FieldServer FS-8700-19 Computer Drive User Manual

A Sierra Monitor Company
Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-19 Metasys N2
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after May 1, 2001
Driver Version:
1.02
Document Revision: 22
FS-8700-19_Metasys_N2 Driver Manual
Table of Contents
TABLE OF CONTENTS
1.
Metasys N2 Description ................................................................................................. 3
2.
Driver Scope of Supply .................................................................................................. 4
2.1.
Supplied by FieldServer Technologies for this driver.................................................. 4
2.2.
Provided by the Supplier of 3rd Party Equipment ........................................................ 4
2.2.1. Hardware ................................................................................................................ 4
2.2.2. Required 3rd Party Software.................................................................................... 4
2.2.3. Required 3rd Party Configuration............................................................................. 4
3.
3.1.
Hardware Connections .................................................................................................. 5
Hardware Connection Tips / Hints.............................................................................. 5
4.
Configuring the FieldServer as a Metasys N2 Client ................................................... 6
4.1.
Data Arrays/Descriptors ............................................................................................. 6
4.2.
Client Side Connection Descriptions .......................................................................... 7
4.3.
Client Side Node Descriptors ..................................................................................... 8
4.4.
Client Side Map Descriptors....................................................................................... 8
4.4.1. FieldServer Related Map Descriptor Parameters .................................................... 8
4.4.2. Driver Related Map Descriptor Parameters............................................................. 9
4.4.3. Timing Parameters ................................................................................................13
4.4.4. Map Descriptor Example 1 – N2Open....................................................................14
4.4.5. Map Descriptor Example 2 - VMA..........................................................................14
4.4.6. Map Descriptor Example 3 - DX9100.....................................................................15
5.
Configuring the FieldServer as a Metasys N2 Server .................................................16
5.1.
Server Side Connection Descriptors .........................................................................16
5.2.
Server Side Node Descriptors...................................................................................17
5.3.
Server Side Map Descriptors ....................................................................................18
5.3.1. FieldServer Specific Map Descriptor Parameters...................................................18
5.3.2. Driver Specific Map Descriptor Parameters ...........................................................18
5.3.3. Map Descriptor Example........................................................................................19
Appendix A. Advanced Topics...........................................................................................20
Appendix A.1. Writing to DX9100 Binary Outputs................................................................20
Appendix A.2. Managing Analog Inputs and Outputs for DX9100. ......................................21
Appendix B. Troubleshooting tips.....................................................................................22
Appendix B.1. Connection Tips & Hints...............................................................................22
Appendix B.2. Offline Behavior ...........................................................................................22
Appendix B.3. Tip on Overrides ..........................................................................................22
Appendix C. Setting up FS-B20 for RS-485.......................................................................23
Appendix C.1. Jumper Settings:..........................................................................................23
Appendix C.2. Hardware connections .................................................................................25
Appendix C.3. Configuration Settings..................................................................................25
Appendix D. Memory Maps ................................................................................................26
Appendix D.1. Metasys DX9100 Memory Map....................................................................26
Appendix D.2. Metasys DC9100 Memory Map....................................................................33
Appendix D.3. Metasys TC9100 Memory Map ....................................................................40
Appendix E.
Error Messages .............................................................................................50
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
1.
Page 3 of 51
Metasys N2 Description
The Metasys N2 network supports communications with a diverse range of devices. Many N2
compatible devices use their own version of the protocol and care must be taken to ensure that
the device of interest is covered by the FieldServer implementation.
At present the FieldServer N2 driver will support communications with the following devices or
device classes when acting as a Client:
1. N2Open-compliant devices. N2Open is a published N2-compatible protocol enabling 3rd
party device vendors to integrate with N2.
2. VMA 1400 series (with restrictions, as described in this document)
3. DX9100 and XT9100
When acting as a Server, the FieldServer N2 driver can emulate an N2Open device only.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
2.
Page 4 of 51
Driver Scope of Supply
2.1.
Supplied by FieldServer Technologies for this driver
FieldServer Technologies
PART #
FS-8915-10
FS-8915-10
FS-8917-02
FS-8917-01
SPA59132
FS-8700-19
2.2.
2.2.1.
UTP cable (7 foot) for Ethernet connection
UTP cable (7 foot) for RS-232 use
RJ45 to DB9F connector adapter
RJ45 to DB25M connection adapter
RS-485 connection adapter
Driver Manual.
Provided by the Supplier of 3rd Party Equipment
Hardware
PART #
2.2.2.
Description
DESCRIPTION
Metasys NCU or other device
Required 3rd Party Software
Depending on application, JCI software may be necessary
2.2.3.
Required 3rd Party Configuration
Depending on application, third party devices may need configuration
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
3.
Page 5 of 51
Hardware Connections
FieldServer as a Client
3rd Party
System
FieldServer
N2 bus
N2 devices
FieldServer as a Server
NCM, N30 or
other N2 client
N2 bus
(408)-262-2299
N2 devices
FieldServer
3rd Party
System
MetasysN2
CONNECTION DIAGRAM
BASE NAME:
FILE NAME: FS-8700-19
3.1.
DATE: 05/31/06
BY:
MC
Hardware Connection Tips / Hints
When using the FS-X40 ensure that the FieldServer is connected to the network using one
or both of the RS-485 ports marked R1 and R2. If more ports are required, P1-P8 may be
used in conjunction with an RS-232-to-RS-485 converter.
When using the FS-X20, ensure that the serial port is configured as an RS-485 port. Refer
to Appendix B.3 for more information.
Only one N2 Client may be connected to a N2 network. If the FieldServer is to act as a
Client, ensure that no other Clients are connected to the same N2 network.
Note: Interceptor mode is no longer supported for this driver.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
4.
Page 6 of 51
Configuring the FieldServer as a Metasys N2 Client
For a detailed discussion on FieldServer configuration, please refer to the FieldServer
Configuration manual. The information that follows describes how to expand upon the factory
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files
provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer
to communicate with a Metasys N2 Server.
4.1.
Data Arrays/Descriptors
The configuration file defines the FieldServer interfaces, and the data routing required. In
order to enable the FieldServer for Metasys N2 communications, the driver independent
FieldServer buffers need to be declared in the “Data Arrays” section, the destination device
addresses need to be declared in the “Client Side Nodes” section, and the data required
from the Servers needs to be mapped in the “Client Side Map Descriptors” section.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the
default value. Where only one legal value is given, no other values for that parameter are
allowed.
Section Title
Data_Arrays
Column Title
Function
Data_Array_Name
Provide name for Data Array
Data_Array_Format
Provide data format. Each Data Array
can only take on one format.
Data_Array_Length
Number of Data Objects. Must be
larger than the data storage area
required by the Map Descriptors for
the data being placed in this array.
Legal Values
Up to 15 alphanumeric
characters
Float, Bit, UInt16, SInt16,
Packed_Bit, Byte,
Packed_Byte,
Swapped_Byte
1-10,000
Example
//
Data Arrays
Data_Arrays
Data_Array_Name,
DA_AI_01,
DA_AO_01,
DA_DI_01,
DA_DO_01,
Data_Format,
UInt16,
UInt16,
Bit,
Bit,
Data_Array_Length
200
200
200
200
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
4.2.
Page 7 of 51
Client Side Connection Descriptions
Section Title
Connections
Column Title
Port
Protocol
Baud*
Parity*
Data_Bits*
Stop_Bits*
Handshaking*
Poll _Delay*
Line_Drive_On*
Line_Drive_Off*
Function
Specify which port the device is
connected to the FieldServer
Specify protocol used
Specify baud rate
Specify parity
Specify data bits
Specify stop bits
Specify hardware handshaking
Time between internal polls
Duration of RTS assert before
start of transmission
Duration of RTS assert after
end of transmission
Legal Values
P1-P8, R1-R21
Metasys_N2
9600
None
8
1
None
0
0.001s
0.000s
Example
//
Client Side Connections
Connections
Port,
Protocol
R1,
Metasys_N2
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
4.3.
Page 8 of 51
Client Side Node Descriptors
Section
Title
Nodes
Column
Title
Function
Legal Values
Node_Name
Provide name for node
Node_ID
Protocol
Station address of physical Server node
Specify protocol used
Specify which port the device is connected to the
FieldServer
Identify type of device
Connection
Node_Type
If this parameter is omitted the driver treats the
configuration as a N2Open configuration and marks
the Node_Type as N2OpenClient when using Ruinet
to check the Node parameters.
Up to 32
alphanumeric
characters
1-255
Metasys_N2
P1-P8, R1-R21
N2OpenClient,
DX9100, VMA,
N2Open
If the Node_Type is specified as N2Open then the
driver still acts as N2 Open configuration but some
legacy port expander functionality used in some
legacy advanced configuration is enabled.
Example
//
Client Side Nodes
Nodes
Node_Name,
PLC 1,
4.4.
Node_ID,
1,
Protocol,
Metasys_N2,
Connection,
P8,
Node_Type
VMA
Client Side Map Descriptors
4.4.1.
FieldServer Related Map Descriptor Parameters
Column Title
Map_Descriptor_Name
Data_Array_Name
Data_Array_Offset
Function
Function
Name of this Map
Descriptor
Name of Data Array
where data is to be
stored in the FieldServer
Starting location in Data
Array
Function of Client Map
Descriptor
Legal Values
Up to 32 alphanumeric
characters
One of the Data Array names
from “Data Array” section
above
0 to maximum specified in
“Data Array” section above
RDBC, WRBC, WRBX
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
4.4.2.
Page 9 of 51
Driver Related Map Descriptor Parameters
4.4.2.1.
N2Open Map Descriptor Parameters
Column Title
Function
Node_Name
Name of Node to fetch data from
Data_Type
Data type
Length
Address
Length of Map Descriptor
Starting address of read block
Used to specify an N2-specific
function, e.g. COS. See
description below.
Used to specify the attribute if an
attribute other than Current Value
is to be accessed. See attribute
table below
MN2_Function*
MN2_Attribute*
Legal Values
One of the node names
specified in “Client Node
Descriptor” above
If the vendor device lists a
point as BD then use
Data_Type=Byte.
If the vendor device lists a
point as ADI then use
Data_Type=Integer.
If the vendor device lists a
point as ADF then use
Data_Type=Float_Reg.
AI, AO, DI, DO,
Float_Reg, Integer, Byte
1
1-256
COS, Override, Release
See
N2Open Attribute Table
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Data Type
Analog Input
Binary Input
Analog Output
Binary Output
Internal Float
Internal Integer
Internal Byte
Page 10 of 51
N2Open Attribute Table
Attribute No.
1
2
3
4
5
6
7
8
1
2
1
2
3
1
2
3
4
5
1
2
1
2
1
2
Attribute
Object Configuration
Object Status
Analog Input Value
Low Alarm Limit
High Alarm Limit
Low Warn Limit
High Warn Limit
Differential
Object Configuration
Object Status
Object Configuration
Object Status
Current Value
Object Configuration
Object Status
Minimum On-Time
Minimum Off-Time
Maximum Cycles/Hour
Object Status
Current Value
Object Status
Current Value
Object Status
Current Value
Using Change of State (COS) – N2Open
If a large number of points are to be monitored, optimal efficiency is achieved by
using the COS mechanism instead of reading each individual point directly. A
N2Open device responds to a COS poll with a change record if a change has taken
place. On startup the device will report the state of all its points when it receives a
COS poll.
Two kinds of Map Descriptors are required for every node that is to be monitored
using COS:
A COS polling Map Descriptor with Function set to COS_Poll.
A COS_Read (i.e. Function set to COS_Read) Map Descriptor for every point
on that node that is to be monitored. Any COS records received will be stored to
the matching Map Descriptor data location.
Note that the COS_Read Map Descriptor has an optional scan_interval. If a value is
set the Map Descriptor will poll at that rate in addition to receiving COS data. This
can be used if the values are to be refreshed continually even if they don’t change. If
the scan_interval is not configured (through omitting the column, or by setting the
value to ‘-‘) the COS_Read Map Descriptor will not cause active polls once the value
has been initialized. See 4.4.4 for example.
Important Note on COS Operation in N2Open
Please be aware that N2Open devices will only report value changes under the
following conditions:
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Point Type
AI
AO
BI, BO
ADI, ADF, BD
Page 11 of 51
Conditions that will trigger a COS report
point status change (e.g. override)
change in alarm or warning status
NB: no value changes within the normal band are reported by COS!
point status change (e.g. override)
NB: no value changes within the normal band are reported by COS!
point status change (e.g. override); includes current value (On/Off)
none; COS cannot be used with internal data types.
Using Override and Release – N2Open
It is not normally necessary to use the Override command explicitly as the
FieldServer automatically uses this command when the Current Value attribute of a
point is written. For any other attribute it uses the Write command. It will sometimes
be necessary to send a Release command to an overridden point, however. To do
this, a Map Descriptor must be configured with Function set to wrbx and
MN2_Function set to Release. Then, when any value is stored to the Map
Descriptor data location, the Release command will be sent to the N2Open point
specified by the Map Descriptor.
4.4.2.2.
VMA Map Descriptor Parameters
Column Title
Function
Node_Name
Name of Node to fetch
data from
Data_Type
Data type
Length
Length of Map Descriptor
Starting address of read
block
Data type specifier to be
set when Data_Type has
been set to Driver
Address
MN2_Type
Legal Values
One of the node names
specified in “Client Node
Descriptor” above
AI, AO, DI, DO, Driver
(used for ADF, ADI and
BD)
1
1-256
5-7
ADI, ADF and BD types: using the “Driver” Data_Type and MN2_Type fields
The VMA protocol uses a byte value to specify the data types. The standard types
AI, AO, DI and DO correspond to a byte value of 1 through 4 respectively. The types
ADF, ADI and BD are believed to correspond to a byte value of 5 through 7
respectively. If the user wishes to use any other type value based on knowledge of a
particular VMA configuration, then that value may also be specified here. Refer to
Section 4.4.5 for a specific example.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Driver Data_Type
MN2_Type values
Point Type
AI
AO
BI
BO
ADF
ADI
BD
Known Value2
1
2
3
4
Page 12 of 51
Suggested Value3
5
6
7
If a large number of points are to be monitored, optimal efficiency is achieved by
using the COS mechanism instead of reading each individual point directly. An
N2Open device responds to a COS poll with a change record if a change has taken
place. On startup the device will report the state of all its points when it receives a
COS poll.
Three kinds of Map Descriptors are required for every node that is to be monitored
using COS:
•
A COS initialization Map Descriptor with Function set to ARS and
MN2_Function set to COS_Enable. This Map Descriptor enables COS polling
of those points on the VMA for which Passive Map Descriptors exist.
•
A COS polling Map Descriptor with Function set to rdbc and MN2_Function set
to COS.
•
A Passive (i.e. Function set to Passive) Map Descriptor for every point on that
node that is to be monitored. Any COS records received will be stored to the
matching Map Descriptor data location.
See example in Section 4.4.5
Using Override and Release - VMA
It is normally not necessary to use the Override command explicitly as the
FieldServer automatically uses this command when the Current Value attribute of a
point is written. For any other attribute it uses the Write command. It will sometimes
be necessary to send a Release command to an overridden point, however. To do
this, a Map Descriptor must be configured with Function set to wrbx and
MN2_Function set to Release. Then, when any value is stored to the Map
Descriptor data location, the Release command will be sent to the VMA point
specified by the Map Descriptor.
Note: The VMA Release function only works for analog and binary inputs (AI and
BI). Outputs may be restored to their original value using an explicit write command.
2
3
For information only. Do not use Driver type for these, but specify AI, AO, BI or BO directly in the Data_Type field.
These values are believed to be correct for the corresponding point types, but no guarantee can be given at this time.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
4.4.2.3.
Page 13 of 51
DX9100 Map Descriptor Parameters
Column Title
Node_Name
Length
Function
Name of Node to fetch
data from
Length of Map Descriptor
Starting address of read
block
Address
Legal Values
One of the node names
specified in “Client Node
Descriptor” above
1
0 - 2397
For DX9100 addresses please refer to the DX9100 user documentation. This lists
the name, function (read/write) and data format of all available points. Alternatively,
obtain assistance from FieldServer Technical Support.
4.4.3.
Timing Parameters
Column Title
Scan_Interval
Function
Rate at which data is polled
Legal Values
≥0.001s
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
DA_AI3,
DA_COS,
DA_AI3,
DA_BI,
DA_Release,
AI_READ,
COS_POLLER,
AI_BY_COS,
BI_BY_COS,
AI_1_Release,
RDBC,
COS_Poller,
COS_Read,
COS_Read,
WRBX,
COS_Poller Map
Descriptor. This only
specifies the
Function, Node and
Scan_Interval.
0,
0,
1,
3,
0,
Function,
Node_A,
Node_A,
Node_A,
Node_A,
Node_A,
Node_name
COS_Read Map
Descriptor sets point type
the same as normal read
Map Descriptor. Optional
scan_interval.
MN2_Function
,
-,
-,
-,
-,
Release,
Ana_Input
-,
Ana_Input,
Dig_Input,
Ana_Input,
Data_Type
5s
30s
10
-
Scan_Interval
Release function used in conjunction with
wrbx. If the Data Array value specified in this
Map Descriptor is changed, then a Release
command is sent to the specified point.
1,
-,
1,
2,
1,
Address
Page 14 of 51
Function,
RDBC,
WRBX,
WRBX,
RDBC,
Node_name,
Node_VMA,
Node_VMA,
Node_VMA,
Node_VMA,
Address,
1,
3,
3,
23,
Driver type 5 (ADF) configured here.
MN2_Function,
-,
-,
Release,
-,
Data_Type,
Ana_Input
Ana_Output,
Ana_Output,
Driver,
MN2_Type,
-,
-,
-,
5,
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
Override release function configured as wrbx.
DA_Name,
DA_AI3,
DA_AO,
DA_AO,
DA_DRV,
DA_Offset,
0,
0,
0,
10,
Map Descriptor Example 2 - VMA
Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
AI_READ,
AO_WRITE,
AO_Release,
Special_type,
//
4.4.5.
Scan_Interval
5s
30s
10s
Note:
To get change of state (COS) reports from an analog port, the warning/alarm levels need to be configured. If the alarm/warning
values are not known, then it would be better to configure an RDBC Map Descriptor which reads the analog input directly. Limits will
then not be required.
Normal read Map Descriptor.
Note RDBC function,
Data_Type and Address
specification.
DA_Name,
Map_Descriptor_Name,
DA_Offset,
Map Descriptor Example 1 – N2Open
Client Side Map Descriptors
Map_Descriptors
//
4.4.4.
FS-8700-19_Metasys_N2 Driver Manual
Function,
RDBC,
WRBX,
Node_name,
Node_DX,
Node_DX,
Address,
1223,
1225,
The address alone is sufficient to specify DX9100
point. The Data Type is determined by the device.
DA_Offset,
0,
0,
Page 15 of 51
Scan_Interval
5s
-
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
DA_Name,
DA_AI3,
DA_AO3,
Map Descriptor Example 3 - DX9100
Client side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
D191_ZN1-T,
D191_ZN1-S,
//
4.4.6.
FS-8700-19_Metasys_N2 Driver Manual
FS-8700-19_Metasys_N2 Driver Manual
5.
Page 16 of 51
Configuring the FieldServer as a Metasys N2 Server
For a detailed discussion on FieldServer configuration, please refer to the FieldServer
Configuration Manual. The information that follows describes how to expand upon the factory
defaults provided in the configuration files included with the FieldServer (See “.csv” files on the
driver diskette).
This section documents and describes the parameters necessary for configuring the FieldServer
to communicate with a Metasys N2Open Client. Note that only the N2Open variation of the
N2 protocol may be used when configuring the FieldServer as a Server.
The configuration file tells the FieldServer about its interfaces, and the routing of data required.
In order to enable the FieldServer for Metasys N2 communications, the driver independent
FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual
node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to
the Clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to
do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the
default.
5.1.
Server Side Connection Descriptors
Section Title
Connections
Column Title
Port
Protocol
Baud*
Parity*
Data_Bits*
Stop_Bits*
Handshaking*
Poll _Delay*
Line_Drive_On*
Line_Drive_Off*
Function
Specify which port the device is
connected to the FieldServer
Specify protocol used
Specify baud rate
Specify parity
Specify data bits
Specify stop bits
Specify hardware handshaking
Time between internal polls
Duration of RTS assert before
start of transmission
Duration of RTS assert after
end of transmission
Legal Values
P1-P8, R1-R24
Metasys_N2
9600
None
8
1
None
0
0.001s
0.000s
Example
//
Server Side Connections
Connections
Port,
Protocol
P8,
Metasys_N2
4
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
5.2.
Page 17 of 51
Server Side Node Descriptors
Section Title
Nodes
Column Title
Node_Name
Function
Provide name for node
MetasysN2 station address of physical
Server node
Protocol
Specify protocol used
Specifies time FieldServer will reserve
Server_Hold_Timeout* Server side connection while waiting for the
Client side to update data in Data_Array
Identify type of device
Node_ID
Node_Type*
This parameter need not be specified. The
Server side of the driver can only operate
as an N2 Server and the option for setting it
to N2Open is purely for backward
compatibility.
Legal Values
Up to 32
alphanumeric
characters
1-255
Metasys_N2
< 0.175s5
N2OpenServer,
N2Open
Example
//
Server Side Nodes
Nodes
Node_Name,
PLC 1,
Node_ID,
1,
Protocol
Metasys_N2
5
Can be set to >0.175s if the Client has bee set to timeout after >200ms. Refer to Appendix E for more
information.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
5.3.
Page 18 of 51
Server Side Map Descriptors
5.3.1.
FieldServer Specific Map Descriptor Parameters
Column Title
Map_Descriptor_Name
Data_Array_Name
Data_Array_Offset
Function
5.3.2.
Column
Title
Function
Name of this Map
Descriptor
Name of Data Array where
data is to be stored in the
FieldServer
Starting location in Data
Array
Function of Server Map
Descriptor
Function
Name of Node to
fetch data from
Data_Type
Data type
Address
Server
Driver Specific Map Descriptor Parameters
Node_Name
Length
Legal Values
Up to 32 alphanumeric
characters
One of the Data Array
names from “Data Array”
section above
0 to maximum specified in
“Data Array” section above
Length of Map
Descriptor
Starting address of
read block
Legal Values
One of the node names specified in “Client
Node Descriptor” above
If the vendor device lists a point as BD then
use Data_Type=Byte.
If the vendor device lists a point as ADI then
use Data_Type=Integer.
If the vendor device lists a point as ADF then
use Data_Type=Float_Reg.
AI, AO, DI, DO, Float_Reg, Integer, Byte
1 - 256
1 - 256
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
The Server function tells the
FieldServer that this Map
Descriptor makes data
available to a Client sending
polls to the FieldServer.
Data_Type,
Ana_Input,
Function,
Server,
Page 19 of 51
Address,
1,
Length
256
Note that a single Server Map
Descriptor of length 256 can
represent all possible points of
one type (e.g. AI).
Node_name,
Node_A,
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
The Data_Array_Offset sets
the start of the data range
covered by the Server Map
Descriptor. The number of
points included is determined
by the Length field.
Data_Array_Name,
DA_AI3,
Data_Array_Offset,
10,
Map Descriptor Example.
Server Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
A1,
//
5.3.3.
FS-8700-19_Metasys_N2 Driver Manual
6
Page 20 of 51
Description
The status bit will indicate the actual status of the output in the field. This bit cannot be
modified by the FieldServer as it is read only, and is meant for actual status display.
The control bit will allow the FieldServer to write a command to the DX9100 for the associated
output. This command will only execute if the override is enabled by the override bit.
The override bit must be set to enable an output to be written to by the FieldServer. If this is
not set, then the control bit will be ignored.
Low byte
Address 1
High byte
Address 1
Address 5
Address6
of
of
Data_Array_Name,
DA_PO1_01 ,
DA_PO1_02 ,
Map_Descriptors
Map_Descriptor_Name,
CMD_DO1_05 ,
CMD_DO1_06 ,
Data_Array_Offset,
0 ,
0 ,
Data_Array_Length
100
100
Function,
Rdbc ,
Rdbc ,
Node_Name,
Dev_30 ,
Dev_30 ,
Address,
0001 ,
0005 ,
Scan_Interval
1.0s // DO3 - DO8 Set and Enable
1.0s // DO3 - DO8 Status
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
Binary Outputs start at address 3, so the first bit of each of these addresses will represent B03
Data_Format,
Packed_Bit ,
Packed_Bit ,
Data_Arrays
Data_Array_Name,
DA_PO1_01
,
DA_PO1_02
,
Example
The example below better illustrates the mapping that is typically needed to deal with DX9100 Binary Outputs. Note that since all
6 outputs are packed into word format when transmitted, a Packed_Bit Array is typically required to access the bits individually.
In this Example, the status for BO3-BO8 can be found in offsets 0-5 of DA_PO1_02, the control bits can be found in offsets 0-5 of
DA_PO1_01, and the override bits can be found in offsets 8-13 of DA_PO1_01.
Override bit
Bit
Output
status bit
Output
control bit
When writing to DX9100 Binary Outputs, it is important to understand that each binary output has three bits associated with it as
described in the table below:
Appendix A.1. Writing to DX9100 Binary Outputs
Appendix A. Advanced Topics
FS-8700-19_Metasys_N2 Driver Manual
FS-8700-19_Metasys_N2 Driver Manual
Page 21 of 51
Appendix A.2. Managing Analog Inputs and Outputs for DX9100.
Relative offset for viewing an AI is 7
Relative offset for viewing and forcing an AO is 6
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 22 of 51
Appendix B. Troubleshooting tips
Appendix B.1. Connection Tips & Hints
When using the FieldServer as an N2 Client, make very sure that it is the only Client /
master on the N2 network. If there is another Client on the network there will be
communication conflicts. These will be reflected on the FieldServer as protocol errors.
Appendix B.2. Offline Behavior
When the Client node on the FieldServer goes offline, the corresponding data objects on the
FieldServer are also marked offline. If a client polls a virtual FieldServer node for this
particular data, therefore, an offline response will be returned by the FieldServer. A request
from an master device for a FieldServer to identify itself would be met by a valid response,
however. This could lead to confusion and status toggling. This can be addressed using
Responsible Map Descriptors and by configuring the virtual FieldServer using the
Offline_Method option. Please refer to the Configuration Manual for further information.
Appendix B.3. Tip on Overrides
It is important that there be only one device (including the slave device itself) updating a
point which is in overridden mode. The reason for this is that the value of the point could be
changed by an update from a non-Metasys Server before the override is released by the
Metasys Master. In this case, the FieldServer would respond to a poll from the Master with
this changed data.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 23 of 51
Appendix C. Setting up FS-B20 for RS-485
Appendix C.1. Jumper Settings:
Jumpers jp16, jp17, and jp18 need to be transferred from pins 1-2 to pins 2-3 in order to
enable RS-485. These jumpers can be found just behind the RJ45 ports inside the box
Jmpr 18 in 485 position.
Jmpr 16 in 485 position.
Jmpr 17 in 485 position.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 24 of 51
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 25 of 51
Appendix C.2. Hardware connections
The FS-8917-16 pigtail cable is typically used for this port arrangement. Connection is
depicted in the following diagram.
SERIAL
FS-X20
RJ45 Male Modular
Jack
ORANGE/WHITE
(RJ45-08)
BROWN
(RJ45-01)
FS-8917-16
+
-
G
BLUE/WHITE
(RJ45-04)
8
8
7
6
5
4
3
2
7
6
5
4
3
2
1
1
RJ45 M ale M odular Jack
RJ45 Female Modular Jack
Appendix C.3. Configuration Settings
•
•
The Port address in the Configuration needs to be set to R1 instead of P1.
Line_Drive_On and Line_Drive_Off need to be defined in the connections section of the
configuration file. These need to be set to at least 0.001s. Refer to Sections 4.2 and 5.1
for more information.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 26 of 51
Appendix D. Memory Maps
Appendix D.1. Metasys DX9100 Memory Map
Module
Module
Module
Module
Module
Module
Module
Module
Module
Module
Module
Module
1
2
3
4
5
6
7
8
9
10
11
12
Module
Module
Module
Module
Module
Module
Module
Module
1
2
3
4
5
6
7
8
Module
Module
Version
Module
Module
Module
Module
Module
Module
1
2
2
9
10
11
12
13
14
Module
Module
Module
Module
Module
Module
3
4
5
6
7
8
Module
Module
Module
Module
Module
Module
Module
Module
1
2
3
4
5
6
7
8
Module
Module
Module
Module
Module
Module
Module
Module
1
2
3
4
5
6
7
8
Module
Module
1
2
Programmable modules
64
160
256
352
448
544
640
736
832
928
1024
1120
Analog input modules
1216
1232
1248
1264
1280
1296
1312
1328
Analog output modules
1344
1360
or later (new for version 6.0):
2304
2320
2336
2352
2368
2384
Digital output modules
1376
1392
1408
1424
1440
1456
Extension modules
1472
1552
1632
1712
1792
1872
1952
2032
Time schedule modules
2112
2128
2144
2160
2176
2192
2208
2224
Optimal start / stop module
2240
2272
0040H
00A0H
0100H
0160H
01C0H
0220H
0280H
02E0H
0340H
03A0H
0400H
0460H
04C0H
04D0H
04E0H
04F0H
0500H
0510H
0520H
0530H
0540H
0550H
0900H
0910H
0920H
0930H
0940H
0950H
0560H
0570H
0580H
0590H
05A0H
05B0H
05C0H
0610H
0660H
06B0H
0700H
0750H
07A0H
07F0H
0840H
0850H
0860H
0870H
0880H
0890H
08A0H
08B0H
08C0H
08E0H
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Signal Condition
Byte
Word
Byte
Word
Byte
Byte
Byte
Word
Word
Word
Word
Word
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
Word
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Word
Byte
Word
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Word
General control module
Read/Write
Johnson Tag
Read
UNIT
Write
SUP
Read
MNT
Read
DIAG
Read
DICT
Read
TOS
Read
DIS
Read
AIS
Read
LRST1
Read
LRST2
Write
LCOS1
Write
LCOS2
Write
CNTR1
Write
CNTR2
Write
CNTR3
Write
CNTR4
Write
CNTR5
Write
CNTR6
Write
CNTR7
Write
CNTR8
Write
PASS
Write
PC1
Write
PC2
Write
PC3
Write
PC4
Write
PC5
Write
PC6
Write
PC7
Write
PC8
Write
UIA
Write
ALD@
Write
DXS1
Write
ALG
Write
ACO1
Write
ACO2
Write
ACO3
Write
ACO4
Write
ACO5
Write
ACO6
Write
ACO7
Write
ACO8
Write
PLCNT
Read
PLCPC
Page 27 of 51
Description
Device model. For DX-9100 always 5
Supervisory central control
Maintenance control
Diagnistics
Digital input counters
Triac output status
Digital input status
Analog input status
Logic results 37637
Logic results 17-32
Logic constants 37637
Logic constants 17-32
Spare
DI1 pulse count
DI2 pulse count
DI3 pulse count
DI4 pulse count
DI5 pulse count
DI6 pulse count
DI7 pulse count
DI8 pulse count
Password code
Prescaler DI1 counter
Prescaler DI2 counter
Prescaler DI3 counter
Prescaler DI4 counter
Prescaler DI5 counter
Prescaler DI6 counter
Prescaler DI7 counter
Prescaler DI8 counter
User interface address
Alarm disable condition source
DX-9100 type settings
Standard algorithm type
Analog constant 1
Analog constant 2
Analog constant 3
Analog constant 4
Analog constant 5
Analog constant 6
Analog constant 7
Analog constant 8
PLC control and status
PLC program counter
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
Signal Condition
Byte
Word
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
Word
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
Programmable Module Type
Read/Write
Johnson Tag
Write
PMTYP
Write
PMOPT
Write
PMF1
Write
PMF2
Write
PMF3
Write
PMF4
Write
PMF5
Write
PMF6
Write
PMF7
Write
PMF8
Write
PMI1@
Write
PMI2@
Write
PMI3@
Write
PMI4@
Write
PMI5@
Write
PMI6@
Write
PMI7@
Write
PMI8@
Write
PMI9@
Write
PMI10@
Write
PMI11@
Write
PMI12@
Write
PMI13@
Write
PMI14@
Write
PMI15@
Write
PMI16@
Write
PMK01
Write
PMK02
Write
PMK03
Write
PMK04
Write
PMK05
Write
PMK06
Write
PMK07
Write
PMK08
Write
PMK09
Write
PMK10
Write
PMK11
Write
PMK12
Write
PMK13
Write
PMK14
Write
PMK15
Write
PMK16
Write
PMK17
Write
PMK18
Write
PMK19
Write
PMK20
Write
PMK21
Write
PMK22
Write
PMK23
Write
PMK24
Write
PMK25
Write
PMK26
Write
PMK27
Write
PMK28
Write
PMK29
Write
PMK30
Write
PMK31
Page 28 of 51
Description
Programmable module type
Programmable module options
Function channel number 1 - F1
Function channel number 2 - F2
Function channel number 3 - F3
Function channel number 4 - F4
Function channel number 5 - F5
Function channel number 6 - F6
Function channel number 7 - F7
Function channel number 8 - F8
Input connection - I1@
Input connection - I2@
Input connection - I3@
Input connection - I4@
Input connection - I5@
Input connection - I6@
Input connection - I7@
Input connection - I8@
Input connection - I9@
Input connection - I10@
Input connection - I11@
Input connection - I12@
Input connection - I13@
Input connection - I14@
Input connection - I15@
Input connection - I16@
Module constant - K1
Module constant - K2
Module constant - K3
Module constant - K4
Module constant - K5
Module constant - K6
Module constant - K7
Module constant - K8
Module constant - K9
Module constant - K10
Module constant - K11
Module constant - K12
Module constant - K13
Module constant - K14
Module constant - K15
Module constant - K16
Module constant - K17
Module constant - K18
Module constant - K19
Module constant - K20
Module constant - K21
Module constant - K22
Module constant - K23
Module constant - K24
Module constant - K25
Module constant - K26
Module constant - K27
Module constant - K28
Module constant - K29
Module constant - K30
Module constant - K31
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 29 of 51
Relative Item
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
Signal Condition
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Byte
Word
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
Programmable Module Type
Read/Write
Johnson Tag
Write
PMK32
Write
PMK33
Write
PMK34
Write
PMOU1
Write
PMOU2
Write
PMOU3
Write
PMOU4
Write
PMOU5
Write
PMOU6
Write
PMOU7
Write
PMOU8
Write
PMAX1
Write
PMAX2
Write
PMHDC
Write
PMDO
Read
PMST
Write
PMAC1
Write
PMAC2
Write
PMAC3
Write
PMAC4
Write
PMAC5
Write
PMAC6
Write
PMAC7
Write
PMAC8
Relative Item
0
1
2
3
4
5
6
7
8
9
10
Signal Condition
Word
FP
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Analog Input Modules
Read/Write
Johnson Tag
Write
AIT
Write
HR
Write
LR
Write
HIA
Write
LOA
Write
FTC
Write
ADF
Read
AI
Read
AI%
Read
ADC
Read
AIST
Description
Module constant - K32
Module constant - K33
Module constant - K34
Output channel 1
Output channel 2
Output channel 3
Output channel 4
Output channel 5
Output channel 6
Output channel 7
Output channel 8
Auxiliary output 1
Auxiliary output 2
Hold mode control/status
Logic output control and status
Programmable module status
Accumulator channel 1
Accumulator channel 2
Accumulator channel 3
Accumulator channel 4
Accumulator channel 5
Accumulator channel 6
Accumulator channel 7
Accumulator channel 8
Description
Analog inout type
High range input
Low range input
High alarm limit
Low alarm limit
Filter constant
Differential on alarm limit (units)
Analog input value
Analog input %
Analog input in counts
Analog input status
Relative Item
0
1
2
3
4
5
6
7
8
9
10
11
12
Signal Condition
Byte
Word
Word
FP
FP
FP
FP
Byte
FP
FP
Word
Word
Word
Analog Output Modules
Read/Write Johnson Tag
Write
AOT
Write
AO@
Write
AOF@
Write
HRO
Write
LRO
Write
OFL
Write
OUT
Write
AOC
Write
HLO
Write
LLO
Write
INC@
Write
DEC@
Write
ENL@
Description
Analog output type
Source of analog output module
Output forcing logic connection
Output high range
Output low range
Output % value in forcing mode
Output module output value %
Analog output control and status
Output high limit
Output low limit
DDC increase logic connection
DDC decrease logic connection
Limit function enable logic connection
Relative Item
Signal Condition
Digital Output Modules
Read/Write Johnson Tag
Description
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Relative Item
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
Signal Condition
Byte
Word
Word
Word
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Word
Word
Word
Signal Condition
Word
Word
Word
Byte
Word
Word
Word
Word
Word
Word
Word
Word
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
Digital Output Modules
Read/Write Johnson Tag
Write
DOT
Write
DO@
Write
FB@
Write
DOF@
Write
HRO
Write
LRO
Write
FST
Write
DB
Write
HLO
Write
LLO
Write
OFL
Write
OUT
Write
DOC
Write
INC@
Write
DEC@
Write
ENL@
Extension Modules
Read/Write
Johnson Tag
Write
XTIOMAP
Write
XTIOTYP
Write
XTIOMOD
Write
XTADX
Write
XTI1@
Write
XTI2@
Write
XTI3@
Write
XTI4@
Write
XTI5@
Write
XTI6@
Write
XTI7@
Write
XTI8@
Write
XTHR01
Write
XTLR01
Write
XTHR02
Write
XTLR02
Write
XTHR03
Write
XTLR03
Write
XTHR04
Write
XTLR04
Write
XTHR05
Write
XTLR05
Write
XTHR06
Write
XTLR06
Write
XTHR07
Write
XTLR07
Write
XTHR08
Write
XTLR08
Write
XTHIA1
Write
XTLOA1
Write
XTHIA2
Write
XTLOA2
Write
XTHIA3
Write
XTLOA3
Write
XTHIA4
Write
XTLOA4
Write
XTHIA5
Write
XTLOA5
Page 30 of 51
Description
Digital output options
Source of digital output module
Source of feedback signal
Output forcing logic connection
Output high range
Output low range
PAT output full stroke time/DAT cycle
PAT deadband
Output high limit
Output low limit
Output % value in forcing mode
Output module output value %
Logic output control and status
DDC increase logic connection
DDC decrease logic connection
Limit function enable logic connection
Description
Extension module I/O map
Extension module I/O type
Extension module I/O mode
Extension module address 0-255
Point connection - I1
Point connection - I2
Point connection - I3
Point connection - I4
Point connection - I5
Point connection - I6
Point connection - I7
Point connection - I8
High output range point 1
Low output range point 1
High output range point 2
Low output range point 2
High output range point 3
Low output range point 3
High output range point 4
Low output range point 4
High output range point 5
Low output range point 5
High output range point 6
Low output range point 6
High output range point 7
Low output range point 7
High output range point 8
Low output range point 8
High alarm limit point 1
Low alarm limit point 1
High alarm limit point 2
Low alarm limit point 2
High alarm limit point 3
Low alarm limit point 3
High alarm limit point 4
Low alarm limit point 4
High alarm limit point 5
Low alarm limit point 5
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
Relative Item
0
1
2
3
4
5
6
Signal Condition
FP
FP
FP
FP
FP
FP
Word
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
LONG
LONG
LONG
LONG
LONG
LONG
LONG
LONG
Byte
Byte
Byte
Byte
Signal Condition
Word
Word
Word
Word
FP
FP
Byte
Extension Modules
Read/Write
Johnson Tag
Write
XTHIA6
Write
XTLOA6
Write
XTHIA7
Write
XTLOA7
Write
XTHIA8
Write
XTLOA8
Read
XTAIS
Read
XTAI1
Read
XTAI2
Read
XTAI3
Read
XTAI4
Read
XTAI5
Read
XTAI6
Read
XTAI7
Read
XTAI8
Write
XTAO1
Write
XTAO2
Write
XTAO3
Write
XTAO4
Write
XTAO5
Write
XTAO6
Write
XTAO7
Write
XTAO8
Write
XTDIC1
Write
XTDIC2
Write
XTDIC3
Write
XTDIC4
Write
XTDIC5
Write
XTDIC6
Write
XTDIC7
Write
XTDIC8
Write
XTCNT
Write
XTDO
Read
XTDI
Read
XTSTC
Time schedule modules
Read/Write
Johnson Tag
Write
TSOPT
Write
TSEX@
Write
TSON@
Write
TSOF@
Write
TSXTM
Write
TSTIM
Write
TSSTA
Page 31 of 51
Description
High alarm limit point 6
Low alarm limit point 6
High alarm limit point 7
Low alarm limit point 7
High alarm limit point 8
Low alarm limit point 8
Extension module alarms
Analog input value 1
Analog input value 2
Analog input value 3
Analog input value 4
Analog input value 5
Analog input value 6
Analog input value 7
Analog input value 8
Analog output value 1
Analog output value 2
Analog output value 3
Analog output value 4
Analog output value 5
Analog output value 6
Analog output value 7
Analog output value 8
Digital input 1 pulse count
Digital input 2 pulse count
Digital input 3 pulse count
Digital input 4 pulse count
Digital input 5 pulse count
Digital input 6 pulse count
Digital input 7 pulse count
Digital input 8 pulse count
Extension module hold control
Logic outputs control and status
Logic inputs status
Extension module local status
Description
Time schedule options LSB
External extension logical connection
On forcing logical connection
Off forcing logical connection
Extension time (min)
Time to next event (min)
Time schedule status
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Module
Module
Module
Module
Module
Module
Module
Module
Module
Module
Module
Module
1
2
3
4
5
6
7
8
9
10
11
12
Module
Module
Module
Module
Module
Module
Module
Module
1
2
3
4
5
6
7
8
Module
Module
Version
Module
Module
Module
Module
Module
Module
1
2
2
9
10
11
12
13
14
Module
Module
Module
Module
Module
Module
3
4
5
6
7
8
Module
Module
Module
Module
Module
Module
Module
Module
1
2
3
4
5
6
7
8
Module
Module
Module
Module
Module
Module
Module
Module
1
2
3
4
5
6
7
8
Module
Module
1
2
Programmable modules
64
160
256
352
448
544
640
736
832
928
1024
1120
Analog input modules
1216
1232
1248
1264
1280
1296
1312
1328
Analog output modules
1344
1360
or later (new for version 6.0):
2304
2320
2336
2352
2368
2384
Digital output modules
1376
1392
1408
1424
1440
1456
Extension modules
1472
1552
1632
1712
1792
1872
1952
2032
Time schedule modules
2112
2128
2144
2160
2176
2192
2208
2224
Optimal start / stop module
2240
2272
Page 32 of 51
0040H
00A0H
0100H
0160H
01C0H
0220H
0280H
02E0H
0340H
03A0H
0400H
0460H
04C0H
04D0H
04E0H
04F0H
0500H
0510H
0520H
0530H
0540H
0550H
0900H
0910H
0920H
0930H
0940H
0950H
0560H
0570H
0580H
0590H
05A0H
05B0H
05C0H
0610H
0660H
06B0H
0700H
0750H
07A0H
07F0H
0840H
0850H
0860H
0870H
0880H
0890H
08A0H
08B0H
08C0H
08E0H
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 33 of 51
Appendix D.2. Metasys DC9100 Memory Map
Note: The DC9100 is not currently supported by the FieldServer MetasysN2 Driver.
The information below is for interest and future use only.
PAGE 0
Item
DEC
Item
HEX
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
Signal Condition Read/Write
0 Byte
Read
MODL
1
2
3
4
5
6
7
8
9
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Read
Read
Read
Read
Read
Read
Read
Read
Write
Write
Write
INP1
INP2
INP3
INP4
INP5
INP6
INP7
INP8
NCM1
NCM2
NCM3
NMC4
REC1
REC2
REC3
REC4
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
WSP1
WSP2
WSP3
WSP4
WSP5
WSP6
WSP7
WSP8
STW1
STW2
STW3
STW4
STW5
STW6
STW7
STW8
DOUT
CHLD
COMP
A
B
C
D
E
F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
29
2A
2B
Johnson
Tag
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
Word
Word
Word
Word
Word
Word
Word
Word
Word
Byte
Byte
Description
Device model. Value always either 2 or
12
Analog input 1
Analog input 2
Analog input 3
Analog input 4
Analog input 5
Analog input 6
Analog input 7
Analog input 8
Numeric calculation modul result
Numeric calculation modul result
Numeric calculation modul result
Numeric calculation modul result
Remote constant 1
Remote constant 2
Remote constant 3
Remote constant 4
Control output 1
Control output 2
Control output 3
Control output 4
Control output 5
Control output 6
Control output 7
Control output 8
Working setpoint 1
Working setpoint 2
Working setpoint 3
Working setpoint 4
Working setpoint 5
Working setpoint 6
Working setpoint 7
Working setpoint 8
Status word 1
Status word 2
Status word 3
Status word 4
Status word 5
Status word 6
Status word 7
Status word 8
Logic output DDC control
Hold mode control
Supervisory mode control
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 34 of 51
PAGE 0
Item
DEC
Item
HEX
44
45
46
47
48
49
50
2C
2D
2E
2F
Signal Condition Read/Write
Johnson
Tag
Byte
Byte
30 Byte
31 Byte
32 Byte
Write
Write
Write
Write
Write
Spare
Spare
PV1@
RS1@
RV1@
PB1@
OF1@
51
33 Byte
Write
SB1@
52
34 Byte
Write
RA1@
53
35 Byte
Write
EF1@
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
36
37
38
39
Byte
FP
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Byte
Byte
Byte
Byte
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
TYPE1
LS1
PB1
TI1
TD1
HL1
LL1
BS1
BO1
AD1
PV2@
RS2@
RV2@
PB2@
OF2@
69
45 Byte
Write
SB2@
70
46 Byte
Write
RA2@
71
47 Byte
Write
EF2@
72
73
74
75
76
77
78
78
79
80
81
82
83
84
85
86
48 Byte
49 FP
FP
FP
FP
FP
FP
FP
FP
50 FP
51 FP
52 Byte
53 Byte
54 Byte
55 Byte
56 Byte
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
TYPE2
LS2
PB2
TI2
TD2
HL2
LL2
LL2
BS2
BO2
AD2
PV3@
RS3@
RV3@
PB3@
OF3@
87
57 Byte
Write
SB3@
88
58 Byte
Write
RA3@
3A
3B
3C
3D
3E
3F
40
41
42
43
44
4A
4B
4C
4D
4E
4E
4F
Description
Process variable connection
Remote setpoint connection
Reference variable connection
Proportional band connection
OFF mode logic control connection
STAND-BY mode logic control
connection
Reverse action logic control connection
External forcing logic control
connection
Controller type
Local setpoint
Proportional band
Reset action
Rate action
Upper limit of the control output
Lower limit of the control output
Change of setpoint during STAND-BY
Change of setpoint during OFF
Deviation alarm
Process variable connection
Remote setpoint connection
Reference variable connection
Proportional band connection
OFF mode logic control connection
STAND-BY mode logic control
connection
Reverse action logic control connection
External forcing logic control
connection
Controller type
Local setpoint
Proportional band
Reset action
Rate action
Upper limit of the control output
Lower limit of the control output
Lower limit of the control output
Change of setpoint during STAND-BY
Change of setpoint during OFF
Deviation alarm
Process variable connection
Remote setpoint connection
Reference variable connection
Proportional band connection
OFF mode logic control connection
STAND-BY mode logic control
connection
Reverse action logic control connection
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 35 of 51
PAGE 0
Item
DEC
Item
HEX
89
Signal Condition Read/Write
Johnson
Tag
59 Byte
Write
EF3@
Byte
FP
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Byte
Byte
Byte
Byte
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
TYPE3
LS3
PB3
TI3
TD3
HL3
LL3
BS3
BO3
AD3
PV4@
RS4@
RV4@
PB4@
OF4@
69 Byte
Write
SB4@
106 6A
Byte
Write
RA4@
107 6B
Byte
Write
EF4@
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
7A
Byte
FP
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Byte
Byte
Byte
Byte
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
TYPE4
LS4
PB4
TI4
TD4
HL4
LL4
BS4
BO4
AD4
PV5@
RS5@
RV5@
PB5@
OF5@
123 7B
Byte
Write
SB5@
124 7C
Byte
Write
RA5@
125 7D
Byte
Write
EF5@
126 7E
127 7F
128
129
130
131
132
133
134
Byte
FP
FP
FP
FP
FP
FP
FP
FP
Write
Write
Write
Write
Write
Write
Write
Write
Write
TYPE5
LS5
PB5
TI5
TD5
HL5
LL5
BS5
BO5
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
5A
5B
5C
5D
5E
5F
60
61
62
63
64
65
66
67
68
105
6C
6D
6E
6F
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
Description
External forcing logic control
connection
Controller type
Local setpoint
Proportional band
Reset action
Rate action
Upper limit of the control output
Lower limit of the control output
Change of setpoint during STAND-BY
Change of setpoint during OFF
Deviation alarm
Process variable connection
Remote setpoint connection
Reference variable connection
Proportional band connection
OFF mode logic control connection
STAND-BY mode logic control
connection
Reverse action logic control connection
External forcing logic control
connection
Controller type
Local setpoint
Proportional band
Reset action
Rate action
Upper limit of the control output
Lower limit of the control output
Change of setpoint during STAND-BY
Change of setpoint during OFF
Deviation alarm
Process variable connection
Remote setpoint connection
Reference variable connection
Proportional band connection
OFF mode logic control connection
STAND-BY mode logic control
connection
Reverse action logic control connection
External forcing logic control
connection
Controller type
Local setpoint
Proportional band
Reset action
Rate action
Upper limit of the control output
Lower limit of the control output
Change of setpoint during STAND-BY
Change of setpoint during OFF
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 36 of 51
PAGE 0
Item
DEC
Item
HEX
Signal Condition Read/Write
Johnson
Tag
135
136
137
138 8A
139 8B
140 8C
87 FP
88 Byte
89 Byte
Byte
Byte
Byte
Write
Write
Write
Write
Write
Write
AD5
PV6@
RS6@
RV6@
PB6@
OF6@
141 8D
Byte
Write
SB6@
142 8E
Byte
Write
RA6@
143 8F
Byte
Write
EF6@
9A
9B
9C
9D
9E
Byte
FP
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Byte
Byte
Byte
Byte
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
TYPE6
LS6
PB6
TI6
TD6
HL6
LL6
BS6
BO6
AD6
PV7@
RS7@
RV7@
PB7@
OF7@
159 9F
Byte
Write
SB7@
160 A0
Byte
Write
RA7@
161 A1
Byte
Write
EF7@
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
A2
A3
A4
A5
A6
A7
A8
A9
AA
AB
AC
AD
AE
AF
B0
Byte
FP
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Byte
Byte
Byte
Byte
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
TYPE7
LS7
PB7
TI7
TD7
HL7
LL7
BS7
BO7
AD7
PV8@
RS8@
RV8@
PB8@
OF8@
177 B1
Byte
Write
SB8@
178 B2
Byte
Write
RA8@
179 B3
Byte
Write
EF8@
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
90
91
92
93
94
95
96
97
98
99
Description
Deviation alarm
Process variable connection
Remote setpoint connection
Reference variable connection
Proportional band connection
OFF mode logic control connection
STAND-BY mode logic control
connection
Reverse action logic control connection
External forcing logic control
connection
Controller type
Local setpoint
Proportional band
Reset action
Rate action
Upper limit of the control output
Lower limit of the control output
Change of setpoint during STAND-BY
Change of setpoint during OFF
Deviation alarm
Process variable connection
Remote setpoint connection
Reference variable connection
Proportional band connection
OFF mode logic control connection
STAND-BY mode logic control
connection
Reverse action logic control connection
External forcing logic control
connection
Controller type
Local setpoint
Proportional band
Reset action
Rate action
Upper limit of the control output
Lower limit of the control output
Change of setpoint during STAND-BY
Change of setpoint during OFF
Deviation alarm
Process variable connection
Remote setpoint connection
Reference variable connection
Proportional band connection
OFF mode logic control connection
STAND-BY mode logic control
connection
Reverse action logic control connection
External forcing logic control
connection
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 37 of 51
PAGE 0
Item
DEC
Item
HEX
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
B4
B5
B6
B7
B8
B9
BA
BB
BC
BD
BE
BF
C0
C1
C2
C3
C4
C5
C6
C7
C8
C9
CA
CB
CC
CD
CE
CF
D0
D1
D2
D3
D4
D5
D6
D7
D8
D9
DA
DB
DC
DD
DE
DF
E0
E1
E2
E3
E4
E5
E6
Signal Condition Read/Write
Byte
FP
FP
FP
FP
FP
FP
FP
FP
FP
Byte
FP
FP
FP
Byte
FP
FP
FP
Byte
FP
FP
FP
Byte
FP
FP
FP
Byte
FP
FP
FP
Byte
FP
FP
FP
Byte
FP
FP
FP
Byte
FP
FP
FP
FP
FP
Byte
FP
FP
Byte
FP
FP
Byte
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Johnson
Tag
TYPE8
LS8
PB8
TI8
TD8
HL8
LL8
BS8
BO8
AD8
IR1
HA1
LA1
FI1
IR2
HA2
LA2
FI2
IR3
HA3
LA3
FI3
IR4
HA4
LA4
FI4
IR5
HA5
LA5
FI5
IR6
HA6
LA6
FI6
IR7
HA7
LA7
FI7
IR8
HA8
LA8
FI8
OH1
OL1
OMS1
OH2
OL2
OMS2
OH3
OL3
OMS3
Description
Controller type
Local setpoint
Proportional band
Reset action
Rate action
Upper limit of the control output
Lower limit of the control output
Change of setpoint during STAND-BY
Change of setpoint during OFF
Deviation alarm
Range analog input 1
High alarm input 1
Low alarm input 1
Filter time input 1
Range analog input 2
High alarm input 2
Low alarm input 2
Filter time input 2
Range analog input 3
High alarm input 3
Low alarm input 3
Filter time input 3
Range analog input 4
High alarm input 4
Low alarm input 4
Filter time input 4
Range analog input 5
High alarm input 5
Low alarm input 5
Filter time input 5
Range analog input 6
High alarm input 6
Low alarm input 6
Filter time input 6
Range analog input 7
High alarm input 7
Low alarm input 7
Filter time input 7
Range analog input 8
High alarm input 8
Low alarm input 8
Filter time input 8
Output 1 high range
Output1 low range
Source of analog output module 1
Output 2 high range
Output 2 low range
Source of analog output module 2
Output OUTA1 high range
Output OUTA1 low range
Source of logic output module OUTA
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 38 of 51
PAGE 0
Item
DEC
Item
HEX
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
Signal Condition Read/Write
E7
E8
E9
EA
EB
EC
ED
EE
EF
F0
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
FE
FF
Relative Item
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Byte
Byte
FP
FP
FP
FP
Byte
Byte
Byte
FP
FP
FP
FP
Byte
Byte
Byte
FP
FP
FP
FP
Byte
Byte
Byte
FP
FP
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Write
Signal Condition
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
10
11
12
13
14
15
16
17
Johnson
Tag
OMS4
OMTY1
FST1
DB1
OH5
OL5
OMS5
OMS6
OMTY2
FST2
DB2
OH7
OL7
OMS7
OMS8
OMty3
FST3
DB3
SB1
SB2
ALDIS
RCTY1
ALGT
COS1
COS2
PAGE 1
Read/Write Johnson Tag
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
FP
Write
Description
Source of logic output module OUTB
Output module type
PAT/DAT output 1 timing
Dead band PAT output 1
Output OUTA2 high range
Output OUTA2 low range
Source of logic output module OUTA
Source of logic output module OUTB
Output module type
PAT/DAT output 2 timing
Dead band PAT output 2
Output OUTA3 high range
Output OUTA3 low range
Source of logic output module OUTA
Source of logic output module OUTB
Output module type
PAT/DAT output 3 timing
Dead band PAT output 3
Symmetry band controller module 5
Symmetry band controller module 6
Alarm disable condition source
DC type settings
Standard algorithm type
Spare constant
Spare constant
Description Relative Item
HR1
High range analog input 1
LR1
Low range analog input 1
HR2
High range analog input 2
LR2
Low range analog input 2
HR3
High range analog input 3
LR3
Low range analog input 3
HR4
High range analog input 4
LR4
Low range analog input 4
HR5
High range analog input 5
LR5
Low range analog input 5
HR6
High range analog input 6
LR6
Low range analog input 6
HR7
High range analog input 7
LR7
Low range analog input 7
HR8
High range analog input 8
LR8
Low range analog input 8
OM%1
Output % Output module 1
OM%2
Output % Output module 2
OM%3
Output % Output module 3
OM%4
Output % Output module 4
OM%5
Output % Output module 5
OM%6
Output % Output module 6
OM%7
Output % Output module 7
OM%8
Output % Output module 8
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Signal Condition
Byte
Word
Word
Word
Word
Word
Word
Word
Word
Word
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Page 39 of 51
Optimal start / stop module
Read/Write Johnson Tag Description
Write
OSOPT
Module options
Write
OSZT@
Zone temperature connection
Write
OSOT@
Outdoor temperature connection
Write
OSSP@
Zone temperature setpoint connection
Write
OSOB@
Off setpoint bias connection
Write
OSDI@
Disable module connection
Write
OSDA@
Disable adaptive action connection
Write
OSTS@
Connection at time schedule output
Write
OSNX@
Connection at next output
Write
OSTIM@
Connection at time to next output
Write
OSPURGE
Minimum cool / heat time (min)
Write
OSMAXST
Maximum start up time (min)
Write
OSMAXSO
Maximum shut down time (min)
Write
OSBHK
Start mode building heating factor
Write
OSBCK
Start mode building cooling factor
Write
OSSBHK
Stop mode building heating factor
Write
OSSBCK
Stop mode building cooling factor
Write
OSFW
Percentage adaptive control (filter weight)
Write
OSHTD
Outdoor heating design temperature
Write
OSCTD
Outdoor cooling design temperature
Write
OSCRNG
Control range
Write
OSSP
Zone temperature on setpoint
Write
OSOB
Zone temperature off setpoint
Write
OSTIM
Remaining time to next event
Write
OSSTA
Operating status
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 40 of 51
Appendix D.3. Metasys TC9100 Memory Map
Note: The TC9100 is not currently supported by the FieldServer MetasysN2 Driver.
The information below is for interest and future use only.
Relative Item
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Signal Condition
Byte
FP
FP
FP
FP
Word
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
FP
Word
W(1)
W(2)
W(3)
W(4)
W(5)
W(6)
W(7)
W(8)
W(9)
W(10)
W(11)
W(12)
W(13)
W(14)
W(15)
W(16)
Byte
B(1)
B(2)
B(3)
General dynamic Parameters
Read/Write Johnson Tag Description
Read
UNIT
Device model. For TC-9100 always 06h
Write
AI1
Process Temperature
Write
AI2
Remote Temperature Set Point Bias
Write
AI3
Pressure
Write
AI4
Override Input
Spare
Spare
Spare
Spare
Read
ADC
Selected Analog Input ADC counter
Write
OCM1
Output Programmable Module #1
Write
OCM2
Output Programmable Module #2
Write
OCM3
Output Programmable Module #3
Write
OCM4
Output Programmable Module #4
Write
OCM5
Output Programmable Module #5
Write
OCM6
Output Programmable Module #6
Write
WSP1
Working Set Point Control Module 1
Write
WSP2
Working Set Point Control Module 2
Write
WSP3
Working Set Point Control Module 3
Write
WSP4
Working Set Point Control Module 4
Write
WSP5
Working Set Point Control Module 5
Write
WSP6
Working Set Point Control Module 6
Write
XAI1
External Analog Input 1
Write
XAI2
External Analog Input 2
Write
XAI3
External Analog Input 3
Write
XAI4
External Analog Input 4
Write
ACO5
Analog Constant 5
Write
ACO6
Analog Constant 6
Read
WAC
Winter Authority Correction
Read
SAC
Summer Authority Correction
Read
ALR
Analog Inputs Alarm Status
AIH1
Analog Input 1 High alarm
AIL1
Analog Input 1 High alarm
AIH2
Analog Input 2 High alarm
AIL2
Analog Input 2 Low alarm
AIH3
Analog Input 3 High alarm
AIL3
Analog Input 3 Low alarm
AIH4
Analog Input 4 High alarm
AIL4
Analog Input 4 Low alarm
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Read
LOS
Logic Output Status
DO3
TRIAC 3 ON
DO4
TRIAC 4 ON
DO5
TRIAC 5 ON
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item
32
33
34
35
36
37
Signal Condition
B(4)
B(5)
B(6)
B(7)
B(8)
Byte
B(1)
B(2)
B(3)
B(4)
B(5)
B(6)
B(7)
B(8)
Byte
B(1)
B(2)
B(3)
B(4)
B(5)
B(6)
B(7)
Byte
B(1)
B(2)
B(3)
B(4)
B(5)
B(6)
B(7)
Byte
B(1)
B(2)
B(3)
B(4)
B(5)
B(6)
Byte
B(1)
B(2)
B(3)
B(4)
B(5)
B(6)
Byte
B(1)
B(2)
B(3)
B(4)
B(5)
B(6)
B(7)
Page 41 of 51
General dynamic Parameters
Read/Write Johnson Tag Description
DO6
TRIAC 6 ON
DO7
TRIAC 7 ON
DO1
TRIAC 1 ON
DO2
TRIAC 2 ON
Not used
Read
ROS
TC9100 Operation Status
MODS
00 = Night mode
01 = Stand-by mode
10 = Comfort mode
11 = OFF mode
MODT
Temporary mode
MODA
Alternate mode
Supervisory mode enabled
WIN
Window open
OCC
Occupancy Sense
AIRQ
Air Quality Sense
Write
MSK
Outputs Central Control - Enable
DO3E
Enable TRIAC 3
DO4E
Enable TRIAC 4
DO5E
Enable TRIAC 5
DO6E
Enable TRIAC 6
DO7E
Enable TRIAC 7
DO1E
Enable TRIAC 1
DO2E
Enable TRIAC 2
Write
ODC
Outputs Central Control - Set Level
DO3C
TRIAC 3 ON
DO4C
TRIAC 4 ON
DO5C
TRIAC 5 ON
DO6C
TRIAC 6 ON
DO7C
TRIAC 7 ON
DO1C
TRIAC 1 ON
DO2C
TRIAC 2 ON
Write
HLD
Control Loops Hold
Loop #1 Hold
Loop #2 Hold
Loop #3 Hold
Loop #4 Hold
Loop #5 Hold
Loop #6 Hold
Write
HLD
Computer mode Control
Loop #1 Hold WSP override
Loop #2 Hold WSP override
Loop #3 Hold WSP override
Loop #4 Hold WSP override
Loop #5 Hold WSP override
Loop #6 Hold WSP override
Write
SUP
MODC
SOFF
STUP
MAN
Supervisory Mode Control
00 = Night mode request
01 = Stand-by mode request
10 = Comfort mode request
11 = OFF mode request
Shut-Off mode request
Start-Up mode request
Not used
Supervisory Mode Control
Manual OP Mode
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
Signal Condition
B(8)
Byte
B(1)
B(2)
B(3)
B(4)
B(5)
B(6)
B(7)
B(8)
FP
Byte
Byte
Byte
Word
FP
FP
FP
FP
FP
FP
FP
Byte
Byte
Byte
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Byte
Byte
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Byte
Byte
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Byte
Page 42 of 51
General dynamic Parameters
Read/Write Johnson Tag Description
Supervisory System Active Refresh
Read
LSC
Control & status
MNT
Maintenance Started
Maintenance Stopped
RAS
Reverse Action
Loop #1 Active
IAS
Intrusion Alarm
AFM
Anti freezing Mode Active
FOS
Three speed Fan Override Real Status
Loop #3 Active
Write
PM1K1
Constant K1 Module #1
R/W
PM1I@1
Input Connection I1@
R/W
PM1I@2
Input Connection I2@
R/W
PM1I@3
Input Connection I3@
R/W
PM1TYP
Options
R/W
PM1K2
Constant K2
R/W
PM1K3
Constant K3
R/W
PM1K4
Constant K4
R/W
PM1K5
Constant K5
R/W
PM1K6
Constant K6
R/W
PM1K7
Constant K7
R/W
PM2K1
Constant K1 Module #2
R/W
PM2I@1
Input Connection I1@
R/W
PM2I@2
Input Connection I2@
R/W
PM2I@3
Input Connection I3@
R/W
PM2TYP
Options
R/W
PM2K2
Constant K2
R/W
PM2K3
Constant K3
R/W
PM2K4
Constant K4
R/W
PM2K5
Constant K5
R/W
PM2K6
Constant K6
R/W
PM2K7
Constant K7
R/W
PM3K1
Constant K1 Module #3
R/W
PM3I@1
Input Connection I1@
R/W
PM3I@2
Input Connection I2@
R/W
PM3I@3
Input Connection I3@
R/W
PM3TYP
Options
R/W
PM3K2
Constant K2
R/W
PM3K3
Constant K3
R/W
PM3K4
Constant K4
R/W
PM3K5
Constant K5
R/W
PM3K6
Constant K6
R/W
PM3K7
Constant K7
R/W
PM4K1
Constant K1 Module #4
R/W
PM4I@1
Input Connection I1@
R/W
PM4I@2
Input Connection I2@
R/W
PM4I@3
Input Connection I3@
R/W
PM4TYP
Options
R/W
PM4K2
Constant K2
R/W
PM4K3
Constant K3
R/W
PM4K4
Constant K4
R/W
PM4K5
Constant K5
R/W
PM4K6
Constant K6
R/W
PM4K7
Constant K7
R/W
PM5K1
Constant K1 Module #5
R/W
PM5I@1
Input Connection I1@
R/W
PM5I@2
Input Connection I2@
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
Signal Condition
Byte
FP
FP
FP
FP
FP
FP
FP
FP
Byte
Byte
Byte
FP
FP
FP
FP
FP
FP
FP
Relative Item Signal Condition
105
Word
106
Spare
107
Spare
108
FP
109
FP
110
FP
111
FP
112
FP
113
FP
114
FP
115
FP
116
Byte
B(1)
B(5)
B(6)
B(8)
117
FP
118
Byte
B(1)
B(5)
B(6)
B(8)
119
FP
120
Byte
B(1)
Page 43 of 51
General dynamic Parameters
Read/Write Johnson Tag Description
R/W
PM5I@3
Input Connection I3@
R/W
PM5TYP
Options
R/W
PM5K2
Constant K2
R/W
PM5K3
Constant K3
R/W
PM5K4
Constant K4
R/W
PM5K5
Constant K5
R/W
PM5K6
Constant K6
R/W
PM5K7
Constant K7
R/W
PM6K1
Constant K1 Module #6
R/W
PM6I@1
Input Connection I1@
R/W
PM6I@2
Input Connection I2@
R/W
PM6I@3
Input Connection I3@
R/W
PM6TYP
Options
R/W
PM6K2
Constant K2
R/W
PM6K3
Constant K3
R/W
PM6K4
Constant K4
R/W
PM6K5
Constant K5
R/W
PM6K6
Constant K6
R/W
PM6K7
Constant K7
Input Output Config Parameters
Read/Write Johnson Tag Description
Read
VER
Firmware Version
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
HIA1
LOA1
HIA2
LOA2
HIA3
LOA3
HIA4
LOA4
OCN1
R/W
R/W
OCO1
OCN2
R/W
R/W
OCO2
OCN3
High Alarm AI1
Low Alarm AI1
High Alarm AI2
Low Alarm AI2
High Alarm AI3
Low Alarm AI3
High Alarm AI4
Low Alarm AI4
Output #1 Configuration
00001 Src of Module (Analog Items 1..31)
?.
11111
000 = Not used
001 = Output for Solenoids
010 = 0 to 10 V Analog Output
011 = ON/OFF Output
100 = DAT Output Type
101 = PAT Output Type
110 = Multistage ON/OFF Type
PAT/DAT Timing for Output Module #1
Output #2 Configuration
00001 Src of Module (Analog Items 1..31)
?.
11111
000 = Not used
001 = Output for Solenoids
010 = 0 to 10 V Analog Output
011 = ON/OFF Output
PAT Dead Band/Multistate Hysteresis #1
Output #3 Configuration
00001 Src of Module (Analog Items 1..31)
?.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item Signal Condition
B(5)
B(6)
B(8)
121
FP
122
Byte
B(1)
B(5)
B(6)
B(8)
123
FP
124
Byte
B(1)
B(5)
B(6)
B(8)
125
FP
126
Byte
B(1)
B(5)
B(6)
B(8)
127
FP
128
Byte
B(1)
B(5)
B(6)
B(8)
129
FP
130
spare
131
Word
132
Word
W(1)
W(2)
W(3)
W(4)
W(5)
W(6)
W(8)
W(9)
W(10)
W(11)
W(12)
W(13)
Page 44 of 51
Input Output Config Parameters
Read/Write Johnson Tag Description
11111
000 = Not used
011 = ON/OFF Output
100 = DAT Output Type
101 = PAT Output Type
110 = Multistage ON/OFF Type
R/W
OCO3
PAT/DAT Timing for Output Module #3
R/W
OCN4
Output #4 Configuration
00001 Src of Module (Analog Items 1..31)
?.
11111
000 = Not used
011 = ON/OFF Output
R/W
R/W
OCO4
OCN5
R/W
R/W
OCO5
OCN6
R/W
R/W
OCO6
OCN7
PAT/DAT Timg Outpt Mod #5 FSB-pnt #2
Output #7 Configuration
00001 Src of Module (Analog Items 1..31)
?.
11111
000 = Not used
R/W
OCO7
Fan Speed Break-point #3
R/W
Write
Read
Read
Read
Read
Clear
ALG
XST
Configuration Index 1
Diagnostic Status
Gain x 2 Jumper
Integral Action Zeroing Jumper
Zone 1 Jumper
Zone 2 Jumper
Dial Request Status
Not used
Intelligent Command Module Com Failure
not valid
not valid
not valid
not valid
EEPROM not protected
Read
Read
Read
Read
Read
Read
DIAL
XTAI1
XTAI2
XTAI3
XTAI4
PAT Dead Band/Multistate Hysteresis #3
Output #5 Configuration
00001 Src of Module (Analog Items 1..31)
?.
11111
000 = Not used
011 = ON/OFF Output
100 = DAT Output Type
101 = PAT Output Type
110 = Multistage ON/OFF Type
111 = Three Windings Control
PAT/DAT Timg Outpt Mod #5 FSB-pnt #1
Output #6 Configuration
00001 Src of Module (Analog Items 1..31)
?.
11111
000 = Not used
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item Signal Condition
W(14)
W(15)
W(16)
133
Word
W(1)
W(2)
W(3)
W(4)
W(5)
W(6)
W(7)
W(8)
W(9)
W(11)
W(12)
W(13)
W(15)
W(16)
134
Word
W(1)
W(2)
W(3)
W(4)
W(5)
W(6)
W(7)
W(8)
W(9)
W(10)
W(11)
W(12)
W(13)
W(14)
135
Byte
B(1)
B(2)
B(3)
B(4)
B(5)
B(6)
B(7)
B(8)
136
Word
137
FP
Page 45 of 51
Input Output Config Parameters
Read/Write Johnson Tag Description
Read
Reset Cycle indication
Read
00 = Power Up Reset
01 = External Reset
10 = Oscillator Failure
Read
11 = Watchdog Reset
R/W
TCS2
TC9100 Controller Options
00 Select Analog Input 1 ADC
to
11 Select Analog Input 4 ADC
TM9100 does not overrd the proc Variable
Half Alternate Mode Timing
0 = Celsius 1 = Fahrenheit
0 = 50 Hz 1 = 60 Hz Power Line
Enable Facilitator Mode
TRIAC7 is ON if mode is Comfort
Digital Input #1 Mode
000 = Not used
001 = Window Open
010 = Occupancy Sensor
011 = Air Quality Sensor
100 = Reverse Action
101 = Intrusion Alarm
Negate Digital Input #1
Digital Input #2 Mode
000 = Not used
001 = Window Open
010 = Occupancy Sensor
011 = Air Quality Sensor
100 = Reverse Action
101 = Intrusion Alarm
Negate Digital Input #2
R/W
TCS3
Enable Jumper Options
Enable Integral Zeroing Loop #1
Enable Integral Zeroing Loop #2
Enable Integral Zeroing Loop #3
Enable Integral Zeroing Loop #4
Enable Integral Zeroing Loop #5
Enable Integral Zeroing Loop #6
Not used
Not used
Enable Gain Doubling Loop #1
Enable Gain Doubling Loop #2
Enable Gain Doubling Loop #3
Enable Gain Doubling Loop #4
Enable Gain Doubling Loop #5
Enable Gain Doubling Loop #6
Write
TCS1
Controller Options
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Default Action 1=Reverse
R/W
HDW1
Hardware Configuration
R/W
HRI1
High Range AI1
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item Signal Condition
138
FP
139
FP
140
FP
141
Byte
B(1)
B(3)
B(4)
B(5)
B(7)
B(8)
142
FP
143
FP
144
FP
145
FP
146
Byte
147
FP
148
FP
149
FP
150
FP
151
Byte
152
FP
153
FP
154
FP
155
FP
156
Byte
157
Byte
B(1)
B(2)
B(3)
B(4)
B(5)
B(6)
B(7)
B(8)
158
Word
W(1)
W(6)
W(7)
W(8)
W(9)
W(13)
W(14)
W(16)
159
Byte
160
FP
161
FP
Page 46 of 51
Input Output Config Parameters
Read/Write Johnson Tag Description
R/W
LRI1
Low Range AI1
R/W
FTC1
Filter Constant AI1
R/W
OFS1
Offset Compensation AI1
R/W
IOP1
Analog Input Options
Controller reference
1 to 6
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Write
HRI2
LRI2
FTC2
OFS2
IOP2
HRI3
LRI3
FTC3
OFS3
IOP3
HRI4
LRI4
FTC4
OFS4
IOP4
OS
Write
STIME
RTC
Input Type: 0=volt 1=resistance
Input Mode
000 - Linear Range
001-Thermistor Linearization 2252.at 25C
010 - Square Root
011 - 0.2 suppression
100-Thermistor Linearization 10 k. at 25C
101 - Square Root & 20 % suppression
Not used
High Range AI2
Low Range AI2
Filter Constant AI2
Offset Compensation AI2
Analog Input Options (see IOP1)
High Range AI3
Low Range AI3
Filter Constant AI3
Offset Compensation AI3
Analog Input Options (see IOP1)
High Range AI4
Low Range AI4
Filter Constant AI4
Offset Compensation AI4
Analog Input Options (see IOP1)
TC9100 Requested Operating Status
00 = Night mode
01 = Stand-by mode
10 = Comfort mode
11 = OFF mode
Not used
Not used
Operating Mode Toggle: Base- Alternate
Not used
Force Operating Mode
Command Module Active
TM9100 Real Time Clk Synchronization
Minutes 0..59
RTC
Spare
Spare
Hours 0..23
RTC
Day of Week 1..7
OT@
SPW
SPS
Outdoor Temperature Connection
Winter set point
Summer set point
R/W
Write
Write
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item Signal Condition
162
FP
163
FP
164
Byte
165
FP
166
FP
167
Word
W(1)
W(2)
W(3)
W(4)
W(5)
W(6)
W(7)
W(8)
W(9)
W(10)
W(11)
W(12)
168
Word
W(1)
W(2)
W(3)
W(4)
W(5)
W(6)
W(7)
W(8)
W(9)
W(10)
W(11)
W(12)
W(13)
W(14)
169
Word
170
FP
171
FP
Relative Item
256
257
258
259
260
261
Page 47 of 51
Input Output Config Parameters
Read/Write Johnson Tag Description
Write
WA
Winter Authority Slope
Write
SA
Summer Authority Slope
R/W
FT@
Freeze Temperature connection
Write
FSP
Freeze set point
R/W
FDIF
Freeze Differential
Write
LOO
Input/Output Override Control
Read
Three Speed Fan Actual Speed
00 = Output OFF
01 = Speed #1
10 = Speed #2
Read
11 = Speed #3
Not used
Read
FOS
Three spd Fan Overrd Reqst by Hardware
Write
Fan Speed Reqst by Command Module
00 = Output OFF
01 = Speed #1
10 = Speed #2
11 = Speed #3
TM9100 Real Time Clk Refresh Request
FOR
Three speed Fan Overrd Reqst Cmd Mod
AIO1
Analog Input #1 Override
AIO2
Analog Input #2 Override
AIO3
Analog Input #3 Override
AIO4
Analog Input #4 Override
Write
CLACT
Control Loops Activity Mode
Read
Loop #1 Heating
Read
Loop #2 Heating
Read
Loop #3 Heating
Read
Loop #4 Heating
Read
Loop #5 Heating
Read
Loop #6 Heating
Not used
Not used
Write
Loop #1 Active
Write
Loop #2 Active
Write
Loop #3 Active
Write
Loop #4 Active
Write
Loop #5 Active
Write
Loop #6 Active
R/W
ALG2
Configuration Index 2
R/W
WAL
Winter Authority Limit
R/W
SAL
Summer Authority Limit
Items Stored in the TM91xx External Database
Signal Condition Read/Write Johnson Tag Description
Byte
Read
UNIT
Device Model : xxH
FP
Read
TEMP
Room Temperature
FP
Read
RSP
Remote Temperature Set Point
Word
Read
LOO
Copy of TC9100 Item LOO
Byte
Read
JMP
TM9100 Jumper Configuration & status
B(1)
JMP1
Clock Setting Disable
B(2)
JMP2
Fan Setting Disable
B(3)
JMP3
Time Schedule Setting Disable
B(4)
JMP4
Model with Time Schedule
B(5)
JMP5
Time Schedule Configuration Changed
Word
Write
TIME
Real Time
W(1)
RTC Minutes 0..59
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item
Items Stored in the TM91xx External Database
Signal Condition Read/Write Johnson Tag Description
W(6)
W(9)
RTC Hours 0..23
W(13)
W(14)
RTC Dy of Week 1..7
W(16)
Relative Item Signal Condition
271
Word
W(1)
W(2)
W(3)
W(4)
W(5)
W(6)
W(7)
W(8)
W(9)
W(10)
272
272
272
273
287
288
289
290
291
292
303
304
305
306
307
308
319
320
321
322
323
Page 48 of 51
TM91xx Daily Schedules:
Read/Write Johnson Tag Description
Write
DST1
Type of Daily Schedule #1
Mode event 1
00 = Set Night Mode
01 = Set Comfort Mode
10 = Set Stand-By Mode
11 = Set OFF Mode
Mode event 2 (Same Fmt. Mode event 1)
Mode event 3 (Same Fmt. Mode event 1)
Mode event 4 (Same Fmt. Mode event 1)
Mode event 5 (Same Fmt. Mode event 1)
W(11)
W(12)
W(13)
W(15)
Word
Word
Word
Mode event 6 (Same Fmt. Mode event 1)
Write
Write
Write
E12S1
E34S1
E56S1
Word
Word
Word
Word
Write
Write
Write
Write
DST2
E12S2
E34S2
E56S2
Word
Word
Word
Word
Write
Write
Write
Write
DST3
E12S3
E34S3
E56S3
Word
Word
Word
Word
Write
Write
Write
Write
DST4
E12S4
E34S4
E56S4
Number of Days of activity 1..7
Event #1 & Event #2 Day #1
Event #3 & Event #4 Day #1
Event #5 & Event #6 Day #1
Spare
Spare
Type of Daily Schedule #2 (Fmt. #1)
Event #1 & Event #2 Day #2
Event #3 & Event #4 Day #2
Event #5 & Event #6 Day #2
Spare
Spare
Type of Daily Schedule #3 (Fmt. #1)
Event #1 & Event #2 Day #3
Event #3 & Event #4 Day #3
Event #5 & Event #6 Day #3
Spare
Spare
Type of Daily Schedule #4 (Fmt. #1)
Event #1 & Event #2 Day #4
Event #3 & Event #4 Day #4
Event #5 & Event #6 Day #4
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Relative Item Signal Condition
324
335
336
Word
337
Word
338
Word
339
Word
340
351
352
Word
353
Word
354
Word
355
Word
356
367
368
Word
369
Word
370
Word
371
Word
372
383
Page 49 of 51
TM91xx Daily Schedules:
Read/Write Johnson Tag Description
Spare
Spare
Write
DST5
Type of Daily Schedule #5 (Fmt. #1)
Write
E12S5
Event #1 & Event #2 Day #5
Write
E34S5
Event #3 & Event #4 Day #5
Write
E56S5
Event #5 & Event #6 Day #5
Spare
Spare
Write
DST6
Type of Daily Schedule #6 (Fmt. #1)
Write
E12S6
Event #1 & Event #2 Day #6
Write
E34S6
Event #3 & Event #4 Day #6
Write
E56S6
Event #5 & Event #6 Day #6
Spare
Spare
Write
DST7
Type of Daily Schedule #7 (Fmt. #1)
Write
E12S7
Event #1 & Event #2 Day #7
Write
E34S7
Event #3 & Event #4 Day #7
Write
E56S7
Event #5 & Event #6 Day #7
Spare
Spare
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 50 of 51
Appendix E. Error Messages
Error Message
MN2:#01 WARN.
Server_Hold_Timeout is
%0.3fs
For N2Open Slave
typical value is %0.3fs
Description and Action
Typically N2open Clients are configured to timeout after 200ms. If a
FieldServer is configured as a Server the Server_Hold_Timeout time
should be set to 0.175s or less otherwise the response will be suppressed.
This message is printed if the Server_Hold_Timeout is set for >0.175s.
If the Client’s timeout is >200ms this message may be ignored.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-19_Metasys_N2 Driver Manual
Page 51 of 51
THIS PAGE INTENTIONALLY LEFT BLANK
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2296 Toll_Free: 888-509-1970 email: support@fieldserver.com