NX-series Safety Controller Ethernet Stand-alone System

NX-series Safety Controller Ethernet Stand-alone System
NX-series Safety Controller
Stand-alone System
Ethernet
Directly connects to any PLC for monitoring and status
2 | NX Series Safety Controller
The safety solution for any application
The NX Stand-alone Safety Controller is a powerful and robust Safety System that reaches the
Safety
PLe according to EN 13849-1 and SIL3 according to IEC 61508. The EtherNet/IP coupler unit
ISO 13849-1, Cat.4/PLe
IEC 61508 SIL3
EN 62061 SIL3
allows for connection to almost any PLC via EtherNet/IP™ or standard Ethernet communications.
The flexible hardware allows the NX safety I/O units to be mixed in any combination with
standard NX I/O units.
Sysmac Studio software allows for configuration, programming,
PLC
simulation and monitoring functionality.
IEC 61131-2
IEC 61131-3
PLCopen® FBD
SSafety
affety
inputs
Ethernet
SSafety
afetty
outputs
outp
puts
Scalability
The system allows up to 63
safety/standard I/O units per
coupler; up to 32 safety I/O units to
a maximum of 256 safety I/O signals.
Configure systems with the right
combination of I/O to optimize cost.
Versatility
Maintainability
The EtherNet/IP coupler unit
enables connections with various
EtherNet/IP and standard Ethernet
devices. You can monitor safety
status and control standard I/O via
the connected PLC.
Detachable screwless
terminal block
The detachable terminal block of
the I/O unit simplifies the
commissioning and maintenance
tasks. Screwless push-in
connections speed up installation.
Connectivity
The stand-alone system eliminates
the need for dedicated controllers
for safety input devices and allows
for direct connection of safety input
devices.
ACR (Automatic Configuration
Restart)
FROM
TO
Safety
Controller
Intermediate Controller
Direct Connection
When replacing a safety I/O Unit,
just remove the old unit and insert a
new unit. The setting data is
automatically downloaded without
using the programming software.
| 3
Flexibility and reusability of programming code
Standard programming with Sysmac Studio
Sysmac Studio is compliant to the IEC 61131-3 standard
and utilizes PLCopen® function blocks.
The safety controller provides a large program capacity of
512 KB (equivalent to more than 1,000 function blocks),
visual setting of IO and automatic generating wiring
diagram,variable style programming, reusable
user-defined function blocks, offline simulation and
simple automatic test.
Visual setting of IO and automatic generating
wiring diagram
Programming with variables
By drag&drop the visual icon, the settings of I/Os are completed.
Wiring diagrams are also automatically generated based on
terminal settings. The wiring diagrams can be used for wiring
check and Technical Construction Files (TCF).
Unlike previous programming with physical addresses,
programming with variables does not depend on the hardware
configuration. You can use the same code for the machine with a
different hardware configuration by flexibly changing connections
between variable names and hardware memoryy addresses.
User-defined function blocks
Offline simulation and simple automatic test
You can define your own function blocks. Repeat use of
user-defined function blocks cuts programming time and
maintains consistency of quality. Secure the code with password
protection and add user-defined help files to make re-using
functions safe and easy.
You can check operation on the Simulator without physical devices.
Furthermore, basing on the relationship between inputs and
outputs, program can be tested automatically.
This significantly reduces program modification and debugging
time.
Emergency stop
circuit system
Safety guard system
Robot control system
Sysmac is a trademark or registered trademark of OMRON Corporation in Japan and other countries for OMRON factory automation products.
STI is a trademark or registered trademark of OMRON Corporation in Japan and other countries. EtherNet/IP™ is a trademark of ODVA.
Other company names and product names in this document are the trademarks or registered trademarks of their respective companies.
The product photographs and figures that are used in this catalog may vary somewhat from the actual products. Microsoft product screen shot(s)
reprinted with permission from Microsoft Corporation.
System configuration
NX-series EtherNet/IP Coupler Unit
NX-series
Safety I/O Units: - up to 32 units
NX Unit power consumption
Maximum I/O power supply current
Model
1.60 W max.
10A
NX-EIC202
NX-series
Safety CPU Units: - 1 unit
Accessary: End cover
Safety CPU Unit
NX-series
Coupler Units: - 1 unit
Maximum number of
safety I/O points
Program
capacity
Number of safety
master connections
Model
256
512KB
32
NX-SL3300
Safety Input Unit
Rated input
voltage
Number of
safety input points
Number of
test output points
4 points
2 points
24 VDC
8 points
2 points
24 VDC
OMRON special
safety input devices
Model
Can be connected
NX-SIH400
Cannot be connected NX-SID800
Safety Output Unit
NX-series
Standard I/O Units (Analog,Digital) *
End cover- 1 unit
* For details refer to Sysmac Catalog
Number of safety
output points
Internal
I/O
common
Rated input
voltage
Maximum load
current
Model
2 points
Sourcing
outputs(PNP)
24 VDC
2.0 A/point
NX-SOH200
4 points
Sourcing
outputs(PNP)
24 VDC
0.5 A/point and
2.0 A/Unit
NX-SOD400
Automation Software Sysmac Studio
Licenses and DVDs are ordered separately.
Product name
Specifications
Sysmac Studio
NX-I/O Edition
Ver.1.
*
Sysmac Studio NX-I/O Edition is a limited license that provides selected functions
required for EtherNet/IP Coupler settings.This product is a license only. You need the
Sysmac Studio Standard Edition DVD media to install it.
Sysmac Studio
Standard Edition
Ver.1.
The Sysmac Studio is the software that provides an integrated environment for setting,
programming, debugging and maintenance of machine automation controllers
including the NJ/NX-series, EtherCat Slave, and the HMI.*
Sysmac Studio runs on the following OS.
Windows XP (Service Pack 3 or higher, 32-bit version)/Windows Vista(32-bit
version)/Windows 7(32-bit/64-bit version)/Windows 8(32-bit/64-bit version)/Windows
8.1(32-bit/64-bit version)/Windows 10(32-bit/64-bit version)
* The Sysmac Studio Standard Edition license (SYSMAC-SE
OMRON Corporation
Number of licenses
Media
1 license
(Media only)
Model
SYSMAC-NE001L
DVD
SYSMAC-SE200D
L) includes functions that the NX-I/O Edition (SYSMAC-NE001L) provides.
Industrial Automation Company
Authorized Distributor:
Kyoto, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2016 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
CSM_1_1_1602
Cat. No. F100-E1-01
0316(0316)
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement