TH1 Series Timer - Delay-on-Make Features:

TH1 Series Timer - Delay-on-Make Features:
Timer - Delay-on-Make
TH1 Series
The TH1 Series is a solid-state relay and timer
combined into one compact, easy-to-use control.
This highly reliable device eliminates the need
for a separate solid-state relay. When mounted to
a metal surface, it can switch load currents up to
20A steady state, and 200A inrush.
Operation (Delay-on-Make):
Upon application of input voltage, the time delay begins.
The output is de-energized before and during the time
delay. At the end of the time delay, the output energizes
and remains energized until input voltage is removed.
Reset: Removing input voltage resets the time delay
and output .
For more information see:
Appendix A, pages 156-164 for function descriptions
and diagrams .
Appendix B, page 165, Figure 4 for dimensional drawing.
Connection:
L1
N/L2
Features:
• High current load capacity up to 20A with
200A inrush
• Solid-state switching - no contact wear or
arcing
• Encapsulated
• Fixed or adjustable time delays from 0.1 - 600s
• ± 2% repeat accuracy
• ± 5% factory calibration
• Metallized mounting surface for heat transfer
Approvals:
Auxiliary Products:
• External ad just potentiometer:
P/N: P1004-95
P/N: P1004-95-X
• Female quick connect:
P/N: P1015-13 (AWG 10/12)
P/N: P1015-64 (AWG 14/16)
• Quick connect t o s crew ad aptor:
P/N: P1015-18
• Versa-knob: P/N: P0700-7
Available Models:
TH1A421
TH1B633
TH1C415
TH1C621
If desired part number is not listed, please call us to
see if it is technically possible to build .
S1 = Optional Low Current Initiate Switch
RT is used when external adjustment is ordered.
Order Table:
TH1
X
Output Rating
─A - 6A
─B - 10A
─C - 20A
X
Input Voltage
─2 - 24VAC
─4 - 120VAC
─6 - 230VAC
X
Adjustment
─1 - Fixed
─2 - External adjust
─3 - Onboard adjust
X
Time Delay*
─1 - 0.1 - 3s
─2 - 0.5 - 60s
─3 - 2 - 180s
─4 - 5 - 600s *If fixed delay is selected, insert
delay (0 .1 - 600) in secs .
Specifications
Time Delay
Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repeat Accuracy . . . . . . . . . . . . . . . . . . . . . . . .
Tolerance (Factory Calibration) . . . . . . . . . . . .
Time Delay vs Temp. & Voltage . . . . . . . . . . .
Recycle Time . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tolerance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Line Frequency . . . . . . . . . . . . . . . . . . . . . .
Power Consumption . . . . . . . . . . . . . . . . . . . . .
Output
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maximum Load Currents
Output
A
B
C
0.1 - 600s in 4 adjustable ranges or fixed
±2% or 20ms, whichever is greater
≤ ± 5%
≤ ±10%
≤ 150ms
24, 120, or 230VAC
±15%
50/60 Hz
≤ 2VA
Solid state
NO, open during timing
Steady State
6A
10A
20A
www.ssac.com • 800-843-8848 • fax: 605-348-5685
Inrush**
60A
100A
200A
Minimum Load Current . . . . . . . . . . . . . . . . . .
Voltage Drop . . . . . . . . . . . . . . . . . . . . . . . . . . .
OFF State Leakage Current . . . . . . . . . . . . . . .
Protection
Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dielectric Breakdown . . . . . . . . . . . . . . . . . . . .
Insulation Resistance . . . . . . . . . . . . . . . . . . . . .
Mechanical
Mounting ** . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Environmental
Operating / Storage Temperature . . . . . . . . .
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
100mA
≅ 2.5V at rated current
≅ 5mA @ 230VAC
Encapsulated
≥ 2000V RMS terminals to mounting surface
≥ 100 MΩ
Surface mount with one #10 (M5 x 0.8) screw
2 x 2 x 1.51 in. (50.8 x 50.8 x 38.4 mm)
0.25 in. (6.35 mm) male quick connect terminals
-20° to 60°C / -40° to 85°C
95% relative, non-condensing
≅ 3.9 oz (111 g)
**Must be bolted to a metal surface using the included heat sink compound. The maximum
mounting surface temperature is 90°C. Inrush: Non-repetitive for 16ms.