FieldServer FS-8700-23 Computer Drive User Manual

A Sierra Monitor Company
Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-23 Cleaver Brooks Hawk
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after May 1, 2001
Driver Version:
1.00
Document Revision: 4
FS-8700-23 Cleaver Brooks Hawk Driver Manual
Table of Contents
Table of Contents
1.
CB-Link Description........................................................................................................3
2.
2.1.
2.2.
Driver Scope of Supply...................................................................................................4
Provided by FieldServer Technologies for this driver ..................................................4
Provided by the Supplier of 3rd Party Equipment.........................................................4
3.
Hardware Connections ...................................................................................................5
4.
Configuring the FieldServer as a ChB-Link Client ........................................................6
4.1.
FieldServer .................................................................................................................6
4.2.
Data Arrays/Descriptors..............................................................................................6
4.3.
Client Side Connection Descriptions ...........................................................................7
4.4.
Client Side Node Descriptors ......................................................................................8
4.4.1. Node_ID ..................................................................................................................8
4.4.2. Node_Type..............................................................................................................8
4.5.
Client Side Map Descriptors........................................................................................9
4.5.1. FieldServer Related Map Descriptor Parameters.....................................................9
4.5.2. Driver Related Map Descriptor Parameters .............................................................9
4.5.3. Timing Parameters ..................................................................................................9
4.5.4. Map Descriptor Example .......................................................................................10
Appendix A. Advanced Properties ....................................................................................11
Appendix A.1. Property Files ..............................................................................................11
Appendix A.2. Configuration Files.......................................................................................11
Appendix B.
Device Information Table..............................................................................12
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-23 Cleaver Brooks Hawk Driver Manual
1.
Page 3 of 13
CB-Link Description
The CB-Link driver allows the FieldServer to transfer data to and from devices over RS-485
using CB-Link protocol. The information that follows describes how to expand upon the factory
defaults provided in the configuration files included with the FieldServer.
Refer to “Model 833-2771 CB-Link” Manual #65-0216 and “Model 833-2757 General Purpose
Interface ControlBus Module” Manual #65-0220 from Cleaver Brooks.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-23 Cleaver Brooks Hawk Driver Manual
2.
Page 4 of 13
Driver Scope of Supply
2.1.
Provided by FieldServer Technologies for this driver
Fieldserver Technologies Part #
SPA59137
2.2.
Description
RS-485 7-way connector adapter with attached
cable
Provided by the Supplier of 3rd Party Equipment
PART #
DESCRIPTION
CB-Link Controller
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-23 Cleaver Brooks Hawk Driver Manual
3.
Page 5 of 13
Hardware Connections
The FieldServer can be connected to the CB – Link device as shown below.
Configure the PLC according to manufacturer’s instructions
!"
#$
%
$
&
%
'( '
(
(
'(
#
(
$
)(
%
(
) )
%
))*
*
#
Net 1
Gnd
_
DC AUX Power
Net 2
+
+
,-.
+
FG
Gnd
_
Power
+ 5 V 1 .5A
0V
%
FG
_ 5 V 5 00 mA
+ 12 V 5 00 mA
_ 12 V 5 00 mA
(
$
P8
P7
P6
P5
P4
P3
P2
P1
RS 23 2
Et hernet
10 Base T
R2
R1
RS 485
(Opt o - Isolat ed)
GRO UND
DTR
RTS
Tx
5
6
7
8
8
1
1
2
3
4
Rx
CTS
DSR
GRO UND
&
$
'43
5
6
'
'43
5
6
/-! 0!1
2-,3
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-23 Cleaver Brooks Hawk Driver Manual
4.
Page 6 of 13
Configuring the FieldServer as a ChB-Link Client
For a detailed discussion on FieldServer configuration, please refer to the FieldServer
Configuration Manual. The information that follows describes how to expand upon the factory
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files
provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer
to communicate with a ChB-Link Server
Note that * indicates an optional parameter, with the bold legal value being the default.
4.1.
FieldServer
Section Title
Bridge
Column Title
Title
System_Node_ID
Function
Title for CSV file
Node ID of the FieldServer
Legal Values
Any text, Maximum 32 characters
8 – 254
Example
//
Common Information
Bridge
Title,
CB_Link client,
4.2.
System_Node_ID
11
Data Arrays/Descriptors
Section Title
Data_Arrays
Column Title
Data_Array_Name
Data_Format
Data_Array_Length
Function
Provide name for Data Array
Provides data format
Number of Data Objects
Legal Values
Up to 15 alphanumeric characters
INT16, INT32, BIT, FLOAT
1-10,000
Example
//
Data Arrays
Data_Arrays
Data_Array_Name,
DA_AI_01,
Data_Format,
Float,
Data_Array_Length
200
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-23 Cleaver Brooks Hawk Driver Manual
4.3.
Page 7 of 13
Client Side Connection Descriptions
Section Title
Connections
Column Title
Function
Legal Values
Specify which port the device is connected to the
Port
R1-R2
FieldServer
Baud
Specify baud rate
9600
Parity
Specify parity
None
IC_Timeout
Inter-Character Timeout
>10.0 s
Squelch_Timer Squelch suppression time
>0.02 s
Poll_Delay
Minimum time between polls
0,55
Example
//
Client Side Connections
Connections
Port,
R2,
Baud,
9600,
Parity,
None,
Ic_Timeout,
10,
Squelch_Timer,
0.02,
Poll_Delay
0.6
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-23 Cleaver Brooks Hawk Driver Manual
4.4.
Page 8 of 13
Client Side Node Descriptors
Section Title
Nodes
Column Title
Node_Name
Function
Provide name for node
CB Link_ID
Device address
Protocol
Specify protocol used
Legal Values
Up to 32 alphanumeric characters
See Section 4.4.1 A, B, and C
below
CB_Link
Port
Port connection
R1-R2
Node_Type
Specify controller connected to CBLink
See Section 4.4.2
Example
//
Client Side Nodes
Nodes
Node_Name,
CBH1,
4.4.1.
CBlink_ID,
0 1 20,
Protocol,
CB_Link,
Port,
R2,
Node_Type
Hawk
Node_ID
Format for declaring node ID is A B C.
A: 0 if only one CB-Link is attached, 8–254 if multiple CB-Links are attached, Default = 0
B: Slot the device is attached to in the PC Link 1-5, default 1
C: Device type (Declare Device Type Code):
Device Description
Device Type Code
Auxenh
26
Ec78xx
32
Efenh
26
Hawk
20
Llenh
26
Orenh
26
Pulsa
19
Q7700
1
Qm40xx
17
Rm78xx
32
S7800
36
S7830
34
Tdenh
26
Testcard
99
Trapscan
18
4.4.2.
Node_Type
Hawk, EC78XX. Others by request. (Refer to Device Information Table)
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-23 Cleaver Brooks Hawk Driver Manual
4.5.
Page 9 of 13
Client Side Map Descriptors
4.5.1.
FieldServer Related Map Descriptor Parameters
Column Title
Map_Descriptor_Name
Data_Array_Name
Data_Array_Offset
Function
4.5.2.
Function
Name of this Map
Descriptor. This Name
refers to the variable in
the related .bp2
property file.
Name of Data Array
where data is to be
stored in the
FieldServer
Starting location in Data
Array
Function of Client Map
Descriptor
Any of the variable names in
the related .bp2 property file.
One of the Data Array
names from “Data Array”
section above
0 to maximum specified in
“Data Array” section above
RDBC
Driver Related Map Descriptor Parameters
Column Title
Function
Node_Name
Name of Node to fetch
data from
Scan_Interval
Specify poll rate
4.5.3.
Legal Values
Legal Values
One of the node names
specified in “Client Node
Descriptor” above
>1.0s
Timing Parameters
Column Title
Timeout
Function
Specify maximum response time
Legal Values
>30.0s
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-23 Cleaver Brooks Hawk Driver Manual
4.5.4.
//
Page 10 of 13
Map Descriptor Example
Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
Control_Source,
Oper_Pressure,
Data_Array_Name,
DA_AI_01,
DA_AI_01,
Data_Array_Offset,
1,
2,
Function,
RDBC,
RDBC,
Node_Name,
CBH1,
CBH1,
Scan_Interval,
10,
10,
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Timeout
30
30
FS-8700-23 Cleaver Brooks Hawk Driver Manual
Page 11 of 13
Appendix A. Advanced Properties
Appendix A.1. Property Files
Each Controller interfacing to the FieldServer requires associated property files (denoted by
file extensions .bp1 and .bp2) to be loaded into the FieldServer. At present, the property
files listed in the device information table below are preloaded onto the FieldServer when
delivered. Other property files may be available upon request.
Appendix A.2. Configuration Files
Each Controller listed in the device information table below has an associated configuration
file as shown in the device information table. This configuration file can be used as a basis
for building a configuration for the FieldServer as it contains the mapping for the related
module.
Note: SYSNet is the generic name for networks of the following modules. Controlbus is the
generic name for the networks in a NIM/CBLink configuration
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-23 Cleaver Brooks Hawk Driver Manual
Page 12 of 13
Appendix B. Device Information Table
MAKE
Honeywell
Cleaver
Brooks
NETWORK INTERFACE UNIT
MODEL
NAME
Q7700
Network Interface Unit
833-2771
CB-Link
CONTROL MODULES
MODEL No.
MAKE
OF
MODULE NAME
MODULE
Honeywell QS7700A
BCS7700
Honeywell QS7800A
7800 SERIES Control
N/A
N/A
N/A
N/A
Honeywell QS7800C
QM40XX Data Acquisition Module
ON REQUEST
QM40XX
Armstrong QS7800D
Honeywell QS7800E
Trapscan System
PulsaFeeder PULSAtrol
ON REQUEST
PULSA
ON REQUEST
PULSA
Honeywell QS7800A
S7830 Expanded Annunciator
S7830
S7830
Honeywell QS7800A
S7800 Keyboard/Display Module
S7800
S7800
Honeywell QS7800A
ST7800 Relay Module
ST7800
Honeywell
Honeywell
Honeywell
CB-Link
CB-Link
CB-Link
CB-Link
CB-Link
RM7800E,G,L,M Relay Modules
RM7840E,G,L,M Relay Modules
Q7700A,B
Display Module
Data Control Bus Module
CB 783
CB 780
CB 784
RM78XX
RM78XX
RM78XX
RM78XX
N/A
N/A
ON REQUEST
ON REQUEST
ON REQUEST
N/A
N/A
ON REQUEST
ON REQUEST
ON REQUEST
N/A∗
833-2727
833-2729
833-2734
833-2734
833-2734
PROPERTY FILE
CONFIGURATION FILE
NOTES
NAME (.BP1;.BP2) NAME (.CSV)
Data Acquisition
Modules
Expanded
Annunciator
Requires S7800
module
Requires 833-2727 or
833-2729 on module
.
∗
This is the chassis that the above modules plug into
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8700-23 Cleaver Brooks Hawk Driver Manual
Page 13 of 13
THIS PAGE INTENTIONALLY LEFT BLANK.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Download PDF