THD1 Series Timer - Delay-on-Make Features:

THD1 Series Timer - Delay-on-Make Features:
Timer - Delay-on-Make
THD1 Series
The THD1 Series combines accurate timing
circuitry with high power solid-state switching.
It can switch motors, lamps, and heaters directly
without a contactor. You can reduce labor,
component cost, and increase reliability with these
small, easy-to-use, Digi-Power timers.
Operation (Delay-on-Make):
Upon application of input voltage, the time delay begins.
The output is de-energized before and during the time
delay. At the end of the time delay, the output energizes
and remains energized until input voltage is removed.
Reset: Removing input voltage resets the time delay
and output .
For more information see:
Appendix A, pages 156-164 for function descriptions
and diagrams .
Appendix B, page 165, Figure 4 for dimensional drawing.
Connection:
L1
External Resistance vs . Time Delay:
N/L2
Features:
• High load currents up to 20A, 200A inrush
• Fixed or adjustable delays from 0.1s - 1000m
• ±0.5% repeat accuracy
• ±1% factory calibration
• 24, 120, or 230VAC
• Metallized mounting surface for heat transfer
• Totally solid state & encapsulated
Approvals:
Auxiliary Products:
• External ad just potentiometer:
P/N: P1004-95
P/N: P1004-95-X
• Female quick connect:
P/N: P1015-13 (AWG 10/12)
P/N: P1015-64 (AWG 14/16)
• Quick connect t o s crew ad aptor:
P/N: P1015-18
• Versa-knob: P/N: P0700-7
Available Models:
THD1B410.5S
THD1C231
THD1C232
THD1C233
THD1C234
THD1C235
THD1C415M
THD1C431
THD1C432
THD1C433
THD1C434
THD1C435
THD1C6110S
If desired part number is not listed, please call us to
see if it is technically possible to build .
S1 = Optional Low Current Initiate
Switch
RT is used when external adjustment
is ordered .
Order Table:
THD1
X
Output Rating
─A - 6A
─B - 10A
─C - 20A
X
Input Voltage
─2 - 24VAC
─4 - 120VAC
─6 - 230VAC
X
Adjustment
─1 - Fixed
─2 - External adjust
─3 - Onboard adjust
X
Time Delay*
─0 - 0.1 - 10s
─1 - 1 - 100s
─2 - 10 - 1000s
─3 - 0.1 - 10m
─4 - 1 - 100m
─5 - 10 - 1000m
*If fixed delay is selected, insert
delay (0 .1 - 1000) followed by (S) sec .
or (M) min .
Specifications
Time Delay
Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repeat Accuracy . . . . . . . . . . . . . . . . . . . . . . . . .
Tolerance (Factory Calibration) . . . . . . . . . . . . .
Recycle Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time Delay vs Temp. & Voltage . . . . . . . . . . . .
Input
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tolerance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Line Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Consumption . . . . . . . . . . . . . . . . . . . . . .
Output
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maximum Load Current
Output
A
B
C
32
0.1s - 1000m in 6 adjustable ranges or fixed
±0.5% or 20ms, whichever is greater
≤ ±1%
≤ 150ms
≤ ±2%
24, 120, or 230VAC
±20%
50/60 Hz
≤ 2VA
Solid state
NO, open during timing
Steady State
Inrush**
6A
60A
10A
100A
20A
200A
Minimum Load Current . . . . . . . . . . . . . . . . . . .
Voltage Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OFF State Leakage Current . . . . . . . . . . . . . . . .
Protection
Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dielectric Breakdown . . . . . . . . . . . . . . . . . . . . .
Insulation Resistance . . . . . . . . . . . . . . . . . . . . . .
Mechanical
Mounting ** . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Environmental
Operating / Storage Temperature . . . . . . . . . .
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
100mA
≅ 2.5V @ rated current
≅ 5mA @ 230VAC
Encapsulated
≥ 2000V RMS terminals to mounting surface
≥ 100 MΩ
Surface mount with one #10 (M5 x 0.8) screw
2 x 2 x 1.51 in. (50.8 x 50.8 x 38.4 mm)
0.25 in. (6.35 mm) male quick connect terminals
-40° to 60°C / -40° to 85°C
95% relative, non-condensing
≅ 3.9 oz (111 g)
**Must be bolted to a metal surface using the included heat sink compound. The maximum
mounting surface temperature is 90°C. Inrush: Non-repetitive for 16ms.
www.ssac.com • 800-843-8848 • fax: 605-348-5685