Chromalox UB-2002E Air Conditioner User Manual

Installation, Operation
SERVICE REFERENCE
DIVISION
and
4
SALES
REFERENCE
RENEWAL PARTS IDENTIFICATION
SECTION
UB
PF417-14
(Supersedes PF417-13)
161-048445-001
DATE
July, 2002
Type UB-1002E, UB-1252E, UB-1502E, UB-2002E
Forced-Air Heaters
Dimensions —
Ceiling Line
17-1/8”
13-3/4”
Back
Wall
For Lower Height
from Ceiling:
Customer to Add
Extention Strap
20-3/4”
8”
Rubber Feet Provided for
Wall Mount Model Only.
6” Min. Spacing to
Adjacent Wall
4-7/8”
Min.
Wall
Mounting
Holes Center
12-1/4”
6”
9-5/16”
3”
/4”
11-3
10”
11-3/4”
7/8” and 1-23/32”
Dia. Holes in Rear
8”
17-11/16”
Figure 2
Mounting UB using Wall
Mounting Brackets*
Figure 1
Mounting UB using
Ceiling Mounting
Brackets*
7’-0” Min. Height
Above Floor
*Wall and/or Ceiling Mounting Brackets are
available as an accessory option — Contact
your local sales representative.
7’-0” Min.
Height Above
Floor
Specifications —
Model ‡
Volts and Phase
kW
Horizontal
Air
Discharge
40’
UB-1002E
208 - 240 - 480 (1 or 3)
10
UB-1252E
208 (3) - 240 (3) - 480 (1 or 3)
12.5
40’
UB-1502E
208 (3) - 240 (1 or 3) - 480 (1 or 3)
15
45’
UB-2002E
240 (1 or 3)
19.9
45’
UB-2002E
208 (3) - 480 (1 or 3)
20
45’
‡ Models with suffix “T” added (480 volts only) are equipped with a transformer, 480 volt primary — 120/240 volt secondary.
‡ Models with suffix “R” added are equipped with a relay (Example: UB-1002E-R 240 volt or 480 volt — 3 phase only).
MOUNTING
WARNING: Hazard of Electric Shock. Disconnect all
power before installing heater.
Note: These heaters are designed for wall or ceiling mounting
only. Other modes of mounting voids factory warranty.
1. Height above floor
A. In areas where ceiling height is more than 12 feet, recommended mounting height is approximately 10 feet to underside of heater.
B. For ceiling heights of 12 feet or less, maximum mounting
height is determined by use of ceiling mounting brackets
offered for these heaters. Minimum spacing to ceiling is 3”
(see Figure 2).
© 2010 Chromalox®, Inc.
C. In either case, minimum mounting height is 7 feet from
floor to bottom of heater (see Figures 1 and 2).
2. Spacing to adjacent walls
A. Rear of case to back wall 4-7/8” minimum (see Figure 2).
B. Side of case to side wall 6” minimum (see Figure 2).
3. If two or more units are operated in the same enclosed space,
their discharges should be directed to aid in development of
mass air movement for uniform heat dispersal.
4. Controlling thermostats to individual heaters should be
mounted at shoulder height on inside walls or columns.
WIRING
Note: All wiring should be done in accordance with local codes
and the National Electrical Code by a qualified person.
WARNING: Hazard of Electric Shock. Any installation involving electric heaters must be effectively
grounded in accordance with the National
Electrical Code to eliminate shock hazard.
1. Connect heater according to the voltage and frequency specified on the nameplate and using the appropriate wiring diagram
(Figures 3 thru 7).
Note: Be sure to check voltage rating of the fan motor which is
either 120, 208 or 240 volt, single phase since heater circuit could
be 480 volts, single or three phase.
2. If an external transformer is used to step down the voltage for operating the fan motor, use appropriate wiring diagram (Figures 3, 5
or 7).
3. Heaters are not provided with a control switch and should be
controlled by a magnetic contactor (integral or external) and a
separately mounted thermostat. External contactor is not necessary with heaters having a model number suffixed with the
letter “R”.
4. Protection against overheating is provided by an internal automatic thermal cutout which opens the electric circuit if the normal air-flow is restricted or stopped. Cutout automatically
energizes heater on removal of the obstruction.
WARNING: Users should install adequate back-up
controls and safety devices with their electric
heating equipment. Where the consequences of
failure may be severe, back-up controls are essential. Although the safety of installation is the
responsibility of the user, Chromalox will be glad to
make equipment recommendations.
OPERATION
DANGER:
1. Do not restrict air-flow through the heater by
placing fabric or other obstructions in front of or
behind the heaters. With some combustible
materials, the resulting high discharge temperatures could cause a fire.
2. This heater is not intended for use in hazardous
atmospheres where flammable vapors, gases, liquids or other combustible atmospheres are present
as defined in the National Electrical Code. Failure
to comply can result in explosion or fire. For these
applications see PDS CXH-EP (PF305).
MAINTENANCE
WARNING: Turn off all power to service heater. Do
not attempt to service heater while unit is operating
as there is hazard of electric shock, injury from
operating fan and burns from hot heating elements.
1. Fan motors in these heaters are provided with sealed ball bearings, factory lubricated, requiring no further lubrication under
normal service conditions.
2. Following long periods of idleness, heater should be vacuumed
before start-up, to remove accumulated combustible particles
which otherwise may smoke or incinerate on initial heat up.
3. Periodically inspect all electrical connections and terminals to
avoid electrical wiring difficulties. Inspect all wiring for frayed
or worn insulation.
WIRING DIAGRAMS
Figure 3
Use with:
UB-1002E
208V, 1Ø or 3Ø
240V, 1Ø
480V, 1Ø or 3Ø
UB-1252E
208V, 3Ø
240V, 3Ø
480V, 1Ø or 3Ø
UB-1502E
208V, 3Ø
240V, 3Ø
480V, 1Ø or 3Ø
UB-2002E
480V, 1Ø or 3Ø
240V, 1Ø or 3Ø
Control Source for
Separately Wired Motors
120 or 240 Volts, 60 Cycle
}
1 or 3 Phase, 60 Cycle
Power Supply 208, 240
or 480 Volts
Heater Bank
1Ø Motor
Cutout
Heater
Fused
Control Switch
Fused
Switch
Contactor
Ground
Wiring Comp't
Baffle
This Wiring
by Customer
F1
F2
T1
Thermostat When Used
L1
L2
L3
For 3 Phase Only
WIRING DIAGRAMS
Figure 4
Use with:
UB-1002E-T
480V, 1Ø or 3Ø
}
UB-1252E-T
480V, 1Ø or 3Ø
Fused
Switch
1 or 3 Phase, 60 Cycle
Power Supply 480 Volts
Alternate 240V Wiring
X4
X3
X2
X1
Heater Bank
Integral 480V/240V
or 120V Transformer
1Ø Motor
120V Wiring
X3 X2
X1
X4
Contactor
UB-1502E-T
480V, 1Ø or 3Ø
Heater
Thermal
Cutout
Control
Switch Optional
UB-2002E-T
480V, 1Ø or 3Ø
H2
Ground
This Wiring
by Customer
Thermostat
When Used
H1
Transformer
Fusing
Wiring Comp't
Baffle
C1
T1
T2
F1
F2
For 3 Phase Only
L1
L2
L3
Figure 5
Use with:
UB-1002E-R
208V, 1Ø or 3Ø
240V, 1Ø or 3Ø
480V, 1Ø or 3Ø
UB-1252E-R
208V, 3Ø
240V, 3Ø
480V, 1Ø or 3Ø
}
1 or 3 Phase, 60 Cycle Power
Supply 208, 240 or 480 Volts
Heater Bank
1Ø Motor
Heater
Fused
Switch
Control
Source 120 or
240 Volts, 60 Cycle
Integral
Cutout
Cutout
UB-1502E-R
208V, 3Ø
240V, 3Ø
480V, 1Ø or 3Ø
Fused
Control Switch
Thermostat
When Used
This Wiring
by Customer
Ground
Wiring Comp't
Baffle
C1
C2
L1
L2
L3
UB-2002E-R
480V, 1Ø or 3Ø
240V, 3Ø
For 3 Phase Only
Figure 6
Use with:
UB-1002E-TR
480V, 1Ø or 3Ø
}
Alternate 240V Wiring
1 or 3 Phase, 60 Cycle Power
Supply 480 Volts
X1
UB-1252E-TR
480V, 1Ø or 3Ø
UB-1502E-TR
480V, 1Ø or 3Ø
UB-2002E-TR
480V, 1Ø or 3Ø
X3
X2
X4
1Ø Motor
Heater Bank
Cutout
Integral 480V/240V
or 120V Transformer
120V Wiring
X1
X3
X2
Heater
X4
Fused
Switch
Integral
Cutout
H1
H2
Control
Switch Optional
Thermostat
When Used
Ground
This Wiring
by Customers
Wiring Comp't
Baffle
T1
T2
C1
C2
L1
For 3 Phase Only
L2
L3
Transformer
Fusing
WIRING DIAGRAMS
Figure 7
Use with:
UB-1002E-R
208V, 1Ø or 3Ø
240V, 1Ø or 3Ø
UB-1252E-R
208V, 3Ø
240V, 3Ø
UB-1502E-R
208V, 3Ø
240V, 3Ø
}
1 or 3 Phase, 60 Cycle
Power Supply 208 or 240 Volts
1Ø Motor
Heater
Fused
Switch
Thermostat
When Used
This Wiring
bny Customer
Ground
Heater Bank
Cutout
Integral
Contactor
Wiring Comp't
Baffle
T1
T2
L1
L2
L3
For 3 Phase Only
RENEWAL PARTS IDENTIFICATION
1
2 MOTORS
3
4
8
120V
208V
240V
Fan
Thermal
Cutout
Transformer
118-045311-001 (3)
193-302120-009
193-302120-009
—————
112-045422-001
300-049200-002 1 (1)
300-049200-002 3 (1)
—————
1 or 3
118-045311-002 (3)
193-302120-009
—————
193-302120-009
112-045422-001
300-049200-002 1 (1)
300-049200-002 3 (1)
—————
480
1 or 3
118-045311-003 (3)
193-302120-009
—————
193-302120-009
112-045422-001
300-049200-002 1 (1)
300-049200-002 1 (1)
315-303675-001
208
3
118-045311-004 (3)
193-302120-009
193-302120-009
—————
112-045422-001
300-049200-002 3 (1)
—————
—————
Model
Volts
Phase
Heating
Element
UB-1002E
208
1 or 3
UB-1002E
240
UB-1002E*
UB-1252E
UB-1252E
240
1 or 3
118-045311-005 (3)
193-302120-009
—————
193-302120-009
112-045422-001
300-049200-002 1 (1)
300-049200-002 3 (1)
UB-1252E*
480
1 or 3
118-045311-006 (3)
193-302120-009
—————
193-302120-009
112-045422-001
300-049200-002 1 (1)
300-049200-002 3 (1)
315-303675-001
UB-1502E
208
3
118-045307-001 (3)
193-302120-009
193-302120-009
—————
112-045422-002
300-049200-006 3 (1)
—————
112-045422-002
300-049200-006 1 (1)
300-049200-006 3 (1)
—————
UB-1502E
240
1 or 3
118-045307-002 (3)
UB-1502E*
480
1 or 3
118-045307-003 (3)
UB-2002E
208
3
118-045307-004 (3)
193-302120-009
—————
193-302120-009
193-302120-009
—————
193-302120-009
112-045422-002
300-049200-006 (1)
315-303675-001
193-302120-009
193-302120-009
—————
112-045422-002
300-049200-006 (1)
—————
—————
315-303675-001
UB-2002E
240
1 or 3
118-045307-009 (3)
193-302120-009
—————
193-302120-009
112-045422-002
300-049200-006 1 (1)
300-049200-006 3 (1)
UB-2002E*
480
1 or 3
118-045307-006 (3)
193-302120-009
—————
193-302120-009
112-045422-002
300-049200-006 (1)
Note: Part numbers suffixed by a number in ( ) indicates quantity of same part number used.
*Note: Fuse 3A 600V KTK-3 — 128-047763-007 (2)
Fuse BLK Barrier — 129-048475-001 (1)
Fuse Block — 129-048473-001 (2)
RENEWAL PARTS IDENTIFICATION
9 RELAYS
Model
Volts
Phase
kW
Motor
Relay
Model
Volts
Phase
kW
Motor
Relay
UB-1002E
UB-1002E
UB-1002E
UB-1002E
UB-1002E
UB-1002E
UB-1002E
UB-1002E
UB-1002E
UB-1002E
UB-1002E
UB-1002E
UB-1252E
UB-1252E
UB-1252E
UB-1252E
UB-1252E
UB-1252E
UB-1252E
UB-1252E
208
208
208
208
240
240
240
240
480
480
480
480
208
208
240
240
480
480
480
480
1
1
3
3
1
1
3
3
1
1
3
3
3
3
3
3
1
1
3
3
10
10
10
10
10
10
10
10
10
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
120V
208V
120V
208V
120V
240V
120V
240V
120V
240V
120V
240V
120V
240V
120V
240V
120V
240V
120V
240V
072-303180-008
072-303180-014
072-303180-007
072-303180-013
072-303180-008
072-303180-014
072-303180-007
072-303180-013
072-303180-011
072-304551-015
072-303180-007
072-303180-013
072-303180-008
072-303180-014
072-303180-008
072-303180-014
072-303180-011
072-304551-015
072-303180-007
072-303180-013
UB-1502E
UB-1502E
UB-1502E
UB-1502E
UB-1502E
UB-1502E
UB-1502E
UB-1502E
UB-2002E
UB-2002E
UB-2002E
UB-2002E
UB-2002E
UB-2002E
UB-2002E
UB-2002E
UB-2002E
UB-2002E
208
208
240
240
480
480
480
480
208
208
240
240
240
240
480
480
480
480
3
3
3
3
1
1
3
3
3
3
1
1
3
3
1
1
3
3
15
15
15
15
15
15
15
15
20
20
19.9
19.9
19.9
19.9
20
20
20
20
120V
240V
120V
240V
120V
240V
120V
240V
120V
208V
120V
240V
120V
240V
120V
240V
120V
240V
072-303180-008
072-303180-014
072-303180-008
072-303180-014
072-303180-008
072-303180-014
072-303180-007
072-303180-013
——————
——————
——————
——————
072-303180-008
072-303180-014
072-303180-008
072-303180-014
072-303180-007
072-303180-013
PARTS COMMON TO ALL HEATERS
5 Wall Bracket Set . . . . . . . . . . . . . . . . . . . . . . .168-026844-003
6 Ceiling Mounting Support (Includes 7 ) . . . . .027-044419-003
7 Ceiling Suspension Brackets . . . . . . . . . . . . . .027-033363-001 (2)
10 Louver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .182-047073-003
11 Grille . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134-119147-003
12 Motor Mounting Frame . . . . . . . . . . . . . . . . . .194-045314-001
Note: Part Numbers suffixed by a number in ( ) indicates quantity of same part number used.
Limited Warranty:
Please refer to the Chromalox limited warranty applicable to this product at
http://www.chromalox.com/customer-service/policies/termsofsale.aspx.
2150 N. RULON WHITE BLVD., OGDEN, UT 84404
Phone: 1-800-368-2493