FieldServer FS-8704-07 Computer Drive User Manual

A Sierra Monitor Company
Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8704-07 AB_CSP
APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after May 1, 2001
FS-8704-07_AB-CSP Manual
Index
TABLE OF CONTENTS
1.
Allen Bradley AB_CSP Description.................................................................................3
2.
2.1.
2.2.
Hardware/Software............................................................................................................4
Supplied by FieldServer Technologies for this Driver...................................................4
Provided by Supplier of 3rd Party Equipment ................................................................4
3.
Hardware Connections .....................................................................................................5
4.
Configuring the FieldServer as a AB-CSP Client ...........................................................6
4.1.
Data Arrays/Descriptors ...............................................................................................6
4.2.
Client Side Connection Descriptors ..............................................................................7
4.3.
Client Side Node Descriptors .......................................................................................7
4.4.
Client Side Map Descriptors Client Side Map Descriptors............................................8
4.4.1. FieldServer Related Map Descriptor Parameters......................................................8
4.4.2. Driver Related Map Descriptor Parameters ..............................................................8
4.4.3. Map Descriptor Example ...........................................................................................9
5.
Configuring the FieldServer as an AB_CSP Server.....................................................10
5.1.
Server Side Connection Descriptors...........................................................................10
5.2.
Server Side Node Descriptors ....................................................................................10
5.3.
Server Side Map Descriptors......................................................................................11
5.3.1. FieldServer Related Map Descriptor Parameters....................................................11
5.3.2. Driver Related Map Descriptor Parameters ............................................................11
5.3.3. Map Descriptor Example .........................................................................................12
Appendix A. Troubleshooting .............................................................................................13
Appendix A.1. Continuous Map Descriptors .........................................................................13
Appendix B.
Command Support .........................................................................................14
Appendix C.
Revision History .............................................................................................15
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8704-07_AB-CSP Manual
1.
Page 3 of 15
Allen Bradley AB_CSP Description
The AB_CSP driver allows the FieldServer to transfer data to and from devices over AB_CSP
Ethernet protocol. The FieldServer can emulate either a Server or Client.
The information that follows describes how to expand upon the factory defaults provided in the
configuration files included with the FieldServer.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8704-07_AB-CSP Manual
2.
Hardware/Software
2.1.
Supplied by FieldServer Technologies for this Driver
FieldServer Technologies PART #
FS-8915-10
FS-8704-07
2.2.
PART #
1
2
Page 4 of 15
DESCRIPTION
Ethernet cable (7 foot)
Driver Manual
Provided by Supplier of 3rd Party Equipment
DESCRIPTION
AB_CSP compatible PLC, e.g. SLC5/05 etc. 1
AB_CSP Client, e.g. Wonderware, Intellution FIX, GE Cimplicity, etc. 2
If FieldServer used as Allen Bradley AB_CSP Client
If FieldServer used as Allen Bradley AB_CSP Server.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8704-07_AB-CSP Manual
3.
Page 5 of 15
Hardware Connections
Make sure the device IP_address is configured to be on the same IP network as the
FieldServer. Use a crossover cable if the FieldServer is connected directly to the PLC device.
Use a straight cable if the FieldServer is connected to a hub.
Configure the PLC according to manufacturer’s instructions
PLC
Ethernet Interface
SITE
ETHERNET
FS-8915-10
FS-8915-10
(408)-262-2299
FIELDSERVER
AB-CSP
CONNECTION DIAGRAM
BASE NAME:
FILE NAME:
DATE: 5/04/04
BY:
MC
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8704-07_AB-CSP Manual
4.
Page 6 of 15
Configuring the FieldServer as a AB-CSP Client
For a detailed discussion on FieldServer configuration, please refer to the FieldServer
Configuration Manual. The information that follows describes how to expand upon the factory
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files
provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer
to communicate with an AB-CSP Server.
4.1.
Data Arrays/Descriptors
The configuration file tells the FieldServer about its interfaces, and the routing of data
required. In order to enable the FieldServer for AB-CSP communications, the driver
independent FieldServer buffers need to be declared in the “Data Arrays” section, the
destination device addresses need to be declared in the “Client Side Nodes” section, and
the data required from the servers needs to be mapped in the “Client Side Map Descriptors”
section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the
default.
Section Title
Data_Arrays
Column Title
Function
Data_Array_Name
Provide name for Data Array
Data_Array_Format
Data_Array_Length
Provide data format. Each Data
Array can only take on one format.
Number of Data Objects. Must be
larger than the data storage area
required by the Map Descriptors for
the data being placed in this array.
Legal Values
Up to 15 alphanumeric
characters
INT16, INT32, BIT,
FLOAT
1-10,000
Example
//
Data Arrays
Data_Arrays
Data_Array_Name,
DA_AI_01,
DA_AO_01,
DA_DI_01,
DA_DO_01,
Data_Format,
Float,
Float,
Bit,
Bit,
Data_Array_Length
200
200
200
200
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8704-07_AB-CSP Manual
4.2.
Page 7 of 15
Client Side Connection Descriptors
Section Title
Connections
Column
Title
Legal
Values
Function
Specify which port the device is connected to the
FieldServer
Specify protocol used
Adapter
Protocol
N1
AB_CSP
Example
//
Client Side Connections
Connections
Adapter,
N1,
4.3.
Protocol
AB_CSP
Client Side Node Descriptors
Section Title
Nodes
Column Title
Node_Name
Function
Provide name for node
Legal Values
Up to 32 alphanumeric
characters
Node ID of physical server
1-255
node (PLC)
Must be on the same
IP address of physical server
subnet as the server or
node (PLC)
gateway
Specify protocol used
AB_CSP
Specify on which port the
device is connected to the N1
FieldServer
Specify PLC
PLC3, PLC5, SLC5
Communications type.
Node_ID
IP_Address
Protocol
Adapter
PLC_Type
Example
//
Client Side Nodes
Nodes
Node_Name,
PLC_01,
Node_ID,
1,
Protocol,
AB_CSP,
PLC_Type,
SLC5,
IP_Address,
192.168.1.13,
Adapter
N1
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8704-07_AB-CSP Manual
4.4.
Page 8 of 15
Client Side Map Descriptors Client Side Map Descriptors
4.4.1.
FieldServer Related Map Descriptor Parameters
Column Title
Map_Descriptor_Name
Data_Array_Name
Data_Array_Offset
Function
4.4.2.
Legal Values
Up to 32 alphanumeric
characters
One of the Data Array
names from “Data Array”
section above
0 to maximum specified in
“Data Array” section above
RDBC, WRBC, WRBX
Driver Related Map Descriptor Parameters
Column Title
Node_Name
File_Type
File_Number
Address
Data_Array_Low_Scale*
Data_Array_High_Scale*
Node_Low_Scale*
Node_High_Scale*
AB_Command
Function
Name of this Map
Descriptor
Name of Data Array
where data is to be
stored in the
FieldServer
Starting location in Data
Array
Function of Client Map
Descriptor
Function
Name of Node to fetch
data from
File type in PLC
File Number in PLC
Starting address of read
block
Scaling zero in Data Array
Scaling max in Data Array
Scaling zero in Connected
Node
Scaling max in Connected
Node
Override the default
command
Legal Values
Client Side Nodes
N, B, F, S
0-255
0 – 255
-32767 to 32767, 0
-32767 to 32767, 100
-32767 to 32767, 0
-32767 to 32767, 100
Unprotected Command
Typed
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8704-07_AB-CSP Manual
4.4.3.
//
Page 9 of 15
Map Descriptor Example
Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name,
CMD_AI_01,
CMD_AO_01,
Data_Array_Name,
DA_AI_01,
DA_AO_01,
Data_Array_Offset,
0,
0,
Function,
RDBC,
RDBC,
Node_Name,
PLC_01,
PLC_01,
File_Type,
N,
N,
File_Number,
10,
11
Address,
0,
0,
Length,
16,
16,
Scan_Interval
1.0s
1.0s
Map_Descriptors
Map_Descriptor_Name,
CMD_DI_01,
CMD_DO_01,
Data_Array_Name,
DA_DI_01,
DA_DO_01,
Data_Array_Offset,
0,
0,
Function,
RDBC,
RDBC,
Node_Name,
PLC_01,
PLC_01,
File_Type,
B,
B
File_Number,
12,
13,
Address,
0,
0,
Length,
16,
16,
Scan_Interval
1.0s
1.0s
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8704-07_AB-CSP Manual
5.
Page 10 of 15
Configuring the FieldServer as an AB_CSP Server
5.1.
Server Side Connection Descriptors
Section Title
Connections
Column Title
Function
Specify which port the device
is connected to the
FieldServer
Specify protocol used
Adapter
Protocol
Virtual IP address of
FieldServer
IP_Address optional
Legal Values
N1
AB_CSP
Must be on the same
subnet as the client or
gateway
Example
//
Server Side Connections
Connections
Adapter,
N1,
5.2.
Protocol,
AB_CSP,
IP_address
192.168.2.1
Server Side Node Descriptors
Section Title
Nodes
Column Title
Node_Name
Node_ID
Protocol
PLC_Type
Function
Provide name for node
Legal Values
Up to 32 alphanumeric
characters
Node ID of physical server
1-255
node
Specify protocol used
AB_CSP
Specify PLC
PLC3, PLC5, SLC5
Communications type.
Example
//
Server Side Nodes
Nodes
Node_Name,
ABE_Srv_11,
Node_ID,
11,
Protocol,
AB_CSP,
PLC_Type
SLC5
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8704-07_AB-CSP Manual
5.3.
Page 11 of 15
Server Side Map Descriptors
5.3.1.
FieldServer Related Map Descriptor Parameters
Column Title
Map_Descriptor_Name
Data_Array_Name
Data_Array_Offset
Function
5.3.2.
Function
Name of this Map
Descriptor
Name of Data Array
where data is to be
stored in the
FieldServer
Starting location in Data
Array
Function of Client Map
Descriptor
Legal Values
Up to 32 alphanumeric
characters
One of the Data Array
names from “Data Array”
section above
0 to maximum specified in
“Data Array” section above
Server
Driver Related Map Descriptor Parameters
Column Title
Node_Name
File_Type
File_Number
Address
Data_Array_Low_Scale*
Data_Array_High_Scale*
Node_Low_Scale*
Node_High_Scale*
Function
Name of Node to fetch
data from
File type in PLC
File number in PLC
Starting address of read
block
Scaling zero in Data Array
Scaling max in Data Array
Scaling zero in Connected
Node
Scaling max in Connected
Node
Legal Values
One of the node names
specified in “Server Side
Nodes” above
N, B, F, I, O, S
0-255
0 - 255
-32767 to 32767, 0
-32767 to 32767, 100
-32767 to 32767, 0
-32767 to 32767, 100
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8704-07_AB-CSP Manual
5.3.3.
Page 12 of 15
Map Descriptor Example
// Client Side Map descriptors
Map_Descriptors
Map_Descriptor_Name,
SMD_AI_01,
SMD_AO_01,
Data_Array_Name,
DA_AI_01,
DA_AO_01,
Data_Array_Offset,
0,
0,
Function,
Server,
Server,
Node_Name,
ABE_Srv_11,
ABE_Srv_11,
File_Type,
N,
N,
File_Number,
10,
11,
Address,
0,
0,
Length,
16,
16,
Map_Descriptors
Map_Descriptor_Name,
SMD_DI_01,
SMD_DO_01,
Data_Array_Name,
DA_DI_01,
DA_DO_01,
Data_Array_Offset,
0,
0,
Function,
Server,
Server,
Node_Name,
ABE_Srv_11,
ABE_Srv_11,
File_Type,
B,
B,
File_Number,
12,
13,
Address,
0,
0,
Length
16
16
Data_Array_Low_Scale,
0,
0,
Data_Array_High_Scale,
100,
100,
Node_Low_Scale,
0,
0,
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Node_High_Scale
100
100
FS-8704-07_AB-CSP Manual
Page 13 of 15
Appendix A. Troubleshooting
Appendix A.1. Continuous Map Descriptors
RS View has been known to crash if it tries to read a server mapping that is discontinuous.
e.g.
Server map 1: N21: 0-31
Server map 2: N21: 32-100
This will crash RS view as the AB_CSP will attempt to map N21: 0-100
If set up as
Server Map 1: N21: 0-100, no problems are experienced
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8704-07_AB-CSP Manual
Page 14 of 15
Appendix B. Command Support
The following commands are supported by the FieldServer for the various PLC types:
PLC_Type
PLC3
PLC5
File_type
FNC
Read
FNC
Write
N
F
B
N
F
B
1
1
1
1
1
1
0
0
2
0
67
26
N
A2
F
A2
B
A2
Range Write
Range Write
Bit Write
Range Write
Typed Write
Read Modify Write
Protected Typed
Logical Write
Protected Typed
Logical Write
Protected Typed
Logical Write
I
A2
O
A2
S
A2
Range Read
Range Read
Range Read
Range Read
Range Read
Range Read
Protected Typed
Logical Read
Protected Typed
Logical Read
Protected Typed
Logical Read
Protected Typed
Logical Read
Protected Typed
Logical Read
Protected Typed
Logical Read
SLC5
AA
AA
AB
Typical
Command
N7: 3, L5
F12: 3, L5
B3/4: 5, l5
N7: 3 , L5
F12: 3, L5
B3/4: 5, L5
N7: 3, L5
B3/4: 5, L7
B3/4: 5, L8
-
-
I: 13, L5
-
-
O: 13, L5
52: 3, L5
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
FS-8704-07_AB-CSP Manual
Page 15 of 15
Appendix C. Revision History
Date
Resp Format
2/3/04
MF
MF
Driver
Ver.
1.00
5/6/04
Meg
Meg
1.00
6/14/04
JD
12/27/04 Meg
1.00
Meg
1.00
Doc.
Comment
Rev.
1
Formatting updated. Revision table added.
Added connection diagram. Converted final
2
chapters to appendices. Removed nonsense
text.
3
Releasing
Changed Appendix numbering to letters and
added borders and shading. Corrected example
4
table formatting. Removed some commas in
example.
Created Troubleshooting section.
DUR0522.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com