P R O D U C T S P E C I F I C AT I O N S
A I R H A N D L E R S
CBX32MV
DAVE LENNOX SIGNATURE
®
COLLECTION
R-410A Ready - Multi-Position - Variable Speed
Bulletin No. 210352
July 2012
Supersedes June 2012
Nominal Capacity - 1.5 to 5+ Tons
Optional Electric Heat - 2.5 to 25 kW
MODEL NUMBER IDENTIFICATION
CB X 32 mV - 036 - 230 - 6 - 01
Unit Type
CB = Air Handler
Refrigerant Type
X = R-410A
Series
Configuration
MV = Multi-Position, Variable
Speed Blower Motor
Nominal Cooling Capacity - Tons
018/024 = 1.5 to 2 tons
024/030 = 2 to 2.5 tons
036 = 3 tons
048 = 4 tons
060 = 5 tons
068 = 5+ tons
Minor Revision Number
Refrigerant Metering Device
2 = Fixed Orifice
3 = TXV - Bleedport (indoor unit)
4 = TXV - Non-bleedport (indoor unit)
5 = TXV - Non-bleedport (outdoor unit)
6 = TXV - R-410A Non-bleedport (indoor unit)
Voltage
230 = 208/230V-60hz-1ph
A
FEATURES
Contents
Blower Data ................................................................10
Dimensions - Downflow ..............................................21
Dimensions - Upflow ...................................................20
Electrical Data...............................................................8
Electric Heat Data .......................................................15
Features........................................................................2
Installation Clearances With Electric Heat ....................8
Model Number Identification .........................................1
Optional Accessories ....................................................8
Replacement Circuit Breakers ......................................9
Specifications................................................................8
Warranty
All covered components - Limited ten years in residential applications, one year in non-residential applications.
Refer to Lennox Limited Warranty Certificate included with each unit for additional details.
Approvals
Tested with matching air conditioners and heat pump units in the Lennox Research Laboratory environmental test room in accordance with AHRI Standard 210/240.
Optional electric heaters are rated in accordance with
US Department of Energy (DOE) test procedures and
Federal Trade Commission (FTC) labeling regulations.
Blower performance data according to unit tests conducted in Lennox air test chamber.
Air handlers are UL Listed to US and Canadian safety standards and components within are bonded for grounding to meet safety standards for servicing required by CEC and NEC.
ISO 9001 Registered Manufacturing Quality System.
Applications
1.5 to 5+ ton nominal sizes.
Multi-position (upflow, downflow or horizontal) applications.
Applicable to expansion valve systems in R-410A cooling applications and check and expansion valve systems in R-410A heat pump applications.
Applicable to Lennox Harmony III™ zoning system.
Wide-range check and expansion valve is factory installed.
See bulletins in section Air Conditioners for cooling capacities.
See bulletins in section Heat Pump Outdoor Units for cooling and heating capacities.
Optional field installed electric heaters available in several sizes for additive heating capacity.
Zoning Applications
Units can be used with certain zoning systems.
Zone control panel MUST be able to interface and communicate with the variable speed motor in the unit.
Lennox Harmony III™ zoning system has this capability.
CBX32MV / Page 2
B
REFRIGERANT SYSTEM
Copper Tube/Enhanced Fin Indoor Coil
Lennox designed and fabricated twin coils.
Assembled in “A” configuration.
Provides extra large surface and contact area, excellent heat transfer and low air resistance for maximum efficiency.
Precise circuiting for uniform refrigerant distribution.
Precisely spaced ripple-edged aluminum fins fitted to durable seamless copper tubes.
Fins are strengthened to resist bending and are equipped with collars that grip tubing for maximum contact area.
Lanced fins provide maximum exposure of fin surface to air stream.
Long life copper tubing is easy to service.
Rifled tubing provides superior heat transfer.
Flared shoulder tubing joints and silver soldering provide tight, leakproof joints.
Coil thoroughly factory tested under high pressure to insure leakproof construction.
FEATURES
REFRIGERANT SYSTEM (CONTINUED)
C
D
Refrigerant Line Connections
Suction (vapor) and liquid lines have sweat connections that extended outside of the cabinet for ease of connection.
See dimension drawings for locations.
Check and Expansion Valve Furnished
For use with R-410A systems.
Wide range valve with Chatleff style fitting.
Factory installed on all models, internal to cabinet.
E
Cabinet
Constructed of heavy-gauge galvanized steel.
Completely insulated with thick fiberglass insulation.
Pre-painted steel cabinets have mildly textured enamel finish with primer coat on unpainted side of all panels.
Units are shipped in one piece but may be disassembled into two separate sections for ease of installation in tight applications. See dimension drawings.
Thick rubber gasket between sections of the two piece cabinets provides an air tight seal.
No external screw heads on sides of cabinet for tight installations without damage to walls or woodwork.
Removable panels provide complete service access.
Electrical inlets provided in sides and top of cabinet.
See dimension drawings for locations.
Low Leakage Cabinet
All models have less than 2% air leakage and meet
ANSI/ASHRAE Standard 193-2010 “Method of Test for
Determining the Air Tightness of HVAC Equipment”.
Multi-Position Capability
Shipped for upflow and horizontal right-hand discharge.
Quickly converted to downflow or left-hand, horizontal air discharge.
Easily converts to downflow position with furnished coil support rails and filter support rack.
Dual Position Drain Pans
Drain pans designed for upflow, downflow or horizontal applications.
Deep, corrosion resistant plastic drain pans have dual pipe drains.
See dimension drawings.
OPTIONS
Downflow Combustible Flooring Base
Base is required for models with electric heat installed in downflow position on combustible floors.
Horizontal Support Frame Kit (Not for -068)
Provides support of unit in horizontal applications.
Consists of (2) 1 x 1-1/2 x 32-5/8 in. and (2) 1 x 3 x
53-7/8 in. painted heavy gauge cold rolled steel support channels with assembly and suspending holes.
Bolts and nuts furnished for field assembly.
Suspending rods must be field provided.
Side Return Unit Stand (Upflow Only, Not for -068)
Raises unit 16 in. above floor for side return air duct connection.
Eliminates need for wooden platform construction.
All aluminum construction.
Two adjustable frames fit -018/024 thru -060 models.
Wall Hanging Bracket Kit (Upflow Only)
Allows unit to be hung on wall at any height.
Consists of heavy-gauge steel support brackets (one for air handler, one for wall mount).
Screws furnished for fastening one bracket to unit.
Bolts for fastening one bracket to wall are field provided.
F
BLOWER
Variable-Speed Blower Motor
High efficiency multi-speed blower motor maintains specified air volumes up to a maximum of 0.8 in. w.g. total external static.
Multi-speed operation is achieved by the use of an ECM
(Electronically Commutated
Motor) motor.
Allows cooling ramping profiles
(field selectable) for enhanced dehumidification.
Motor accelerates and decelerates gradually, reducing start-up and shut-down sound.
G
Leadless blower motor features simple plug-in connections.
Motor is controlled by the icomfort™ control that allows blower to operate at two of eight air volumes or speeds available.
Speeds may be field selected on icomfort™ control depending on size of air handler and air volume desired.
See blower performance tables.
Blower Assembly
Lennox designed and built, direct drive blower.
Each blower is statically and dynamically balanced as an assembly before installation in the unit.
Blower motor is resiliently mounted to blower assembly.
Blower slides out of cabinet for servicing.
CBX32MV / Page 3
FEATURES
CONTROLS
H
icomfort™ Control
Advanced control board communicates information about various operating parameters in the air handler to the optional
icomfort Wi-Fi™ Thermostat to constantly maintain the highest level of comfort, performance and efficiency available.
Auto Configuration - On start-up the control board automatically sends a description of the unit to the optional
icomfort™ Thermostat to automatically configure the number of stages and features available.
Connections for connecting a conventional heating/ cooling thermostat are also provided on the board.
Board also features:
• Lennox Humiditrol
®
Whole Home Dehumidification
System (EDA) compatible.
• EEPROM storage of all local configurations.
• Non-volatile memory storage of 100 alarm codes with display of last 10 codes for troubleshooting.
• Connections for optional outdoor temperature sensor
(communicates temperature on RSBUS to thermostat).
• Controls evaporator humidity by controlling blower and compressor staging on two-stage outdoor units.
• Two stages - HEAT and COOL (with four different air volume selections for each) are made by simple jumper pins on board.
• ADJUST jumper pin allows approximately 10% higher, normal or 10% lower motor speed selection within HEAT and COOL speeds selected for fine tuning air volume.
• DELAY jumper pin allows selection of blower motor de-humidification profiles during cooling mode.
Option 1 - Motor runs at 100% of capacity until demand met. Once demand is met, motor ramps down to stop.
Option 2 −
Cooling: When cool demand is initiated, motor ramps up to 100% and runs at 100% until demand is satisfied. Once demand is met, motor runs at 100% for 45 seconds, then ramps down to stop.
Heat Pump: When heat pump demand is initiated,
30 second motor on delay starts. After the motor on delays expires, motor ramps up to 100% and runs at
100% until demand is satisfied. Once demand is met, motor runs at 100% for 45 seconds, then ramps down to stop.
Option 3 - Motor runs at 82% of capacity for approximately 7.5 minutes, then 100% capacity (if needed) until demand is satisfied. Once demand is met, motor ramps down to stop.
Option 4 - Motor runs at 50% capacity for 30 seconds, then 82% capacity for approximately 7.5 minutes. If demand is not satisfied, motor runs at 100% capacity until demand is met. Once demand is met, motor runs at
50% capacity for 30 seconds, then ramps down to stop.
Display LED - Seven segment LED displays alphanumeric information related to diagnostics as well as system operation and status. Diagnostic codes are held in non-volatile memory, immune from power interruptions. Holds up to ten diagnostic codes in order of occurrence for recall on demand. Port on blower door allows for easy viewing.
Dehumidification (Active or Humiditrol
®
Option) - A jumper on the control board must be clipped to enable active dehumidification and/or operation with a Humiditrol Whole-Home Dehumidification System.
A humidity controlling thermostat or device is also required. During a call for cooling, air volume is automatically reduced, forcing humidity removal by the air conditioner or heat pump system. After the humidity has reached the desired set-point the cooling air volume returns to its designed rate. A dehumidification signal from the thermostat reduces the cooling cfm to 70% of the requested cooling cfm.
Electric Heat Operation - Control for up to three electric heat stages.
EvenHeater
®
Electric Heat Control - Up to four electric heat stages are available when utilizing the
EvenHeater
®
control feature furnished on the icomfort™ control. EVENHEAT jumper position on control board determines target discharge air temperature of 85 °F,
100 °F, 115°F or 130°F. Default setting is 85°F. An optional Discharge Air Sensor is required.
Heat Pump Operation - A jumper on the control board must be clipped to enable operation with a single or two-stage heat pump. The indoor blower is started without delay when a call for heat is received.
Two Stage Cooling Operation - A jumper on the control board must be clipped to enable operation with a two-stage air conditioner. The cooling blower speeds for first and second stage cooling will be dictated by the applicable DIP switch settings.
Lennox System Operations Monitor Connection -
Monitors outdoor unit operation. (communicating mode).
Continuous Blower Speed - Adjustable continuous blower speed is a percentage of the high cooling speed selection. There are four selectable options (via DIP switch settings) of 28%, 38% (default setting), 70% and
100%.
Transformer - 70VA transformer furnished as standard.
Factory installed in the unit control box.
Accessory Terminals - Two accessory terminals are furnished for additional power supply requirements for 120 volt (less than 1 amp) power humidifiers and powered air cleaners. One 24 volt humidifier output is furnished for non-powered humidifiers.
Control board is factory installed in the unit control box.
CBX32MV / Page 4
FEATURES
CONTROLS (CONTINUED)
OPTIONS
icomfort Wi-Fi™ Thermostat (part of the icomfort™
Residential Communicating Control System)
The icomfort Wi-Fi™ Thermostat recognizes and connects to all icomfort™enabled products to automatically configure and control the heating/cooling system (based on user-specified settings) for the highest level of comfort, performance and efficiency.
Also recognizes model and serial number information for icomfort™-enabled products to simplify system installation.
Wi-Fi remote temperature monitoring and adjustment through a home wireless network for desktop PCs, laptops and apps for smartphones or tablets. Service alerts and reminders sent via text message or e-mail.
Dealer Dashboard features online real-time monitoring of installed icomfort systems.
A simple easy-to-use touchscreen allows complete system configuration. Scheduled maintenance alerts, system warnings and troubleshooting are also displayed on thermostat screen.
Easy to read 7 inch color screen (measured diagonally).
Conventional outdoor units (not icomfort™-enabled) can easily be added and controlled by the
icomfort Wi-Fi™
Thermostat.
Installer setup screens allow quick and simple system configuration without a manual, Installer can also run tests on complete system or individual components for easy maintenance and troubleshooting.
Serial communications bus (RSBus), with less wiring than a conventional heating/cooling system, allows system communication. Uses 4-wire, 18-gauge standard thermostat wiring.
See the icomfort Wi-Fi™ Thermostat Product
Specifications bulletin in the Controls section for more information.
ComfortSense
®
7000 Touchscreen Thermostat
Electronic 7-day, universal, multi-stage, programmable, touchscreen thermostat.
4 Heat/2 Cool.
Auto-changeover.
Controls humidity during cooling mode.
Offers enhanced capabilities including humidification / dehumidification / dewpoint measurement and control,
Humiditrol
®
control, and equipment maintenance reminders.
HOME
MODE
AUTO
SCHED
ON
SCHEDULE OPTIONS
SET AT
HEAT
SET AT
COOL
WED
INDOOR RH 26%
AN 21 12:35AM
Easy-to-use, menu driven thermostat with a back-lit,
LCD touchscreen.
Remote outdoor temperature sensor (optional) allows the thermostat to display outdoor temperature. Required in dual-fuel and Humiditrol
®
applications.
See the ComfortSense
®
7000 Product Specifications bulletin in the Controls section for more information.
Outdoor Temperature Sensor
Used with icomfort™ thermostats and ComfortSense
®
7000 thermostat.
When installed outdoors, sensor allows thermostat to display outdoor temperature. Sensor is auto-detected when connected to thermostat.
NOTE - Sensor is required for
Humiditrol
®
applications.
Thermostat
Thermostat (icomfort™ thermostats or programmable/ non-programmable) is not furnished with unit.
See Thermostat bulletins in Controls Section and
Lennox Price Book for selection.
Hot Water Heat Kit
Air handler kit to control a third-party hot water boiler with a hot water heating coil installed downstream from the air handler.
Kit contains all necessary relays and plug-in wiring harness to control boiler.
NOTE - This kit is only approved for use in systems using either the ComfortSense
®
7000 or icomfort™-enabled thermostats.
CBX32MV / Page 5
FEATURES
OPTIONAL Electric Heat
I
Field install internal to unit cabinet.
Available in several voltages and kW sizes.
See Electric Heat tables.
Helix wound nichrome heating elements exposed directly in air stream resulting in instant heat transfer, low element temperatures and long service life.
Each element equipped with accurately located limit control with fixed temperature off setting and automatic reset.
Supplemental thermal cutoff limit control, provides positive protection in case of excessive temperatures.
Thermal sequencer relay brings elements on and off line, in sequence and equal increments, with time delay between each.
Initiates and terminates blower operation.
Heating control relay(s) furnished as standard.
Control box and access cover constructed of heavy gauge galvanized steel.
Factory assembled with controls installed and wired.
Electric heat low voltage controls plug-in to air handler.
Circuit Breaker Models
The following heaters are equipped with circuit breakers for overload and short circuit protection:
ECB40-4CB, -5CB, -6CB, -8CB, -9CB, -12.5CB, -15CB,
-20CB and -25CB (208/240V-1ph)
ECB40-15CB, -20CB and -25CB (208/240V-3ph
Factory wired and mounted on electric heat unit.
Current sensitive and temperature actuated.
Manual reset.
Circuit breakers qualify as disconnect means at unit in many areas, eliminate the need for field provided disconnect.
Consult local electrical code in your area.
OPTIONS
Circuit Breaker Cover Kit
Flexible plastic cover protects circuit breaker.
Recommended in areas with high humidity or unconditioned areas to prevent nuisance tripping.
Single-Point Power Source Control Box
Control Box may be used with optional electric heat when single power supply is connected to multi-circuit electric heat.
Field installs external to the unit cabinet on either side or top.
Constructed of heavy gauge steel, baked enamel finish, prepunched mounting holes, electrical inlet knockouts, and terminal strip.
Removable cover provides easy access.
Dimensions (H x W x D) - 7 x 7 x 4 in.
INDOOR AIR QUALITY
J
Air Filter
Tool-less access to filter area for quick and easy servicing.
Disposable frame type filter furnished and factory installed in rails in cabinet.
See Specifications tables for sizes.
OPTIONS
Healthy Climate
®
Germicidal UVC Light
Germicidal lamp emits C-Band ultra-violet (UVC) energy at 253.7 nanometers, which is proven to be effective in reducing microbes such as viruses, bacteria, yeasts, and molds. This process either destroys the organism or controls its ability to reproduce. UVC germicidal light greatly reduces the growth and proliferation of mold and other bioaerosols (bacteria and viruses) on illuminated surfaces (particularly coil and drain pan). Surfaces must be cleaned prior to UVC light being installed.
Available in 24 volt and 110/230V-1ph models.
Air handlers have a factory provided knockout in the coil delta plate for mounting light within coil area.
Shielding baffle is required when installing light above a non-UVC resistant component, such as a filter.
Baffle must be ordered separately.
CBX32MV / Page 6
SPECIFICATIONS
General Data
Connections in.
Indoor
Coil
Model Number CBX32MV-018/024 CBX32MV-024/030
Nominal tonnage 1.5 to 2 2 to 2.5
Refrigerant
Suction / vapor (o.d.) line - sweat
Liquid line (o.d.) - sweat
Condensate drain - in. (fpt)
Net face area - ft.
2
Tube outside diameter - in.
R-410A
5/8
3/8
(2) 3/4
3.56
3/8
R-410A
3/4
3/8
(2) 3/4
4.44
3/8
Blower Data
Filters
Number of rows
Fins per inch
Wheel nominal diameter x width - in.
Motor output - hp
1
Number and size - in.
Shipping Data - 1 Package - lbs.
3
12
10 x 7
1/2
(1) 15 x 20 x 1
126
3
12
10 x 8
1/2
(1) 20 x 20 x 1
152
ELECTRICAL DATA
Voltage - phase - 60hz
2
Maximum overcurrent protection (unit only)
3
Minimum circuit ampacity (unit only)
CONTROLS
208/230V-1ph
15
5
208/230V-1ph
15
5
CBX32MV-036
3
R-410A
3/4
3/8
(2) 3/4
5.0
3/8
3
12
10 x 8
1/2
(1) 20 x 20 x 1
183
208/230V-1ph
15
5
icomfort Wi-Fi™ Thermostat
4
Remote Outdoor Sensor (for dual fuel and Humiditrol
®
)
5
Discharge Temperature Sensor
ComfortSense
®
7000 Thermostat
Remote Outdoor Sensor (for dual fuel and Humiditrol
®
)
88W58
X2658
88K38
Y0349
X2658
88W58
X2658
88K38
Y0349
X2658
88W58
X2658
88K38
Y0349
X2658
OPTIONAL ACCESSORIES - order separately
Circuit Breaker Cover Kit
Downflow Combustible Flooring Base
Electric Heat
Healthy Climate
Germicidal Light
UVC-24V (24V)
Shielding Baffle (required)
UVC-41W-S (110/230v-1 ph)
Shielding Baffle (required)
82W01
34J72
X9423
Y2120
X9424
X9900
56J18
82W01
44K15
See Electric Heat Data tables
X9423
Y2120
X9424
X9900
56J18
82W01
44K15
X9423
Y2120
X9424
X9900
56J18 Horizontal Support Frame Kit
Hot Water Heat Kit
Side Return Unit Stand (Upflow)
Single-Point Power Source Control Box
90W84
45K31
21H39
90W84
45K32
21H39
90W84
45K32
21H39
Wall Hanging Bracket Kit (Upflow) 45K30 45K30 45K30
1
Disposable frame type filter.
2
HACR type circuit breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
4
Remote Outdoor Sensor may be used with an icomfort™-enabled outdoor unit for a secondary (alternate) sensor reading. Sensor may also be used with a conven-
5 tional outdoor unit.
Optional for EvenHeater
®
electric heat operation and service diagnostics.
INSTALLATION CLEARANCES WITH ELECTRIC HEAT
Cabinet
To Plenum
To Outlet Duct within 3 feet (914 mm)
Floor
0 inch (0 mm)
1 inch (25 mm)
1 inch (25 mm)
See Note #1
Service / Maintenance See Note #2
1
Units installed on combustible floors in the downflow position with electric heat require optional downflow combustible
2 flooring base.
Front service access - 24 inches (610 mm) minimum.
NOTE - If cabinet depth is more than 24 inches (610 mm), allow a minimum of the cabinet depth plus 2 inches (51 mm).
CBX32MV / Page 7
SPECIFICATIONS
General Data
Connections in.
Indoor
Coil
Model Number
Nominal tonnage
Refrigerant
Suction / vapor (o.d.) line - sweat
Liquid line (o.d.) - sweat
Condensate drain - in. (fpt)
Net face area - ft.
2
Tube outside diameter - in.
Blower Data
Filters
Number of rows
Fins per inch
Wheel nominal diameter x width - in.
Motor output - hp
1
Number and size - in.
Shipping Data - 1 Package - lbs.
ELECTRICAL DATA
Voltage - phase - 60hz
2
Maximum overcurrent protection (unit only)
3
Minimum circuit ampacity (unit only)
CBX32MV-048
4
R-410A
7/8
3/8
(2) 3/4
7.22
3/8
3
12
12 x 9
1
(1) 20 x 24 x 1
212
CBX32MV-060
5
R-410A
7/8
3/8
(2) 3/4
7.22
3/8
3
12
12 x 9
1
(1) 20 x 24 x 1
212
CBX32MV-068
5+
R-410A
1-1/8
3/8
(2) 3/4
7.77
3/8
3
12
15 x 9
1
(1) 20 x 25 x 1
244
208/230V-1ph
20
11
208/230V-1ph
20
11
208/230V-1ph
20
11
CONTROLS
icomfort
4
®
Touch Communicating Thermostat
Remote Outdoor Sensor (for dual fuel and Humiditrol
®
)
5
Discharge Temperature Sensor
ComfortSense
®
7000 Thermostat
Remote Outdoor Sensor (for dual fuel and Humiditrol
®
)
49W95
X2658
88K38
Y0349
X2658
49W95
X2658
88K38
Y0349
X2658
49W95
X2658
88K38
Y0349
X2658
OPTIONAL ACCESSORIES - order separately
Circuit Breaker Cover Kit
Downflow Additive Base
Electric Heat
Healthy Climate
Germicidal Light
Horizontal Support Frame Kit
Hot Water Heat Kit
Side Return Unit Stand (Upflow)
Shielding Baffle (required)
Single-Point Power Source Control Box
Wall Hanging Bracket Kit (Upflow)
UVC-24V (24V)
Shielding Baffle (required)
UVC-41W-S (110/230v-1 ph)
82W01
44K15
X9423
Y2120
X9424
X9900
56J18
90W84
45K32
21H39
45K30
82W01
44K15
See Electric Heat Data tables
X9423
Y2120
X9424
X9900
56J18
90W84
45K32
21H39
45K30
82W01
44K15
X9423
Y2120
X9424
X9900
N/A
90W84
N/A
21H39
45K30
1
Disposable frame type filter.
2
HACR type circuit breaker or fuse.
3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
4
Remote Outdoor Sensor may be used with an icomfort™-enabled outdoor unit for a secondary (alternate) sensor reading. Sensor may also be used with a conven-
5 tional outdoor unit.
Optional for EvenHeater
®
electric heat operation and service diagnostics.
REPLACEMENT CIRCUIT BREAKERS
Voltage
208/240V - 1 Phase
208/240V - 3 Phase
Description
25 amp, 2 pole
30 amp, 2 pole
35 amp, 2 pole
40 amp, 2 pole
45 amp, 2 pole
50 amp, 2 pole
60 amp, 2 pole
30 amp, 3 pole
35 amp, 3 pole
40 amp, 3 pole
45 amp, 3 pole
50 amp, 3 pole
60 amp, 3 pole
Catalog No.
41K13
17K70
72K07
49K14
17K71
41K12
17K72
64W47
41K14
41K16
18M86
41K15
41K17
CBX32MV / Page 8
BLOWER DATA
CBX32MV-018/024 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper
Setting
+
NORM
–
1 cfm
715
670
580
“HEAT” Speed
2 cfm
855
770
700
3 cfm
1000
900
800
Jumper Speed Positions
4 cfm
1130
1035
930
1 cfm
465
425
385
“COOL” Speed
2 cfm
690
620
560
3 cfm
900
825
735
4 cfm
1050
950
850
NOTES - The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous fan speed is approximately 28%, 38%, 70% and 100% (Jumper selectable) of the same second-stage COOL speed selected.
Lennox Harmony III™ Zone Control applications - minimum blower speed is 250 cfm.
CBX32MV-018/024 BLOWER MOTOR WATTS
AT “+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)
Jumper
Speed Positions
“HEAT” Speed Tap 1
0
100
0.1
113
Motor Watts @ Various External Static Pressures - in. wg.
0.2
126
0.3
142
0.4
154
0.5
172
0.6
190
“COOL” Speed
Tap 2
Tap 3
Tap 4
Tap 1
Tap 2
Tap 3
155
237
338
36
89
183
176
260
361
47
103
198
197
289
379
61
118
229
221
305
409
71
129
248
237
314
433
81
143
266
260
337
457
95
163
290
278
356
447
106
177
307
Tap 4
266 294 315
AT “NORM” SETTING (“Adjust” Jumper at NORM Setting)
Jumper
Speed Positions
“HEAT” Speed Tap 1
Tap 2
0
77
118
0.1
96
136
0.2
106
154
330
0.3
123
177
349
0.4
130
189
373 390
Motor Watts @ Various External Static Pressures - in. wg.
0.5
150
212
0.6
165
224
“COOL” Speed
Tap 3
Tap 4
Tap 1
183
264
30
198
284
41
224
300
55
248
326
62
264
343
76
284
367
86
307
385
94
Tap 2
Tap 3
Tap 4
71
137
211
83
158
225
101
176
249
113
199
272
125
219
295
138
238
318
156
254
331
AT “–” (Minus) SETTING (“Adjust” Jumper at “–” Setting)
Jumper
Speed Positions
0 0.1
Motor Watts @ Various External Static Pressures - in. wg.
0.2
0.3
0.4
0.5
0.6
“HEAT” Speed Tap 1
Tap 2
Tap 3
59
95
132
73
106
148
89
118
171
106
136
186
113
152
211
130
171
225
142
183
248
“COOL” Speed
Tap 4
Tap 1
Tap 2
Tap 3
Tap 4
195
27
57
110
148
217
35
65
124
170
242
47
83
141
195
259
59
94
157
207
283
71
110
176
230
302
77
119
188
248
314
88
134
213
272
0.7
156
200
266
336
92
148
231
282
118
197
327
411
0.7
206
295
373
426
0.7
178
247
321
406
106
166
273
342
0.8
173
215
284
349
106
166
242
306
135
207
343
401
0.8
230
310
390
406
0.8
201
265
343
390
114
185
296
367
CBX32MV / Page 9
BLOWER DATA
CBX32MV-024/030 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper
Setting
+
NORM
–
1 cfm
800
725
655
“HEAT” Speed
2 cfm
935
850
765
3 cfm
1070
975
880
Jumper Speed Positions
4 cfm
1210
1100
990
1 cfm
660
600
540
“COOL” Speed
2 cfm
880
800
720
3 cfm
1100
1000
900
4 cfm
1320
1200
1080
NOTES - The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous fan speed is approximately 28%, 38%, 70% and 100% (Jumper selectable) of the same second-stage COOL speed selected.
Lennox Harmony III™ Zone Control applications - minimum blower speed is 250 cfm.
CBX32MV-024/030 BLOWER MOTOR WATTS
AT “+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)
Jumper
Speed Positions
“HEAT” Speed Tap 1
0
65
0.1
90
Motor Watts @ Various External Static Pressures - in. wg.
0.2
120
0.3
145
0.4
185
0.5
210
0.6
240
“COOL” Speed
Tap 2
Tap 3
Tap 4
Tap 1
Tap 2
Tap 3
95
140
215
45
80
150
125
190
250
60
110
195
150
225
285
90
135
225
185
250
315
120
165
260
230
290
350
140
205
295
265
320
390
155
250
320
310
350
440
165
285
370
Tap 4
265 315 350
AT “NORM” SETTING (“Adjust” Jumper at NORM Setting)
Jumper
Speed Positions
“HEAT” Speed Tap 1
Tap 2
0
50
80
0.1
75
105
0.2
100
130
400
0.3
135
155
440
0.4
155
200
485 525
Motor Watts @ Various External Static Pressures - in. wg.
0.5
180
245
0.6
195
265
“COOL” Speed
Tap 3
Tap 4
Tap 1
110
155
40
150
205
55
175
230
80
200
270
105
235
290
120
275
325
130
320
360
150
Tap 2
Tap 3
Tap 4
65
105
200
90
145
245
120
175
275
145
220
300
190
250
335
210
285
385
240
335
420
AT “–” (Minus) SETTING (“Adjust” Jumper at “–” Setting)
Jumper
Speed Positions
0 0.1
Motor Watts @ Various External Static Pressures - in. wg.
0.2
0.3
0.4
0.5
0.6
“HEAT” Speed Tap 1
Tap 2
Tap 3
45
60
85
65
85
105
90
110
130
110
145
165
130
175
210
150
200
245
165
215
280
“COOL” Speed
Tap 4
Tap 1
Tap 2
Tap 3
Tap 4
115
30
55
85
145
145
50
75
115
175
175
70
100
135
215
205
90
135
175
245
230
100
155
210
280
280
115
185
255
325
325
125
190
295
355
0.7
190
235
305
370
140
210
320
410
185
315
425
555
0.7
250
345
405
480
0.7
215
295
350
405
165
260
370
470
0.8
195
240
330
390
165
225
345
450
200
335
465
605
0.8
275
365
450
505
0.8
230
310
390
460
180
285
405
515
CBX32MV / Page 10
BLOWER DATA
CBX32MV-036 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper
Setting
+
NORM
–
1 cfm
1230
1120
1010
“HEAT” Speed
2 cfm
1335
1215
1185
3 cfm
1445
1315
1200
Jumper Speed Positions
4 cfm
1545
1400
1265
1 cfm
900
810
730
“COOL” Speed
2 cfm
1225
1125
1000
3 cfm
1380
1275
1135
4 cfm
1545
1400
1265
NOTES - The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous fan speed is approximately 28%, 38%, 70% and 100% (Jumper selectable) of the same second-stage COOL speed selected.
Lennox Harmony III™ Zone Control applications - minimum blower speed is 250 cfm.
CBX32MV-036 BLOWER MOTOR WATTS
AT “+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)
Jumper
Speed Positions
“HEAT” Speed Tap 1
0
220
0.1
235
Motor Watts @ Various External Static Pressures - in. wg.
0.2
265
0.3
290
0.4
310
0.5
335
0.6
360
“COOL” Speed
Tap 2
Tap 3
Tap 4
Tap 1
Tap 2
Tap 3
285
345
470
90
225
305
305
365
495
110
245
325
330
405
515
135
265
350
355
430
530
155
290
390
380
455
545
180
320
420
405
485
560
195
350
445
430
515
575
210
370
475
Tap 4
470 495 515
AT “NORM” SETTING (“Adjust” Jumper at NORM Setting)
Jumper
Speed Positions
“HEAT” Speed Tap 1
Tap 2
0
155
225
0.1
185
245
0.2
215
270
530
0.3
240
295
545
0.4
265
325
560 575
Motor Watts @ Various External Static Pressures - in. wg.
0.5
285
345
0.6
300
370
“COOL” Speed
Tap 3
Tap 4
Tap 1
275
320
100
290
345
120
315
375
140
340
405
150
375
435
185
400
460
190
420
485
215
Tap 2
Tap 3
Tap 4
160
255
320
190
270
345
220
295
375
240
320
405
265
345
435
290
375
460
320
400
485
AT “–” (Minus) SETTING (“Adjust” Jumper at “–” Setting)
Jumper
Speed Positions
0 0.1
Motor Watts @ Various External Static Pressures - in. wg.
0.2
0.3
0.4
0.5
0.6
“HEAT” Speed Tap 1
Tap 2
Tap 3
120
140
185
135
165
210
165
195
240
185
215
265
205
245
285
225
270
310
245
300
330
“COOL” Speed
Tap 4
Tap 1
Tap 2
Tap 3
Tap 4
245
65
120
160
245
255
90
140
190
255
290
105
160
225
290
310
125
185
240
310
335
145
215
275
335
355
160
235
295
355
380
185
255
320
380
0.7
265
315
360
405
190
275
350
405
230
395
505
595
0.7
385
450
545
595
0.7
335
390
445
515
240
340
420
515
0.8
300
335
385
430
215
295
380
430
250
410
535
610
0.8
465
475
570
610
0.8
355
415
465
540
250
365
445
540
CBX32MV / Page 11
BLOWER DATA
CBX32MV-048 and cbx32MV-060 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper
Setting
+
NORM
–
1 cfm
1850
1705
1560
“HEAT” Speed
2 cfm
1960
1800
1625
3 cfm
2090
1900
1720
Jumper Speed Positions
4 cfm
2150
2005
1770
1 cfm
1625
1425
1205
“COOL” Speed
2 cfm
1820
1625
1375
3 cfm
2055
1805
1555
4 cfm
2145
2005
1725
NOTES - The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous fan speed is approximately 28%, 38%, 70% and 100% (Jumper selectable) of the same second-stage COOL speed selected.
Lennox Harmony III™ Zone Control applications - minimum blower speed is 450 cfm.
CBX32MV-048 and cbx32MV-060 BLOWER MOTOR WATTS
AT “+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)
Jumper
Speed Positions
“HEAT” Speed Tap 1
0
455
0.1
505
Motor Watts @ Various External Static Pressures - in. wg.
0.2
540
0.3
585
0.4
630
0.5
665
0.6
710
“COOL” Speed
Tap 2
Tap 3
Tap 4
Tap 1
Tap 2
Tap 3
555
680
730
300
425
625
595
720
780
335
475
660
645
770
825
370
500
705
675
820
870
360
545
755
730
865
920
435
585
810
780
900
970
465
635
850
820
945
1020
500
670
885
Tap 4
700 750 800
AT “NORM” SETTING (“Adjust” Jumper at NORM Setting)
Jumper
Speed Positions
“HEAT” Speed Tap 1
Tap 2
0
360
400
0.1
385
440
0.2
425
485
845
0.3
465
520
895
0.4
495
555
940 990
Motor Watts @ Various External Static Pressures - in. wg.
0.5
525
595
0.6
565
640
“COOL” Speed
Tap 3
Tap 4
Tap 1
480
580
215
520
625
235
560
665
275
605
710
295
640
760
330
685
800
360
765
835
400
Tap 2
Tap 3
Tap 4
310
415
580
335
445
610
375
490
655
405
535
695
440
565
740
465
605
785
500
650
830
AT “–” (Minus) SETTING (“Adjust” Jumper at “–” Setting)
Jumper
Speed Positions
0 0.1
Motor Watts @ Various External Static Pressures - in. wg.
0.2
0.3
0.4
0.5
0.6
“HEAT” Speed Tap 1
Tap 2
Tap 3
265
320
375
305
350
410
340
395
435
370
420
470
410
450
515
440
475
545
460
515
575
“COOL” Speed
Tap 4
Tap 1
Tap 2
Tap 3
Tap 4
400
140
200
280
375
435
170
230
315
420
480
195
260
340
440
525
215
285
380
475
555
250
315
415
515
595
275
355
445
550
640
300
385
465
575
0.7
745
865
985
1055
535
710
940
1030
0.7
505
545
610
670
335
415
505
610
0.7
600
670
785
875
430
530
675
870
0.8
540
580
645
700
360
450
540
645
0.8
780
895
1030
1110
575
745
970
1080
0.8
635
705
805
925
465
565
715
910
CBX32MV / Page 12
BLOWER DATA
CBX32MV-068 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper
Setting
+
NORM
–
1 cfm
1875
1760
1550
“HEAT” Speed
2 cfm
1975
1825
1650
3 cfm
2090
1920
1725
Jumper Speed Positions
4 cfm
2150
2030
1800
1 cfm
1640
1465
1250
“COOL” Speed
2 cfm
1840
1625
1390
3 cfm
2075
1800
1560
4 cfm
2150
2000
1720
NOTES - The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous fan speed is approximately 28%, 38%, 70% and 100% (Jumper selectable) of the same second-stage COOL speed selected.
Lennox Harmony III™ Zone Control applications - minimum blower speed is 450 cfm.
CBX32MV-068 BLOWER MOTOR WATTS
AT “+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)
Jumper
Speed Positions
“HEAT” Speed Tap 1
0
365
0.1
410
Motor Watts @ Various External Static Pressures - in. wg.
0.2
455
0.3
495
0.4
545
0.5
610
0.6
660
“COOL” Speed
Tap 2
Tap 3
Tap 4
Tap 1
Tap 2
Tap 3
430
540
665
255
355
505
485
585
710
290
390
565
540
635
755
320
425
610
590
695
770
365
475
70
640
750
790
415
515
715
690
800
810
455
580
790
765
815
830
505
630
815
Tap 4
725 745 755
AT “NORM” SETTING (“Adjust” Jumper at NORM Setting)
Jumper
Speed Positions
“HEAT” Speed Tap 1
Tap 2
0
310
345
0.1
345
385
0.2
385
420
770
0.3
425
460
790
0.4
465
500
810 830
Motor Watts @ Various External Static Pressures - in. wg.
0.5
510
620
0.6
560
615
“COOL” Speed
Tap 3
Tap 4
Tap 1
385
475
180
430
525
205
480
560
240
525
615
285
580
660
325
640
720
365
695
785
405
Tap 2
Tap 3
Tap 4
250
345
445
285
375
510
320
415
560
355
460
595
410
505
665
455
560
725
505
610
790
AT “–” (Minus) SETTING (“Adjust” Jumper at “–” Setting)
Jumper
Speed Positions
0 0.1
Motor Watts @ Various External Static Pressures - in. wg.
0.2
0.3
0.4
0.5
0.6
“HEAT” Speed Tap 1
Tap 2
Tap 3
215
255
295
245
295
330
285
325
375
325
370
395
375
410
445
415
460
495
460
510
555
“COOL” Speed
Tap 4
Tap 1
Tap 2
Tap 3
Tap 4
335
125
160
225
290
370
150
185
245
325
400
170
225
280
355
445
210
255
320
400
505
245
300
370
445
550
270
335
420
490
600
300
365
460
545
0.7
495
545
600
660
340
415
510
595
550
695
845
850
0.7
725
835
840
845
0.7
610
680
750
845
435
535
670
845
0.8
540
580
660
705
370
450
545
650
590
750
865
870
0.8
790
865
865
870
0.8
665
735
815
810
480
585
735
865
CBX32MV / Page 13
ELECTRIC HEAT DATA - CBX32MV-018/024
Volts
Input kW
Input
1
Btuh
Input
2
Blower
Motor
Full Load
Amps
3
Minimum
Circuit
Ampacity
5
Maximum
Overcurrent
Protection
SINGLE PHASE
2.5 kW
4 lbs.
4 kW
4 lbs.
5 kW
4 lbs.
6 kW
4 lbs.
8 kW
5 lbs.
9 kW
5 lbs.
ECB40-2.5
Terminal Block
ECB40-4
(34W86)
(55W89)
Terminal Block
ECB40-4CB (55W90)
30A Circuit breaker
ECB40-5
ECB40-5CB
EB40-6
ECB40-6CB
ECB40-8
ECB40-8CB
ECB40-9CB
(34W87)
Terminal Block
(34W90)
35A Circuit breaker
(34W88)
Terminal Block
(34W91)
40A Circuit breaker
(34W89)
Terminal Block
(34W92)
50A Circuit breaker
(34W93)
60A Circuit breaker
1
1
1
1
1
2
208 1.9
220 2.1
230 2.3
240 2.5
208 3.0
220 3.4
230 3.7
240 4.0
208 3.8
220 4.2
230
240
208
220
230
240
208
220
230
240
208
220
230
240
4.6
5.0
4.5
5.0
5.5
6.0
6.0
6.7
7.3
8.0
6.8
7.6
8.3
9.0
6,400
7,200
7,800
8,500
10,250
11,450
12,550
13,650
12,800
14,300
15,700
17,100
15,400
17,100
18,800
20,500
20,500
22,900
25,100
27,300
23,100
25,800
28,200
30,700
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
1
3
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
2
Electric heater capacity only - does not include additional blower motor heat capacity.
4
Amps shown are for blower motor only.
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
Bold text indicates that the circuit breaker on “CB” circuit breaker models must be replaced with size noted. See Table on Page 6.
5
HACR type circuit breaker or fuse.
4
45
4
45
4
45
50
4
50
4
50
60
60
4
30
4
30
4
30
35
4
35
4
35
4
35
40
20
20
20
20
4
25
4
25
4
25
30
41
43
45
47
46
48
30
31
32
33
35
36
50
52
23
24
25
26
28
29
16
17
18
18
CBX32MV / Page 14
ELECTRIC HEAT DATA - CBX32MV-024/030
Volts
Input kW
Input
1
Btuh
Input
2
Blower
Motor
Full
Load
Amps
3
Minimum
Circuit
Ampacity
5
Maximum
Overcurrent
Protection
CkT 1 Ckt 2 CkT 1 Ckt 2
Single Point
Power Source
3
Minimum
Circuit
Ampacity
5
Maximum
Overcurrent
Protection
SINGLE PHASE
4 kW
4 lbs.
5 kW
4 lbs.
6 kW
4 lbs.
ECB40-4 (55W89)
Terminal Block
ECB40-4CB (55W90)
30A Circuit breaker
ECB40-5
Terminal Block
ECB40-5CB
35A Circuit breaker
EB40-6
(34W87)
(34W90)
(34W88)
Terminal Block
ECB40-6CB (34W91)
40A Circuit breaker
1
1
1
208 3.0
10,250
220 3.4
11,450
230 3.7
12,550
240 4.0
13,650
208 3.8
12,800
220 4.2
14,300
230 4.6
15,700
240 5.0
17,100
208 4.5
15,400
220 5.0
17,100
230 5.5
18,800
240 6.0
20,500
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
23 - - -
4
25
- - -
24 - - -
4
25
- - -
25 - - -
4
25
- - -
26 - - 30 - - -
28 - - -
4
30
- - -
29 - - -
4
30
- - -
30 - - -
4
30
- - -
31 - - 35 - - -
32 - - -
4
35
- - -
33 - - -
4
35
- - -
35 - - -
4
35
- - -
36 - - 40 - - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
8 kW
5 lbs.
9 kW
5 lbs.
12.5 kW
10 lbs.
ECB40-8
ECB40-8CB
(34W89)
Terminal Block
(34W92)
50A Circuit breaker
ECB40-9CB (34W93)
60A Circuit breaker
ECB40-12.5CB
(34W94)
(1) 30A and
(1) 45A Circuit breaker
1
2
2
208
220
230
6.0
6.7
7.3
20,500
22,900
25,100
240 8.0
27,300
208 6.8
23,100
220 7.6
25,800
230 8.3
28,200
240 9.0
30,700
208 9.4
32,000
220 10.5 35,800
230 11.5 39,200
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
41 - - -
4
45
- - -
43 - - -
4
45
- - -
45 - - -
4
45
- - -
47 - - 50 - - -
46 - - -
4
50
- - -
48 - - -
4
50
- - -
50 - - -
52
24
25
26
- - -
38
4
60
60
25
40
4
25
42 30
- - -
- - -
4
40
4
40
45
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
62
65
68
15 kW
12 lbs.
ECB40-15CB (34W95)
(1) 35A and
(1) 60A Circuit breaker
2
240 12.5 42,600
208 11.3 38,400
220 12.6 43,000
230 13.8 47,000
4.0
4.0
4.0
4.0
27
28
29
30
44 30
45
4
30
48
4
30
50
4
30
52 35
45
4
45
4
50
4
50
60
71
73
77
80
80
80
80
80
240 15.0 51,200 4.0
31 83 90
1
3
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
2
Electric heater capacity only - does not include additional blower motor heat capacity.
4
Amps shown are for blower motor only.
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
Bold text indicates that the circuit breaker on “CB” circuit breaker models must be replaced with size noted. See Table on Page 6.
5
HACR type circuit breaker or fuse.
- - -
- - -
- - -
70
70
70
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
CBX32MV / Page 15
ELECTRIC HEAT DATA - CBX32MV-036
Volts
Input kW
Input
1
Btuh
Input
2
Blower
Motor
Full Load
Amps
3
Minimum
Circuit
Ampacity
5
Maximum
Overcurrent
Protection
Ckt 1 Ckt 2 Ckt 1 Ckt 2
Single Point
Power Source
3
Minimum
Circuit
Ampacity
5
Maximum
Overcurrent
Protection
SINGLE PHASE
4 kW
4 lbs.
5 kW
4 lbs.
6 kW
4 lbs.
8 kW
5 lbs.
9 kW
5 lbs.
12.5 kW
10 lbs.
15 kW
12 lbs.
20 kW
19 lbs.
ECB40-4 (55W89)
Terminal Block
ECB40-4CB (55W90)
35A Circuit breaker
ECB40-5 (34W87)
Terminal Block
ECB40-5CB (34W90)
35A Circuit breaker
ECB40-6
Terminal Block
ECB40-6CB
40A Circuit breaker
ECB40-8
Terminal Block
ECB40-8CB
50A Circuit breaker
ECB40-9CB
60A Circuit breaker
ECB40-12.5CB
(1) 30A and
(1) 45A Circuit breaker
ECB40-15CB
(34W88)
(34W91)
(34W89)
(34W92)
(34W94)
(34W95)
(1) 35A and
(1) 60A Circuit breaker
ECB40-20CB
(34W93)
(34W96)
(2) 60A Circuit breaker
1
1
1
1
2
2
2
2
208 3.0
10,250
220 3.4
11,450
230 3.7
12,550
240 4.0
13,650
208 3.8
12,800
220 4.2
14,300
230 4.6
15,700
240 5.0
17,100
208 4.5
15,400
220 5.0
17,100
230 5.5
18,800
240 6.0
20,500
208 6.0
20,500
220 6.7
22,900
230 7.3
25,100
240 8.0
27,300
208 6.8
23,100
220 7.6
25,800
230 8.3
28,200
240 9.0
30,700
208 9.4
32,000
220 10.5 35,800
230 11.5
39,200
240 12.5 42,600
208 11.3
38,400
220 12.6 43,000
230 13.8 47,000
240 15.0 51,200
208 15.0 51,200
220 16.8 57,300
230 18.4 62,700
240 20.0 68,200
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
45
45
4
45
4
50
4
50
4
60
50
60
60
60
- - -
- - -
- - -
- - -
4
40
4
40
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
46
48
50
52
28
29
30
31
24
25
26
27
46
48
50
52
41
43
45
47
32
33
35
36
28
29
30
31
23
24
25
26
50
53
55
57
45
48
50
52
38
40
42
44
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
4
45
4
45
4
50
50
4
50
4
4
35
35
35
40
4
45
4
25
4
25
4
25
4
30
4
30
4
30
4
30
4
35
4
30
30
4
30
4
30
4
35
50
4
50
4
60
4
25
25
30
4
50
4
50
60
THREE PHASE
8 kW
5 lbs.
10 kW
6 lbs.
15 kW
12 lbs.
20 kW
19 lbs.
ECB40-8 (34W98)
Terminal Block
ECB40-10
(34W99)
Terminal Block
ECB40-15CB (35W00)
50A Circuit breaker
ECB40-20CB (35W01)
(2) 35A Circuit breaker
1
1
1
2
208
220
230
240
208
220
230
240
208
220
230
240
208
220
230
240
6.0
6.7
7.3
8.0
7.5
8.4
9.2
11.3
20,500
22,900
25,100
27,300
25,600
28,700
31,400
10.0 34,100
38,400
12.6 43,000
13.5 47,000
15.0 51,200
15.0 51,200
16.8 57,300
18.4 62,700
20.0 68,200
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
26
27
28
28
31
33
34
35
44
46
48
50
31
33
34
35
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
26
28
29
30
4
30
30
30
30
35
35
35
40
45
50
50
50
35
35
35
4
40
- - -
- - -
- - -
- - -
4
30
4
30
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
4
30
35
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
57
61
63
65
1
3
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
2
Electric heater capacity only - does not include additional blower motor heat capacity.
4
Amps shown are for blower motor only.
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
Bold text indicates that the circuit breaker on “CB” circuit breaker models must be replaced with size noted. See Table on Page 6.
5
HACR type circuit breaker or fuse.
95
101
105
109
73
77
80
83
62
65
68
71
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
60
70
70
70
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
100
110
110
110
80
80
80
90
70
70
70
80
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
CBX32MV / Page 16
ELECTRIC HEAT DATA - CBX32MV-048 AND CBX32MV-060
Volts
Input kW
Input
1
Btuh
Input
2
Blower
Motor
Full
Load
Amps
3
Minimum
Circuit
Ampacity
5
Maximum
Overcurrent
Protection
Ckt 1 Ckt 2 Ckt 3 Ckt 1 Ckt 2 Ckt 3
Single Point
Power Source
3
Minimum
Circuit
Ampacity
5
Maximum
Overcurrent
Protection
SINGLE PHASE
4 kW
4 lbs.
5 kW
4 lbs.
6 kW
4 lbs.
8 kW
5 lbs.
9 kW
5 lbs.
12.5 kW
10 lbs.
15 kW
12 lbs.
20 kW
19 lbs.
25 kW
19 lbs.
ECB40-4 (55W89)
Terminal Block
ECB40-4CB (55W90)
35A Circuit breaker
ECB40-5 (34W87)
Terminal Block
ECB40-5CB
(34W90)
35A Circuit breaker
ECB40-6
(34W88)
Terminal Block
ECB40-6CB (34W91)
40A Circuit breaker
ECB40-8 (34W89)
Terminal Block
ECB40-8CB (34W92)
50A Circuit breaker
ECB40-9CB
(34W93)
60A Circuit breaker
THREE PHASE
8 kW
5 lbs.
10 kW
6 lbs.
15 kW
12 lbs.
20 kW
19 lbs.
25 kW
19 lbs.
ECB40-12.5CB
ECB40-15CB
ECB40-20CB
ECB40-25CB
ECB40-8
Terminal block
ECB40-10
Terminal block
ECB40-15CB
50A Circuit breaker
ECB40-20CB
(2) 35A Circuit breaker
ECB40-25CB
(34W94)
(1) 30A and
(1) 45A Circuit breaker
(34W95)
(1) 35A and
(1) 60A Circuit breaker
(34W96)
(2) 60A Circuit breaker
(34W97)
(1) 60A and
(2) 45A Circuit breaker
(34W98)
(34W99)
(35W00)
(35W01)
(35W02)
(1) 50A and
(1) 40A Circuit breaker
1
1
1
1
2
2
2
2
3
1
1
1
2
2
208 3.0 10,250 7.4
220 3.4 11,450 7.4
230 3.7 12,550 7.4
240 4.0 13,650 7.4
208 3.8 12,800 7.4
220 4.2 14,300 7.4
230 4.6 15,700 7.4
240 5.0 17,100 7.4
208 4.5 15,400 7.4
220 5.0 17,100 7.4
230 5.5 18,800 7.4
240 6.0 20,500 7.4
208 6.0 20,500 7.4
220 6.7 22,900 7.4
230 7.3 25,100 7.4
240 8.0 27,300 7.4
208 6.8 23,100 7.4
220 7.6 25,800 7.4
230 8.3 28,200 7.4
240 9.0 30,700 7.4
208 9.4 32,000 7.4
220 10.5 35,800 7.4
230 11.5 39,200 7.4
240 12.5 42,600 7.4
208 11.3 38,400 7.4
220 12.6 43,000 7.4
230 13.5 47,000 7.4
240 15.0 51,200 7.4
208 15.0 51,200 7.4
220 16.8 57,300 7.4
230 18.4 62,700 7.4
240 20.0 68,200 7.4
208 18.8 64,100 7.4
220 21.0 71,700 7.4
230 23.0 78,300 7.4
240 25.0 85,300 7.4
208 6.0 20,500 7.4
220 6.7 22,900 7.4
230 7.3 25,100 7.4
240 8.0 27,300 7.4
208 7.5 25,600 7.4
220 8.4 28,700 7.4
230 9.2 31,400 7.4
240 10.0 34,100 7.4
208 11.3 38,400 7.4
220 12.6 43,000 7.4
230 13.5 47,000 7.4
240 15.0 51,200 7.4
208 15.0 51,200 7.4
220 16.8 57,300 7.4
230 18.4 62,700 7.4
240 20.0 68,200 7.4
208 18.8 64,100 7.4
220 21.0 71,700 7.4
230 23.0 78,300 7.4
240 25.0 85,300 7.4
27 - - - - - -
4
30 - - - - - -
28 - - - - - -
4
30 - - - - - -
29 - - - - - -
4
30 - - - - - -
30 - - - - - -
4
30 - - - - - -
32 - - - - - 35 - - - - - -
33 - - - - - 35 - - - - - -
34 - - - - - 35 - - - - - -
35 - - - - - -
4
40 - - - - - -
36 - - - - - 40 - - - - - -
38 - - - - - 40 - - - - - -
39 - - - - - 40 - - - - - -
41 - - - - - -
4
45 - - - - - -
45 - - - - - 50 - - - - - -
47 - - - - - 50 - - - - - -
49 - - - - - 50 - - - - - -
51 - - - - - -
4
60 - - - - - -
50 - - - - - 60 - - - - - -
52 - - - - - 60 - - - - - -
54 - - - - - 60 - - - - - -
56 - - - - - 60 - - - - - -
28 38 - - 30
4
40 - - -
29 40 - - 30
4
40 - - -
30 42 - - 30 45 - - -
31 44 - - -
4
35
45 - - -
32 45 - - 35
4
45 - - -
33 48 - - 35
4
50 - - -
34 50 - - 35
4
50 - - -
35 52 - - -
4
40
60 - - -
50 50 - - -
4
50
4
50 - - -
52 53 - - 60 60 - - -
54 55 - - 60 60 - - -
56 57 - - 60 60 - - -
47
49
38
40
38
40
4
4
50
50
4
40
4
40
4
40
4
40
51 42 42 60 45 45
53 44 44 60 45 45
30 - - - - - 35 - - - - - -
31 - - - - - 35 - - - - - -
32 - - - - - 35 - - - - - -
33 - - - - - 35 - - - - - -
35 - - - - - 40 - - - - - -
37 - - - - - 40 - - - - - -
38 - - - - - 40 - - - - - -
39 - - - - - 40 - - - - - -
48 - - - - - 50 - - - - - -
51 - - - - - -
4
60 - - - - - -
52 - - - - - -
4
60 - - - - - -
54 - - - - - -
4
60 - - - - - -
35 26 - - -
4
40
37 28 - - -
4
40
38 29 - - -
4
40
4
30 - - -
4
30 - - -
4
30 - - -
39 30 - - -
4
40
35 - - -
42 33 - - -
4
45
4
35 - - -
44 34 - - -
4
45
4
35 - - -
45 36 - - 50 40 - - -
47 38 - - 50 40 - - -
100
105
109
113
77
81
84
88
66
69
72
75
- - -
- - -
- - -
- - -
122
129
135
141
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
62
65
67
70
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
75
78
81
84
1
3
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
2
Electric heater capacity only - does not include additional blower motor heat capacity.
4
Amps shown are for blower motor only.
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
Bold text indicates that the circuit breaker on “CB” circuit breaker models must be replaced with size noted. See Table on Page 6.
5
HACR type circuit breaker or fuse.
70
70
70
70
- - -
- - -
- - -
- - -
80
80
90
90
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
80
90
90
90
100
125
125
125
70
70
80
80
- - -
- - -
- - -
- - -
125
150
150
150
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
CBX32MV / Page 17
ELECTRIC HEAT DATA - CBX32MV-068
Volts
Input kW
Input
1
Btuh
Input
2
Blower
Motor
Full
Load
Amps
3
Minimum
Circuit
Ampacity
5
Maximum
Overcurrent
Protection
Ckt 1 Ckt 2 Ckt 3 Ckt 1 Ckt 2 Ckt 3
Single Point
Power Source
3
Minimum
Circuit
Ampacity
5
Maximum
Overcurrent
Protection
SINGLE PHASE
5 kW
4 lbs.
6 kW
4 lbs.
8 kW
5 lbs.
9 kW
5 lbs.
12.5 kW
10 lbs.
15 kW
12 lbs.
20 kW
19 lbs.
25 kW
19 lbs.
ECB40-5 (34W87)
Terminal Block
ECB40-5CB
(34W90)
35A Circuit breaker
ECB40-6
(34W88)
Terminal Block
ECB40-6CB (34W91)
40A Circuit breaker
ECB40-8 (34W89)
Terminal Block
ECB40-8CB (34W92)
50A Circuit breaker
ECB40-9CB
(34W93)
60A Circuit breaker
ECB40-12.5CB
(34W94)
(1) 30A and
(1) 45A Circuit breaker
ECB40-15CB (34W95)
(1) 35A and
(1) 60A Circuit breaker
ECB40-20CB
(2) 60A Circuit breaker
ECB40-25CB
(34W96)
(34W97)
(1) 60A and
(2) 45A Circuit breaker
THREE PHASE
8 kW
5 lbs.
10 kW
6 lbs.
15 kW
12 lbs.
20 kW
19 lbs.
25 kW
19 lbs.
ECB40-8 (34W98)
Terminal block
ECB40-10 (34W99)
Terminal block
ECB40-15CB
(35W00)
50A Circuit breaker
ECB40-20CB (35W01)
(2) 35A Circuit breaker
ECB40-25CB
(35W02)
(1) 50A and
(1) 40A Circuit breaker
1
1
1
2
2
2
2
3
1
1
1
2
2
208 3.8 12,800 7.4
220 4.2 14,300 7.4
230 4.6 15,700 7.4
240 5.0 17,100 7.4
208 4.5 15,400 7.4
220 5.0 17,100 7.4
230 5.5 18,800 7.4
240 6.0 20,500 7.4
208 6.0 20,500 7.4
220 6.7 22,900 7.4
230 7.3 25,100 7.4
240 8.0 27,300 7.4
208 6.8 23,100 7.4
220 7.6 25,800 7.4
230 8.3 28,200 7.4
240 9.0 30,700 7.4
208 9.4 32,000 7.4
220 10.5 35,800 7.4
230 11.5 39,200 7.4
240 12.5 42,600 7.4
208 11.3 38,400 7.4
220 12.6 43,000 7.4
230 13.5 47,000 7.4
240 15.0 51,200 7.4
208 15.0 51,200 7.4
220 16.8 57,300 7.4
230 18.4 62,700 7.4
240 20.0 68,200 7.4
208 18.8 64,100 7.4
220 21.0 71,700 7.4
230 23.0 78,300 7.4
240 25.0 85,300 7.4
208 6.0 20,500 7.4
220 6.7 22,900 7.4
230 7.3 25,100 7.4
240 8.0 27,300 7.4
208 7.5 25,600 7.4
220 8.4 28,700 7.4
230 9.2 31,400 7.4
240 10.0 34,100 7.4
208 11.3 38,400 7.4
220 12.6 43,000 7.4
230 13.5 47,000 7.4
240 15.0 51,200 7.4
208 15.0 51,200 7.4
220 16.8 57,300 7.4
230 18.4 62,700 7.4
240 20.0 68,200 7.4
208 18.8 64,100 7.4
220 21.0 71,700 7.4
230 23.0 78,300 7.4
240 25.0 85,300 7.4
32 - - - - - 35 - - - - - -
33 - - - - - 35 - - - - - -
34 - - - - - 35 - - - - - -
35 - - - - - -
4
40 - - - - - -
36 - - - - - 40 - - - - - -
38 - - - - - 40 - - - - - -
39 - - - - - 40 - - - - - -
41 - - - - - -
4
45 - - - - - -
45 - - - - - 50 - - - - - -
47 - - - - - 50 - - - - - -
49 - - - - - 50 - - - - - -
51 - - - - - -
4
60 - - - - - -
50 - - - - - 60 - - - - - -
52 - - - - - 60 - - - - - -
54 - - - - - 60 - - - - - -
56 - - - - - 60 - - - - - -
28 38 - - 30
4
40 - - -
29 40 - - 30
4
40 - - -
30 42 - - 30 45 - - -
31 44 - - -
4
35
45 - - -
32 45 - - 35
4
45 - - -
33 48 - - 35
4
50 - - -
34 50 - - 35
4
50 - - -
35 52 - - -
4
40
60 - - -
50 50 - - -
4
50
4
50 - - -
52 53 - - 60 60 - - -
54 55 - - 60 60 - - -
56 57 - - 60 60 - - -
4
40
47 38 38
4
50
49 40 40
4
50
4
40
4
4
40
40
51 42 42 60 45 45
53 44 44 60 45 45
30 - - - - - 35 - - - - - -
31 - - - - - 35 - - - - - -
32 - - - - - 35 - - - - - -
33 - - - - - 35 - - - - - -
35 - - - - - 40 - - - - - -
37 - - - - - 40 - - - - - -
38 - - - - - 40 - - - - - -
39 - - - - - 40 - - - - - -
48 - - - - - 50 - - - - - -
51 - - - - - -
4
60 - - - - - -
52 - - - - - -
4
60 - - - - - -
54 - - - - - -
4
60 - - - - - -
35 26 - - -
4
40
37 28 - - -
4
40
38 29 - - -
4
40
44 34 - - -
4
45
4
30 - - -
4
30 - - -
4
30 - - -
39 30 - - -
4
40
35 - - -
42 33 - - -
4
45
4
35 - - -
4
35 - - -
45 36 - - 50 40 - - -
47 38 - - 50 40 - - -
100
105
109
113
122
129
135
141
77
81
84
88
66
69
72
75
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
62
65
67
70
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
75
78
81
84
1
3
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
2
Electric heater capacity only - does not include additional blower motor heat capacity.
4
Amps shown are for blower motor only.
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
Bold text indicates that the circuit breaker on “CB” circuit breaker models must be replaced with size noted. See Table on Page 6.
5
HACR type circuit breaker or fuse.
70
70
70
70
- - -
- - -
- - -
- - -
80
80
90
90
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
100
125
125
125
125
150
150
150
80
90
90
90
70
70
80
80
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
- - -
CBX32MV / Page 18
DIMENSIONS - INCHES (MM) UPFLOW
3/4
(19)
3/4
(19)
11-1/16 (281)
D
SUPPLY
OPENING
3/4
(19)
DETAIL OF PIPING PLATE
1-1/8 (29)
SUCTION LINE
LINE VOLTAGE
(Top and Left Side)
INLETS
(Top and
Right Side)
TOP VIEW
B C
3-1/2 (89)
AIR FLOW
G
OPTIONAL
ELECTRIC
(Field
Installed)
BLOWER
Note − Units are shipped in one piece but may be disassembled into two separate sections for ease of installation.
A
PIPING
PLATE
H
5/8
(16)
Return Air
F
F R O N T V I E W
5/8
(16)
FILTER
ACCESS
SUCTION
LINE
LIQUID
LINE
FILTER
1
(25)
COIL
Return Air
S I D E
E
V I E W
5/8
(16)
Model
No.
F
G
D
E
H
A
B
C
CBX32MV-018/024 CBX32MV-024/030 inch
45-1/4
16-1/4
20-5/8
14-3/4
19
15
24-5/8
20-5/8
mm
1149
413
524
375
483
381
625
524
inch
49-1/4
21-1/4
20-5/8
19-3/4
19
20
24-5/8
24-5/8
mm
1251
540
524
502
483
508
625
625
CX32MV-036 inch
51
21-1/4
22-5/8
19-3/4
21
20
26-3/4
24-5/8
mm
1295
540
878
502
533
508
640
625
CBX32MV-048
CBX32MV-060 inch mm
58-1/2 1486
21-1/4 540
24-7/8
19-3/4
23
20
27-7/8
30-5/8
625
502
584
508
708
778
CBX32MV-068 inch
65
21-1/4
26-5/8
19-3/4
25
20
32-3/8
32-5/8
mm
1651
540
675
502
635
508
822
829
CBX32MV / Page 19
DIMENSIONS - INCHES (MM) DOWNFLOW
DETAIL OF PIPING PLATE
1-1/8 (29)
SUCTION LINE
5/8
(16)
5/8
(16)
E
F
RETURN
OPENING
1 (25)
1
(25)
TOP VIEW
3-1/2 (89)
B
FILTER
ACCESS
C
PIPING
PLATE
H
FILTER
SUCTION
LINE
COIL
AIR FLOW
G
A
OPTIONAL
ELECTRIC
HEAT
Installed)
LOW VOLTAGE
(Right Side)
BLOWER
5/8
(16)
Supply Air
D
Supply Air
3/4
(19)
F R O N T V I E W S I D E
11-1/16
V I E W
NOTE - Units are shipped in one piece but may be disassembled into two separate sections for ease of installation.
A
B
C
D
E
F
G
H
Model
No.
CBX32MV-018/024 CBX32MV-024/030 inch
45-1/4
16-1/4
20-5/8
14-3/4
19
15
24-5/8
20-5/8
mm
1149
413
524
375
483
381
625
524
inch
49-1/4
21-1/4
20-5/8
19-3/4
19
20
24-5/8
24-5/8
mm
1251
540
524
502
483
508
625
625
CX32MV-036 inch
51
21-1/4
22-5/8
19-3/4
21
20
26-3/4
24-5/8
mm
1295
540
878
502
533
508
640
625
CBX32MV-048
CBX32MV-060 inch mm
58-1/2 1486
21-1/4
24-7/8
540
625
19-3/4
23
20
27-7/8
30-5/8
502
584
508
708
778
CBX32MV-068 inch
65
21-1/4
26-5/8
19-3/4
25
20
32-3/8
32-5/8
mm
1651
540
675
502
635
508
822
829
CBX32MV / Page 20
DIMENSIONS - INCHES (MM) HORIZONTAL
RIGHT-HAND AIR DISCHARGE
DETAIL OF PIPING PLATE
FILTER
SUCTION
LINE
5/8
(16)
1-1/8 (29)
LIQUID
LINE
COIL
BLOWER C
Note − Units are shipped in one piece but may be disassembled into two separate sections for ease of installation.
H
SUCTION LINE
OPTIONAL ELECTRIC HEAT
(Field Installed)
TOP VIEW
A
G
5/8
(16)
LINE VOLTAGE
INLETS
(Top and Right Side)
11-1/16
(281)
3/4
(19)
3/4
(19)
5/8
(16)
E
F
RETURN
AIR
OPENING
1
(25)
PIPING
PLATE
AIR
FLOW
B AIR
OPENING
D
END VIEW
FILTER
ACCESS
F R O N T V I E W
LOW VOLTAGE INLETS
(Bottom and Right Side)
E N D V I E W
3/4
(19)
LEFT-HAND AIR DISCHARGE
FILTER
DETAIL OF PIPING PLATE
C BLOWER
COIL
3/4
(19)
Note − Units are shipped in one piece but may be disassembled into two separate sections for ease of installation.
3/4
(19)
11-1/16
(281)
LOW VOLTAGE
INLETS
5/8
(16)
OPTIONAL ELECTRIC HEAT
(Field Installed)
SUCTION LINE
TOP VIEW
A
G H
1-1/8 (29)
SUCTION
LINE
3/4
(19)
D
SUPPLY
AIR
OPENING
FILTER
ACCESS
B
AIR
FLOW
PIPING
PLATE
1
(25)
RETURN
OPENING
E
F
5/8
(16)
END VIEW
LINE VOLTAGE INLETS
(Bottom and Left Side)
Model
No.
G
H
E
F
C
D
A
B
CBX32MV-018/024 CBX32MV-024/030 inch
45-1/4
16-1/4
20-5/8
14-3/4
19
15
24-5/8
20-5/8
mm
1149
413
524
375
483
381
625
524
inch
49-1/4
21-1/4
20-5/8
19-3/4
19
20
24-5/8
24-5/8
mm
1251
540
524
502
483
508
625
625
FRONT VIEW
CX32MV-036 inch
51
21-1/4
22-5/8
19-3/4
21
20
26-3/4
24-5/8
mm
1295
540
878
502
533
508
640
625
CBX32MV-048
CBX32MV-060 inch
58-1/2
21-1/4
24-7/8
19-3/4
23
20
27-7/8
30-5/8
mm
1486
540
625
502
584
508
708
778
END VIEW
5/8
(16)
CBX32MV-068 inch
65
21-1/4
26-5/8
19-3/4
25
20
32-3/8
32-5/8
mm
1651
540
675
502
635
508
822
829
CBX32MV / Page 21
DIMENSIONS - INCHES (MM)
AIR FLOW
PIPING
PLATE
AIR FLOW
B
B
AIR FLOW
RIGHT-HAND AIR FLOW
B
A
5/8
(16)
AIR FLOW
5/8
(16)
5/8
(16)
A
LEFT-HAND AIR FLOW
A
Model
No.
in.
A mm
B in.
mm
CBX32MV-018/024 45-1/4 1149 16-1/4 413
CBX32MV-024/030 49-1/4 1251 21-1/4 540
CBX32MV-036
CBX32MV-048
CBX32MV-060
CBX32MV-068
51 1295 21-1/4 540
58-1/2 1486 21-1/4 540
65 1651 21-1/4 540
B
PIPING
PLATE
AIR FLOW
UPFLOW DOWNFLOW
A
5/8
(16)
SIDE RETURN UNIT STAND
(Upflow Only)
21-1/4
-024/030 thru -060
- 21-1/4 (540)
20 (508) to
ALL UNITS
CBX32MV / Page 22
DIMENSIONS - INCHES (MM)
DOWNFLOW COMBUSTIBLE FLOORING BASE
1-5/8
(41)
Catalog No. - 34J72
1-5/8
(41)
11-3/8
(289)
15
(381)
SUPPLY
OPENING
23-1/4
(591)
1-5/8
(41)
1-5/8 (41)
TOP VIEW
20
(508)
11-3/8
(289)
23−1/4
(591)
Catalog No. − 44K15
5/8
(16)
1-5/8
(41)
TOP VIEW
A
22-1/8 (562)
13-1/2 (343)
Opening
SIDE VIEW
3 (76)
Break off extended width at pre-perforated line to fit specific air handler application.
NOTE - Width of base includes an additional 2 in. (51 mm) for air handler positioning adjustment.
5/8
(16)
1-5/8 (41)
13-1/2 (343)
Opening
SUPPLY AIR
OPENING
SIDE VIEW
3 (76)
1
No modification required.
Model
No.
A
B
C
D
E
CBX32MV-018/024 CBX32MV-024/030 CBX32MV-036 in.
22-1/8
- - -
- - -
- - -
- - -
mm
562
- - -
- - -
- - -
- - -
in.
- - -
22-5/8
- - -
- - -
- - -
mm
- - -
575
- - -
- - -
- - -
in.
- - -
- - -
24-5/8
- - -
- - -
mm
- - -
- - -
625
- - -
- - -
CBX32MV-048
CBX32MV-060 in.
- - -
- - -
- - -
26-5/8
- - -
mm
- - -
- - -
- - -
676
- - -
CBX32MV-068 in.
- - -
- - -
- - -
- - -
28-5/8
mm
- - -
- - -
- - -
- - -
727
CBX32MV / Page 23
REVISIONS
Sections
Optional Accessories
Description of Change
Added icomfort Wi-Fi™ Thermostat.
Removed icomfort Touch
®
Communicating Thermostat (product discontinued).
Visit us at www.lennox.com
For the latest technical information, www.lennoxdavenet.com
Contact us at 1-800-4-LENNOX
NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency. ©2012 Lennox Industries, Inc.