Data Sheet | ABB SD/S x.16.1 Switch/Dim Actuators Datenblatt

Add to My manuals
4 Pages

Below you will find brief information for Switch/Dim Actuators SD/S x.16.1. The SD/S x.16.1 is a modular installation device for EIB/KNX bus systems. It features a bus connection terminal for integration into the distribution board and allows for control of up to 8 dimmable electronic ballast devices or transformers. Each channel of the device includes a load relay that can be manually operated (on/off) via a push-button, which simultaneously indicates the switch status.

advertisement

ABB Switch/Dim Actuators SD/S x.16.1 Datasheet | Manualzz

ABB i-bus ® EIB / KNX Switch/Dim Actuators SD/S x.16.1

2CDG 110 079 R0011, 2CDG 110 080 R0011,

2CDG 110 081 R0011

The ABB i-bus ® Switch/Dim Actuators with a rated current of 16 A are

EIB / KNX modular installation devices in ProM design for installation in the distribution board on 35 mm mounting rails. The connection to the ABB i-bus ® is implemented via a bus connection terminal.

The SD/S controls via 2-, 4- or

8-channel dimmable electronic ballast devices or transformers with 1 – 10 V control interfaces.

Per channel the load relay can be manually operated (on/off) via operating element which simultaneously indicates the switch status.

The switching relays are particularly suitable for switching ohmic loads, inductive and capacitive loads as well as fl uorescent lamp loads (AX) to

EN 60 669.

The switching relays can be switched on or off manually without a bus or auxiliary voltage. The operating element simultaneously indicates the switch status.

The devices are powered via the

EIB / KNX and do not require and additional power supply.

8

Technical data

Power supply

Outputs control circuit

Outputs load circuit rated values

Load circuit (relay) switching currents

Load circuit (relay) service life

Load circuit (relays) switching times 1)

– Operating voltage

– Current consumption EIB / KNX

– Power consumption via EIB / KNX

– SD/S-type

– Number of control outpute 1 – 10 V (passive)

– Max. current per control output

– Max. number of ballast devices (2 mA/ballast) 3)

– Max. cable length, with max. load (100 mA)

2.16.1 4.16.1 8.16.1

2 4 8

100 mA 100 mA 100 mA

50 50 50

70 m with cable cross-section 0.8 mm 2

100 m with cable cross-section 1.5 mm 2

– SD/S-type

– Number of load outputs (floating)

– U n

rated voltage

– I n

rated current

– Power loss per device at max. load

– AC1 operation (cos ϕ = 0.8) IEC 60 947-4-1

– Fluorescent lighting load AX acc. EN 60 669-1

– Minimum switching performance

– DC current switching capacity (ohmic load)

– Lamp loads

– mechanical endurance

– electrical endurance to IEC 60 947-4-1

– AC1 (240 V/cos ϕ = 0.8)

– AC5a (240 V/cos ϕ = 0.45)

21 ... 30 V DC, made available by the bus

2.16.1 4.16.1 8.16.1

8.5 mA 9 mA

Max. 250 mW

9.5 mA maximum

2.16.1 4.16.1 8.16.1

2 4 8

250 / 440 V AC (50/60 Hz)

16 A - AC 1 or 10 AX

2.6 W

16 A / 230 V

10 AX / 250 V (140

μF)

2)

100 mA / 12 V

100 mA / 24 V

10 A / 24 V =

See table 2

> 3 x 10 6

> 10 5

> 3 x 10 4

5.2 W 10.4 W

– Max. relay position change per output and

minute if all relays are switched

simultaneously object. The position changes

should be distributed over a minute.

– Max. relay position change per output

and minute if only one relay is switched

2.16.1 4.16.1 8.16.1

60 30 15

120 120 120

1) The specifi cations apply only after the bus voltage has been applied to the device for at least 30 seconds.

The typical elementary delay of the relay is approx. 20 ms.

2) The maximum inrush-current peak (see table 3) may not be exceeded

3) The control current of 1 – 10 V devices determine the number of connectable ballast devices. Typical devices are between 0.4 … 4 mA.

Table 1 - Part 1: Switch/Dim Actuators SD/S x.16.1, technical data

8

SD/S x.16.1

Page 1 of 4

SDS_x161_TD_EN_V1-0

2CDC 507 067 D0201

SD/S x.16.1

8

ABB i-bus ® EIB / KNX Switch/Dim Actuators SD/S x.16.1

2CDG 110 079 R0011, 2CDG 110 080 R0011,

2CDG 110 081 R0011

Technical data (Continuation from page 1)

Connections: ABB i-bus ® – EIB / KNX

Connections: control circuit – 2 terminals per control circuit

Connections: load circuit

– sleeves without/with plastic

– TWIN sleeves

– Tightening torque

– 2 terminals per load circuit

– sleeves without/with plastic

– TWIN sleeves

– Tightening torque

Operating and display elements

Enclosure

Safety class

Isolation category

EIB / KNX safety extra low voltage

Temperature range

Environmental conditions

– Red LED and EIB / KNX push button

– Switch position display

– IP 20

– II

– Overvoltage category

– Pollution degree

– SELV 24 V DC

– Operation

– Storage

– Transport

– humidity

Design – Modular installation device (MDRC))

– SD/S-type

– Dimensions (H x W x D)

– Width W in mm

– Mounting width (modules at 18 mm)

– Mounting depth in mm

Weight

Installation

Mounting position

Housing, colour

Approvals

CE mark

– On 35 mm mounting rail

– as required

– Plastic housing, grey

– EIB / KNX to EN 50 090-2-2 low voltage guideline

Table 1 - Part 2: Switch/Dim Actuators SD/S x.16.1, technical data

Bus connection terminal,

0.8 mm Ø, single core

Screw terminal with slotted screw

0.2 ... 2 mm 2 finely stranded

0.2 ... 4 mm 2 single core

0.25 … 2.5 / 0.25 … 4 mm 2

0.5 – 2.5 mm 2

Contact pin length min. 8 mm

Max. 0.6 Nm

Screw terminal with universal head (PZ 1)

0.2 ... 4 mm 2 finely stranded,

2 x (0.2 – 2.5 mm 2 )

0.2 ... 6 mm 2 single core,

2 x (0.2 – 4 mm 2 )

0.25 … 2,5 / 0.25 … 4 mm 2

0.5 – 2.5 mm 2

Contact pin length min. 8 mm

Max. 0.8 Nm for assignment of the physical address

Relay operator to EN 60 529 to EN 61 140

III to EN 60 664-1

2 to EN 60 664-1

– 5 °C ... + 45 °C

– 25 °C ... + 55 °C

– 25 °C ... + 70 °C

Max. 93%, moisture condensation should be excluded

Modular installation device, ProM

2.16.1 4.16.1 8.16.1

90 x W x 64,5

4 6 8

64.5 64.5 64.5

0.18 0.28 0.46

EN 60 715

Certification

Note:

Note:

Note:

Connection of 230 mains voltage to one of the 1 – 10 V outputs leads to the destruction of the 1 – 10 V output.

Control, load and EIB / KNX sides are electrically isolated. Individual switching outputs are fl oating outputs. When connecting the control line it is important to consider that the control outputs each feature a common reference ground with one another.

Several electronic ballast devices with 1 – 10 V interfaces can be controlled with a channel of the Switch/Dim Actuators. The number of dimmable ballast devices per channel is limited both by the switching and the control powers of the

Switch/Dim Actuator. See description in the product manual.

8

SD/S x.16.1

Page 2 of 4

SDS_x161_TD_EN_V1-0

2CDC 507 067 D0201

SD/S x.16.1

ABB i-bus ® EIB / KNX Switch/Dim Actuators SD/S x.16.1

2CDG 110 079 R0011, 2CDG 110 080 R0011,

2CDG 110 081 R0011

8

Lamp loads, switching powers for lamp circuit

Lamps

Fluorescent lamps T5 / T8

Low-volt halogen lamps

Dulux lamp

Mercury-vapour lamp

Switching capacity (switching contact)

Number of electronic ballast devices

(T5/T8, single element) 1)

1)

– Incandescent lamp load

– Uncorrected luminaire

– Parallel compensated

– DUO circuit

– Inductive transformer

– Electronic transformer

– Halogen lamp 230 V

– Uncorrected luminaire

– Parallel compensated

– Uncorrected luminaire

– Parallel compensated

– Max. peak inrush-current Ip (150

μs)

– Max. peak inrush-current Ip (250

μs)

– Max. peak inrush-current Ip (600

μs)

– 18 W (ABB EVG 1 x 58 CF)

– 24 W (ABB EVG-T5 1 x 24 CY)

– 36 W (ABB EVG 1 x 36 CF)

– 58 W (ABB EVG 1 x 58 CF)

– 80 W (Helvar EL 1 x 80 SC)

2300 W

2300 W

1500 W

1500 W

1200 W

1500 W

2300 W

1100 W

1100 W

2000 W

2000 W

400 A

320 A

200 A

23

23

14

11

10

1) For multiple element lamps or other types the number of electronic ballast devices must be determined using the peak inrush current of the electronic ballast devices. See description in the product manual.

Table 2: Lamp load for load current circuit SD/S x.16.1

Application program

Switch Dim 2f 1 – 10 V/1

Switch Dim 4f 1 – 10 V/1

Switch Dim 8f 1 – 10 V/1

Number communication objects

40

80

160

Max. number of group addresses

254

254

254

Max. number of associations

255

255

255

8

Table 3: User programs SD/S x.16.1

Note:

Note:

The programming requires EIB Software Tool ETS2 V1.3 or higher.

If ETS3 is used a “.VD3” or higher type file must be imported.

The application program is in the ETS2 / ETS3 at ABB / Lighting / Switching/

Dimming Actuators 1-10 V / Switch Dim xf 1-10 V/1

(x = number of outputs 2, 4 or 8)

The devices do not support the closing function of a project or the KNX devices in the ETS. If you inhibit access to all devices of the project with a “BA password”

(ETS2) or “BCU code” (ETS3), it has no effect on this device.

Data can still be read and programmed.

See the product manual ”Switch/Dim Actuators SD/S” for a detailed description of the application program.

The manual is available free of charge on the Internet at www.abb.de/eib.

SD/S x.16.1

Page 3 of 4

SDS_x161_TD_EN_V1-0

2CDC 507 067 D0201

SD/S x.16.1

ABB i-bus ® EIB / KNX Switch/Dim Actuators SD/S x.16.1

2CDG 110 079 R0011, 2CDG 110 080 R0011,

2CDG 110 081 R0011

Circuit diagram

8

Dimension drawing

1 Label carrier

2 Programming button

3 Programming LED

4 Bus Connection contact position indication

6 load current circuit,

2 terminals per circuit

7 control current circuit,

2 terminals per circuit

8

SD/S 2.16.1

B 72 mm

4 space units

SD/S 4.16.1

108 mm

6 space units

SD/S 8.16.1

144 mm

8 space units

Maxluxitalia

Sistemi Multimediali Professionali

Rivenditore prodotti ABB KNX

Divisione Vendite: mailto: [email protected]

Divisione Progetti: mailto: [email protected]

Informazioni: mailto: [email protected]

www.maxluxitalia.com

SD/S x.16.1

Page 4 of 4

SDS_x161_TD_EN_V1-0

2CDC 507 067 D0201

SD/S x.16.1

advertisement

Key Features

  • Modular installation device for EIB/KNX bus systems
  • Control of up to 8 dimmable electronic ballast devices or transformers
  • Manual operation (on/off) via a push-button
  • Switch status indication
  • Rated current of 16 A
  • Suitable for switching ohmic, inductive, and capacitive loads as well as fluorescent lamp loads
  • Powered via EIB/KNX bus, no additional power supply required

Related manuals

Frequently Answers and Questions

What is the maximum rated current for the SD/S x.16.1?
The SD/S x.16.1 has a rated current of 16 A for each load output.
Can the SD/S x.16.1 be manually operated?
Yes, each channel has a manual operating element (push-button) for on/off switching.
How many dimmable ballast devices can be controlled by one channel of the SD/S x.16.1?
The maximum number of dimmable ballast devices per channel is determined by the switching and control capabilities of the SD/S x.16.1. Typically, devices with a control current of 0.4 to 4 mA can be connected. Refer to the product manual for detailed information.
Download PDF