TCS Series Current Sensor Features:

TCS Series Current Sensor Features:
Current Sensor
TCS Series
The TCS Series is a low cost method of go/no go
current detection. It includes a solid-state output to
sink or source current when connected directly to
a standard PLC digital input module . Its normally
open or normally closed output can also be used
to control relays, lamps, valves, and small heaters
rated up to 1A steady, 10A inrush. The TCS is selfpowered (no external power required to operate
the unit) and available with an adjustable actuation
range of 2 - 20A or factory fixed actuation points
from 2 - 45A.
For more information see:
Appendix B, page 166, Figure 21 for dimensional drawing.
Appendix C, page 169, Figure 19 for connection diagram.
Features:
• Direct connection to a PLC digital input
module
• 3 to 50VDC, 24 to 240VAC
• 1A steady - 10A inrush
• Actuation Points –
2 - 45A (fixed units)
2 - 20A (adjustable units)
• NO or NC solid-state output
• Complete isolation between sensed current
& control circuit
Approvals:
Auxiliary Products:
Operation
Normally Open: When a current equal to or greater than the actuate current is passed through the toroidal
sensor, the output closes. When the current is reduced to 95% of the actuate current or less, the output opens.
Normally Closed: When the current through the toroid is equal to or greater than the actuate current, the output
opens. When the current is reduced below 95% of the actuate current, the output closes. To increase sensitivity,
multiple turns may be made through the TCS’s toroidal sensor. The trip point range is divided by the number of
turns through the toroidal sensor to create a new range. When using an external CT, select a 2VA, 0-20A output
CT rated for the current to be monitored. Select TCS adjustment range 0. Pass one secondary wire lead through
the TCS’ toroid and connect the secondary leads together.
• Female q uick connect:
P/N: P1015-64 (AWG 14/16)
• Quick connect to screw adaptor:
P/N: P1015-18
• Mounting bracket: P/N: P1023-6
• DIN rail: P/N: C103PM (Al)
• DIN rail adaptor: P/N: P1023-20
Available Models:
TCSG2A
TCSGAA
TCSGAB
TCSH2A
TCSH2B
If desired part number is not listed, please call us to
see if it is technically possible to build .
L = Load
V = Voltage
PS = Power Supply
PLC = PLC Digital Input Module
R = Reset
TP = Trip Point
OC = Monitored Current
NO = Normally Open Output
NC = Normally Closed Output
Order Table:
TCS
X
Output Voltage
─G - 3-50VDC
─H - 24-240VAC
TCSH3A
TCSH4A
TCSHAA
TCSHAB
X
Actuate Current
─A - 2-20A adjustable
─Fixed - Specify from
2-45A in 1A increments
X
Output Form
─A - Normally Open
─B - Normally Closed
Specifications
Sensor
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Toroid, through hole wiring, alternating current,
monitored wire must be properly insulated
Current to Actuate . . . . . . . . . . . . . . . . . . . . . . . . . Adjustable: - 2 - 20A, guaranteed range
Fixed: - 2 - 45A, +0/-20%
Reset Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≅ 95% of the actuate current
Maximum Allowable Current . . . . . . . . . . . . . . . Steady - 50A turns
Inrush - 300A turns for 10s
Actuate Current vs. Temp. & Voltage . . . . . . . . ≤ ±5%
Response Times . . . . . . . . . . . . . . . . . . . . . . . . . . . Overcurrent - ≤ 200ms
Undercurrent - ≤ 1s
Burden . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 0.5VA
Output
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Solid state
Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NO or NC
Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1A steady, 10A inrush
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AC - 24 to 240VAC +10/-20%
DC - 3 to 50VDC
Voltage Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AC NO & NC - ≅ 2.5V
DC NO & NC - ≅ 1.2V
124
Protection
Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Encapsulated
Dielectric Breakdown . . . . . . . . . . . . . . . . . . . . . . ≥ 2000V RMS terminals to mounting surface
Insulation Resistance . . . . . . . . . . . . . . . . . . . . . . . ≥ 100 MΩ
Mechanical
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Surface mount with one #10 (M5 x 0.8)
screw
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 x 2 x 1.75 in. (50.8 x 50.8 x 44.5 mm)
Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.25 in. (6.35 mm) male quick connect
terminals (2)
Sensor Hole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.36 in. (9.14 mm) for up to #4 AWG
2
(21 .1 mm ) THHN wire
Environmental
Operating / Storage Temperature . . . . . . . . . . . -20° to 60°C / -40° to 85°C
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95% relative, non-condensing
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≅ 2.6 oz (74 g)