- No category
advertisement
INSTALLATION,
OPERATION AND
MAINTENANCE
MANUAL
Publication No. IOM 108.2
February, 2007
TABLE OF CONTENTS
INSPECTION
INSTALLATION
LOCATING CONDENSING UNITS
LOCATING UNIT COOLERS
UNIT COOLER MINIMUM DISTANCES
FIELD WIRING
REFRIGERANT PIPING
LEAK TESTING
EVACUATION
CHARGING & START-UP
GENERAL MAINTENANCE
TYPICAL FIELD WIRING DIAGRAMS
HIGH SIERRA SEQUENCE OF OPERATIONS
TROUBLE SHOOTING GUIDE
REPLACEMENT PARTS
PAGE
2
6
6
7
5
5
2
3
4
7
8
9
11-12
13-16
221 S. BERRY ST., BREA, CA. 92821 TEL (714) 529-1935 www.russellcoil.com
FAX (714) 529-7203
INSPECTION
When the equipment is received, check the quantity of cartons and crates against the bill of lading.
· Inspect all containers for visible damage.
· Report any damage or shortages to the freight company immediately.
· It is the customer's responsibility to file a freight claim.
· Check the unit name plates to verify that the voltage and phase is correct before installation.
Installation and maintenance should be performed by qualified personnel who are familiar with local codes and regulations. Installers should have previous experience with this type of equipment.
CAUTION: Avoid contact with sharp edges and coil surfaces.
INSTALLATION
LOCATING CONDENSING UNITS
Condensing unit - Minimum clearances
Drawing 1
Discharge air
A
B
CONDENSING UNIT
Intake air
C
Table 1
Minimum
HP Dimensions (in)
A B C
1/2 - 2 60 24 36
3 - 6 72 24 36
8 - 15 72 30 48
20 - 40 48 48 48
B
PLAN VIEW
Do not locate condensing units so that they are bordered on three or more sides by tall obstructions. Condensing units should be positioned so that the airflow through the condenser is the same as the prevailing winds. If strong variable winds are common, a wind deflector should be used on the discharge side of the unit. Be certain that there is adequate room around the unit for regular inspection and service. For multiple unit sites, do not locate units where the air discharge from one condensing unit will enter into the air intake of other units.
Roof mounted condensing units should be located above supporting walls, over storage areas or spaces not sensitive to noise or vibration. They must be adequately supported.
Pad mounted condensing units should be installed a minimum of 4 inches above ground level, away from windows, doors and other areas where noise may be a problem. All units must be level when mounted.
2
CONDENSING UNIT INSTALLATION (continued.)
Condensing units with spring mounted compressors are shipped with retainers under the compressor feet to prevent damage during shipment. For Copeland H and K body compressors, remove the retainers and loosen the mounting nut to allow 1/16” clearance between the nut and rubber spacer. For 3HP and larger units, the mounting nuts must be removed to insert the rubber spacer. Insert the rubber spacer over the mounting studs, replace the nut and tighten to within 1/16” of the spacer. DO NOT TIGHTEN THE NUTS
AGAINST THE SPACER OR FOOT.
Units with iso-pad mounted compressors are shipped with the mounting nuts tight. These should be checked to make certain that they have not loosened during shipment.
LOCATING AND MOUNTING UNIT COOLERS
Determine the best location for the unit in the walk-in cooler or freezer. Consider the air pattern required to cover the entire space. For High Sierra Systems with two unit coolers, locate the unit coolers so that the piping runs from the suction and liquid line tees are equal in size and length.
Do not restrict the inlet or outlet air stream. Place the unit cooler as far as possible from
any door openings. Direct the discharge air stream towards the door whenever possible.
This will help to prevent warm, moist air from being drawn into the coil (Drawings 2, 3 and
Table 2). Adequate clearances should be maintained around the unit cooler to allow for proper airflow through the unit and for regular maintenance and service to be preformed.
For all Hot Gas defrost unit coolers, ensure that the drain pan is in contact with the Hot Gas drain pan loop after installation. If the drain pan is removed for any reason, verify that it has
physical contact with the defrost loop when replaced.
The drain line should be pitched a minimum of 4" per foot to allow proper drainage and should exit the room as quickly as possible. Do not reduce the drain line size. Do not locate line bends, elbows or drain traps within the refrigerated space. All drain lines must be
trapped outside of the enclosure where the temperature is never below 35 degrees. Drain lines should run to an open drain and should never be attached directly to a sewage or waste line. Drain lines must be protected from possible freezing. Freezer units must have copper drain lines that are heated and insulated.
Remove all packaging materials before lifting the unit into position. Be certain that the unit is not sitting on the drain fitting or refrigerant connections. All-Temp units should be hung using
5/16" minimum diameter, stainless steel support rods or fasteners at all hanging slots. Use minimum 3/8" hanger rods for Inter-Temp and Ultra-Temp models.
Tighten all fasteners securely. All units must be positioned level, flush with the ceiling and all gaps must be properly caulked. Allow minimum clearances on all sides of the unit cooler(s) as indicated in Table 2 (next page).
3
Recommended Minimum Dimensions
Table 2
Unit cooler
Height
Air intake* Side clearance clearance
H
15
19
1 x H
15
19
1 x H
15
19
25
32
50
25
32
50
25
32
50
* Absolute minimum Distance
** 15’ is adequate clearance for these models
Dimensions are in inches.
Air discharge Unit to clearance
2 x H floor
5 x H
30
38
75
95
50
64
100
125
160
180**
Drawing 2 obstruction free area
Air H*
5 x H* 12" min.
door
Slope Drain line 4" per foot and trap.
Drawing 3
H*
H*
Back Wall
2 x H* H*
Alternate
Door
Location
5 x H*
Keep air discharge area free from obstruction
Door
4
Air
Discharge
Front Wall
Alternate
Door
Location
FIELD WIRING
All field wiring must be done in compliance with local and national electrical codes. Use only properly sized Copper conductors. A system wiring diagram is located inside the condensing unit control box. Wire components as indicated on the diagram. The equipment nameplates are marked with electrical characteristics. All field wiring should enter the equipment through electrical conduit bushings. Note: All units must be grounded.
Before applying power to the units, check all connections to ensure they have not come loose during shipment. Be certain that the power is disconnected before tightening any electrical
connections. Disconnect switches and evaporator branch circuit protection are supplied by the equipment installer and must conform to governing electrical codes. Air defrost systems are wired so that the evaporator fans run continuously. For electric defrost and High Sierra systems, the evaporator fans are cycled off during the defrost and re-cooling period.
Electric defrost unit coolers are supplied with a temperature sensing defrost termination switch that will end the defrost at a preset coil temperature. (Recommended time clock settings for electric defrost are 2 defrosts per day, with a twenty minute fail safe setting. Adjust according to job site conditions. Fewest possible defrosts for the shortest possible duration are desirable.)
A high limit control is provided to prevent overheating if there is a component failure. A fan delay control is installed to allow the water condensate on the fins to freeze before the evaporator fan motors start. A pumpdown cycle is mandatory for all systems.
For both Sierra and High Sierra systems, a liquid line solenoid is factory installed and wired to each unit cooler terminal board (multiple evap systems receive multiple solenoid valves). Follow the system wiring diagram (provided in the condensing unit). Connection to TB1-44 must be made to assure proper pumpdown function. The room thermostat is mounted on the unit cooler for single evaporator systems and supplied loose for multiple evaporator systems. Follow the system wiring diagram supplied in the condensing unit.
REFRIGERANT PIPING
Condensing units and unit coolers are thoroughly cleaned and dehydrated at the factory. Use only ACR (refrigeration grade) tubing that is dehydrated and sealed. Only use WROT Copper fittings, cast fittings are a source of refrigerant leaks. All liquid and suction elbows must be long radius types for minimum pressure drop. Refrigerant lines must be properly supported to prevent vibration and breakage. Tube clamps should have a gasketed liner to prevent abrasion of the tubing. Sierra and High Sierra must not exceed more then a 100’ refrigerant line run.
Install all piping and components in accordance with local and national codes. Make refrigerant connections by using only hard or Silver bearing solder such as Silfos, Stay-Silv or higher Silver content brazing material. Slowly purge dry nitrogen through the tubing while brazing to prevent the formation of Copper oxide scale.
LIQUID LINE
Refer to the current ASHRAE Refrigeration Systems and Applications Handbook for assistance in determining appropriate liquid line sizes.
Horizontal and vertical liquid lines are normally the same diameter. However, pressure loss due to vertical lift may lead to flash gas that can inhibit proper TXV (and system) performance if not properly accounted for. Under sizing the liquid line can result in flash gas while over sizing the liquid line will unnecessarily increase the system charge requirement.
Sierra and High Sierra condensing units include Russell’s patented finned receiver ® , which is integrated into the air-cooled condenser. This finned receiver ® also acts as an efficient liquid sub-cooler. An additional liquid to suction heat exchanger is not normally required. The liquid line must be insulated to obtain the maximum benefits of the subcooled liquid.
5
SUCTION LINES
The suction line and it’s components must be carefully selected and installed. The suction line must be sized to maintain a balance of adequate refrigerant velocity, to allow for good oil return, and a low pressure drop that will prevent excessive capacity loss. The optimal line size will result in a reasonable refrigerant velocity and a minimum pressure drop. Total suction line pressure loss should not exceed 2 o F equivalent loss. For best system performance, the suction line should be insulated.
Suction line risers should be no larger in diameter than the horizontal pipe run. Refer to the current ASHRAE Refrigeration Systems and Applications Handbook for correct suction line and riser sizing. Horizontal suction line runs should slope in the direction of flow, 1 inch per ten feet of length. All suction lines should be insulated as soon as they exit the refrigerated space. Install a 1/4-inch schrader fitting near the evaporator outlet to assist in accurate superheat readings. All suction line risers should be trapped to facilitate oil return. Additional
P-Traps are required for every 15 feet of elevation. Oil traps should be the same diameter as the suction line riser that it attaches to.
MULTIPLE EVAPORATOR PIPING
High Sierra systems involving multiple evaporators require that piping runs be of equal length to each evaporator. The line runs must be of equivelent length from the bull-head tees to each unit cooler. This will ensure proper distributon of hot gas to each unit cooler during the defrost cycle. Reference the drawing below for further clarification.
Evaporator
TXV
Liquid
Sol. Valve
Check
Valves
Drain Pan Circuit
Evaporator
Check Valve
TXV
Liquid
Sol. Valve
Check
Valves
Drain Pan Circuit
Check Valve
Condensing Unit
Fan Cyle
Control
Set: 90c.i.
60c.o.
Reversing
Valve
Power
Supply
Insulation
Compressor
Bi-Flow
Liquid Filter
Liquid
Shutoff
Valve
Suction Filter
Size For Total System Capacity
Size for one evaporator capacity.
Must be equal length or equivelent pressure drop.
Tee must be oriented to split hot gas defrost.
Defrost
Termination
Set: 250c.i.
200c.o.
Check
Valve
Relief
Valve
TXV
Sight
Glass
Condenser Coil
LEAK TESTING
After all refrigerant connections are made, add the proper system refrigerant until the pressure is 25 to 35 PSI. Then pressurize with dry nitrogen up to 120 PSI. Always use a pressure reducing regulator. Wait 30 minutes for the refrigerant to reach all parts of the system. Use an electronic leak detector to inspect all connections and system components. Repair any leaks that are found and re-check until all leaks are eliminated. Leave the system pressurized over night. Once the system is tight, it must be evacuated before charging.
6
EVACUATION
Proper installation procedures must include a deep evacuation of the system. A clean/dry system is essential when charging refrigerant. Open all service valves. The high vacuum method is the most effective procedure for assuring a clean and dry system. It requires the use of a two-stage high vacuum pump, an electronic high-vacuum gauge and 3/8" minimum
OD copper tubing. Use a high vacuum sealant on all lines and connections. Clean and dry
DEEP VACUUM OIL is essential for proper system evacuation.
This step is required FOR SIERRA/HIGH SIERRA SYSTEMS:
Evacuation access fitting:
AREA 1: From the compressor service valve (including the compressor head) through the condenser up to the liquid line module; Connecting to the port on the compressor discharge valve gets this area.
AREA 2: From the liquid line module to the liquid line solenoid; connecting to the liquid line “King” valve port gets this area on Sierra system. The connection will not properly evacuate area 1, above, since evacuation would have to be pulled through the check valve in the module, which will have about 1 PSI restriction. However, on High Sierra systems a pressure tap at the connection for the terminator pressure control evacuates the liquid line since this connection is downstream of the module.
AREA 3 : From the liquid line solenoid to the compressor (including the crankcase) connecting to the suction service port gets this area.
The need for this clarification has arisen from the fact that some systems have experienced high head pressure because non-condensables were left in the system when these procedures were not followed.
All systems - continued
Connect the vacuum lines to both the high and low-pressure sides of the system. Run the vacuum pump until the gauge reaches 500 microns for newly installed systems. With the pump still running, shut off the high vacuum line valve. The vacuum gauge should not exceed
(1500 microns or less ) after two minutes once the pump is closed off, though the pressure will increase slightly even on the most leak-free system. Open the compressor service valves and pull a continuous vacuum for a minimum of 4 hours. Pulling the vacuum overnight is highly recommended (mandatory for 5 HP systems and larger). Do not allow the system to stand at high vacuum without the vacuum pump operating. Do not start the compressor while the system is under a vacuum.
CHARGING
Both Sierra and High Sierra systems are designed to operate with minimum refrigerant charge and minimum head pressures. - Low head pressures are normal at low ambient conditions.
Make the charging line connection with a hose that is purged of air, through a filter drier.
Break the vacuum with the proper system refrigerant. Charge liquid refrigerant into the high side of the system. This should enable the system to operate. Add refrigerant charge as necessary to achieve a clear sight glass with the system close to normal operating condition, whether it is winter or summer. Ambient temperature is not relevant to the charging procedure.
IMPORTANT! Sierra and High Sierra systems are critical charge systems.
Be careful, DO NOT OVERCHARGE!
7
CHARGING continuation...
Refrigerant can be added most rapidly by introducing liquid directly into the liquid line down stream of the liquid line valve. Close the liquid line intermittently and add refrigerant directly into the port on the side of the liquid line valve until the sight glass is clear.
NOTE: Some new refrigerants require liquid charging only.
Be extra diligent not to log liquid in the accumulator, if one is present in the system. An accumulator is not recommended for Sierra or High Sierra systems. They can negatively impact the charging procedure of these systems. Liquid build-up in the accumulator may result from improper charging. Once in the accumulator the refrigerant returns very slowly.
Depending on how much is accumulated, how much frost is on the accumulator (frost acts as an insulator so the refrigerant boils off slower), ambient temperature, etc..., this excess refrigerant can cause significant problems.
START UP
Install gauges on the system to check both high and low pressures. Using the gauges, verify that the low-pressure control is properly set (3 PSI cut out, 15 PSI cut in).
Pump down the system by closing the liquid line solenoid and the service valve to verify that there is no objectionable increase in head pressure.
Be certain that the fan cycling control is properly adjusted. At the correct setting the cut-out setting should be 30 PSI above the design suction pressure. The cut-in setting should be 30
PSI above the cut out pressure.
THIS STEP IS REQUIRED FOR HIGH SIERRA ONLY
Move the high side gauge to the defrost termination schrader valve on the suction line and start a defrost cycle. Verify that the defrost terminates at 250 PSI, adjust the termination control if necessary. Set the time clock defrost fail-safe to
A MAXIMUM OF 10 MINUTES
and an initial setting of 2 defrosts per day.
Check the evaporator superheat after the system has run long enough to reach a balanced state. Low temperature systems normally operate most efficiently at a superheat settings that range from 6 to 8 degrees at design room temperature. Medium temperature rooms normally operate from 8 to 10 degree evaporator superheat. Adjust expansion valves only if necessary.
GENERAL MAINTENANCE
Disconnect all electrical power to the unit before inspecting or cleaning. Unit coolers and condensing units should be checked periodically and cleaned of all dirt or grease accumulation.
Fan blades and guards may require more frequent cleaning. Remove debris from the condenser coil using a brush or vacuum cleaner. All fan motors are life lubricated and do not require periodic oiling. Do not use ammonia or other cleaning agents that are corrosive or react with Copper or Aluminum.
If the liquid line filter is replaced High Sierra system, it must be replaced with a Bi-Flow filter.
8
TYPICAL FIELD WIRING DIAGRAMS
HIGH SIERRA COUNTER FLOW DEFROST
Condensing unit Condensing unit
Legend (all diagrams)
— — Field wiring
TB1 - Terminal block # 1
TB2 - Terminal block # 2
C6 - Heater contactor
LLS - Liquid line solenoid
EF - Evaporator fan motor(s)
T’stat - Room thermostat
DT - Defrost Termination
FD - Fan Delay Control
Single unit cooler
1 Phase motor(s)
SIERRA SYSTEMS
Condensing unit
2 unit coolers
1 Phase motors
Condensing unit
Air Defrost
Systems
Condensing unit
Electric Defrost
Single unit cooler
1 phase motors
1 phase heaters
Condensing unit
Electric Defrost
Single unit cooler
1 phase motors
3 phase heaters
*See page 5 for wiring instructions.
9
Electric Defrost
Two unit coolers
1 phase motors
1 phase heaters
HIGH SIERRA - Sequence of operation.
Refrigeration cycle
The High Sierra counter flow defrost system is unique in design. It operates like most conventional systems during the refrigeration cycle. As cooling is called for, the compressor, condenser fan(s), evaporator fans and liquid line solenoid valve are all energized.
Refrigerant vapor exits the compressor discharge port, moves through the High Sierra reversing valve and into the air-cooled condenser. As ambient air flows through the condenser, the refrigerant vapor gives up it's heat, becomes liquid and moves through the patented Sierra Finned
Receiver ® and liquid sub-cooler.
The sub-cooled liquid refrigerant exits the sub-cooler, passing through the High Sierra check valve
/ TXV valve assembly, leaving the condensing unit via a bi-flow liquid filter.
The liquid refrigerant enters the evaporator, flowing through a factory mounted solenoid valve. It passes through the expansion valve to be boiled off in the coil, providing cooling for the box. The vaporized refrigerant returns through the suction line, the reversing valve and suction filter into the compressor suction port.
As with any normal pump-down system, when the room temperature satisfies the thermostat, it deenergizes the liquid line solenoid, causing the system to pump down and cycle off.
Counter flow defrost cycle
The defrost timer initiates the counter flow defrost cycle. The number of defrost cycles is set by the installer. (The recommended frequency is one to two defrosts per day with the fail safe override set at 10 minutes. A normal defrost cycle lasts from 3 to 7 minutes.)
Upon the signal from the defrost timer, the reversing valve switches modes and the evaporator fan motors are turned off. The liquid line solenoid remains energized.
The direction of refrigerant flow is now reversed, as are the functions of the evaporator and condenser. The reversing valve diverts the compressor discharge through, what was formerly the suction line, back towards the evaporator. A suction line check valve, (factory mounted), routes the discharge gas through the evaporator drain pan circuit and into the coil tubes, thus providing the heat source for the counter flow defrost.
The evaporator, now acting as the condenser, converts the discharge gas into liquid, releasing large amounts of heat, defrosting the coil(s) very quickly.
The liquid refrigerant then exits the coil through the distributor, and the factory mounted TXV bypass check valve. It moves through the liquid line, the bi-flow liquid filter, through the condenser
TX valve and into the system condenser (now acting as the evaporator). The liquid refrigerant is then boiled off and returned to the compressor as suction gas, passing first through the reversing valve and suction filter.
The defrost cycle is ended when the system pressure reaches the termination point at the defrost control (located in the condensing unit). The installer must verify that the coil clears completely of
all frost and ice. If the defrost cycle terminates before all frost has been completely removed from the coil, the defrost termination pressure control setting may be increased incrementally until the coil defrosts properly (maximum setting 300 psi). The recommended defrost termination setting is
250 psi with a 50 psi differential.
10
Counterflow defrost cycle - continued
After the refrigeration cycle resumes, the evaporator fan motors remain off during the cool down period (never less than two minutes). This allows all condensate to drain before the fan motors are energized, thus preventing water from blowing off the coil and into the room.
Notes:
1. The condensing unit pressure relief valve is provided to regulate potential excessive pressures that may develop in the liquid line during extended shut down periods. It does not come into play during the refrigeration or defrost cycles.
2. The condensing unit TX valve is factory set and should not be field adjusted.
3. The evaporator fan delay control is located in the condensing unit control panel.
High Sierra Piping
Diagram 4
Diagram 5
11
Typical High Sierra replacement parts- Low Temp. Models*
Comp. Cond. Unit Rev. Valve Strainer Cond. Unit Liquid Filter Condenser Low Pres.
High Pres.
Fan Cycle
Type Model No.
PART# PART#
RHH100L44 21012 123277001
RHH165L44 21012 123277001
RHH215L44 21012 123277001
RHH315L44 21012 123277001
RHS075L44 21012 123277001
RHS100L44 21012 123277001
RHS150L44 21012 123277001
RHS200L44 21012 123277001
RHS250L44 21012 123277001
RHS300L44 21012 123277001
RHD300L44 16506 123277002
RHD400L44 16506 123277002
RHD500L44 16506 123277002
TXV (c.u.)
SBFSE-AA-Z
SBFSE-A-Z
SBFSE-B-Z
SBFSE-C-Z
SBFSE-AA-Z
SBFSE-A-Z
SBFSE-A-Z
SBFSE-B-Z
SBFSE-B-Z
SBFSE-C-Z
SBFSE-C-Z
EBSSE-6-Z
EBSSE-6-Z
PART# 230V Motor Blade Control Control Control
104471048 102540004 119103001 24464232 204464208 204464002
104471049 102540004 119103001 24464232 204464208 204464002
104471049 102540004 119103001 24464232 204464208 204464002
104471046 102540004 119103001 24464232 204464208 204464002
104471048 102540004 119103001 24464232 204464208 204464002
104471048 102540004 119103001 24464232 204464208 204464002
104471049 102540004 119103001 24464232 204464208 204464002
104471049 102540004 119103001 24464232 204464208 204464002
104471046 102540004 119103001 24464232 204464208 204464002
104471046 102540004 119103001 24464232 204464208 204464002
104471046 201006007 213266000 24464232 204464208 204464002
104471047 201006007 213266000 24464232 204464208 204464002
104471047 201006007 213266000 24464232 204464208 204464002
RHO200L44 21012 123277001
RHO250L44 21012 123277001
RHO300L44 21012 123277001
RHO301L44 21012 123277001
RHO400L44 21012 123277001
RHO500L44 16506 123277002
RHO600L44 16506 123277002
SBFSE-A-Z
SBFSE-B-Z
SBFSE-B-Z
SBFSE-C-Z
SBFSE-C-Z
EBSSE-6-Z
EBSSE-6-Z
104471049 201006007 213266000 24464232 204464208 204464002
104471046 201006007 213266000 24464232 204464208 204464002
104471046 201006007 213266000 24464232 204464208 204464002
104471046 201006007 213266000 24464232 204464208 204464002
104471047 201006007 213266000 24464232 204464208 204464002
104471047 201006007 213266000 24464232 204464208 204464002
104471047 201006007 213266000 24464232 204464208 204464002
DHD5L44
DHD6L44
DHD8L44
DHD9L44
DHD10L44
DHD12L44
DHD15L44
DHO6L44
21054 123277003 EBSSE-6-Z 104471047 205051004 213266000 204464041 Hi/Lo Combo 204464002
21054 123277003 EBSSE-7 1/2-Z 104471047 205051004 213266000 204464041 Hi/Lo Combo 204464002
21054 123277003 EBSSE-10-Z
21054 123277003 EBSSE-10-Z
21000 123277004 EBSSE-13-Z
21000 123277004 EBSSE-13-Z
21000 123277004 EBSSE-13-Z
16506 123277002 EBSSE-6-Z
104471066 205051004 213266000 204464041 Hi/Lo Combo
104471066 205051004 213266000 204464041 Hi/Lo Combo
104471066 205051004 213266000 204464041 Hi/Lo Combo
104471066 205051004 213266000 204464041 Hi/Lo Combo
104471193 205051004 213266000 204464041 Hi/Lo Combo
104471066 205051004 213266000 204464041 Hi/Lo Combo
204464002
204464002
204464002
204464002
204464002
204464002
DHO8L44
DHO10L44
DHO13L44
VHD15L44
VHD22L44
VHD27L44
VHD30L44
VHD44L44
VHD54L44
VHD60L44
21054 123277003 EBSSE-6-Z
21054 123277003 EBSSE-10-Z
104471066 205051004 213266000 204464041 Hi/Lo Combo 204464002
104471066 205051004 213266000 204464041 Hi/Lo Combo 204464002
21054 123277003 EBSSE-10-Z 104471066 205051004 213266000 204464041 Hi/Lo Combo 204464002
21049
21049
21055
21055
123277005
123277005
123277005
123277005
OSE-21-Z
OSE-21-Z
OSE-30-Z
OSE-30-Z
104471021
†
104471021
†
104471021
†
104471021
†
21055
21056
21056
123277005
Factory
OSE-45-Z 104471022
†
Contact (2) 104471022
†
(2) OSE-30-Z 104471022
†
110204000 210385000 204464041 Hi/Lo Combo
110204000 210385000 204464041 Hi/Lo Combo
110204000 210385000 204464041 Hi/Lo Combo
110204000 210385000 204464041 Hi/Lo Combo
110204000 210385000 204464041 Hi/Lo Combo
110204000 210385000 204464041 Hi/Lo Combo
110204000 210385000 204464041 Hi/Lo Combo
204464002
204464002
204464002
204464002
204464002
204464002
204464002
* Parts may vary based upon specific operating conditions.
† V-Series filter is not Bi-Flow Design. Part number is for replaceable core filter (shell only). Core Part# 14471034 (may require more than one core)
Russell Part #
21065
21066
21067
21068
21070
21072
21073
21074
21075
21076
21077
21079
21080
21063
204464020
104799015
204464004
104799020
104799010
Description
Rebuild kit for Russell Part#16506
Rebuild kit for Russell Part#21054
Rebuild kit for Russell Part#21000
Rebuild kit for Russell Part#21056
O-Ring Kit for Russell Part# 21012
O-Ring Kit for Russell Part#16506
O-Ring Kit for Russell Part# 21054
O-Ring Kit for Russell Part# 21000
O-Ring Kit for Russell Part# 21049
O-Ring Kit for Russell Part# 21055
O-Ring Kit for Russell Part# 21056
PILOT ASSY/MANIFOLD for Russell Part# 21054
PILOT ASSY/MANIFOLD for Russell Part# 21000
PILOT ASSY/MANIFOLD for Russell Part# 21049
HIGH SIERRA Defrost Termination Control
HIGH SIERRA Evap Fan Delay Control
HIGH SIERRA Condensing Unit Fan Cycle Control
HIGH SIERRA RELAYS R1 & R2 (Same number for each)
HIGH SIERRA Defrost Timer
12
Comp.
Type
Model
Number
Typical High Sierra replacement parts - R-Series Medium Temp. Models*
Reversing Rev. Valve
Valve Strainer
Cond. Unit
TXV
Repl. Core Condenser
Liquid Filter 230V Motor Blade
Low Pres. High Pres.
Control Control
RHH075H22 21012 123277001 SBFVE-AA-C 104471048 102540004 119103001 24464232 204464208
RHH100H22 21012 123277001 SBFVE-A-C 104471048 102540004 119103001 24464232 204464208
RHH151H22 21012 123277001 SBFVE-A-C 104471049 102540004 119103001 24464232 204464208
RHH201H22 21012 123277001 SBFVE-B-C 104471049 102540004 119103001 24464232 204464208
RHH251H22 21012 123277001 SBFVE-B-C 104471046 102540004 119103001 24464232 204464208
RHH301H22 21012 123277001 SBFVE-C-C 104471046 102540004 119103001 24464232 204464208
RHH401H22 21012 123277001 SBFVE-C-C 104471047 205051004 213266000 24464232 204464208
RHH500H22 21012 123277001 SBFVE-C-C 104471047 205051004 213266000 24464232 204464208
RHH050M44 21012 123277001 SBFSE-A-C 104471048 102540004 119103001 24464232 204464208
RHH075M44 21012 123277001 SBFSE-A-C 104471048 102540004 119103001 24464232 204464208
RHH101M44 21012 123277001 SBFSE-B-C 104471048 102540004 119103001 24464232 204464208
RHH150M44 21012 123277001 SBFSE-B-C 104471049 102540004 119103001 24464232 204464208
RHH201M44 21012 123277001 SBFSE-C-C 104471049 102540004 119103001 24464232 204464208
RHH300M44 21012 123277001 SBFSE-C-C 104471046 102540004 119103001 24464232 204464208
RHH400M44 16506 123277002 EBSSE-6-C 104471047 205051004 213266000 24464232 204464208
RHS050H22 21012 123277001 SBFVE-AA-C 104471048 102540004 119103001 24464232 204464208
RHS075H22 21012 123277001 SBFVE-AA-C 104471048 102540004 119103001 24464232 204464208
RHS100H22 21012 123277001 SBFVE-A-C 104471048 102540004 119103001 24464232 204464208
RHS150H22 21012 123277001 SBFVE-A-C 104471049 102540004 119103001 24464232 204464208
RHS200H22 21012 123277001 SBFVE-B-C 104471049 102540004 119103001 24464232 204464208
RHS300H22 21012 123277001 SBFVE-C-C 104471046 102540004 119103001 24464232 204464208
RHS400H22 21012 123277001 SBFVE-C-C 104471047 205051004 213266000 24464232 204464208
RHS050M44 21012 123277001 SBFSE-A-C 104471048 102540004 119103001 24464232 204464208
RHS100M44 21012 123277001 SBFSE-A-C 104471048 102540004 119103001 24464232 204464208
RHS200M44 21012 123277001 SBFSE-B-C 104471049 102540004 119103001 24464232 204464208
RHS300M44 21012 123277001 SBFSE-C-C 104471046 102540004 119103001 24464232 204464208
RHS400M44 16506 123277002 EBSSE-6-C 104471047 205051004 213266000 24464232 204464208
RHO200M44 21012 123277001 SBFSE-C-C 104471049 205051004 213266000 24464232 204464208
RHO250M44 21012 123277001 SBFSE-C-C 104471046 205051004 213266000 24464232 204464208
RHO300M44 21012 123277001 SBFSE-C-C 104471046 205051004 213266000 24464232 204464208
RHO301M44 16506 123277002 EBSSE-6-C 104471046 205051004 213266000 24464232 204464208
RHO400M44 16506 123277002 EBSSE-6-C 104471047 205051004 213266000 24464232 204464208
RHO500M44 16506 123277002 EBSSE-6-C 104471047 205051004 213266000 24464232 204464208
RHO600M44 21054 123277003 EBSSE-6-C 104471047 205051004 213266000 24464232 204464208
RHO650M44 21000 123277004 EBSSE-7 1/2-C 104471066 205051004 213266000 24464232 204464208
* Parts selection may vary based upon specific operating conditions.
Medium Temp models are only available for warm ambient locations.
13
Comp.
Type
Typical High Sierra replacement parts- D-Series and V-Series Medium Temp. Models*
Model
Number
DHD5H22
DHD7H22
DHD8H22
DHD10H22
DHD12H22
DHD5M44
DHD6M44
DHD7M44
DHD8M44
DHD10M44
DHD12M44
DHO6M44
DHO7M44
DHO8M44
DHO10M44
DHO13M44
Reversing
Valve
16506
21054
21054
21054
21000
21054
21054
21054
21000
21000
21049
16506
21054
21054
21000
21000
Rev. Valve
Strainer
123277002
123277003
123277003
123277003
123277004
123277003
123277003
123277003
123277004
123277004
123277005
123277002
123277003
123277003
123277004
123277004
Cond. Unit
TXV
Bi-Flo
†
Liquid Filter
Condenser
230V Motor Blade
Low Pres.
Control
High Pres.
Control
Fan Cycle
Control
EBSVE-8-C 104471066 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSVE-11-C 104471066 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSVE-11-C 104471066 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSVE-15-C 104471193 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSVE-15-C 104471193 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSSE-10-C 104471066 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSSE-10-C 104471066 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSSE-10-C 104471066 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSSE-13-C 104471066 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSSE-13-C 104471193 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSSE-13-C 104471193 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSSE-7 1/2-C 104471047 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSSE-10-C 104471066 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSSE-10-C 104471066 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSSE-13-C 104471193 205051004 213266000 204464041 Hi/Lo Combo 204464002
EBSSE-13-C 104471193 205051004 213266000 204464041 Hi/Lo Combo 204464002
VHD15H22
VHD20H22
VHD25H22
VHD30H22
VHD35H22
VHD40H22
VHD50H22
VHD60H22
VHD70H22
VHD80H22
VHD15M44
VHD20M44
VHD25M44
VHD30M44
VHD35M44
VHD40M44
VHD50M44
VHD60M44
VHD70M44
21000
21049
21049
21049
21055
21055
21055
21056
21056
21057
21049
21049
21055
21055
21055
21056
21056
21056
21057
123277004
123277005
123277005
123277005
EBSVE-20-C 104471021
†
EBSVE-20-C 104471021
†
OVE-30-C
OVE-30-C
104471021
†
104471022
†
123277005
123277005
OVE-40-C
OVE-40-C
104471031
†
104471031
†
123277005 (2) OVE-30-C 104471031
†
Contact Factory (2) OVE-30-C 104471032
†
Contact Factory (2) OVE-40-C 104471033
†
Contact Factory (2) OVE-40-C 104471033
†
123277005
123277005
123277005
123277005
123277005
Contact Factory
Contact Factory
Contact Factory
OSE-21-C
OSE-21-C
OSE-30-C
OSE-30-C
OSE-30-C
OSE-35-C
OSE-45-C
OSE-45-C
104471021
†
104471021
†
104471021
†
104471022
†
104471031
†
104471031
†
104471031
†
104471032
†
Contact Factory (2) OSE-30-C 104471033
†
Contact Factory (2) OSE-35-C 104471033
†
110204000
110204000
110204000
110204000
110204000
110204000
110204000
110204000
110204000
110204000
110204000
110204000
110204000
110204000
110204000
110204000
110204000
110204000
110204000
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
210385000 204464041 Hi/Lo Combo 204464002
VHD80M44 21057 110204000 210385000 204464041 Hi/Lo Combo 204464002
* Parts selection may vary based upon specific operating conditions.
† V-Series filter is not Bi-Flow Design. Part number is for replaceable core filter (shell only). Core Part# 14471034 (may require more than one core)
Medium Temp models are only available for warm ambient locations.
14
MODEL NUMBER
ALL MODELS
ALL MODELS
ALL MODELS
ALL MODELS
ALL MODELS (OPTIONAL)
ALL "AE" MODELS
ALL "AE" MODELS
1 - 6 FAN AE MODELS
AE14-37B, AE16-36B,
AE16-41B, AE16-46B
AE24-72B, AE24-85B,
AE26-92B
AE26-60B, AE26-75B
AE34-105B, AE36-120B,
AE36-140B
AE44-140B, AE46-164B,
AE46-185B
AE54-180B, AE56-210B
AE64-215B, AE66-245B,
AE66-280B
ALL-TEMP²B - MODELS AA, AE (AFTER APRIL, 2004 )
MOTOR, SHADED POLE, 1/20 HP, 1550 RPM, 115 V.
MOTOR, SHADED POLE, 1/20 HP, 1550 RPM, 208-230 V.
MOTOR, SHADED POLE, 1/20 HP, 1550 RPM, 460 V.
PART NUM.
102540003
102540004
102540005
FAN GUARD, PLASTIC, BLACK, 12"
FAN GUARD, WIRE, EPOXY COATED, BLACK, 12"
MOTOR MOUNT
MOTOR, PSC, 1/20 HP, 1550 RPM, 115 V., (3 MFD CAPACITOR NOT INCL.)
MOTOR, PSC, 1/20 HP, 1550 RPM, 230 V., (2 MFD CAPACITOR NOT INCL.)
CAPACITOR, 3 MFD, FOR 1/20 115 V. PSC MOTOR
CAPACITOR, 2 MFD, FOR 1/20 230 V. PSC MOTOR
DEFROST CONTROL, DEFROST TERMINATION, (TIMER RESET) 2 WIRE
DEFROST CONTROL, FAN DELAY, 2 WIRE
HEATER SAFETY SWITCH, 2 WIRE
DEFROST HEATER, CORE, 500 WATTS, 26-1/4" LENGTH, 208-230/460 V.
119647000
201006011
21062000
108178001
108178002
202163010
202163009
103079010
103079009
103079003
206240006
DEFROST HEATER, DRAIN PAN, 500 WATTS, 21" LENGTH, 208-230/460 V.
200172042
DEFROST HEATER, CORE, 1000 WATTS, 44-1/4" LENGTH, 208-230/460 V.
206240008
DEFROST HEATER, DRAIN PAN, 1000 WATTS, 39" LENGTH, 208-230/460 V.
200172044
DEFROST HEATER, CORE, 800 WATTS, 40-1/4" LENGTH, 208-230/460 V.
206240007
DEFROST HEATER, DRAIN PAN, 800 WATTS, 35" LENGTH, 208-230/460 V.
200172043
DEFROST HEATER, CORE, 1500 WATTS, 62-1/4" LENGTH, 208-230/460 V.
206240009
DEFROST HEATER, DRAIN PAN, 1500 WATTS, 57" LENGTH, 208-230/460 V.
200172045
DEFROST HEATER, CORE, 2000 WATTS, 80-1/4" LENGTH, 208-230/460 V.
206240010
DEFROST HEATER, DRAIN PAN, 2000 WATTS, 75" LENGTH, 208-230/460 V.
200172046
DEFROST HEATER, CORE, 2500 WATTS, 97-3/4" LENGTH, 208-230 V.
206240011
DEFROST HEATER, DRAIN PAN, 2500 WATTS, 93" LENGTH, 208-230/460 V.
200172047
DEFROST HEATER, CORE, 3000 WATTS, 115-3/4" LENGTH, 208-230/460 V.
206240012
DEFROST HEATER, DRAIN PAN, 3000 WATTS, 111" LENGTH, 208-230/460 V. 200172048
1 FAN AA, & AE MODELS
AA28-76B, -97B, -122B,
ALL-TEMP²B - HINGED END PANEL UNITS (AFTER APRIL, 2004 )
VENTURI, 20" LENGTH
AA26-70B, -87B, AE26-60B,
AE26-75B
AA28-106B, -134B, AA26-115B
AE26-92B, AE24-85B
3 FAN AA & AE MODELS
4 FAN AA & AE MODELS*
5 FAN AA & AE MODELS*
6 FAN AA & AE MODELS*
1 FAN AA, & AE MODELS
AA28-76B, -97B, -122B,
AA26-70B, -87B, AE26-60B,
AE26-75B
AA28-106B, -134B, AA26-115B
AE26-92B, AE24-85B
3 FAN AA & AE MODELS
4 FAN AA & AE MODELS*
5 FAN AA & AE MODELS*
6 FAN AA & AE MODELS*
SHORT
LONG
ACF Model 1 Fan Evaps
ACF Model 2 Fan (Short) Evaps
ACF Model 2 Fan (Long) Evaps
ACF Model 3 Fan Evaps
ACF Model 4 Fan Evaps
ACF Model 5 Fan Evaps
VENTURI, 34" LENGTH
VENTURI, 38" LENGTH
VENTURI, 56" LENGTH
VENTURI, 74" LENGTH
VENTURI, 92" LENGTH
VENTURI, 110" LENGTH
DRAIN PAN, 27" LENGTH
DRAIN PAN, 41" LENGTH
DRAIN PAN, 45" LENGTH
DRAIN PAN, 63" LENGTH
DRAIN PAN, 81" LENGTH
DRAIN PAN, 99" LENGTH
DRAIN PAN, 117" LENGTH
HINGED END PANEL
HINGED END PANEL
Hot Gas Drain Pan Assembly w/ loop
Hot Gas Drain Pan Assembly w/ loop
Hot Gas Drain Pan Assembly w/ loop
Hot Gas Drain Pan Assembly w/ loop
Hot Gas Drain Pan Assembly w/ loop
Hot Gas Drain Pan Assembly w/ loop
15
8519104
8519241
8519242
8519243
8519244
8519245
8519246
8519592
8519593
8519594
8519595
8519596
8519597
8519598
8518612
8518613
12297800
12297900
12298000
12298100
12298200
12298300
High Sierra Systems
Additional Service, Installation and Trouble Shooting Tips
In the event of freezing drain pan Problems: Check the following
1. Verify that the unit cooler has been installed in a way insuring the drain pan is slightly pitched towards the drain connection. This will provide positive drainage of the condensate.
2. The surface of the drain pan must be touching the Hot Gas drain pan tubes, located in the bottom of the unit cooler. Later model units have the drain pan loops welded to the drain pan.
3. The High Sierra system has a time initiated and pressure terminated defrost. The pressure switch is factory set at 250# Cut In pressure and 200# Cut Out pressure. If the 250 pound setting does not clear the coil, the setting may be raised to a higher pressure, but no higher than 300 pounds (use high pressure gauge for this check). The time clock should have a maximum of (3) three defrosts per 24 hours. (We suggest the clock be set for 1 to 2 defrosts per 24 hours). The time clock fail safe should be set at 10 minutes maximum. 1 to 2 defrosts per 24 hours will ensure a longer defrost, 3-5 minutes in length.
4. The evaporator fans should have a two minute delay after defrost. This control is located in the condensing unit control panel. If the delay setting is less than two minutes, it should be corrected.
5. Check drain pan for straightness, if warped, the pan may have to be replaced.
6. Check the Hot Gas Loop, it should be straight and must make contact with the drain pan.
7. Evaporator Drain lines must be installed with copper tubing, wrapped with heat tape, insulated and trapped. The trap should be located outside of the freezer.
8. Superheat setting must be checked, 8°F @ coil, 20°F to 40°F at the compressor.
9. Refrigerant charge, charge to clear sight glass after room is within 10° of desired temperature.
DO NOT OVER CHARGE.
10. Check the expansion valve bulb on the outdoor unit, it must be clamped tightly in the proper location.
11. Fan Cycling control, Fan on at 90 psi. off at 60 psi.
Russell High Sierra System Data Sheet
Date: ____________ Contractor: ______________________________
High Sierra C.U. Model #_____________________ Serial # ____________________
Evaporator Coil Model #______________________ Serial # ____________________
1. Discharge pressure before defrost _________lbs.
After defrost _______________ lbs.
2. Suction pressure before defrost _________ lbs.
3. Superheat @ Coil before defrost _________ °F
After defrost _______________ lbs.
After defrost_______________°F
4. Compressor Superheat before defrost _________°F After defrost_______________°F
5. Sight glass condition before _________ after defrost___________ (clear or bubbles)
6. Suction Temperature reading across reversing valve IN__________ OUT__________
7. How long did the defrost last _____ Time clock fail safe setting ______
8. What was the defrost termination pressure ___________ lbs.
9. How many defrosts per day__________
10.Coil condition after defrost _____________________________
11. Condenser fan cycling control: Cut in ________ Cut Out ________
12. Fan Delay setting (should be no less than 2 minutes in duration) _____________ www.russellcoil.com
221 S. BERRY ST. BREA, CA. 92822-1030 TEL. (714) 529-1935 FAX (714) 529-7203
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project