for open circuit or ground. If open or grounded, replace the compressor.
Check the compressor overload if externally mounted.
Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)
Check the voltage. See the limits on the preceding page. If voltage is not within these limits, call an electrician.
Check overload, if externally mounted.
Replace if open. (If the compressor temperature is high, remove the overload, cool, and retest.)
—18—
COMPLAINT CAUSE REMEDY
Compressor cycles on Fan motor If not running, determine the cause. Replace if overload. required.
Condenser air flow restriction
Condenser fins
(damaged)
Capacitor
Remove the cabinet, inspect the interior surface of the condenser. If restricted, clean carefully with a vacuum cleaner (do not damage fins) or brush. Clean the interior base before re-assembling.
If the condenser fins are closed over a large area on the coil surface, head pressures will increase, causing the compressor to cycle.
Straighten the fins or replace the coil.
Test the capacitor.
Insufficient cooling
Wiring
Refrigeration system
Air filter
Check the terminals. If loose, repair or replace.
Check the system for a restriction.
If restricted, clean or replace.
Excessive noise
Unit undersized
Blower or fan
Copper tubing
Determine if the unit is properly sized for the area to be cooled.
Check the set screw, or clamp. If loose or missing, correct. If the blower or fan is hitting scroll or barrier, rearrange the air handling parts.
Remove the cabinet and carefully rearrange the tubing not to contact the cabinet, compressor, shroud, and barrier.
—19—
4. CIRCUIT DIAGRAM
LOCATION
NO.
1
2
3
4
5
DESCRIPTION
MOTOR
BK
BL
RD
OR(BR)
YL
GN/YL
(GN)
CAPACITOR
POWER INPUT
WH(BL)
(Ribbed)
BK(BR)
(Plain)
GN/YL(GN)
BK
BL
RD
OR(BR)
YL
THERMISTOR
CN-TH1
F
C
H
OR
BK
RD
RY-SYNC
WH
SYNC
MOTOR
BK
COMP.
R
C
S
3854A20022K
WIRING DIAGRAM
OLP
BK
RD
BL BL
ZNR
RY-COMP
4 3
FUSE
TRANS
FORMER
250V/T2A
(115V/T2A)
POWER CORD ASSY
FAN MOTOR
COMPRESSOR
CAPACITOR
OVERLOAD PROTECTOR
PART NO.
CP05C10
67300020
67303026
67301616
67300718
67301405
Q'TY
PER SET
1
1
1
1
1
—20—
5. EXPLODED VIEW - CP
749740
130910
267110
149980
559011
W48602
132111-1
132111-2
135312
147582-1
147581
W48602
359012
352390
147582-2
152302
269310
135303
135313
W0CZZ
137215
268714
263230
238310 268712
550140
—21—
567502
552102
346811
352390-1
130410
5-1. EXPLODED VIEW - ZQ
749740
130910
132111-1
149980
559011
W48602
135312
149410
132111-2
147582-1
147581
W48602
359012
352390
147582-2
269310
135313
152302
264110
266003
135500
W0CZZ 550140
—22—
567502
346811
352390-1
130410
6. SERVICE PARTS LIST
ZQ05C10(TWC051HPAA6.AWYAFRD)
LocNo FRD P/NO DESCRIPTION
130410 67302921
130910 67303709
135312 67306003
135313 67306103
Base Assy Single
Cabinet Assy Single
Grille Assy Front
Grille Assy Inlet
135500 67300309
147581 67306400
147582-1 67306262
147582-2 67306263
149410 67304100
149980 67303115
Cover
Link
Louver Vertical
Louver Vertical
Knob Assy
Shroud
152302 67304300
269310 67300405
264110 67300020
266003 67300500
346811 67303027
352390 67302727
352390-1 67302728
550140 67301900
Filter (Mech)
Thermostat
Power Cord Assy
Switch Rotary
Motor Assy Single
Air Guide Assy Upper
Air Guide Assy Lower
Isolator Comp
559011
67302613
359012 67302612
567502 67301405
Fan Assy Axial
Fan Turbo
O.L.P.
W0CZZ 67300718
W48602 67302500
Capacitor
Clamp Spring
132111-1 67303800 Installation Kit w/Curtains L
132111-2 67303801 Installation Kit w/Curtains R
749740 67304000 Upper Guide Cabinet
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
REMARK
R
R
R
R
R
R
R
R
R
R
—23—
CP05N10(TWC051HPMK6.AWYAFRD)
LocNo FRD P/NO
130410 67302921
DESCRIPTION
Base Assy Single
130910 67303709
135312 67306008
135313 67306107
Cabinet Assy Single
Grille Assy Front
Grille Assy Inlet
147581 67304600
147582-1 67306262
147582-2 67306263
149980 67303115
152302 67304300
238310 67500115
263230 67307806
Link
Louver Vertical 2 ea
Louver Vertical 2 ea
Shroud
Filter (Mech)
Escutcheon
Thermistor
269310 67300020
267110 67307703
268712 67307611
268714 67307612
346811 67303026
352390 67302727
352390-1 67302728
Power Cord Assy
Remote Controller
PWB(PCB) Assy Display
PWB(PCB) Assy Main
Motor Assy Single
Air Guide Assy Upper
Air Guide Assy Lower
550140 67301900
559011 67302613
359012 67302612
567502 67301405
Isolator Comp
Fan Assy Axial
Fan Turbo
O.L.P.
W0CZZ 67300718
W48602 67302500
Capacitor
Clamp Spring
132111-1 67303800 Installation Kit w/Curtains L
132111-2 67303801 Installation Kit w/Curtains R
749740 67304000 Upper Guide Cabinet
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
REMARK
R
R
R
R
R
R
R
R
R
R
R
—24—
MEMO
—25—
MEMO
—26—
Use Factory Certified Parts...
FRIEDRICH AIR CONDITIONING CO.
Visit our web site at www.friedrich.com
Post Office Box 1540 • 4200 N. Pan Am Expressway • San Antonio, Texas 78295-1540
• (210) 357-4400 • FAX (210) 357-4490
CP05.Svc (05/0 7 )
P/NO:MFL38735502
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 1.1 FEATURES
- 3 1.2 SPECIFICATIONS
- 5 1.4 SAFETY PRECAUTIONS
- 5 1.5 INSULATION RESISTANCE TEST
- 6 2.1 MECHANICAL PARTS
- 6 2.1.1 FRONT GRILLE
- 6 2.1.2 CABINET
- 6 2.1.3 CONTROL BOARD
- 7 2.2 AIR HANDLING PARTS
- 7 2.2.1 AIR GUIDE UPPER
- 7 2.2.2 ORIFICE, TURBO FAN AND FAN
- 8 2.2.3 MOTOR
- 8 2.2.4 AIR GUIDE
- 8 2.3 ELECTRICAL PARTS
- 8 2.3.1 OVERLOAD PROTECTOR
- 9 2.3.2 COMPRESSOR
- 9 2.3.3 CAPACITOR
- 9 2.3.4 THERMOSTAT
- 9 2.3.5 ROTARY SWITCH
- 10 2.3.6 POWER CORD
- 10 2.4 REFRIGERANT CYCLE
- 10 2.4.1 CONDENSER
- 11 2.4.2 EVAPORATOR
- 11 2.4.3 CAPILLARY TUBE
- 13 3.1 OUTSIDE DIMENSIONS
- 14 3.2 PIPING SYSTEM
- 15 3.3 TROUBLESHOOTING GUIDE