Powerware® 9155 Single-phase UPS
Powerware 9355 Three-phase UPS
Product Focus
Powerful. Intelligent. Elegant.
Reliability and efficiency have
never looked so attractive.
8–15 kVA
Product Introduction
Product Snapshot
Technology:
9155: Split-phase double-conversion
online UPS
9355: Three-phase double-conversion
online UPS
Power Rating:
9155: 8 kVA, 10 kVA, 12 kVA, 15 kVA
at 0.9 power factor
9355: 10 kVA and 15 kVA
at 0.9 power factor
Input Voltage:
9155: 200–240 Vac with Neutral or with
optional input isolation transformer
9355: 208V/120V or 220V/127V
Output Voltage:
9155: 100/200, 110/220, 120/240 Vac
180° phase displacement; 120/208,
127/220 Vac 120° phase displacement
9355: 208V/120V or 220V/127V
480:120V/208V or 600:120/208 with
input isolation transformer
(at 60 Hz only)
Frequency:
50/60 Hz auto-sensing
Dimensions:
Two-high configuration:
32.2” H x 12.0” W x 32” D
Three-high configuration:
47.8” H x 12.0” W x 33.5” D
Configuration:
Battery Backup:
Small-footprint tower, black
9155: Up to 29 minutes typical, extendable
up to four hours
9355: Up to 22 minutes typical, extendable
up to three hours
See Battery Back-up Times chart
Features
• Protects connected equipment from all nine of the most
common power problems with true online, double-conversion
topology
• Delivers maximum power density in a compact tower
design, only 12” wide and 33” deep, including batteries
• Provides more real wattage in less space with a 0.9 power
factor—protecting more equipment for every utility dollar,
and leaving more room for expansion
• Delivers extra capacity or redundancy through patented
Powerware Hot Sync® paralleling of multiple modules
• Significantly increases battery life through microprocessorcontrolled ABM® technology
• Provides 0.99 power factor and generator friendly <5% total
harmonic distortion using an active IGBT rectifier to control the
input power factor
• Ensures data and system integrity with complete power management software for remote monitoring, management, and
shutdown
• Provides investment protection and peace of mind with an
Eaton factory limited warranty, technical support, and optional
service plans
With advances in miniaturization and processing power, a single
rack of equipment demands more power than ever—and more
equipment will be served by dual cord power supplies. It’s a challenge to provide power protection for expanding loads in shrinking spaces.
Fortunately, technology advancements have also raised the density per square foot of power protection systems. The Powerware
9155 and new Powerware 9355 uninterruptible power systems
(UPSs) deliver premium levels of efficiency, reliability and flexibility—all in a sleek tower half the size of most competitor units on
the market today.
These double-conversion, online UPSs resolve all nine common
utility power problems and supply clean, continuous power to
all connected equipment. Even when presented with the most
severe power problems, power output remains stable. And if the
utility power goes out altogether, there is no delay transferring to
backup power.
These capabilities make the Powerware 9155 and Powerware
9355 ideal for protecting essential data center, communications
and electrical engineering infrastructures in corporate, telecom,
healthcare, banking, public sector and industrial applications.
Powerware 9155/Powerware 9355 shown in perspective.
Premium power protection is now easier than ever.
With raised-floor real estate at a premium, you will appreciate that
these UPSs are only 12” wide and 33” deep, including internal batteries. With such a small footprint, you have more location options,
and more space is available for future expansion.
Equipment installation is easy, essentially plug-and-play. You can
order either UPS with your choice of output receptacles with more
than 17 types. To change or move data center equipment, you simply unplug from the old receptacle, plug into a new one, and go.
No need for an electrician to run new conduit and wiring.
Scalable architecture meets current and future load
requirements.
Powerware 9155 UPSs are available in four models (8, 10, 12, and 15
kVA). Powerware 9355 UPSs come in 10 and 15 kVA models, so you
can choose the configuration that most closely meets your capacity
requirements and price point.
Powerware 9355 rear view with
optional output receptacles
And you can scale from there. Using our signature Powerware Hot
Sync paralleling technology, up to three (Powerware 9155) or up to
four (Powerware 9355) equivalent UPS modules can be paralleled
for extra capacity or redundancy. A 15 kVA UPS, for example, can
grow to support loads of up to 45 kVA. There’s no dependence on
communications wiring among those UPS modules.
Battery innovations optimize battery performance and
service life.
Standard internal batteries provide power until auxiliary power takes
over or systems are gracefully shut down. Battery runtime can be
extended to hours by adding matching Extended Battery Modules
(EBMs).
POWERWARE UPS BACKUP TIMES (IN MINUTES)
VA
15000
14500
14000
13500
13000
12500
12000
11500
11000
10500
10000
9500
9000
8500
8000
7500
7000
6500
6000
5500
5000
4500
4000
3500
3000
2500
Watt
13500
13050
12600
12150
11700
11250
10800
10350
9900
9450
9000
8550
8100
7650
7200
6750
6300
5850
5400
4950
4500
4050
3600
3150
2700
2250
UPS
(1)
+ Internal EBM
32 Battery
64
4.6
23.0
4.9
24.1
5.2
25.2
5.5
26.4
5.8
27.6
6.1
28.8
6.5
30.2
6.9
31.6
7.3
33.3
7.8
35.1
8.4
37.2
9.1
39.6
9.9
42.3
10.8
45.5
11.9
49.1
13.1
53.2
14.6
58.0
16.3
63.5
18.4
70.0
20.1
77.6
22.4
86.6
25.2
97.4
28.6
110
32.8
127
38.3
148
45.6
176
(2)
EBM
64
43.0
45.2
47.3
49.4
51.6
54.0
56.5
59.3
62.4
65.9
69.8
74.2
79.4
85.2
91.9
99.7
109
119
131
145
162
182
207
238
277
329
(3)
EBM
64
65.1
68.3
71.5
74.7
78.1
81.6
85.5
89.7
94.4
99.6
106
112
120
129
139
151
164
180
198
220
245
276
313
359
418
-
(4)
UPS
(1)
EBM + Internal EBM
64 64 Battery 96
88.6
13.3
43.0
93.0
14.1
45.2
97.4
14.9
47.3
102
15.8
49.4
106
16.7
51.6
111
17.6
54.0
116
18.6
56.5
122
19.2
59.3
129
20.2
62.4
136
21.4
65.9
144
22.6
69.8
153
24.1
74.2
163
25.7
79.4
175
27.6
85.2
189
29.8
91.9
205
32.3
99.7
224
35.2
109
245
38.6
119
270
42.5
131
300
47.2
145
334
52.6
162
376
59.2
182
426
67.1
207
77.0
238
89.7
277
107
329
(2)
EBM
96
76.7
80.5
84.2
88.1
92.0
96.2
101
106
111
117
124
132
141
152
164
178
194
212
234
259
289
325
369
423
-
(3)
EBM
96
113
119
125
130
136
142
149
156
164
174
184
196
209
225
242
263
286
314
346
383
428
-
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Front view
Rear view
After 15 years of in-service experience, Eaton
has real-world proof that ABM technology
can significantly increase battery service life.
Powerware 9155/Powerware 9355 EBM
Powerware 9155 and Powerware 9355 UPSs also use sophisticated
technologies that maximize the health and service life of batteries:
• ABM technology uses a unique three-stage charging technique that
significantly extends battery service life and optimizes recharge
time, compared to traditional trickle charging.
• Temperature-compensated charging monitors battery temperature
and adjusts the charge rate accordingly, which properly charges
the battery and greatly extends battery life.
• An integrated battery management system tests and monitors battery health and remaining lifetime, and provides advance notification to guide preventive maintenance.
Unlike heavy, old-style batteries, Eaton's are easily field-replaceable.
One person, working alone, can replace a battery without disrupting
data center operations or power to protected equipment.
Advanced design delivers unequaled power
performance.
The innovative design of these UPSs deliver the industry’s best performance combination of efficiency, input current distortion, input
power factor, and output power factor.
Lower costs, lower temperatures. High efficiency (greater than 90
percent across all load ranges) reduces utility costs, extends battery
runtimes, and produces cooler operating conditions.
Generator-friendly design. Total input harmonic distortion (THD)
remains below five percent without compromising overall efficiency. The result is maximum transfer of power between source
and protected load, and exceptional compatibility with auxiliary
generators.
More real power. On the output side, high power factor enables
these UPSs to provide their full power capability to modern IT
equipment that may have a wide range of leading and lagging
power factors. And, with a 0.99 input power factor, these UPSs
avoid the disturbances that energy converters tend to cause.
Inside view of Powerware 9155
Parallel Cabinet
Powerware Hot Sync Redundant/Capacity
Powerware 9155 UPS
Parallel Cabinet
Load
Protect your investment
Rest easy, knowing that your UPS is always on
the job.
While it protects your critical systems, the UPS itself is protected in
several ways:
Self-diagnosis. The UPS constantly monitors its own operation, such
as voltage, temperature or function of internal elements—and sends
alarms or takes action if it detects a potential problem. You’ll know
your UPS is always performing up to specifications to protect your
equipment.
Self-correction. If it senses an issue—planned or unplanned—the
UPS instantly transfers the power path to a bypass source, with zero
interruption in power. When the alarm condition passes, the UPS
automatically reverts from bypass to normal operation.
Remote monitoring. You can have Eaton specialists securely monitor your Powerware 9155 and Powerware 9355 UPSs around the
clock with eNotify service, or you can monitor your own UPSs over
your LAN or the Internet. Either way, you’ll always be informed
about conditions in your power protection infrastructure.
Redundancy. Using Powerware Hot Sync technology, you can
configure up to N+3 redundancy. Any module can serve as backup
for any other, with no interruption or downtime. For instance, you
could perform full maintenance on any UPS without having to
remove any loads from conditioned power.
Most other paralleling systems on the market use a top-down configuration; if the master fails, the subsidiary units fail. With Eaton’s
patented approach, each UPS module is independent yet synchronized with the others. There is no single point of failure.
Connectivity options offer maximum flexibility.
The standard unit is equipped with an RS-232 serial port to communicate with power management software. You can customize your
UPS by adding one or two interface cards for other applications:
Monitor the UPS from anywhere. Connect the UPS to the Ethernet
network and Internet for secure monitoring and management using
a standard Web browser or SNMP.
ConnectUPSTM Web/SNMP Card
Interwork with your existing Building Management System.
A Modbus® Card enables real-time monitoring of UPS systems
through a Building Management System or Industrial Automation
System.
Modbus Card
Gather information from relay contact devices. Provide a dry-contact interface between the UPS and any relay-connected device,
including the IBM® e-server® iSeries and a variety of industrial
applications.
Relay Interface Card
Have central control and visibility of UPS systems.
The Powerware 9155 and Powerware 9355 are shipped with a CD
that includes Powerware LanSafeTM power management software
and a 30-day trial version of Powerware PowerVision® UPS performance analysis and monitoring software. Using an intuitive, graphical interface and SNMP (Simple Network Management Protocol),
administrators can:
Independently manage diverse servers. A Multi-Server card enables
up to six serially connected devices of mixed operating systems to
be independently managed and controlled by a single UPS.
Multi-Server Card
Powerware Software
Suite
• Securely monitor UPS and battery performance over your existing
Ethernet network and the Internet.
• Establish prioritized shutdown of network devices and client/server applications.
• Test all networked UPS systems from one node.
• Analyze trends and network conditions.
• Stay informed of potential power problems by pager and e-mail.
Monitor environmental conditions. An optional Environmental
Monitoring Probe remotely monitors temperature, humidity, and
two user-supplied contacts/sensors, such as smoke and intrusion
detection.
Environmental
Monitoring Probe
Gain peace of mind with industry-leading warranty
and service plans.
all-inclusive packages with unique features, such as advanced
remote monitoring with trending, customized capacity planning
reports, and power protection audits. Add your choice of guaranteed
response times, and you can tailor just the right support package for
your needs.
We are so confident about the performance and reliability of the
Powerware 9155 and Powerware 9355 UPSs and battery systems
that we back them with extensive warranty and service plans.
Warranty coverage. Gain the peace of mind that comes with factory
warranty coverage (parts and labor, UPS and batteries) and rapid
response from certified support engineers.
Powerware 9155
• 2 year limited factory warranty
• 10 year pro-rated warranty
• $250,000 load protection guarantee
From Eaton—a global leader in power quality solutions.
The culmination of 40 years of R&D excellence, the Powerware 9155
and Powerware 9355 UPSs deliver confidence, and ensure that your
organization’s critical electronics are protected by the most reliable,
efficient, and full-featured protection available.
Eaton is a global leader in power quality and management solutions—the #1 manufacturer of UPSs above 5000 VA (Frost & Sullivan:
World UPS Markets, 2004). Eaton’s Power Quality Solutions Operation
is headquartered in Raleigh, North Carolina, U.S.
Powerware 9355
• 1 year Service Protection Plan
• 7 x 24 emergency response
• On-site start-up support (8 hours/day, 5 days/week)
• 3 year battery warranty
• 1 year eNotify remote monitoring
For more information on the Powerware 9155 and the new
Powerware 9355 UPS:
www.powerware.com
1-800-356-5794
Service plans. Beyond the warranty period, service plans are available to match any need—from basic UPS and/or battery support to
Powerware 9155 and Powerware 9355 at-a-glance
MODEL SELECTION TABLE - POWERWARE 9155 UPS (8–15 kVA)
Order Number1
K408110000
K408120000
K408130000
K410110000
K410120000
K410130000
K412110000
K412120000
K412130000
K415110000
K415120000
K415130000
Description
PW9155 Model 8 - 32 Battery (2-high)
PW9155 Model 8 - 64 Battery (3-high)
PW9155 Model 8 - 32 Battery with Transformer (3-high)
PW9155 Model 10 - 32 Battery (2- high)
PW9155 Model 10 - 64 Battery (3- high)
PW9155 Model 10 - 32 Battery with Transformer (3-high)
PW9155 Model 12 - 32 Battery (2-high)
PW9155 Model 12 - 64 Battery (3-high)
PW9155 Model 12 - 32 Battery with Transformer (3-high)
PW9155 Model 15 - 32 Battery (2- high)
PW9155 Model 15 - 64 Battery (3- high)
PW9155 Model 15 - 32 Battery with Transformer. (3- high)
Power
Rating2
(kVA/W)
8kVA / 7.2kW
8kVA / 7.2kW
8kVA / 7.2kW
10kVA / 9kW
10kVA / 9kW
10kVA / 9kW
12kVA / 10.8kW
12kVA / 10.8kW
12kVA / 10.8kW
15kVA / 13.5kW
15kVA / 13.5kW
15kVA / 13.5kW
Input & Output
Connection4
Hardwired
Hardwired
Hardwired
Hardwired
Hardwired
Hardwired
Hardwired
Hardwired
Hardwired
Hardwired
Hardwired
Hardwired
Output
Receptacles
See PDM chart
See PDM chart
See PDM chart
See PDM chart
See PDM chart
See PDM chart
See PDM chart
See PDM chart
See PDM chart
See PDM chart
See PDM chart
See PDM chart
Dimensions
H x W x D (in)
32.2 x 12.0 x 32.0
47.8 x 12.0 x 32.0
47.8 x 12.0 x 32.0
32.2 x 12.0 x 32.0
47.8 x 12.0 x 32.0
47.8 x 12.0 x 32.0
32.2 x 12.0 x 32.0
47.8 x 12.0 x 32.0
47.8 x 12.0 x 32.0
32.2 x 12.0 x 32.0
47.8 x 12.0 x 32.0
47.8 x 12.0 x 32.0
Unit
Weight3
(lb)
352
590
558
352
590
558
352
590
558
352
590
558
1. 50/60 Hz auto-sensing. All models can be used for frequency/phase conversion with derated 80% load, please refer to manual for details.
2. Input voltage 200–240V with neutral or with optional input isolation transformer. Output voltages are user-selectable 100/200, 110/220, 120/240 Vac 180° phase displacement, or 120/208, 127/220 Vac 120° phase displacement.
3. Weight is installed weight, add 47lbs (2-high models) or 50lbs (3-high models) to determine shipping weight.
4. An input neutral is required for all configurations unless the input isolation transformer is used.
MODEL SELECTION TABLE - POWERWARE 9355 UPS (10–15 kVA)
Order Number1
KA1011100000010
KA1012100000010
KA1011200000010
KA1012200000010
KA1011400000010
KA1011600000010
KA1511100000010
KA1512100000010
KA1511200000010
KA1512200000010
KA1511400000010
KA1511600000010
Description
PW9355 with 32-Battery (2-high)
PW9355 with 64-Battery (3-high)
PW9355 with 32-Battery (2-high)
PW9355 with 64-Battery (3-high)
PW9355 with 32-Battery with Transformer (3-high)
PW9355 with 32-Battery with Transformer (3-high)
PW9355 with 32-Battery (2-high)
PW9355 with 64-Battery (3-high)
PW9355 with 32-Battery (2-high)
PW9355 with 64-Battery (3-high)
PW9355 with 32-Battery with Transformer (3-high)
PW9355 with 32-Battery with Transformer (3-high)
Power
Input & Output
Rating2
(kVA/W)
Voltages4
10 kVA / 9kW
208/208
10 kVA / 9kW
208/208
10 kVA / 9kW
220/2202
10 kVA / 9kW
220/2202
10 kVA / 9kW
480/208
10 kVA / 9kW
600/208
15 kVA / 13.5kW
208/208
15 kVA / 13.5kW
208/208
15 kVA / 13.5kW
220/2202
15 kVA / 13.5kW
220/2202
15 kVA / 13.5kW
480/208
15 kVA / 13.5kW
600/208
1. 50/60 Hz auto-sensing.
2. 220V units are wye connected 220/127V input and 220/127V output, 3-phase, 4-wire plus ground.
3. Weight is installed weight, add 47 pounds (for 2-high models) or 50 pounds (for 3-high models) to determine shipping weight.
4. An input neutral is required for all configurations unless the input isolation transformer is used.
5. Internal battery, full load.
Battery
Backup5
8
22
8
22
8
8
4
13
4
13
4
4
Dimensions
H x W x D (in)
32.2 x 12.8 x 33.5
47.8 x 12.8 x 33.5
32.2 x 12.8 x 33.5
47.8 x 12.8 x 33.5
47.8 x 12.8 x 33.5
47.8 x 12.8 x 33.5
32.2 x 12.8 x 33.5
47.8 x 12.8 x 33.5
32.2 x 12.8 x 33.5
47.8 x 12.8 x 33.5
47.8 x 12.8 x 33.5
47.8 x 12.8 x 33.5
Unit
Weight3
(lb)
373
609
373
609
577
57
373
609
373
609
577
577
ACCESSORIES
Order Number
Description
Dimensions H x W x D (in)
Unit Weight (lb)
24.0 x 20.3 x 2.2
-
57.3
-
Powerware Hot Sync
124100017-001
103004336
Powerware 9155 Parallel Cabinet
Powerware HotSync CAN Bridge Card
Notes: Up to three Powerware 9155 UPS and up to four Powerware 9355 UPS (available Fall 2005) UPSs can be paralleled with the Parallel Cabinet. Each Powerware 9155 UPS and Powerware 9355 UPS must have a
Powerware Hot Sync CAN Bridge Card installed in the second X-Slot communication bay.
Extended Battery Module (EBM)
103004192-5501
103004193-5501
Powerware 9155 and Powerware 9355 EBM 64 (2-high)
Powerware 9155 and Powerware 9355 EBM 96 (3-high)
32.2 x 12.0 x 30.2
47.8 x 12.0 x 30.2
480
710
Fits both 2& 3-high models
136
16.5 x 12.0 x 7.0
21.0 x 14.0 x 6.75
15
31
Notes: up to four EBM 64 cabinets or three EBM 96 cabinets can be added to each UPS for extended runtime.
Seismic Mounting Kit
103004194-5501
Seismic Kit, Rated Zone 4, UL Tested, Performance rating
based on NEBS GR-63-CORE Standard Vibration Test
Powerware 9155 Maintenance Bypass Module (MBM)
103004184-5501
BPE14MBB1A
UPS-Mounted, Maintenance Bypass Module
Wall-mounted, Maintenance Bypass Module
Powerware 9155 Parallel System Start Up
OSTUP9155P15KCX
OSTUP9155P10KCX
103004626
103004627
Powerware 9155 8-10 kVA 2 or 3 Unit Parallel
Powerware 9155 12-15 kVA 2 or 3 Unit Parallel
Powerware 9155 Parallel System 2 unit upgrade kit (includes Can Bridge Cards, Procedures, and Parallel User's Guide)
Powerware 9155 Parallel System 3 unit upgrade kit (includes Can Bridge Cards, Procedures, and Parallel User's Guide)
Connectivity Options
103002974-5501
05146288-5501
103002510-5501
05146508-5501
05146447-5501
1018460
103003055
103003637-5501
ConnectUPS-X Web/SNMP/xHub Card
ConnectUPS-MX SNMP/Modem Card (9155 only)
Modbus Card
USB Card
Multi-Server Card (9155 only)
Relay Interface Card (AS/400 Compatible)
Industrial Relay Card
Environmental Probe (requires ConnectUPS Web/SNMP card)
Spare Parts
106711155
Powerware 9155 Spare Parts Kit "A"
106711169
Powerware 9355 Spare Parts Kit "A"
Upgrades
103004195
103004196
103004657
Powerware 9155 8 kVA to Powerware 9155 10 kVA
Powerware 9155 12 kVA to Powerware 9155 15 kVA
Powerware 9355 10 kVA to Powerware 9355 15 kVA
Power Distribution Module (PDM) with Mechanical Bypass Switch
Optional Receptacle Panels
(1) L15-30R
(1) L21-20R
(1) L21-30R
(2) 5-15R
(2) 5-20R
(2) 6-15R
(2) 6-20R
(2) L5-15R
(1) L5-20R1
(1) L5-30R1
(2) L6-15R
(1) L6-20R1
(1) L6-30R1
(1) L14-20R1
(1) L14-30R1
(2) IEC 320 C13 (120V)
(2) IEC 320 C19 (120V)
Blank panel
Breaker
30A
20A
30A
15A
20A
15A
20A
15A
20A
30A
15A
20A
30A
20A
30A
20A
20A
Voltage
208V
208/120V
208/120V
120V
120V
208V
208V
120V
120V
120V
208V
208V
208V
120/208V
120/208V
120V
120V
Phase
3
3
3
1
1
2
2
1
1
1
2
2
2
2
2
1
1
Note: Maximum of eight panels per PDM (Powerware 9155). Maximum of four panels per PDM (Powerware 9355).
1. The combined quantities of single-locking receptacle panels must not exceed five per PDM.
POWERWARE 9155 UPS WARRANTY AND SERVICE CHART
POWERWARE 9355 UPS SERVICE CHART
Start-up Warranty Upgrades
Service Protection Plan Upgrades
Warranty PowerTrustTM Service Plan Upgrade
upgrade for first year of service only
Start-up Services Upgrade (5x8 to 7x24)
Recertification/Restart
Coverage
or Response
Time
4 hr
2 hr
8 hr
4 hr
2 hr
7x24
7x24
Item #
SP41A
SP21A
PP81B
PP41B
PP21B
SU97A
RC07N
Unit +
Internal
Service Plan Contracts
Battery
EBM 64
EBM 96
PowerTrust ULTRATM Service Plan (Premium)
PowerTrust ULTRATM Service Plan (7x24) parts and labor coverage, annual 7x24 UPS
preventative maintenance, battery parts & labor coverage, eNotify remote UPS
and battery monitoring - must be connected; 30% discount on upgrades and T&M;
includes 1 complete battery update every 6 year period):
8 hr Response
PU81N
PU81N-BA6
PU81N-BA9
4 hr Response
PU81N
PU81N-BA6
PU81N-BA9
2 hr Response
PU21N
PU21N-BA6
PU21N-BA9
PowerTrustTM Service Plan (Premium)
PowerTrustTM Service Plan (7x24 parts and labor coverage, annual 5x8 UPS and battery preventative maintenance, eNotify remote UPS and battery monitoring; 15%
discount on upgrades):
8 hr Response
PT82N
4 hr Response
PT42N
2 hr Response
PT22N
PowerTrustTM VALUE Service Plan
PowerTrustTM VALUE Service Plan (5x8 parts and labor coverage, next business day
response, annual 5x8 UPS preventative maintenance, eNotify remote UPS and battery
monitoring):
PVN3N
3 Year Battery Labor Coverage
Adds labor and freight to 3YR battery parts warranty:
BL87N
Preventative
Battery Preventive Maintenance
Priced per VRLA cabinet:
5x8 coverage
7x24 coverage
UPS Preventive Maintenance
5x8 coverage
7x24 coverage
Unit +
Internal
Battery
0006N-BIN
0005-BIN
0006N
0005N
Service Plan Features
Service plan terms available
90 days on-site labor (5x8);
two years parts coverage
On-site startup of UPS and
batteries, 7/24
On-site corrective
maintenance, 7x24
Full coverage of UPS and internal
battery module
7x24 technical telephone
support
Service
priority
Full coverage of extended
battery modules
One 7x24 annual preventive
maintenance inspection
0006N-BAG
0005N-BAT
EBM 96
0006N-BAG
0005N-BAG
On-Site
Gold Plan
On-Site
Gold Plan
Plus
2 Yr
2, 3, 5 Yr
2, 3, 5 Yr
Service included
Optional service
POWERWARE 9155 UPS
(ON-SITE SERVICE IS 24 HOURS A DAY, 7 DAYS A WEEK)
ON-SITE GOLD
Part Number
Powerware 9155 UPS (8–10 kVA)
2 Yr
2OSGX915510KVCX
3 Yr
3OSGX915510KVCX
5 Yr
5OSGX915510KVCX
Powerware 9155 UPS (12–15 kVA)
2 Yr
2OSGX915515KVCX
3 Yr
3OSGX915515KVCX
5 Yr
EBM 64
Limited
Factory
Warranty
5OSGX915515KVCX
ON-SITE GOLD PLUS
Part Number
2OSGP915510KVCX
3OSGP915510KVCX
5OSGP915510KVCX
2OSGP915515KVCX
3OSGP915515KVCX
5OSGP915515KVCX
POWERWARE 9155 UPS EXTENDED BATTERY MODULES
(ON-SITE SERVICE IS 24 HOURS A DAY, 7 DAYS A WEEK)
Powerware 9155 EBM 64
2 Yr
3 Yr
5 Yr
Powerware 9155 EBM 96
2 Yr
3 Yr
5 Yr
ON-SITE GOLD
Part Number
ON-SITE GOLD PLUS
Part Number
2OSGX9155EB64CX
3OSGX9155EB64CX
5OSGX9155EB64CX
2OSGP9155EB64CX
3OSGP9155EB64CX
5OSGP9155EB64CX
2OSGX9155EB96CX
3OSGX9155EB96CX
5OSGX9155EB96CX
2OSGP9155EB96CX
3OSGP9155EB96CX
5OSGP9155EB96CX
POWERWARE 9155 UPS PARALLEL SYSTEM
(ON-SITE SERVICE IS 24 HOURS A DAY, 7 DAYS A WEEK)
ON-SITE GOLD
Part Number
Powerware 9155 UPS (8-10 kVA) 2 Unit Parallel System
2 Yr
2OSGX915510P2CX
3 Yr
3OSGX915510P2CX
5 Yr
5OSGX915510P2CX
Powerware 9155 UPS (8-10 kVA) 3 Unit Parallel System
2 Yr
2OSGX915510P3CX
3 Yr
3OSGX915510P3CX
5 Yr
5OSGX915510P3CX
Powerware 9155 UPS (12-15 kVA) 2 Unit Parallel System
2 Yr
2OSGX915515P2CX
3 Yr
3OSGX915515P2CX
5 Yr
5OSGX915515P2CX
Powerware 9155 UPS (12-15 kVA) 3 Unit Parallel System
2 Yr
2OSGX915515P3CX
3 Yr
3OSGX915515P3CX
5 Yr
5OSGX915515P3CX
ON-SITE GOLD PLUS
Part Number
2OSGP915510P2CX
3OSGP915510P2CX
5OSGP915510P2CX
2OSGP915515P3CX
3OSGP915515P3CX
5OSGP915515P3CX
2OSGP915515P2CX
3OSGP915515P2CX
5OSGP915515P2CX
2OSGP915515P3CX
3OSGP915515P3CX
5OSGP915515P3CX
Four button graphical LCD
with backlight
X-Slot Communication Bay #1
Fans
Signal Input 1
Signal Input 2
REPO (normally open)
REPO (normally closed)
X-Slot Communication Bay #2
DB-9 Communication Port
Relay Contact
Internal batteries on slide out
trays (field-replaceable)
Front view of 3-high module with
cover off
TECHNICAL SPECIFICATIONS1
Power
Ratings (kVA/Watts)
9155: 8, 10, 12 and 15 kVA at 0.9 power factor
9355: 10 and 15 kVA at 0.9 power factor
Topology
True double-conversion online UPS
Electrical Input
Nominal Input Voltage
9155: 200V-240V with neutral or with optional
input transformer
9355: 208V/120V or 220V/127V three phase
Input Voltage Range
-15%, +10% from nominal at 100% load without
depleting battery
Operating Frequency
50/60 Hz (45 to 65 Hz)
Input Power Factor
P.F >0.99 typical, >0.96 frequency converter
Input Current Distortion
5% THD
Electrical Output
Nominal Output Voltage
9155: 100/200, 110/220, 120/240 Vac 180° phase
displacement; 120/208, 127/220 Vac 120° phase
displacement
9355: 208/120, 220/127 Vac
Output Voltage Regulation
±1% Static; ±5% dynamic at 100% resistive load
change, <1 ms response time
Efficiency
9155: 90% typical
9355: 91% typical
Battery
Battery Type
9Ah, sealed, lead-acid, maintenance-free
Battery Runtime
See Battery Runtime Chart
Battery Replacement
Field-replaceable
Charger
Default is 3.4A per battery string. Charger current is
configurable from 0.5A to 25A per string with an
overall maximum of 34A (limited by input current)
Start-On-Battery
Allows start of UPS without utility input
General
Diagnostics
Full system self-test at startup
UPS Bypass
Automatic on overload or UPS failure
Parallel for Redundancy
Yes, using Powerware Hot Sync technology
and Capacity
Dimensions and Weights
See Model Selection Table
Overload
150% for 5 sec / 125% for 1 min (online),
(Normal Operation)
110% for 10 min
Communications
LCD Display
Graphical LCD with blue backlight
LEDs
(4) LEDs for notice and alarm
Audible Alarms
Yes
Communication Ports
(1) RS-232, (1) relay contact, (1) REPO,
(2) environmental input
Communication Slot
(2) X-Slot communication bays
Power Management
Bundled Software Suite CD
Software
Environmental
Operating Temperature
10ºC to +40ºC, +45ºC with 7.5% derating;
Batteries recommended max. +25ºC
Storage Temperature
-15ºC to +25ºC
Relative Humidity
0–95%, non condensing
Audible Noise
9155: Audible Noise: < 53 dBA at 1 meter
(noise less room) typical
9355: Audible Noise: < 56 dBA at 1 meter
(noise less room) typical
Altitude
< 1000m at +40°C, < 3000m at +25°C
Certifications
Safety Certifications
9155: NOM-0190SCFI-1993, UL 1778, CSA C22.2, No. 107.3;
EN 5502 Class A (CISPR22 Class A) and IEC 60950;
IEC 62040-1-1
9355: IEC 62040-1-1, IEC 60950, EN 62040-1-1, UL 1778
EMC Compliance
9155: IEC 62040-2, FCC Part 15, ICES-003, VCCI
9355: EN 50091-2 Class A
Quality
ISO 9001: 2000 and ISO 14001:1996
Markings
9155: UL, cUL, CSA, CE and NOM-NYCE
9355: UL, cUL
1. Due to continuous product improvements, program specifications are subject to change without notice.
UNITED STATES
8609 Six Forks Road
Raleigh, NC 27615 U.S.A.
Toll Free: 1.800.356.5794
or 919.872.3020
www.powerware.com
CANADA
Ontario: 416.798.0112
LATIN AMERICA
Argentina: 54.11.4343.6323
Brazil: 55.11.3616.8500
México: 52.55.5488.5252
EUROPE/MIDDLE EAST/AFRICA
Denmark: 45.3686.7910
Finland: 358.94.52.661
France: 33.1.6012.7400
Germany: 49.7841.666.0
Italy: 39.02.66.04.05.40
Norway: 47.23.03.65.50
Sweden: 46.8.598.940.00
United Kingdom: 44.1753.608.700
ASIA PACIFIC
Australia/NZ: 61.2.9878.5000
China: 86.21.6361.5599
HK/Korea/Taiwan: 852.2745.6682
India: 91.11.2649.9414 to 18
Singapore/SEA: 65.6829.8888
Powerware, ABM, ConnectUPS, LanSafe,
PowerVision, Powerware Hot Sync, and X-Slot
are trade names, trademarks, and/or service
marks of Eaton Power Quality Corporation or its
subsidiaries and affiliates. All other trademarks
are property of their respective owners.
© 2005 Eaton Corporation
All Rights Reserved
Printed in USA
9155/9355FXA
July 2005
Download PDF

advertising