TL Series Timer - Lockout Features

TL Series Timer - Lockout Features
Timer - Lockout
TL Series
The TL Series provides protection against short
cycling of a compressor. At the end of each
operation, or whenever power is lost, a lockout
delay is initiated. This lockout delay prevents
restarting of the compressor until the head
pressure has equalized. Compressor relay chatter
due to thermostat bounce is eliminated by use
of optional one second delay-on-make. The TL
Series should not be used with cooling anticipator
resistors or solid-state switches. (See the TA
Series) .
Connection:
L1
Operation (Lockout):
Lockout: On initial closure of S1, the compressor relay
energizes immediately (or after an optional 1 s delay).
When the S1 opens or input voltage is interrupted, the
output opens and remains open for the lockout time delay.
During this lockout time delay period, the compressor
relay cannot be re-energized.
Reset: The lockout time delay cannot be reset. After the
time delay is completed, the unit automatically resets.
N/L2
For more information see:
Appendix A, pages 156-164 for function descriptions
and diagrams .
Appendix B, page 165, Figure 1 for dimensional drawing.
Features
• Ideal for HVAC/R applications
• Lockout delay prevents short cycling of a
compressor
• Optional 1s delay-on-make prevents
contactor chatter
• Totally solid state and encapsulated
• 24VAC to 230VAC in 3 ranges
• Eliminates nuisance service calls due to
blown fuse or tripped breakers
Approvals:
Auxiliary Products:
• Female quick connect:
P/N: P1015-64 (AWG 14/16)
• Mounting bracket: P/N: P1023-6
• Quick connect t o s crew ad aptor:
P/N: P1015-18
• DIN rail: P/N: C103PM (Al)
• DIN rail adaptor: P/N: P1023-20
Available Models:
TL120A5T
TL230A5
TL230A5T
TL24A5
If desired part number is not listed, please call us to
see if it is technically possible to build .
V = Voltage
S1 = Initiate Switch
CR = Compressor or Control Relay
Order Table:
TL
X
Input Voltage
─24A - 24VAC
─120A - 120VAC
─230A - 230VAC
X
Lockout Time
─2 - 2m
─3 - 3m
─5 - 5m
X
Delay-on-Make
─Blank - No delay
─T - 1s
Specifications
Input
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Line Frequency . . . . . . . . . . . . . . . .
Tolerance . . . . . . . . . . . . . . . . . . . . . . . . .
Output
Minimum Load Current . . . . . . . . . . . .
Maximum Load Current . . . . . . . . . . . .
Inrush Current . . . . . . . . . . . . . . . . . . . .
Voltage Drop . . . . . . . . . . . . . . . . . . . . .
Time Delay
Initiate Time . . . . . . . . . . . . . . . . . . . . . .
Lockout Time* . . . . . . . . . . . . . . . . . . . .
Tolerance . . . . . . . . . . . . . . . . . . . . . . . . .
Option . . . . . . . . . . . . . . . . . . . . . . . . . . .
100
24, 120, or 230VAC
50/60 Hz
±20%
≤ 40mA
1A @ 24VAC; 0.5A @ 120 & 230VAC at 60°C
10A at 60°C
24VAC - 2.5V @ 1A
120 & 230VAC - 4.2V @ 0.5A
≅ 8ms
Fixed 2, 3, or 5m
-15% - 35%
1s delay-on-make eliminates contactor chatter
due to thermostat bounce
Protection
Circuitry . . . . . . . . . . . . . . . . . . . . . . . . .
Dielectric Breakdown . . . . . . . . . . . . . .
Insulation Resistance . . . . . . . . . . . . . . .
Mechanical
Mounting . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions . . . . . . . . . . . . . . . . . . . . . . .
Termination . . . . . . . . . . . . . . . . . . . . . .
Environmental
Operating / Storage Temperature . . .
Humidity . . . . . . . . . . . . . . . . . . . . . . . . .
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . .
Encapsulated
≥ 2000V RMS terminals to mounting surface
≥ 100 MΩ
Surface mount with one #10 (M5 x 0.8) screw
2 x 2 x 1.21 in. (50.8 x 50.8 x 30.7 mm)
0.25 in. (6.35 mm) male quick connect terminals
-40° to 70°C / -40° to 85°C
95% relative, non-condensing
≅ 2.4 oz (68 g)
*Power must be applied for at least 15 s to achieve a full lockout delay. Less than 15s will
result in proportionally shorter delay periods.
NOTE: Cooling anticipator resistor or leakage may cause erratic operation. See TA Series
for use with 24VAC systems that include anticipator resistors or use solid-state switches.