Gallagher Cabinets
Gallagher
Cabinets
Gallagher Cabinets are secure enclosures for the Gallagher Controllers 6000, 3000 and
5000GL, and Gallagher GBUS and LOCAL BUS I/O Devices.
There are three housing options for the modular Gallagher printed circuit boards (PCBs).
The sizes of the individual PCBs vary and are designed to be proportional to the footprint of
the cabinets.
1. Gallagher Cabinet
Manufactured from a stong polycarbonate/ABS plastic alloy, the
Gallagher Cabinet has a UL94 flame rating of HB. It provides one
footprint for Gallagher Controllers and LOCAL BUS I/O PCBs. When
a PCB is installed, optical tamper protection is provided for both the
front and the rear.
One Cabinet houses any one of the following options:
• 1x Gallagher Controller
(6000, 3000 or 5000GL)
• 2x Gallagher Universal
Reader Interfaces
• 1x Gallagher 4R or 8R Module
• 2x Gallagher Strike
Controllers
• 1x Gallagher I/O Interface
• 1x Gallagher Relay Interface
• 1x Gallagher Reader I/O
Interface
• 1x Gallagher High Density I/O
Interface. A second Gallagher
High Density I/O Interface can
be installed in a single cabinet
using standoffs.
2. Gallagher GBUS I/O Accessory Cabinet
A variation of the Gallagher Cabinet, the Gallagher GBUS I/O
Accessory Cabinet is a secure enclosure providing one footprint
for Gallagher GBUS I/O devices. This cabinet is supplied with a
mounting plate and tamper board.
The input/output expansion boards are modular, designed to be
mounted on the mounting plate in the following combinations:
• Up to 4x Gallagher 8-Input Expansion or Gallagher GBUS
Universal Reader Interfaces, or
• Up to 2x Gallagher I/O Expansion Interfaces, or
• 1x Gallagher I/O Expansion and up to 2x Gallagher 8-Input
Expansion or Gallagher GBUS Universal Reader Interfaces
security.gallagher.co
3. Gallagher Dual Cabinet
The Gallagher Dual Cabinet is a secure steel enclosure
accommodating two footprints, doubling the housing capacity for
any combination of Gallagher PCBs. When the PCB is installed,
optical tamper protection is provided for both the front and rear of
the Cabinet. The Cabinet is also available with an optional 8 Amp
power supply which has visible indicators for ‘low mains’ and ‘low
battery’ power monitoring. A separate mounting plate and tamper
board is available to enable Gallagher GBUS I/O Devices (excluding
the Gallagher High Density I/O Interface) to be fitted with optical
tamper protection.
All devices must be mounted in the Cabinets following the
installation instructions to comply with international emission
standards such as C-Tick, CE and FCC.
Gallagher Controller Sub-Plate
The Gallagher Controller Sub-Plate is designed to be mounted over a
Gallagher Controller 5000GL to allow either of the following to be
installed in the same footprint:
• 1x Gallagher I/O Expansion Interface
• 2x Gallagher 8-Input Expansion Interfaces.
It can also be installed over a Gallagher
Controller 3000 where there is no Gallagher Dialler.
GALLAGHER CABINET AND GALLAGHER GBUS I/O ACCESSORY CABINETS
Housing (Provides 1 footprint)
JANUARY 2013
Height x Width x Depth
280 mm x 280 mm x 94 mm
Weight
1.9 kg
Temperature Range
-10° to +55° C
Humidity
95% non-condensing
Protection Rating
IP44
Fire Resistance
Flame rating of plastic used in Cabinet
UL94/VO
Compliance Standards
Compliance with other international standards will be proven as required. Please
contact Gallagher for the latest list of approvals. All Gallagher products must be
installed in accordance with the Installation instructions to
comply with international standards.C-Tick, CE
Environmental Data
GALLAGHER DUAL CABINET
Housing (Provides 1 footprint)
Height x Width x Depth
620 mm x 372 mm x 150 mm
Weight
6.8 kg
Material
Aprox 1mm thick steel
Humidity
90% non-condensing
GALLAGHER POWER SUPPLY UNIT
Construction
Mean Well AD-155A PSU with customized monitoring board and isolated auxiliary power output. Please see the Dual
Cabinet and Power Supply Installation Note for full specifications.
Input Voltage
Output Voltage
Current Range
100 V AC - 240 V AC
Primary power output
13.8 V DC
Auxiliary isolated power output
13.5 V DC
Total output current: 8A (10A with cooling fan - fan not included)
Primary output current range: 0~8A (including max. 0.5A battery output)
Auxiliary isolated output current range
0 ~ 1 A*
*Total current output (primary + auxiliary outputs) may be configured to a maximum of 8A
Working Temperature
-10° to +50° C
Standards Compliance
EN55022 (EMC Standard)
EN60950 (Safety)
Built in Protection
Short circuit/Over load/Over voltage protection
Battery low and polarity protection
(Mains power and low battery monitoring via visual LED indicators
and Gallagher Command Centre alarms)
GALLAGHER WORLD HEADQUARTERS
Kahikatea Drive, Hamilton 3206
Private Bag 3026, Hamilton 3240
New Zealand
TEL: +64 7 838 9800
EMAIL: [email protected]
security.gallagher.co
REGIONAL OFFICES
New Zealand.................................... +64 7 838 9800
Americas....................................... +1 888 430 0770
Asia................................................ +852 2910 7912
Australia....................................... +61 2 9412 4477
India............................................ +91 80 2661 1590
Middle East........................................+9615 808728
South Africa................................. +27 11 974 4740
United Kingdom / Europe........... +44 2476 64 1234
Disclaimer: System configuration, network capacities and the
volume of system activity affect performance. Please contact
Gallagher for advice. In accordance with the Gallagher policy of
continuing development, design and specifications are subject
to change without notice. Gallagher Group Limited is an ISO
9001:2008 Certified Supplier. Copyright © Gallagher Group
Limited 2012. All rights reserved.
3E1338 – 02/13
Monitoring
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement