THD2 Series Timer - Interval Features:

THD2 Series Timer - Interval Features:
Timer - Interval
THD2 Series
The THD2 Series combines accurate timing
circuitry with high power solid-state switching.
It can switch motors, lamps, and heaters directly
without a contactor. You can reduce labor,
component cost, and increase reliability with these
small, easy-to-use, Digi-Power timers.
Operation (Interval):
Upon application of input voltage, the time delay begins.
The output energizes during the time delay. At the end
of the time delay, the output de-energizes and remains
de-energized until input voltage is removed.
Reset: Removing input voltage resets the time delay and
the output.
For more information see:
Appendix A, pages 156-164 for function descriptions
and diagrams .
Appendix B, page 165, Figure 4 for dimensional drawing.
Connection:
L1
N/L2
External Resistance vs . Time Delay:
Features:
• High load currents up to 20A, 200A inrush
• Fixed or adjustable delays from 0.1s - 1000m
• ±0.5% repeat accuracy
• ±1% factory calibration
• 24, 120, or 230VAC
• Metallized mounting surface for heat transfer
• Totally solid state and encapsulated
Approvals:
Auxiliary Products:
• External ad just potentiometer:
P/N: P1004-95
P/N: P1004-95-X
• Female quick connect:
P/N: P1015-13 (AWG 10/12)
P/N: P1015-64 (AWG 14/16)
• Quick connect t o s crew ad aptor:
P/N: P1015-18
• Versa-knob: P/N: P0700-7
Available Models:
THD2B4110M
THD2B41600S
THD2B6110M
THD2C231
THD2C232
THD2C233
THD2C234
THD2C235
S1 = Optional Low Current Initiate Switch
RT is used when external adjustment is ordered.
Order Table:
THD2
X
Output Rating
─A - 6A
─B - 10A
─C - 20A
X
Input Voltage
─2 - 24VAC
─4 - 120VAC
─6 - 230VAC
THD2C423
THD2C430
THD2C431
THD2C432
THD2C433
THD2C434
THD2C435
If desired part number is not listed, please call us to
see if it is technically possible to build .
X
Adjustment
─1 - Fixed
─2 - External adjust
─3 - Onboard adjust
X
Time Delay*
─0 - 0.1 - 10s
─1 - 1 - 100s
─2 - 10 - 1000s
*If fixed delay is selected, insert
─3 - 0.1 - 10m
delay (1 - 1000) followed by (S) secs .
─4 - 1 - 100m
─5 - 10 - 1000m or (M) mins .
Specifications
Time Delay
Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.1s - 1000m in 6 adjustable ranges or fixed
Repeat Accuracy . . . . . . . . . . . . . . . . . . . . . . . .±0.5% or 20ms, whichever is greater
Tolerance (Factory Calibration) . . . . . . . . . . . .≤ ±1%
Reset Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .≤ 150ms
Time Delay vs Temp. & Voltage . . . . . . . . . . .≤ ±2%
Input
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24, 120, or 230VAC
Tolerance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .±20%
AC Line Frequency . . . . . . . . . . . . . . . . . . . . . .50/60 Hz
Output
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Solid state
Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .NO, closed during timing
Maximum Load Current
Output
Steady State
Inrush**
A
6A
60A
B
10A
100A
C
20A
200A
74
Minimum Load Current . . . . . . . . . . . . . . . . . .100mA
Voltage Drop . . . . . . . . . . . . . . . . . . . . . . . . . . .≅ 2.5V at rated current
OFF State Leakage Current . . . . . . . . . . . . . . .≅ 5mA @ 230VAC
Protection
Circuitry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Encapsulated
Dielectric Breakdown . . . . . . . . . . . . . . . . . . . .≥ 2000V RMS terminals to mounting surface
Insulation Resistance . . . . . . . . . . . . . . . . . . . . .≥ 100 MΩ
Mechanical
Mounting ** . . . . . . . . . . . . . . . . . . . . . . . . . . . .Surface mount with one #10 (M5 x 0.8) screw
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 x 2 x 1.51 in. (50.8 x 50.8 x 38.4 mm)
Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.25 in. (6.35 mm) male quick connect terminals
Environmental
Operating / Storage Temperature . . . . . . . . .-40° to 60°C / -40° to 85°C
Humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95% relative, non-condensing
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .≅ 3.9 oz (111 g)
**Must be bolted to a metal surface using the included heat sink compound. The maximum
mounting surface temperature is 90°C. Inrush: Non-repetitive for 16ms.
www.ssac.com • 800-843-8848 • fax: 605-348-5685
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com