TDUB Series Timer - Delay-on-Break Features:

TDUB Series Timer - Delay-on-Break Features:
Timer - Delay-on-Break
Connection:
L1
N/L2
TDUB Series
The TDUB Series combines digital timing circuitry
with universal voltage operation. Voltages of
24 to 240VAC and 12 to 24VDC are available in
three ranges. The TDUB Series offers DIP switch
selectable time delays ranging from 0.1 seconds to
102.3 minutes in three ranges. Its 1A rated output,
ability to operate on multiple voltages, and wide
range of switch selectable time delays make the
TDUB Series an excellent choice for process control
systems and OEM equipment .
Features:
Operation (Delay-on-Break):
Input voltage must be applied before and during timing.
Upon closure of the initiate switch, the output energizes.
The time delay begins when the initiate switch is opened
(trailing edge triggered). The output remains energized
during timing. At the end of the time delay, the output
de-energizes. The output will energize if the initiate switch
is closed when input voltage is applied.
Reset: Reclosing the initiate switch during timing resets
the time delay. Loss of input voltage resets the time delay
and output .
Auxiliary Products:
For more information see:
Appendix A, pages 156-164 for function descriptions
and diagrams .
Appendix B, page 165, Figure 1 for dimensional drawing.
• Switch selectable time setting
• 0.1s - 102.3m in 3 ranges
• ± 0.5% repeat accuracy
• ± 2% setting accuracy
• 1A, solid-state output
• Wide voltage ranges
Approvals:
• Female quick connect:
P/N: P1015-13 (AWG 10/12)
P/N: P1015-64 (AWG 14/16)
P/N: P1015-14 (AWG 18/22)
• Quick connect t o s crew ad aptor:
P/N: P1015-18
• DIN rail: P/N: C103PM
• DIN rail adaptor: P/N: 1023-20
Available Models:
TDUB3000A
TDUB3002A
TDUBH3002A
TDUBL3002A
If desired part number is not listed, please call us to
see if it is technically possible to build .
UTL = Optional Untimed Load
S1 = Initiate Switch
L = Timed Load
Add the value of switches in the ON
position for the total time delay.
Order Table:
Input Voltage Range
24 to 120VAC
100 to 240VAC
12 to 24VDC
24 to 120VAC
100 to 240VAC
12 to 24VDC
24 to 120VAC
100 to 240VAC
12 to 24VDC
Time Range
0.1 - 102.3s
0.1 - 102.3s
0.1 - 102.3s
1 - 1023s
1 - 1023s
1 - 1023s
0.1 - 102.3m
0.1 - 102.3m
0.1 - 102.3m
Part Number
TDUBL3000A
TDUBL3001A
TDUBL3002A
TDUB3000A
TDUB3001A
TDUB3002A
TDUBH3000A
TDUBH3001A
TDUBH3002A
Specifications
Time Delay
Range* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.1 - 102.3s in 0.1s increments
1 - 1023s in 1s increments
0.1 - 102.3m in 0.1m increments
Repeat Accuracy . . . . . . . . . . . . . . . . . . . . . . . ±0.5% or 20ms, whichever is greater
Setting Accuracy . . . . . . . . . . . . . . . . . . . . . . . ≤ ±2% or 20ms, whichever is greater
Reset Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 150ms
Initiate Time . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 20ms
Time Delay vs Temp. & Voltage . . . . . . . . . ≤ ±5%
Input
Voltage / Tolerance . . . . . . . . . . . . . . . . . . . . 24 to 240VAC, 12 to 24VDC /±20%
AC Line Frequency / DC Ripple . . . . . . . . . 50/60 Hz / ≤ 10%
Power Consumption . . . . . . . . . . . . . . . . . . . AC ≤ 2VA; DC ≤ 1W
Output
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Solid state
Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NO, closed before and during timing
Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1A steady state, 10A inrush at 60°C
Voltage Drop . . . . . . . . . . . . . . . . . . . . . . . . . . AC ≅ 2.5V @ 1A; DC ≅ 1V @ 1A
www.ssac.com • 800-843-8848 • fax: 605-348-5685
Off State Leakage Current . . . . . . . . . . . . . .
Protection
Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dielectric Breakdown . . . . . . . . . . . . . . . . . .
Insulation Resistance . . . . . . . . . . . . . . . . . . .
Polarity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .
Termination . . . . . . . . . . . . . . . . . . . . . . . . . . .
Environmental
Operating / Storage Temperature . . . . . . .
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC ≅ 5mA @ 230VAC; DC ≅ 1mA
Encapsulated
≥ 2000V RMS terminals to mounting surface
≥ 100 MΩ
DC units are reverse polarity protected
Surface mount with one #10 (M5 x 0.8) screw
2 x 2 x 1.21 in (50.8 x 50.8 x 30.7 mm)
0.25 in. (6.35 mm) male quick connect terminals
-40° to 60°C / -40° to 85°C
95% relative, non-condensing
≅ 2.4 oz (68 g)
*For CE approved applications, power must be removed from the unit when a switch
position is changed.
47
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement