Progress Lighting P8643-01 is a versatile outdoor wall lantern that combines classic design with energy-efficient LED technology. Crafted from durable cast aluminum with a handsome weathered zinc finish, this fixture is built to last and withstand the elements. Its clear seeded glass panels provide a warm and inviting glow, enhancing the curb appeal of your home. With its easy installation process and dusk-to-dawn photocell sensor that automatically turns the light on at dusk and off at dawn, the P8643-01 offers both convenience and energy savings.
advertisement
P.O. BOX 11846 TUCSON, AZ 85734 • 1301 E. WIEDING ROAD TUCSON, AZ 85706
(520) 294-3292 • FAX (520) 741-2837 w w w . i o t a e n g i n e e r i n g . c o m
I-42-EM-A
SERIES D
10W–42W RAPID START
4 PIN COMPACT LAMP
EMERGENCY LIGHTING EQUIPMENT
INSTRUCTION MANUAL
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.
CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2.
CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by disconnecting the unit connector.
3.
CAUTION – This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace the entire unit when necessary. The EPA certified RBRC ® Battery Recycling Seal indicates that IOTA
Engineering is voluntarily participating in an industry program to collect and recycle these batteries at the end of their useful life, when taken out of service in the United States or Canada. The RBRC program provides a convenient alternative to placing used Ni-Cad batteries into the trash or the municipal waste stream, which may be illegal in your area. Please call 1-800-822-8837 for information on Ni-Cad battery recycling and disposal bans/restrictions in your area. IOTA Engineering’s involvement in this program is part of our commitment to preserving our environment and conserving our natural resources.
4.
DO NOT USE OUTDOORS. The I-42-EM-A is for use with grounded, UL Listed, indoor fixtures except in heated air outlets or hazardous locations.
5.
The I-42-EM-A requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C. lead.
6.
Do not mount near gas or electric heaters.
7.
The I-42-EM-A should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
8.
The I-42-EM-A will cold strike and operate one 10W through 42W, or two 10W through 26W, 4 pin Rapid
Start compact fluorescent lamps. Contact customer service for additional lamp usage.
9.
The I-42-EM-A is compatible with most electronic A.C. ballasts (including multiple lamps) as follows:
Electronic ballasts – one or two lamp emergency operation.
10.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
11.
Do not use this equipment for other than intended use.
12.
Install in accordance with the National Electrical Code and local regulations.
13.
Installation and servicing should be performed by qualified personnel.
14.
Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before final installation.
SAVE THESE INSTRUCTIONS
C
R
U
L
US LISTED
INSTALLATION INSTRUCTIONS
CAUTION: Before installing, make certain the A.C. power is off and the
I-42-EM-A unit connector is disconnected.
1. LAMPS OPERATED
Refer to the chart below for the type of lamp(s) operated and the number of lamps to be operated in the emergency mode.
If you have any questions regarding specific lamps, contact customer service.
O P T
1
2
3
4
I O N
1
1
1
0
8
L
4
A
W
2
0 W
W
-
-
M
3
W
1
2
P
2
6
W
3 W
W
C
C
T o o
Y m m
P p p
E a a c c t t
E M E R G E N C Y
O P E R A T I O N
O n e L a m p
O
T
T n w w e o o
L
L
L a a a m m m p p p
D
D i i
C s
V
L o
C o
I O
E n n s c o c o
L
A n n
E
D e c n n e c t t
T
S n n e c e c e t d e d e d t e d
W I R I N G
D I A G
1
1
R A M S
3
3
, 2
, 2
The 6
″
violet leads provide the lamp selection option. The unit is shipped from the factory with the leads disconnected and capped.
2. MOUNTING THE I-42-EM-A
When used with ceiling mounted downlight fixtures, the I-42-EM-A should be mounted on the fixture above the ceiling. The flex conduit marked “A” should be wired into the ballast/lamp compartment or to an electrical junction box on the fixture which allows access to the ballast/lamp connections. Refer to Illustration 1 for typical mounting.
When battery packs are remote mounted, the remote distance can not exceed ½ of the distance from ballast to lamp specified by the A.C. ballast manufacturer. For example, if the A.C. ballast manufacturer recommends no more than 25
′
remote distance, then the battery pack should not exceed 12½
′
. Under no circumstances should the battery pack exceed a distance of 50
′
from the lamp.
Illustration 1
Downlight Fixture
I-42-EM-A
FLEX “A”
A.C. BALLAST &
LAMP SOCKET COMPARTMENT
FLEX “B”
JUNCTION
BOX
SWITCH BOX
CEILING
TILE
TEST SWITCH
CHARGE LIGHT
INSURE WIRING IS IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS.
Page 2
3. MOUNTING THE TEST SWITCH AND CHARGE INDICATOR LIGHT
Cut the single gang switch box into the ceiling tile adjacent to the fixture within reach of the I-42-EM-A flex marked “B”. After mounting the switch box, connect flex “B” to the box and route all leads inside the box. Refer to Illustration 1 for typical mounting.
4. WIRING
A. The I-42-EM-A and A.C. ballast must be on the same branch circuit.
B. The I-42-EM-A requires an unswitched A.C. power source of either 120 or 277 volts; therefore, when used with switched fixtures, the I-42-EM-A input must be wired ahead of the switch.
C. Refer to the wiring diagrams on the back page for the proper wiring. For wiring diagrams of ballasts not shown, consult our customer service.
5. LABELS
Attach the appropriate labels adjacent to the Test Switch and Charge Indicator. Annotate Re-lamping label for lamp type and wattage. The Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone attempting to service the fixture.
6. COMPLETING INSTALLATION
When the installation is complete, switch the A.C. power on and join the I-42-EM-A unit connector.
OPERATION
General – This unit is primarily designed to be used with compact fluorescent lamp downlight fixtures. It will wire in conjunction with the existing A.C. ballast(s) and lamp(s) to provide the emergency function. It can also be wired for emergency only operation. The Test Switch and Charge Indicator light are offered in a standard single gang switch box for installation adjacent to the fixture.
Normal Mode – A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended. The I-42-EM-A is in the standby charging mode. The Charge Indicator will be lit providing a visual indication that the battery is being charged.
Emergency Mode – The A.C. power fails. The I-42-EM-A senses the A.C. power failure and automatically switches to the Emergency Mode. One lamp or two lamps are illuminated, at reduced output, for a minimum of 90 minutes. When the
A.C. power is restored, the I-42-EM-A switches the system back to the Normal Mode and resumes battery charging.
See page 1 of the Instruction Manual.
TESTING & MAINTENANCE
Pressing the Test Switch turns off the light on the Charge Indicator and forces the unit into emergency mode, interrupting power to the designated A.C. ballast. The emergency lamp is now being lit by the I-42-EM-A unit. After releasing the
Test Switch, the fixture returns to normal operation after a momentary delay. To simulate a “BLACK OUT” use the wall switch or circuit breaker to turn off A.C. power.
Initial Testing – Allow the unit to charge approximately 1 hour, then conduct a short discharge test by depressing the test switch. The Charge Indicator light will go out and the fluorescent tube will be illuminated. When the I-42-EM-A is used in fixtures with more than one A.C. ballast, the second A.C. ballast is NOT de-energized with the test switch. It may, therefore, be advisable to switch the A.C. fixture power off prior to depressing the test switch. Allow a 24 hour charge before conducting a one hour test.
The I-42-EM-A is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life Safety
Code, outlines the following schedule:
Monthly – Insure that the Charge Indicator light is illuminated. Conduct a 30 second discharge test by depressing the
Test Switch. One lamp should operate at reduced output.
Annually – Insure that the Charge Indicator light is illuminated. Conduct a full 1½ hour discharge test. The unit should operate as intended for the duration of the test.
“Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.
Consult Customer Service or visit www.iotaengineering.com for current warranty information.
Page 3
TYPICAL WIRING DIAGRAMS
Use in conjunction with Rapid Start ballasts and 4 pin lamps only.
1. ONE LAMP RAPID START BALLAST
UNSWITCHED
LINE
COMMON
SWITCHED OR
UNSWITCHED
LINE
WHITE
BLACK
ONE LAMP
A.C.
BALLAST
BLK (120V)
ORG (277V)
WHITE
WHT/BLK
TEST
SWITCH
➀
BLUE
BLUE
RED
RED
*LAMP
*A.C./EMERGENCY LAMP
WHITE
WHT/BLK
FLEX A
BLUE
BLU/WHT
YELLOW
RED/WHT
RED
EMERGENCY
I-42-EM-A
BALLAST
FLEX B
VIOLET
VIOLET
➁
RED OR RED/BLK (+)
➃
WHT/RED
WHT/BLK
WHT/BLK
➂
CHARGE
INDICATOR
UNIT CONNECTOR
➀
➁
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
LAMP SELECTOR LEADS. REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER APPLICATION.
➂
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
➃
TEST ACCESSORY LEAD—REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POSITIVE LEAD WIRING.
2. TWO LAMP RAPID START BALLAST WITH ONE LAMP EMERGENCY OPERATION
UNSWITCHED
LINE
COMMON
SWITCHED OR
UNSWITCHED
LINE
WHITE
BLACK
TWO LAMP
A.C.
BALLAST
BLUE
BLUE
RED
RED
YEL
YEL
LAMP
BLK (120V)
ORG (277V)
WHITE
WHT/BLK
TEST
SWITCH
➀
*LAMP
WHITE
WHT/BLK
FLEX A
BLUE
BLU/WHT
YELLOW
RED/WHT
RED
*A.C./EMERGENCY LAMP
EMERGENCY
I-42-EM-A
BALLAST
FLEX B
VIOLET
VIOLET
➁
RED OR RED/BLK (+)
➃
WHT/RED
WHT/BLK
WHT/BLK
CHARGE
INDICATOR
➂
UNIT CONNECTOR
➀
➁
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
LAMP SELECTOR LEADS. REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER APPLICATION.
➂
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
➃
TEST ACCESSORY LEAD—REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POSITIVE LEAD WIRING.
3. TWO LAMP RAPID START BALLAST WITH TWO LAMP EMERGENCY OPERATION
UNSWITCHED
LINE
COMMON
SWITCHED OR
UNSWITCHED
LINE
WHITE
BLACK
TWO LAMP
A.C.
BALLAST
BLUE
BLUE
RED
RED
YEL
YEL
*LAMP
BLK (120V)
ORG (277V)
WHITE
WHT/BLK
TEST
SWITCH
➀
*LAMP
WHITE
WHT/BLK
FLEX A
BLUE
BLU/WHT
YELLOW
RED/WHT
RED
*A.C./EMERGENCY LAMP
EMERGENCY
I-42-EM-A
BALLAST
FLEX B
VIOLET
VIOLET
➁
RED OR RED/BLK (+)
➃
WHT/RED
WHT/BLK
WHT/BLK
CHARGE
INDICATOR
➂
UNIT CONNECTOR
➀
➁
SELECT PROPER VOLTAGE LEAD. CAP UNUSED LEAD.
LAMP SELECTOR LEADS. REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER APPLICATION.
➂
DO NOT MATE CONNECTOR UNTIL INSTALLATION
IS COMPLETE AND A.C. POWER IS SUPPLIED.
➃
TEST ACCESSORY LEAD—REFER TO INSTALLATION
INSTRUCTIONS FOR PROPER POSITIVE LEAD WIRING.
Rev. 112204
68442-102
Page 4