LCH Energence Rooftop Units

Add to my manuals
44 Pages

advertisement

LCH Energence Rooftop Units | Manualzz

P R O D U C T S P E C I F I C AT I O N S

P A C K A G E D E L E C T R I C / E L E C T R I C

LCH

Energence

®

Rooftop Units

60 HZ

Bulletin No. 210556

August 2012

Supersedes June 2012

ASHRAE 90.1

COMPLIANT

7.5 to 12.5 Tons

Net Cooling Capacity − 90,000 to 136,000 Btuh

Optional Electric Heat - 7.5 to 60 kW

MODEL NUMBER IDENTIFICATION

Brand/Family

L = Energence ®

Unit Type

C = Packaged Electric Cooling w/ optional Electric Heat

Major Design Sequence

H = 1st Generation

L C H 120 H 4 B N 1 Y

Nominal Cooling Capacity - Tons

092 = 7.5 Tons

102 = 8.5 Tons

120 = 10 Tons

150 = 12.5 Tons

Cooling Efficiency

H = High Efficiency

S = Standard Efficiency

Voltage

Y = 208/230V-3 phase-60hz

G = 460V-3 phase-60hz

J = 575V-3 phase-60hz

Minor Design Sequence

1 = 1st Revision

2 = 2nd Revision

3 = 3rd Revision

Factory Installed Electric Heat

N = No Heat

C = 7.5 kW Electric Heat

E = 15 kW Electric Heat

G = 22.5 kW Electric Heat

J = 30 kW Electric Heat

K = 45 kW Electric Heat

L = 60 kW Electric Heat

Blower Type

B = Belt Drive, Constant Air Volume (CAV)

M = MSAV ® (Multi-Stage Air Volume) Supply Air Blower Option, Belt Drive

Refrigerant Type

4 = R-410A

A

FEATURES AND BENEFITS

E

D

M

G

C

L

K

J

I

N

H

B

F

Unit shown with optional

Economizer with

Outdoor Air Hoods

Lennox’ Energence

®

packaged rooftop unit product line was created to save energy with intelligence by offering some of the highest energy efficiency ratings available with a powerful, easy to use unit controller.

This makes Energence rooftop units perfect for business owners looking for an HVAC product with the lowest total cost of ownership. Energence rooftop units feature:

• Hinged Access Panels - Provide quick access to components and protect panels and roof from damage during servicing.

• Isolated Compressor Compartment - Allows performance check during normal compressor operation without disrupting airflow.

• Corrosion-Resistant Removable, Reversible Drain Pan - Provides application flexibility, durability and improved serviceability.

• Thermostatic Expansion Valves - Provide peak cooling performance across the entire application range.

• Scroll Compressors - Standard on all units for reliable, long-term operation.

Lennox’ Environ™ Coil System - Smaller, lighter condenser coil.

• Humiditrol

®

Dehumidification System - Patented system allows for independent control of temperature and humidity, providing enhanced comfort control.

Constant Air Volume (CAV) or MSAV

® constant or multi-staged air delivery.

(Multi-Stage Air Volume) Supply Air Blower Option - Allows

• Auto-Tensioner for Blower Belt - Factory option ensures blower is delivering the proper airflow for comfort, while maximizing efficiency and belt life.

• MERV 13 Filters - Available as factory or field option, provide an enhanced level of indoor air quality, and can help the building qualify for additional LEED credits.

• Foil-Faced Insulation - Insulation on all internal surfaces that have contact with airflow helps minimize airborne fibers and improve IAQ.

Prodigy

®

Control System

Standard on every Energence rooftop unit, the new Prodigy

®

unit controller is the heart of the Lennox

®

controls offering. The intuitive user interface makes setup, troubleshooting and service easier than ever. Each unit tracks the runtime of every major component and records the date and time when service or maintenance is performed.

SmartWire™ System

The SmartWire system simplifies field sensor or thermostat installation through advanced connectors that are keyed and color-coded to help prevent miswiring. Not only is the wire coloring scheme standardized across all models, each connection is intuitively labeled to make troubleshooting and servicing quick and easy.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 2

APPROVALS

AHRI Certified to AHRI Standard

340/360-2007.

ETL listed.

Efficiency ratings are certified by

CSA.

Components are bonded for grounding to meet safety standards for servicing required by UL,

ULC and National and Canadian

Electrical Codes.

All models are ASHRAE 90.1-2010 energy efficiency compliant and meet or exceed requirements of

Section 6.8.

MSAV models meet California

Code of Regulations, Title 24 and ASHRAE 90.1-2010 Section

6.4.3.10 requirements for staged airflow.

A

FEATURES AND BENEFITS

Contents

Accessory Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .37

Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36

Electrical/Electric Heat Data . . . . . . . . . . . . . . . . . . . . . . . .29

Electric Heat Capacities. . . . . . . . . . . . . . . . . . . . . . . . . . .33

Features And Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Humiditrol

®

Dehumidification System Ratings . . . . . . . . . . . . . . .23

Optional Conventional Temperature Control Systems . . . . . . . . . . .34

Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

Outdoor Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . .34

Prodigy

®

Control System . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

Sequence Of Operation - Msav

®

(Multi-Stage Air Volume) Models . . . . .11

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33

Weight Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35

APPROVALS

AHRI Certified to AHRI Standard

340/360-2007.

ETL listed.

Efficiency ratings are certified by

CSA.

Components are bonded for grounding to meet safety standards for servicing required by UL,

ULC and National and Canadian

Electrical Codes.

All models are ASHRAE 90.1-2010 energy efficiency compliant and meet or exceed requirements of

Section 6.8.

MSAV models meet California

Code of Regulations, Title 24 and ASHRAE 90.1-2010 Section

6.4.3.10 requirements for staged airflow.

E

NERGY

S

TAR ®

certified units are designed to use less energy, help save money on utility bills, and help protect the environment.

The E

NERGY

S

TAR ®

Partner of the Year Award signifies that

Lennox has made outstanding contributions to design energy efficient units that will lower energy bills, while meeting industry standards for comfort and indoor air quality. Lennox was the first

HVAC manufacturer to win this award and has been a four-time recipient since 2003.

ISO 9001 Registered

Manufacturing Quality System.

WARRANTY

Limited five years on compressors.

Limited three years on the Lennox’

Environ™ Coil System.

Limited three years on Prodigy

®

Unit Controller.

Limited one year all other covered components.

COOLING SYSTEM

Designed to maximize sensible and latent cooling performance at design conditions.

System can operate from 0°F to 125°F without any additional controls.

R-410A Refrigerant

Non-chlorine based, ozone friendly, R-410A.

B

Scroll Compressors

Scroll compressors on all models for high performance, reliability and quiet operation.

Resiliently mounted on rubber grommets for quiet operation.

Compressor Crankcase Heaters

Protects against refrigerant migration that can occur during low ambient operation.

Thermal Expansion Valve

Assures optimal performance throughout the application range.

Removable element head.

Filter/Driers

High capacity filter/drier protects the system from dirt and moisture.

High Pressure Switches

Protects the compressors from overload conditions such as dirty condenser coils, blocked refrigerant flow, or loss of outdoor fan operation.

Low Pressure Switches

Protects the compressors from low pressure conditions such as low refrigerant charge, or low/no airflow.

Freezestats

Protects the evaporator coil from damaging ice build-up due to conditions such as low/no airflow, or low refrigerant charge.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 3

FEATURES AND BENEFITS

COOLING SYSTEM

(CONTINUED)

C

Lennox’ Environ™ Coil System

Condenser coil features lightweight, all aluminum brazed fin construction.

Constructed of three components: a flat extrusion tube, fins inbetween the flat extrusion tube and two refrigerant manifolds.

Environ™ Coil System Features:

• Improved heat transfer performance due to high primary surface area (flat tubes) versus secondary surface (fins).

• Smaller internal volume

(reduced refrigerant charge).

• High durability (all aluminum construction).

• Fewer brazed joints.

• Compact design (reduces unit weight).

• Easy maintenance/cleaning.

Face-split design.

Mounting brackets with rubber inserts secure coil to unit providing vibration dampening and corrosion protection.

Evaporator Coil

Copper tube construction, enhanced rippled-edge aluminum fins, flared shoulder tubing connections, silver soldered construction for improved heat transfer.

Cross row circuiting with rifled copper tubing optimizes both sensible and latent cooling capacity.

Condensate Drain Pan

Plastic pan, sloped to meet drainage requirements per

ASHRAE 62.1.

Side or bottom drain connections.

Reversible to allow connection at back of unit.

D

Outdoor Coil Fan Motors

Thermal overload protected, totally enclosed, permanently lubricated ball bearings, shaft up, wire basket mount.

Outdoor Coil Fans

PVC coated fan guard furnished.

REQUIRED SELECTIONS

Cooling Capacity

Specify nominal cooling capacity of the unit

OPTIONS/ACCESSORIES

Factory Installed

Conventional Fin/Tube

Condenser Coil

(replaces Environ Coil System)

Copper tube construction, enhanced rippled-edge aluminum fins, flared shoulder tubing connections, silver soldered construction.

NOTE - Required if Humiditrol

®

Dehumidification System is ordered.

Service Valves

Fully serviceable brass valves installed in discharge & liquid lines.

Not available for units equipped with Environ Coil System or

Humiditrol option.

Factory or Field Installed

Condensate Drain Trap

Available in copper or PVC.

Field installed only, may be factory ordered to ship with unit.

Drain Pan Overflow Switch

Monitors condensate level in drain pan, shuts down unit if drain becomes clogged.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 4

FEATURES AND BENEFITS

CABINET

E

Construction

Heavy-gauge steel panels and full perimeter heavy-gauge galvanized steel base rail provides structural integrity for transportation, handling, and installation.

Base rails have rigging holes.

Three sides of the base rail have forklift slots.

Raised edges around duct and power entry openings in the bottom of the unit provide additional protection against water entering the building.

Airflow Choice

Units are shipped in downflow

(vertical) configuration, can be field converted to horizontal airflow with optional Horizontal Discharge Kit.

Duct Flanges

Provided for horizontal duct attachment.

Power Entry

Electrical lines can be brought through the unit base or through horizontal access knock-outs

Exterior Panels

Constructed of heavy-gauge, galvanized steel with a two-layer enamel paint finish.

Insulation

All panels adjacent to conditioned air are fully insulated with nonhygroscopic fiberglass insulation.

Unit base is fully insulated. The insulation also serves as an air seal to the roof curb, eliminating the need to add a seal during installation.

F

Hinged Access Panels

Hinged tool-less access panels are provided for the filter section, blower/heating section and compressor/controls section.

All hinged panels have seals and quarter-turn latching handles to provide a tight air and water seal.

REQUIRED SELECTIONS

Airflow Configuration

Specify downflow or horizontal.

OPTIONS/ACCESSORIES

Factory or Field Installed

Return Air Adaptor Plate

For same size L Series

®

and

T-Class™ unit replacement.

Installs on return air opening in unit to match return air opening on existing roof curbs. Also see

Accessory Air Resistance table.

Factory Installed

Corrosion Protection

A completely flexible immersed coating with an electrodeposited dry film process. (AST ElectroFin

E-Coat) Meets Mil Spec

MIL-P-53084, ASTM B117

Standard Method Salt Spray

Testing.

Indoor Corrosion Protection:

- Coated coil

- Coated reheat coil (Humiditrol)

- Painted blower housing

- Painted base

Outdoor Corrosion Protection:

- Coated coil

- Painted base

Field Installed

Coil Guards

Painted, galvanized steel wire guards to protect outdoor coil.

Not used with Hail Guards.

Hail Guards

Constructed of heavy gauge steel, painted to match cabinet, helps protect outdoor coils from hail damage.

Not used with Coil Guards.

Horizontal Discharge Kit

Consists of duct covers to block off downflow supply and return air openings for horizontal applications.

Also includes return air duct flanges for end return air when economizer is used in horizontal applications.

NOTE - When configuring unit for horizontal application with economizer, a separate Horizontal

Barometric Relief Damper with

Hood must be ordered separately for installation in the return air duct.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 5

FEATURES AND BENEFITS

G

BLOWER

A wide selection of supply air blower options are available to meet a variety of airflow requirements.

Motor

Overload protected, equipped with ball bearings. Belt drive motors are offered on all models and are available in several different sizes to maximize air performance.

Motor Efficiency

All blower motors 5 hp and above meet minimum energy efficiency standards in accordance with the

Energy Independence and Security

Act (EISA).of 2007.

Supply Air Blower

Forward curved blades, double inlet, blower wheel is statically and dynamically balanced. Equipped with ball bearings and adjustable pulley (allows speed change).

Blower assembly slides out of unit for servicing.

REQUIRED SELECTIONS

Select Constant Air Volume

(CAV) or MSAV

®

(Multi-Stage

Air Volume) Supply Air Blower

Option

On Constant Air Volume (CAV) models, the supply air blower will provide a constant volume of air.

On MSAV (Multi-Stage Air Volume) models the supply air blower will stage the amount of airflow according to compressor stages, heating demand, ventilation demand or smoke alarm.

NOTE - Units with the MSAV supply air blower option have the same face split indoor coils as units with the CAV supply air blower option. Part load airflow in cooling mode on MSAV units should not be set below 220 cfm/ nominal full load ton to reduce the risk of evaporator coil freeze-up.

H

Utilizes a Variable Frequency

Drive (VFD) to stage the supply blower airflow. The VFD alters the frequency and voltage of the power supply to the blower to control blower speed.

The amount of airflow for each stage can be set according to an

ECTO parameter in the Prodigy

®

Unit Controller. Unit is shipped from the factory with preset airflow.

The MSAV supply air blower option can be ordered with or without an Electronic Bypass Control. If equipped with the bypass control the MSAV features manual

(default) or automatic electronic bypass control of the VFD. In case of a VFD malfunction, a VFD alarm is generated by the Prodigy

®

Unit Controller. The VFD can be manually bypassed to continue unit operation at full blower speed.

Or the unit controller can be set to automatically switch to full blower speed if a VFD alarm is generated.

The VFD has an operational range of -40 to 125°F outdoor air ambient temperature.

Lower operating costs are obtained when the blower is operated on lower speeds.

Ordering Information

Specify motor horsepower and drive kit number when base unit is ordered.

OPTIONS/ACCESSORIES

Factory Installed

Blower Belt Auto-Tensioner

Provides proper tension to belt drive blower belt without the need for regular adjustments. Maintains airflow and proper performance.

ELECTRICAL

REQUIRED SELECTIONS

Voltage Choice

Specify when ordering base unit.

OPTIONS/ACCESSORIES

Factory Installed

Circuit Breakers

HACR type. For overload and short circuit protection. Factory wired and mounted in the power entry panel. Current sensitive and temperature activated. Manual reset.

Phase/Voltage Detection

(Optional for CAV Models Only)

Phase detection monitors power supply to assure phase is correct at unit start-up. If phase is incorrect, the unit will not start and an alarm code is reported to the unit controller. Protects unit from being started with incorrect phasing which could lead to issues such as compressors running backwards.

Voltage detection monitors power supply voltage to assure proper voltage. If voltage is not correct

(over/under voltage conditions) the unit will not start and an alarm code is reported to the unit controller.

NOTE - Phase/voltage detection is furnished when the MSAV (Multi-

Stage Air Volume) option is ordered.

Factory or Field Installed

Disconnect Switch

Accessible from outside of unit, spring loaded weatherproof cover furnished.

I

Electric Heat

Helix wound nichrome elements, individual element limit controls, wiring harness. Unit fuse block is furnished as standard. See

Options / Accessories tables for ordering information.

J

GFI Service Outlets (2)

115V ground fault circuit interrupter

(GFCI) type, non-powered, fieldwired.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 6

FEATURES AND BENEFITS

INDOOR AIR QUALITY

K

Air Filters

Disposable 2 inch filters furnished as standard.

OPTIONS/ACCESSORIES

Factory or Field Installed

Healthy Climate

®

High

Efficiency Air Filters

Disposable MERV 8 or MERV 13

(Minimum Efficiency Reporting

Value based on ASHRAE 52.2) efficiency 2 inch pleated filters.

Healthy Climate

®

UVC

Germicidal Lamps

Germicidal lamps emit ultra-violet

(UV-C) energy, which has been proven to be effective in reducing microbes such as viruses, bacteria, yeasts, and molds. This process either destroys the organism or controls its ability to reproduce.

UV-C energy greatly reduces the growth and proliferation of mold and other bioaerosols (bacteria and viruses) on illuminated surfaces (particularly coil and drain pan).

Lamps are field installed in the blower/evaporator coil section.

All necessary hardware for installation is included.

Lamps operate on 208/230V power supply. Step-down transformer must be field supplied when used with 460V and 575V rooftop units.

Magnetic safety interlock terminates power when access panels are removed.

Approved by ETL.

Field Installed

Replacement Filter Media Kit

With Frame

Replaces existing pleated filter media. Includes washable metal mesh screen and metal frame with clip for holding replaceable nonpleated filter.

Indoor Air Quality (CO

Sensors

Monitors CO

2

)

2

levels, reports to the Prodigy

®

Unit Controller which adjusts economizer dampers as needed.

SERVICEABILITY

Designed to streamline general maintenance and decrease troubleshooting time.

Diagnostics

Prodigy Unit Controller diagnostic scrolling text pinpoints problems, minimizing troubleshooting time.

SmartWire™ System

Advanced wiring connectors are keyed and color-coded to prevent miswiring. Wire coloring scheme is standardized across all models.

Each connection is intuitively labeled to make troubleshooting and servicing quick and easy.

Electrical Plugs

Positive connection electrical plugs are used to connect common accessories or maintenance parts for easy removal or installation.

Toolless, Hinged Access

Panels

Large access panels are hinged and have quarter-turn, latching handles for quick and easy access to maintenance areas (filter, compressor / controls/ blower / heat section).

Blower Access

Supply air blower parts are located near the access door for easy servicing and adjustment.

Thermal Expansion Valves

Thermal expansion valves are located near the perimeter of the unit for easier access.

Removable element head allows change out of element and bulb without removing the TXV.

Coil Cleaning

Condenser coils with hinged access panels allow easy cleaning.

Standard Components

A large number of common maintenance parts are standard throughout the entire range of sizes (3-30 tons), reducing the need to carry a lot of different parts to the job or maintain in inventory.

Compressor Compartment

Compressors are located near the perimeter of the unit for easier access.

Compressors are isolated from the condenser airflow allowing system operation checks to be done without changing the airflow across the outdoor coils.

Service Valves (optional)

Optional factory installed liquid and discharge service valves allow refrigerant to be isolated to the high side for service work on the low side of the refrigeration system.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 7

PRODIGY

®

CONTROL SYSTEM

L

PRODIGY UNIT CONTROLLER

Indoor Air Quality Input -

Demand Control Ventilation ready

Low Ambient Controls - Cooling operation down to 0°F.

Gas Valve Time Delay Between

First and Second Stage

Minimum Compressor Run Time

The Prodigy Unit Controller is a microprocessor-based control board that provides flexible control of all unit functions.

Prodigy Unit Controller features:

Scrolling Display - Scrolls full text instead of numerical codes.

Push Buttons - Simplified navigation during setup and diagnostics.

Guided Setup Procedure -

Insures proper installation and setup of the rooftop unit.

Profile setup - Copy key setpoints between units with the same configuration greatly reducing setup time.

USB Port - Easily download and transfer unit information via a USB flash drive and also interface with Lennox

Unit Controller

Software.

Self Test Mode - Confirm proper component and system operation.

Time Clock with Run-time

Information

Built-In Functions Include:

Adjustable Blower On/Off Delay

Built-in Control Parameter

Defaults

Compressor Time-Off Delay

DDC Compatible

Dirty Filter Switch Input

Discharge Air Temperature

Control

Display/Sensor Readout

Network Capable - Can be daisy chained to other units or controls.

Night Setback Mode

Return Air Temperature Limit

Control

Safety Switch Input - Allows

Controller to respond to a external safety switch trip.

Service Relay Output

Smoke Alarm Mode - Four choices.

Staging - up to 4 heat/4 cool (zone sensor or network operation). Up to 2 heat/2 cool (standard Prodigy unit controller thermostat input).

Up to 3 cool (thermostat input with additional relay).

“Strike Three” Protection

Gas Reheat Control -

Simultaneous heating and cooling operation for controlling humidity for process air applications such as supermarkets.

On Demand Dehumidification -

Monitors and controls condenser hot gas reheat operation with

Humiditrol

®

option.

Thermostat Bounce Delay

Warm Up Mode Delay

LED Indicators

PC Interface - For use with PC with optional Unit Controller software.

Zone Sensor Operation - Controls zone temperature.

OPTIONS / ACCESSORIES

Factory or Field Installed

Economizer Control Options -

See Economizer / Outdoor Air /

Exhaust Options.

Fresh Air Tempering

Extensive Unit Diagnostics -

Over 100 diagnostic and status messages in English.

Exhaust Fan Control Modes -

Fresh air damper position.

Blower Proving Switch

Monitors blower operation, shuts down unit if blower fails.

Dirty Filter Switch

Senses static pressure increase indicating dirty filter condition.

NOTE - Prodigy Control System features shown vary with the type of rooftop unit the control is installed in.

Permanent Diagnostic Code Storage

Field Changeable Control

Setpoints - Over 200 different control setpoints.

Energence

NOTE - See separate Prodigy Control

System Product Specifications Bulletin for additional information.

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 8

CONTROLS OPTIONS

Factory or Field Installed

Fresh Air Tempering

Used in applications with high outside air requirements. The

Controller energizes the first stage heat as needed to maintain a minimum supply air temperature for comfort, regardless of the thermostat demand. When ordered as a factory option, the sensor ships with the unit but must be field installed.

Smoke Detector

Photoelectric type, installed in supply air section, return air section or both sections. Available with power board and single sensor (supply or return) or power board and two sensors (supply and return). Power board located in unit control compartment.

Interoperability via BACnet

®

or

LonTalk

®

Protocols

Communication compatible with third-party automation systems that support the BACnet Application

Specific Controller device profile, LonMark

®

Space Comfort

Controller functional profile, or

LonMark Discharge Air Controller functional profile.

Commercial Control Systems

L Connection

®

Network Control

System

Complete building automation control system for single or multi-zone applications. Options include local interface, software for local or remote communication, and hardware for networking other control functions. See L

Connection Network Control

System Product Specifications

Bulletin for details.

Aftermarket DDC

Novar® Unit Controller and options.

Thermostats

Control system and thermostat options. Aftermarket unit controller options.

Field Installed

Humidity Sensor Kit

Humidity sensor required with factory installed Humiditrol

® dehumidification option or

Supermarket reheat field selectable option.

OPTIONS / ACCESSORIES

M

ECONOMIZER/EXHAUST

OPTIONS

Factory or Field Installed

Economizer - Downflow or

Horizontal With Hood

Parallel gear-driven action return air and outdoor air dampers, plug-in connections to unit, nylon bearings, neoprene seals, 24-volt, fully-modulating, spring return motor, adjustable minimum damper position. Economizer includes outdoor air hood.

Outdoor Air Hood is included when economizer is factory installed and is furnished with economizer when ordered for field installation.

Choice of economizer control options:

1. Differential Sensible Control

Factory setting. Uses outdoor air and return air sensors that are furnished with the unit.

The Prodigy Unit Controller compares outdoor air with return air. When the outdoor air is below the configured setpoint and cooler than return air, the controller activates the economizer.

NOTE - Differential Sensible

Control can be configured in the field to provide Offset Differential

Sensible Control or Single

Sensible Control.

In Offset Differential Sensible

Control mode, the economizer is enabled if the temperature differential (offset) between outdoor air and return air reaches the configured setpoint.

In Single Sensible Control mode, the economizer is enabled when outdoor air temperature falls below the configured setpoint.

2. Global Control

The unit controller communicates with a DDC system with one global sensor

(enthalpy or sensible) to determine whether outside air is suitable for free cooling on all units connected to the control system. Sensor must be field provided.

N

3. Single Enthalpy Control

Outdoor air enthalpy sensor enables economizer if the outdoor enthalpy is less than the setpoint of the board.

4. Differential Enthalpy Control

Two solid-state enthalpy sensors allow the economizer control to select between outdoor air or return air, whichever has lower enthalpy.

Factory or Field Installed

Downflow Barometric Relief

Dampers

Barometric Relief Dampers allow relief of excess air, aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle For use in downflow applications only. Exhaust hood furnished.

Power Exhaust Fan

Installs internal to unit for downflow applications only with Economizer option. Provides exhaust air pressure relief. Interlocked to run when supply air blower is operating, fan runs when outdoor air dampers are 50% open

(adjustable), motor is overload protected. Requires Economizer and Downflow Barometric Relief

Dampers. Fan is 20 in. diameter with 5 blades (K1PWRE10B) WITH

1/3 hp motor.

Field Installed

Horizontal Barometric Relief

Dampers

For use when unit is configured for horizontal applications requiring an economizer.

Allows relief of excess air

Aluminum blade dampers prevent blow back and outdoor air infiltration during off cycle.

Field installed in return air duct.

Bird screen and exhaust hood furnished.

Requires Horizontal Discharge Kit.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 9

OUTDOOR AIR OPTIONS

Factory or Field Installed

Outdoor Air Damper - Downflow or Horizontal With Air Hood

Linked mechanical dampers, 0 to

25% (fixed) outdoor air adjustable, installs in unit. Includes outdoor air hood.

Automatic model features fully modulating spring return damper motor with plug-in connection.

Manual model features a slide damper.

Maximum mixed air temperature in cooling mode: 100°F.

ROOF CURBS (DOWNFLOW)

Nailer strip furnished, mates to unit, US National Roofing

Contractors Approved, shipped knocked down.

Clip Curbs - Uses interlocking tabs to fasten corners together. No tools required.

Standard Curbs - Curb corners fasten together with furnished hardware.

Transition Curbs - Curbs are regionally sourced. Dimensions will vary based upon the source.

Contact your Lennox sales representative for a detailed cut sheet with applicable dimensions.

See Options/Accessories table for available curbs.

CEILING DIFFUSERS

Ceiling Diffusers

(Flush or Step-Down)

Aluminum grilles, large center grille, insulated diffuser box with flanges, hanging rings furnished, interior transition (even air flow), internally sealed (prevents recirculation), adapts to T-bar ceiling grids or plaster ceilings.

Transitions (Supply and

Return)

Used with diffusers, installs in roof curb, galvanized steel construction, flanges furnished for duct connection to diffusers, fully insulated.

OPTIONS / ACCESSORIES

HUMIDITROL DEHUMIDIFICATION® SYSTEM

NOTE - Not available with

Environ Coil System.

Conventional Fin/Tube condenser coil must be ordered as a factory option.

Factory installed option designed to control humidity.

Provides dehumidification on demand using ASHRAE 90.1 recommended method for comfort conditioning humidity control.

Unit comes equipped with one row reheat coil, solenoid valve and humidity controller.

In addition to a thermostat or room sensor used for conventional operation, a humidity sensor is required and must be located in the occupied space. Remote

Mounted Humidity Sensor Kit is required for field installation.

The humidity sensor provides input to the Unit Controller which is used to control activation of the dehumidification operation.

Reheat controls are located in the compressor control section of the unit for easy access.

Benefits

Improves indoor air quality.

Helps prevents damage due to high humidity levels.

Improves comfort levels by reducing space humidity levels.

OPERATION

No Dehumidification Demand

The unit will operate conventionally whenever there is a demand for cooling or heating and no dehumidification demand.

Free cooling is only permitted when there is no demand for dehumidification.

Dehumidification Demand Only

The Unit Controller is factory set at 60% relative humidity setpoint and can be adjusted at the Unit

Controller or with optional Unit

Controller Software.

For L Connection

®

Network Control

Panel (NCP) applications, the humidity setpoint can be adjusted at the NCP.

Reheat operation will initiate on a dehumidification demand and does not require a cooling demand.

REHEAT

COIL

HUMIDITROL REFRIGERANT SCHEMATIC

EVAPORATOR

COIL

CONDENSER COIL

The unit will operate in the dehumidification mode until the relative humidity of the conditioned space is below the setpoint.

The reheat coil is sized to provide

68°F to 75°F supply air during reheat operation.

This reduces sensible cooling capacity and extends compressor run time to control humidity when the cooling load is low.

A solenoid valve diverts hot gas from the compressor to the reheat coil.

The cooled and dehumidified air from the evaporator is reheated as it passes through the reheat coil.

The de-superheated and partially condensed refrigerant continues to the outdoor condenser coil where condensing is completed. The unit will continue to operate in this mode until the dehumidification demand is satisfied.

See Sequence of Operation for additional information.

Dehumidification and Cooling

Demand (Thermostat/Room

Sensor Application)

If both a dehumidification and a full cooling load demand occur, the system will operate in cooling until the cooling demand is satisfied.

Then the system will energize the dehumidification mode.

ACCESSORIES

Humidity Sensor Kit, Remote

Mounted Humidity sensor required with factory installed Humiditrol

®

Option or Supermarket reheat field selectable option.

REFRIGERANT

CIRCUIT 1

REFRIGERANT

CIRCUIT 2

REHEAT

VALVE

CHECK

VALVE

EXPANSION

VALVES

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 10

SEQUENCE OF OPERATION - MSAV

®

(MULTI-STAGE AIR VOLUME) MODELS

Objective: Outline the unit functions as a result of room thermostat or zone sensor demands.

Given: When economizer is present, it will function as an integral part of the unit cooling system. When not present,

unit will function as if economizer is present but outdoor ambient is high and sensed as not suitable.

UNIT OPERATION WITH 2-STAGE THERMOSTAT (2 COOL AND 2 HEAT STAGES, Y1, Y2, W1, W2)

SUPPLY AIR BLOWER SPEED

Unit has following supply air blower speed setting:

• Ventilation speed

• Cooling Speed - Low

• Cooling Speed - High

• Heating speed

• Smoke speed (Used only in smoke removal option - not discussed)

1

UNIT FEATURES AN ECONOMIZER AND OUTDOOR AIR IS SUITABLE

Cooling - Thermostat Mode (Y1, Y2)

Y1 Demand:

All compressors are off, supply air blower is on low cooling speed to minimize blower power consumption, economizer modulates (minimum to maximum open position) to maintain 55°F supply air temperature (default unit controller setting).

Y2 Demand:

All compressors are off, supply air blower is on high cooling speed providing higher cooling capacity, and economizer modulates to maintain 55°F supply air temperature.

If economizer stays at maximum open for 3 minutes, compressor 1 is energized while supply air blower stays on high cooling speed providing maximum cooling capacity.

1

Outdoor air suitability is determined by the energy state of outdoor ambient (enthalpy or sensible) and its ability to achieve the desired free cooling effects. Outdoor air suitability can also be determined by a third party controller and provided to the rooftop unit via a network connection.

UNIT DOES NOT FEATURE AN ECONOMIZER OR OUTDOOR AIR IS NOT SUITABLE

Y1 Demand:

Compressor 1 operates and supply air blower operates at low cooling speed.

Y2 Demand:

All compressors operate and supply air blower operates at high cooling speed.

DEHUMIDIFICATION MODE

If a unit with Humiditrol

®

Dehumidification Option receives a call for dehumidification, economizer free cooling is locked out.

Call For Dehumidification, No Y1, Y2 demand:

1st stage compressor operates, supply air blower operates at high cooling speed, and the reheat valve is energized.

Y1 Demand With A Call For Dehumidification:

All compressors operate, supply air blower operates at high cooling speed and the reheat valve is energized.

Y2 Demand With A Call For Dehumidification:

All compressors operate, supply air blower operates at high cooling speed, and the reheat valve is de-energized.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 11

SEQUENCE OF OPERATION - MSAV

®

(MULTI-STAGE AIR VOLUME) MODELS

UNIT OPERATION WITH 3-STAGE THERMOSTAT OR ZONE SENSOR

(3 COOL AND 2 HEAT STAGES, Y1, Y2, Y3 AND W1, W2)

SUPPLY AIR BLOWER SPEED

Unit has following supply air blower speed setting:

• Ventilation speed

• Cooling Speed - Low

• Cooling Speed - High

• Heating speed

• Smoke speed (Used only in smoke removal option - not discussed)

1

UNIT FEATURES AN ECONOMIZER AND OUTDOOR AIR IS SUITABLE

Cooling - Thermostat or Zone Sensor Mode (Y1, Y2, Y3)

Y1 Demand:

All compressors are off, supply air blower is on low cooling speed to minimize blower power consumption, economizer modulates (minimum to maximum open position) to maintain 55°F supply air temperature (default unit controller setting).

Y2 Demand:

All compressors are off, supply air blower is on high cooling speed providing higher cooling capacity, and economizer modulates to maintain 55°F supply air temperature.

If economizer stays at maximum open for 3 minutes, compressor 1 is energized while supply air blower stays on high cooling speed providing maximum cooling capacity. After compressors are energized the economizer stays at maximum open.

Y3 Demand:

Compressors 1 and 2 are energized while supply air blower stays on high cooling speed.

1

Outdoor air suitability is determined by the energy state of outdoor ambient (enthalpy or sensible) and its ability to achieve the desired free cooling effects. Outdoor air suitability can also be determined by a third party controller and provided to the rooftop unit via a network connection.

UNIT DOES NOT FEATURE AN ECONOMIZER OR OUTDOOR AIR IS NOT SUITABLE

Y1 Demand:

Compressor 1 operates and supply air blower operates at low cooling speed.

Y2 or Y3 Demand:

All compressors operate and supply air blower operates at high cooling speed.

DEHUMIDIFICATION MODE

If a unit with Humiditrol® Dehumidification Option receives a call for dehumidification, economizer free cooling is locked out.

Call For Dehumidification, No Y1, Y2 demand:

1st stage compressor operates, supply air blower operates at high cooling speed, and the reheat valve is energized.

Y1 Demand With A Call For Dehumidification:

All compressors operate, supply air blower operates at high cooling speed and the reheat valve is energized.

Y2 Or Y3 Demand With A Call For Dehumidification:

All compressors operate, supply air blower operates at high cooling speed, and the reheat valve is de-energized.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 12

SEQUENCE OF OPERATION - MSAV

®

(MULTI-STAGE AIR VOLUME) MODELS

HEATING MODE (ELECTRIC HEAT)

NOTE - HEATING MODE IS THE SAME FOR ALL CONTROL OPTIONS

W1 Demand:

1st stage electric heat is energized and the supply air blower operates at heating speed.

W2 Demand:

2nd stage electric heat is energized and the supply air blower operates at heating speed (45 or 60 kW electric heat option only).

MODULATING OUTDOOR AIR DAMPER

The minimum damper position for “occupied low blower” and “occupied high blower” is adjusted during unit setup to provide minimum fresh air requirements per ASHRAE 62.1 at the corresponding supply air blower speeds.

• When supply air blower is off or the unit is in unoccupied mode, the outdoor air damper is closed.

• When unit is in occupied mode and supply air blower is operating at a speed below the “midpoint” blower speed, the outdoor air damper is at minimum “low blower” position.

• When unit is in occupied mode and supply air blower is operating at a speed equal to or above the “midpoint” blower speed, the outdoor air damper is at minimum “high blower” position.

NOTE - The “midpoint” blower speed is an average of the minimum and maximum blower speed (minimum speed + maximum speed divided by 2).

POWER EXHAUST OPERATION

NOTE - POWER EXHAUST OPERATION IS THE SAME FOR ALL CONTROL OPTIONS

Power exhaust blower operates when economizer outdoor air dampers are 50% open (adjustable) and when supply air blower speed is above 70% (adjustable) of full speed.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 13

OPTIONS / ACCESSORIES

Item Description

Model

Number

Catalog

Number

Unit Model No

092 102 120 150

COOLING SYSTEM

Condensate Drain Trap

Conventional Fin/Tube Condenser Coil (replaces Environ Coil System)

PVC - C1TRAP20AD2

76W26

OX OX OX OX

Copper - C1TRAP10AD2

76W27

OX OX OX OX

Factory O O O O

Corrosion Protection

Drain Pan Overflow Switch

Refrigerant Type

Service valves (not for Environ™ Coil System or Humiditrol equipped units)

Factory O O O O

E1SNSR71AD1

68W88

OX OX OX OX

R-410A O O O O

Factory O O O O

BLOWER - SUPPLY AIR

Blower Option CAV (Constant Air Volume) Factory

MSAV (Multi-Stage Air Volume) supply air blower option (With VFD Bypass Control) Factory

MSAV (Multi-Stage Air Volume) supply air blower option (Without VFD Bypass Control) Factory

Motors - Constant Air

Volume (CAV)

Belt Drive (standard or high efficiency) - 2 hp Factory

Belt Drive (standard or high efficiency) - 3 hp Factory

Motors - MSAV

®

Multi-Stage Air Volume

Belt Drive (standard efficiency) - 5 hp Factory

Belt Drive (high efficiency) - 2 hp Factory

Belt Drive (standard or high efficiency) - 3 hp Factory

Belt Drive (standard efficiency) - 5 hp Factory

Drive Kits

See Blower Data Tables for selection

Kit #1 590-890 rpm Factory

Kit #2 800-1105 rpm Factory

Kit #3 795-1195 rpm Factory

Kit #4 730-970 rpm Factory

Kit #5 940-1200 rpm Factory

Kit #6 1015-1300 rpm Factory

Kit #7 730-970 rpm Factory

Kit #8 940-1200 rpm Factory

Kit #9 1015-1300 rpm Factory

Kit #10 900-1135 rpm Factory

Kit #11 1040-1315 rpm Factory

Kit #12 1125-1425 rpm Factory

Blower Belt Auto-Tensioner Factory

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

Blower Proving Switch

Commercial Controls L Connection

®

C1SNSR35FF1

53W65

OX OX OX OX

Building Automation System Factory X X X X

Dirty Filter Switch

Fresh Air Tempering

Prodigy

®

Control System - BACnet

Prodigy

®

Control System - LonTalk

Novar

®

®

Module - C0CTRL60AE1L

59W51

OX OX OX OX

®

Module - C0CTRL65FF1

54W27

OX OX OX OX

ETM-2051 - E0CTRL30B1

64W73

OX OX OX OX

Novar

®

LSM Factory O O O O

Smoke Detector - Supply or Return (Power board and one sensor)

Smoke Detector - Supply and Return (Power board and two sensors)

E1SNSR55B-1

53W67

OX OX OX OX

C1SNSR75AD1

58W63

OX OX OX OX

C1SNSR44B-1

53W80

OX OX OX OX

C1SNSR43B-1

53W81

OX OX OX OX

NOTE - Catalog and model numbers shown are for ordering field installed accessories.

OX - Configure To Order (Factory Installed) or Field Installed

O = Configure To Order (Factory Installed)

X = Field Installed

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

CABINET

Coil Guards

Hail Guards

Horizontal Discharge Kit

Return Air Adaptor Plate (for L Series

®

Environ™ Coil System - E1GARD21B-1

92W62

Conventional Fin/Tube Condenser Coil - E1GARD20B-1

55W06

Environ™ Coil System - E1GARD11B-1

92W61

Conventional Fin/Tube Condenser Coil - E1GARD10B1

55W07

and T-Class™ replacement)

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

K1HECK00B-1

51W25

X X X X

C1CONV10B-1

54W96

OX OX OX OX

CONTROLS

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 14

OPTIONS / ACCESSORIES

Item Description

Model

Number

Catalog

Number

Unit Model No

092 102 120 150

INDOOR AIR QUALITY

Air Filters

Healthy Climate

®

High Efficiency Air Filters

20 x 25 x 2 (Order 4 per unit)

Replacement Media Filter With Metal Mesh

Frame (includes non-pleated filter media)

Indoor Air Quality (CO

2

) Sensors

Sensor - Wall-mount, off-white plastic cover with LCD display

Sensor - Wall-mount, off-white plastic cover, no display

Sensor - Black plastic case with LCD display, rated for plenum mounting

Sensor - Wall-mount, black plastic case, no display, rated for plenum mounting

CO

2

Sensor Duct Mounting Kit - for downflow applications

Aspiration Box - for duct mounting non-plenum rated CO

2

( 87N53 or 77N39)

UVC Germicidal Lamps

1

Healthy Climate

®

UVC Light Kit (208/230v-1ph)

sensors

HUMIDITROL

®

CONDENSER REHEAT OPTION

MERV 8 - C1FLTR15B-1

50W61

OX OX OX OX

MERV 13 - C1FLTR40B-1

52W41

OX OX OX OX

C1FLTR30B-1-

C0SNSR50AE1L

C0SNSR52AE1L

C0SNSR51AE1L

C0MISC19AE1

C0MISC19AE1-

C0MISC16AE1-

C1UVCL10B-1

Y3063

77N39

87N53

87N52

87N54

85L43

90N43

54W62

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

OX OX OX OX

Humiditrol (NOTE - Not available with Environ Coil System. Conventional Fin/Tube condenser coil must be ordered as a factory option)

Humidity Sensor Kit, Remote mounted (required)

Factory

COSNSR31AE-1

17M50

ELECTRICAL

O

X

O

X

O

X

O

X

Voltage 60 hz 208/230V - 3 phase Factory

460V - 3 phase Factory

O

O

O

O

O

O

O

O

HACR Circuit Breakers

575V - 3 phase Factory

Factory

O

O

O

O

O

O

O

O

Disconnect Switch - See Electrical/Electric Heat tables for selection 80 amp - C1DISC080B-1

54W56

OX OX OX OX

150 amp - C1DISC150B-1

54W57

OX OX OX OX

GFI Service

Outlets

15 amp non-powered, field-wired (208/230V, 460V only) LTAGFIK10/15

74M70

OX OX OX OX

20 amp non-powered, field-wired (575V only) Factory O O O O

Phase/Voltage Detection (Optional for CAV options only, furnished with MSAV option) Factory O O O O

ELECTRIC HEAT

7.5 kW

15 kW

22.5 kW

30 kW

45 kW

208/230V-3ph - C1EHO075B-1Y

56W38

OX OX

460V-3ph - C1EHO075B-1G

56W39

OX OX

575V-3ph - C1EHO075B-1J

56W40

OX OX

208/230V-3ph - C1EHO015B-1Y

56W41

OX OX OX OX

460V-3ph - C1EHO150B-1G

56W42

OX OX OX OX

575V-3ph - C1EHO150B-1J

56W43

OX OX OX OX

208/230V-3ph - C1EHO225B-1Y

56W44

OX OX OX OX

460V-3ph - C1EHO225B-1G

56W45

OX OX OX OX

575V-3ph - C1EHO225B-1J

56W46

OX OX OX OX

208/230V-3ph - C1EHO300B-1Y

56W47

OX OX OX OX

460V-3ph - C1EHO300B-1G

56W48

OX OX OX OX

575V-3ph - C1EHO300B-1J

56W49

OX OX OX OX

208/230V-3ph - C1EHO450B-1Y

56W50

OX OX OX OX

460V-3ph - C1EHO450B-1G

56W51

OX OX OX OX

60 kW

575V-3ph - C1EHO450B-1J

56W52

OX OX OX OX

208/230V-3ph - C1EHO600B-1Y

55W02

OX OX

460V-3ph - C1EHO600B-1G

55W03

575V-3ph - C1EHO600B-1J

55W04

OX OX

OX OX

1

Lamps operate on 110-230V single-phase power supply. Step-down transformer may be ordered separately for 460V and 575V units. Alternately, 110V power supply may be used to directly power the UVC ballast(s)

NOTE - Catalog and model numbers shown are for ordering field installed accessories.

OX - Configure To Order (Factory Installed) or Field Installed

O = Configure To Order (Factory Installed)

X = Field Installed

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 15

OPTIONS / ACCESSORIES

Item Description

ECONOMIZER

Economizer

Economizer - Downflow or Horizontal (Hood furnished)

Economizer Controls

Differential Enthalpy

Sensible Control

Single Enthalpy

Global Control

Downflow Barometric Relief Dampers

Barometric Relief Dampers (Exhaust hood furnished)

Horizontal Barometric Relief Dampers

Barometric Relief Dampers (Exhaust hood furnished)

OUTDOOR AIR

Outdoor Air Dampers

Motorized Dampers (Hood furnished)

Manual Dampers (Hood furnished)

POWER EXHAUST

Standard Static

Model

Number

Catalog

Number

Unit Model No

092 102 120 150

E1ECON15B-1

55W05

OX OX OX OX

Order 2 - C1SNSR64FF1

53W64

OX OX OX OX

Sensor is Furnished Factory O O O O

C1SNSR64FF1

53W64

OX OX OX OX

Sensor Field Provided Factory O O O O

C1DAMP55B-1

74W46

OX OX OX OX

LAGEDH03/15

53K04

X X X X

E1DAMP20B-1

63W60

OX OX OX OX

C1DAMP10B-1

53W48

OX OX OX OX

208/230V-3ph - K1PWRE10B-1Y

53W44

OX OX OX OX

460V-3ph - K1PWRE10B-1G

53W45

OX OX OX OX

575V-3ph - K1PWRE10B-1J

53W46

OX OX OX OX

ROOF CURBS - DOWNFLOW

Clip Curb

8 in. height

14 in. height

18 in. height

24 in. height

Standard

8 in. height

14 in. height

24 in. height

Adjustable Pitched Curb

14 in. height

CEILING DIFFUSERS

Step-Down - Order one

Flush - Order one

Transitions (Supply and Return) - Order one

C1CURB23B-1

54W46

C1CURB20B-1

54W47

C1CURB21B-1

54W48

C1CURB22B-1

54W49

C1CURB12B-1

54W44

C1CURB10B-1

54W43

C1CURB11B-1

54W45

C1CURB55B-1

54W50

RTD11-95

29G04

RTD11-135

29G05

RTD11-185

29G06

FD11-95

29G08

FD11-135

29G09

FD11-185

29G10

LASRT08/10

24L14

LASRT10/12

49K55

LASRT15

49K56

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X X

X

X X

X

X X

X

X

X

X

X

X

X

X

X

X

X

NOTE - Catalog and model numbers shown are for ordering field installed accessories.

OX - Configure To Order (Factory Installed) or Field Installed

O = Configure To Order (Factory Installed)

X = Field Installed

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 16

SPECIFICATIONS

General Data

Cooling

Performance

Refrigerant

Charge

Indoor

Coil

Nominal Tonnage

Model Number

Efficiency Type

Blower Type

Gross Cooling Capacity - Btuh

1

Net Cooling Capacity - Btuh

AHRI Rated Air Flow - cfm

Total Unit Power - kW

2

1

EER (Btuh/Watt)

IEER (Btuh/Watt)

Refrigerant Type

Environ™ Coil System Circuit 1

Circuit 2

Circuit 1 Conventional Fin/Tube

Coil Option

Conventional Fin/Tube

With Humiditrol

Circuit 2

Circuit 1

Circuit 2 ®

Option

Electric Heat Available - See page 15

Compressor Type (number)

Outdoor Coil

Environ

(Fin/Tube)

Outdoor

Coil Fans

Net face area (total) - sq. ft.

Tube diameter - in.

Number of rows

Fins per inch

Motor - (No.) hp

Motor rpm

Total Motor watts

Diameter - (No.) in.

Number of blades

Total Air volume - cfm

Net face area (total) - sq. ft.

Tube diameter - in.

Number of rows

Fins per inch

Drain connection - Number and size

Expansion device type

Nominal motor output

Maximum usable motor output

(US Only)

Motor - Drive kit number

7.5 Ton

LCH092H4B

High

Constant Air

Volume CAV

93,000

90,000

3000

7.5

12.7

13.0

R-410A

7 lbs. 8 oz.

7 lbs. 8 oz.

13 lbs. 8 oz.

12 lbs. 8 oz.

17 lbs. 0 oz.

12 lbs. 8 oz.

Scroll (2)

28.0 (29.33)

0.71 (3/8)

1 (3)

20 (20)

(2) 1/3

1075

880

(2) 24

3

8000

12.78

3/8

4

14

7.5 Ton

LCH092H4M

High

MSAV (Multi-Stage

Air Volume)

93,000

90,000

2800

7.5

12.7

14.0

R-410A

7 lbs. 8 oz.

7 lbs. 8 oz.

13 lbs. 8 oz.

12 lbs. 8 oz.

8.5 Ton

LCH102H4B

High

Constant Air

Volume CAV

103,800

100,000

3400

8.1

12.4

12.9

R-410A

7 lbs. 8 oz.

7 lbs. 8 oz.

13 lbs. 8 oz.

12 lbs. 8 oz.

17 lbs. 0 oz.

12 lbs. 8 oz.

17 lbs. 0 oz.

12 lbs. 8 oz.

7.5,15,22.5,30 & 45 KW

Scroll (2)

28.0 (29.33)

0.71 (3/8)

1 (3)

20 (20)

(2) 1/3

1075

880

(2) 24

Scroll (2)

28.0 (29.33)

0.71 (3/8)

1 (3)

3

8000

12.78

3/8

4

14

3/8

4

14

(1) 1 in. NPT coupling

20 (20)

(2) 1/3

1075

880

(2) 24

3

8000

12.78

Balance port TXV, removable head

2 hp, 3 hp, 5 hp

2.3 hp, 3.45 hp, 5.75 hp

3

Indoor

Blower and

Drive

Selection

2 hp

Kit 1 590-890 rpm (std. and high efficiency)

Kit 2 800-1105 rpm (std. and high efficiency)

Kit 3 795-1195 rpm (std. and high efficiency)

3 hp

Kit 4 730-970 rpm (std. efficiency)

Kit 5 940-1200 rpm (std. efficiency)

Kit 6 1015-1300 rpm (std. efficiency)

Kit 7 730-970 rpm (high efficiency)

Kit 8 940-1200 rpm (high efficiency)

Kit 9 1015-1300 rpm (high efficiency)

5 hp

Kit 10 900-1135 rpm (std. efficiency)

Kit 11 1040-1315 rpm (std. efficiency)

Kit 12 1125-1425 rpm (std. efficiency)

(1) 15 X 15 (1) 15 X 15

Filters

Blower wheel nominal diameter x width - in.

Type of filter

Number and size - in.

(1) 15 X 15

Disposable

(4) 20 x 25 x 2

Electrical characteristics

208/230V, 460V or 575V - 60 hertz - 3 phase

NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.

8.5 Ton

LCH102H4M

High

MSAV (Multi-Stage

Air Volume)

103,800

100,000

3400

8.1

12.4

14.0

R-410A

7 lbs. 8 oz.

7 lbs. 8 oz.

13 lbs. 8 oz.

12 lbs. 8 oz.

17 lbs. 0 oz.

12 lbs. 8 oz.

Scroll (2)

28.0 (29.33)

0.71 (3/8)

1 (3)

20 (20)

(2) 1/3

1075

880

(2) 24

3

8000

12.78

3/8

4

14

(1) 15 X 15

1 AHRI Certified to AHRI Standard 340/360; 95°F outdoor air temperature and 80°F db/67°F wb entering evaporator air; minimum external duct static pressure.

2

Integrated Energy Efficiency Ratio certified and tested according to AHRI Standard 340/360.

3

Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.

NOTE – Units equipped with MSAV ® (Multi-Stage Air Volume) option are limited to a motor service factor of 1.0.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 17

SPECIFICATIONS

General Data

Cooling

Performance

Refrigerant

Charge

Indoor

Coil

Nominal Tonnage

Model Number

Efficiency Type

Blower Type

Gross Cooling Capacity - Btuh

1

Net Cooling Capacity - Btuh

AHRI Rated Air Flow - cfm

Total Unit Power - kW

2

1

EER (Btuh/Watt)

IEER (Btuh/Watt)

Refrigerant Type

Environ™ Coil System Circuit 1

Circuit 2

Circuit 1 Conventional Fin/Tube

Coil Option

Conventional Fin/Tube

With Humiditrol

Circuit 2

Circuit 1

Circuit 2

®

Option

Electric Heat Available - See page 15

Compressor Type (number)

Outdoor Coil

Environ

(Fin/Tube)

Outdoor

Coil Fans

Net face area (total) - sq. ft.

Tube diameter - in.

Number of rows

Fins per inch

Motor - (No.) hp

Motor rpm

Total Motor watts

Diameter - (No.) in.

Number of blades

Total Air volume - cfm

Net face area (total) - sq. ft.

Tube diameter - in.

Number of rows

Fins per inch

Drain connection - Number and size

Expansion device type

Nominal motor output

Maximum usable motor output

(US Only)

Motor - Drive kit number

10 Ton

LCH120H4B

High

Constant Air

Volume CAV

122,000

118,000

3600

9.9

12.2

13.2

R-410A

7 lbs. 8 oz.

7 lbs. 8 oz.

14 lbs. 8 oz.

13 lbs. 8 oz.

18 lbs. 0 oz.

13 lbs. 8 oz.

Scroll (2)

28.0 (29.33)

0.71 (3/8)

1 (3)

20 (20)

(2) 1/3

1075

880

(2) 24

3

8000

13.54

3/8

4

14

10 Ton

LCH120H4M

High

MSAV (Multi-

Stage Air Volume)

122,000

118,000

3300

9.8

12.2

14.0

R-410A

7 lbs. 8 oz.

7 lbs. 8 oz.

14 lbs. 8 oz.

13 lbs. 8 oz.

12.5 Ton

LCH150S4B

Standard

Constant Air

Volume CAV

142,000

136,000

4100

12.4

11

11.2

R-410A

8 lbs. 0 oz.

8 lbs. 0 oz.

16 lbs. 8 oz.

14 lbs. 8 oz.

18 lbs. 0 oz.

13 lbs. 8 oz.

18 lbs. 8 oz.

14 lbs. 8 oz.

15,22.5,30,45 & 60 KW

Scroll (2)

28.0 (29.33)

0.71 (3/8)

1 (3)

20 (20)

(2) 1/3

1075

880

(2) 24

Scroll (2)

28.0 (29.33)

0.71 (3/8)

1 (3)

3

8000

13.54

3/8

4

14

3/8

4

20

(1) 1 in. NPT coupling

20 (20)

(2) 1/2

1075

920

(2) 24

3

8800

13.54

Balance port TXV, removable head

2 hp, 3 hp, 5 hp

2.3 hp, 3.45 hp, 5.75 hp

3

Indoor

Blower and

Drive

Selection

2 hp

Kit 1 590-890 rpm (std. and high efficiency)

Kit 2 800-1105 rpm (std. and high efficiency)

Kit 3 795-1195 rpm (std. and high efficiency)

3 hp

Kit 4 730-970 rpm (std. efficiency)

Kit 5 940-1200 rpm (std. efficiency)

Kit 6 1015-1300 rpm (std. efficiency)

Kit 7 730-970 rpm (high efficiency)

Kit 8 940-1200 rpm (high efficiency)

Kit 9 1015-1300 rpm (high efficiency)

5 hp

Kit 10 900-1135 rpm (std. efficiency)

Kit 11 1040-1315 rpm (std. efficiency)

Kit 12 1125-1425 rpm (std. efficiency)

(1) 15 X 15 (1) 15 X 15

Filters

Blower wheel nominal diameter x width - in.

Type of filter

Number and size - in.

(1) 15 X 15

Disposable

(4) 20 x 25 x 2

Electrical characteristics

208/230V, 460V or 575V - 60 hertz - 3 phase

NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.

12.5 Ton

LCH150S4M

Standard

MSAV (Multi-

Stage Air Volume)

142,000

136,000

4200

12.4

11

13.1

R-410A

8 lbs. 0 oz.

8 lbs. 0 oz.

16 lbs. 8 oz.

14 lbs. 8 oz.

18 lbs. 8 oz.

14 lbs. 8 oz.

Scroll (2)

28.0 (29.33)

0.71 (3/8)

1 (3)

20 (20)

(2) 1/2

1075

920

(2) 24

3

8800

13.54

3/8

4

20

(1) 15 X 15

1

AHRI Certified to AHRI Standard 340/360; 95°F outdoor air temperature and 80°F db/67°F wb entering evaporator air; minimum external duct static pressure.

2

Integrated Energy Efficiency Ratio certified and tested according to AHRI Standard 340/360.

3

Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.

NOTE – Units equipped with MSAV

®

(Multi-Stage Air Volume) option are limited to a motor service factor of 1.0.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 18

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

7.5 TON HIGH EFFICIENCY LCH092H4B (1ST STAGE) - CONSTANT AIR VOLUME

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

75°F

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

85°F

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

Motor

Cap.

Dry Bulb

Cap.

Input

Dry Bulb

Cap.

Dry Bulb

Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

2400

3000

3600

2400

3000

3600

2400

3000

3600

48.6

51.0

52.9

51.3

53.9

55.9

54.1

56.8

58.6

1.95

0.63 0.76 0.93

46.8

1.96

0.67 0.85 1.00

49.1

1.97

0.72 0.95 1.00

50.9

1.96

0.50 0.61 0.72

49.5

1.97

0.53 0.65 0.80

51.9

1.98

0.55 0.70 0.90

53.7

1.97

0.39 0.49 0.59

52.2

1.98

0.39 0.51 0.63

54.7

1.99

0.41 0.54 0.67

56.5

2.21

0.64 0.78 0.95

44.9

2.22

0.68 0.88 1.00

47.2

2.22

0.74 0.97 1.00

48.9

2.22

0.51 0.62 0.73

47.6

2.22

0.53 0.66 0.83

49.7

2.23

0.56 0.71 0.93

51.5

2.22

0.39 0.49 0.60

50.2

2.23

0.40 0.52 0.64

52.4

2.24

0.41 0.55 0.69

54.1

2.49

0.65 0.80 0.98

42.9

2.50

0.70 0.90 1.00

45.0

2.50

0.76 0.99 1.00

46.7

2.50

0.51 0.63 0.76

45.5

2.50

0.55 0.67 0.86

47.7

2.51

0.57 0.74 0.96

48.9

2.50

0.39 0.51 0.60

48.0

2.51

0.40 0.53 0.65

50.1

2.51

0.42 0.56 0.71

51.5

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

2.81

0.66

0.83

1.00

2.82

0.72

0.94

1.00

2.82

0.79

1.00

1.00

2.82

0.52

0.64

0.78

2.82

0.56

0.69

0.89

2.83

0.58

0.76

0.99

2.82

0.39

0.51

0.61

2.83

0.41

0.55

0.67

2.83

0.42

0.57

0.73

7.5 TON HIGH EFFICIENCY LCH092H4B (2ND STAGE) - CONSTANT AIR VOLUME

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

85°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

95°F

Sensible To Total

Ratio (S/T)

Total

Cool

105°F

Comp.

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Cap.

Dry Bulb Cap.

Input Dry Bulb Cap.

Dry Bulb Cap.

cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

2400

3000

3600

2400

87.9

92.3

95.6

93.0

5.19

5.20

5.21

5.20

3000 97.3

5.21

3600 100.6

5.22

2400 98.2

5.21

3000 102.5

5.23

3600 105.9

5.24

.69

.83

.98

84.0

.74

.92

1.00

88.0

.79

1.00 1.00

91.4

.55

.66

.79

.58

.61

.42

.43

.71

.77

.53

.56

.88

.97

.64

.69

89.0

93.0

95.7

93.8

97.9

5.86

5.87

5.87

5.87

5.88

5.88

5.88

5.89

.44

.60

.75

100.8

5.89

.70

.76

.85

1.00

79.8

.95

1.00

83.5

.82

1.00 1.00

87.3

.55

.59

.62

.42

.43

.45

.68

.73

.79

.54

.58

.61

.81

.91

.99

.65

.71

.77

84.5

88.2

90.8

89.0

92.9

95.4

6.64

6.64

6.64

6.64

6.65

6.65

6.65

6.65

6.65

.72

.88

1.00

75.2

.78

.98

1.00

78.7

.85

1.00 1.00

82.9

.56

.69

.84

79.5

.60

.76

.94

82.8

.63

.82

1.00

85.2

.42

.54

.67

84.2

.44

.59

.73

87.5

.45

.62

.79

89.9

Comp.

Motor

Input

115°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

7.55

7.54

7.55

7.54

7.54

7.54

7.54

7.54

7.54

.74

.58

.61

.64

.43

.44

.46

.92

1.00

.81

1.00

1.00

.88

1.00

1.00

.71

.78

.87

.98

.86

1.00

.56

.60

.64

.69

.76

.84

8.5 TON HIGH EFFICIENCY LCH102H4B (1ST STAGE) - CONSTANT AIR VOLUME

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

75°F

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

85°F

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

Motor

Cap.

Dry Bulb

Cap.

Input

Dry Bulb

Cap.

Dry Bulb

Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

2720

3400

4080

2720

3400

4080

2720

3400

4080

52.3

54.8

56.6

55.2

57.7

59.7

58.0

60.7

62.5

2.13

2.14

2.15

2.14

2.15

2.16

2.16

2.16

2.17

.62

.76

.96

50.4

.66

.87

1.00

52.7

.72

.97

1.00

54.6

.49

.60

.71

.52

.55

.38

.39

.40

.64

.69

.48

.51

.53

.82

.93

.58

.62

.67

53.2

55.6

57.4

56.1

58.4

60.2

2.41

2.42

2.43

2.42

2.43

2.44

2.43

2.44

2.45

.52

.56

.38

.39

.40

.63

.67

.74

.50

.78

.98

48.4

.90

1.00

50.6

.99

1.00

52.4

.61

.65

.71

.49

.51

.55

.73

.84

.96

.59

.63

.68

51.2

53.3

54.9

53.8

56.0

57.8

2.73

2.73

2.74

2.73

2.74

2.74

2.74

2.75

2.75

.64

.81

1.00

46.3

.69

.93

1.00

48.4

.77

1.00 1.00

50.3

.50

.62

.76

48.7

.54

.67

.88

50.9

.56

.73

.99

52.4

.38

.49

.60

51.3

.39

.53

.65

53.6

.40

.56

.71

55.0

3.08

3.09

3.09

3.09

3.09

3.10

3.09

3.10

3.10

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

.65

.84

1.00

.97

1.00

.57

.38

.40

.41

.71

.80

1.00

1.00

.50

.55

.63

.68

.76

1.00

.50

.54

.56

.79

.92

.61

.67

.73

8.5 TON HIGH EFFICIENCY LCH102H4B (2ND STAGE) - CONSTANT AIR VOLUME

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

85°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

95°F

Sensible To Total

Ratio (S/T)

Total

Cool

105°F

Comp.

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Cap.

Dry Bulb

Cap.

Input

Dry Bulb

Cap.

Dry Bulb

Cap.

cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

2720 98.8

5.54

3400 103.3

5.56

4080 106.9

5.56

2720 104.3

5.56

3400 108.8

5.57

4080 112.0

5.58

2720 109.6

5.57

3400 114.3

5.59

4080 117.8

5.60

.70

.85

1.00

94.4

.76

.95

1.00

98.6

6.27

6.27

.82

1.00 1.00 102.6

6.28

.55

.68

.81

99.6

6.28

.59

.74

.91

103.8

6.29

.62

.80

.99

106.6

6.30

.42

.54

.66

104.7

6.29

.43

.58

.72

109.2

6.30

.45

.61

.77

112.2

6.31

.72

.78

.84

.56

.60

.63

.43

.44

.45

.88

1.00

89.7

.98

1.00

93.5

1.00 1.00

.69

.76

98.2

.82

1.00 101.2

7.12

.55

.59

.62

.84

.94

94.7

98.5

7.10

7.11

7.12

7.11

7.12

.67

99.7

7.12

.74

103.6

7.12

.80

106.4

7.13

.73

.91

1.00

84.7

.80

1.00 1.00

88.7

.88

1.00 1.00

93.1

.57

.71

.87

89.3

.61

.78

.97

92.7

.65

.85

1.00

95.2

.43

.56

.69

94.1

.45

.60

.76

97.4

8.09

8.08

8.08

8.08

8.08

8.08

8.08

8.08

.46

.64

.83

100.0

8.08

Comp.

Motor

Input

115°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

.76

.95

1.00

.83

1.00

1.00

.91

1.00

1.00

.59

.62

.66

.43

.45

.47

.73

.91

.81

1.00

.89

1.00

.58

.61

.66

.71

.78

.86

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 19

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

10 TON HIGH EFFICIENCY LCH120H4B (1ST STAGE) - CONSTANT AIR VOLUME

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

75°F

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

85°F

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

Motor

Cap.

Dry Bulb

Cap.

Input

Dry Bulb

Cap.

Dry Bulb

Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

3200

4000

4800

3200

4000

4800

3200

4000

4800

61.5

64.5

66.8

64.8

68.1

70.3

68.5

71.5

73.9

2.61

2.64

2.67

2.65

2.68

2.71

2.69

2.72

2.75

.64

.78

.95

59.3

.68

.86

1.00

62.2

.73

.95

1.00

64.3

.51

.62

.73

62.5

.53

.66

.82

65.5

.56

.70

.91

67.7

.40

.50

.60

66.0

.40

.52

.64

68.9

.41

.55

.68

70.9

2.96

2.99

3.02

2.99

3.03

3.06

3.04

3.07

3.10

.54

.58

.39

.40

.42

.65

.70

.76

.52

.80

.97

56.8

.89

1.00

59.5

.98

1.00

61.5

.63

.67

.73

.50

.53

.56

.75

.84

.94

.61

.65

.70

60.0

62.7

64.7

63.4

65.9

67.9

3.34

3.37

3.40

3.38

3.41

3.44

3.42

3.46

3.48

.66

.82

1.00

54.3

.71

.93

1.00

56.8

.78

1.00 1.00

58.8

.52

.64

.78

57.2

.55

.69

.88

59.8

.58

.75

.98

61.6

.40

.51

.62

60.5

.41

.54

.67

62.7

.43

.57

.73

64.7

3.77

3.80

3.83

3.81

3.84

3.87

3.85

3.88

3.91

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

.67

.85

1.00

.96

1.00

.60

.40

.41

.43

.74

.81

1.00

1.00

.53

.56

.65

.70

.78

1.00

.52

.55

.58

.80

.91

.63

.68

.75

10 TON HIGH EFFICIENCY LCH120H4B (2ND STAGE) - CONSTANT AIR VOLUME

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

85°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

95°F

Sensible To Total

Ratio (S/T)

Total

Cool

105°F

Comp.

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Cap.

Dry Bulb Cap.

Input Dry Bulb Cap.

Dry Bulb Cap.

cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

3200 118.3

7.09

4000 123.7

7.16

4800 127.9

7.21

3200 124.8

7.17

4000 130.2

7.24

4800 134.2

7.29

3200 131.6

7.26

4000 136.6

7.33

4800 140.5

7.38

.67

.83

1.00 113.1

8.00

.72

.94

1.00 118.2

8.07

.79

1.00 1.00 122.7

8.13

.53

.65

.79

119.2

8.08

.56

.70

.90

124.4

8.16

.59

.77

.99

127.9

8.21

.40

.52

.63

125.7

8.17

.42

.55

.68

130.6

8.24

.43

.58

.74

134.1

8.29

.68

.75

.82

1.00 1.00 116.9

9.17

.54

.57

.61

.41

.42

.44

.86

1.00 107.4

9.04

.97

1.00 112.2

9.11

.66

.72

.81

113.4

9.12

.93

118.1

9.19

.80

1.00 121.0

9.23

.52

.56

.60

.64

.70

.77

119.6

123.7

127.3

9.21

9.27

9.32

.54

.68

.84

Comp.

Motor

Input

115°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

.70

.89

1.00 101.4 10.23

.72

.93

1.00

.78

1.00 1.00 106.1 10.29

.81

1.00

1.00

.85

1.00 1.00 111.3 10.37

.90

1.00

1.00

106.8 10.30

.56

.58

.75

.97

111.1 10.36

.60

.62

.82

1.00 114.1 10.40

.64

.41

.53

.66

112.8 10.38

.41

.43

.58

.72

116.7 10.45

.43

.44

.62

.80

119.5 10.49

.45

.70

.78

.87

.55

.59

.63

.89

1.00

1.00

.68

.75

.84

12.5 TON STANDARD EFFICIENCY LCH150S4B (1ST STAGE) - CONSTANT AIR VOLUME

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

75°F

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

85°F

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

Motor

Cap.

Dry Bulb

Cap.

Input

Dry Bulb

Cap.

Dry Bulb

Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

3800

4400

5000

3800

4400

5000

3800

4400

5000

79.6

82.3

84.5

84.1

86.9

89.1

88.8

91.3

93.7

3.27

0.64 0.78 0.95

76.6

3.29

0.67 0.84

3.32

0.69 0.91

1

1

79

81.1

3.31

0.51 0.62 0.74

80.8

3.35

0.52 0.65

0.8

83.3

3.37

0.54 0.67 0.86

85.5

3.37

0.39 0.49 0.59

85.2

3.4

3.43

0.4

0.4

0.51 0.62

0.53 0.65

87.9

89.9

3.66

0.65

0.8

0.98

73.2

3.69

0.68 0.86

3.71

0.72 0.93

1

1

75.5

77.5

3.71

0.51 0.63 0.76

77.4

3.74

0.53 0.66 0.82

79.6

3.77

0.55 0.69 0.89

81.4

3.77

0.39

0.5

0.61

81.6

3.8

0.4

0.52 0.63

83.9

3.83

0.41 0.54 0.66

85.8

4.1

0.66 0.83

4.13

0.69

0.9

1

1

69.5

71.8

4.15

0.73 0.97

1 73.8

4.15

0.52 0.64 0.78

73.5

4.18

0.54 0.67 0.85

75.8

4.21

0.56 0.71 0.92

77.5

4.21

4.24

0.4

0.4

0.5

0.62

0.53 0.65

77.7

79.7

4.27

0.41 0.55 0.68

81.5

4.59

4.62

4.65

4.64

4.68

4.7

4.71

4.73

4.76

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

0.67

0.86

1

1 0.71

0.93

0.77

1 1

0.52

0.65

0.81

0.55

0.69

0.88

0.57

0.73

0.96

0.39

0.51

0.63

0.4

0.53

0.66

0.41

0.56

0.7

12.5 TON STANDARD EFFICIENCY LCH150S4B (2ND STAGE) - CONSTANT AIR VOLUME

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

85°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

95°F

Sensible To Total

Ratio (S/T)

Total

Cool

105°F

Comp.

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Cap.

Dry Bulb

Cap.

Input

Dry Bulb

Cap.

Dry Bulb

Cap.

cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

3800 138.7

8.68

0.71 0.86

4400 143.3

8.74

0.75 0.92

1

1

131.9

136

9.72

0.73 0.89

9.79

0.77 0.95

139.9

9.84

0.82

1

1

5000 147 8.8

0.78 0.98

1 1 1

3800 146.6

8.79

0.56 0.69 0.83 139.3

9.84

0.57

0.7

0.85

124.7 10.91 0.75 0.92

128.7 10.97

0.8

0.99

1

1

Comp.

Motor

Input

115°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

116.8 12.25 0.77

120.9 12.32 0.83

0.96

1

1

1

1

132.6 11.04 0.84

1 1 125.4 12.39 0.87

1

132 11.02 0.58 0.72 0.88 123.5 12.36

0.6

0.75

0.92

4400

5000

151.2

154.5

8.86

8.91

0.58 0.72 0.88 143.6

0.6

0.76 0.94 146.9

9.9

9.95

0.6

0.74 0.91 135.4 11.08 0.61 0.77 0.95

127 12.43 0.63

0.8

0.99

0.62 0.79 0.98 138.5 11.13 0.64 0.82

1 129.6 12.47 0.65

0.86

1

3800 154.9

8.91

0.42 0.55 0.67 147.3

9.96

0.43 0.56 0.68 139.3 11.15 0.43 0.56

0.7

130.7 12.48 0.44

0.58

0.72

4400 159 8.98

0.43 0.57

0.7

150.9 10.02 0.44 0.58 0.72 142.6

11.2

0.44 0.59 0.74 133.6 12.54 0.45

0.61

0.78

5000 162.8

9.04

0.44 0.59 0.74 154.6 10.08 0.45 0.61 0.76 145.8 11.26 0.46 0.62 0.79 136.5 12.59 0.46

0.64

0.83

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 20

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

7.5 TON HIGH EFFICIENCY LCH092H4M (1ST STAGE) - MSAV (Multi-Stage Air Volume) SUPPLY AIR BLOWER

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

Cap.

Dry Bulb Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW

1680

2100

2520

1680

2100

2520

1680

2100

2520

Total

Cool

43.9

46.9

49.2

46.6

49.6

51.9

49.4

52.5

54.6

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

1.94

0.59 0.69 0.81

42.4

1.95

0.61 0.74 0.88

45.2

1.96

0.65

0.8

0.96

47.3

1.95

0.48 0.56 0.65

45.2

1.96

0.49 0.59 0.70

47.8

1.96

0.51 0.62 0.76

50.1

1.96

0.38 0.46 0.54

47.8

1.97

0.38 0.48 0.57

50.7

1.97

0.39 0.49 0.59

52.7

2.20

2.20

2.21

2.20

2.21

2.22

2.21

2.22

2.23

75°F

Sensible To Total

Ratio (S/T)

Dry Bulb

Sensible To Total

Ratio (S/T)

75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

0.60 0.70 0.82

0.62 0.76 0.90

0.66 0.81 0.98

0.48 0.57 0.66

0.50 0.59 0.72

0.52 0.63 0.77

0.38 0.47 0.55

0.39 0.48 0.57

0.39 0.50 0.60

Total

Cool

Cap.

40.9

43.5

45.4

43.5

46.0

48.1

46.1

48.8

50.6

Comp.

85°F

Motor

Input Dry Bulb

Total

Cool

Cap.

2.48

0.60 0.71 0.84

39.2

2.49

0.63 0.78 0.93

41.6

2.49

0.67 0.84 1.00

43.4

2.49

0.48 0.58 0.68

41.7

2.49

0.50 0.60 0.73

44.0

2.50

0.52 0.64 0.79

45.9

2.50

0.39 0.47 0.55

44.2

2.50

0.39 0.49 0.58

46.7

2.51

0.40 0.50 0.62

48.4

Comp.

Motor

Input

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

2.81

0.61

0.73

0.86

2.81

0.64

0.80

0.95

2.82

0.69

0.87

1.00

2.81

0.49

0.58

0.69

2.81

0.51

0.61

0.75

2.82

0.53

0.66

0.82

2.82

0.38

0.47

0.56

2.82

0.39

0.49

0.59

2.82

0.40

0.51

0.63

7.5 TON HIGH EFFICIENCY LCH092H4M (2ND STAGE) - MSAV (Multi-Stage Air Volume) SUPPLY AIR BLOWER

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

85°F

Sensible To Total

Ratio (S/T)

Total

Cool

Cap.

Dry Bulb

Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW

2400

3000

3600

2400

87.9

92.3

95.6

93.0

5.19

5.20

5.21

5.20

3000 97.3

5.21

3600 100.6

5.22

2400 98.2

5.21

3000 102.5

5.23

3600 105.9

5.24

.69

.83

.98

84.0

.74

.92

1.00

88.0

.79

1.00 1.00

91.4

.55

.66

.79

89.0

.58

.71

.88

93.0

.61

.77

.97

95.7

.42

.53

.64

93.8

.43

.56

.69

97.9

5.86

5.87

5.87

5.87

5.88

5.88

5.88

5.89

.44

.60

.75

100.8

5.89

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

95°F 105°F

Comp.

Motor

Input

Comp.

Motor

Input

115°F

Sensible To Total

Ratio (S/T)

Total

Cool

Sensible To Total

Ratio (S/T)

Total

Cool

Sensible To Total

Ratio (S/T)

Dry Bulb

Cap.

Dry Bulb

Cap.

Dry Bulb

75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

.70

.76

.85

1.00

79.8

.95

1.00

83.5

.82

1.00 1.00

87.3

.55

.59

.62

.42

.43

.45

.68

.73

.79

.54

.58

.61

.81

.91

.99

.65

.71

.77

84.5

88.2

90.8

89.0

92.9

95.4

6.64

6.64

6.64

6.64

6.65

6.65

6.65

6.65

6.65

.72

.88

1.00

75.2

.78

.98

1.00

78.7

.85

1.00 1.00

82.9

.56

.69

.84

79.5

.60

.76

.94

82.8

.63

.82

1.00

85.2

.42

.54

.67

84.2

.44

.59

.73

87.5

.45

.62

.79

89.9

7.55

7.54

7.55

7.54

7.54

7.54

7.54

7.54

7.54

.74

.58

.61

.64

.43

.44

.46

.92

1.00

.81

1.00

1.00

.88

1.00

1.00

.71

.78

.87

.98

.86

1.00

.56

.60

.64

.69

.76

.84

8.5 TON HIGH EFFICIENCY LCH102H4M (1ST STAGE) - MSAV (Multi-Stage Air Volume) SUPPLY AIR BLOWER

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

Cap.

Dry Bulb

Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW

1920

2400

2880

1920

2400

2880

1920

2400

2880

Total

Cool

49.5

52.6

54.8

52.3

55.4

57.8

55.5

58.6

60.9

Comp.

Motor

Input

2.14

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

2.12

0.61 0.72 0.84

47.8

2.13

0.64 0.78 0.92

50.8

2.14

0.68 0.83 0.99

52.9

2.13

2.15

0.53 0.65 0.79

55.8

2.15

0.5

0.4

0.4

0.59 0.69

0.48 0.57

0.5

0.6

50.7

2.14

0.52 0.62 0.73

53.6

53.7

56.5

2.16

0.41 0.52 0.63

58.6

2.4

75°F

Sensible To Total

Ratio (S/T)

Dry Bulb

Total

Cool

Cap.

2.41

0.65 0.79 0.94

48.8

2.42

2.41

0.63 0.73 0.86

46.1

2.42

0.52 0.63 0.75

51.5

2.43

0.53 0.66 0.81

53.6

2.42

2.43

0.69 0.85

0.51

0.6

1

0.7

0.4

0.51

0.6

50.8

48.8

0.4

0.49 0.57

51.7

54.4

2.43

0.41 0.52 0.64

56.3

Comp.

Motor

Input

85°F

Sensible To Total

Ratio (S/T)

Dry Bulb

Total

Cool

Cap.

75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

2.71

0.63 0.75 0.87

44.2

2.72

0.66 0.81 0.96

46.6

2.73

0.71 0.87

1 48.4

2.72

0.51

0.6

0.71

46.9

2.73

0.52 0.64 0.77

49.3

2.73

0.54 0.68 0.83

51.2

2.73

0.39 0.49 0.58

49.5

2.74

0.41 0.51 0.61

52

2.74

0.41 0.53 0.65

53.9

Comp.

Motor

Input

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

3.07

0.63

0.76

0.9

3.08

0.68

0.83

0.98

3.08

0.72

0.9

1

3.08

0.51

0.61

0.72

3.08

3.09

3.09

3.09

0.53

0.56

0.65

0.79

0.7

0.87

0.4

0.49

0.59

0.4

0.52

0.62

3.09

0.41

0.54

0.67

8.5 TON HIGH EFFICIENCY LCH102H4M (2ND STAGE) - MSAV (Multi-Stage Air Volume) SUPPLY AIR BLOWER

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

85°F

Sensible To Total

Ratio (S/T)

Total

Cool

Cap.

Dry Bulb Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW

2720 98.8

5.54

3400 103.3

5.56

4080 106.9

5.56

2720 104.3

5.56

3400 108.8

5.57

4080 112.0

5.58

2720 109.6

5.57

3400 114.3

5.59

4080 117.8

5.60

.70

.85

1.00

94.4

.76

.95

1.00

98.6

6.27

6.27

.82

1.00 1.00 102.6

6.28

.55

.68

.81

99.6

6.28

.59

.74

.91

103.8

6.29

.62

.80

.99

106.6

6.30

.42

.54

.66

104.7

6.29

.43

.58

.72

109.2

6.30

.45

.61

.77

112.2

6.31

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb Cap.

Dry Bulb Cap.

Dry Bulb

75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F

.72

.78

Total

Cool

.88

1.00

89.7

.98

1.00

93.5

.84

1.00 1.00

98.2

.56

.60

.63

.43

.44

.45

.69

.76

Comp.

Motor

Input

.82

1.00 101.2

7.12

.55

.59

.62

.84

.94

94.7

98.5

7.10

7.11

7.12

7.11

7.12

.67

99.7

7.12

.74

103.6

7.12

.80

106.4

7.13

105°F

Sensible To Total

Ratio (S/T)

Total

Cool

.73

.91

1.00

84.7

.80

1.00 1.00

88.7

.88

1.00 1.00

93.1

.57

.71

.87

89.3

.61

.78

.97

92.7

.65

.85

1.00

95.2

.43

.56

.69

94.1

.45

.60

.76

97.4

Comp.

Motor

Input

8.09

8.08

8.08

8.08

8.08

8.08

8.08

8.08

.46

.64

.83

100.0

8.08

115°F

Sensible To Total

Ratio (S/T)

.76

.59

.62

.66

.43

.45

.47

.95

1.00

.83

1.00

1.00

.91

1.00

1.00

.73

.91

.81

1.00

.89

1.00

.58

.61

.66

.71

.78

.86

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 21

RATINGS

NOTE − For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

10 TON HIGH EFFICIENCY LCH120H4M (1ST STAGE) - MSAV (Multi-Stage Air Volume) SUPPLY AIR BLOWER

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

Cap.

Dry Bulb Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW

2240

2800

3360

2240

2800

3360

2240

2800

3360

Total

Cool

59

62.9

65.7

62.5

66.2

69.3

66.3

70.2

73.1

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

2.61

0.68 0.77 0.87

57

2.64

0.71 0.82 0.92

60.6

2.67

0.74 0.86 0.98

63.3

2.64

0.55 0.65 0.74

60.5

2.67

0.57 0.68 0.79

64

2.7

0.58 0.71 0.83

66.8

2.67

0.44 0.53 0.62

64

2.71

0.44 0.55 0.65

67.8

2.74

0.45 0.57 0.69

70.3

2.96

2.99

3.02

2.99

3.03

3.06

3.03

3.07

3.1

75°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

0.68 0.78 0.88

0.72 0.83 0.94

0.75 0.87 0.99

0.56 0.65 0.75

0.57 0.69

0.59 0.72 0.84

0.44 0.54 0.63

0.44 0.56 0.67

0.45 0.58

0.8

0.7

Total

Cool

Cap.

54.9

58.2

60.6

58.2

61.4

64

61.6

65.1

67.6

Comp.

Motor

Input

85°F

Sensible To Total

Ratio (S/T)

Dry Bulb

Total

Cool

Cap.

3.34

0.69

0.8

0.89

52.6

3.38

0.72 0.84 0.96

55.6

3.41

0.76 0.89

1 58

3.38

0.56 0.67 0.76

55.8

3.42

0.58

0.7

0.81

58.9

3.45

0.6

0.73 0.86

61.1

3.42

0.44 0.54 0.64

59.1

3.46

0.45 0.56 0.67

62.2

3.49

0.45 0.59 0.71

64.5

Comp.

Motor

Input

3.78

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

0.7

0.81

0.91

3.82

0.74

0.86

0.98

3.85

0.77

0.91

1

3.82

0.56

0.67

0.77

3.86

0.58

0.71

0.83

3.88

0.6

0.75

0.88

3.86

0.44

0.55

0.65

3.9

0.45

0.57

0.68

3.93

0.45

0.59

0.72

10 TON HIGH EFFICIENCY LCH120H4M (2ND STAGE) - MSAV (Multi-Stage Air Volume) SUPPLY AIR BLOWER

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

85°F

Sensible To Total

Ratio (S/T)

Total

Cool

Cap.

Dry Bulb

Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW

3200 118.3

7.09

4000 123.7

7.16

4800 127.9

7.21

3200 124.8

7.17

4000 130.2

7.24

4800 134.2

7.29

3200 131.6

7.26

4000 136.6

7.33

4800 140.5

7.38

.67

.83

1.00 113.1

8.00

.72

.94

1.00 118.2

8.07

.79

1.00 1.00 122.7

8.13

.53

.65

.79

119.2

8.08

.56

.70

.90

124.4

8.16

.59

.77

.99

127.9

8.21

.40

.52

.63

125.7

8.17

.42

.55

.68

130.6

8.24

.43

.58

.74

134.1

8.29

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

95°F

Sensible To Total

Ratio (S/T)

75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

.68

.75

.54

.57

.61

.41

.42

.44

Dry Bulb

.66

.72

.80

1.00 121.0

9.23

.52

.56

.60

.81

.64

.70

.77

Total

Cool

Cap.

113.4

119.6

123.7

127.3

9.21

105°F

Comp.

Motor

Input

.86

1.00 107.4

9.04

.97

1.00 112.2

9.11

.82

1.00 1.00 116.9

9.17

9.12

.93

118.1

9.19

9.27

9.32

Sensible To Total

Ratio (S/T)

Dry Bulb

Total

Cool

Cap.

Comp.

Motor

Input

115°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

.70

.89

1.00 101.4 10.23

.72

.93

1.00

.78

1.00 1.00 106.1 10.29

.81

1.00

1.00

.85

1.00 1.00 111.3 10.37

.90

1.00

1.00

.54

.68

.84

106.8 10.30

.56

.58

.75

.97

111.1 10.36

.60

.62

.82

1.00 114.1 10.40

.64

.41

.53

.66

112.8 10.38

.41

.43

.58

.72

116.7 10.45

.43

.44

.62

.80

119.5 10.49

.45

.70

.55

.59

.63

.89

.78

1.00

.87

1.00

.68

.75

.84

12.5 TON STANDARD EFFICIENCY LCH150S4M (1ST STAGE) - MSAV (Multi-Stage Air Volume) SUPPLY AIR BLOWER

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

Cap.

Dry Bulb

Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW

2560

3200

3840

2560

3200

3840

2560

3200

3840

71.1

76.1

79.7

75.5

80.4

84

80.1

85.2

89

3.21

0.6

0.7

0.82

68.5

3.27

0.63 0.76 0.89

73.1

3.3

0.66 0.81 0.97

76.6

3.26

0.49 0.58 0.66

72.9

3.31

0.51

0.6

0.72

77.4

3.35

0.52 0.63 0.77

80.8

3.31

0.39 0.47 0.55

77.3

3.36

0.39 0.49 0.58

82.2

3.41

0.4

0.51 0.61

85.3

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

75°F

Comp.

Motor

Input

85°F

Sensible To Total

Ratio (S/T)

Total

Cool

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

Motor

Dry Bulb

Cap.

Dry Bulb

Cap.

Input

75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

4.06

4.1

0.61 0.73 0.85

63

0.64 0.79 0.94

66.8

3.61

0.61 0.71 0.83

66

3.66

0.64 0.77 0.91

70.2

3.7

3.66

0.67 0.83 0.99

73.1

0.5

0.58 0.67

70.1

3.71

0.51 0.61 0.73

74.1

3.75

0.52 0.64 0.79

77.3

3.71

0.39 0.48 0.56

74.3

3.77

0.39

0.5

0.59

78.6

3.81

0.4

0.51 0.62

81.6

4.14

4.11

4.2

0.69 0.85

1

0.5

0.59 0.69

4.15

0.51 0.62 0.75

70.7

0.53 0.66 0.81

69.6

67

73.5

4.15

0.39 0.48 0.56

70.9

4.21

4.25

0.4

0.4

0.5

0.6

0.52 0.63

74.9

77.8

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

4.55

0.62

0.75

0.87

4.6

0.66

0.81

0.97

4.64

0.71

0.88

4.61

0.5

0.6

1

0.71

4.66

0.52

0.63

0.77

4.69

0.54

0.67

0.84

4.66

0.39

0.48

0.58

4.71

0.4

0.5

0.61

4.76

0.41

0.53

0.65

12.5 TON STANDARD EFFICIENCY LCH150S4M (2ND STAGE) - MSAV (Multi-Stage Air Volume) SUPPLY AIR BLOWER

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume cfm

Total

Cool

Cap.

kBtuh

Comp.

Motor

Input kW

85°F

Sensible To Total

Ratio (S/T)

Dry Bulb

Total

Cool

Cap.

75°F 80°F 85°F kBtuh

Input kW

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

Total

Cool

Cap.

105°F

Comp.

Motor

Input

Sensible To Total

Ratio (S/T)

Dry Bulb

Total

Cool

Cap.

Comp.

Motor

Input

75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

115°F

3800 138.7

8.68

0.71 0.86

4400 143.3

8.74

0.75 0.92

1

1

131.9

136

9.72

0.73 0.89

9.79

0.77 0.95

139.9

9.84

0.82

1

1

124.7 10.91 0.75 0.92

128.7 10.97

0.8

0.99

1

1

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

116.8 12.25 0.77

120.9 12.32 0.83

0.96

1

1

1

1

5000 147 8.8

0.78 0.98

1 1 1 132.6 11.04 0.84

1 1 125.4 12.39 0.87

1

3800 146.6

8.79

0.56 0.69 0.83 139.3

9.84

0.57

0.7

0.85

132 11.02 0.58 0.72 0.88 123.5 12.36

0.6

0.75

0.92

4400

5000

151.2

154.5

8.86

8.91

0.58 0.72 0.88 143.6

0.6

0.76 0.94 146.9

9.9

9.95

0.6

0.74 0.91 135.4 11.08 0.61 0.77 0.95

127 12.43 0.63

0.8

0.99

0.62 0.79 0.98 138.5 11.13 0.64 0.82

1 129.6 12.47 0.65

0.86

1

3800 154.9

8.91

0.42 0.55 0.67 147.3

9.96

0.43 0.56 0.68 139.3 11.15 0.43 0.56

0.7

130.7 12.48 0.44

0.58

0.72

4400 159 8.98

0.43 0.57

0.7

150.9 10.02 0.44 0.58 0.72 142.6

11.2

0.44 0.59 0.74 133.6 12.54 0.45

0.61

0.78

5000 162.8

9.04

0.44 0.59 0.74 154.6 10.08 0.45 0.61 0.76 145.8 11.26 0.46 0.62 0.79 136.5 12.59 0.46

0.64

0.83

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 22

HUMIDITROL

®

DEHUMIDIFICATION SYSTEM RATINGS

7.5 TON HIGH EFFICIENCY LCH092H4 WITH HUMIDITROL OPERATING (1ST STAGE)

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

75°F

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

85°F

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

Motor

Cap.

Dry Bulb Cap.

Input Dry Bulb Cap.

Dry Bulb Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

2400

3000

3600

2400

3000

3600

2400

3000

3600

26.1

30.8

35.5

33.8

38.0

42.1

41.6

45.1

48.7

2.0

2.0

2.0

2.0

2.0

1.9

1.9

1.9

2.0

.45

.63

.81

.49

.69

.89

.54

.76

.98

.32

.48

.64

.35

.52

.70

.37

.56

.75

.19

.33

.47

.20

.35

.50

.20

.37

.53

22.1

26.0

29.9

29.1

32.8

36.5

37.0

39.6

43.1

2.2

2.2

2.2

2.2

2.2

2.2

2.2

2.2

2.2

.20

.21

.07

.05

.03

.33

.36

.39

.20

.41

.44

.23

.24

.25

.55

.59

.62

.39

.62

.66

.39

.42

.46

.77

.82

.86

.58

18.0

21.2

24.3

24.3

27.6

30.9

30.5

34.1

41.5

2.4

2.4

2.5

2.5

2.5

2.4

2.4

2.4

2.4

.21

.47

.73

14.0

.22

.48

.74

16.4

.24

.49

.74

18.7

.07

.30

.52

19.5

.06

.30

.54

22.4

.05

.31

.56

25.4

-.06

.12

.31

25.0

-.10

.12

.35

28.5

-.13

.13

.39

32.0

2.7

2.7

2.7

2.7

2.7

2.6

2.6

2.6

2.7

.09

.09

-.05

-.08

-.10

-.19

-.24

-.30

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

.09

.39

.37

.36

.21

.19

.18

.02

.01

.01

.47

.47

.23

.27

.31

.69

.66

.63

.46

7.5 TON HIGH EFFICIENCY LCH092H4 WITH HUMIDITROL OPERATING (2ND STAGE)

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

75°F

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

85°F

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

Motor

Cap.

Dry Bulb Cap.

Input Dry Bulb Cap.

Dry Bulb Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

2400

3000

3600

2400

3000

3600

2400

3000

75.3

78.8

82.3

84.0

88.6

93.3

92.7

98.5

3600 104.2

4.0

4.1

4.1

4.1

4.1

4.0

4.0

4.0

4.0

.63

.76

.89

.68

.81

.94

68.2

71.2

.73

.90

1.00

74.1

.48

.61

.73

.51

.53

.33

.34

.34

.65

.71

.45

.48

.51

.79

.84

.58

.63

.68

78.0

81.7

85.5

87.8

92.3

96.8

4.5

4.6

4.6

4.6

4.6

4.5

4.5

4.5

4.5

.49

.52

.29

.30

.30

.62

.68

.73

.46

.78

.82

.64

.69

.43

.46

.49

.92

.96

.75

.79

61.2

63.5

.90

1.00

65.9

.60

.84

.57

.62

.68

72.0

74.8

77.6

82.9

86.2

89.4

5.1

5.1

5.1

5.1

5.1

5.0

5.0

5.0

5.0

.61

.80

.96

54.1

.67

.83

.98

55.9

.73

.89

1.00

57.7

.43

.60

.76

66.1

.47

.63

.80

68.0

.50

.68

.84

69.8

.25

.40

.55

78.0

.26

.44

.62

80.0

.27

.48

.68

82.0

5.6

5.6

5.6

5.6

5.6

5.5

5.5

5.5

5.5

.49

.22

.22

.23

.67

.74

.41

.45

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

.60

.82

1.00

.83

1.00

.88

.60

.63

.67

.38

.42

.46

1.00

.77

.81

.84

.54

.61

.68

8.5 TON HIGH EFFICIENCY LCH102H4 WITH HUMIDITROL OPERATING (1ST STAGE)

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

75°F

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

85°F

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

Motor

Cap.

Dry Bulb Cap.

Input Dry Bulb Cap.

Dry Bulb Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

2720

3400

4080

2720

3400

4080

2720

3400

4080

34.2

39.1

44.0

42.5

47.0

51.5

50.7

54.9

59.0

2.1

2.1

2.1

2.2

2.2

2.1

2.1

2.1

2.1

.47

.57

.67

.49

.64

.78

.51

.70

.89

.33

.44

.55

.33

.48

.62

.34

.52

.70

.18

.31

.44

.18

.32

.47

.17

.34

.50

28.5

32.4

36.4

37.8

41.5

45.1

47.2

50.5

51.8

2.4

2.4

2.4

2.4

2.4

2.3

2.3

2.3

2.4

.20

.20

.05

.03

.02

.34

.37

.39

.19

.40

.44

.20

.21

.23

.51

.58

.66

.36

.60

.68

.36

.40

.44

.68

.80

.93

.52

22.7

25.8

28.9

33.2

31.8

38.8

43.6

46.2

48.7

2.6

2.6

2.7

2.7

2.7

2.6

2.6

2.6

2.6

.22

.45

.68

17.0

.24

.53

.82

19.1

.26

.62

.96

21.3

.06

.27

.48

28.5

.06

.32

.57

30.5

.06

.36

.66

32.4

-.09

.10

.29

40.1

-.12

.11

-.14

.11

.33

.37

41.8

43.5

2.9

2.9

2.9

2.9

2.9

2.9

2.8

2.8

2.9

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

.09

.39

.48

.12

.14

-.07

-.07

.69

.84

.57

1.00

.19

-.08

.24

.29

-.23

-.01

-.26

-.29

.00

.00

.45

.55

.65

.21

.25

.30

8.5 TON HIGH EFFICIENCY LCH102H4 WITH HUMIDITROL OPERATING (2ND STAGE)

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

75°F

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

85°F

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

Motor

Cap.

Dry Bulb Cap.

Input Dry Bulb Cap.

Dry Bulb Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

2720

3400

85.3

89.2

4080 93.1

2720 100.8

3400 104.5

4080 108.2

2720 116.2

3400 119.7

4080 123.2

4.4

4.4

4.4

4.5

4.5

4.3

4.3

4.4

4.4

.64

.81

.97

.69

.84

.98

.75

.87

.99

.48

.63

.77

77.9

81.7

85.5

93.3

.51

.66

.80

97.8

.54

.69

.83

100.3

.32

.45

.58

112.6

.33

.48

.63

115.2

.34

.51

.68

118.1

5.0

5.0

5.0

5.0

5.1

4.9

4.9

4.9

5.0

.49

.52

.28

.29

.29

.63

.69

.75

.45

.65

.68

.42

.45

.49

.82

1.00

70.5

.84

1.00

74.2

.88

1.00

77.8

.62

.77

.80

85.9

89.2

.84

92.4

.57

101.3

.62

104.1

.68

107.0

5.5

5.5

5.6

5.6

5.6

5.5

5.5

5.5

5.5

.62

.84

1.00

63.1

.68

.84

1.00

66.7

.75

.89

1.00

70.2

.43

.62

.77

78.5

.46

.64

.81

81.5

.50

.68

.84

84.6

.24

.40

.56

93.8

.24

.43

.62

96.4

.25

.46

.68

98.9

6.1

6.1

6.2

6.2

6.2

6.0

6.0

6.0

6.1

.48

.20

.20

.20

.68

.76

.40

.44

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

.60

.86

1.00

.84

1.00

.90

.62

.62

.67

.37

.41

.44

1.00

.78

.81

.84

.55

.62

.68

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 23

HUMIDITROL

®

DEHUMIDIFICATION SYSTEM RATINGS

10 TON HIGH EFFICIENCY LCH120H4 WITH HUMIDITROL OPERATING (1ST STAGE)

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

75°F

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

85°F

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

Motor

Cap.

Dry Bulb Cap.

Input Dry Bulb Cap.

Dry Bulb Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

3200

4000

4800

3200

4000

4800

3200

4000

4800

49.5

59.0

68.6

61.2

68.2

75.2

73.0

77.4

81.9

2.7

2.7

2.7

2.7

2.8

2.6

2.6

2.6

2.7

.48

.70

.92

42.3

.56

.82

1.00

49.1

.62

.92

1.00

55.9

.30

.49

.66

52.4

.34

.55

.77

57.7

.37

.62

.87

62.9

.17

.32

.48

62.5

.17

.35

.54

66.2

.19

.39

.61

70.0

3.0

3.0

3.0

3.0

3.1

2.9

2.9

2.9

3.0

.23

.26

.06

.05

.06

.39

.45

.56

.20

.66

.94

35.1

.81

1.00

39.1

.96

1.00

43.2

.41

.49

.57

.24

.28

.31

.64

.75

.89

.42

.50

.57

43.5

47.1

50.7

52.0

55.1

58.1

3.3

3.3

3.3

3.3

3.4

3.2

3.2

3.2

3.3

.22

.60

.98

.31

.80

.93

27.9

29.2

.41

1.00 1.00

30.5

.01

.30

.59

.05

.06

-.12

-.14

-.16

.38

.50

.11

.15

.18

.75

.92

.34

.42

.51

34.7

36.5

38.4

41.5

43.9

46.3

3.6

3.6

3.6

3.6

3.7

3.5

3.5

3.5

3.6

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

.01

.46

1.00

.77

-.01

-.02

-.06

-.12

-.18

-.13

.03

-.23

-.04

-.34

-.09

.97

.08

.15

.28

.98

.19

.28

.40

.97

.80

.50

.72

10 TON HIGH EFFICIENCY LCH120H4 WITH HUMIDITROL OPERATING (2ND STAGE)

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

75°F

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

85°F

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

Motor

Cap.

Dry Bulb Cap.

Input Dry Bulb Cap.

Dry Bulb Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

3200 104.7

4000 114.8

4800 125.0

3200 118.9

4000 128.7

4800 138.4

3200 133.1

4000 142.5

4800 151.9

5.6

5.6

5.6

5.7

5.8

5.4

5.5

5.5

5.5

.61

.73

.86

95.0

.63

.78

.93

103.4

.65

.82

.99

111.8

.45

.57

.69

108.5

.47

.60

.74

117.3

.48

.64

.79

126.1

.29

.41

.53

122.0

.30

.43

.56

131.2

.31

.45

.59

140.4

6.3

6.3

6.3

6.4

6.4

6.1

6.2

6.2

6.2

.44

.46

.26

.27

.27

.58

.62

.65

.42

.59

.62

.39

.41

.42

.75

.78

.91

.95

85.3

91.9

.82

1.00

98.6

.57

.71

98.1

.75

105.9

.79

113.8

.51

110.9

.55

119.9

.58

128.9

6.9

7.0

7.0

7.1

7.1

6.8

6.8

6.9

6.9

.56

.76

.95

75.5

.60

.79

.98

80.5

.65

.82

1.00

85.4

.39

.56

.73

87.7

.42

.59

.75

94.5

.44

.61

.78

101.4

.23

.36

.50

99.8

.23

.38

.53

108.6

.23

.40

.57

117.5

7.6

7.6

7.7

7.7

7.7

7.5

7.5

7.5

7.6

.42

.20

.19

.19

.59

.64

.36

.39

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

.53

.77

1.00

.79

1.00

.82

.56

.58

.60

.34

.36

.37

1.00

.74

.76

.78

.49

.52

.56

12.5 TON STANDARD EFFICIENCY LCH150S4 WITH HUMIDITROL OPERATING (1ST STAGE)

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

75°F

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

85°F

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

Motor

Cap.

Dry Bulb Cap.

Input Dry Bulb Cap.

Dry Bulb Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

3800

4400

5000

3800

4400

5000

3800

4400

5000

55.2

58.2

61.2

63.7

66.6

69.4

72.2

74.9

77.7

3.6

3.6

3.6

3.7

3.7

3.4

3.5

3.5

3.5

.48

.70

.91

45.8

.53

.77

1.00

47.9

.57

.84

1.00

50.0

.29

.48

.66

53.8

.32

.51

.73

56.1

.33

.55

.79

58.4

.15

.31

.47

61.9

.16

.33

.51

64.4

.16

.35

.55

66.9

3.9

3.9

4.0

4.0

4.0

3.8

3.8

3.8

3.9

.21

.24

.05

.05

.05

.40

.45

.50

.20

.67

.94

36.4

.76

1.00

37.6

.85

1.00

38.8

.41

.46

.51

.23

.25

.28

.63

.72

.79

.42

.45

.51

44.0

45.7

47.4

51.6

53.8

56.1

4.2

4.2

4.3

4.3

4.4

4.1

4.1

4.1

4.2

.25

.61

.97

27.0

.31

.73

1.00

27.3

.33

.73

.90

27.6

.04

.32

.59

34.1

.05

.36

.68

35.3

.08

.42

.79

36.4

-.10

.12

.35

41.3

-.11

.14

.39

43.3

-.12

.16

.45

45.3

4.6

4.6

4.6

4.7

4.7

4.5

4.5

4.5

4.6

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

.33

.22

.10

.03

-.04

-.10

.51

.99

.69

1.00

.89

.12

.19

.25

-.28

-.07

-.29

-.06

-.30

-.04

1.00

.52

.65

.60

.22

.27

.33

12.5 TON STANDARD EFFICIENCY LCH150S4 WITH HUMIDITROL OPERATING (2ND STAGE)

Entering

Wet

Bulb

Temperature

63°F

67°F

71°F

Total

Air

Volume

Total

Cool

Comp.

Motor

Input

65°F

Sensible To Total

Ratio (S/T)

Total

Cool

Outdoor Air Temperature Entering Outdoor Coil

Comp.

Motor

75°F

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

85°F

Motor

Input

Sensible To Total

Ratio (S/T)

Total

Cool

Comp.

Motor

Cap.

Dry Bulb Cap.

Input Dry Bulb Cap.

Dry Bulb Cap.

Input cfm kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW 75°F 80°F 85°F kBtuh kW

3800 122.7

4400 127.4

5000 132.1

3800 137.7

4400 142.5

5000 147.2

3800 152.7

4400 157.5

5000 162.4

7.5

7.6

7.7

7.7

7.8

7.3

7.3

7.3

7.5

.63

.79

.96

110.6

.66

.82

.97

114.4

.69

.84

.99

118.2

.47

.62

.76

124.7

.49

.64

.79

128.7

.50

.66

.81

132.7

.31

.44

.57

138.8

.31

.46

.60

143.1

.31

.47

.63

147.3

8.3

8.3

8.4

8.5

8.5

8.0

8.1

8.1

8.2

.46

.48

.27

.27

.27

.62

.65

.69

.44

.63

.65

.42

.43

.45

.80

.99

98.6

.83

1.00 101.4

.86

1.00 104.2

.61

.78

111.8

.80

115.0

.82

118.2

.56

125.0

.60

128.6

.63

132.2

9.0

9.1

9.2

9.2

9.3

8.8

8.8

8.9

9.0

.61

.81

1.00

86.5

.65

.84

1.00

88.4

.69

.87

1.00

90.3

.42

.60

.79

98.8

9.6

9.6

9.6

9.8

.44

.63

.81

101.3

.46

.65

.84

103.7

9.8

9.8

.23

.39

.55

111.1

10.0

.23

.41

.59

114.2

10.0

.23

.43

.63

117.2

10.0

.44

.19

.19

.19

.64

.69

.39

.42

95°F

Sensible To Total

Ratio (S/T)

Dry Bulb

75°F 80°F 85°F

.60

.82

1.00

.85

1.00

.88

.60

.62

.65

.37

.39

.41

1.00

.80

.83

.85

.55

.59

.63

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 24

BLOWER DATA

092 AND 102 BELT DRIVE BLOWER − BASE UNIT

BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR

FILTERS IN PLACE. FOR ALL UNITS ADD:

1 − Wet indoor coil air resistance of selected unit.

2 − Any factory installed options air resistance (heat section, economizer, etc.)

3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.)

Then determine from blower table blower motor output required.

See page 27 for blower motors and drives. See page 27 for wet coil and option/accessory air resistance data.

MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.)

7.5 kW, 15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm

Total

Air

Volume cfm

0.2

0.4

0.6

0.8

1.0

Total Static Pressure − in. w.g.

1.2

1.4

1.6

1.8

2.0

2.2

2.4

2.6

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1750 481 0.21 549 0.4 618 0.57 688 0.7 758 0.82 824 0.93 885 1.08 941 1.23 991 1.39 1038 1.54 1082 1.68 1124 1.82 1166 1.95

2000 493 0.29 561 0.47 629 0.64 700 0.77 768 0.9 832 1.02 892 1.17 946 1.33 995 1.49 1041 1.66 1085 1.81 1126 1.97 1167 2.12

2250 507 0.37 574 0.56 643 0.72 712 0.86 779 0.99 842 1.13 900 1.28 953 1.44 1001 1.61 1045 1.78 1088 1.95 1128 2.12 1168 2.3

2500 521 0.46 588 0.64 657 0.81 727 0.95 792 1.09 853 1.24 909 1.4 960 1.57 1007 1.74 1050 1.93 1091 2.11 1130 2.29 1170 2.48

2750 537 0.56 604 0.74 674 0.91 743 1.06 806 1.21 865 1.36 920 1.53 969 1.71 1014 1.89 1055 2.08 1095 2.27 1133 2.47 1172 2.66

3000 554 0.67 622 0.86 692 1.02 760 1.18 822 1.34 878 1.5 931 1.68 979 1.86 1021 2.06 1061 2.26 1099 2.46 1136 2.65 1174 2.85

3250 572 0.78 641 0.98 712 1.15 778 1.32 838 1.49 892 1.66 943 1.84 989 2.03 1030 2.24 1068 2.45 1105 2.65 1141 2.85 1178 3.06

3500 592 0.9 663 1.12 733 1.3 798 1.47 855 1.65 907 1.83 956 2.02 1000 2.22 1039 2.44 1076 2.65 1111 2.86 1146 3.07 1183 3.27

3750 614 1.04 687 1.28 756 1.47 818 1.65 872 1.83 923 2.02 970 2.22 1011 2.43 1049 2.65 1084 2.87 1118 3.09 1152 3.29 1189 3.51

4000 639 1.22 713 1.48 780 1.66 838 1.83 890 2.02 939 2.22 984 2.44 1023 2.66 1059 2.89 1093 3.11 1126 3.33 1160 3.54 1197 3.77

4250 667 1.43 741 1.69 805 1.86 859 2.02 909 2.22 956 2.45 998 2.68 1036 2.92 1070 3.15 1103 3.37 1135 3.59 1169 3.81 1207 4.05

120 BELT DRIVE BLOWER − BASE UNIT

BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR

FILTERS IN PLACE. FOR ALL UNITS ADD:

1 − Wet indoor coil air resistance of selected unit.

2 − Any factory installed options air resistance (heat section, economizer, etc.)

3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.)

Then determine from blower table blower motor output required.

See page 27 for blower motors and drives. See page 27 for wet coil and option/accessory air resistance data.

MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.)

15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm

60 kW - 4000 cfm

Total

Air

Volume cfm

0.2

0.4

0.6

0.8

1.0

Total Static Pressure − in. w.g.

1.2

1.4

1.6

1.8

2.0

2.2

2.4

2.6

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2000 497 0.25 558 0.44 624 0.6 694 0.74 764 0.85 830 0.99 889 1.16 943 1.34 994 1.52 1045 1.71 1096 1.89 1146 2.08 1197 2.27

2250 511 0.34 573 0.52 638 0.68 708 0.82 776 0.94 839 1.09 896 1.26 948 1.45 998 1.64 1048 1.83 1098 2.01 1149 2.2 1200 2.4

2500 527 0.44 589 0.62 654 0.78 723 0.91 789 1.05 850 1.21 904 1.39 955 1.58 1003 1.77 1052 1.96 1101 2.14 1152 2.33 1203 2.53

2750 545 0.55 606 0.72 672 0.88 740 1.03 804 1.17 861 1.34 914 1.53 962 1.72 1010 1.92 1057 2.1 1105 2.29 1154 2.47 1206 2.68

3000 564 0.66 626 0.84 692 1.01 759 1.16 819 1.32 874 1.49 924 1.68 971 1.88 1017 2.08 1063 2.26 1110 2.44 1158 2.63 1208 2.83

3250 585 0.79 648 0.98 714 1.14 778 1.31 836 1.48 887 1.66 935 1.86 981 2.06 1026 2.26 1071 2.45 1117 2.63 1163 2.8 1213 3

3500 607 0.93 672 1.13 737 1.31 798 1.48 852 1.66 901 1.85 948 2.05 993 2.26 1037 2.46 1081 2.65 1125 2.83 1171 3.01 1221 3.21

3750 632 1.1 698 1.31 762 1.5 819 1.67 869 1.86 915 2.05 961 2.25 1005 2.47 1049 2.68 1092 2.88 1136 3.05 1181 3.24 1231 3.45

4000 660 1.3 726 1.52 787 1.7 838 1.87 885 2.06 930 2.26 974 2.48 1018 2.71 1062 2.93 1105 3.12 1149 3.3 1194 3.49 1245 3.72

4250 691 1.53 755 1.75 810 1.91 857 2.07 901 2.27 945 2.5 990 2.74 1034 2.98 1077 3.2 1120 3.39 1163 3.58 1210 3.79 1262 4.03

4500 724 1.78 783 1.98 831 2.12 874 2.28 917 2.5 962 2.75 1006 3.02 1051 3.27 1094 3.49 1137 3.7 1181 3.89 1228 4.11 1281 4.38

4750 757 2.05 809 2.2 851 2.33 891 2.51 935 2.76 980 3.05 1025 3.33 1070 3.59 1113 3.82 1156 4.03 1201 4.24 1249 4.47 1303 4.75

5000 787 2.31 831 2.43 870 2.57 910 2.78 954 3.06 1000 3.38 1046 3.68 1091 3.95 1135 4.19 1178 4.4 1224 4.62 1272 4.86 1325 5.13

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 25

BLOWER DATA

150 BELT DRIVE BLOWER − BASE UNIT

BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR

FILTERS IN PLACE. FOR ALL UNITS ADD:

1 − Wet indoor coil air resistance of selected unit.

2 − Any factory installed options air resistance (heat section, economizer, etc.)

3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.)

Then determine from blower table blower motor output required.

See page 27 for blower motors and drives. See page 27 for wet coil and option/accessory air resistance data.

MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT (Maximum Static Pressure - 2.0 in. w.g.)

15 kW, 22.5 kW, 30 kW and 45 kW - 2800 cfm

60 kW - 4000 cfm

Total

Air

Volume cfm

0.2

0.4

0.6

0.8

1.0

Total Static Pressure − in. w.g.

1.2

1.4

1.6

1.8

2.0

2.2

2.4

2.6

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2500 537 0.31 596 0.56 663 0.81 736 1.03 805 1.2 867 1.34 924 1.47 976 1.62 1026 1.77 1073 1.95 1118 2.13 1162 2.32 1206 2.51

2750 555 0.43 614 0.69 681 0.94 753 1.16 820 1.34 879 1.48 935 1.61 986 1.76 1034 1.92 1081 2.11 1126 2.31 1171 2.51 1215 2.71

3000 574 0.57 633 0.83 700 1.08 770 1.31 834 1.49 892 1.62 946 1.75 996 1.91 1044 2.09 1090 2.29 1135 2.5 1180 2.71 1225 2.92

3250 595 0.73 654 0.99 721 1.25 789 1.48 850 1.65 905 1.78 957 1.91 1006 2.08 1053 2.27 1099 2.48 1145 2.7 1190 2.92 1235 3.15

3500 617 0.89 677 1.17 743 1.44 807 1.66 865 1.82 919 1.94 970 2.08 1017 2.26 1064 2.47 1110 2.69 1155 2.92 1200 3.15 1246 3.39

3750 640 1.09 701 1.38 765 1.64 826 1.84 882 1.99 933 2.12 982 2.27 1029 2.46 1075 2.68 1120 2.91 1166 3.15 1211 3.39 1258 3.65

4000 665 1.32 725 1.62 787 1.86 846 2.03 899 2.17 949 2.3 996 2.47 1042 2.68 1087 2.92 1132 3.16 1177 3.4 1223 3.66 1270 3.93

4250 691 1.57 750 1.87 810 2.07 866 2.22 917 2.35 964 2.51 1010 2.7 1055 2.93 1099 3.17 1144 3.42 1189 3.67 1235 3.95 1283 4.25

4500 718 1.85 776 2.12 833 2.28 886 2.4 935 2.55 981 2.73 1025 2.95 1069 3.2 1112 3.45 1156 3.7 1201 3.97 1248 4.27 1297 4.59

4750 745 2.14 802 2.36 856 2.48 907 2.6 954 2.77 997 2.99 1040 3.23 1083 3.49 1126 3.75 1170 4.01 1215 4.29 1262 4.61 1311 4.96

5000 773 2.42 828 2.59 880 2.69 928 2.83 972 3.03 1014 3.28 1056 3.55 1097 3.82 1140 4.08 1183 4.35 1229 4.65 1276 4.98 1325 5.33

5250 802 2.69 854 2.82 904 2.93 950 3.09 991 3.33 1032 3.61 1072 3.9 1113 4.17 1155 4.44 1198 4.72 1243 5.02 1291 5.36 1340 5.71

5500 831 2.95 881 3.06 928 3.2 971 3.4 1011 3.68 1050 3.99 1089 4.28 1129 4.56 1170 4.83 1213 5.11 1258 5.42 1306 5.75 1355 6.1

5750 860 3.21 908 3.33 952 3.5 992 3.75 1030 4.07 1068 4.4 1106 4.7 1145 4.98 1186 5.25 1229 5.53 - - - - - - - - - - - - - - - - - -

6000 890 3.48 934 3.63 976 3.86 1013 4.16 1050 4.52 1086 4.85 1123 5.16 1162 5.44 1202 5.7 - - - - - - - - - - - - - - - - - - - - - - - -

6250 919 3.78 961 3.99 999 4.27 1034 4.63 1069 5.01 1104 5.35 1141 5.65 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 26

BLOWER DATA

FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS

Motor Efficiency Nominal hp

Maximum hp

Standard & High

Standard & High

Standard & High

Standard

Standard

Standard

High

High

High

Standard

Standard

Standard

2

3

3

3

2

2

3

3

3

5

5

5

2.3

2.3

2.3

3.45

3.45

3.45

3.45

3.45

3.45

5.75

5.75

5.75

Drive Kit Number

9

10

11

12

7

8

3

4

5

6

1

2

RPM Range

590 - 890

800 - 1105

795 - 1195

730 - 970

940 - 1200

1015 - 1300

730 - 970

940 - 1200

1015 - 1300

900 - 1135

1040 - 1315

1125 - 1425

NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.

NOTE – Units equipped with MSAV

®

(Multi-Stage Air Volume) option are limited to a motor service factor of 1.0.

POWER EXHAUST FAN PERFORMANCE

Return Air System Static Pressure

in. w.g.

0

0.05

0.10

0.15

0.20

0.25

0.30

0.35

Air Volume Exhausted

cfm

3175

2955

2685

2410

2165

1920

1420

1200

FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE - in. w.g.

Air

Volume cfm

1750

3750

4000

4250

4500

4750

5000

5250

5500

5750

6000

2000

2250

2500

2750

3000

3250

3500

Wet Indoor Coil

092, 102,120

0.04

0.14

0.15

0.17

0.19

0.20

0.22

0.24

0.25

0.27

0.29

0.05

0.06

0.07

0.08

0.10

0.11

0.12

150

0.06

0.21

0.23

0.26

0.28

0.31

0.33

0.36

0.39

0.41

0.44

0.08

0.09

0.11

0.13

0.15

0.17

0.19

Electric

Heat

0.03

0.09

0.09

0.13

0.14

0.17

0.20

0.22

0.25

0.31

0.33

0.03

0.04

0.04

0.05

0.06

0.06

0.09

Economizer

0.05

0.15

0.19

0.19

0.22

0.25

0.29

0.32

0.34

0.45

0.52

0.06

0.08

0.11

0.12

0.13

0.15

0.15

Humiditrol

Condenser

Reheat Coil

0.02

0.05

0.05

0.06

0.07

0.07

0.08

0.08

0.09

0.10

0.10

0.02

0.02

0.03

0.03

0.03

0.04

0.04

MERV 8

0.01

0.03

0.04

0.04

0.04

0.05

0.06

0.06

0.07

0.07

0.08

0.01

0.01

0.01

0.02

0.02

0.02

0.03

Filters

MERV 13

0.03

0.08

0.08

0.09

0.09

0.10

0.10

0.11

0.12

0.12

0.13

0.03

0.04

0.05

0.05

0.06

0.06

0.07

Return Air

Adaptor

Plate

0.00

0.00

0.00

0.00

0.00

0.02

0.02

0.04

0.07

0.09

0.11

0.12

0.16

0.18

0.19

0.22

0.25

0.27

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 27

BLOWER DATA

CEILING DIFFUSERS AIR RESISTANCE - in. w.g.

Unit Size

Air Volume cfm

RTD11 Step-Down Diffuser

2 Ends Open

1 Side, 2 Ends

Open

2400

2600

2800

0.21

0.24

0.27

0.18

0.21

0.24

092 Models

3000

3200

3400

3600

3800

3600

0.32

0.41

0.50

0.61

0.73

0.36

0.29

0.37

0.45

0.54

0.63

0.28

102 & 120 Models

150 Models

5200

4200

4400

4600

4800

5000

3800

4000

4200

4400

4600

4800

5000

5200

5400

5600

5800

0.40

0.44

0.49

0.54

0.60

0.65

0.69

0.75

0.22

0.28

0.34

0.40

0.46

0.52

0.58

0.64

0.70

0.44

0.49

0.54

0.59

0.62

0.19

0.24

0.29

0.34

0.39

0.32

0.36

0.40

0.44

0.49

0.53

0.58

CEILING DIFFUSER AIR THROW DATA

Model No.

092 Models

Air Volume cfm

2600

2800

3000

1

Effective Throw Range

RTD11 Step-Down ft.

FD11 Flush ft.

24 - 29

25 - 30

27 - 33

19 - 24

20 - 28

21 - 29

3200

3400

3600

28 - 35

30 - 37

25 - 33

22 - 29

22 - 30

22 - 29

102, 120

Models

3800

4000

4200

4400

5600

5800

27 - 35

29- 37

32 - 40

34 - 42

39 - 49

42 - 51

22 - 30

24 - 33

26 - 35

28 - 37

28 - 37

29 - 38

150 Models

6000

6200

6400

44 - 54

45 - 55

46 - 55

40 - 50

42 - 51

43 - 52

6600 47 - 56 45 - 56

1

Throw is the horizontal or vertical distance an air stream travels on leaving the outlet or diffuser before the maximum velocity is reduced to 50 ft. per minute. Four sides open.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 28

0.24

0.29

0.34

0.39

0.43

0.47

0.51

0.37

0.42

0.46

0.50

0.54

0.16

0.20

All Ends & Sides

Open

0.15

0.18

0.21

0.25

0.32

0.39

0.48

0.57

0.23

0.26

0.29

0.33

FD11 Flush

Diffuser

0.15

0.19

0.23

0.27

0.31

0.35

0.39

0.27

0.31

0.35

0.39

0.43

0.10

0.12

0.44

0.51

0.15

0.18

0.21

0.24

0.14

0.17

0.20

0.25

0.31

0.37

ELECTRICAL/ELECTRIC HEAT DATA 7.5 TON

7.5 TON HIGH EFFICIENCY (R-410A) LCH092H4

1

Voltage - 60hz

Compressor 1

Compressor 2

Outdoor Fan

Motors (2)

Rated Load Amps

Locked Rotor Amps

Rated Load Amps

Locked Rotor Amps

Full Load Amps

(total)

Power Exhaust Full Load Amps

(1) 0.33 HP

Service Outlet 115V GFI (amps)

Indoor Blower Horsepower

Motor

2

Maximum

Overcurrent

Protection

3

Minimum

Circuit

Ampacity

Full Load Amps

Unit Only

With (1) 0.33 HP

Power Exhaust

Unit Only

With (1) 0.33 HP

Power Exhaust

2

7.5

50

50

42

45

208/230V - 3 Ph

13.1

83.1

13.1

83.1

2.4

(4.8)

2.4

15

3

10.6

50

60

45

48

5

16.7

60

70

52

55

2

3.4

25

25

20

22

460V - 3 Ph

6.1

41

6.1

41

1.3

(2.6)

1.3

15

3

4.8

25

25

22

23

5

7.6

30

30

25

26

2

2.7

15

20

15

16

575V - 3 Ph

4.4

33

4.4

33

1

(2)

1

20

3

3.9

20

20

16

17

5

6.1

20

25

19

20

2

3

2

3

ELECTRIC HEAT DATA

Electric Heat Voltage

Maximum

Overcurrent

Protection

Minimum

Circuit

Ampacity

Maximum

Overcurrent

Protection

Minimum

Circuit

Ampacity

Unit+

Electric Heat

Unit+

Electric Heat

Unit+

Electric Heat and (1) 0.33

HP

Power Exhaust

Unit+

Electric Heat and (1) 0.33

HP

Power Exhaust

208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V

7.5 kW

50 50 50 50 60 60 25 25 30 15 20 20

15 kW

22.5 kW

4

4

50

70

60

80

4

60

80

60

90

4

4

60

80

70

90

30 kW

4

90 100

4

100 110

4

100 125

45 kW 150

150 150 150

4

150 175

7.5 kW

30 kW

45 kW 127 145 131 149 139 157

22.5 kW

4

42

15 kW

49

22.5 kW

69

88

7.5 kW

50

15 kW

60

80

30 kW

4

100 110

4

100 110

4

110 125

45 kW 150

7.5 kW

45

15 kW

52

42

55

78

100

50

60

90

150

45

58

4

4

4

45

53

72

92

60

60

80

150 175

48

56

45

59

81

104

60

70

90

48

62

4

4

51

60

80

100

70

70

90 100

150 175

54

63

51

66

89

112

70

70

54

69

30

40

50

80

20

27

39

50

72

25

30

40

60

80

22

29

30

40

60

80

22

29

40

52

74

25

35

45

60

80

23

31

35

45

60

80

24

33

44

55

78

30

35

45

60

80

26

34

25

35

40

60

15

22

31

40

58

20

25

35

45

60

16

23

25

35

45

60

16

23

32

41

60

20

25

35

45

70

17

25

30

35

45

70

18

26

35

44

62

25

30

40

45

70

19

27

22.5 kW

72

30 kW

91

81

103

75

95

84

107

83

103

92

115

45 kW 130 148 134 152 142 160

40

51

74

42

53

76

45

57

79

32

41

59

34

43

61

36

45

64

ELECTRICAL ACCESSORIES

Disconnect 7.5 kW 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56

15 kW 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56

22.5 kW 54W56 54W56 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56

30 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56

45 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56

1

2

3

4

NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.

Extremes of operating range are plus and minus 10% of line voltage.

HACR type breaker or fuse.

Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

Factory installed circuit breaker not available.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 29

ELECTRICAL/ELECTRIC HEAT DATA 8.5 TON

8.5 TON HIGH EFFICIENCY (R-410A) LCH102H4

2

3

1

Voltage - 60hz

Compressor 1 Rated Load Amps

Locked Rotor Amps

Compressor 2

Outdoor Fan

Motors (2)

Power Exhaust

Rated Load Amps

Locked Rotor Amps

Full Load Amps

(total)

Full Load Amps

(1) 0.33 HP

Service Outlet 115V GFI (amps)

Indoor Blower

Motor

Maximum

Overcurrent

Protection

Minimum

Circuit

Ampacity

Horsepower

Full Load Amps

Unit Only

With (1) 0.33 HP

Power Exhaust

Unit Only

With (1) 0.33 HP

Power Exhaust

2

7.5

50

50

44

46

208/230V - 3 Ph

13.7

83.1

13.7

83.1

2.4

(4.8)

2.4

15

3

10.6

50

60

47

49

5

16.7

60

70

54

56

2

3.4

25

25

20

22

460V - 3 Ph

6.2

41

6.2

41

1.3

(2.6)

1.3

15

3

4.8

25

25

22

23

5

7.6

30

30

25

26

2

2.7

20

20

16

17

575V - 3 Ph

4.8

33

4.8

33

1

(2)

1

20

3

3.9

20

20

17

18

5

6.1

25

25

20

21

3

2

3

ELECTRIC HEAT DATA

Electric Heat Voltage

2

Maximum

Overcurrent

Protection

Minimum

Circuit

Ampacity

Maximum

Overcurrent

Protection

Minimum

Circuit

Ampacity

Unit+

Electric Heat

Unit+

Electric Heat

Unit+

Electric Heat and (1) 0.33

HP

Power Exhaust

Unit+

Electric Heat and (1) 0.33

HP

Power Exhaust

7.5 kW

15 kW

208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V

4

50

50

22.5 kW

4

70

50

60

80

4

50

60

80

50

60

90

4

4

60

60

80

60

70

90

25

30

40

25

30

40

30

35

45

20

25

35

20

25

35

25

30

35

30 kW

45 kW 150 150 150 150

7.5 kW

4

90 100

44

15 kW

49

22.5 kW

69

30 kW

88

44

55

78

100

4

100 110

47

53

72

92

47

59

81

104

4

4

100 125

150 175

54

60

80

100

54

66

89

112

45 kW 127 145 131 149 139 157

7.5 kW

50 50 60 60 70 70

50

80

20

27

39

50

72

25

60

80

22

29

40

52

74

25

60

80

25

33

44

55

78

30

40

60

16

22

31

40

58

20

45

60

17

23

32

41

60

20

45

70

20

26

35

44

62

25

15 kW

60

22.5 kW

4

80

60

90

4

4

60

80

70

90

4

70 70

90 100

30 kW

4

100 110

4

100 110

4

110 125

45 kW 150

7.5 kW

46

15 kW

52

150

46

58

4

150 175

49

56

49

62

4

150 175

56

63

56

69

22.5 kW

72

30 kW

91

81

103

75

95

84

107

83

103

92

115

45 kW 130 148 134 152 142 160

30

40

60

80

22

29

40

51

74

35

45

60

80

23

31

42

53

76

35

45

60

80

26

34

45

57

79

25

35

45

60

17

23

32

41

59

25

35

45

70

18

25

34

43

61

30

40

45

70

21

27

36

45

64

ELECTRICAL ACCESSORIES

Disconnect 7.5 kW 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56

15 kW 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56

22.5 kW 54W56 54W56 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56

30 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56

45 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56

1

2

3

4

NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.

Extremes of operating range are plus and minus 10% of line voltage.

HACR type breaker or fuse.

Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

Factory installed circuit breaker not available.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 30

ELECTRICAL/ELECTRIC HEAT DATA 10 TON

10 TON HIGH EFFICIENCY (R-410A) LCH120H4

2

1

Voltage - 60hz

Compressor 1 Rated Load Amps

Locked Rotor Amps

Compressor 2

Outdoor Fan

Motors (2)

Power Exhaust

Rated Load Amps

Locked Rotor Amps

Full Load Amps

(total)

Full Load Amps

(1) 0.33 HP

Service Outlet 115V GFI (amps)

Indoor Blower

Motor

Maximum

Overcurrent

Protection

3

Minimum

Circuit

Ampacity

Horsepower

Full Load Amps

Unit Only

With (1) 0.33 HP

Power Exhaust

Unit Only

With (1) 0.33 HP

Power Exhaust

2

7.5

50

50

43

46

208/230V - 3 Ph

13.5

109

13.5

109

2.4

(4.8)

2.4

15

3

10.6

50

60

46

49

5

16.7

60

70

53

56

2

3.4

30

30

24

26

460V - 3 Ph

8

59

8

59

1.3

(2.6)

1.3

15

3

4.8

30

30

26

27

5

7.6

35

35

29

30

2

2.7

20

20

16

17

575V - 3 Ph

5

40

5

40

1

(2)

1

20

3

3.9

20

20

18

19

5

6.1

25

25

20

21

ELECTRIC HEAT DATA

3

2

Electric Heat Voltage

2

Maximum

Overcurrent

Protection

Minimum

Circuit

Ampacity

Maximum

Overcurrent

Protection

Unit+

Electric Heat

Unit+

Electric Heat

Unit+

Electric Heat and (1) 0.33

HP

Power Exhaust

15 kW

22.5 kW

208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V

4

4

50

70

60

80

4

60

80

60

90

4

4

60

80

70

90

30 kW

4

90 100

4

100 110

4

100 125

30

40

50

30

40

60

35

45

60

25

35

40

25

35

45

30

35

45

80 80 80 60 60 70 45 kW 150 150 150 150

4

150 175

60 kW

4

150 175

4

150 175

4

150 175

15 kW

49

22.5 kW

69

30 kW

88

55

78

100

53

72

92

59

81

104

60

80

100

66

89

112

45 kW 127 145 131 149 139 157

60 kW 135 154 139 158 146 166

15 kW

60 60

4

60 70 70 70

22.5 kW

30 kW

4

4

80 90

100 110

4

4

80 90

100 110

4

4

90 100

110 125

45 kW 150 150

4

150 175

4

150 175

60 kW

4

150 175

4

150 175

4

150 175

80

27

39

50

72

77

30

40

60

80

80

80

29

40

52

74

79

35

45

60

80

80

90

33

44

55

78

82

35

45

60

80

90

70

22

31

40

58

62

25

35

45

60

70

70

23

32

41

60

63

25

35

45

70

70

70

26

35

44

62

66

30

40

45

70

70

3

Minimum

Circuit

Ampacity

Unit+

Electric Heat and (1) 0.33

HP

Power Exhaust

15 kW

52

22.5 kW

72

30 kW

91

58

81

103

56

75

95

62

84

107

63

83

103

69

92

115

45 kW 130 148 134 152 142 160

60 kW 138 157 142 161 149 169

ELECTRICAL ACCESSORIES

29

40

51

74

79

31

42

53

76

80

34

45

57

79

84

23

32

41

59

63

25

34

43

61

64

27

36

45

64

67

Disconnect 15 kW 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56

22.5 kW 54W56 54W56 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56

30 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56

45 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56

60 kW

5

N/A

5

N/A

5

N/A

5

N/A

5

N/A

5

N/A 54W56 54W56

5

N/A 54W56 54W56 54W56

NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.

1

Extremes of operating range are plus and minus 10% of line voltage.

2

HACR type breaker or fuse.

3

Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

4

Factory installed circuit breaker not available.

5

Disconnect must be field furnished.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 31

ELECTRICAL/ELECTRIC HEAT DATA 12.5 TON

12.5 TON STANDARD EFFICIENCY (R-410A) LCH150S4

1

Voltage - 60hz

Compressor 1

Compressor 2

Rated Load Amps

Locked Rotor Amps

Rated Load Amps

Locked Rotor Amps

Outdoor Fan

Motors (2)

Power Exhaust

Full Load Amps

(total)

Full Load Amps

(1) 0.33 HP

Service Outlet 115V GFI (amps)

Indoor Blower Horsepower

Motor

2

Maximum

Overcurrent

Protection

3

Minimum

Circuit

Ampacity

Full Load Amps

Unit Only

With (1) 0.33 HP

Power Exhaust

Unit Only

With (1) 0.33 HP

Power Exhaust

2

7.5

70

70

58

60

208/230V - 3 Ph

19.6

136

19.6

136

3

(6)

2.4

15

3

10.6

80

80

61

64

5

16.7

80

80

67

70

2

3.4

30

30

25

27

460V - 3 Ph

8.2

66.1

8.2

66.1

1.5

(3)

1.3

15

3

4.8

30

35

27

28

5

7.6

35

35

30

31

2

2.7

25

25

20

21

575V - 3 Ph

6.6

55.3

6.6

55.3

1.2

(2.4)

1

20

3

3.9

25

25

22

23

5

6.1

25

30

24

25

2

3

2

3

ELECTRIC HEAT DATA

Electric Heat Voltage

Maximum

Overcurrent

Protection

Minimum

Circuit

Ampacity

Maximum

Overcurrent

Protection

Minimum

Circuit

Ampacity

Unit+

Electric Heat

Unit+

Electric Heat

Unit+

Electric Heat and (1) 0.33

HP

Power Exhaust

Unit+

Electric Heat and (1) 0.33

HP

Power Exhaust

208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V

15 kW

70 70 80 80 80 80 30 30 35 25 25 30

22.5 kW

4

70 80

4

80 90

4

80 90 40 40 45 35 35 35

30 kW

4

90 100

4

100 110

45 kW 150 150 150 150

4

4

100 125

150 175

60 kW

4

150 175

4

150 175

4

150 175

50

80

80

60

80

80

60

80

90

40

60

70

45

60

70

45

70

70

15 kW

58

22.5 kW

69

30 kW

88

58

78

100

61

72

92

61

81

104

67

80

100

67

89

112

45 kW 127 145 131 149 139 157

60 kW 135 154 139 158 146 166

15 kW

70 70 80 80 80 80

27

39

50

72

77

30

29

40

52

74

79

35

33

44

55

78

82

35

22

31

40

58

62

25

23

32

41

60

63

25

26

35

44

62

66

30

22.5 kW

30 kW

4

4

80 90

100 110

4

4

80 90

100 110

4

4

90 100

110 125

45 kW 150 150

4

150 175

4

150 175

60 kW

4

150 175

15 kW

60

22.5 kW

72

60

81

4

150 175

64

75

64

84

4

150 175

70

83

70

92

30 kW

91 103 95 107 103 115

45 kW 130 148 134 152 142 160

60 kW 138 157 142 161 149 169

40

60

80

80

29

40

51

74

79

45

60

80

80

31

42

53

76

80

45

60

80

90

34

45

57

79

84

35

45

60

70

23

32

41

59

63

35

45

70

70

25

34

43

61

64

40

45

70

70

27

36

45

64

67

ELECTRICAL ACCESSORIES

Disconnect 15 kW 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56 54W56

22.5 kW 54W56 54W56 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56

30 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56

45 kW 54W57 54W57 54W57 54W57 54W57 54W57 54W56 54W56 54W56 54W56 54W56 54W56

60 kW

5

N/A

5

N/A

5

N/A

5

N/A

5

N/A

5

N/A 54W56 54W56 54W57 54W56 54W56 54W56

NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.

1

Extremes of operating range are plus and minus 10% of line voltage.

2

HACR type breaker or fuse.

3

Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

4

Factory installed circuit breaker not available.

5

Disconnect must be field furnished.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 32

ELECTRIC HEAT CAPACITIES

Volts

Input kW

Input

7.5 kW

Btuh

Output

No. of

Stages kW

Input

15 kW

Btuh

Output

No. of

Stages kW

Input

22.5 kW

Btuh

Output

No. of

Stages kW

Input

208 5.6 19,100

220 6.3 21,500

1

1

11.3 38,600

12.6 43,000

1

1

16.9 57,700

18.9 64,500

2

2

30 kW

Btuh

Output

22.5 76,800

25.2 86,000

No. of

Stages

2

2

kW

Input

45 kW

Btuh

Output

33.8 115,300

No. of

Stages

2

kW

Input

60 kW

Btuh

Output

No. of

Stages

45.0 153,600 2

37.8 129,000 2 50.4 172,000 2

230 6.9 23,600 1 13.8 47,100 1 20.7 70,700 2 27.5 93,900 2 41.3 141,000 2 55.1 188,000 2

240 7.5 25,600 1 15.0 51,200 1 22.5 76,800 2 30.0 102,400 2 45.0 153,600 2 60.0 204,800 2

440 6.9 21,500 1 12.6 43,000 1 18.9 64,500 2 25.2 86,000

460 6.9 23,600 1 13.8 47,100 1 20.7 70,700 2 27.5 93,900

2

2

37.8 129,000

41.3 141,000

2

2

50.4 172,000

55.1 188,000

2

2

480 7.5 25,600 1 15.0 51,200 1 22.5 76,800 2 30.0 102,400 2 45.0 153,600 2 60.0 204,800 2

550 6.3 21,500 1 12.6 43,000 1 18.9 64,500 2 25.2 86,000

575 6.9 23,600 1 13.8 47,100 1 20.7 70,700 2 27.5 93,900

2

2

37.8 129,000

41.3 141,000

2

2

50.4 172,000

55.1 188,000

2

2

600 7.5 25,600 1 15.0 51,200 1 22.5 76,800 2 30.0 102,400 2 45.0 153,600 2 60.0 204,800 2

UNIT CLEARANCES - INCHES (MM)

C

OPTIONAL

OUTDOOR

AIR HOOD

A

1

Unit Clearance

Service Clearance

Minimum Operation Clearance in.

60

36

A mm

1524

914

in.

36

36

B mm

914

914

NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.

1

Service Clearance - Required for removal of serviceable parts.

Minimum Operation Clearance - Required clearance for proper unit operation.

in.

36

36

C mm

934

914

in.

60

36

D mm

1524

914

Top

Clearance

Unobstructed

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 33

OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS - FIELD INSTALLED

COMMERCIAL TOUCHSCREEN THERMOSTAT

Intuitive Touchscreen Interface -

Two Stage Heating / Two Stage Cooling

Conventional or Heat Pump - Seven Day Programmable - Four Time Periods/

Day - Economizer Output - Title 24 Compliant - ENERGY STAR® Qualified -

Backlit Display - Automatic Changeover

C0STAT02AE1L

(14W81)

Sensors For Touchscreen Thermostat

1

Remote non-adjustable wall mount 20k temperature sensor .........................

1

Remote non-adjustable wall mount 10k averaging temperature sensor ........

1

Remote non-adjustable duct mount temperature sensor ...............................

Outdoor temperature sensor ............................................................................

C0SNZN01AE2-

(47W36)

C0SNZN73AE1-

(47W37)

C0SNDC00AE1-

(19L22)

C0SNSR03AE1-

(X4148)

Accessories For Touchscreen Thermostat

Locking cover (clear) ........................................................................................

C0MISC15AE1-

(39P21)

1

Remote sensors for C0STAT02AE1L can be applied in the following combinations: (1)

C0SNZN01AE1-, (2) C0SNZN73AE1-, (2) C0SNZN01AE1- and (1) C0SNZN73AE1-, (4)

C0SNZN01AE1-, (3) C0SNZN01AE1- and (2) C0SNZN73AE1.

DIGITAL NON-PROGRAMMABLE THERMOSTATS

Intuitive Interface - Automatic Changeover - Simple Up and Down Temperature Control

Two-stage heating / cooling conventional systems .......................................

C0STAT10AE1L

(13K98)

Sensor For Digital Non-Programmable Thermostats Above

Remote wall mounted temperature sensor.......................................................

C0SNZN00AE1-

(26K57)

Intuitive Interface - Automatic Changeover - Backlit Display - Simple Up and Down Temperature Control

One-stage heating / cooling conventional systems ..........................................

C0STAT12AE1L

(51M32)

Sensor For Digital Non-Programmable Thermostats Above

Outdoor temperature sensor ............................................................................

C0SNSR04AE1-

(X2658)

Accessories For Digital Non-Programmable Thermostats Above

Optional wall mounting plate ............................................................................

C0MISC17AE1-

(X2659)

OUTDOOR SOUND DATA

Unit

Model Number

092, 102 and 120

Octave Band Sound Power Levels dBA, re 10

-12

Watts Center Frequency - HZ

125

76

250

79

500

84

1000

83

2000

79

4000

73

8000

66

150 77 80 85

1

Note - The octave sound power data does not include tonal corrections.

Sound Rating Number according to AHRI Standard 370-2001.

84 79 74 66

1

Sound Rating

Number (dB)

88

88

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 34

WEIGHT DATA

Model Number

092 Base Unit

092 Max. Unit

102 Base Unit

102 Max. Unit

120 Base Unit

120 Max. Unit

150 Base Unit

150 Max. Unit

lbs.

1120

1277

1127

1284

1162

1326

1202

1366

Net kg

508

579

511

582

527

601

545

620

lbs.

1205

1362

1212

1369

1247

1411

1287

1451

Shipping kg

547

618

550

621

566

640

584

658

OPTIONS / ACCESSORIES

Description

CEILING DIFFUSERS

Step-Down

RTD11-95

RTD11-135

RTD11-185

Flush

FD11-95

FD11-135

FD11-185

Transitions

LASRT08/10

LASRT10/12

LASRT15

CONVENTIONAL FIN/TUBE CONDENSER COIL

Fin/Tube Condenser Coil

ECONOMIZER / OUTDOOR AIR / EXHAUST

lbs.

88

205

392

75

174

289

30

32

36

160

Economizer

Economizer Dampers

Barometric Relief Dampers (downflow)

Barometric Relief Damper Hood (downflow)

Outdoor Air Hood (downflow)

Outdoor Air Dampers

Outdoor Air Damper Section (downflow) - Automatic

Outdoor Air Damper Section (downflow) - Manual

Outdoor Air Damper Hood (downflow)

Power Exhaust

ELECTRIC HEAT

7.5 kW

15 kW

22.5 kW

30 kW

45 kW

60 kW

HUMIDITROL

®

Humiditrol 20

MSAV (MULTI-STAGE AIR VOLUME) SUPPLY AIR BLOWER OPTION

Variable Frequency Drive (VFD) and associated components

ROOF CURBS - CLIP CURB

10

50

50

57

57

59

68

55

8

25

23

9

2

9

31

Downflow

8 in. height

14 in. height

18 in. height

24 in. height

ROOF CURBS - STANDARD

Downflow

8 in. height

14 in. height

24 in. height

PACKAGING

LTL Packaging (less than truck load)

89

109

126

150

91

115

153

105

Shipping Weight kg

40

93

178

34

79

131

14

15

16

73

25

4

11

10

4

1

4

14

23

23

26

26

27

31

9

5

40

49

57

68

41

52

69

48

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 35

DIMENSIONS - INCHES (MM)

Model

No.

CORNER WEIGHTS

AA

Base Max.

Base

BB

Max.

Base

CC

Max.

Base

DD

Max.

CENTER OF GRAVITY

EE

Base Max.

Base

FF

Max.

lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm in. mm in. mm

092 281 127 327 148 252 114 286 130 275 125 306 139 312 142 358 162 46.5 1181 45.5 1156 24.5 622 25.5 648

102 282 128 329 149 254 115 287 130 276 125 308 139 314 143 360 163 46.5 1181 45.5 1156 24.5 622 25.5 648

120 294 133 340 154 264 120 297 135 283 128 318 144 321 146 372 169 46.5 1181 45.5 1156 24.5 622 25.5 648

150 304 138 350 159 273 124 306 139 293 133 327 148 332 151 383 174 46.5 1181 45.5 1156 24.5 622 25.5 648

Base Unit - The unit with NO INTERNAL OPTIONS.

Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external to unit or high static power exhaust.

AA

6-1/8

(156)

5-5/8

(143)

BOTTOM SUPPLY

AIR OPENING

BB

58-1/8

(1476)

6-1/8

(156)

60-1/8 (1527)

BASE

BOTTOM

POWER ENTRY

5-1/2 (140) Dia.

7 (178)

DD

24

(610)

10-3/4

(273)

20

(508)

28

(711)

27

(686)

CENTER OF

GRAVITY

BOTTOM RETURN

AIR OPENING

EE

FF

6-5/8

(168)

7 (178)

34-7/8

(886)

BOTTOM

CONDENSATE

OPTIONAL DISCONNECT

(FACTORY INSTALLED)

101-1/4

(2572)

TOP VIEW

BASE

99-1/4

(2521)

CC

60-1/8

(1527)

END VIEW

43-3/8

(1102)

46-7/8

(1191)

3-1/2

(89)

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 36

1

(25)

ELECTRIC

INLETS

15-1/2

(394)

6-1/8

(156)

CONDENSATE

DRAIN (FRONT)

5-3/8

(137)

46-7/8

(1191)

34-7/8

(886)

FORKLIFT SLOTS

(BOTH SIDES)

101-1/4

(2572)

SIDE VIEW

LIFTING HOLES

(FOR RIGGING)

15-1/2

(394)

HORIZONTAL

SUPPLY AIR

OPENING

HORIZONTAL

RETURN AIR

OPENING

1-5/8

(41)

30

(762)

12-1/8

(308)

CONDENSATE

DRAIN (BACK)

30

(762)

5-3/8

(137)

31-1/2

(800)

66-3/8

(1686)

SIDE VIEW

(Horizontal Openings)

ACCESSORY DIMENSIONS - INCHES (MM)

OUTDOOR AIR HOOD DETAIL

21−3/8

(543)

OUTDOOR AIR HOOD

(Furnished with Economizer or

Outdoor Air Damper)

EXHAUST AIR HOOD

(Furnished, Field Installed)

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 37

ACCESSORY DIMENSIONS - INCHES (MM)

HORIZONTAL ECONOMIZER APPLICATION

(with Optional Horizontal Barometric Relief Dampers and Horizontal Discharge Kit)

ECONOMIZER

DAMPERS

15-1/2

(394)

HORIZONTAL

BAROMETRIC RELIEF

DAMPERS AND HOOD

RETURN AIR

DUCT TRANSITION

(Field fabricated and installed on unit)

RETURN

AIR

INLET

RETURN AIR DUCT

(Field Fabricated - Must be sized to accommodate Horizontal Barometric Relief

Hood and Return Air Requirements)

HORIZONTAL RELIEF HOOD DIMENSIONS

Width - 31-5/8 in. (803 mm)

Height - 14-1/2 in. (368 mm)

SUPPLY AIR DUCT

(Field Provided)

SUPPLY

AIR

OUTLET

TOP VIEW

30

(762)

HORIZONTAL

SUPPLY AIR

OPENING

(On Unit)

38-3/4

(984)

This opening not used in

Horizontal

Applications with

Economizer

OUTDOOR AIR HOOD

(Furnished with Economizer)

21-3/8

(543)

HORIZONTAL BAROMETRIC

RELIEF DAMPERS

(Optional - Must be Ordered Extra and

Field Installed on Field fabricated

Return Air Duct)

OUTDOOR

AIR

4-1/8

(105)

HORIZONTAL

RETURN AIR

OPENING

EXHAUST

AIR

19-3/4

(502)

27-3/4

(705)

6-1/8

(156)

BACK VIEW

RETURN AIR

DUCT TRANSITION

(Field fabricated and installed on unit)

RETURN AIR DUCT INLET

(Field Fabricated - Must be sized to accommodate Horizontal Barometric

Relief Hood and Return Air Requirements)

OPTIONAL RETURN AIR OPENING

WITH ECONOMIZER AND HORIZONTAL

DISCHARGE KIT (required)

(Field Installed)

NOTE - Return Air Duct and Transition must be supported.

END VIEW

14-1/2

(368)

1

13

(300)

HORIZONTAL BAROMETRIC RELIEF DAMPERS

(Field installed in horizontal return air duct adjacent to unit)

31-5/8 (803)

1

29-1/2 (749)

6-1/2

(165)

FRONT VIEW SIDE VIEW

1

NOTE - Opening size required in return air duct.

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 38

ACCESSORY DIMENSIONS - INCHES (MM)

CLIP CURBS - DOUBLE DUCT OPENING

1-13/16

(46)

26-3/4

(679)

95-3/8

(2423)

8-1/2

(216)

29-3/4

(756)

91-3/4

(2330)

SUPPLY

OPENING

RETURN

OPENING

29-3/4

(756)

7-1/8

(181)

1-13/16

(46)

21-3/4

(552)

54-1/4

(1378)

50-5/8

(1286)

8 (203)

14 (356)

18 (457)

24 (610)

NOTE - Roof deck may be omitted within confines of curb.

DETAIL ROOF CURB

1-13/16

(46)

TYPICAL FLASHING DETAIL FOR ROOF CURB

BASE BOTTOM

PACKAGED

UNIT

FIBERGLASS

INSULATION

(Furnished)

NAILER STRIP

(Furnished)

ROOF CURB

(Extends around entire perimeter of unit)

RIGID INSULATION

(Field Supplied)

COUNTER FLASHING

(Field Supplied)

CANT STRIP

(Field Supplied)

ROOFING

MATERIAL

8 (203)

14 (356)

18 (457)

24 (610)

FACTORY INSTALLED

PERIMETER WOOD

NAILER STRIP

2 (51)

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 39

ACCESSORY DIMENSIONS - INCHES (MM)

STANDARD ROOF CURBS - DOUBLE DUCT OPENING

1-13/16

(46)

1-13/16

(46)

26-3/4

(679)

95-3/8

(2423)

8-1/2

(216)

29-3/4

(756)

91-3/4

(2330)

SUPPLY

OPENING

RETURN

OPENING

29-3/4

(756)

7-1/8

(181)

21-3/4

(552)

54-1/4

(1378)

50-5/8

(1286)

8 (203)

14 (356)

24 (610)

TYPICAL FLASHING DETAIL FOR ROOF CURB

BASE BOTTOM

PACKAGED

UNIT

FIBERGLASS

INSULATION

(Furnished)

NAILER STRIP

(Furnished)

ROOF CURB

(Extends around entire perimeter of unit)

RIGID INSULATION

(Field Supplied)

COUNTER FLASHING

(Field Supplied)

CANT STRIP

(Field Supplied)

ROOFING

MATERIAL

NOTE - Roof deck may be omitted within confines of curb.

DETAIL ROOF CURB

1-13/16

(46)

8 (203)

14 (356)

24 (610)

FACTORY INSTALLED

PERIMETER WOOD

NAILER STRIP

2 (51)

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 40

ACCESSORY DIMENSIONS - INCHES (MM)

ROOF CURBS WITH SUPPLY & RETURN AIR TRANSITIONS FOR CEILING DIFFUSERS

LASRT08/10 ROUND TRANSITIONS

(for 092 models with FD11−95, RTD11−95 Diffusers)

30

(762)

Typ.

1−1/2

(38)

31

(787)

8

(203)

2

(51)

RETURN

AIR

OPENING

SUPPLY

AIR

OPENING

20 IN. (508 mm)

Diameter

LASRT10/12 & LASRT15 RECTANGULAR TRANSITIONS

(for 102 thru 150 models with FD11−135−185, RTD11−135−185 Diffusers)

30

(762)

Typ.

1−1/2

(38)

31 (787)

LASRT10/12

39 (991)

LASRT15

8 (203)

2 (51)

27-3/4 (705)

LASRT10/12

35-3/4 (908)

LASRT15

17-3/4

(451)

30-1/2

(775)

4

(102)

30-1/2

(775)

TOP VIEW

31-1/2 (800)

LASRT08/10

LASRT10/12

39-1/2 (1003)

LASRT15

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 41

ACCESSORY DIMENSIONS - INCHES (MM)

COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS

STEP-DOWN CEILING DIFFUSER FLUSH CEILING DIFFUSER

G

E

F

G H

2 (51)

H

D

C

G

E

F

G

J

A

B

L

K

B

Model Number

A

B

E

F

C

D

G

H

J

K

L

Duct Size

in.

mm in.

mm in.

mm in.

mm in.

mm in.

mm in.

mm in.

mm in.

mm in.

mm in.

mm in.

mm

RTD11-95

47-5/8

1159

29-5/8

752

14-3/8

365

27-1/2

699

45-1/2

1158

22-1/2

572

11-1/2

292

13-3/4

349

45-1/2

1156

27-1/2

699

8-1/8

206

20 round

508 round

Model Number

A

B

E

F

C

D

G

H

Duct Size

in.

mm in.

mm in.

mm in.

mm in.

mm in.

mm in.

mm in.

mm in.

mm

A

H

2 (51)

H

D

C

FD11-95

47-5/8

1159

29-5/8

752

16-5/8

422

27

686

45

1143

22-1/2

572

11-1/4

286

13-1/2

343

20 round

508 round

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 42

ACCESSORY DIMENSIONS - INCHES (MM)

COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS

S T E P D O W N C E I L I N G D I F F U S E R F L U S H C E I L I N G D I F F U S E R

H

E

G

F

G

J

D

H

E

G

F

G

C

K

2 (51) 2 (51)

N

B

M

B

L

A

Model Number

A

B

C

D

E

F

G

H

J

K

L

M

N

in.

mm

Duct Size in.

mm in.

mm in.

mm mm in.

mm in.

mm mm in.

mm in.

mm in.

in.

mm in.

mm in.

mm in.

mm in.

1156

4-1/2

114

18

457

2-1/2

64

28

711

2-3/4

70

RTD11-135

47-5/8

1210

35-5/8

905

20-5/8

524

33-1/2

851

45-1/2

45-1/2

1156

33-1/2

851

9-1/8

232

18 x 28

457 x 711

1156

4-1/2

114

18

457

2-1/2

64

36

914

4-3/4

121

RTD11-185

47-5/8

1210

47-5/8

1210

24-5/8

625

45-1/2

1156

45-1/2

45-1/2

1156

45-1/2

1156

10-1/8

257

18 x 36

457 x 914

Model Number

A

in.

mm

B

in.

mm

C

D

in.

mm in.

mm

E

F

G

in.

mm

H

in.

mm in.

J

K

mm in.

mm

Duct Size in.

mm in.

mm in.

mm

FD11-135

47-5/8

1210

35-5/8

905

23-1/4

591

18

457

2-1/4

57

28

33

838

45

1143

4-1/2

114

711

2-1/2

64

18 x 28

457 x 711

J

D

C

K

A

FD11-185

47-5/8

1210

47-5/8

1210

29-1/4

743

18

457

2-1/4

57

36

45

1143

45

1143

4-1/2

114

914

4-1/2

114

18 x 36

457 x 914

Energence

®

Packaged Electric / Electric 7.5 to 12.5 Ton / Page 43

REVISIONS

Section

Blower Data

Electrical Data

Options / Accessories

Description

Updated wet coil air resistance.

Updated GFI data for 575V.

Updated GFI Service Outlets usage.

Visit us at www.lennox.com

For the latest technical information, www.lennoxcommercial.com

Contact us at 1-800-4-LENNOX

NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.

Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.

Installation and service must be performed by a qualified installer and servicing agency. ©2012 Lennox Industries, Inc.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement