AC Power
For Business-Critical Continuity™
Liebert FS™ DC Energy Storage System
User Manual - 190kW/10 Seconds, 540VDC
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.0
GENERAL SYSTEM INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
1.1
General Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1.1
1.1.2
1.2
Safety Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Requesting Assistance from Liebert . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
General System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2.1
1.2.2
1.2.3
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Applicable Standards and Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.0
SITE PREPARATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1
System Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.2
Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3
Flooring Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3.1
2.3.2
2.3.3
2.4
Floor Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Floor-Space Occupation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4.1
2.4.2
2.4.3
2.4.4
2.4.5
DC Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Status/Control Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Grounding Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Monitoring Connections—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
12
12
12
12
3.0
UNLOADING AND UNPACKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1
Inspection Before Removal From the Truck . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2
Unloading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.1
3.2.2
3.3
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Positioning the Liebert FS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3.1
3.3.2
Moving the Liebert FS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Storing the Liebert FS for Delayed Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.0
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.1
Cabinet Floor Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1.1
4.1.2
4.1.3
4.2
Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.2.1
4.2.2
4.2.3
4.2.4
4.2.5
4.2.6
4.3
Concrete, Masonry or Stone Floor Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Wood Floor Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Raised Floor Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
General Wiring Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DC Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Status/Control Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ground Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Auxiliary Control Power Supply Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Monitoring Connections—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
26
28
28
28
29
31
Startup Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
i
5.0
SYSTEM OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.1
Detailed System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.1.1
5.1.2
5.1.3
5.1.4
5.1.5
5.1.6
5.1.7
5.1.8
5.1.9
5.1.10
5.1.11
5.1.12
5.1.13
5.1.14
5.1.15
System Module Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
User interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Interconnection Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Conversion Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Magnetic Levitation Module (MLM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flywheel Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rotor/Flywheel—Rotating Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vacuum System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flywheel Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ventilation and Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
33
34
34
35
35
36
37
38
39
39
40
41
42
42
43
5.2
List of System User-Configurable Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5.3
Modes of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
5.3.1
5.3.2
5.3.3
5.3.4
5.3.5
5.3.6
5.3.7
5.3.8
5.3.9
OFF Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STANDBY Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STARTUP Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHARGE Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
READY Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DISCHARGE Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SHUTDOWN Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COAST Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FAULT Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
46
46
46
47
47
48
48
49
49
5.4
Maintenance and Reliability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6.0
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
6.1
Operator Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.2
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.2.1
6.2.2
6.2.3
6.2.4
6.3
Main screen function descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System MODE Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System STATUS Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Other Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
54
55
55
56
Security Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.3.1
6.3.2
6.3.3
Security Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
EPROM (System) Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
ii
6.4
Menu Tree and Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.4.1
6.4.2
6.4.3
6.4.4
6.4.5
6.4.6
6.4.7
6.4.8
6.4.9
6.4.10
6.4.11
6.4.12
6.4.13
6.4.14
6.4.15
6.5
Screen Tree Menu Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Navigation and Operation of Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Setup and Parameter Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
View. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time/Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Voltages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Network—Requires DCM Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vitals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
57
59
59
61
61
62
62
62
64
65
66
66
66
68
68
System Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
6.5.1
6.5.2
6.5.3
6.5.4
6.5.5
6.5.6
6.5.7
Initial System Startup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspection before Initial System Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Parameters Setup at Initial System Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initial System Startup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Regular Startup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspection Before Regular Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting up the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
69
69
70
70
71
71
71
6.6
Shutdown Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
7.0
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
7.1
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
7.2
Liebert Global Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
7.3
Routine Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
7.4
Maintenance Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
7.5
Record Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
7.6
Optional Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
7.7
Torque Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
7.8
Detecting Trouble . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
7.9
Reporting a Problem. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
7.10
Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
7.11
Recommended Test Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
7.12
Limited Life Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
8.0
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
8.1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
8.2
Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
8.3
Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
iii
APPENDIX A.0
UPS INTERCONNECTION KITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Appendix A.1
Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Appendix A.1.1
Appendix A.1.2
Appendix A.2
Appendix A.2.1
Appendix A.2.2
Appendix A.2.3
Appendix A.2.4
Appendix A.2.5
Appendix A.3
Appendix A.3.1
Appendix A.3.2
Appendix A.3.3
Appendix A.3.4
Appendix A.3.5
Appendix A.4
Appendix A.4.1
Appendix A.4.2
Appendix A.4.3
Appendix A.4.4
Appendix A.4.5
Appendix A.5
Appendix A.5.1
Appendix A.5.2
Appendix A.5.3
Appendix A.5.4
Appendix A.5.5
Appendix A.5.6
Appendix A.5.7
General Wiring Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
DC Power Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Installing the Liebert FS With a Liebert Series 610, Liebert Series 600T
or Liebert Series 600. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Description - Liebert Series 610/600T/600 UPS Interconnection Kit . . . . . . . . . . . . . .
Status/Control Connections - Liebert Series 610/600T/600 UPS
Interconnection Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Configuration - Liebert FS and Liebert Series 610, 600T or 600 . . . . . . . . . . . . .
Liebert FS Configuration - Single Liebert FS on Liebert
Series 610/600T/600 DC Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert FS Configuration - Multiple Liebert FS Units on Liebert
Series 610/600T/600 DC Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
87
88
88
89
89
Installing the Liebert FS With a Liebert Npower UPS . . . . . . . . . . . . . . . . . . . . 90
Description - Liebert Npower UPS Interconnection Kit . . . . . . . . . . . . . . . . . . . . . . . .
Status/Control Connections - Liebert Npower UPS Interconnection Kit . . . . . . . . . . .
UPS Configuration - Liebert FS and Liebert Npower . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert FS Configuration - Single Liebert FS Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert FS Configuration - Multiple Liebert FS Units on Liebert
Npower DC Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
90
91
91
91
92
Installing the Liebert FS With a Liebert Series 300 UPS . . . . . . . . . . . . . . . . . . 93
Description - Liebert Series 300 UPS Interconnection Kit . . . . . . . . . . . . . . . . . . . . . .
Status/Control Connections - Liebert Series 300 UPS Interconnection Kit . . . . . . . . .
UPS Configuration - Liebert FS and Liebert Series 300 . . . . . . . . . . . . . . . . . . . . . . . .
Liebert FS Configuration - Single Liebert FS on Series 300 DC Bus . . . . . . . . . . . . . .
Liebert FS Configuration - Multiple Liebert FS Units on Liebert
Series 300 DC Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
93
94
94
95
95
Installing the Liebert FS With a Liebert HiPulse UPS . . . . . . . . . . . . . . . . . . . . 96
Description—HiPulse UPS Interconnection Kit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Status/Control Connections—Liebert HiPulse UPS Interconnection Kit. . . . . . . . . . .
IKIT-A05 DC Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS Configuration—Liebert FS and Liebert HiPulse . . . . . . . . . . . . . . . . . . . . . . . . . .
Single Liebert FS on UPS DC Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Single Liebert FS in Parallel with Battery Pack on UPS DC Bus . . . . . . . . . . . . . . . .
Liebert FS Configuration – Multiple Liebert FS Units . . . . . . . . . . . . . . . . . . . . . . . . .
96
96
97
97
98
98
99
APPENDIX B.0
DATA COLLECTION MODULE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Appendix B.1
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Appendix B.1.1
Appendix B.1.2
Appendix B.2
Appendix B.2.1
Appendix B.2.2
Appendix B.2.3
Appendix B.2.4
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
DCM Installation and Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DCM Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Accessing the DCM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring DCM System Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iv
100
101
103
103
Appendix B.3
Appendix B.3.1
Appendix B.3.2
Appendix B.3.3
Appendix B.4
Appendix B.4.1
Appendix B.4.2
DCM Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Logging into the DCM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Status and Detailed Status Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Datafiles Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
DCM Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
DCM Troubleshooting Principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Resetting the DCM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
APPENDIX C.0
VERSATILE INTERFACE BOARD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Appendix C.1
General Information—Versatile Interface Board . . . . . . . . . . . . . . . . . . . . . . . . 107
Appendix C.1.1
Appendix C.1.2
Appendix C.2
Appendix C.2.1
Appendix C.2.2
Appendix C.2.3
Appendix C.2.4
Appendix C.2.5
Appendix C.3
Appendix C.3.1
Appendix C.4
Appendix C.4.1
Appendix C.4.2
Appendix C.4.3
Appendix C.4.4
Versatile Interface Board Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
VIB Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
VIB Installation and Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
VIB Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIB Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIB Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIB Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIB Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
110
110
110
110
111
VIB Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
VIB Operational States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Troubleshooting the VIB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
UIB State Not Displayed on the Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIB in “Disabled” or “Not Available” State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inputs Not Recognized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outputs Not Asserted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
112
112
112
112
APPENDIX D.0
INSTALLATION DRAWINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Appendix D.1
Liebert FS Flywheel Submittal Document Matrix . . . . . . . . . . . . . . . . . . . . . . . 113
Appendix D.2
Other Liebert FS Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
APPENDIX E.0
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Appendix E.1
Ground Test Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
APPENDIX F.0
AUXILIARY BACKUP AC POWER SUPPLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Appendix F.1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Appendix F.2
Backup AC Power Supply Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Appendix F.3
Recommended Backup Power Supply Configuration . . . . . . . . . . . . . . . . . . . . . 150
Appendix F.3.1
Appendix F.3.2
Appendix F.4
Operating the Liebert FS+DC in Parallel With Batteries . . . . . . . . . . . . . . . . . . . . . . 151
Operating the Liebert FS Without Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Scenarios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
v
FIGURES
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
Figure 9
Figure 10
Figure 11
Figure 12
Figure 13
Figure 14
Figure 15
Figure 16
Figure 17
Figure 18
Figure 19
Figure 20
Figure 21
Figure 22
Figure 23
Figure 24
Figure 25
Figure 26
Figure 27
Figure 28
Figure 29
Figure 30
Figure 31
Figure 32
Figure 33
Figure 34
Figure 35
Figure 36
Figure 37
Figure 38
Figure 39
Figure 40
Figure 41
Figure 42
Figure 43
Figure 44
Figure 45
Figure 46
Figure 47
Figure 48
Figure 49
Figure 50
Figure 51
Figure 52
Figure 53
Liebert FS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Single Liebert FS unit or multiple Liebert FS units integrated into a UPS system. . . . . . . . . . . . 5
Liebert FS unit(s) integrated into UPS system for ride-through to backup generator. . . . . . . . . . 5
One or more Liebert FS units in parallel with one or more battery strings, battery
cabinets or batteries in racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Liebert FS DC power duration for one or multiple units in parallel . . . . . . . . . . . . . . . . . . . . . . . . 8
Integrating a single Liebert FS unit into a UPS system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Integrating multiple Liebert FS units into a UPS system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Liebert FS shipping package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Removing lag bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Lifting the Liebert FS cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Removing the metal support plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Location of serial and model number plate (cabinet side panel removed and open door) . . . . . . 16
Liebert FS cabinet caster location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Dimensions, general layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Internal layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Floor mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Floor mounting template layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Checking hole depth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Inserting anchors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Expanding anchors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Securing mounting brackets to the cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Mounting rear bolts—rear side of cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Mounting front bolts—front side of cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Bubble level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Raised floor mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Liebert FS cabinet with UPS interconnection kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Liebert FS with circuit breaker mounting plate and access panels for DC and control
wiring connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Typical circuit breaker wiring for DC connections (view from rear of circuit breaker) . . . . . . . . 27
Ground connection on the Liebert FS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Service panel location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Auxiliary backup power connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Auxiliary power fused disconnect with connection points for AC wire . . . . . . . . . . . . . . . . . . . . . 30
Top access panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Remote monitoring (DCM) connections (inside cabinet front door) . . . . . . . . . . . . . . . . . . . . . . . 31
Liebert FS front view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Electrical system schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Schematic of the levitation system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Liebert FS flywheel module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Rotating group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Cross-section of the synchronous reluctance motor rotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Vacuum system operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Schematic for the speed and temperature sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Cutaway flywheel module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Voltage and Inductance curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Vreg delta help screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
STANDBY mode diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Startup mode diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
CHARGE mode diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
READY mode diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
DISCHARGE mode diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
SHUTDOWN mode diagram - shutdown after full discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
SHUTDOWN mode diagram - user-initiated shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Typical operation modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
vi
Figure 54
Figure 55
Figure 56
Figure 57
Figure 58
Figure 59
Figure 60
Figure 61
Figure 62
Figure 63
Figure 64
Figure 65
Figure 66
Figure 67
Figure 68
Figure 69
Figure 70
Figure 71
Figure 72
Figure 73
Figure 74
Figure 75
Figure 76
Figure 77
Figure 78
Figure 79
Figure 80
Figure 81
Figure 82
Figure 83
Figure 84
Figure 85
Figure 86
Figure 87
Figure 88
Figure 89
Figure 90
Figure 91
Figure 92
Figure 93
Figure 94
Figure 95
Figure 96
Figure 97
Figure 98
Figure 99
Figure 100
Figure 101
Figure 102
Figure 103
Figure 104
Figure 105
Figure 106
Figure 107
Figure 108
Control panel view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Main screen functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Fault screen functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Menu tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
User level main menu screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
READ ONLY level parameter view screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
USER level or above parameter edit screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
HELP screen for User Setup Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Graphical HELP screen for VREG DELTA1, VREG TSOC, and VREG DELTA2
Transition setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
USER or higher level parameter selection for view/edit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
VIEW menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
TIME/DATE set. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Temperature view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Figure 5-14. Voltages view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
History view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Charge history. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Discharge history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Discharge History, Event list screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Warning history, Event list screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Fault history, Event list screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Vitals history view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Counters - screen 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Options view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Networks view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Networks view, Edit DHCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Networks view, Edit Settings (Service level). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Electrical view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Vitals view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Password screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Change password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Change password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
ABOUT screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Serial numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Tools for USER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
USER level menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
VIEW menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Warning history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Fault history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Warning screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Fault screen descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Top view of Liebert FS Cabinet with UPS interconnection kit . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Liebert Series 610 225kVA UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Liebert Series 610/600T/600 status/control terminal block wiring . . . . . . . . . . . . . . . . . . . . . . . . 88
Liebert FS integrated into a Liebert Npower UPS system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Liebert Series 300 UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Liebert Series 300 status/control terminal block wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Liebert HiPulse status/control terminal block wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Circuit-breaker (open door and cabinet faceplate removed). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Data Collection Module location, features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
DCM LAN connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Options view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Enable or disable DCM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Networks view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
vii
Figure 109
Figure 110
Figure 111
Figure 112
Figure 113
Figure 114
Figure 115
Figure 116
Figure 117
Figure 118
Figure 119
Figure 120
Figure 121
Figure 122
Figure 123
Figure 124
Figure 125
Figure 126
Figure 127
Figure 128
Figure 129
Figure 130
Figure 131
Figure 132
Figure 133
Figure 134
Figure 135
Figure 136
Figure 137
Figure 138
Figure 139
Figure 140
Figure 141
Figure 142
Figure 143
Figure 144
Figure 145
Figure 146
Figure 147
Figure 148
Figure 149
Figure 150
Figure 151
Figure 152
Figure 153
Figure 154
Figure 155
Figure 156
Networks view, turn off DHCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Networks view, edit settings (service level). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DCM screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DCM setup screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DCM status screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Datafiles screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Data Collection Module reset button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIB components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O Designations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Versatile Interface Board mounted in the Liebert FS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VIB screw terminal connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
No UVR, circuit breaker to terminal block wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical system block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24 UVR, circuit breaker to terminal block wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
48 UVR, circuit breaker to terminal block wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outline drawing, Liebert FS cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control wiring, external interconnect diagram—Liebert FS cabinet to Liebert Npower
UPS module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control wiring external interconnect—Liebert FS to Liebert Series 300 . . . . . . . . . . . . . . . . . .
Control wiring—external interconnect diagram, Liebert FS cabinet to Liebert
Series 610 UPS module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control wiring—external interconnect diagram, Liebert FS cabinet to Liebert
Series 610 UPS module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Elevation drawing, Liebert FS cabinet with shipping package . . . . . . . . . . . . . . . . . . . . . . . . . .
Elevation drawing—Liebert FS cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control wiring diagram, Liebert FS power rack system in parallel for capacity . . . . . . . . . . . .
Liebert FS cabinet with optional power terminal block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert FS cabinet mechanical installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Elevation drawing—Liebert FS cabinet with integrated circuit breaker . . . . . . . . . . . . . . . . . .
One-line drawing, three Liebert FS systems in parallel configuration . . . . . . . . . . . . . . . . . . . .
Control wiring diagram—Liebert FS cabinet - manually operated circuit breaker . . . . . . . . . .
One-line diagram—Liebert FS systems with factory-integrated circuit breakers
with Liebert UPS module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
One-line diagram—single Liebert FS system with factory-integrated circuit breaker
supplying Liebert UPS module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control wiring diagram—Liebert FS - optional electrically operated circuit breaker
Liebert Npower units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Two-eight paralleled Liebert FS units with factory-integrated circuit breaker in parallel
with a Liebert UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
One-line diagram, single Liebert FS and battery with factory-integrated circuit breaker
supplying Liebert UPS—UPS DC terminal point of common connection . . . . . . . . . . . . . . . . . .
One-line diagram, single Liebert FS and battery with factory-integrated circuit
breaker supplying Liebert UPS—UPS battery point of common connection . . . . . . . . . . . . . . .
Status/control wiring, multiple units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring specifications, Liebert FS and Liebert Series 300 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring specifications, Liebert FS and Liebert Npower. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring specifications, Liebert FS and Liebert Series 610 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring specifications, Liebert FS and Liebert HiPulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Floor mounting template . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System mounting kit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liebert FS block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power line diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS cable entry—bottom . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UPS cable entry—top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Raised floor mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A single Liebert FS+DC unit operating with a UPS in conjunction with batteries . . . . . . . . . .
viii
102
102
103
103
104
105
106
107
109
110
111
114
115
116
117
117
118
119
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
151
Figure 157 Multiple Liebert FS+DC units operating with a UPS in conjunction with batteries . . . . . . . . .
Figure 158 A single Liebert FS unit operating with a UPS and without batteries attached
to the DC bus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 159 Multiple Liebert FS units operating with a UPS and without batteries attached
to the DC bus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 160 Liebert FS connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
151
152
152
153
TABLES
Table 1
Table 2
Table 3
Table 4
Table 5
Table 6
Table 7
Table 8
Table 9
Table 10
Table 11
Table 12
Table 13
Table 14
Table 15
Table 16
Table 17
Table 18
Table 19
Table 20
Table 21
Table 22
Table 23
Table 24
Table 25
Table 26
Table 27
Table 28
Table 29
Table 30
Table 31
Table 32
Table 33
Table 34
Table 35
Table 36
System information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
General system specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Tightening torque for ground connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Control panel keyboard layout (refer to Figure 54) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Operation modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
System status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
EEPROM parameter number ranges. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
PCMC parameters, read-only and user (Liebert FS software). . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Control parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Software versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Maintenance schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Torque specifications (unless otherwise labeled) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Recommended test equipment and tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Projected component life, replacement schedule. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Faults—causes and responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Key to UPS model interconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Liebert Series 610/600T/600 model ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Liebert FS Software Control Parameter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Liebert FS Software Control Parameters varying with UPS size . . . . . . . . . . . . . . . . . . . . . . . . . 89
Liebert Npower model ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Liebert FS Software Control Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Liebert FS Software Control Parameters varying with UPS size . . . . . . . . . . . . . . . . . . . . . . . . . 91
List of Liebert Series 300 models ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Liebert FS Software Control Parameter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Liebert FS Software Control Parameters varying with UPS size . . . . . . . . . . . . . . . . . . . . . . . . . 95
Liebert HiPulse model ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Liebert FS Software Control Parameter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Liebert FS Software Control Parameters varying with UPS size . . . . . . . . . . . . . . . . . . . . . . . . . 98
Liebert FS Software Control Parameter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Liebert FS Software Control Parameters varying with UPS size . . . . . . . . . . . . . . . . . . . . . . . . . 98
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
VIB I/O functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Submittal documents accompanying Liebert FS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
ix
x
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and maintenance of your Liebert FS.
!
WARNING
!
WARNING
The installation of the Liebert FS must comply with applicable national, federal, state and
local codes.
ONLY qualified service personnel should perform maintenance on the Liebert FS
system. When performing maintenance with any part of the equipment, service personnel
and test equipment should be standing on rubber mats. The service personnel should wear
insulating shoes for isolation from direct contact with the floor (earth ground).
Never work alone, even if all power is removed from the equipment. A second person should
be standing by to assist and summon help in case an accident should occur.
Under typical operation and with all UPS doors closed, only normal safety precautions are
necessary. The area around the Liebert FS system should be kept free of puddles of water,
excess moisture and debris.
Special safety precautions are required for procedures involving handling, installation and
maintenance of the UPS system. Observe all safety precautions in this manual before
handling, installing or operating the UPS system.
This equipment contains circuits that are energized with high voltage. Only test
equipment designed for troubleshooting and for use with those voltages should be used.
Always check with an AC and DC voltmeter to ensure safety before making contact or using
tools. Even when the power is turned Off, dangerously high electric charges may exist within
the UPS.
Exercise extreme care when handling Liebert FS cabinets to avoid equipment damage or
injury to personnel. Refer to Section 3.0 and Section 4.0 for equipment handling
information and installation procedures.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
others approved for use in fighting electrical fires.
!
WARNING
Extreme caution is required when performing maintenance.
Be constantly aware that the Liebert FS contains high DC as well as AC voltages. With input
power off and the battery disconnected, high voltage at filter capacitors and power circuits
should be discharged within 30 seconds. However, if a power circuit failure has occurred, you
should assume that high voltage may still exist after shutdown. Check with a voltmeter
before making contact.
Check for voltage with both AC and DC voltmeters prior to making contact.
!
WARNING
When the Liebert FS is under power, both the operator and any test equipment must be
isolated from direct contact with earth ground and the Liebert FS chassis frame by using
rubber mats.
Some components within the cabinets are not connected to chassis ground. Any contact
between floating circuits and the chassis is a lethal shock hazard. Exercise caution that the
test instrument exterior does not make contact either physically or electrically with earth
ground.
1
!
CAUTION
!
CAUTION
!
CAUTION
!
CAUTION
!
CAUTION
!
CAUTION
Do not loosen or tamper with vacuum components and fittings.
This unit contains components sensitive to electrostatic discharge.
Do not remove plug-in printed circuit cards during operation. Improper removal of a card can
cause severe damage to the unit.
The 110/230VAC must remain connected at all times to ensure reliable backup power to
Liebert FS auxiliaries.
Do not use this unit for other than its intended use.
A qualified electrician must perform all electrical connections.
All wiring size and installation must comply with all applicable local, regional and national
regulations (e.g., National Electric Code for USA).
Safety Precautions
Read this manual thoroughly, paying special attention to the sections that apply to you, before working with the Liebert FS.
Under typical operation and with all cabinet doors closed, only normal safety precautions are necessary. The area around the Liebert FS should be kept free from puddles of water, excess moisture or
debris.
Special safety precautions are required for procedures involving handling, installation and maintenance of the Liebert FS. Observe precautions in 7.0 - Maintenance before as well as during performance of any maintenance procedure on the Liebert FS.
This equipment contains circuitry that is energized with high voltage. Only test equipment designated for troubleshooting should be used. This is particularly true for oscilloscopes. Always check
with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the
power is turned Off, dangerously high voltage may exist at the capacitor banks.
ONLY qualified service personnel should perform maintenance on the Liebert FS. When performing
maintenance with any part of the equipment under power, service personnel and test equipment
should be standing on rubber mats. The service personnel should wear insulating shoes for isolation
from direct contact with the floor (earth ground).
One person should never work alone. A second person should be standing by to assist and summon
help in case an accident should occur.
2
General System Information
1.0
GENERAL SYSTEM INFORMATION
1.1
General Information
1.1.1
Safety Considerations
Read and follow the instructions in this manual before interacting with the system. This document
contains important information and instructions for your Liebert FS. All procedures defined in the
manual related to unpacking, installing and operating the unit must be followed.
Refer to this manual before contacting Liebert Global Services for technical assistance.
!
1.1.2
WARNING
Failure to recognize electrical hazards could prove fatal. Failure to abide by instructions
provided herein may void your warranty.
Requesting Assistance from Liebert
If you require assistance for any reason, contact Liebert Global Services at 1-800-LIEBERT
(1-800-543-2378). Have the following information available:
Table 1
System information
Date Purchased
Date Installed
Location
System Model Number
System Serial Number
Interconnected UPS Manufacturer
Interconnected UPS Model
Software Version; Primary *
Software Version; Secondary *
Software Version; Bootloader *
3
General System Information
1.2
General System Description
The Liebert FS is a flywheel energy storage system, a mechanical battery that stores energy in the
form of a rotating mass. This energy is immediately convertible to useful electric power.
The Liebert FS is available with a wide performance range up to 190 kW as a single unit configuration.
Figure 1
Liebert FS
The Liebert FS is configured as a two-terminal plus ground DC flywheel power system and is used as
a functional replacement for or an availability supplement to a bank of chemical batteries for an
Uninterruptible Power System. Like a chemical battery bank, Liebert FS receives charge and float
power from the two terminal UPS DC bus and returns power to the same DC bus whenever the bus
voltage droops below a programmable threshold level.
Integrated into a UPS, the Liebert FS is used as the alternate source of power to supply DC power to
the UPS inverter if the AC supply voltage (UPS input) is outside the acceptable range. The Liebert FS
supplies power to the UPS inverter until the utility power is restored, until an alternate power source
is available, or until the Liebert FS’ energy is exhausted.
One or more Liebert FS units may be integrated into UPS and can be put in parallel as shown in
Figures 2 and 3, to achieve higher power output or higher ride-through duration.
4
General System Information
Figure 2
Single Liebert FS unit or multiple Liebert FS units integrated into a UPS system
UPS Block Diagram
Utility
Power
DC
Loads
DC
EMERSO
N
AC
EMERSO
N
Liebert
EMERSO
N
Liebert
Network Power
Network Power
Liebert FS Unit 1
Figure 3
UPS
DC Bus
AC
Lieber t
Network Power
Liebert FS Unit 2
Liebert FS Unit N
Liebert FS unit(s) integrated into UPS system for ride-through to backup generator
UPS Block Diagram
Utility
Power
ATS
UPS
DC Bus
AC
DC
Loads
DC
Backup
Generator
EMERSO
N
AC
EMERSO
N
Lieber t
Lieber t
Network Power
Network Power
Liebert FS Unit 1 Liebert FS Unit 2
5
EMERSO
N
Lieber t
Network Power
Liebert FS Unit N
General System Information
Figure 4
One or more Liebert FS units in parallel with one or more battery strings, battery cabinets or
batteries in racks
UPS Block Diagram
Utility
Power
EMERSON
1.2.1
DC
Loads
DC
Li ebert
EMERSON
Network Power
Liebert
FS Unit 1
UPS
DC Bus
AC
Network Power
Li ebert
Liebert
FS Unit 2
EMERSON
Network Power
AC
Li ebert
Liebert
FS Unit N
Battery 1
Battery 2
Battery N
General Specifications
Table 2 summarizes the technical specifications of the Liebert FS.
Table 2
General system specifications
Rated Power Delivery
Dependent upon the duration required;
refer to Figure 5
Input Voltage (DC)
360 through 600 VDC; > 520 VDC required for 190kW
Output Voltage (DC)
350 through 590 VDC; > 510 VDC required for 190kW
Input Voltage Aux. (AC)
85 VAC – 265 VAC (47-63Hz)
Operating Temperature
-20°C to 50°C (-4°F to 122°F)
Non-Operating Temperature
-20°C to 80°C (-4°F to 176°F)
Dimensions (W x D x H)
63 x 83 x 180 cm (25 x 33 x 71 in)
Total Weight
590 kg (1,300 lb)
For more-detailed technical specifications, refer to Technical specifications on page 148.
6
General System Information
1.2.2
Features and Benefits
The Liebert FS provides clean constant DC output to the DC bus, at the user-selected, regulated voltage, until the stored energy is depleted. See Figure 5 for a graphic representation of the performance
power and duration curves of single and paralleled unit combinations.
Key Technological Features
•
•
•
•
•
Active magnetic bearings
Internal, integrated vacuum system
Synchronous reluctance motor-generator
Fiber composite flywheel
Unique patented safety system
Key Customer Benefits
•
•
•
•
•
•
•
•
•
•
1.2.3
High reliability
Significantly increased power supply reliability
Low total cost of ownership
Operational flexibility
Environmentally friendly
Easy to install and easy to operate.
Low standby losses
Small footprint
Lightweight
Reliable, cost effective power systems for UPS ride-through needs
Applicable Standards and Certification
For distribution in North America, the Liebert FS is listed to the following Underwriter’s Laboratory
(UL) applicable requirements:
• UL 508, Standard for Safety for Electrical Industrial Control Equipment;
• UL 1004, Standard for Safety for Electric Motors;
• UL 1248, Standard for Safety for Engine-Generator Assemblies;
The Liebert FS is designed in accordance with the applicable sections of the requirements published by:
• National Fire Protection Association (NFPA)/National Electric Code (NEC)
• National Electrical Manufacturer's Association (NEMA)
• Occupational Safety & Health Administration (OSHA)
The Liebert FS is also listed to the following Canadian Standards as determined by UL (cUL):
• CSA-C22.2 No. 100-04, “Motors and Generators,”
• CSA-C22.2 No. 14-95, “Industrial Control Equipment,”
The "Uniform Building Code (UBC) Zone 4" certification requirements.
7
General System Information
For distribution in Europe, the Liebert FS is CE-marked and meets the applicable requirements of
the following European directives:
“Low Voltage Directive” 73/23/EEC and its amendments by the directive 93/68/EEC;
“Machinery Directive” 98/037/EEC and its amendments by the directive 98/79/EEC;
• IEC/EN 60439-1:1999—”Low-voltage switchgear and control gear assemblies Part 1: Typetested and partially type-tested assemblies”
• IEC/EN 60204-1:1997—”Safety of machinery - Electrical equipment of machines Part 1: General requirements”
• EN 1127-1:1997—”Explosive atmospheres: Explosion prevention and protection Part 1: Basic
concepts and methodology”
• Machinery Directive Annex 1—”Essential Health and Safety Requirements Relating to the
Design and Construction of Machinery and Safety Components”
“Electromagnetic Compatibility (EMC) Directive” 89/336/EEC and its amendments by the directives 92/31/EEC and 93/68/EEC.
Figure 5
Liebert FS DC power duration for one or multiple units in parallel
1900 kW-sec delivered
GT model, 510 VDC, with filter
10 seconds at 190kW (max. power)
@ 510 VDC min
kWb = Refers to Kilowatts on the DC bus of the UPS system
Discharge Voltage = 510VDC
The Liebert FS is integrated into UPS systems as shown in Figures 2 through 4 and Figures 6
and 7.
8
General System Information
Figure 6
Integrating a single Liebert FS unit into a UPS system
UPS Block Diagram
Bypass
Breaker
Bypass
GRID
Feeder
Breaker
UPS
Input
Breaker
Utility
Static
Switch
UPS
Output
Breaker
UPS
DC
Bus
UPS
Rectifier
CRITICAL
AC LOADS
EMERSON
Lieber t
Network Power
Liebert FS
Several Liebert FS units can be put in parallel to achieve higher power output and higher ridethrough duration (see Figure 7). One or more Liebert FS units may also be connected in parallel with
a UPS battery plant (valve- regulated or wet cells) to provide an overall incremental reliability and
life improvement for the DC battery plant. In this situation, the Liebert FS unit would be connected
in parallel with the battery plant (through its own disconnect device) to the UPS DC Bus.
Figure 7
Integrating multiple Liebert FS units into a UPS system
UPS Block Diagram
Bypass Breaker
Static
Switch
Bypass
GRID
Feeder
Breaker
UPS
Input
Breaker
UPS
Rectifier
Utility
EMERSON
Lieber t
Network Power
Liebert FS
Unit #1
UPS
DC Bus
EMERSON
Lieber t
Net work Power
Liebert FS
Unit #2
9
UPS
Output
Breaker
UPS
Inverter
EMERSON
Lieber t
Network Power
Liebert FS
Unit #N
CRITICAL
AC LOADS
Site Preparation
2.0
SITE PREPARATION
Site preparation for the Liebert FS is minimal. If a UPS system is already installed, the only requirements are to properly:
• Place the unit in relation to walls, ceiling and other equipment and
• Fasten the unit to the floor.
!
CAUTION
The following sections should be read thoroughly before proceeding with site preparation for
installing the Liebert FS.
NOTE
All drawings referred to in this section are in Appendix D.0 - Installation Drawings.
2.1
System Location
Choose a location for the Liebert FS that offers:
•
•
•
•
•
•
•
2.2
Easy connection to inputs, outputs and auxiliary equipment
Enough space to service the Liebert FS
Air circulation sufficient to expel heat produced by Liebert FS
Protection against moisture and excessive humidity (not to exceed 95% non-condensing)
Protection against excessive dust and other particulate matter
Compliance with fire prevention regulations and practices
Operating environment temperature of -4°F to 122°F (-20°C to 50°C)
Environmental Considerations
Place the system in a clean, dust-free environment. Air must be free to circulate around the cabinet(s). The system pulls air through the front of the Liebert FS and exhausts it out the top for cooling.
If the unit must be located in a dusty environment, Liebert recommends installing an optional air filter, which mounts on the lower inside of the Liebert FS door.
Adequate ventilation, including air conditioning if necessary, must be provided to limit heat accumulation. The ambient temperature for the unit must be from -4°F to 122°F (-20°C to 50°C). Avoid placing the unit in direct sunlight or near other heat sources.
There is a 32°F (0°C) minimum ambient temperature requirement for starting up the unit. Once the
unit has been running for some time, it will keep itself warm enough in ambient temperatures as low as
-4°F (-20°C).
Humidity is not to exceed 95% (non-condensing).
10
Site Preparation
2.3
Flooring Requirements
2.3.1
Floor Loading
The Liebert FS should be mounted on a finished surface, such as concrete, block, brick or wood. The
floor must be strong enough to support the equipment load and suitable for installation of an anchoring kit with vertical floor loading properly calculated (assume 2,000 PSI or 140 kg/cm2 contact load at
caster wheels; this includes safety factors).
• When installing on a concrete, masonry or stone floor, use the factory-supplied masonry fasteners
(anchors). The fastener manufacturer’s allowable shear load (parallel to floor) for these fasteners
is 2,030 lb. (9 kN) when mounted in normal-weight concrete (2,000 to 3,000 PSI; 140-210 kg/cm2)
of at least 3 in. (7.6cm) thickness.
• If installing on a floor consisting of a material other than normal-weight concrete as described
above, the mounting should be capable of sustaining a shear load (parallel to floor) of at least
1,500 lb. (6.7 kN) for each of the four mounting points.
• If installing on a raised floor that is less than 2 in. (5cm) thick or constructed of a material not
appropriate for the masonry fasteners provided or lag screw engagement, mount using through
bolts with nuts and large diameter washers as shown in Figure 155.
Full details for mounting the cabinet are found in 4.1 - Cabinet Floor Mounting.
NOTE
The above loads (both the fastener manufacturer load and the minimum mounting load)
include the required safety factors.
2.3.2
Floor-Space Occupation
The Liebert FS cabinet requires a floor space of 23" wide by 33" deep (63 x 83cm), resulting in a footprint of 5.7 square feet (0.5m2).
2.3.3
Clearances
The Liebert FS installation requires a ceiling height of at least 7 ft. (214cm).
The unit occasionally vents air out of the top. Loose ceiling tiles above the unit may be moved by the
airflow. Ample clearance to access the cable connection at the top of the unit must also be provided.
All system electrical connections are to be routed through the top or side of the cabinet.
A 36" (91cm) clearance is required in the front of the unit for National Electrical Code (NEC) compliance.
Maintenance access to all components is from the front; no side or back access is required for maintenance. Either side of the system cabinet can be placed against walls (assuming minimum distance
from edge of floor). Repair may require access to the rear of the unit. In this unlikely instance, the
unit may need to be rolled out from its installed location (cabinet is on casters).
2.4
Electrical Considerations
!
2.4.1
CAUTION
A qualified electrician must perform all electrical connections. The wires (DC power,
grounding, optional status/control and auxiliary power supply) that connect the Liebert FS
system(s) to the UPS system must be provided by the electrical contractor (standard) or by
Liebert as an option. Wire size and installation must comply with all applicable local, regional
and national regulations (e.g., National Electric Code for USA).
DC Power Connections
Place the Liebert FS as close as practical to the interconnected UPS. The maximum distance allowed
between the UPS and the Liebert FS depends on power levels and the type of DC cables used. Liebert
requires sizing DC cables and placing the Liebert FS for a maximum of no more than 2V loop drop (at
rated power) between the UPS and the Liebert FS.
The Liebert FS is delivered with the standard UPS interconnection kit for connection of the positive
and negative terminals coming from the UPS DC bus or from an external disconnect switch.
For details, see 4.2.2 - DC Power Connections.
11
Site Preparation
2.4.2
Status/Control Connections
Site preparation for Status/Control connections vary according to the type of UPS interconnection kit
provided with your Liebert FS.
Liebert recommends making Status/Control connections on the UPS system side.
For details, refer to 4.2.3 - Status/Control Connections.
2.4.3
Grounding Connections
A grounding wire must be connected from the Liebert FS to the UPS ground terminal. Identify in
advance the location of the grounding terminal on the UPS system. For further details, see 4.2.2 - DC
Power Connections.
2.4.4
AC Power Connections
Plan for the availability of a dedicated 110 or 230VAC, 50 or 60Hz circuit with branch circuit protection as a source for AC auxiliary power supply to the Liebert FS. This AC power must be rated for
400VA and must be located either on the output circuit of the UPS system or on another UPS-protected circuit. A qualified electrical contractor should make arrangements for this connection to be
permanent.
The field-supplied AC wire must comply with all applicable local, regional and national regulations
(e.g., National Electric Code for USA). An 18 AWG (0.82mm2) cable is recommended for this connection.
For details, see 4.2.5 - AC Auxiliary Control Power Supply Connections and Appendix F.0 Auxiliary Backup AC Power Supply.
2.4.5
Remote Monitoring Connections—Optional
If the optional Data Collection Module (DCM) is provided with your Liebert FS system, plan to have
communication cables (local network connection, phone line) installed to support the remote notification and/or monitoring options chosen.
For details, see 4.2.6 - Remote Monitoring Connections—Optional.
12
Unloading and Unpacking
3.0
UNLOADING AND UNPACKING
NOTE
All drawings referred to in this section are in Appendix D.0 - Installation Drawings.
3.1
Inspection Before Removal From the Truck
While the Liebert FS shipping package is still on the truck:
• Inspect the equipment and shipping container(s) for any signs of damage or mishandling. Check
also if the shock and tilt gauges (installed for shipping purposes) indicate excessive shock and/or
tilting. If any damage is noted, file a damage claim with the shipping agency within 24 hours and
contact your local sales representative or Liebert at 1-800-LIEBERT to notify them of the damage
claim and the condition of the equipment.
• Compare the contents of the shipment with the bill of lading. Report any missing items to the carrier, your local Liebert representative and Liebert at 1-800-LIEBERT immediately. Please have
the bill of lading available.
!
3.2
CAUTION
Do not attempt to install the system if damage is apparent.
Unloading
Figure 8
Liebert FS shipping package
Shipping Support
Bands
(on either side)
76"
(1933mm)
Metal
Support
Plates
(one on
either side)
Front View
Side View
Do not tilt the Liebert FS
more than 15 degrees
from vertical.
Shipping Weight:1462 lb. (663kg)
Weight, unit only: 1300 lb (590kg)
24"
(610mm)
48"
(1219mm)
4.4"
(112mm)
45"
(1143mm)
14623
Top View
The FS as shipped (see Figure 8) can weigh up to 1,462 lb. (663kg). It must be handled with care. It
must be kept upright—pay special attention to the arrows, which indicate the upright position.
13
Unloading and Unpacking
3.2.1
Handling
The Liebert FS shipping package is designed to be handled using a forklift. Forklift operators must
avoid rough handling when picking up, moving and lowering it.
!
!
3.2.2
CAUTION
Exhibit care when handling Liebert FS cabinet to avoid equipment damage or injury to
personnel. Failure to do so could throw off the calibration of the mechanical components
contained in the unit and possibly cause permanent damage.
CAUTION
The Liebert FS has sensitive electronics and mechanical components that have been
calibrated prior to shipment.
!
CAUTION
!
CAUTION
Test lift and balance the cabinet before transporting it. Maintain minimum tilt from vertical
at all times—do not exceed 15 degrees of tilt.
Sheet metal components and framework may have sharp edges.
Unpacking
To reduce the possibility of shipping damage, flywheel cabinets are secured to the pallet by two
mounting brackets and two banding straps. These same two mounting brackets are used to mount the
cabinet to the floor.
Packing elements should be removed in this order to ease unpacking:
1. Cut and remove the banding straps (see Figure 8).
!
CAUTION
Use care when removing banding straps and metal mounting brackets. The banding straps
are under tension and may snap violently, causing injury. Always wear proper eye and foot
protection when unpacking or installing the system.
2. Remove hex head bolts holding mounting brackets to pallet as shown in Figure 9.
3. Remove lag bolts holding metal mounting brackets to pallet.
4. Remove mounting brackets from Liebert FS.
Figure 9
Removing lag bolts
Lag bolts
securing
Liebert FS to
shipping pallet
Metal mounting
bracket bolted to
shipping pallet
14
Unloading and Unpacking
5. Use a forklift to remove the cabinet from the shipping pallet.
To lift the Liebert FS, the forks should be inserted between the caster wheel assemblies (see
Figure 10). Forks must be extended to the full depth of the cabinet—at least 6 ft. (2m) fork
length—to properly support the equipment (see Figure 10). This likely requires fork extenders.
The Liebert FS unit can weigh up to 1,300 lb. (590kg) and must be handled with care.
Figure 10 Lifting the Liebert FS cabinet
Forks must be
extended the
full depth of the
cabinet
6. Unbolt and remove the two metal support plates (one on either side of the pallet).
Figure 11 Removing the metal support plates
Metal
support
plate
Caster
(for moving
short
distances)
Leveling
foot (one
on each
corner)
NOTE
Retain the four bolts (1/2" diameter x 1-3/4" long; 12.7mm diameter x 44.5mm long) attaching
the metal support plates to the cabinet. These will be used to attach brackets to the cabinet for
surface mounting.
7. Examine the Liebert FS internally and externally for transit damage. Report any damage to the
shipper, your local Liebert representative and Liebert immediately.
!
CAUTION
Do not attempt to install the system if there is any damage.
8. Check visually for loose connections and unsecured components in the cabinet.
9. You will find the installation manual, operation manual and options manual (if any) enclosed in
the pocket inside the cabinet door (see Figure 12).
10. You will find the serial number and model number plate mounted on the cabinet door pocket or on
the upper right corner of the face of the cabinet frame inside the door (see Figure 12). Record the
model number and serial number in Table 1 - System information.
15
Unloading and Unpacking
Figure 12 Location of serial and model number plate (cabinet side panel removed and open door)
Manuals
Serial Number
and Model
Number Plates
3.3
Positioning the Liebert FS
3.3.1
Moving the Liebert FS
When moving the unit a short distance, the Liebert FS may be rolled on its built-in casters (see
Figure 13) to its location.
!
CAUTION
Before moving the Liebert FS across a floor, determine whether the surface will support the
unit’s weight—1,462 lb. (663kg) as shipped; 1,300 lb. (590kg) uncrated.
Figure 13 Liebert FS cabinet caster location
Casters on each corner
(for moving unit short
distances only)
When moving the unit a longer distance or over rough flooring, move the Liebert FS with a forklift or
similar equipment to facilitate the relocation and to reduce vibration of the unit.
!
3.3.2
CAUTION
Ensure that the handling equipment is rated for the weight of the Liebert FS—1,462 lb.
(663kg) as shipped; 1,300 lb. (590kg) uncrated.
Storing the Liebert FS for Delayed Installation
If the equipment will not be installed immediately, it must be stored indoors where the temperature
stays within -4°F to 176°F (-20°C to 80°C) and the humidity is no higher than 95% (non-condensing).
16
Installation
4.0
INSTALLATION
The Liebert FS system design and safety characteristics allow for a relatively simple and quick installation. The system is designed to be rolled or lifted into place and bolted to the floor using Liebert's
mounting kit, included with the system. The mounting kit in most cases does not require any special
floor preparations (see3.0 - Unloading and Unpacking).
!
CAUTION
!
CAUTION
!
CAUTION
The Liebert FS system must be installed in accordance with the instructions and drawings in
this manual.
Never attempt to install or power up any unit suspected of damage during shipment.
The Initial System Startup must be performed ONLY under the supervision of a
Liebert-certified service technician to ensure proper system operation. Failure to abide by
instructions provided herein may void your warranty.
Contact your local Liebert sales representative or Liebert at 1-800-LIEBERT to arrange for
system startup.
Figure 14 Dimensions, general layout
Top
Control
Panel
71-1/8"
(1801mm)
Bottom
25"
(636mm)
Front
32-1/2"
(828mm)
Right Side
12-100120-09
17
Installation
Figure 15 Internal layout
Factory-Integrated
Circuit Breaker
Fan
Data
Control
Module
Versatile
Interface
Board
Magnetic
Levitation
Module
Inductor
Capacitor
Module
71-1/8"
(1807mm)
Power
Conversion
Module
Flywheel
Module
25"
(636mm)
32-1/2"
(828mm)
Front
(door open)
Right Side
(panel removed )
NOTE
The Liebert FS is designed for front-access-only for installation and maintenance. While the
likelihood of repair is minimal, some repair procedures require side and/or rear access.
Normally, the easiest way to handle this is to disconnect the power and control wiring and roll
the unit out into an open area on its casters. While it is acceptable, under certain
circumstances, to connect the Liebert FS to its companion UPS unit through the sides of the
Liebert FS and UPS cabinets rather than through external conduit, repair access to the Liebert
FS unit will be easier to facilitate if through-cabinet wiring is not installed.
18
Installation
4.1
Cabinet Floor Mounting
NOTE
Before beginning, ensure that the floor where the Liebert FS will be mounted meets the floor
loading specifications in 2.3 - Flooring Requirements.
• For placement on concrete, masonry or stone floors, see 4.1.1 - Concrete, Masonry or Stone
Floor Mounting.
• For placement on wood floors, see 4.1.2 - Wood Floor Mounting.
• For placement on raised floors, see 4.1.3 - Raised Floor Mounting.
Figure 16 Floor mounting
Liebert
EMERSON
Network Power
Floor Mounting
Bracket
NOTE
All drawings referred to in this section are in Appendix D.0 - Installation Drawings.
19
Installation
4.1.1
Concrete, Masonry or Stone Floor Mounting
Mounting Kit for Concrete, Masonry or Stone Floors
Liebert has included a complete anchoring kit with each Liebert FS for surface mounting. The kit is
intended to securely fasten the Liebert FS to its intended location for operational safety and seismic
requirements.
This kit includes (items depicted in Figure 150):
•
•
•
•
•
•
•
•
Two (2) cabinet mounting brackets (from shipping pallet)
Four (4) concrete expansion anchors
Two (2) drop-in hex head anchor bolts
Two (2) washers for anchor bolts
One (1) masonry drill bit
One (1) floor mounting template (Figure 149)
Two (2) drop-in hex flange anchor bolts
One (1) setter rod or drive pin (specifically designed for measuring hole depth and for expanding
the anchors)
• Four (4) hex bolts from shipping package, each 1/2" diameter and 3/4" long (12.7mm diameter x
20mm long)
Mounting Tools
These tools are needed for the mounting the Liebert FS on the floor:
•
•
•
•
•
•
•
•
Concrete drill with 1/2" (12.7mm) minimum chuck size
Masonry drill bit (included in mounting kit)
Masonry drill bit—used for pilot hole—for example, 1/8" (3.2mm) diameter
Setter rod (included in mounting kit)
Hammer or mallet, 16 oz. (0.5kg) or larger
Shop vacuum cleaner (to remove dust from hole when drilling)
3/4" (19mm) combination wrench
18mm combination wrench
Concrete, Masonry or Stone Floor Mounting Instructions
To mount the Liebert FS cabinet on the floor:
1. Prepare a clean, level, finished surface, free of obstructions, for installation of the mounting kit.
2. Tape the floor mounting template mounting template (Figure 149) to the installation location.
3. Using a bit smaller than the one provided in the mounting kit, drill a pilot hole at each of the four
places marked with an “X” on the template.
4. Remove template and continue with larger drill bit provided.
Figure 17 Floor mounting template layout
16"
(406mm)
X
X
Drill 4 holes, each
2" (51mm) deep,
with 5/8" masonry bit
X
29-1/2"
(749mm)
X
Front of Liebert FS
20
Installation
5. Drill 2" (51mm) deep holes in prepared surface using the drill bit included in the kit per bolt
pattern described in Figure 149 - Floor mounting template. The setter rod should be used as a
depth gauge to ensure proper depth. The setter rod is marked with two circles indicating the
maximum and minimum hole depth allowed (see Figure 18).
If a hole is drilled too deep, refill the hole with debris to the achieve proper depth.
Figure 18 Checking hole depth
Setter Rod (provided)
Depth Marks
Concrete Floor
2.05"
(52mm)
6. Insert four (4) drop-in concrete expansion anchors into drilled holes.
Figure 19 Inserting anchors
Insert anchor flush with floor .
Use hammer if required.
7. Tap anchors into drilled holes using hammer or mallet. When top of anchor is flush with
mounting surface, use setter rod to expand and secure.
Figure 20 Expanding anchors
Strike with
hammer
to set plug
21
Installation
8. Match mounting brackets with the holes on the bottom of the cabinet (see Figure 21). Make sure
that the bracket holes align with the mounting spots on the underside of the cabinet and secure
the brackets with the four (4) 1/2" diameter x 3/4" long (12.7mm diameter x 20mm long) hex bolts
retained from the shipping package. Tighten the bolts with a torque of 40 foot-pounds (54 N-m).
Figure 21 Securing mounting brackets to the cabinet
Bolt securing bracket
to cabinet
9. Insert the two (2) hex flange bolts in the rear anchors, where the back of the cabinet will be.
Complete tightening of the rear bolts should result in 1/2" (12.7mm) gap between bolt flange and
floor (see Figure 22 and Figure 134). The rear bolts must be tightened to 20 foot-pounds
(27 N-m) of torque. Bolt height or length may need to be adjusted if mounting surface is uneven or
if mounting bracket does not slide beneath bolt flange.
10. Position and align cabinet and bracket slots with the newly inserted bolts at rear and position
cabinet such that bolts fit in bracket slots (see Figure 22).
Figure 22 Mounting rear bolts—rear side of cabinet
1/2"
(12.7mm)
floor to
flange
22
Installation
11. Insert and begin tightening two (2) hex head bolts with one washer each through bracket
mounted at front of cabinet into anchor inserts in mounting surface (see Figure 23).
Figure 23 Mounting front bolts—front side of cabinet
12. Check the bubble level on the floor of the cabinet on the right hand side of the Power Conversion
Module (see Figure 24). The Liebert FS is sufficiently level when the bubble is within the outer of
the two circles. If the bubble is outside the outer circle, use the leveling feet to adjust until bubble
is within the outer circle.
Figure 24 Bubble level
Bubble
level
13. Once the cabinet is level, firmly tighten the front bolts to drop-in anchors as shown in
Figure 134. The front bolts must be tightened to 40 foot-pounds (54 N-m) of torque.
23
Installation
4.1.2
Wood Floor Mounting
Determine which of these cases applies to your installation:
• For wood flooring over concrete, follow the instructions in 4.1.1 - Concrete, Masonry or Stone
Floor Mounting.
• For wood flooring on joists, follow the instructions in this section.
Wood Floor Mounting Parts
• Two (2) cabinet mounting brackets (previously secured Liebert FS cabinet to shipping pallet)
• Four (4) (1/2" diameter x 2-1/2" long) [or 12.7mm diameter x 63.5mm] lag screws (not included in
mounting kit) are recommended
• One floor mounting template, see Figure 149
• Four (4) 1/2" diameter x 3/4" long (12.7mm diameter x 20mm long) hex bolts (from shipping package—see 3.2.2 - Unpacking)
Wood Floor Mounting Tools
The following tools are needed for the cabinet wood floor mounting:
•
•
•
•
•
•
Electric drill
1/4" (7mm) drill bit
Drill bit—used for pilot hole—for example, 1/8" (3.2mm) diameter
Shop vacuum cleaner (to remove dust from hole when drilling)
3/4" (19mm) combination wrench
18mm combination wrench
Wood Floor Mounting Instructions
Installation in wood floor on joists does not require drop-in anchors.
1. Prepare a clean, level surface, free of obstructions, for installation of the mounting kit.
2. Tape the floor mounting template (Figure 149) to the installation location.
3. Drill pilot holes, remove the template and use a 1/4" (7mm) drill bit to drill holes 2.5" (64mm)
deep.
!
CAUTION
Ensure that holes are centered in the joist.
4. Match mounting brackets with holes under base of cabinet (see Figure 21). Make sure that the
bracket holes align with the mounting spots on the underside of the cabinet and secure brackets
with the four hex bolts retained from the shipping package. Each bolt is 1/2" diameter x 3/4" long
(12.7mm diameter x 20mm long). Tighten the bolts with a torque wrench at 40 foot-pounds
(54 N-m).
5. Insert two lag screws through bracket mounted at rear of cabinet leaving head with 1/2" (12.7mm)
gap above floor (see Figure 22).
6. Position and align cabinet and bracket slots with the newly drilled holes at rear and position
cabinet such that bolts fit in bracket slots (see Figure 22).
7. Insert two (2) lag screws through bracket mounted at front of cabinet (see Figure 23).
8. Check the bubble level on the floor of the cabinet on the right hand side of the Power Conversion
Module (see Figure 24). The Liebert FS is sufficiently level when the bubble is within the outer of
the two circles. If the bubble is outside the outer circle, use the leveling feet to adjust until bubble
is within the outer circle.
9. Once the cabinet is level, firmly tighten the front lag screws to a torque 40 foot-pounds (54 N-m).
24
Installation
4.1.3
Raised Floor Mounting
Raised Floor Mounting Kit
Liebert has included a complete anchoring kit with each Liebert FS for surface mounting. The kit is
intended to securely fasten the Liebert FS to its location for operational safety and seismic requirements.
The anchoring kit includes:
• One floor mounting template, Figure 149
• 2 cabinet mounting brackets
• 4 drop-in hex flange bolts, each 1/2" diameter, 3" long (12.7mm, 76.mm)
• 4 washers (1/2" hole and 2" outer diameter) for hex flange bolts
• 4 lock washers for hex flange bolts
• 4 nuts for hex flange bolts, each 1/2" (12.7mm)
• 4 hex bolts, each 1/2" diameter, 3/4" long (12.7mm diameter, 20mm long) retained from shipping
package (see 3.2.2 - Unpacking)
Raised Floor Mounting Tools
The following tools are needed for the cabinet raised floor mounting:
• Electric drill with 1/2" (12.7mm) minimum chuck size
• 5/8" (16mm) drill bit
• Drill bit—used for pilot hole—for example, 1/8" (3.2mm) diameter
• 3/4" (19mm) combination wrench
• 18mm combination wrench
Raised Floor Mounting Instructions
To mount the Liebert FS cabinet on the floor:
1. Prepare a clean, level finished surface, free of obstructions, for installation of mounting kit.
2. Tape the floor mounting template (see Figure 149) to installation location, pre-drill a pilot hole,
then remove paper and continue with 5/8" (16mm) drill bit.
3. Match mounting brackets with holes under base of cabinet (see Figure 21). Make sure that the
bracket holes align with the mounting spots on the underside of the cabinet and secure brackets
with the four 1/2" diameter x 3/4" long (12.7mm diameter x 20mm long) hex bolts retained from
the shipping package. The bolts must be tightened to 40 foot-pounds (54 N-m) of torque.
4. Position and align cabinet and bracket slots with the newly drilled holes (see Figure 22).
5. Insert four drop-in hex flange bolts through bracket mounted at front and rear of cabinet (see
Figure 23).
Figure 25 Raised floor mounting
Large diameter washer
2"
(50mm) dia .
Lockwasher
1/2" (12.7mm)
dia. steel bolt
25
Raised
floor
Installation
6. Attach a large diameter washer, a lock washer and a nut to each hex flange bolts as described in
Figure 25 and Figure 155.
7. Check the bubble level on the floor of the cabinet on the right hand side of the Power Conversion
Module (see Figure 24). The Liebert FS is sufficiently level when the bubble is within the outer of
the two circles. If the bubble is outside the outer circle, use the leveling feet to adjust until bubble
is within the outer circle.
8. Once cabinet is level, firmly tighten down all hex flange bolts with nuts. The bolts must be
tightened to 40 foot-pounds (54 N-m) of torque.
4.2
Wiring Connections
4.2.1
General Wiring Considerations
!
CAUTION
A qualified electrical contractor must perform all electrical connections. The wires (DC power,
ground, upgraded status/control and auxiliary power supply) that connect the Liebert FS
system(s) to the UPS system are field-supplied or by Liebert as an option. Wire size and
installation must comply with all applicable local, regional and national regulations (e.g.,
National Electric Code for USA).
The electrical connections to the Liebert FS are:
• DC power
• Status/control (upgraded)
• Ground
• Auxiliary backup power
• Remote monitoring—optional
Figure 26 Liebert FS cabinet with UPS interconnection kit
Ground Terminal
DC Power
Terminals
Rear
Front
Fan Coil Module
Circuit
Breaker
Manufacturer’s
Connection
Status/Control
Terminal Block
(upgraded)
Power and Status/Control wiring must be run in separate conduits or cable trays. Refer to Appendix
D.0 - Installation Drawings for locations of the various electrical connections between Liebert FS
system(s) and UPS system.
!
CAUTION
Power and Status/Control wiring must be separated.
26
Installation
!
!
!
CAUTION
Do not cut entry holes for conduit while the access plates are still set on the top of the
Liebert FS cabinet. Remove the access plates from the cable-access areas in the top of the
Liebert FS cabinet prior to cutting entry holes in them.
CAUTION
After reinstalling access plates, be certain that no foreign matter (metal shavings, insulation
or wire fragments, etc.) remains inside the Liebert FS. Likewise, be certain to block any
“extra holes” in the plates through which foreign matter (or rodents) could later enter the
Liebert FS.
CAUTION
The instructions for installation of DC Power AND Status/Control connections vary according
to the type of UPS interconnection kit that is integrated into your Liebert FS unit.
Figure 27 Liebert FS with circuit breaker mounting plate and access panels for DC and control wiring
connections
DC and Ground
Connections
Access Panel
Control and
Communication
Access Panel
TOP VIEW
Circuit Breaker
Mounting Plate
Figure 28 Typical circuit breaker wiring for DC connections (view from rear of circuit breaker)
POS
POS
NEG
NEG
27
Installation
4.2.2
DC Power Connections
The instructions for installation of DC power connections vary according to the type of UPS interconnection kit integrated into your Liebert FS unit. Follow the installation instructions in Appendix
A.0 - UPS Interconnection Kits for the relevant UPS interconnection kit installed in your unit.
4.2.3
Status/Control Connections
The instructions for installing Status/Control connections vary according to the type of UPS interconnection kit that is integrated into your Liebert FS. Follow the installation instructions in Appendix
A.0 - UPS Interconnection Kits for the relevant UPS interconnection kit installed in your unit.
4.2.4
Ground Connections
A ground connection is available on the Liebert FS (see Figure 29). The electrical contractor must
ensure that the Liebert FS is effectively grounded to UPS chassis or UPS ground terminal. The
ground connection must be as short as possible. The maximum ground wire size is 1/0 AWG - 600VDC
wire (54mm2 wire section). Wire size and installation must comply with all applicable local, regional
and national regulations (e.g., National Electric Code for USA). Check all connections with Multimeter to verify ground continuity. (Refer also to Appendix E.1 - Ground Test Procedure.
!
CAUTION
Ensure that all grounds are secure and free of corrosion. Proper grounding is necessary for
optimum performance, safety and reliability.
Figure 29 Ground connection on the Liebert FS
Ground Terminal
Locations (DC
ground and filter
caps if required)
Side panel
removed for
clarity.
The tightening torque for the ground connections must be in accordance with Table 3. Use these values unless the equipment is labeled with a different torque value.
Table 3
Tightening torque for ground connection
Ground Wire Gauge
Tightening Torque
AWG
Approximate metric
equivalent wire section (mm2)
Inchpounds
N-m
4
2
1
1/0
21
34
42
54
110
150
150
180
12
17
17
20
28
Installation
4.2.5
AC Auxiliary Control Power Supply Connections
The AC auxiliary power supply connections to the Liebert FS are made through the auxiliary power
fused disconnect on the mounting plate above the inductor-capacitor module and to the right of the
optional VIB and DCM modules (see Figure 30). See Appendix F.0 - Auxiliary Backup AC
Power Supply for details on the purpose of the auxiliary AC power supply.
Figure 30 Service panel location
Service Panel (cover removed);
Provides access to fused disconnect
and the optional VIB and DCM.
The Auxiliary Power Fused Disconnect (see Figure 31) accommodates the connection of an AC wire
(Line, Neutral, Ground) and is rated for 110/230 VAC - 50/60 Hz. Open the circuit while wiring, check
the fuses and then close it. The AC wire must be connected to the auxiliary power fused disconnect
from the top to a dedicated AC circuit rated for 400VA with branch circuit protection. This AC outlet
must be connected to a protected low-voltage (110VAC-230VAC, 400VA) source. A qualified electrical
contractor should make this connection permanent.
The AC wire is field-supplied. It must conform to all applicable local, regional, national regulations,
such as the National Electric Code for USA. An 18 AWG (0.82 mm2) cable is recommended for this
connection.
Tighten the connections for the 18 AWG cable (0.82 mm2) to 15 inch-pounds (1.6N-m).
Figure 31 Auxiliary backup power connections
AC Auxiliary
Power Fused
Disconnect
Location of MCM
(cover plate
removed)
!
CAUTION
The AC power supply must remain connected at all times. Precautions must be taken to
ensure that the connection is not broken. Disconnection may cause damage to the equipment.
29
Installation
The AC wire is field-supplied. Wire size and installation must comply with all applicable local,
regional and national regulations (e.g., National Electric Code for USA). An 18 AWG cable (approximate metric equivalent: 0.82mm2 wire section) is recommended for this connection.
Figure 32 shows the auxiliary power fused disconnect and terminals 1, 2 and 3, the landing points
for the AC wire on the Liebert FS side. Open the circuit while wiring, check the fuses and close afterwards when ready to test or start up Liebert FS.
Figure 32 Auxiliary power fused disconnect with connection points for AC wire
Terminal 1
Neutral
Terminal 2
Line
Terminal 3
Ground
Fused disconnect
The AC wire should be pulled from the left (top access recommended) and through the rear top access
panel (see Figure 33). Run the AC wire along the underside of the top cabinet frame rail from the
rear to the front of the cabinet. Terminate the AC wire at the fused disconnect (pictured in Figure 32;
see also Figure 26).
Figure 33 Top access panel
Top access
panel for
AC auxiliary
power supply
connections
Front of Liebert FS
30
Installation
4.2.6
Remote Monitoring Connections—Optional
The Liebert FS standard unit does not include remote monitoring connections. Remote monitoring
capabilities are provided as an option see Figure 34). If your unit is equipped with the optional Data
Collection Module (DCM), refer to the installation and configuration instructions in Appendix B.0 Data Collection Module.
Figure 34 Remote monitoring (DCM) connections (inside cabinet front door)
AC Auxiliary
Power Fused
Disconnect
Location of MCM
(cover plate
removed)
4.3
Startup Considerations
!
CAUTION
The Initial System Startup must be performed ONLY under the supervision of a
Liebert-certified service technician to ensure proper system operation. Failure to abide by
instructions provided herein may void your warranty.
Contact your local Liebert representative or call 1-800-LIEBERT to arrange for system
startup.
31
System Overview
5.0
SYSTEM OVERVIEW
5.1
Detailed System Description
Figure 35 Liebert FS front view
Front View (door open,
right side panel removed)
UPS Interconnection Kit
LCD
Control
Panel
Versatile Interface
Board (option)
Data Collection
Module (option)
Motor Generator
Filter Assembly
Magnetic Levitation
Module (above
flywheel module)
Power
Conversion
Module
Flywheel Module)
Air Filter
(optional)
Built-In Casters, 4
32
System Overview
5.1.1
System Module Description
The Liebert FS is a modular system composed as follows:
•
•
•
•
•
•
Control Panel
UPS Interconnection Kit
Power Conversion Module
Main Control Module
Flywheel Module
E-Stop (optional-special order)
Components are illustrated in Figure 35.
Control Panel
The Liebert FS uses a control panel as the primary means for an operator to interface with the system.
UPS Interconnection Kit
The UPS Interconnection Kit is a module that enables the physical interconnection of the Liebert FS
and a UPS system. There are several versions that vary, depending on the UPS model.
The Liebert FS is delivered with a UPS interconnection kit consisting of a circuit breaker for connection of the positive and negative terminals coming from the UPS DC bus or from an external disconnect switch.
Power Conversion Module
The power conversion module is a bi-directional power electronics-based power converter capable of
sourcing or sinking power to and from the UPS DC bus.
While performing the Liebert FS’s backup power mission, the power conversion module converts
“variable frequency - variable voltage” AC power from the Liebert FS’ motor-generator and delivers
regulated DC voltage output to the UPS DC bus.
Conversely, for the Liebert FS’s needs in charging power, the power conversion module converts DC
power from the UPS DC bus into “variable frequency - variable voltage” AC power for the Liebert FS’
motor-generator.
Main Control Module
The Main Control Module provides the overall control of the Liebert FS as well as the specific control
for:
• Motor-generator
• Active magnetic levitation hardware
Flywheel Module
The Flywheel Module houses several major components:
• Motor-generator—synchronous reluctance technology
• Rotating group—high-speed carbon composite flywheel, high-speed shaft and rotor of the motorgenerator
• 5-axis active magnetic levitation hardware
• Molecular vacuum pump
E-Stop
The E-Stop is an Emergency Stop that allows the Liebert FS to disconnect from the UPS. The E-Stop
is a CE requirement for systems shipping to Europe (and other areas requiring the CE Mark). The
feature is available elsewhere as an option. Two choices are available for how the E-Stop is powered,
internally or externally. If E-Stop is activated, Liebert FS will enter a self-discharge and shutdown
mode.
33
System Overview
5.1.2
Power System
The electrical system of the Liebert FS is shown in Figure 36. The schematic shows the Magnetic
Levitation Module [see 5.1.7 - Magnetic Levitation Module (MLM)]. The pre-charge resistor and
contactor which limit the inrush current into the DC bus capacitors. The six-pulse IGBT power converter (IGBT Power Conversion Module (PCM) on page 36) which is controlled by the Power
Conversion Module Controller (Power Conversion Module on page 33) and which also monitors
and controls the operation of the entire system. These components are housed within the Power Conversion Module. The Flywheel Module is shown as a cross-section to illustrate the rotating group and
the synchronous reluctance motor-generator.
Figure 36 Electrical system schematic
Flywheel Module
IGBT Power Converter
+
Soft Start
DC Monitoring
Motor Generator Controls
5.1.3
AU Auxiliary
Backup
Control
Panel
COM
Power Conversion Module Controller
Position
Sensors
Speed
Sensors
-
Temperature
Sensors
To UPS
Battery
Input
Magnetic Levitation
Module
Remote Monitoring
& Controls (Optional )
System Performance
The maximum output power of the Liebert FS varies according to the duration required. This is illustrated in Figure 5 (output power versus time). Increased power, duration or redundancy may be
achieved by adding units in parallel as shown in Figures 2 through 4.
34
System Overview
5.1.4
User interfaces
Control Panel
The Liebert FS uses a Control Panel as the primary means for an operator to interface with the system. Operating parameter values are displayed and updated in real time. Alarm states and system
notices are also displayed when they occur. User configurable system parameters are adjusted via the
Control Panel.
Data Collection Module (DCM)
An optional software and hardware package that reads data from the Liebert FS is available. The
data is stored and then can be transmitted through an RS-232 port, over a LAN (Local Area Network)
or over the Internet, enabling a diagnostic reporting capability.
Versatile Interface Board (VIB)
An optional software and hardware package is available that allows for remote monitoring and control; via isolated auxiliary contacts:
Monitored Information
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
OFF Mode
STARTUP Mode
CHARGE Mode
State of Charge (SOC) = 0%
State of Charge (SOC) = 12.5%
State of Charge (SOC) = 25%
State of Charge (SOC) = 37.5%
State of Charge (SOC) = 50%
State of Charge (SOC) = 62.5%
State of Charge (SOC) = 75%
State of Charge (SOC) = 87.5%
Full Charge (SOC) = 100%
DISCHARGE Mode
SHUTDOWN Mode
WARNING Mode
FAULT mode
Rotor Hot Standby
Control Commands
• Startup
• Shutdown
• Clear Fault
5.1.5
UPS Interconnection Kit
The UPS Interconnection Kit (IKIT) is a module of the Liebert FS that simplifies the interconnection
to a UPS system. There are different versions of the IKIT available that have been specifically developed for the UPS systems the Liebert FS can integrate with. The Liebert FS in the standard configuration is delivered with an IKIT consisting of a fused Power Terminal Block for connection of the
Positive and Negative terminals coming from the UPS DC bus or from an external disconnect switch.
35
System Overview
5.1.6
Power Conversion Module
Power Conversion Module Controller (PCMC)
The Power Conversion Module Controller is located within the Power Conversion Module. The PCMC
uses microprocessor-controlled logic to control the six pulse IGBT solid state switches and monitor the
active magnetic levitation system.
These operations are firmware controlled eliminating the need for manual adjustments. The logic
includes a self-test and diagnostic circuitry to identify any faults. Diagnostics are performed via a PC
through the RS232 communication port or through the control panel located on the front of the Liebert FS.
IGBT Power Conversion Module (PCM)
The PCMC provides the overall control of the Liebert FS as well as the specific control for the synchronous reluctance motor generator via the IGBT solid-state switches within the Power Conversion
Module.
The Power Conversion Module is a bi-directional system capable of sourcing or sinking power to and
from the stator. It converts variable frequency, variable voltage from the stator and delivers a constant voltage DC output. Conversely, it converts DC power from the UPS System DC Bus to variable
frequency, variable voltage output to the stator as directed by the PCMC to increase the speed of the
synchronous reluctance motor-generator.
When delivering DC power, the output of the synchronous reluctance generator is rectified to DC by
passing the high frequency AC current through a solid-state power conversion device. The DC output
voltage of the Liebert FS has less than 2% Vrms ripple.
The voltage and frequency are adjusted using Pulse Width Modulation. The IGBT switches operate at
a frequency of 18 kHz to produce the smooth sinusoidal current waveform to and from the motor generator. This is smoothed out further using an inductive and capacitive filter.
36
System Overview
5.1.7
Magnetic Levitation Module (MLM)
The Magnetic Levitation Module provides control of the active magnetic levitation hardware.
The Liebert FS has a unique active magnetic levitation system that fully levitates the flywheel-rotating group, allowing the flywheel to rotate without any physical contact. This has a number of advantages over mechanical bearing systems:
• Reduced drag- Mechanical bearings have a drag that is proportional to the square of the speed.
The levitation system developed by Liebert uses the same power regardless of speed.
• Reliability and zero maintenance- The levitation system ensures there is no contact between the
rotating parts and the housing and therefore there are no components to wear out. This ensures
the unit will operate maintenance free for the life of the system.
The levitation system, works by measuring the displacement using a capacitive sensor, if the distance
needs to be adjusted; the current to the electromagnet is altered to change the displacement, each
axis is measured and controlled separately with its own capacitive sensor, electromagnet and feedback loop which, is controlled by the MLM. This is all done using analog control so it is very fast acting and reliable. There are 5 different circuits working independently, these are: Radial: Upper X, Y;
Lower X, Y and Axial: Z Only
The principle of operation is the same in each case. The upper radial Y-axis is shown in Figure 37.
Figure 37 Schematic of the levitation system
Z
Y
X
AMPLIFIER
ELECTRO
MAGNET
AMPLIFIER
ELECTROMAGNET
ROTOR
CAPACITIVE
DISPLACEMENT
MEASUREMENT
CONDITIONER
CONTROLLER
DISPLACEMENT
SETPOINT
DISPLACEMENT SIGNAL
INFRARED EMITTER
Active Magnetic Levitation Hardware
The electromagnets and capacitive displacement sensors that provide the active magnetic levitation
are located within the flywheel module. See 5.1.7 - Magnetic Levitation Module (MLM) for a full
description of their operation.
37
System Overview
5.1.8
Flywheel Module
The Flywheel Module houses several major components:
• The Rotating Group (high-speed carbon composite flywheel, high-speed shaft and rotor of the
Motor-Generator)
• The Motor-Generator (synchronous reluctance technology)
• The Molecular Vacuum Pump
• Flywheel Sensors
• Active Magnetic Levitation Hardware
• Safety System
Figure 38 Liebert FS flywheel module
Axial Electromagnet
Upper Radial
Electromagnet
Inner Housing
Molecular Vacuum
System
Carbon Fiber
Flywheel
M-G Stator
Synchronous Reluctance
4-pole M-G Rotor
Liquid Cooling
Passages
Lower Radial
Electromagnet
38
System Overview
5.1.9
Rotor/Flywheel—Rotating Group
The flywheel is made of carbon/glass composite. This is mounted on a metal shaft with integral
motor-rotor and together these components form the rotating group. The rotating group is magnetically levitated and centered so that it does not touch any other part while in normal operation.
Figure 39 Rotating group
5.1.10 Motor Generator
The rotor is positioned within the stator in such a way that the rotor and stator provide the
motor-generator function of the Liebert FS. The stator is liquid cooled and operates within a housing
in which air has been evacuated. Together the stator and rotor operate as a synchronous reluctance
motor-generator produces enough power for the system to supply its own internal demand and to supply to the output DC bus up to the rated power. The illustration in Figure 40 shows the four poles of
the synchronous reluctance machine.
Figure 40 Cross-section of the synchronous reluctance motor rotor
39
System Overview
5.1.11 Vacuum System
During manufacture, the vacuum chambers are evacuated and baked to remove water vapor. The vacuum system is then permanently sealed off to prevent any air entering the system and to remove the
possibility of accidental loss of vacuum. The Liebert FS does not require an external vacuum pump to
maintain a suitable vacuum level; the vacuum system instead relies on absorbers to maintain a rough
vacuum within the upper chamber. A zero-maintenance molecular drag pump acts with the flywheel
shaft to maintain a high-vacuum in the lower chamber, as shown in Figure 41. Vacuum levels of
much less than 100 microTorr (10-7 atmosphere) are maintained in the lower chamber. The absorber
material only needs to be recharged or changed, once every 15 years.
Figure 41 Vacuum system operation
Air and Water Vapor
Upper Chamber
Molecular Drag Pump
Rotating Shaft
Lower Chamber
40
System Overview
5.1.12 Flywheel Sensors
Speed
The speed detection system uses an infrared emitter and a sensor to detect the rotation of the shaft. A
hole drilled through the shaft allows light to pass and is detected on the opposite side by an infrared
detector. This signal is used to detect the rotor angle, the speed and any over speed condition. The
pulsed signal passes into the 6711 DSP to be converted into a speed signal. This is then passed to the
2812 DSP. The 2812 checks for over-speed and shuts down the power electronics if this occurs. If
either of the processors lock-up, the rotor will slow down, this guarantees that on over-speed cannot
occur.
Temperature
The stator and rotor temperature detectors are thermocouples and are both conditioned in a similar
way. The stator sensor is a Type J thermocouple potted into the stator windings. The rotor sensor is a
non-contact type sensor that detects the temperature of the rotor surface and gives an output in a
Type J thermocouple format.
Figure 42 Schematic for the speed and temperature sensors
NON- CONTACT
ROTOR
TEMPERATURE
SENSOR
J TYPE
THERMOCOUPLE
OUTPUT
STATOR
WINDINGS
ROTOR
STATOR
TEMPERATURE
SENSOR
J TYPE
THERMOCOUPLE
AMPLIFIERS, CONDITIONERS,
LINEARIZERS AND COLD
JUNCTION COMPENSATION IN
ONE CHIP
INFRARED
DETECTOR
CONDITIONER
AND DIVIDE BY 2
SUPPLY
FROM
CIRCUIT
BOARD
DSP 6711
TIMER INPUT
DETERMINES
SPEED
DSP 2812
DETECTS
OVERSPEED
41
System Overview
5.1.13 System Safety
Every composite flywheel is inspected, spin balanced and tested to 110% over-speed in accordance
with NEMA guidelines. A patented dual-wall safety system ensures that in the unlikely event a flywheel were to separate during operation, the inner housing would retain the carbon fiber. As the carbon fiber separates, it will expand and transfer its torque to the inner housing. The inner housing is
then allowed to rotate inside the outer housing. The cooling fluid in the outer housing, which surrounds the inner housing acts as a dynamic brake. The stored energy is released in a controlled manner as the flywheel / inner housing comes to a rest. The outer housing holds the entire safety system
and acts as a reservoir for the cooling fluid
The Liebert FS has been previously tested under the following fault conditions with no adverse safety
effects:
•
•
•
•
•
•
•
Motor-generator AC short circuit
DC short circuit
Power Conversion Module failure
Magnetic Levitation System failure
Composite rotor failure
Motor Rotor Failure
Loss of Vacuum
Figure 43 Cutaway flywheel module
Outer Housing
Rotating Group
Inner Housing
Coolant
5.1.14 Cabinet
The Liebert FS is a compact design housed in a free-standing cabinet with a NEMA 1 construction
rating or IEC equivalent. No space is required between the back or sides of the cabinet and any walls.
The front clearance of 36" per the National Electrical Code is required. The Liebert FS accommodates
top (standard) and side entry cables. The Liebert FS can be rolled into place and go through standard
doors.
42
System Overview
5.1.15 Ventilation and Cooling
The Liebert FS stator and power electronics are liquid cooled with a liquid-to-air radiator. The radiator within the Liebert FS package is designed for natural and forced air-cooling. Air inlets are provided from the bottom front of the Liebert FS enclosure. Air exhaust is from the top of the unit. Air
filters are provided as an option. A minimum 12" clearance overhead is required for the exhaust airflow.
The Liebert FS was designed with reliability in mind, the radiator is positioned to take advantage of
natural cooling and forced-air is only used when there is an elevated temperature. This also applies to
the circulating pump for the coolant, which is a highly reliable magnetically coupled centrifugal pump
that is powered with a brushless DC motor. This pump operates only when there is an elevated temperature within the stator or the PCM, this extends the life of the pump to the point that it will continue to operate over the life of the unit.
5.2
List of System User-Configurable Parameters
In order to support a wide set of UPS integrations, the Liebert FS can be configured using the following operating parameters: See 6.0 - Operation for more information on these parameters and
instructions on system setup and entering parameters to system.
Charge Voltage (Vcharge)
Vcharge is the voltage threshold above which the Liebert FS begins to charge/recharge.
Vcharge must be set at least 10VDC greater than Vreg.
• Range: 360-600VDC
• Default setting: 520VDC
Regulation Voltage (Vreg)
• Vreg is the voltage setpoint at which the Liebert FS will regulate the DC bus voltage in Discharge
Mode
• Vreg must be set at least 10 VDC less than Vcharge.
• Range: 350-590VDC
• Default setting: 510VDC
Maximum Charge Current (Max Charge Current)
• Max Charge Current is the Maximum Current the Liebert FS is allowed to draw from the UPS
DC bus.
• Range—1-50A (typical operation requires a minimum of 3A or 5A)
• Default setting—20 A
Charge Conductance (Charge Amps/Volts)
Charge amps/volts is used to set the Liebert FS charging current drawn from the UPS DC bus based
upon how much the UPS DC bus voltage is above Vcharge and so without exceeding the Max Charge
Current.
• Range—0.1-10 A/V
• Default setting: 2 A/V
43
System Overview
Figure 44 Voltage and Inductance curve
DC Bus
Current
Overload : Constant Current
Discharge
Mode
Behavior: Voltage Source
User Adjustable Parameters :
1. Vcharge: 260V – 600V
2. Vreg: 250 V – 590 V
3. Charge Amps /Volt: 0.1A/V – 10A/V
4. Max Charge Current : 1A – 50A
Vcharge
Charge
Mode
Vreg
Charge
Amps/
Volt
Max Charge Current
Behavior: Current Sink
DC Bus
Voltage
The V-I (Voltage and Inductance) curve (see Figure 44) shows the performance characteristics and
modes of operation of the Liebert FS system based on the seven user-configurable system parameters.
Regulation Voltage Delta During Discharge (Vreg Delta 1)
Vreg Delta is the programmed amount of voltage drop from the beginning of discharge (SOC = 100%)
to the Vreg Delta TSOC.
• Range—from 0 to (Vreg - 250) VDC
(Ex: if Vreg = 500, then the Vreg Delta1 can be set between 0 and 250 VDC)
• Default setting—0 VDC
Regulation Voltage Delta Transition at State of Charge (Vreg Delta T SOC)
• Range—0-100%
• Default setting—0
44
System Overview
Regulation Voltage Delta During Discharge (Vreg Delta 2)
Vreg Delta 2 is the programmed amount of voltage drop from the Transition State of Charge to the
end of discharge (T SOC to the end of discharge (SOC = 0%)
• Range—From 0 to (Vreg - Vreg Delta1) VDC
(Ex: if Vreg = 500, and Vreg Delta1 = 50, Vreg Delta2 can be set between 0 and 200 VDC)
• Default setting—0VDC
NOTE
Programming of Regulation Voltage (Vreg) Delta User Configurable Parameters
• During a discharge the regulation voltage (Vreg) can be adjusted by setting the three
parameter set points described above; Vreg Delta 1, the Transition State of Charge (T SOC)
and Vreg Delta 2. (For more information on programming these parameters from the
Control Panel see 6.4.1 - Screen Tree Menu Functions)
• The Liebert FS allows for programming two different discharge slopes (Vreg Delta1 and
Vreg Delta2) and enabling a soft “handcuff” or transition before end of discharge.
(Ex: if T SOC = 20 then transition from Vreg Delta 1 to Vreg Delta 2 will take place when
80%, (Vreg TSOC), of the stored energy has been discharged, see Figure 45).
• Vreg Delta1 is used to program an initial slope from beginning of discharge to Vreg TSOC
over which the regulated voltage value will decrease and at which point a transition will
automatically occur to the secondary slope to 0% SOC at the Vreg Delta2 setpoint.
Figure 45 Vreg delta help screen
[2]V_REG******------------------------|
******
[5]DELTA1
V|
******------------O|
|** [6]DELTA2
L|
| **--------T|
|
|
|----------------+---+
100%
[7]TSOC 0%
5.3
Modes of Operation
The Liebert FS consists of a variety of operational modes. Each mode is based on a set of programmed
conditions. The Control Panel indicates the current mode and the status of that mode. Function keys
are enabled or disabled depending on the mode and status.
The Liebert FS modes are:
•
•
•
•
•
•
•
•
•
OFF
STANDBY
STARTUP
CHARGE
READY
DISCHARGE
SHUTDOWN
COAST
FAULT
The Liebert FS is programmed to operate in a variety of conditional modes. The modes and status for
each mode will be indicated on the control panel. The Liebert FS is set up to transition through the
various modes with no or minimal user intervention.
45
System Overview
5.3.1
OFF Mode
When the Liebert FS is initially powered on, it enters the OFF mode and magnetically levitates its
rotating group. A manual user command will make the system transition from OFF mode to STARTUP mode if all startup conditions are met.
NOTE
Startup conditions are:
• UPS DC bus voltage ≥ Vcharge and
• Status is “OK”.
The Liebert FS also will enter OFF mode at the end of a shutdown and will transition automatically
from SHUTDOWN mode to OFF mode.
5.3.2
STANDBY Mode
In STANDBY Mode, the Liebert FS will be ready for Startup but be in a STANDBY Mode waiting for
user initiation of STARTUP Mode (State of Charge = 0%). By pressing the STARTUP button “F1” at
that point the Liebert FS will automatically transition into STARTUP Mode.
Figure 46 STANDBY mode diagram
State of Charge < 0
State of Charge > 0
UPS DC Bus Voltage = Vcharge
0%
10 .5%
99
0%
The Liebert FS will be in STANDBY Mode as long as:
• Liebert FS’s SOC is less than 0%; and
• UPS DC Bus Voltage = Vcharge
• STARTUP has not been initiated
5.3.3
STARTUP Mode
In STARTUP mode, the Liebert FS will charge (increase flywheel speed) up to the minimum operating speed (State of Charge = 0%). At that point the Liebert FS will automatically transition into
CHARGE mode.
Figure 47 Startup mode diagram
State of Charge < 0
State of Charge > 0
0%
10 5%
.
99
0%
Note: UPS DC Bus Voltage ≥ Vcharge
The Liebert FS will be in STARTUP mode as long as:
• Liebert FS’s SOC is less than 0% and
• UPS DC Bus Voltage ≥ Vcharge.
NOTE
In STARTUP mode, the Liebert FS will not be capable of supporting the UPS DC bus.
In case the UPS DC bus voltage drops below Vcharge while in STARTUP mode, the Liebert FS will
transition automatically into COAST mode. As soon as the UPS DC bus voltage rises above Vcharge,
the Liebert FS automatically exits COAST mode and resumes STARTUP mode.
46
System Overview
5.3.4
CHARGE Mode
To charge the Liebert FS, the Liebert FS will draw power from the UPS DC bus to accelerate the flywheel (as long as the UPS DC bus voltage is higher than Vcharge). In this mode, the Liebert FS State
of Charge (SOC) will progressively increase from 0% to 100%.
Figure 48 CHARGE mode diagram
State of Charge < 0
State of Charge > 0
Note: UPS DC Bus Voltage ≥ Vcharge
0%
10 5%
.
99
0%
The Liebert FS will be in CHARGE mode as long as:
• Liebert FS’s SOC is between 0% and 100% and
• UPS DC Bus Voltage ≥ Vcharge.
NOTE
While in CHARGE mode, the Liebert FS will be capable of supporting the UPS DC bus.
5.3.5
READY Mode
When the SOC reaches 100%, the unit will automatically transition into the READY mode. This is the
mode in which the Liebert FS will spend most of its operating time. In this mode, the Liebert FS
maintains its State Of Charge greater than 99.5%. The Liebert FS’s SOC will be allowed to drift down
to SOC = 99.5%, at which point it will transition back into CHARGE mode and charge back up to
READY mode and SOC = 100%. During normal operation, the Liebert FS will continue to automatically transition between the READY and CHARGE modes to maintain a SOC between 99.5 and 100%
until either a DISCHARGE or SHUTDOWN is initiated.
Figure 49 READY mode diagram
State of Charge < 0
State of Charge > 0
0%
10 5%
.
99
0%
Note: UPS DC Bus
Voltage ≥ Vcharge
The Liebert FS will be in READY mode as long as:
• Liebert FS’s SOC is between 99.5% and 100% and
• UPS DC Bus Voltage ≥ Vcharge.
NOTE
While in READY mode—just as in CHARGE mode—the Liebert FS will be capable of
supporting the UPS DC bus.
47
System Overview
5.3.6
DISCHARGE Mode
Starting from either CHARGE or READY mode, the Liebert FS will enter the DISCHARGE mode if
the UPS DC Bus Voltage goes below Vcharge. In DISCHARGE mode, the Liebert FS will regulate the
DC bus at Vreg.
Figure 50 DISCHARGE mode diagram
State of Charge < 0
State of Charge > 0
Note: UPS DC Bus Voltage = Vreg
0%
10 5%
.
99
0%
The Liebert FS will be in DISCHARGE mode as long as:
• UPS DC Bus Voltage < Vcharge and
• Liebert FS’s SOC is more than 0%.
The Liebert FS will leave the DISCHARGE mode and transition into CHARGE mode if the UPS DC
bus recovers (UPS DC Bus Voltage = Vcharge) before the Liebert FS’s SOC reaches 0%. In case the
UPS DC bus doesn’t recover before the Liebert FS’s SOC reaches 0%, the Liebert FS will transition
into SHUTDOWN mode.
5.3.7
SHUTDOWN Mode
In SHUTDOWN mode, the flywheel will actively spin down.
There are two ways the Liebert FS can transition into SHUTDOWN mode, by a complete discharge
and by a user command.
Following a Liebert FS Discharge Down to SOC = 0%
This is the most common SHUTDOWN process. This occurs when the Liebert FS’s SOC drops below
0% and the UPS System DC Bus voltage is less than Vcharge. If the Liebert FS entered the SHUTDOWN mode after leaving DISCHARGE mode, the Liebert FS will automatically transition into
STARTUP mode provided the UPS System DC Bus voltage returns to a value greater than Vcharge
(i.e., when the electric grid returns or the standby generator supplies power to the UPS).
Figure 51 SHUTDOWN mode diagram - shutdown after full discharge
State of Charge < 0
Note: UPS DC Bus Voltage < Vcharge
State of Charge > 0
0%
10 5%
.
99
0%
48
System Overview
Following a User Command
In any mode, except OFF mode, the user may command the Liebert FS to transition in SHUTDOWN.
While in SHUTDOWN mode, the user will still be able to command the Liebert FS to transition into
CHARGE mode (if SOC > 0%) or STARTUP mode (if SOC < 0%), provided that the UPS System DC
bus voltage is greater than Vcharge.
Figure 52 SHUTDOWN mode diagram - user-initiated shutdown
State of Charge < 0
State of Charge > 0
5.3.8
0%
10 5%
.
99
0%
COAST Mode
A transition into COAST mode can occur when the UPS System DC Bus voltage drops below Vcharge
while the Liebert FS is in STARTUP mode. While in COAST mode, the Liebert FS is in an idling condition where it neither draws nor generates any power.
As soon as the UPS DC Bus Voltage rises above Vcharge, the Liebert FS will automatically exit
COAST mode and resume STARTUP mode.
After five minutes in COAST Mode, if the UPS DC Bus voltage has not risen above Vcharge, the
Liebert FS will automatically transition into SHUTDOWN Mode.
5.3.9
FAULT Mode
The Liebert FS includes self-test and diagnostic circuitry such that most systems malfunctions can be
identified. In case of a system malfunction, the Liebert FS will transition into FAULT mode.
While in FAULT mode, the Liebert FS is disabled—all power electronics are turned off. Most faults
are cleared automatically by the system without the need for user intervention. Some faults do
require user action to clear the fault or to notify Liebert Global Services. Refer to the 8.0 - Troubleshooting for more information).
NOTE
Depending on the nature of the fault, the Liebert FS may still be capable of supporting the UPS
DC bus. Refer to 8.0 - Troubleshooting for more information.
The Liebert FS is programmed to operate in a variety of conditional modes. The modes and status for
each mode will be indicated on the control panel. The Liebert FS is set up to transition through the
various modes with no or minimal user intervention. Figure 53 illustrates the various modes of operation.
49
System Overview
Figure 53 Typical operation modes
KEY #
MODE
DESCRIPTION
1
READY
Idle condition waiting for event
2
DISCHARGE
FS supporting the critical load
3
CHARGE
Charging to top speed
UPS Module
Grid Supply lost ,FS supporting the load
B
Generator Starts , A.T.S. transfers the load
C
FS fully charged ready to support the load
D
FS supports the load as the A .T.S. transitions back to grid supply
E
FS fully charged ready to support the load
A
AC Power Flow
Grid
A
V Generator
V Grid
V Load
GEN
ATS
B
C
D
E
AC
VOLTAGE
0 VAC
DC Bus Voltage
V Float
Vcharge
Vreg
DC
VOLTAGE
1
2
Power Flow
Flywheel
Module
480
VAC
FS
MODES
AC Power Flow
DC
3
1
TOP
SPEED
R.P.M.
MIN
SPEED
FS Speed
ZERO
SPEED
50
2
3
1
System Overview
5.4
Maintenance and Reliability
The Liebert FS is designed to require minimal preventive servicing and maintenance. There are no
user serviceable parts in the Liebert FS. Please contact a Liebert-Certified Technician before attempting to remove or service any components of the system. No bearings maintenance or replacement is
required over the life of the Liebert FS under normal operation conditions. No vacuum pump maintenance or replacement is required over the life of the Liebert FS under normal operation conditions.
The optional inlet air filter in the cabinet will need to be replaced when it is sufficiently dirty as to
reduce the flow of air into the cabinet. Ambient conditions at the installation site will determine the
frequency of replacement. The Liebert FS Flywheel Module is designed for fifteen-year service life
before first scheduled maintenance. At fifteen years, the vacuum absorbers should be replaced or
regenerated.
The reliability of the Liebert FS power electronics is consistent with UPS power electronics of comparable energy levels. The mechanical assemblies are of higher life and reliability than other commercially available flywheel systems due to the elimination of rolling element bearings and external
vacuum-pumping systems.
51
Operation
6.0
OPERATION
6.1
Operator Controls
The Liebert FS uses a Control Panel as the primary means for an operator to interface with the system. The Control Panel enables the operator to perform the following tasks:
Initial setup and adjustments to programmable parameters (access limited by Security
Access function):
• Set the Liebert FS Control Parameters
• Configure Liebert FS for operation with external equipment
Initial setup and adjustments to Security Access functions
• Set pass codes and access levels
Execute operational procedures:
• Startup and shutdown of the Liebert FS.
Quick view of operational status:
• View current Mode of Operation
• View current Status
Access System Status reports:
• Check temperatures and voltages
• Check vital system health indicators
Access System History
• Check number of discharges
• Check for total hours of operation
• Check for warnings and faults history
Monitor the power flow between the Liebert FS and a UPS and other Liebert FS meter
readings:
•
•
•
•
•
Monitor power flow from Liebert FS to the UPS DC Bus or from UPS to the Liebert FS
Monitor Liebert FS State of Charge
Monitor DC Bus Voltage
Determine if the critical load is being supplied power from the Liebert FS
Monitor charging after discharge
52
Operation
6.2
Control Panel
The Control Panel (see Figure 54) below represents the Control Panel on the Liebert FS. The diagram is labeled as a reference for the various keys, functions and data found on the Control Panel.
NOTE
(The actual locations of status indicators on the Control Panel display, corresponding to the
numbers below, may vary from Figure 54 depending on software version.)
Figure 54 Control panel view
8
10
9
11
D
RPM:
SOC:
SOC:
BUS:
PWR:
LIEBERT FS
See Table 4
for keyboard layout
7
6
5
4
3
MODE:
DISCHARGE
STATUS:
OK
MENU
SHUTDN
F1
F2
V U C P
50652
12
93.3%
500 V
190 .2kW
13
LOCK
14
F3
F4
F5
15
F6
!
I
17
2
0
1
2
3
1
.
4
5
6
-
7
8
9
16
18
X
19
NOTE
The control panel view is for reference only. Not all items will be enabled and visible on the
screen at the same time during operation
Navigating the control panel is a simple process that involves responses to user prompts displayed in
the control panel. Using the panel to operate the unit will be described further in this section.
Table 4
Keyboard
Location
Control panel keyboard layout (refer to Figure 54)
Keyboard
Location
Operation / Navigation Keys
Screen Indication Keys
1
Numerical Keypad
11
SOC: State of Charge Bar
2
LEDs used for Servicing
12
SOC: State of Charge Value
3
F2 Shutdown key - Main Screen
13
PWR: Bus Power
4
F1 Start Up key - Main Screen
14
F5 More Information key - Fault Screen
5
Soft Menus
15
F6 Menu key - Main Screen
6
STATUS: System status (see 6.2.3 System STATUS Indicators)
16
F3 Clear Fault key - Fault Screen
7
MODE: System mode (see 6.2.2 System MODE Indicators)
17
Enter key
8
BUS: Internal DC Bus Voltage
18
Scroll Up and Down keys
9
RPM: Flywheel Rotation Speed
19
Backspace
10
Power and Options: On/Off
53
Operation
6.2.1
Main screen function descriptions
Figures 55 and 56. provide descriptions and locations of the information and functions available
from the Main screen and the Fault Screen.
Figure 55 Main screen functions
Current Security Level
Contactor Status
Option Status
PWM
Status
Current Operating Mode
Liebert FS
Status
Message
MODE:
D
RPM:
SOC:
SOC:
BUS:
PWR:
DISCHARGE
STATUS: OK
START
F2
Startup Button
U
F3
F4
Shutdown Button
C
P
48020
73.4%
545V
12.3kW
LOCK
SHUT DN
F1
V
MENU
F5
Charge
Status
Internal
Bus
Voltage
F6
Menu
Button
Panel Lock/Unlock Button
Figure 56 Fault screen functions
Fault Status Message
Liebert FS
MODE:
D
FAULT
STATUS: 2 FAULTS
CLEAR
F1
F2
F3
F4
54
U
C
P
RPM:
SOC:
SOC:
BUS:
PWR:
73.4%
545V
12.3kW
MORE
MENU
F5
F6
More Information
Button
Fault Clear Button
V
48020
Bus
Power
Operation
6.2.2
System MODE Indicators
The Liebert FS has nine modes of operation: OFF, STARTUP, CHARGE, READY, DISCHARGE,
SHUTDOWN, COAST, FAULT and STANDBY. These are displayed on the main screen of the control
panel as identified in Figure 55. Table 5 lists the system Modes along with the corresponding Contactor Status, and the Conditions required to operate in these Modes: external voltage range, speed
and command.
NOTE:
See 5.3 - Modes of Operation for further details on modes of operation.
Table 5
Operation modes
Condition
Mode
Contactor
External Voltage
Speed
Command
OFF
Open
Vext < Vchg
0 ~ 3500
—
STANDBY
Open
Vext > Vchg
0 ~ 200
—
STARTUP
Close
Vext > Vchg
200 ~ Min Speed
STARTUP
CHARGE
Close
Vext > Vchg
Min Speed ~ Max Speed
STARTUP
READY
Close
Vext > Vchg
Max Speed ~ Max Speed + 200
STARTUP
DISCHARGE
Close
Vext < Vchg
Min Speed ~ Max Speed
STARTUP
COAST
Close
330 < Vext < Vchg
200 ~ Min Speed
STARTUP
SHUTDOWN
Open
Vext < 330
200 ~ Min Speed
STARTUP
Open
Any
Min Speed ~ Max Speed
SHUTDOWN
Close
Vext > 330
200 ~ Min Speed
SHUTDOWN
FAULT
Open
Any
0 ~ Max Speed
—
STANDBY
—
After CLRFLT
Min Speed: Minimum operating speed; State of Charge (SOC) will be 0% at this speed.
Max Speed: Maximum operating speed; State of Charge (SOC) will be 100% at this speed.
6.2.3
System STATUS Indicators
The Liebert FS system displays multiple status conditions during operation. Table 6 shows the complete list of status indicators for the Liebert FS and the corresponding condition.
Table 6
System status indicators
Message
Condition
1
OK
All systems operating normally.
2
READY
All systems operational and ready for startup.
3
APPLY 520*V
External voltage is less than the Charge Voltage*
4
n WARNINGS
Multiple warnings
5
n FAULTS
Multiple faults
6
OVERSPEED
Speed is higher than the Max Speed plus 200 RPM
7
TESTING VACUUM
Vacuum testing at 10000 RPM
8
OPENING CONTACTOR
Waiting until the current is stabilized
9
CLOSING CONTACTOR
Waiting until the voltages are stabilized
10
WAIT
Waiting until the voltages are stabilized
* Charge voltage is an adjustable user parameter; 520V is used only as an example.
55
Operation
6.2.4
Other Status Indicators
The Liebert FS system displays additional indicators during operation.
• Option Status; DCM or VIB (example: V abbreviation for VIB enabled
V
RPM:
SOC:
SOC:
V
51050
RPM:
SOC:
SOC:
95.2%
Operative
V
51050
RPM:
SOC:
SOC:
95.2%
Inoperative
51050
RPM:
SOC:
SOC:
95.2%
Disabled
51050
95.2%
Uninstalled
Default setting
• Security Levels
P
RPM:
SOC:
SOC:
51050
95.2%
RPM:
SOC:
SOC:
PWM on
51050
95.2%
PWM off
U
RPM:
SOC:
SOC:
51050
95.2%
RPM:
SOC:
SOC:
READ ONLY
S
51050
RPM:
SOC:
SOC:
95.2%
USER
51050
95.2%
SERVICE
Default setting
• PWM: Pulse Width Modulation Status (ON or OFF)
• SOC: State of Charge (0-100%)
SOC shows a relative energy stored in the system. SOC is determined with the following equation. It is 100% at Max Speed. A negative SOC means the required energy in % to get to the
CHARGE state.
2
2
rpm – MinRpm
SOC = ------------------------------------------------------------------ × 100
2
2( 2)
MaxRpm – MinRpm
• Contactor Status
C
RPM:
SOC:
SOC:
51050
RPM:
SOC:
SOC:
95.2%
Closed
51050
95.2%
Open
• LOCK/UNLOCK of the Control Panel
Control Panel can be locked or unlocked for security purposes. Locking or unlocking the display panel
requires a user password to confirm. See 6.3.2 - Password.
• PWR: Bus Power
PWR shows the DC power transfer in kW. Positive power indicates DISCHARGE and negative
power indicates CHARGE, respectively.
56
Operation
6.3
Security Access
6.3.1
Security Levels
The Liebert FS software has two security levels: READ-ONLY and USER. Security levels restrict
access to system resources, such as EEPROM parameters, terminal commands and display panel
functions. From the Main Screen, Figure 55, the display can be locked at any time to prevent use of
Control Panel. Pressing F4 button under “LOCK” will prompt the user to enter a password to “LOCK”
the system. Once locked F4 will now read “UNLOCK” and pressing this will prompt you to enter the
Password to the system so that the user will be able to operate the Control Panel and adjust system
parameters and settings.
6.3.2
Password
READ-ONLY level has no password and it is default level at reset.
The USER level password is user-configurable and saved in EEPROM. The default USER level password is “1234”, and the password should be between 3 - 12 digits.
6.3.3
EPROM (System) Parameters
EEPROM (system) parameters can be accessed through display panel or terminal commands. They
can be read and written through terminal or display panel, but accessible parameters are limited by
security levels. The parameters for each level have different number range. Unused numbers are
reserved for future usage.
Table 7
EEPROM parameter number ranges
Security Level
Parameter Number Range
Read-Only
0 ~ 99
User (Editable)
0 ~ 99
6.4
Menu Tree and Navigation
6.4.1
Screen Tree Menu Functions
The following diagram shows all of the screens accessible from the control panel and the path to bring
up these screens. The screens are used for configuring the Liebert FS for operation and accessing data
current and historical data on its performance. The screens are organized by five primary function
areas; Parameters, View, Security, About, and Tools. These are displayed on the Main Menu screen.
Some of the screens require User level or Service level passwords to access as shown in the legend
below. Refer to 6.3 - Security Access for more information on this subject.
Table 8
No
PCMC parameters, read-only and user (Liebert FS software)
Parameter Name
Unit
Default
Minimum
Maximum
1
Vcharge Setpoint
V
520
360
800
2
Vreg Setpoint
V
510
350
790
3
Icharge Max Setpoint
A
30
1
50
4
Amps per Volt Setpoint
A/V
20
1
50
5
Vreg Delta Setpoint 1
V
0
0
150
6
Vreg Delta Transition (SOC)
%
0
0
100
7
Vreg Delta Setpoint 2
V
0
0
150
57
Operation
Figure 57 Menu tree
Parameters
User/ Adv
Time/ Date
View/ Set
Temperatures
Menu
View
Voltages
Charge
History
Discharge
Options
Warning
Electrical
Fault
Network
Vitals
Vitals
Counters
Security
Password Input
About
S/N
Tools
Reboot
Max Drag Power
Min Drag Power
Last 10k Drag
Max Miser
Max Runout
Contact Closure
Shutdown to Off
Bootup Count
Hours since bootup
Pump On-time
Fan 1 On-time
Fan 2 On-time*
* FS, Serial P or N
units only
LEGEND
All Level Menu
User Level Menu
58
Rotor
Stator
IGBT
PCM/ PPM
MLM/ MCM
Cabinet
24V PS #1
24V PS #2 *
* FS models only
Operation
6.4.2
Navigation and Operation of Control Panel
Navigation of the menu screens is simple and intuitive. From the Main Screen, also referred to as
“Home”, menu functions and screens can be accessed by using the function keys and the numeric keypad. The function keys, F1- F6, initiate certain system functions and Modes; STARTUP, SHUTDOWN and also perform certain menu screen functions; DONE, PREVIOUS, NEXT, and HOME. The
up and down arrows on the control panel enable the user to scroll up or down certain menus. The
numeric keypad can be used to enter values for system setup and the Enter and Backspace keys to
enter numbers or backspace to change entry. Pressing F6 or DONE completes the entry process.
Always double check by going back to the previous screen to verify the entry is complete and accurate.
To access the Main Menu press the F6 button below the “Menu” option in the lower right. When
pressed, the “Menu” key, will display the Main Menu screen as shown in Figure 58. From this screen
each of the submenus may be accessed, provided the user has security access where needed, refer to
Figure 57.
Each screen in the menu tree will show numbers in front of the subject if more information is available at the next menu level. Pressing the number for the subject using the numeric keypad will bring
up that screen. If the subject is preceded by a double arrow symbol (>>) instead of a number no further information is available or the parameter may not be modified without security access.
At each screen and level in the menu tree, when finished accessing data or changing system parameters, the user may select DONE using the function keys to move back to the prior screen in the menu
or when available press HOME, F5, to return to the Main Screen. On some screens such as in the History screens you will be able to access additional screens of data recorded by pressing NEXT, see
Figures 70 and 71.
Figure 58 User level main menu screen
MENU>
1. PARAMETERS
2. VIEW
3. SECURITY
4. ABOUT
5. TOOLS
DONE
F1
F2
F4
F5
F6
!
I
6.4.3
F3
0
1
2
3
.
4
5
6
-
7
8
9
X
System Setup and Parameter Access
Setting up the Liebert FS:
In order to operate the system the system parameters must be configured for the application. The system parameters or “EEPROM” parameters can be accessed by first pressing MENU, F6, and the number one (1) button on the Control Panel keypad for the PARAMETERS screen. Liebert FS software
has two kinds of access screen according to the security level.
In READ-ONLY mode, seven basic parameters can be monitored. Modifying the parameters in this
mode is not allowed. In this mode the parameters will have double arrow symbols to the left of the
parameters.
59
Operation
Figure 59 READ ONLY level parameter view screen
>>
>>
>>
>>
>>
>>
>>
V_CHARGE SETPOINT
V_REG SETPOINT
MAX CHARGE CURRENT
CHARGE AMPS/VOLT
V_REG_DELTA 1
V_REG_DELTA TRANSITION SOC
V_REG_DELTA 2
520 V
500 V
30.0
A
/V
2.0 A
0 V
0%
0 V
HELP
DONE
In the USER mode, below the 7 basic parameters can be modified, see 6.3.2 - Password for access
level and passwords. Pressing the corresponding number to the parameter to the left of the number
will take you to the parameter setup screen for that particular parameter.
Figure 60 USER level or above parameter edit screen
1.
2.
3.
4.
5.
6.
7.
V_CHARGE SETPOINT
V_REG SETPOINT
MAX CHARGE CURRENT
CHARGE AMPS/VOLT
V_REG_DELTA 1
V_REG_DELTA TRANSITION SOC
V_REG_DELTA 2
520 V
500 V
30.0
2.0 A /V
0 V
0 %
0 V
HELP
DONE
In setting the parameters there is a help screen to guide the user through the setup and help visualize
the operation the system when utilizing this parameter. The help screens are displayed in
Figures 61 and 62. The help screen also describes the other system parameters used in operation.
Figure 61 HELP screen for User Setup Parameters
When voltage is above [1] V_CHARGE
Flywheel charges up and draws :
(( Vbus – [1] V_CHARGE) * [4] AMPS/VOLT) amps,
Not exceeding [3] MAX CHARGE CURRENT.
When voltage sags, it is regulated at
[2] V_REG whose slope can be adjusted by
[5] DELTA 1, [6] SOC TRANS, & [7] DELTA 2
DONE
MORE
DONE
Figure 62 Graphical HELP screen for VREG DELTA1, VREG TSOC, and VREG DELTA2 Transition setup
(Pressing the “MORE” button, F1, from Figure 5-8. accesses this screen)
[2]V_REG******------------------------|
******
[5]DELTA1
V|
******------------O|
| **
[6]DELTA2
L|
|
**--------|
T
PREV
|
|
|---------------------+----+
100%
[7]TSOC 0%
60
DONE
Operation
Each EEPROM parameter has its own screen which contains parameter description, data range, current value and default value button. Default button shows the default value for the parameter. From
this screen the UP/DOWN arrow keys can used to move between parameters. The UP/Down arrow
will increase/decrease the parameter number, respectively.
Figure 63 USER or higher level parameter selection for view/edit
2:
VREG SETPOINT:
: 220 .. 510V
RANGE
CURRENT : 500V
NEW VALUE :
DEFAULT
6.4.4
CANCEL
DONE
View
Functions in MENU > VIEW display various system status including real-time and statistical data.
The menu path is represented in the upper left hand corner of the screen and lets you know your current screen location in the menu tree. You can select the function by entering the number.
Figure 64 VIEW menu
MENU>VIEW>
1. TIME/DATE
2. TEMPERATURES
3. VOLTAGES
4. HISTORY
5. OPTIONS
6. NETWORK
7. ELECTRICAL
8. VITALS
HOME
6.4.5
DONE
Time/Date
In MENU>VIEW>TIME/DATE, system time is displayed and can be adjusted. However, USER security level or higher is required to adjust the time or date, see 6.3.2 - Password. Pressing SET button
changes to the edit mode. Cursor will blink on NEW TIME. You can type in new time data or move to
NEW DATE by UP/DOWN arrow button. Moving to NEW DATE should be made before typing in any
digits. All digits for time (4 digits) or date (6 digits) should be typed in before ENTER or you will get
the INVALID INPUT error message.
Figure 65 TIME/DATE set
CURRENT TIME :
:
NEW TIME
10:49
hh:mm (24HR)
CURRENT DATE :
:
NEW DATE
03/08/07
mm/dd/yy
SET
HOME
61
DONE
Operation
6.4.6
Temperatures
MENU>VIEW>TEMPERATURES shows the temperatures of various system parts.
Figure 66 Temperature view
>>
>>
>>
>>
>>
ROTOR
STATOR
IGBT
PPM
MCM
67.12
40.20
52.22
46.17
38.46
°C
°C
°C
°C
°C
>>
>>
CABINET
24V PS
35.12°C
50.34°C
HELP
6.4.7
DONE
Voltages
MENU>VIEW>VOLTAGES shows the major power supply voltages on the controller board. These
values are updated continuously.
NOTE
If an earlier model Liebert FS, serial number P or N, flywheel system has been upgraded with
this software, it will display only the 24V power supply voltage.
Figure 67 Figure 5-14. Voltages view
>> 3.3V:
>> 5V:
>> 12V:
3.29 V
5.01 V
11.99 V
>> 24V #1:
>> 24V #2:
>> 24V BKP:
24.01 V
24.00 V
23.99 V
HOME
6.4.8
DONE
History
The Liebert FS records and stores a limited history of the following items; CHARGE, DISCHARGE,
WARNING, FAULT, VITALS, and COUNTERS which are listed in the main History menu screen.
(See Figure 69). In the event list screens, Figures 71 through 73, users may move between pages
using the PREV and NEXT buttons. History data can be cleared by RESET button. SERVICE or
higher level is required to reset the list.
Figure 68 History view
MENU>VIEW>HISTORY>
1. CHARGE
2. DISCHARGE
3. WARNING
4. FAULT
5. VITALS
6. COUNTERS
HOME
DONE
• Charge: The most recent charge (LAST CHARGE) is displayed in time (sec.) and energy (kW) on
this screen as are the accumulated charge time/energy (TOTAL CHARGE). (See Figure 69.)
Figure 69 Charge history
>> LAST CHARGE:
12.34
56.78
12345
12345678
>> TOTAL CHARGE:
HOME
62
sec
kW
sec
kW
DONE
Operation
• Discharge: The most recent discharge (LAST DISCHARGE) is displayed in time (sec.) and energy
(kW) on this screen as are the accumulated discharge time/energy (TOTAL DISCHARGE) and the
number of times system has discharged (DISCHARGE COUNT). (SeeFigure 70.)
Figure 70 Discharge history
>> LAST DISCHARGE:
12.34
56.78
12345
12345678
123
>> TOTAL DISCHARGE:
>> DISCHARGE COUNT:
LIST
HOME
sec
kW
sec
kW
DONE
• A Discharge History event list screen, Figure 72, is available and shows the event number, date
(month./day/year), time of event (00:00-24:00) average power (kW), and duration of discharge (seconds). The recorded events are sequentially numbered and listed from most recent to last. The letter “D” after the time indicates that this is the DISCHARGE History screen.
The first screen has the function options of NEXT or DONE viewing. The next page will have the
function button options of PREV (Previous), NEXT or DONE.
Figure 71 Discharge History, Event list screen
08
09
10
11
12
13
14
04/31/06
03/21/06
03/10/06
02/01/06
01/15/06
11/11/05
04/25/05
10:15
03:11
20:25
14:12
09:18
18:35
22:12
38.14s
31.26kW
08.10s
41.46kW
21.04s
75.61kW
18.19s
37.36kW
28.44s
51.21kW
16.10s
95.20kW
27.12s
33.76kW
NEXT DONE
PREV
D
D
D
D
D
D
D
• Warning/Fault: Liebert FS software holds 35 warning and fault event information, respectively. Seven warnings/faults are displayed in a single screen.
Figure 72 Warning history, Event list screen
01
02
03
04
05
06
07
03/10/05
03/10/05
02/24/05
01/30/05
12/20/04
11/13/04
09/30/04
11:43
10:37
04:03
23:22
13:45
07:28
16:23
W
W
W
W
W
W
W
AUX POWER LOW
VIB INOPERATIVE
OVERSPEED
STATOR HOT
ROTOR HOT
RUNOUT
VACUUM
NEXT
DONE
CURRENT OFFSET
CHECKSUM
SOFTWARE OV
DC BUS OV
SPARE OPEN
INTER PROCR COMM
MISER
NEXT
DONE
Figure 73 Fault history, Event list screen
01 03/10/05
02 03/10/05
03 02/24/05
04 01/30/05
05 12/20/04
06 11/13/04
07 09/30/04
RESET
11:43
10:37
04:03
23:22
13:45
07:28
16:23
F
F
F
F
F
F
F
63
Operation
• Vitals (USER or above): Key system efficiency and performance measurements are displayed in
Max/Min measurements along with the date recorded.
Figure 74 Vitals history view
>>
>>
>>
>>
>>
MAX DRAG POWER:
MIN DRAG POWER:
LAST 10K DRAG:
MAX MISER: 1.23 @
MAX RUNOUT: 1.23 @
10.0 W,
2.0 W,
1.0 W,
12345,
34567,
11/30/05
11/29/05
11/30/05
11/28/05
11/27/05
HOME
DONE
• Counters (USER or above) provide totals of run time hours; system and components, and numbers
of startup and shutdown events; contactor closures and bootup. OPERATING HOURS is the total
operating hours in the CHARGE/ DISCHARGE/ READY mode.
Figure 75 Counters
>>
>>
>>
>>
>>
CONTACTOR CLOSURE:
SHUTDOWN TO OFF:
BOOTUP COUNT:
HOURS SINCE BOOTUP:
OPERATING HOURS:
NEXT
3
4
5
12.34 hr
1234567 hr
HOME
DONE
Figure 76 Counters - screen 2
>>
>>
>>
PUMP ON-TIME:
FAN#1 ON-TIME:
FAN#2 ON-TIME:
12.34 hr
56.78 hr
19.24 hr
HOME
BACK
6.4.9
Options
Each option, if installed, can be enabled by pressing its number and its status will then be displayed.
Additional information on setup and operation of these options is available in the related section of
this manual.
Figure 77 Options view
1. DCM
2. VIB
: INOPERATIVE
: OPERATIVE
HOME
64
DONE
Operation
6.4.10 Network—Requires DCM Option
The Network view screen displays the addresses of the DCM. Static address settings can be entered
using the keypad into this screen. If this option is installed, reference the Liebert Data Collection
Module (DCM) Option Manual for more information on setting up the DCM on a network and or
assigning IP addresses. Figure 78 shows the Network screen in a read-only mode.
Figure 78 Networks view
>>
>>
>>
>>
>>
DHCP:
IP ADDRESS:
NET MASK:
DEFAULT GATEWAY:
DNS SERVER:
ON
192.168.1.155
255.255.255.0
192.168.1.1
192.168.1.13
HOME
DONE
By entering a Password to access the User level mode (see 6.3.2 - Password), you can edit this function. Pressing the EDIT button, F1, will place the system in the edit mode. The DHCP must be disabled or turned OFF to proceed with setting IP addresses and other settings. After pressing EDIT you
will see up/down arrows next to the DHCP ON value. Pressing the up or down arrows on the keypad
will allow you to turn OFF or ON this function.
Figure 79 Networks view, Edit DHCP
>>
>>
>>
>>
>>
DHCP:
IP ADDRESS:
NET MASK:
DEFAULT GATEWAY:
DNS SERVER:
ON
192.168.1.155
255.255.255.0
192.168.1.1
192.168.1.13
HOME
EDIT
DONE
Once you have turned DHCP OFF, press EDIT again and now you will see numbers next to each of
the settings. Pressing the corresponding number will allow you to enter or change that value. At any
time you may press CANCEL to cancel the changes. Once the changes or entries are complete, press
APPLY to complete entry process. Pressing APPLY will reboot system and in a few minutes the system will display the new screen.
Figure 80 Networks view, Edit Settings (Service level)
>>
>>
>>
>>
>>
DHCP:
IP ADDRESS:
NET MASK:
DEFAULT GATEWAY:
DNS SERVER:
ON
192.168.1.155
255.255.255.0
192.168.1.1
192.168.1.13
HOME
CANCEL
65
DONE
Operation
6.4.11 Electrical
The screen MENU>VIEW>ELECTRICAL shows the major electrical system variables. These quantities are updated continuously.
NOTE
Positive values for DC BUS CURRENT and OUTPUT POWER indicate Discharge mode and
negative values for same indicate Charge mode.
Figure 81 Electrical view
>>
>>
>>
>>
>>
INT. BUS VOLTAGE:
EXT. BUS VOLTAGE:
DC BUS CURRENT:
OUTPUT POWER:
STATUS OF CHARGE:
500
500
100
50
65.78
V
V
A
Kw
%
HOME
DONE
6.4.12 Vitals
MENU>VIEW>VITALS shows the current vital system values. These quantities are updated continuously.
Figure 82 Vitals view
>>
>>
>>
>>
DRAG POWER:
MISER:
RUNOUT:
RPM:
12.34
1.234
0.012
12345
W
C
Mil
RPM
HOME
6.4.13 Security
Security levels can be changed in the MENU>SECURITY screen.
66
DONE
Operation
Figure 83 Password screens
PASSWORD:
DONE
PASSWORD: ****
PASSWORD CONFIRMED
DONE
PASSWORD: ****
INVALID PASSWORD
DONE
USER level password can be modified by pressing the CHG PW button. Current password is required
to change the password. The USER level password should be between 3 - 12 digits length, hence digits
after 13th are ignored if more than 12 digits are entered.
Figure 84 Change password
U
PASSWORD:
CHG PW
LOGOUT
DONE
CURRENT PASSWORD:
DONE
CURRENT PASSWORD: ****
NEW PASSWORD:
DONE
67
Operation
Figure 85 Change password
CURRENT PASSWORD: ****
NEW PASSWORD: ******
RE-ENTER PASSWORD: ******
PASSWORD CHANGED
HOME
DONE
6.4.14 About
About screen shows the version of the firmware and company information. The controller board has
two DSPs and each DSP has bootloader and application firmware.
Figure 86 ABOUT screen
LIEBERT CORPORATION
COPYRIGHT 2003-2006
APPL: PRI-3.00 SEC-3.01
BL : PRI-3.02 SEC-3.01
S/N
HOME
DONE
Figure 87 Serial numbers
>>
>>
>>
>>
>>
>>
SYSTEM S/N:
FM S/N:
MLM S/N:
PCM S/N:
SO#:
USER
001
001
0001
0002
123-456-7
USER-DEFINE
HOME
DONE
6.4.15 Tools
Tools menu has REBOOT function for USER to reboot system.
Figure 88 Tools for USER
MENU>TOOLS>
1. REBOOT
HOME
68
DONE
Operation
6.5
System Startup
6.5.1
Initial System Startup Procedure
Initial System Startup is defined as the first or initial startup following installation of the system.
Several additional steps are required prior to the normal startup procedure including the following
Inspection before Initial System Startup, (Section 5.5.2), and Control Parameters Setup (Section
5.5.3.). These steps are required to ensure safe and proper startup of flywheel system and for warranty purposes.
!
6.5.2
CAUTION
The Initial System Startup shall ONLY be performed under the supervision of a
Liebert-certified service technician in order to ensure proper system operation. Failure to
abide by instructions provided herein may void your warranty.
Inspection before Initial System Startup
A Liebert technician will perform the following tasks:
• Visual Inspection
Inspect equipment for signs of damage
Verify installation per drawings
Inspect cabinet for foreign objects
Verify ground conductors are properly sized and connected
Verify all printed circuit boards are configured properly
• Mechanical Inspection
Check all control wiring connections for tightness
Check all power wiring connections for tightness
Check that cabinet is attached to the floor
Check all terminal screws, nuts and/or spade lugs for tightness
Check all cooling pump connections
• Electrical Inspection
Check fuses for continuity
Check and verify UPS DC bus voltage
• Pre-Startup
Perform MLM Pre-Start procedure using Boot Up process with UPS DC bus
Perform MLM Inspection and test
Verify UPS settings and adjustments
Run pumps and fans for several minutes
69
Operation
6.5.3
Control Parameters Setup at Initial System Startup
Please have the relevant UPS Interconnection Kit Handbook (Liebert UPS Interconnection Kit [IKIT]
Handbook for specific Brand and Model UPS) available for the Liebert technician. The Control
Parameters Setup values that need to be programmed are included in this manual.
You may record in Table 9 the values found in the specific IKIT (Interconnection Kit) Handbook for
your UPS. For future reference you may also want to record Software Versions; Primary and Secondary and Bootloader Version from the About parameter screen, Section 5.4.12. above.
Table 9
Control parameters
Control Parameter
Value
Default
Charge Voltage
VDC
520
Regulation Voltage
VDC
510
Maximum Charge Current
Charging Amps/Volts
Vreg Delta 1
Vreg TSOC
Vreg Delta 2
Table 10
A
30
A/V
2
VDC
0
%
0
VDC
0
Software versions
Software Application
Version
Primary application 2812
Secondary application 6711
Primary Bootloader
Secondary Bootloader
The Liebert technician will perform or direct the Control Parameters Setup (described in 6.4.1 Screen Tree Menu Functions) and proceed to the Initial Startup Procedure.
NOTE
DC bus ripple voltage should be measured and taken into consideration when programming
the Charge Voltage; the Charge voltage should be below the DC float voltage and include
compensation for any ripple voltage present to avoid frequent charging and discharging.
6.5.4
Initial System Startup Procedure
A Liebert technician will perform or direct the following tasks at Initial System Startup:
•
•
•
•
•
•
Inspection before Initial System Startup (Section 5.5.2. of this manual)
System Control Parameters Setup
Assist with Initial System Startup
Complete Warranty documentation
Complete commissioning documentation
Provide basic user training on Liebert FS operation *
70
Operation
6.5.5
Regular Startup Procedure
!
CAUTION
The Initial System Startup shall be performed ONLY under the supervision of a Liebert
technician to ensure proper system operation. Failure to abide by instructions provided herein
may void your warranty.
NOTE
A regular startup is any startup after the Initial System Startup.
6.5.6
Inspection Before Regular Startup
The following verifications must be done before performing a regular startup of the Liebert FS (see
6.5.7 - Starting up the System):
1. Make sure the Liebert FS is properly secured to the floor with the Liebert-provided mounting kit
and in compliance with the floor mounting instructions in 4.1 - Cabinet Floor Mounting.
2. Check for coolant leaks in and around the Liebert FS unit.
3. Ensure that Liebert FS cabinet panels are in place on the cabinet and that no tools have been left
in the cabinet
4. Ensure that the Liebert FS Main circuit-breaker (optional) or the customer-provided external DC
disconnect switch is open
5. Verify that the AC Auxiliary Backup Power is connected and powered by closing fused disconnect
or wall disconnect and check if the Control Panel is ON and with no warning or fault messages
displayed.
The Liebert FS may now be started up.
6.5.7
Starting up the System
!
CAUTION
The following procedure assumes that the Initial System Startup has been performed under
the supervision of a Liebert technician.
Powering Up the Liebert FS
Once AC voltage is applied to the Liebert FS, the Liebert FS Control Panel will boot up. Its screen will
begin to illuminate after 5 to 10 seconds and then display a series of boot up protocols.
Booting Up
1. It takes about 25 seconds to load and initialize the primary application software at STARTUP or
after reset.
2. Title block and firmware versions will be displayed (see Figure 82). If the secondary DSP does
not boot up properly, versions for the secondary DSP may be corrupted or zero.
3. EEPROM checksum will be calculated and compared with the stored value. EEPROM checksum
fault will be generated if they do not match. For this case, default values are loaded for
parameters in RAM. However, EEPROM contents are not changed.
!
CAUTION
Do not attempt to run the system unless the system loads valid parameters.
4. Response from secondary DSP will be checked. “INTERPROCESSOR COMM FAULT” will be
generated if the communication is not set up properly. The controller will reset itself for this case.
5. Previous operation command (STARTUP or SHUTDOWN) will be retrieved to determine the
current operation mode.
6. Option status is checked. Current available options are VIB and DCM.
71
Operation
Validation of Control Parameters Setup
1. Once the Control Panel has successfully booted up, the Control Panel will display the Main
Screen (see Figure 55).
2. Verify the Control Parameters values are correct. (Consult Table 9 and the relevant UPS
Interconnection Kit Handbook for choosing the proper Control Parameters values).
3. Adjust the Control Parameters values if necessary (see 6.4.1 - Screen Tree Menu Functions).
for instruction on how to change the values of the Control Parameters) then press “F6 DONE”.
Initiating Liebert FS Startup Sequence
NOTE
Startup procedures will vary for each UPS model.
1. Once sufficient DC voltage is applied to the UPS DC Bus, the Liebert FS will be able to transition
from the OFF Mode to Startup Mode, unless system was previously Shutdown by command.
The following action is conditional on the UPS interconnection kit that has been installed on your
Liebert FS:
• Standard UPS Interconnection Kit (IKIT-STD)
The Standard UPS interconnection kit (IKIT-STD) includes a fused Power Terminal Block. It is
recommended for maintenance use to have an external disconnect switch installed between the
UPS and the Liebert FS.
Close the customer-provided external disconnect switch at the time indicated by the UPS startup
procedure.
• Optional UPS Interconnection Kit
NOTE
Optional UPS interconnection kits include circuit-breakers then referred to as “Liebert FS
Main circuit-breaker”.
Open the Liebert FS cabinet front door and close the Liebert FS main circuit-breaker at the time
indicated by the UPS startup procedure. Close the cabinet door.
2. The Control Panel will then show the Main screen (see Figure 55). The System Mode should read
“OFF”. The Liebert FS will actively check for presence of sufficient voltage to allow system
startup.
3. As soon as the UPS DC bus voltage is greater than Vcharge, the System Status will change from
“OFF” to “STAND BY”. The “F1 STARTUP” key will then be enabled.
4. Press the “F1 STARTUP” key.
Liebert FS Startup Sequence
As soon as the “F1 STARTUP” key is pressed, the Liebert FS will launch its startup sequence. This
will progressively lead the Liebert FS through the different Modes of Operation (STAND BY, STARTUP, CHARGE) to eventually reach a ready state of idling (READY Mode) once it is completely
charged up. The automatic transition between modes is described in 5.2 - List of System User-Configurable Parameters.
6.6
Shutdown Procedure
There are two ways the Liebert FS may enter a Shutdown sequence: either a) following a Liebert FS
discharge down to SOC = 0%; or b) following a user-initiated command.
In any Mode, except OFF Mode, the user may command the Liebert FS to transition in SHUTDOWN
Mode by pressing the “F2 SHUTDOWN” key. This action is recommended for normal shutdown of the
system. In this condition, the Liebert FS will not discharge to support an outage. You will be asked to
confirm “Yes” or “No” to SHUTDOWN. Press “Yes” to confirm shutdown and put system in SHUTDOWN mode.
For more information concerning the SHUTDOWN Mode, please refer to 5.2 - List of System UserConfigurable Parameters.
72
Maintenance
7.0
MAINTENANCE
7.1
Safety Precautions
Observe all safety precautions in this manual, paying particular attention to Important Safety
Instructions on page 1.
ONLY qualified service personnel should perform maintenance on the Liebert FS.
Observe all of the warnings below before performing any maintenance on the Liebert FS and associated equipment.
!
!
WARNING
Before performing preventive maintenance tasks, the Liebert FS must be de-energized and
electrically isolated (both AC and DC connections to the Liebert FS must be electrically
disconnected).
CAUTION
Always identify connecting wiring prior to disconnecting any wiring.
Do not substitute parts except as authorized by Liebert Corporation.
Keep Liebert FS cabinets free of foreign materials such as solder, wire cuttings, etc.
Contact Liebert Global Services if you are not sure of the procedures to follow or if you are not
familiar with the circuitry.
!
WARNING
Extreme caution is required when performing maintenance.
Be constantly aware that the Liebert FS contains high DC as well as AC voltages. With input
power off and the battery disconnected, high voltage at filter capacitors and power circuits
should be discharged within 30 seconds. However, if a power circuit failure has occurred, you
should assume that high voltage may still exist after shutdown. Check with a voltmeter
before making contact.
Check for voltage with both AC and DC voltmeters prior to making contact.
When the Liebert FS is under power, both the operator and any test equipment must be
isolated from direct contact with earth ground and the chassis frame by using rubber mats.
Some components within the cabinet are not connected to chassis ground.
Any contact between floating circuits and the chassis is a lethal shock hazard. Use differential
oscilloscopes when measuring a floating circuit. The differential input should have at least
800 VRMS common mode input rating and a common mode rejection ratio of at least 80dB.
Exercise caution that the test instrument exterior does not make contact, either physically or
electrically, with earth ground.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
others approved for use in fighting electrical fires.
73
Maintenance
7.2
Liebert Global Services
Startup, maintenance and training programs for the Liebert FS are available through your Liebert
sales representative.
Professional Startup
Liebert FS Startup—Liebert’s customer engineers perform a thorough, non-powered inspection of
the units and will then conduct a complete electrical checkout that includes calibrating all components to published specifications. Customer operation training will be conducted during startup.
Load bank testing and full site acceptance testing are additional services that can be performed during a Liebert FS startup. One preventive maintenance service call can be added to the initial
Liebert FS startup agreement.
Maintenance Agreements: The Signature Program
Liebert FS Service Agreements—Liebert Global Services (LGS) has a variety of available maintenance agreements, depending on specific site needs. Choose the level of support appropriate for each
installation. Mission-critical sites can have the standard parts-and-labor, around-the-clock coverage
for their Liebert FS, with or without scheduled preventive maintenance visits. Other sites can benefit
from a variety of money-saving options.
While the Liebert FS is designed to be maintenance-free, Liebert suggests at least one preventive
maintenance visit per year. This preventive maintenance work would normally be done in conjunction
with a service visit for another Liebert UPS product. The annual visit will require taking the
Liebert FS off-line for a thorough, nonpowered inspection. These visits are in addition to the general
housekeeping tasks (changing air filters, etc.) that can be performed by customer personnel.
Training
Customer training courses include the proper operation of the system, emergency procedures, preventive maintenance and some corrective maintenance.
Warranties
Contact Liebert Global Services if you have any questions regarding the warranty on your Liebert FS.
7.3
Routine Maintenance
You are encouraged to become thoroughly familiar with the equipment, but at no time should you go
beyond the specific procedures in this manual while performing maintenance or correcting a malfunction. If you have any doubt as to what must be done, call Liebert Global Services at 1-800-LIEBERT
for further instructions.
The Liebert FS is designed for unattended operation, but does require some common-sense maintenance:
• Keep good records—Troubleshooting is easier if you have historical background
• Keep it clean—Keep the Liebert FS free of dust and moisture
• Keep it cool—The Liebert FS will reliably meet all performance specifications and design life at
temperatures up to 122°F (50°C)
• Keep connections tight—Tighten all connections at installation and at least annually thereafter
(see torque requirements,Table 12)
74
Maintenance
7.4
Maintenance Schedule
!
WARNING
!
CAUTION
Any maintenance on the system should be delayed by at least 10 minutes after system is shut
down to be certain all electronics have discharged. Use appropriate safety precautions to
ensure unit is disconnected and de-energized.
Unless specified otherwise, ONLY a Liebert-certified service technician should perform all
maintenance work. Failure to use a Liebert technician for maintenance actions, unless
specifically noted, may void your warranty.
The Liebert FS maintenance schedule consists of actions listed in Table 11.
Table 11
Maintenance schedule
Frequency
Every
1 yr
Every
3 yrs
Every
6 yrs
Every
15 yrs
Service
Performer
System Visual Inspection *
Check
or Test
—
—
—
Liebert/Owner
System Cleaning (if necessary)
Check
or Test
—
—
—
Liebert/Owner
System Testing
(and adjustments, if necessary)
—
Check
or Test
—
—
Liebert
PCM Capacitor Bank
—
—
Service or
Replace
—
Liebert
Flywheel Module
—
Check
or Test
—
Service or
Replace
Liebert
UPS Interconnection Kit (if option installed)
—
Check
or Test
—
—
Liebert
Check
or Test
—
—
—
Liebert/Owner
Item/Action
Air Filter (if option installed)
NOTE
The recommended System Visual Inspection every year should include a check and torque of
cabinet DC circuit breaker box lug connections and the DC ground; see the relevant section of
Appendix A.0 - UPS Interconnection Kits for torque requirements.
NOTE
Liebert may determine additional maintenance actions as necessary and issue service or
technical bulletins to address any additions.
NOTE
The optional inlet Air Filter in the cabinet will need to be replaced when it is sufficiently dirty
to significantly reduce the flow of air into the cabinet. Ambient conditions at the installation
site will determine the frequency of replacement if option is installed
7.5
Record Log
Set up a maintenance log to record scheduled checks and any abnormal conditions.
The log should have space for all metered parameter indications including phase readings, alarm
messages, mode of operation, air filter replacement date and observation notes.
A periodic walk-through inspection of the Liebert FS room is advised to check for visible and audible
indications of problems. Log the inspection, metered parameter indications and any discrepancies.
75
Maintenance
7.6
Optional Air Filters
The optional air filters must be inspected and serviced on a regular schedule. The period between
inspections will depend upon environmental conditions. Under normal conditions, the air filters will
require cleaning or replacement approximately every 12 months.
!
CAUTION
Be certain recyclable filter elements are dry before reinstalling them in the Liebert FS.
Abnormal or dusty conditions will require more-frequent cleaning and replacement of air filters
(sometimes as often as every two months). Inspect installations in new buildings more often, then
extend the inspection period as experience dictates.
7.7
Torque Requirements
All electrical connections must be tight. Table 12 provides the torque values for the connections in
the Liebert FS. Use these values unless the equipment is labeled otherwise.
Table 12
Torque specifications (unless otherwise labeled)
Nut And Bolt Combinations
Grade 2
Standard
Electrical Connections
With Belleville Washers
Bolt Shaft Size
Lb-in
N-m
Lb-in
N-m
1/4
53
6.0
46
5.2
5/16
107
12
60
6.8
3/8
192
22
95
11
1/2
428
48
256
29
Circuit Breakers with Compression Lugs (For Power Wiring)
Current Rating
Lb-in
N-m
250A
250
28
Circuit Breakers with Compression Lugs (For Control Wiring)
7.8
AWG Wire Size or Range
Lb-in
N-m
#22 - #14
3.5 to 5.3
0.4 to 0.6
Detecting Trouble
It is important that the operator check the instrument readings if abnormal equipment performance
is suspected. Any metered value that differs appreciably from normal could mean an impending malfunction and should be investigated.
Items to check include:
• Alarm messages indicate malfunction or impending malfunction. A daily check of the operator
control panel will help to provide an early detection of problems. Refer to Table 16 to interpret
alarm messages.
• Tracing a problem to a particular section is facilitated by alarm messages and the metered
parameter indications. These are stored in the Status Reports and can be displayed at the operator control panel or at an optional terminal. A Liebert Global Services engineer will be familiar
with test points inside the unit.
76
Maintenance
7.9
Reporting a Problem
If a problem occurs within the Liebert FS, review all alarm messages along with other pertinent data.
This information should be given by telephone to the Liebert service representative’s office nearest
you. This information can be downloaded to Liebert Global Services by using the optional modem.
Contact Liebert Global Services at 1-800-LIEBERT to report a problem or to request assistance.
7.10
Corrective Actions
For each alarm message on the operator control panel, you can find the recommended corrective
action in Table 16.
7.11
Recommended Test Equipment
Table 13 lists recommended test equipment and tools required to maintain, troubleshoot and repair
the Liebert FS. You may substitute instruments of equivalent range and accuracy.
All instruments should be calibrated and be within the current calibration cycle. Calibration data for
the instruments should be maintained in equipment-history files and the instruments labeled for
audit and verification.
Table 13
Qty
7.12
Recommended test equipment and tools
Test Equipment
Manufacturer
Model or Type
1
Oscilloscope
Tektronix, H-P or Fluke
DC to 50 MHz
2
Voltage Probes
Tektronix, H-P or Fluke
10X, with 10 ft cable
2
Voltage Probes
Tektronix, H-P or Fluke
100X, with 10 ft cable
1
Digital Multi-meter
Fluke
87, with test leads
1
Tool Kit
N/A
Standard electrical contractor tools
Limited Life Components
Your Liebert FS has a design life well in excess of 15 years. Well-maintained units can continue to
provide economic benefits for 20 years or more. Long-life components are used in your Liebert FS
wherever practical and cost-effective.
However, due to current component material and manufacturing technology limitations, a few components in your Liebert FS will wear out and require replacement in less than 10 years. The following
limited-life components are utilized in your Liebert FS. In order to prevent a wear-out failure of one of
these components affecting your critical load operations, it is recommended these components be periodically inspected and replaced before their expected wear-out life. Individual users may have sitespecific requirements that differ from these typical life expectations.
Table 14
Projected component life, replacement schedule
Component
Expected Life
Replace in:
Power DC filter capacitors
About 7 years
5-6 years
Air filters, disposable
(see also 7.6 - Optional Air Filters)
1-3 years
Check 4 times/year
Power capacitors are considered “failed” when their measured capacitance is –5% below their nameplate rating.
In most cases, replacement components must exactly match the original component specifications and
are not readily available from third-party component distributors. For assistance with your specific
component specifications, replacement component selection and sourcing, call 1-800-Liebert.
For customers using Liebert Global Services’ Preventive Maintenance Services, periodic inspection of
these components are part of this service as is recommending to customers replacement intervals to
avoid interruptions in critical load operations.
77
Troubleshooting
8.0
TROUBLESHOOTING
NOTE
Refer to this section before calling Liebert Global Services for support.
8.1
General
The Liebert FS is capable of detecting conditions outside of normal operating parameters and providing notice at the Control Panel. This data is recorded as either Warnings or Faults and can be viewed
in the software menu tree at the screen location MENU>VIEW>. These Warnings and Faults can also
be communicated by the Versatile Interface Board (VIB), if this option has been installed, to an external device or system; (see Appendix C.0 - Versatile Interface Board). This data will also be
recorded in the Data Collection Module option if this has been selected. Please see Appendix B.0 Data Collection Module for instructions on how to access this data via the DCM.
Any Warnings and Faults that may occur will be displayed on the Main screen of the Control Panel.
The Liebert FS’ Warnings and Faults tables (see Tables 15 and 16), describe these Warnings, meanings and possible causes. The operator action required or automatic system function that will result is
explained.
In addition to the information displayed on the Main screen, other system information that can be
used for troubleshooting is available and can be accessed from the Control Panel. From the Main
screen the Menu screen can be selected by pressing (F6) on the Control Panel located below MENU.
Figure 89 USER level menu
MENU>
1.
2.
3.
4.
5.
PARAMETERS
VIEW
SECURITY
ABOUT
TOOLS
HOME
DONE
Selecting View displays various system statuses including real-time and historical data. You can
select the function by number.
Figure 90 VIEW menu
MENU>VIEW>
1. TIME/DATE
2. TEMPERATURES
3. VOLTAGES
4. HISTORY
5. OPTIONS
6. NETWORK
7. ELECTRICAL
8. VITALS
HOME
DONE
Selecting History will provide a history of Warnings and Faults as introduced in Section 5, Operations, of this manual. Other information that can be useful in troubleshooting are the Temperatures,
Voltages, Options, Electrical and Vitals screens.
Warning/Fault: The Liebert FS holds 35 warning and fault information, respectively. A single screen
shows seven warnings or faults. Users can move between pages using PREV, NEXT button. (See
Figures 91 and 92 below).
78
Troubleshooting
Figure 91 Warning history
01
02
03
04
05
06
07
03/10/05
03/10/05
02/24/05
01/30/05
12/20/04
11/13/04
09/30/04
11:43
10:37
04:03
23:22
13:45
07:28
16:23
W
W
W
W
W
W
W
AUX POWER LOW
VIB INOPERATIVE
OVERSPEED
STATOR HOT
ROTOR HOT
RUNOUT
VACUUM
NEXT
DONE
CURRENT OFFSET
CHECKSUM
SOFTWARE OV
DC BUS OV
SPARE OPEN
INTER PROCR COMM
MISER
NEXT
DONE
Figure 92 Fault history
01 03/10/05
02 03/10/05
03 02/24/05
04 01/30/05
05 12/20/04
06 11/13/04
07 09/30/04
RESET
11:43
10:37
04:03
23:22
13:45
07:28
16:23
F
F
F
F
F
F
F
The warnings, fault meanings and possible causes in the following text and in Table 15 may be used
in troubleshooting the messages and may also aid in identifying conditions outside the flywheel system that may adversely affect it.
8.2
Warnings
A Warning is an indication of an abnormal system condition significant enough to warrant being
annunciated and logged. Warning conditions may indicate that a system parameter is out of its normal operating range, or may signal an external problem. A Warning indication is for information only
and does not require any operator intervention for continued operation of the unit. While in Warning
condition, normal operation of the unit will continue unimpeded. A warning can indicate an operating
condition that warrants observation and may require preventative maintenance.
Figure 93 Warning screen
Liebert FS
MODE:
CHARGE
STATUS:
2 WARNINGS
D
RPM:
SOC:
SOC:
BUS:
PWR:
SHUTDN
LOCK
Warning Status Message
MORE
V
U
C
39562
45.4%
538V
32.3kW
MENU
More information
Button (F5)
The Warning condition is indicated by the System Status field displaying “WARNING” in the Control
Panel window (see Figure 93). If one Warning is present, the Warning Label (see Table 15.) will be
displayed.
While the Warning condition exists, and if more than one Warning is present, F5 the “More Info” key
will be enabled in the Control Panel window. If pressed, the separate Warning Labels will be displayed in the Control Panel window.
Any of eight warnings could occur while the Liebert FS is operating. Warnings give advance alert of
potential problems and schedule service and preventive maintenance. These can be monitored and
investigated through the use of data from the Control Panel and system tests.
79
Troubleshooting
Table 15 lists the warnings and some troubleshooting steps that may be taken if any of the Warnings
in appear.
Table 15
Warnings
Warning
Label
Meaning / Possible Causes
Troubleshooting
AUXPOWER
LOW
Auxiliary power supply is low when the system is
not in OFF mode.
Factory-configurable warning
Check / Test Auxiliary power supply
VACUUM
LOW
Drag power exceeds 85W *
Check Vitals and Vacuum History
MISER HIGH
Miser voltage is higher than 2V
Calibrate board
RUNOUT
HIGH
Runout is higher than 2.0 mil.*
Check Vitals and Runout History
PWR SPLY
VOLT LOW
Power supply for PPMC/PCMC is lower than 21V.
Power supply for PPMC/PCMC is lower
than 21V
VIB
INOPERATIVE
VIB inoperative while enabled
Check VIB cable connections and wiring
OVERSPEED
Speed is higher than the Max Speed
Have Certified Service personnel check
software settings
SET TIME/
DATE
Time and date have not been set
Set Time/Date in Menu>View>Time/Date
* Warnings of this nature should be monitored and may be used to schedule preventive maintenance.
If Warnings persist, contact your local Liebert representative or contact Liebert Global Services at
800-543-2378. You may also visit the Liebert Web site for information at www.liebert.com.
NOTE
A “Standby, Motor Hot” message may be displayed as a result of consecutive and repetitive
discharges. This is not a Warning but a normal operating occurrence that may occur due to
frequent charging and discharging of system. Once motor cools it will automatically resume
operation.
80
Troubleshooting
8.3
Faults
A Fault is defined as an undesirable system operating condition that could cause further damage to
the system or potentially drop the load. Once detected, Faults may trigger an appropriate emergency
action such as shutting the unit down. Most Fault conditions are automatically taken care of by the
Liebert FS control system and require no Operator intervention. A few Fault conditions may be
resolved only through operator intervention or service by a Liebert technician.
A Fault condition must be valid for a certain amount of time before it is recognized as an active Fault.
This prevents spurious signals from causing false Fault detection and unnecessary state changes.
Figure 93 shows the appearance of an active Fault on the main screen.
Figure 94 Fault screen descriptions
Fault Status Message
Liebert FS
D
RPM:
SOC:
SOC:
BUS:
PWR:
FAULT
MODE:
STATUS:
2 FAULTS
CLEAR
MORE
V
U
C
48351
75.4%
538V
0.0kW
Bus Power
MENU
More information
Button (F5)
Fault Clear Button (F3)
While in Fault condition, normal operation of the unit is suspended, the operation of the Power Conversion Module is paused, and the unit transitions into FAULT Mode, where it waits for one of the following to occur:
1. The condition to clear the fault [AUTO CLEAR]
2. The unit to automatically transition in SHUTDOWN Mode [AUTO SHUTDOWN]
3. Operator action [OPERATOR CLEAR].
The Fault condition is indicated by the System Mode displaying “FAULT” in the Control Panel window.
If there are multiple Fault conditions present, the F5 “More Info” key will be enabled in the Control
Panel window. If pressed, information related to the specific Faults will be displayed in the Control
Panel window (see Figures 54 through 56). If there are multiple faults they will both be displayed by
pressing the F5 “MORE” button.
In many cases, when FAULT Mode is entered, the Fault may be cleared by pressing the F3 “CLEAR
FAULT” button on the Control Panel or utilizing the VIB option - if enabled - to send a “CLEAR
FAULT” signal to the system. In order to “CLEAR FAULT” the operator must be in proper security
access level; User or above. Table 16 describes the fault labels, meanings and possible causes for the
81
Troubleshooting
Faults. Table 17 - Troubleshooting describes actions that may alleviate the condition or provide
valuable information for technical support.
Table 16
Faults—causes and responses
Fault Label
Meaning / Possible Causes
Operator Auto
Auto
Clear* Clear Shutdown
GROUND FAULT
Ground fault current out of range.
X
HW BUS OV
HW overvoltage. (hardware protection)
X
X PHASE OC
AC phase overcurrent. x = A, B, C.
X
IGBT OVRTEMP
IGBT overtemperature.
X
VACUUM FAULT
Drag power exceeds 125W.
X
RUNOUT FAULT
Runout higher than 2.9mil.
X
MISER FAULT
Miser voltage is higher than 5V.
X
BEARING
Magnetic bearing fault.
X
AUX POWER LOW
Auxiliary power supply voltage is low when the
system is in Off mode. Configurable fault.
INTER PRCR COMM
Communication error with secondary DSP. System
reboots.
PWR SPLY VOLT
Power supply voltage is lower than 19V. (Speed
dependent; auto shutdown at high speed)
X
UNDEF PDP INT
Undefined PDP interrupt.
X
CURRENT OFFSET
AC motor current sensor error.
X
SW OV
DC bus voltage is higher than the threshold, which is
service-configurable.
X
CHECKSUM
Calculated checksum does not match the stored
checksum.
S
CONTACTOR TIME OUT
Bus voltage/current is not stable while trying to close
or open contactor.
X
CONTACTOR CLOSE FAIL
Contactor failed to close on startup.
X
FAN OPEN
Fan open circuit or disconnected.
X
X
X
FAN SHORT
Fan short circuit.
X
PUMP OPEN
Pump open circuit or disconnected.
X
PUMP SHORT
Pump short circuit.
X
HW OVERSPEED
Hardware detected overspeed.
X
PRECHARGE PROTECTION
Stop PWM when large voltage differential exists
between internal and external bus.
X
BUS CURRENT OFFSET
DC current sensor error.
X
X
S - Indicates a Certified Service Provider will be required to reset system.
NOTE
If a fault recurs after being cleared by the operator, and the condition persists, contact your
Liebert technician.
Faults that initiate an AUTOSHUTDOWN include: MISER, RUNOUT, PWR SPLY VOLT (at high
speed), and will require Service level and higher to reset.
82
Troubleshooting
Fault messages displayed can, in some cases, be investigated for a solution. Listed below in Table 17
are troubleshooting steps for the Fault messages that can occur.
Table 17
Troubleshooting
Fault Label
Troubleshooting Action
GROUND FAULT
Contact Service provider. Schedule service.
HW BUS OV
Check DC bus voltage at UPS and adjust as necessary to within threshold.
X PHASE OC
Check IGBT, resistor diodes.
IGBT OVRTEMP
Check cooling pump, test pump and fans.
VACUUM FAULT
Check in History, Vitals, collect data, contact Certified Service Provider.
RUNOUT FAULT
Check in History, Vitals, collect data, contact Certified Service Provider.
MISER FAULT
Check calibration in Tools.
BEARING
Contact Service provider. Schedule service.
AUX POWER LOW
Check and test Auxiliary Power module.
INTER PRCR COMM
Contact Service provider. Schedule service.
PWR SPLY VOLT
Check data in Menu>View>Electrical.
UNDEF PDP INT
Contact Service provider. Schedule service.
CURRENT OFFSET
Contact Service provider. Schedule service.
SW OV
Contact Service provider. Schedule service.
CHECKSUM
Contact Service provider. Schedule service.
CONTACTOR TIME OUT
Check DC bus voltage at UPS and adjust as necessary to within threshold.
CONTACTOR CLOSE FAIL
Check DC bus voltage at UPS and adjust as necessary to within threshold.
FAN OPEN
Check fan connections.
FAN SHORT
Check fan.
PUMP OPEN
Check pump connections.
PUMP SHORT
Check pump.
HW OVERSPEED
Contact Service provider. Schedule service.
PRECHARGE PROTECTION
Contact Service provider. Schedule service.
BUS CURRENT OFFSET
Check bus voltages, contact service provider to calibrate settings.
Refer to the general drawings in Appendix D.0 - Installation Drawings for the location of system
components.
If a Fault condition persists contact your Liebert technician. You may also visit the Liebert Web site
at www.liebert.com for information.
83
UPS Interconnection Kits
APPENDIX A.0 UPS INTERCONNECTION KITS
Your Liebert FS is equipped with a UPS interconnection kit to connect it to one of these Liebert UPS
systems:
•
•
•
•
Liebert Series 610™, 600T™ or 600™
Liebert Npower™
Liebert Series 300™
Liebert HiPulse™
The Liebert FS system must be installed according to the instructions in 4.0 - Installation. Integrate
your Liebert FS system into an Uninterruptible Power Supply (UPS) system in accordance with the
instructions and drawings in this manual.
!
CAUTION
The initial system startup must be performed ONLY under the supervision of a
Liebert-certified service technician to ensure proper system operation. Failure to abide by
instructions provided herein may void your warranty.
Contact your local Liebert sales representative or Liebert Global Services at 1-800-LIEBERT
to arrange for system startup.
NOTE
Before beginning installation, ensure that your Liebert FS unit is equipped with the correct
UPS interconnection kit.
The first two digits of the Liebert FS model number represent the UPS system the product is
designed for, as shown in Table 18.
Table 18
Key to UPS model interconnection
Liebert FS Model #
Use With Liebert UPS
25FS
Liebert Series 300
37FS
Liebert Npower
39FS
Liebert Series 610/600T/600
Contact Liebert
Liebert HiPulse (50Hz European Model)
Appendix A.1 Wiring Connections
Appendix A.1.1 General Wiring Considerations
!
CAUTION
A qualified electrical contractor must perform all electrical connections. The wires (DC power,
ground, optional status/control and auxiliary backup power) that connect the Liebert FS
system(s) to the UPS system are field-supplied or, as an option, by Liebert. Wire size and
installation must comply with all applicable local, regional and national regulations (e.g.,
National Electric Code for USA).
The electrical connections to the Liebert FS are:
•
•
•
•
•
DC power
Status/control
Ground
Auxiliary backup power
Remote monitoring (optional)
NOTE
The connection instructions included in this section address ONLY the cabling of the DC power
and Status/Control connections specific to the individual UPS interconnection kits.
Instructions for installing ground, auxiliary backup power and remote monitoring connections
are in 4.0 - Installation.
84
UPS Interconnection Kits
Power and status/control wiring must be run in separate conduits or cable trays. Refer to Appendix
D.0 - Installation Drawings for locations of the various electrical connections between Liebert FS
system(s) and UPS system.
!
CAUTION
Power and status/control wiring must be separated
Figure 95 Top view of Liebert FS Cabinet with UPS interconnection kit
Ground Terminal
DC Power
Terminals
Rear
Front
Fan Coil Module
Circuit
Breaker
Manufacturer’s
Connection
Status/Control
Terminal Block
(upgraded)
!
!
CAUTION
Do not cut entry holes for conduit while the access plates are still set on the top of the
Liebert FS cabinet. Remove the access plates from the cable-access areas in the top of the
Liebert FS cabinet prior to cutting entry holes.
CAUTION
After reinstalling access plates, be certain that no foreign matter (metal shavings, insulation
or wire fragments, etc.) remains inside the Liebert FS. Likewise, be certain to block any
“extra holes” in the plates through which foreign matter (or rodents) could later enter the
Liebert FS.
85
UPS Interconnection Kits
Appendix A.1.2 DC Power Connections
The DC power connections to the Liebert FS are made through the circuit breaker (see Figure 96) in
the UPS interconnection kit installed in your Liebert FS. The maximum wire size for the circuit
breaker terminals is 350MCM - 600VDC (approximate metric equivalent: 150mm2 wire section). Wire
size and installation must comply with all applicable local, regional and national regulations (e.g.,
National Electric Code for USA).
Figure 96 Circuit breaker
Liebert FS
Positive
Terminal
Liebert FS
Negative
Terminal
The Liebert FS cabinet is configured for top entry cables in standard configuration. The cables can
also be run through the side panels. The Liebert FS cabinet does not accommodate bottom entry
cables.
The connection of the circuit breaker is described in Figure 135 - Elevation drawing—Liebert FS
cabinet with integrated circuit breaker. Refer to this drawing to ensure that the adequate connections are performed.
Circuit Breaker Torque
Tighten the positive and negative terminals of the DC power connections on the circuit breaker to
250 in-lb. (29 N-m) unless the equipment is labeled with a different torque value.
86
UPS Interconnection Kits
Appendix A.2 Installing the Liebert FS With a Liebert Series 610, Liebert Series 600T or
Liebert Series 600
The Liebert Series 610/600T/600 UPS interconnection kit for the Liebert FS is compatible with the
Liebert Series 610, Liebert Series 600T and Liebert Series 600 models in Table 19.
Table 19
Liebert Series 610/600T/600 model ratings
UPS Output Rating
kVA
65
80
100
125
150
225
300
400
400
450
500
500
625
750
750
1,000
kW
52
64
80
100
120
180
240
320
360
360
400
450
500
600
675
900
Figure 97 Liebert Series 610 225kVA UPS
Appendix A.2.1 Description - Liebert Series 610/600T/600 UPS Interconnection Kit
The Liebert Series 610/600T/600 UPS interconnection kit for the Liebert FS is composed of:
DC Power Interface
One Thermal-Magnetic Molded Case circuit breaker rated for 250 ADC - 600VDC equipped with:
• An undervoltage relay (UVR) rated for 48VDC, 50 mA
• Auxiliary contacts: Normally Open (NO) and Normally Closed (NC).
Status/Control Interface
One Status/Control Terminal Block used to ensure the status/control connections between the
Liebert FS and the Liebert Series 610/600T/600.
87
UPS Interconnection Kits
Appendix A.2.2
Status/Control Connections - Liebert Series 610/600T/600 UPS Interconnection Kit
The status/control interface is the Status/Control Terminal Block. The connection of the Status/Control Terminal Block is described in Figure 137 - Control wiring diagram—Liebert FS cabinet manually operated circuit breaker. Refer to this drawing to ensure that proper connections are
performed. In case multiple Liebert FS units are connected to the same UPS DC bus, refer to Figure
129 - Control wiring—external interconnect diagram, Liebert FS cabinet to Liebert Series
610 UPS module to perform the Status/Control connections between each Liebert FS.
This interconnection kit includes Status/Control Connections that enable transfer of signals between
the Liebert FS system(s) and the UPS system such as:
• Circuit breaker status (closed/open); and
• Undervoltage relay coil excitation voltage.
Figure 98 Liebert Series 610/600T/600 status/control terminal block wiring
B
r
o
w
n
B
r
o
w
n
B
l
u
e
Yellow/
Blue
Y
e
l
l
o
w
Row for
installation of
contractor wire
connections
Two rows
1
2
3
4
5
6
7
8
9
10
The recommended gauge for Status/Control connection wires is 16 AWG - 600VDC (1.3mm2 wire section). Wire size and installation must comply with all applicable local, regional and national regulations (e.g., National Electric Code for USA).
Appendix A.2.3 UPS Configuration - Liebert FS and Liebert Series 610, 600T or 600
To optimize the integration between the Liebert Series 610/600T/600 UPS system and the Liebert FS,
some parameters must be checked on the UPS system:
• The UPS rectifier walk-in time must be set as short as possible. Contact your Liebert representative if your unit has received the upgraded board that enables the setting of “rectifier walk-in
time” lower than standard.
• Ensure that the “auto battery self test” has either been disabled or upgraded to accommodate
Liebert FS integration.
88
UPS Interconnection Kits
Appendix A.2.4
Liebert FS Configuration - Single Liebert FS on Liebert Series 610/600T/600 DC Bus
The following Software Control Parameters must be set when the Liebert FS is connected to the DC
bus of the Liebert Series 610/600T/600 UPS system.
NOTE
The Software Control Parameter values specified below are recommended. These values may
require adjustments due to the battery type. These must be used unless otherwise specified by
the Liebert-certified service technician at initial system startup.
Instructions to set these parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at
Initial System Startup.
Table 20
Liebert FS Software Control Parameter settings
Liebert FS Software Control Parameter
Setting
Charge Voltage
520VDC
Regulation Voltage
510VDC
Vreg Delta
0VDC
Maximum Charge Current
See Table 21
Charge Amps/Volts
See Table 21
Table 21
Liebert FS Software Control Parameters varying with UPS size
UPS Output Rating (kVA)
65
80
100
125
150
Liebert FS Maximum Charge Current (A)
25
31
39
49
50
Liebert FS Charge Amps/Volts (A/V)
1.7
2.1
2.6
3.3
3.4
Appendix A.2.5
Liebert FS Configuration - Multiple Liebert FS Units on Liebert Series 610/600T/600
DC Bus
The Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are connected in parallel on the DC bus of a Liebert Series 610/600T/600 UPS system.
Instructions to set these parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at
Initial System Startup.
Multiple Liebert FS Parallel Operation - Regular Configuration with Liebert Series 610/
600T/600
The Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are connected in parallel on the DC bus of a Liebert Series 610/600T/600 UPS system for proper operation
with longer run times or higher backup power requirements. The Liebert FS units will contribute all
together at the same time to the task of supporting the UPS DC bus.
NOTE
This configuration is recommended for UPS models with output power levels greater than
150 kVA (i.e., 225, 300, 400, 450, 500, 625, 750 and 1,000 kVA).
NOTE
In this configuration, the UPS DC bus usually does NOT have batteries in parallel with the
Liebert FS units, however, parallel operation with batteries is acceptable. If batteries to be used
are in parallel with the Liebert FS units on the UPS DC bus, contact your local Liebert sales
representative to arrange a review of the application.
NOTE
Your Liebert-certified service technician will configure the Software Control Parameter values
at initial system startup depending on the number of paralleled units.
89
UPS Interconnection Kits
Appendix A.3 Installing the Liebert FS With a Liebert Npower UPS
The Liebert Npower UPS interconnection kit for the Liebert FS is compatible with the Liebert
Npower models in Table 22.
Table 22
UPS
Output
Rating
Liebert Npower model ratings
kVA
30
40
50
65
80
100
130
kW
24
32
40
52
64
80
104
Figure 99 Liebert FS integrated into a Liebert Npower UPS system
Liebert FS
Liebert
Npower UPS
Appendix A.3.1 Description - Liebert Npower UPS Interconnection Kit
The Liebert Npower UPS interconnection kit for the Liebert FS is composed of:
DC Power Interface
One Thermal-Magnetic Molded Case circuit breaker rated for 250 ADC - 600VDC equipped with:
• An undervoltage relay (UVR) rated for 24VDC, 50 mA
• Auxiliary contacts: Normally Open (NO) and Normally Closed (NC).
Status/Control Interface
One Liebert Npower Battery Information Board (BIB). This board is used to ensure the status/
control connections between the Liebert FS and the Liebert Npower.
90
UPS Interconnection Kits
Appendix A.3.2 Status/Control Connections - Liebert Npower UPS Interconnection Kit
The status/control interface is the Liebert Npower Battery Information Board (BIB). The connection
of the BIB is described in Figure 140 - Control wiring diagram—Liebert FS - optional electrically operated circuit breaker Liebert Npower units. Refer to this drawing to ensure that the
proper connections are performed. In case multiple Liebert FS units are connected to the same UPS
DC bus, refer to Figure 132 - Control wiring diagram, Liebert FS power rack system in parallel for capacity to perform the Status/Control connections between each Liebert FS.
This interconnection kit includes Status/Control Connections that enable transfer of signals between
the Liebert FS system(s) and the UPS system such as:
• Circuit breaker status (closed/open); and
• Undervoltage relay coil excitation voltage.
The recommended gauge for status/control connection wires is 16 AWG - 600VDC (1.3mm2 wire section). Wire size and installation must comply with all applicable local, regional and national regulations (e.g., National Electric Code for USA).
Appendix A.3.3 UPS Configuration - Liebert FS and Liebert Npower
To optimize the integration between the Liebert Npower UPS system and the Liebert FS, some
parameters must be checked on the UPS system:
• The UPS rectifier walk-in time must be set at a value as low as possible. Contact your Liebert representative if your unit has received the upgraded board that permits the setting of “rectifier
walk-in time” lower than standard.
• Ensure that the “auto battery self test” has either been disabled or upgraded to accommodate
Liebert FS integration.
Appendix A.3.4 Liebert FS Configuration - Single Liebert FS Unit
The following Software Control Parameters must be set when the Liebert FS is connected to the
DC bus of the Liebert Npower UPS system.
NOTE
The Software Control Parameter values specified below are recommended. These values may
require adjustments due to the battery type. These must be used unless otherwise specified by
the Liebert-certified service technician at initial system startup. Instructions to set these
parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at Initial System
Startup.
Table 23
Liebert FS Software Control Parameters
Liebert FS Software
Control Parameter
Setting
Charge Voltage
520VDC
Regulation Voltage
510VDC
Vreg Delta
0VDC
Maximum Charge Current
See Table 24
Charge Amps/Volts
See Table 24
Table 24
Liebert FS Software Control Parameters varying with UPS size
UPS Output Rating (kVA)
30
40
50
65
80
100
130
Liebert FS Maximum Charge Current (A)
11
15
19
25
31
38
50
Liebert FS Charge Amps/Volts (A/V)
0.8
1.0
1.3
1.7
2.1
2.6
3.4
91
UPS Interconnection Kits
Appendix A.3.5 Liebert FS Configuration - Multiple Liebert FS Units on Liebert Npower DC Bus
Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are connected
in parallel on the DC bus of a Liebert Npower UPS system for proper operation with longer run times
or higher backup power requirements.
Instructions to set these parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at
Initial System Startup.
NOTE
In this configuration, the UPS DC bus usually does NOT have batteries in parallel with the
Liebert FS units, however, parallel operation with batteries is acceptable. If batteries to be used
are in parallel with the Liebert FS units on the UPS DC bus, contact your local Liebert sales
representative to arrange a review of the application.
NOTE
Your Liebert-certified service technician will configure the Software Control Parameter values
at initial system startup depending on the number of paralleled units.
92
UPS Interconnection Kits
Appendix A.4 Installing the Liebert FS With a Liebert Series 300 UPS
The Liebert Series 300 UPS interconnection kit for the Liebert FS is compatible with the Liebert
Series 300 models in Table 25.
Table 25
List of Liebert Series 300 models ratings
UPS Output Rating
kVA
10
15
20
30
40
50
65
75
100
125
kW
8
12
16
24
32
40
52
60
80
100
Figure 100 Liebert Series 300 UPS
Appendix A.4.1 Description - Liebert Series 300 UPS Interconnection Kit
The Liebert Series 300 UPS interconnection kit for the Liebert FS is composed of:
DC Power Interface
One Thermal-Magnetic Molded Case circuit breaker rated for 250 ADC - 600VDC equipped with:
• An undervoltage relay (UVR) rated for 24VDC, 50 mA
• Auxiliary contacts: Normally Open (NO) and Normally Closed (NC).
Status/Control Interface
One status/control terminal Block used to ensure the status/control connections between the
Liebert FS and the Liebert Series 300.
93
UPS Interconnection Kits
Appendix A.4.2 Status/Control Connections - Liebert Series 300 UPS Interconnection Kit
The status/control interface is the Status/Control Terminal Block. The connection of the Status/Control Terminal Block is described in the Figure 137 - Control wiring diagram—Liebert FS cabinet - manually operated circuit breaker. Refer to this drawing to ensure that the adequate
connections will be performed. If multiple Liebert FS units are connected to the same UPS DC bus,
refer to Figure 129 - Control wiring—external interconnect diagram, Liebert FS cabinet to
Liebert Series 610 UPS module to perform the Status/Control connections between each
Liebert FS.
This interconnection kit includes status/control connections that enable transfer of signals between
the Liebert FS system(s) and the UPS system such as:
• Circuit breaker status (closed/open); and
• Undervoltage relay coil excitation voltage
Figure 101 Liebert Series 300 status/control terminal block wiring
B
r
o
w
n
B
r
o
w
n
B
l
u
e
Yellow/
Blue
Y
e
l
l
o
w
Row for
installation of
contractor wire
connections
Two rows
1
2
3
4
5
6
7
8
9
10
The recommended gauge for status/control connection wires is 16 AWG - 600VDC (1.3mm2 wire section). Status/Control wires must be sized and installed in compliance with all applicable local,
regional and national regulations (e.g., National Electric Code for USA).
Appendix A.4.3 UPS Configuration - Liebert FS and Liebert Series 300
To optimize the integration between the Liebert Series 300 UPS system and the Liebert FS, some
parameters must be checked on the UPS system:
• The UPS rectifier walk-in time must be set at a value as low as possible. Contact your Liebert representative if your unit has received the upgraded board that enables the setting of “rectifier
walk-in time” lower than standard.
• Ensure that the “auto battery self test” has been either disabled or upgraded to accommodate
Liebert FS integration.
94
UPS Interconnection Kits
Appendix A.4.4 Liebert FS Configuration - Single Liebert FS on Series 300 DC Bus
The following Software Control Parameters must be reset when the Liebert FS is connected to the DC
Bus of the Liebert Series 300 UPS system.
NOTE
The Software Control Parameter values specified below are recommended. These values may
require adjustments due to the battery type. These must be used unless otherwise specified by
the Liebert-certified service technician at initial system startup.
Instructions to set these parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at
Initial System Startup.
Table 26
Liebert FS Software Control Parameter settings
Liebert FS Software Control Parameter
Setting
Charge Voltage
395VDC
Regulation Voltage
385VDC
Vreg Delta
0VDC
Maximum Charge Current
See Table 27
Charge Amps/Volts
See Table 27
Table 27
Liebert FS Software Control Parameters varying with UPS size
UPS Output Rating (kVA)
10
15
20
30
40
50
65
75
100
125
Liebert FS Maximum Charge Current (A)
5
8
10
16
21
26
34
39
50
50
0.7
1.1
1.4
2.1
2.8
3.5
4.5
5.2
6.7
6.7
Liebert FS Charge Amps/Volts (A/V)
Appendix A.4.5 Liebert FS Configuration - Multiple Liebert FS Units on Liebert Series 300 DC
Bus
Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are connected
in parallel on the DC bus of a Liebert Series 300 UPS system for proper operation with longer run
times or higher backup power requirements.
Instructions to set these parameters on the Liebert FS are in 6.5.3 - Control Parameters Setup at
Initial System Startup.
NOTE
In this configuration, the UPS DC bus usually does NOT have batteries in parallel with the
Liebert FS units, however, parallel operation with batteries is acceptable. If batteries to be used
are in parallel with the Liebert FS units on the UPS DC bus, contact your local Liebert sales
representative to arrange a review of the application.
NOTE
Your Liebert-certified service technician will configure the Software Control Parameter values
at initial system startup depending on the number of paralleled units.
95
UPS Interconnection Kits
Appendix A.5 Installing the Liebert FS With a Liebert HiPulse UPS
The Liebert HiPulse UPS interconnection kit for the Liebert FS is compatible with the Liebert
HiPulse™ models in Table 28.
Table 28
Liebert HiPulse model ratings
UPS Output Rating
kVA
80
120
160
200
300
400
500
600
800
kW
64
96
128
160
240
320
400
480
640
Appendix A.5.1 Description—HiPulse UPS Interconnection Kit
HiPulse UPS interconnection kit is composed of:
DC Power Interface
One Thermal-Magnetic Molded Case circuit-breaker rated for 250 ADC, 600VDC equipped with
auxiliary contacts: two (2) sets of Normally Open (NO) and Normally Closed (NC).
Status/Control Interface
One Status/Control Terminal Block used to ensure the status/control connections between the
Liebert FS and the Liebert HiPulse.
Appendix A.5.2 Status/Control Connections—Liebert HiPulse UPS Interconnection Kit
The status/control interface of the IKIT-A05 is the Status/Control Terminal Block. The connection of
the Status/Control Terminal Block is illustrated in Figure 102. Please refer to this drawing to ensure
that the proper connections are made. In case multiple Liebert FS units are connected to the same
UPS DC bus, please refer to Figure 144 to perform the Status/Control connections between each
Liebert FS.
This IKIT includes Status/Control Connections that enable transfer of “IKIT circuit-breaker status
(closed/open)” signals between the Liebert FS system(s) and the UPS system.
Figure 102 Liebert HiPulse status/control terminal block wiring
B
l
u
e
Yellow/
Blue
Y
e
l
l
o
w
B
l
u
e
Yellow/
Blue
Y
e
l
l
o
w
Row for
installation of
contractor wire
connections
Two rows
1
2
3
4
5
6
7
8
9
10
The recommended gauge for Status/Control Connection wires is 16 AWG – 600 VDC (approximate
metric equivalent: 1.3 mm² wire section). All wiring must comply with all applicable local, regional,
national regulations.
96
UPS Interconnection Kits
Appendix A.5.3 IKIT-A05 DC Power Connections
The DC power connections to the Liebert FS are made through the circuit-breaker (see Figure 103)
in the IKIT-A05. The minimum wire size to be used is 1/0 AWG - 600VDC wire (54 mm2 wire section).
The maximum wire size for the circuit-breaker terminals is 350MCM – 600VDC (150 mm2 wire section). All wiring must comply with all applicable local, regional, national regulations. Use copper conductors only, rated minimum 140°F (60°C).
Figure 103 Circuit-breaker (open door and cabinet faceplate removed)
Liebert FS positive
terminal
Liebert FS negative
terminal
The Liebert FS cabinet is configured for top entry cables in standard configuration. The cables can
also be run through the side panels. The Liebert FS cabinet does not accommodate bottom entry
cables.
The connection of the circuit-breaker is described in Figure 135 - Elevation drawing—Liebert FS
cabinet with integrated circuit breaker. Refer to this drawing to ensure that the proper connections are made.
Circuit Breaker Torque
Tighten the positive and negative terminals of the DC power connections on the circuit breaker to
250 in-lb. (29 N-m) unless the equipment is labeled with a different torque value.
Appendix A.5.4 UPS Configuration—Liebert FS and Liebert HiPulse
To optimize the integration between the interconnected UPS system and the Liebert FS, some parameters must be checked on the UPS system:
• The UPS rectifier walk-in time must be set at a value as low as possible. Please check with your
UPS Manufacturer representative if your unit has received the upgraded board that enables the
setting of “rectifier walk-in time” lower than standard.
• Check that the “auto battery self test” has either been disabled or upgraded to accommodate
Liebert FS integration.
97
UPS Interconnection Kits
Appendix A.5.5 Single Liebert FS on UPS DC Bus
The following Liebert FS Software Control Parameters must be set when a single Liebert FS is connected alone on the DC bus of the Liebert HiPulse UPS system.
NOTE
The Software Control Parameter values specified below must be used unless otherwise
specified by the Liebert-certified service technician at Initial System Startup.
Instructions on setting these parameters on the Liebert FS are found in 6.5.3 - Control Parameters
Setup at Initial System Startup.
Table 29
Liebert FS Software Control Parameter settings
Liebert FS Software Control Parameter
Setting
Charge Voltage
436 VDC
Regulation Voltage
426 VDC
Vreg Delta
0 VDC
Maximum Charge Current
See Table 30
Charge Amps/Volts
See Table 30
Table 30
Liebert FS Software Control Parameters varying with UPS size
UPS Output Rating (kVA)
80
120
Liebert FS Maximum Charge Current (A)
39
50
Liebert FS Charge Amps/Volts (A/V)
4
5
Appendix A.5.6 Single Liebert FS in Parallel with Battery Pack on UPS DC Bus
The following Software Control Parameters must be reset when the Liebert FS is connected in parallel with a battery pack on the DC bus of the Liebert Hipulse UPS system.
NOTE
The Software Control Parameter values specified below must be used unless otherwise
specified by the Liebert-certified service technician at Initial System Startup. These values may
require adjustments due to the battery type.
Instructions on setting these parameters on the Liebert FS are found in 6.5.3 - Control Parameters
Setup at Initial System Startup.
Table 31
Liebert FS Software Control Parameter settings
Liebert FS Software Control Parameter
Setting
Charge Voltage
436 VDC
Regulation Voltage
426 VDC
Vreg Delta
0 VDC
Maximum Charge Current
See Table 32
Charge Amps/Volts
See Table 32
Table 32
Liebert FS Software Control Parameters varying with UPS size
UPS Output Rating (kVA)
80
120
Liebert FS Maximum Charge Current (A)
39
50
Liebert FS Charge Amps/Volts (A/V)
4
5
98
UPS Interconnection Kits
Appendix A.5.7 Liebert FS Configuration – Multiple Liebert FS Units
Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are connected
in parallel on the DC bus of a Liebert HiPulse™ UPS system.
Instructions to set these parameters on the Liebert FS are found in 6.5.3 - Control Parameters
Setup at Initial System Startup.
Multiple Liebert FS Parallel Operation—Regular Configuration
Liebert FS Software Control Parameters must be reset when multiple Liebert FS units are connected
in parallel on the DC bus of a Liebert HiPulse™ UPS system for proper operation with longer run
times or higher backup power requirements. The Liebert FS units will contribute all together at the
same time to the task of supporting the UPS DC bus.
Instructions on setting these parameters on the Liebert FS are found in 6.5.3 - Control Parameters
Setup at Initial System Startup.
NOTE
In this configuration, the UPS DC bus usually does NOT have batteries in parallel with the
Liebert FS units, however, parallel operation with batteries is acceptable. If batteries to be used
are in parallel with the Liebert FS units on the UPS DC bus, contact your local Liebert sales
representative to arrange a review of the application.
NOTE
Your Liebert-certified service technician will configure the Software Control Parameter values
at Initial System Startup depending on the number of paralleled units.
99
Data Collection Module
APPENDIX B.0 DATA COLLECTION MODULE
Appendix B.1 General Information
Appendix B.1.1 Overview
The Data Collection Module (DCM) is designed to provide real-time data monitoring and data storage
for the Liebert FS. The DCM collects data on virtually every event that occurs in the Liebert FS. Data
such as speed, temperature and voltage are just a few of the data points that the DCM will be collecting and storing on its internal memory card. The DCM has an HTML interface, which means any
Internet browser, such as Internet Explorer or Netscape, is all that is required to access the
Liebert FS data.
Appendix B.1.2 Features
The DCM comes equipped with four (4) RS-232 communication ports and a 10/100 Base-T RJ-45 port.
The DCM runs on the Linux operating system, which resides on the internal compact flash memory
card. Dynamic Host Configuration Protocol (DHCP) has been enabled on the DCM to allow easy integration with an existing network.
Appendix B.2 DCM Installation and Configuration
Appendix B.2.1 Installation
The DCM has been installed at the front of the Liebert FS inside the door on the service panel and has
been securely mounted adjacent to the AC auxiliary fused disconnect. The power cable and the serial
communication cable have been connected at the factory as seen in Figure 104.
The DCM has been installed on the inside door of the Liebert FS and has been securely mounted adjacent to the Control Panel. The power cable and the serial communication cable have been connected
at the factory as seen in Figure 104.
Figure 104 Data Collection Module location, features
Fused
Disconnect
DCM Power and
Serial Connections
Serial
Connections
Ethernet Port
Power
Connection
100
Data Collection Module
Appendix B.2.2 DCM Requirements
The Data Collection Module requires a connection to an existing network via an Ethernet cable. An
RJ-45 jack is built directly into the bottom of the faceplate of the DCM and located adjacent to the
power supply connection. The DCM may also be connected via modem through COM2 serial port.
By connecting to your existing network with an Ethernet cable, you will be able to access the DCM via
your Internet browser. Figure 105 displays the LAN connection, which is located on the bottom side
of the DCM.
Figure 105 DCM LAN connection
Power Connection
LAN Connection
DHCP is enabled at the factory. A connected DHCP Server automatically assigns an IP Address to
the DCM. To confirm that the DCM is enabled and operative, check the Liebert FS Control Panel.
From the Main Menu Screen, select number 2 “View” screen.
Figure 106 Options view
MENU>VIEW
1. TIME/DATE
2. TEMPERATURES
3. VOLTAGES
4. HISTORY
5. OPTIONS
6. NETWORK
7. ELECTRICAL
8. VITALS
HOME
DONE
Select the number 5 “Options” screen to view the current status of the options. To enable or disable
this option, select and press the number 1 for the DCM option. To exit this screen, press the F6 or
“Done” key.
Figure 107 Enable or disable DCM
1. DCM
2. VIB
: INOPERATIVE
: OPERATIVE
HOME
101
DONE
Data Collection Module
To view the Network settings return to the View menu and press number 6 “Network”. The Network
view screen displays the network addresses coming from the DCM. Static address settings can be
entered using the keypad into this screen. The Network screen will show the assigned IP Address,
Default Gateway, Subnet Mask and DNS Server.
Figure 108 Networks view
>>
>>
>>
>>
>>
DHCP:
IP ADDRESS:
NET MASK:
DEFAULT GATEWAY:
DNS SERVER:
ON
192.168.1.155
255.255.255.0
192.168.1.1
192.168.1.13
HOME
DONE
By entering a Password to access the User or Service level mode you can edit this function. Pressing
the EDIT button, F1, will place the system in the edit mode. The DHCP must be disabled or turned
Off to proceed with setting IP addresses and other settings. After pressing EDIT you will see up/down
arrows next to the DHCP On value. Pressing the up or down arrows on the keypad will allow you to
turn this function Off or On.
Figure 109 Networks view, turn off DHCP
>>
>>
>>
>>
>>
DHCP:
IP ADDRESS:
NET MASK:
DEFAULT GATEWAY:
DNS SERVER:
ON
192.168.1.155
255.255.255.0
192.168.1.1
192.168.1.13
HOME
EDIT
DONE
Once you have turned DHCP OFF, press EDIT again and now you will see numbers next to each of
the settings. Pressing the corresponding number will allow you to enter or change that value. At any
time you may press CANCEL to cancel the changes, once changes or entries are complete, press
APPLY to complete entry process. Pressing APPLY will reboot system and in a few minutes the system will display the new screen.
Figure 110 Networks view, edit settings (service level)
1.
2.
3.
4.
5.
OFF
192.168.1.155
255.255.255.0
192.168.1.1
192.168.1.13
DHCP:
IP ADDRESS:
NET MASK:
DEFAULT GATEWAY:
DNS SERVER:
HOME
CANCEL
102
APPLY
Data Collection Module
Appendix B.2.3 Accessing the DCM
From a personal computer connected to the same network as the DCM, enter the IP Address of the
DCM, assigned by the LAN network server or manually configured, into the address line of the Internet browser to gain access to the DCM as seen in Figure 111.
Figure 111 DCM screen
Enter IP
Address
The DCM software has a screen menu bar along the top of the page. Three screens may be accessed:
STATUS, SETUP and DATAFILES. The screens allow for setup of the DCM and different ways to
browse the data recorded by the DCM.
Appendix B.2.4 Configuring DCM System Parameters
One of the tabs in the menu bar is the DCM system “Setup” page. This page will allow you to customize your DCM settings. For example, you may want to assign a static IP Address to the DCM. There
are seven fields on the Setup page as seen in Figure 112. Enter data in the fields and once you are
done with entries, click the Submit button to enter changes or click Reset to reset the DCM.
The default Username and Password for setup are “hello” and “hello” respectively. Liebert recommends changing both the username and password to prevent unauthorized changes to the system.
Figure 112 DCM setup screen
103
Data Collection Module
• Software Version: The current version of the software running on the DCM.
• Configuration Type: Select from the drop-down menu as to whether it is a Static IP Address or
a DHCP server assigned.
• IPAddress: The IP Address of the DCM
• Subnet Mask: The Subnet mask of the DCM
• Gateway: The Gateway of the DCM
• User: The user name to gain access to the DCM.
• Password: The password to gain access to the DCM.
If a parameter setting needs to be changed (i.e., dynamic IP to static IP), please consult your network
administrator for the correct parameters. To save any changes, click the Submit button. The DCM
will automatically reboot itself. You will need to reconnect to the DCM through the browser.
Appendix B.3 DCM Operation
Upon Initial System Startup of the Liebert FS by a Liebert-certified service technician, the DCM will
be operational. There is nothing to turn on or configure.
Appendix B.3.1 Logging into the DCM
Enter the IP Address into the address line of the Internet browser to gain access to the DCM as
shown in Figure 111. The DCM’s IP Address is described in Appendix B.2 - DCM Installation
and Configuration. The first page that appears is the Status Page.
Appendix B.3.2 Status and Detailed Status Screens
The Status page displays various data points from the Liebert FS as shown in Figure 113. Data is
refreshed approximately every five (5) seconds.
Figure 113 DCM status screen
The Status page provides basic system operational data, all data normally found on the Main Screen
of the system Control Panel, such as Mode, RPM and Power.
The Status screen provides more detailed information on system characteristics, such as Serial No.,
and performance. This includes real time information on voltages and temperatures in the system.
104
Data Collection Module
Appendix B.3.3 Datafiles Screen
This screen lists the different files types for viewing and download. There are five files types: F, S, L,
A and D.
• F indicates a fast data packet, containing electrical information such as voltages, amps and watts.
• S represents a slow packet for measurements collected over a longer period, such as temperatures.
• L stands for Log files and these contain information on system modes, statuses and commands.
• A indicates an alarm file and will contain information on any Faults or Warnings recorded.
• D files indicate a system discharge and allow a user to view the time, duration and amount of Discharge.
Figure 114 Datafiles screen
105
Data Collection Module
Appendix B.4 DCM Troubleshooting
Appendix B.4.1 DCM Troubleshooting Principles
There are few circumstances in which the Liebert FS might operate in an unexpected manner. This
section explains a few of these circumstances and offers some solutions to such issues.
Table 33
Troubleshooting
What You See…
What It Means…
What To Do…
A gray windows appears in the Web
browser when connecting to the DCM
The HTML page is not
loading properly
Ensure that the correct IP address is
entered and or check with IT
administrator
Cannot connect to specified address
The DCM is not online or
connect to the network
Verify that the Ethernet cable is
securely connected to the DCM
Appendix B.4.2 Resetting the DCM
If the DCM requires rebooting, use a small object, such as a paperclip, to press the reset button,
shown in Figure 115. The reset button is marked RST. It is adjacent to the RS-232 COM2 Port. The
DCM will emit a series of beeps if the DCM is reset. Allow a minimum of 90 seconds for a complete
reboot before attempting to connect to the DCM.
Figure 115 Data Collection Module reset button
Reset Button
106
Versatile Interface Board
APPENDIX C.0 VERSATILE INTERFACE BOARD
Appendix C.1 General Information—Versatile Interface Board
Appendix C.1.1 Versatile Interface Board Overview
The Versatile Interface Board (VIB) is designed to provide real-time status feedback and control of
the Liebert FS. The VIB has 16 digital outputs (isolated, dry Form C contacts) and three digital
inputs (optical isolator) that provide the user with information about the operational mode and state
of charge of the Liebert FS, as well as the ability for the user to start the system, stop the system and
clear alarms.
The VIB consists of the following components:
•
•
•
•
12578 - Auxiliary I/O Interface Board
11516 - User Interface Board (UIB)
12781 - Cable Assembly
Mounting hardware
Figure 116 shows the two main electrical components of the VIB.
Figure 116 VIB components
P/N 11516
P/N 12578
107
Versatile Interface Board
Appendix C.1.2 VIB Features
The VIB provides fully isolated inputs and outputs that operate on a wide range of voltages for maximum flexibility. Each I/O is programmed to perform a dedicated function. The specific function of
each I/O is listed below in Table 34.
Table 34
I/O
VIB I/O functions
Interface
VIB Designation
1
Description
1
Output 1
Off
2
Output 2
Startup
Mode = Startup (200 < RPM < 25000)
3
Output 3
Charge
Mode = Charge (RPM > 25000)
4
Output 4
SOC >= 0%
State of Charge >= 0%
5
Output 5
SOC >= 12.5%
State of Charge >= 12.5%
6
Output 6
SOC >= 25%
State of Charge >= 25%
7
Output 7
SOC >= 37.5%
State of Charge >= 37.5%
8
Output 8
SOC >= 50%
State of Charge >= 50%
9
Output 9
SOC >= 62.5%
State of Charge >= 62.5%
10
Output 10
SOC >= 75%
State of Charge >= 75%
11
Output 11
SOC >= 87.5%
State of Charge >= 87.5%
12
Output 12
Ready
Mode = Ready (SOC >= 99%)
13
Output 13
Discharge
Mode = Discharge
14
Output 14
Shutdown
Mode = Shutdown
15
Output 15
Warning
Mode = Warning
16
Output 16
Fault
Mode = Fault
17
Input 1
Start2
Start Command Issued
18
Input 2
Shutdown2
Shutdown Command Issued
19
Input 3
Clear Fault
Clear Fault Command Issued
20
Output 17
Rotor Temp
Rotor Temp High
Mode = Off (RPM < 200)
1. The “OFF” signal is also used to indicate if the temperature of the rotor is too warm. If the “OFF” output is asserted while any
of the other “Mode” outputs are asserted (STARTUP, CHARGE, SHUTDOWN, DISCHARGE) or while the State of Charge is
>= 0%, then the rotor is too warm and must cool before charge resumes.
2. “START” and “SHUTDOWN” inputs are mutually exclusive. If they are asserted simultaneously, both will be ignored.
For reference, the I/O designations are shown in Figure 117. The number of each I/O is also labeled
on the circuit board.
108
Versatile Interface Board
Figure 117 I/O Designations
I /O 1
N.C.
MOC
W/N.O.
I/O 2
~
I /O 2
N.C.
MOC
W/N.O.
I/O 3
~
I /O20
~
N.C.
W/N.O.
MOC
~
I/O 20
COM
I /O19
~
N.C.
W/N.O.
USER INTERFACE BOARD ASSY 11518--
W/N.O.
I/O 1
XXXXX XXXXX XXX
xxxx
X xxxxxxxxx xxxxx xxxxxxx
xxxxx xxxxx xxxx xxxx xxxxxx
xx x xxxx xxxxx xx x xxxxxx
xxxxxxxx xxx xxxxx xxxxxxx xx
I/O 19
COM
I /O18
~
N.C.
W/N.O.
~
LIEBERT
I/O Label
(X20)
I/O 8
I/ O 3
MOC
I /O17
~
~
I/ O 4
N.C.
I/O 16
COM
I /O15
~
~
I /O 6
N.C.
W/N.O.
MOC
W/N.O.
I/O 15
COM
I /O14
~
A
N.C.
MOC
W/N.O.
I/O 7
W/N.O.
~
N.C.
I /O 7
~
N.C.
W/N.O.
N.C.
MOC
I /O16
~
I/ O 5
I/O 6
I/O 17
COM
S/N
W/N.O.
I/O 5
N.C.
W/N.O.
N.C.
REV
W/N.O.
I/O 4
COM
I/O 14
N.C.
COM
B
I /O 8
~
N.C.
I /O12
~
~
I /O 9
N.C.
W/N.O.
MOC
N.C.
MOC
W/N.O .
N.C.
I/O 10
I/O 13
COM
I/O 12
COM
I /O11
~
~
I/O 10
N.C.
W/N.O.
MOC
W/N.O .
I/O 9
N.C.
W/N.O.
I /O13
~
C
W/N.O .
I/O 8
COM
109
I/O 11
Versatile Interface Board
Appendix C.2 VIB Installation and Configuration
Appendix C.2.1 VIB Installation
The VIB has been installed behind the service panel of the Liebert FS. The power/communications
cable has been connected to the Main Control Module at the factory.
NOTE
If The VIB option has been purchased separately, refer to the installation instructions included
with the kit for the proper mounting procedure.)
Figure 118 Versatile Interface Board mounted in the Liebert FS
Appendix C.2.2 VIB Requirements
The VIB requires software version 2.09 or later to operate properly. To verify the software version,
press F6 from the main screen of the display panel. The software version is displayed in the lower left
corner of the display. Press F6 when finished.
Appendix C.2.3 VIB Input Specifications
•
•
•
•
•
•
Opto-isolated inputs, active high.
Minimum Trigger Voltage: 3.5V DC (“IN” relative to “COM”).
Maximum Operating Voltage: 32V DC (“IN” relative to “COM”).
Minimum Input Current: 5mA DC.
Inputs must be present for at least 200ms to be recognized as valid signals.
Each input has a green status LED to indicate assertion of the signal.
Appendix C.2.4 VIB Output Specifications
• Dry contact Form C relay: Normally Open (NO), Normally Closed (NC) and Common (COM) outputs available.
• Maximum Contact Resistance: 50mΩ
• Minimum Insulation Resistance: 100MΩ at 500V DC
• Maximum Switching Power: 500VA, 90W
• Maximum Switching Voltage: 250V AC, 30V DC
• Maximum Switching Current: 2A AC, 3A DC
• Minimum Life: 100,000 operations on resistive loads
• Each output has a green status LED to indicate assertion of the signal
110
Versatile Interface Board
Appendix C.2.5 VIB Connections
The VIB is supplied with removable screw-terminal connectors to allow for easy integration
Figure 119. The user must supply the wire as specified below to make the connections to the VIB
connectors.
• Wire gauge: 12-24 AWG
• Stripped length: 0.125" - 0.250"
• Tightening torque: 4.4 inch-pounds (maximum)
Figure 119 VIB screw terminal connections
Appendix C.3 VIB Operation
Upon Initial System Startup of the Liebert FS by a Liebert-certified service technician, your VIB will
be operational. There is nothing to turn on or configure. Make sure that all external connections to
the VIB are made with the Liebert FS power off. Making connections while power is applied may have
undesirable effects and may damage the equipment.
Appendix C.3.1 VIB Operational States
The operational status of the VIB is indicated on the main screen of the Display Panel. There are
three possible states: “Enabled”, “Disabled” and “Not Available”. They are indicated on the Display
Panel by “1,” “0” or “NA,” respectively.
“Enabled” State
If the VIB is detected when the system is powered-up or rebooted, it will automatically be enabled. If
for any reason the VIB has been disabled, it can be re-enabled by pressing F6 (Setup Parameters),
then F3 (UIB Enable). While the VIB is enabled, the “Start,” “Stop” and “Clear Fault” buttons will not
be visible on the Display Panel. To control the Liebert FS from the Display Panel, the VIB must first
be disabled.
“Disabled” State
If the VIB is not detected when the system is powered-up or rebooted, it will automatically be disabled. At any time during operation the VIB can be disabled by pressing F6 (Setup Parameters), then
F3 (UIB Disable). When the VIB is disabled, the inputs are ignored and all outputs are turned off.
Before disabling the VIB, consider how disabling the board will affect other system components.
“Not Available” State
The Liebert FS continually monitors the status of the VIB to verify that it is operating correctly. If the
response from the VIB is not what is expected by the Liebert FS, “WARNING” will be displayed on
the front panel.
111
Versatile Interface Board
Appendix C.4 Troubleshooting the VIB
Appendix C.4.1 UIB State Not Displayed on the Front Panel
• Check that no other faults are present on the display panel.
• Call Liebert for instructions on how to enable the VIB functionality.
Appendix C.4.2 VIB in “Disabled” or “Not Available” State
• Attempt to enable the VIB by pressing F6 (Setup Parameters), then F3 (UIB Enable).
• Verify that the cable to the VIB is plugged in properly.
• Verify power is present on the Auxiliary I/O board. This is indicated by illumination of LED
“LD2”.
• Verify power is provided to the UIB. This is indicated by illumination of “LD1” on the Auxiliary
I/O board and “LD21Pentagon on the UIB. Note that “LD2”on the Auxiliary I/O board will be illuminated only if the UIB is connected.
• Check the continuity of the cable from pin to pin.
Appendix C.4.3 Inputs Not Recognized
•
•
•
•
Verify power is present at the VIB.
Verify the VIB is enabled on the display panel.
Verify that the proper voltage is being supplied to the input.
Verify that the LED indicator corresponding to the input illuminates when the input signal is
applied.
Appendix C.4.4 Outputs Not Asserted
• Verify power is present at the VIB.
• Verify the VIB is enabled on the display panel.
• Verify that the LED indicator corresponding to the output illuminates when the output is
asserted.
112
Installation Drawings
APPENDIX D.0 INSTALLATION DRAWINGS
Appendix D.1 Liebert FS Flywheel Submittal Document Matrix
Following is a list of submittal documents that must accompany each Liebert FS that ships from the
factory. The documents are grouped by Liebert FS model number.
Table 35
Submittal documents accompanying Liebert FS
Liebert FS Model Number:
25FS19ES0000; Liebert
Series 300 Flywheel
Storage Solution
Liebert FS Model Number:
37FS19ES0000; Liebert
NPower Flywheel
Storage Solution
Liebert FS Model Number:
39FS19ES0000; Liebert Series
610/600T/
600 Flywheel Storage Solution
12-100120-00
12-100120-00
12-100120-00
12-100120-02
12-100120-01
12-100120-03
12-100120-08
12-100120-08
12-100120-04
12-100120-09
12-100120-09
12-100120-08
12-100120-10
12-100120-10
12-100120-09
12-100120-11
12-100120-11
12-100120-11
12-100120-12
12-100120-12
12-100120-12
12-100120-13
12-100120-13
12-100120-13
12-100120-14
12-100120-14
12-100120-14
12-100120-16
12-100120-16
12-100120-16
12-100120-17
12-100120-17
12-100120-17
12-100120-18
12-100120-18
12-100120-18
12-100120-20
12-100120-19
12-100120-20
12-100120-21
12-100120-20
12-100120-21
12-100120-22
12-100120-21
12-100120-22
Control_WL_S300
12-100120-22
Control_WL_S610
—
Control_WL_NPower
—
113
Installation Drawings
Appendix D.2 Other Liebert FS Drawings
Following is a list of additional Liebert FS drawings that are available for distribution. These drawings are not directly linked to any specific Liebert FS model number, because most of them are applicable to Liebert FS cabinets connected in parallel and we do not have a unique model number to
identify such units.
Parallel Liebert FS Cabinets – Two - Three Cabinets, no DC Junction Box
•
•
•
•
12-100120-04 – Control Wiring, Liebert Series 610, 600T, 600, 300
12-100120-14 – One Line Diagram
12-100120-10 – Control Wiring, Paralleled Units
12-100120-20 – One Line Diagram, Paralleled Units
Parallel Liebert FS Cabinets – Four-Eight Cabinets with DC Junction Box
• 12-100120-17 – One Line Diagram
• 12-100120-10 – Control Wiring, Paralleled Units
• 12-100120-20 – One Line Diagram, Paralleled Units
Single Liebert FS Cabinets – Additional Elevation Drawings
• 12-100120-11 – Liebert FS Custom Configuration without Circuit Breaker
Figure 120 No UVR, circuit breaker to terminal block wiring
Note: PCM is UPS module.
114
Installation Drawings
Figure 121 Electrical connections
115
Installation Drawings
Figure 122 Electrical system block diagram
116
Installation Drawings
Figure 123 24 UVR, circuit breaker to terminal block wiring
Note: PCM is UPS module.
12-100120-16
Rev. 0
Figure 124 48 UVR, circuit breaker to terminal block wiring
Note: PCM is UPS module.
12-100120-16
Rev. 0
117
Installation Drawings
12-100120-00
Rev. 01
Figure 125 Outline drawing, Liebert FS cabinet
118
Installation Drawings
Figure 126 Control wiring, external interconnect diagram—Liebert FS cabinet to Liebert Npower UPS
module
FUSED
DISCONNECT
C.G. #116
Provided by others;
120V, 60Hz AC, 400VA
UPS-Protected
Aux. Control Power
C.G. #17
TB1
TB69
C.G. #18
TB6
TB73
C.G. #19
TB7
TB70
Liebert FS
Liebert Npower
UPS Module
12-100120-01
Rev. 01
Figure 127Control wiring external interconnect—Liebert FS to Liebert Series 300
FUSED
DISCONNECT
C.G. #116
Provided by others;
120V, 60Hz AC, 400VA
UPS-Protected
Aux. Control Power
C.G. #29
TB1
IL-TB1
Liebert FS
Liebert Series 300
UPS Module
12-100120 -02
Rev. 01
119
Installation Drawings
Figure 128Control wiring—external interconnect diagram, Liebert FS cabinet to Liebert Series 610 UPS
module
FUSED
DISCONNECT
C.G. #116
Provided by others;
120V, 60Hz AC, 400VA
UPS-Protected
Aux. Control Power
C.G. #16
TB1
I1-TB1
Liebert FS
Liebert Series 610
UPS Module
12-100120-03
Rev. 01
120
121
Aux
2
2
1
6
7
8
8
9
9
10
10
1
1
2
2
6
6
7
7
8
8
9
9
10
10
1
1
UVR
NOTES
1. Minimum available UV coil current must be N times 50mA where N = number of Liebert FS paralleled units.
2. 16AWG - 600VDC (minimum) wires to be provided and installed by customer or installation contractor.
3. Contact closed when circuit breaker is closed.
4. Series 600/610 can power a total of three UVRs maximum in any combination of FS units, plus module
battery disconnect switches.
5. UPS-protected 1PH AC source recommended. See Section 2.4.4 in user manual.
4
To UPS
7
UVR
3
5
1
UVR
TB1
3
2
2
Fused Disconnect
6
6
2
8
8
3
9
9
3
12-100120-04
Rev. 01
7
7
1
TB1
10
10
5
UVR
6
3
TB1
2
3
1
1
2
Gnd
N
Line
5
Fused Disconnect
Fused Disconnect
Liebert FS Status/Control
Terminal Block #3
Gnd
N
Line
Line
N
Gnd
Liebert FS Status/Control
Terminal Block #2
Liebert FS Status/Control
Terminal Block #1
Installation Drawings
Figure 129 Control wiring—external interconnect diagram, Liebert FS cabinet to Liebert Series 610 UPS module
76.9"
(1953mm)
Front View
45"
(1143mm)
Right Side View
4.4"
(112mm)
24"
(610mm)
48"
(1219mm)
Shipping
Support
Bands
(on either
side)
122
6"
(1219mm)
12-100120-08
Rev. 01
Weight, unit only: 1300 lb (590kg)
Shipping Weight: 1462 lb (663kg)
54"
(1372mm)
Metal Support
Plates (one on
either side)
Retain -These
are the floor
mounting
brackets
Installation Drawings
Figure 130Elevation drawing, Liebert FS cabinet with shipping package
Installation Drawings
Figure 131Elevation drawing—Liebert FS cabinet
Standard Upgraded
Interactive Display
Top
70.9"
(1801mm)
Bottom
25"
(635mm)
32.5"
(826mm)
Front
Right Side
12-100120 -09
Rev. 1
123
Installation Drawings
12-100120-10
Rev. 01
Figure 132Control wiring diagram, Liebert FS power rack system in parallel for capacity
124
Installation Drawings
Figure 133Liebert FS cabinet with optional power terminal block
Optional Power
Terminal Block
(shown without
cover plate)
12-100120-11
Rev. 01
125
126
25”
(635mm)
Front View
32-5”
(825.5mm)
Right-Side View
12-100120-12
Rev. 01
Half-Size View
of Floor Anchor
Rear Mount
.5"
(12.7mm)
Do Not
Tighten
Weight: 1300 lb. (589.6kg)
12” (305mm) Overhead Clearance
36” (914mm)
Minimum
Front Clearance
Standard
Interactive Liquid
Crystal Display
Installation Drawings
Figure 134Liebert FS cabinet mechanical installation
Installation Drawings
Figure 135Elevation drawing—Liebert FS cabinet with integrated circuit breaker
Factory-Integrated
Circuit Breaker
(shown without cover)
12-100120-13
Rev. 01
127
3
In
128
1
Bi-Directional
Power Converter
1
Liebert FS (3)
FLYWHEEL
Normally
Open
Factory-Integrated
Circuit Breaker
When parallel, all DC power cables must be identical in length, ± 10%.
Liebert FS (2)
Liebert FS (1)
Bi-Directional
Power Converter
Normally
Open
Factory-Integrated
Circuit Breaker
1
FLYWHEEL
1
Battery/Usage
(optional)
Battery/DC In
FLYWHEEL
Normally
Open
Factory-Integrated
Circuit Breaker
Rectifier
Liebert UPS Module
3
Out
Liebert FS
Systems
in Parallel
12-100120-14
Rev. 01
Bi-Directional
Power Converter
Inverter
Installation Drawings
Figure 136One-line drawing, three Liebert FS systems in parallel configuration
To Liebert FS
PCM DC Output
(-)
(+)
Liebert FS
Circuit
Breaker
129
Yel
Blu/Yel
Blu
Brown
Brown
(GND)
UVR Aux.
Contacts
Contractor to Provide Cables
To Liebert UPS Module
(-)
(+)
NC
COM
NO
UVR Control
NOTE
1. PCM – Power Conversion Module
1
3
3
4
5
6
7
8
9
10
TB1
12-100120-16
Rev. 01
To Liebert
UPS Module
Installation Drawings
Figure 137Control wiring diagram—Liebert FS cabinet - manually operated circuit breaker
3
In
130
1
Bi-Directional
Power Converter
Bi-Directional
Power Converter
1
Liebert FS (3)
FLYWHEEL
Normally
Open
Circuit Breaker
DC Junction Box
Bi-Directional
Power Converter
Inverter
Liebert FS
Systems
in Parallel
3
Out
Bi-Directional
Power Converter
12-100120-17
Rev. 01
Liebert FS (N)
FLYWHEEL
Normally
Open
Circuit Breaker
1
NOTES
1. Npower: 2-8 units in parallel without requiring a DC
disconnect switch.
2. Series 610/600 2-3 units in parallel without requiring a DC
disconnect switch. It can power a total of three UVRs
maximum in any combination of FS units, plus module
battery disconnect switches.
Liebert FS (2)
FLYWHEEL
Normally
Open
Circuit Breaker
1
When parallel, all DC power cables
must be identical in length, ± 10%
Liebert FS (1)
FLYWHEEL
Normally
Open
Circuit Breaker
1
Battery/Usage
(optional)
Rectifier
Liebert UPS Module
Installation Drawings
Figure 138One-line diagram—Liebert FS systems with factory-integrated circuit breakers with Liebert UPS
module
Installation Drawings
Figure 139 One-line diagram—single Liebert FS system with factory-integrated circuit breaker supplying
Liebert UPS module
Liebert UPS Module
Rectifier
Inverter
3
In
3
Out
Battery/DC In
Battery/Usage
(optional)
Circuit Breaker
Liebert FS
System
Normally
Open
Bi-Directional
Power Converter
FLYWHEEL
12-100120 -18
Rev. 0
131
Installation Drawings
Brown
(Therm (Out)
113
Therm (In)
12-100120-19
Rev. 0
114
Motor Oper. Power
Brown
TB4 TB6 TB7
TB9
TB3 TB5
Blue/Yellow
Blue N .C.
Note:
1. PCM – Power Conversion Module
400
P2
Yellow N .C.
BT 8
401
Figure 140Control wiring diagram—Liebert FS - optional electrically operated circuit breaker Liebert
Npower units
BT 2
BT 1
114 Therm (Out)
113 Therm (In)
112 (-)
110 (+)
109 Logic GND
108 N.C.
Breaker Aux.
107 Common
106 N.O.
Contacts
105 Motor Oper . Off Signal
104 Motor Oper . On Signal
103 Control Relay Power
102 24 VDC UVR
101 24 VDC +
132
Contractor to Provide Cables
to Liebert UPS Module
Yellow
Blue/Yellow
Blue
Brown
(-) (+) (GND)
Liebert FS
Circuit Breaker
(-)
UVR Aux.
Contacts
To Liebert FS
PCM DC
Output
(+)
(-) (+)
401
400
Brown
Control
Contractor to
Provide
Cables to
Liebert UPS
Module
3
In
133
2
1
Bi-Directional
Power Converter
2
Liebert FS (3)
FLYWHEEL
Normally
Open
Circuit Breaker
DC Junction Box
Bi-Directional
Power Converter
2
Inverter
Liebert FS
Systems
in Parallel
3
Out
Bi-Directional
Power Converter
12-100120-20
Rev. 01
Liebert FS (N)
FLYWHEEL
Normally
Open
Circuit Breaker
NOTES
1. Series 610/600 requires the use of MBD for more than
three units in parallel. It can power a total of three UVRs
maximum in any combination of FS units, plus module
battery disconnect switches.
Liebert FS (2)
FLYWHEEL
When parallel, all DC power cables must be
identical in length, ± 10%.
Series 610/600 requires the use of MBD
for more than three units in parallel.
Liebert FS (1)
FLYWHEEL
Normally
Open
Normally
Open
Bi-Directional
Power Converter
Circuit Breaker
2
2
Module Battery
Disconnect
Circuit Breaker
2
Battery/Usage
(optional)
Rectifier
Liebert UPS Module
Installation Drawings
Figure 141Two-eight paralleled Liebert FS units with factory-integrated circuit breaker in parallel with a
Liebert UPS
Installation Drawings
Figure 142One-line diagram, single Liebert FS and battery with factory-integrated circuit breaker supplying
Liebert UPS—UPS DC terminal point of common connection
Liebert UPS Module
Rectifier
Inverter
3
In
3
Out
Circuit Breaker
Normally
Open
VRLA Battery
or
Flooded Battery
Liebert FS
System
Bi-Directional
Power Converter
FLYWHEEL
12-100120 -21
Rev. 0
134
Installation Drawings
Figure 143One-line diagram, single Liebert FS and battery with factory-integrated circuit breaker supplying
Liebert UPS—UPS battery point of common connection
Liebert UPS Module
Rectifier
Inverter
3
In
3
Out
Circuit Breaker
Normally
Open
VRLA Battery
or
Flooded Battery
Liebert FS
System
Bi-Directional
Power Converter
FLYWHEEL
12-100120 -22
Rev. 0
135
To UPS
136
AUX
UVR
7
7
8
8
9
9
10
10
3
3
4
4
5
5
5
3
5. Available only with IKIT-CB1, A05, D01, E01.
4. UVR not available with IKIT-CB1, A05, D01, E01.
3. Contact closed when circuit breaker is closed
2. 16 AWG-600VDC (minimum) wires to be provided and installed by customer or
installation contractor.
1. Minimum UV coil current must be N times 50mA where N = Number of Liebert FS
paralleled units.
Notes: Unless Otherwise Specified
2
6
6
2
5
5
1
4
4
1
3
3
1
1
2
2
UVR
UVR
3
4
3
6
6
7
7
8
8
3
End (N) Liebert FS Cabinet
FS Status / Control Terminal Block
4
5
Intermediate (1 through N-1) Liebert FS Cabinet
FS Status / Control Terminal Block
9
9
10
10
Installation Drawings
Figure 144 Status/control wiring, multiple units
Installation Drawings
Figure 145 Wiring specifications, Liebert FS and Liebert Series 300
Wire
No.
Terminal Designation
From
To
Signal
Name
Maximum
Voltage
Maximum
Current
Color
Wire Size
& Type
Maximum
Length
Remarks
Series 300 UPS - Cable Group # 27 (Flywheel CB IFM) From I1 In UPS Module to TB1 on Liebert FS Module
901
I1-TB1-1
TB1-1
Trip Signal (+)
+24 VDC
100mA
902
I1-TB1-2
TB1-2
Trip Signal (-)
-24 VDC
100mA
903
I1-TB1-7
TB1-7
Aux Comm
24 VDC
100mA
904
I1-TB1-8
TB1-8
Aux N.O.
24 VDC
100mA
1/C #16
(2.5 mm2)
Stranded
500 ft
(150 m)
Series 300 UPS - Cable Group # 116 Flywheel Aux Power, Customer-Provided to Liebert FS TB1 on Fused Disconnect
914
FBO
TB1-1
Line
120VAC
3.5A
915
FBO
TB1-2
Neutral
120VAC
3.5A
916
FBO
TB1-3
GND
120VAC
3.5A
1.
2.
3.
4.
5.
1/C #16
(2.5 mm2)
Stranded
500 Ft
(150
Meters)
UPSProtected
Auxiliary
Control
Power
Each cable group must be run in a separate, grounded, rigid metal conduit to prevent control signal interference.
Refer to UPS module/Liebert FS control connection diagram for location of wiring connections.
All external wires furnished by others.
N.O. = Normally Open; N.C. = Normally Closed; Comm = Common; F.B.O. = Furnished By Others, GND = Ground
All wiring must be in accordance with national and local electrical codes.
Dwg. No. Control_WL_S300_Liebert-FS Rev. 01
137
Installation Drawings
Figure 146 Wiring specifications, Liebert FS and Liebert Npower
Wire
No.
Terminal Designation
From
To
Signal
Name
Maximum Maximum
Voltage Current
Color
Wire Size
& Type
Maximum
Length Remarks
Liebert N-Power UPS - Cable Group # 17 (Flywheel CB IFM) From TB69 in UPS Module to TB1 on Liebert FS Module
101
TB69-1
TB1-1
Trip Signal (+)
+24 VDC
100mA
102
TB69-2
TB1-2
Trip Signal (-)
-24 VDC
100mA
103
TB69-3
TB1-3
Motor Op Relay
24 VDC
100mA
104
TB69-4
TB1-4
Motor Op On
24 VDC
100mA
105
TB69-5
TB1-5
Motor Op Off
24 VDC
100mA
106
TB69-6
TB1-6
Aux N.O.
24 VDC
100mA
107
TB69-7
TB1-7
Aux Comm
24 VDC
100mA
108
TB69-8
TB1-8
Aux N.C.
24 VDC
100mA
109
TB69-9
TB1-9
Comm
24 VDC
100mA
110
TB69-10
TB1-10
Battery Sense (+) +24 VDC
100mA
112
TB69-12
TB1-11
Battery Sense (-) -24 VDC
100mA
1/C #16 (2.5 mm2)
Stranded
1/C #16 (2.5 mm2)
Stranded
500 ft
(150m)
Liebert N-Power UPS - Cable Group # 18 (Flywheel CB IFM) from TB73 in UPS Module to TB6 on Liebert FS Module
Line
TB73-1
TB6-1
Motor Op Pwr
120 VAC
100mA
Neutral
TB73-2
TB6-2
Motor Op Neutral
N
100mA
500 FT
(150m)
Liebert N-Power UPS - Cable Group # 19 (Flywheel CB IFM) From TB70 in UPS Module to TB7 on Liebert FS Module
113
TB70-1
TB7-1
Temp Sensor
24 VDC
100mA
114
TB70-2
TB7-2
Sensor Return
24 VDC
100mA
1/C #16 (2.5 mm2)
Stranded
500 ft
(150m)
Liebert N-Power UPS - Cable Group # 116 Flywheel Aux Power, Customer Provided to Liebert FS TB1 on Fused
Disconnect
Output
A PHS
FBO
Output
Net
FBO
TB1-2
Neutral
120VAC
3.5A
Gnd
FBO
TB1-3
GND
120VAC
3.5A
1.
2.
3.
4.
5.
TB1-1
Line
120VAC
3.5A
1/C #16 (2.5 mm2)
Stranded
500 ft
(150m)
UPSProtected
Auxiliary
Control
Power
Each cable group must be run in a separate grounded rigid metal conduit to prevent control signal interference.
Refer to UPS module/Liebert FS control connection diagram for location of wiring connections.
All external wires furnished by others.
N.O. = Normally Open; N.C. = Normally Closed; Comm = common; F.B.O. = Furnished By Others, GND = ground
All wiring must be in accordance with national and local electrical codes.
Dwg. No. Control_WL_NPower_Liebert-FS Rev. 1
138
Installation Drawings
Figure 147 Wiring specifications, Liebert FS and Liebert Series 610
Wire
No.
Terminal
Designation
From
To
Signal
Name
Maximum
Voltage
Maximum
Current
Color
Wire Size
& Type
Maximum
Length
Remarks
Liebert Series 610 UPS - Cable Group #16 (Flywheel CB IFM) From I1 in UPS Module to TB1 on Liebert FS Module
901
I1-TB1-1 TB1-1 Trip Signal (+)
+24 VDC
100mA
902
I1-TB1-2 TB1-2
Trip Signal (-)
-24 VDC
100mA
903
I1-TB1-7 TB1-7
Aux Comm
24 VDC
100mA
904
I1-TB1-8 TB1-8
Aux N.O.
24 VDC
100mA
1/C #16 (2.5 mm2)
Stranded
500 Ft
(150 M
Liebert Series 610 UPS - Cable Group #116 Flywheel Aux Power, Customer-Provided to Liebert FS TB1 on Fused
Disconnect
914
FBO
TB1-1
Line
120VAC
3.5A
915
FBO
TB1-2
Neutral
120VAC
3.5A
916
FBO
TB1-3
GND
120VAC
3.5A
1.
2.
3.
4.
5.
2
1/C #16 (2.5 mm )
Stranded
500 Ft
(150m)
UPSProtected
Auxiliary
Power
Control
Each cable group must be run in a separate, grounded, rigid metal conduit to prevent control signal interference.
Refer to UPS module/Liebert FS control connection diagram for location of wiring connections.
All external wires furnished by others.
N.O. = Normally Open; N.C. = Normally Closed; Comm = common; F.B.O. = Furnished By Others, GND = ground
All wiring must be in accordance with national and local electrical codes.
Dwg. No. Control_WL_S610_Liebert-FS Rev. 01
139
Installation Drawings
Figure 148 Wiring specifications, Liebert FS and Liebert HiPulse
WIRING SPECIFICATIONS FOR THE LIEBERT FS AND LIEBERT HIPULSE
ARE AVAILABLE BY CONTACTING:
Your local Liebert Sales Representative
Your local Liebert Service Representative
Liebert Corp. at 1-800-Liebert (1-800-543-2378
140
min.
max.
NOTE: If hole is drilled too deep, backfill to correct
to proper depth.
4X O5/8" (16mm) Mason Drill x 2.00 (51mm)
2.25 (57mm)
29-1/2"
(749mm)
16"
(406mm)
Installation Drawings
Figure 149 Floor mounting template
141
5
4
3
7
Bolts and Washers come with cabinet
2
Drill Template Dwg
8
6
1
Installation Drawings
Figure 150 System mounting kit
142
143
FAN #2
PUMP
COOLING SYSTEM
FAN #1
MAIN
CONTROL MODULE
POWER CONVERSION MODULE
CONTROLLER
ANALOG AXIAL AXIS CONTROLLER
Z
ANALOG RADIAL AXIS CONTROLLER
LOWER Y
ANALOG RADIAL AXIS CONTROLLER
LOWER X
ANALOG RADIAL AXIS CONTROLLER
UPPER Y
ANALOG RADIAL AXIS CONTROLLER
UPPER X
UPPER BEARING COIL
Y
X
X
PCM TO MCM
LOWER BEARING COIL
INSULATOR LOWER BEARING COIL
UNIVERSAL PO SITION SENSO R
TEMP.
SPEED
UNIVERSAL PO SITION SENSO R
Z
Y
INSULATOR UPPER BEARING COIL
AUXILIARY BACKUP
POWER 24V
MCM POWER SUPPLY
FLYWHEEL MODULE
LOWER BEARING POWER
LOWER BEARING SENSOR
UPPER BEARING POWER
UPPER BEARING SENSOR
DATA COLLECTION
MODULE (DCM)
(OPTIONAL)
LO WER BEARING POWER
LOWER BEARING SENSOR
VERSATILE
INTERFACE BOARD
(VIB) (OPTIONAL)
MCM
BACKPLANE
UPPER BEARING POWER
UPPER BEARING SENSOR
DISPLAY
STATOR POWER CABLE
FILTER
FILTER
CIRCUIT BREAKER
(OPTIONAL)
POWER CONVERSION MODULE
24VDC POWER SUPPLY
24VDC POWER SUPPLY
POWER DISTRIBUTION BOARD
POWER INTERFACE BOARD
POWER BLOCK
FUSE BOARD
CAPACITO R BANK
PRECHARGE BOARD
TERMINAL BLOCK
AND FUSE
OPTIONAL
CAPACITORS
Installation Drawings
Figure 151 Liebert FS block diagram
Installation Drawings
Figure 152 Power line diagram
144
Liebert FS
Cabinet
Unit N
NOTES
Liebert FS
Cabinet
Unit N
Liebert FS
Cabinet
Unit N
3-Phase
Input
145
Ground Bus
( + ) Bus
(-) Bus
CABINET
UPS
1. All cables should be routed before bolting cabinets together.
2. All Liebert FS cabinets shown with front door open.
3. Cabinets shown connected as one system. When connected to a UPS module, all power
and control wiring supplied by customer (standard) or Liebert (option).
4. See installation, operation and maintenance manual for additional information.
5. All external wiring is to be in accordance with national and local electrical codes.
6. Bus wiring must be capable of handling total load current.
7. Power connection must be connected with a bus structure or to a single point
connection at the UPS (Do not daisy-chain).
3-Phase
Output
Installation Drawings
Figure 153 UPS cable entry—bottom
Liebert FS
Cabinet
Unit N
NOTES
146
Liebert FS
Cabinet
Unit 1
3-Phase
Input
UPS
CABINET
1. All cables should be routed before bolting cabinets together.
2. All Liebert FS cabinets shown with front door open.
3. Cabinets shown connected as one system. When connected to a UPS module, all
power and control wiring supplied by customer (standard) or Liebert (option).
4. See installation, operation and maintenance manual for additional information.
5. All external wiring is to be in accordance with national and local electrical codes.
6. Bus wiring must be capable of handling total load current.
7. Power connection must be connected with a bus structure or to a single point
connection at the ups (Do not daisy-chain).
Liebert FS
Cabinet
Unit 2
( + ) Bus
( - ) Bus
Ground Bus
3-Phase
Output
Installation Drawings
Figure 154 UPS cable entry—top
Installation Drawings
Figure 155 Raised floor mounting
F
29-½” (75mm)
F
16” (406mm)
F
F
TOP VIEW
Large diameter washer
2"
(50mm) dia.
Lockwasher
1/2" (12.7mm)
dia. steel bolt
Raised
floor
NOTE: Combination of floor material of given thickness , plus
properties of large diameter washer and fastener , should result in
lateral load capability to withstand shear due to load F =1500 lb (680kg),
parallel to floor .
For thicker floors that might require a bolt length longer than
can fit inside mounting channel , insert bolt from below with nut above .
147
Specifications
APPENDIX E.0 SPECIFICATIONS
Table 36
Technical specifications
INPUT, DC
Float Voltage
Charging Current
Rated Input Charging
Maximum Idling Consumption
350 through 600 VDC; > 520 VDC required for 190kW
5 through 50 Amps per Liebert FS
350-600 VDC; > 520 VDC required for 190kW
Less than 300 W
INPUT, AC
Control Circuit Rating
100-240VAC, 440W, 50/60Hz
OUTPUT, DC
Nominal Power
Nominal Delivered Energy
190 kW 1
190 kW for 10 seconds 1
Maximum Delivered Energy
220 kW for 5 seconds
Discharge Voltage (adjustable)
350 through 600 VDC
Rated Output Discharge
DC Voltage Regulation
350-600 VDC, 250A; > 510 VDC required for 190 kW
± 1% steady state
DC ripple
< 2%
Current Short Time
400A
Short Circuit Withstand Current Capacity
(Circuit-breaker/fused terminal block)
20 kADC / 10 kADC
INPUT, AC (AUX)
Auxiliary Voltage
Auxiliary Power Rating
110VAC – 230VAC (50/60Hz)
400VA
ENVIRONMENTAL
Operating Temperature
Startup Temperature
Non-Operating Temperature
Humidity
Operating Altitude
Non-Operating Altitude
Operating Audible Noise Level
Heat Dissipation
Cabinet Environmental Rating
Pollution Degree
-20°C to 50°C (-4°F to 122°F)
0°C to 50°C (32°F to 122 °F)
-20°C to 80°C (-4°F to 176 °F)
5% to 95% non-condensing
Up to 3,000 meters (9,842 feet) above sea level
Up to 12,000 meters (39,370 feet) above sea level
<50 dBa at 1 meter in Ready mode; less than 65 dBa
when discharging
Less than 300W (1,025 BTU/h)
NEMA 1 / IP 30
3 (Industrial)
PHYSICAL DATA
Dimensions (W x D x H)
Footprint
63 x 83 x 181 cm (25 x 33 x 71 in)
0.5 m² (5.7 sq ft)
Weight
590 kg (1,300 lb)
Shipping Package Weight
660 kg (1,460 lb)
Cable Access
Top or Side Entry
STANDARDS / MARKINGS
UL Listed
cUL Listed
CE Mark
1.
For discharge voltages below 510 VDC, contact Liebert (1-800-LIEBERT) or your local representative.
148
Specifications
Appendix E.1 Ground Test Procedure
The purpose of the GTS is to confirm integrity of grounding path. This test is performed when the system is completely shutdown and isolated from all external powers. Use the checklist below.
Items Required
• Handheld Multimeter - Ohmmeter
The ground-test procedure consists of verifying the resistance between the following points (expected
values are given in some instances):
•
•
•
•
•
•
•
•
•
•
•
•
PE and PPM Box (0 Ohms)
PE and MCM Box (0 Ohms)
PE and outer containment (0 Ohms)
PE and door 0 Ohms.
PE and external capacitor box (0 Ohms)
PE and right side of enclosure (0 Ohms)
PE and left side of enclosure (0 Ohms)
PE and bottom of enclosure (0 Ohms)
PE and top of enclosure (0 Ohms)
PE and water slide (0 Ohms)
PE and the ground on fused disconnect
PE and the building ground
NOTE
Connect tester cable to non-painted metal or screw for testing.
149
Auxiliary Backup AC Power Supply
APPENDIX F.0 AUXILIARY BACKUP AC POWER SUPPLY
Appendix F.1 Overview
The Liebert FS must be operated with a backup AC power supply to protect the unit’s mechanical
bearings if:
• the external DC supply is lost and
• the Liebert FS has developed a fault
If these two events occur simultaneously, the backup power supply will power the magnetic levitation
hardware to prevent the rotating group from running on the mechanical touchdown bearings.
This section details the function of the backup power supply and how it should be attached to the
Liebert FS. This is supplementary information—refer to appropriate sections of the user manual for
details on installation and operation.
Appendix F.2 Backup AC Power Supply Specification
Voltage:
110 to 230VAC, 400VA
Frequency: 50 to 60Hz
Note: Connection to a 480VAC supply requires a 480 to 110 transformer, available from Liebert as an
option.
Appendix F.3 Recommended Backup Power Supply Configuration
If the Liebert FS
is operating:
Liebert recommends:
For details, see:
In parallel
with batteries
Attaching the backup AC power supply to the output of the UPS.
Figures 156 and 157
Without batteries
Feeding the backup AC supply from a separate, protected supply.
This may be the output of another UPS or a supply from a separate
feeder circuit.
Figures 158 and 159
150
Auxiliary Backup AC Power Supply
Appendix F.3.1
Operating the Liebert FS+DC in Parallel With Batteries
If the Liebert FS is operating in parallel with batteries, Liebert recommends attaching the backup AC
power supply to the output of the UPS, as shown in Figures 156 and 157.
Figure 156 A single Liebert FS+DC unit operating with a UPS in conjunction with batteries
UPS
Grid
supply
UPS AC
Output
BACKUP AC
POWER
SUPPLY
DC bus
Liebert FS
Battery
pack
Figure 157 Multiple Liebert FS+DC units operating with a UPS in conjunction with batteries
UPS
Grid
supply
UPS AC
Output
Distribution BACKUP AC POWER SUPPLY
panel*
DC bus
Battery
pack
* NOTE:
Distribution panel allows
removal of a Liebert FS without disrupting the other units
3 Liebert FS units
151
Auxiliary Backup AC Power Supply
Appendix F.3.2
Operating the Liebert FS Without Batteries
If the Liebert FS is operating without batteries, Liebert recommends feeding the backup AC power
supply from a separate, protected supply. This may be the output of another UPS or a supply from a
separate feeder circuit (see Figures 158 and 159).
Figure 158 A single Liebert FS unit operating with a UPS and without batteries attached to the DC bus
UPS
Grid
Supply
UPS
Output
BACKUP AC
POWER SUPPLY
Fed from a protected AC
supply, either the output
of another UPS or a
separate feeder supply
DC Bus
Liebert FS
Figure 159 Multiple Liebert FS units operating with a UPS and without batteries attached to the DC bus
UPS
Grid
Supply
UPS
Output
Distribution
panel*
BACKUP AC
POWER
SUPPLY
Fed from a protected AC
supply, either the output
of another UPS or a
separate feeder supply
DC Bus
* NOTE:
Distribution panel allows
removal of a Liebert FS without
disrupting the other units
3 Liebert FS Units
152
Auxiliary Backup AC Power Supply
Appendix F.4 Scenarios
This section describes five scenarios that might occur.
• Loss of backup AC supply at 0 RPM - This causes a fault message to appear on the control
panel to indicate there is a problem with the backup supply. The unit will not start until the
backup supply is reinstalled.
• Loss of backup AC supply at full speed - This causes a warning message to appear on the control panel to indicate there is a problem with the backup supply. This warning does not affect the
operation of the system.
• Loss of external DC supply - The Liebert FS will discharge normally until it reaches
25000 RPM. It will then change to shutdown mode and drive down to 3500 RPM, it will then coast
to a stop over a number of hours.
• Loss of external DC supply and loss of backup supply - The Liebert FS can support the
magnetic levitation hardware using energy from the flywheel. It will discharge normally until
25000 RPM, then change to shutdown mode and drive down to 3500 RPM. At this speed it can no
longer support itself, and the unit will turn off. The flywheel will safely drop onto the mechanical
touchdown bearings and will slowly come to a stop.
• Loss of external DC supply, loss of backup supply and a fault message appears on the
control panel - This unlikely combination of events will cause the flywheel to drop onto the
mechanical touchdown bearings without slowing to a safe rotation speed. The ceramic touchdown
bearings can withstand very high speeds. However, if the flywheel were to drop onto the ceramic
bearings at full speed, the bearings would last only a minute before starting to degrade. Although
the system has been designed to retain the rotor as it slows, internal damage will occur during
this period. The Liebert FS would require refurbishing at the factory before it could be used again.
Figure 160 Liebert FS connection
DC bus
BACKUP AC
POWER SUPPLY
Liebert FS
Flywheel
module
153
Auxiliary Backup AC Power Supply
154
Ensuring The High Availability
0f Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical
continuity, ensures network resiliency and adaptability through
a family of technologies—including Liebert power and cooling
technologies—that protect and support business-critical systems.
Liebert solutions employ an adaptive architecture that responds
to changes in criticality, density and capacity. Enterprises benefit
from greater IT system availability, operational flexibility and
reduced capital equipment and operating costs.
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877
monitoring@emersonnetworkpower.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@emersonnetworkpower.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@emersonnetworkpower.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F, Dah Sing Financial Centre
108 Gloucester Road, Wanchai
Hong Kong
852 2572220
Fax: 852 28029250
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
© 2007 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change
without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert
Corporation. All names referred to are trademarks
or registered trademarks of their respective owners.
SL-29315_REV04_08-07
Emerson Network Power.
The global leader in enabling Business-Critical Continuity.
AC Power
Embedded Computing
Embedded Power
Connectivity
DC Power
Monitoring
EmersonNetworkPower.com
Outside Plant
Power Switching & Controls
Racks & Integrated Cabinets
Services
Precision Cooling
Surge Protection
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2007 Emerson Electric Co.