TRB Series Timer - Delay-on-Break Features:

TRB Series Timer - Delay-on-Break Features:
Timer - Delay-on-Break
TRB Series
Features:
The TRB Series combines an isolated, 10A
electromechanical relay output with analog timing
circuitry. False trigger of the TRB by a transient is
unlikely because of the complete isolation of the
circuit from the line prior to initiation. The initiate
contact is common to one side of the line and may
be utilized to operate other loads. Installation is
easy due to the TRB’s industry standard 8 or 11-pin
plug-in base wiring.
Connection:
8-pin octal SPDT
• Onboard adjustable time delays
• Fixed or adjustable delays from 0.05 - 600s in
multiple ranges
• ±2% repeat accuracy
• AC and DC operating voltages are available
• Isolated, 10A, SPDT or DPDT output contacts
Approvals:
8-pin models UL listed
when used in combination
with P1011-6 socket only.
Operation (Delay-on-Break):
Input voltage must be applied before and during timing.
Upon closure of the initiate switch, the output relay
energizes. The time delay begins when the initiate switch
is opened (trailing edge triggered). The output remains
energized during timing. At the end of the time delay,
the output de-energizes. The output will energize if the
initiate switch is closed when input voltage is applied.
Reset: Reclosing the initiate switch during timing resets
the time delay. Loss of input voltage resets the time delay
and output .
Auxiliary Products:
• Panel mount kit: P/N: BZ1
• Hold-down c lips (sold i n p airs):
P/N: PSC8 (NDS-8)
P/N: PSC11 (NDS-11)
• Octal 8-pin socket: P/N: NDS-8
• 11-pin socket: P/N: NDS-11
• Octal socket for UL listing: P/N: P1011-6
• External ad just potentiometers:
P/N: P1004-XX
P/N: P1004-XX-X
• Versa-knob: P/N: P0700-7
For more information see:
Appendix A, pages 156-164 for function descriptions
and diagrams .
Appendix B, page 165, Figure 9 for dimensional drawing.
L1
N/L2
11-pin SPDT
L1
N/L2
11-pin DPDT
L1
N/L2
Order Table:
TRB
External RT P/N Selection Table
Value
Part Number
1M ohm
1.5M ohm
2M ohm
3M ohm
5M ohm
1M ohm
1.5M ohm
2M ohm
3M ohm
5M ohm
P1004-16
P1004-15
P1004-14
P1004-12
P1004-13
P1004-16-X
P1004-15-X
P1004-14-X
P1004-12-X
P1004-13-X
TRB120A3X600
TRB24A1Y0.2
TRB24A4Y60
TRB24D10Y10
If desired part number is not listed, please call us to
see if it is technically possible to build .
S1 = Initiate Switch
Relay contacts are isolated .
RT is used when external adjustment is ordered.
X
Input Voltage
─24A - 24VAC
─24D - 24VDC/28VDC
─110D - 110VDC
─120A - 120VAC
─230A - 230VAC
X
Adjustment and Output Form
─1 - Fixed, Octal, SPDT
(AC Volts only)
─2 - Onboard Adjust, Octal, SPDT
(AC Volts only)
─3 - Lock Shaft Adjust, Octal, SPDT
(AC Volts only)
─4 - Onboard adjust, 11-pin, DPDT
─7 - Ext. Adjust, 11-pin, SPDT
without potentiometer
─10 - Fixed, 11-pin, DPDT
X
Time Tolerance
─X - ±20%
─Y - ±10%
─Z - ±5%
*If fixed delay is selected, insert
delay (0.05 - 600) in seconds .
Specifications
Time Delay
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog circuitry
Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50ms - 10m in 15 adjustable ranges or fixed
Repeat Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . ±2% or 20ms, whichever is greater
Fixed Time Tolerance & Setting Accuracy . . . . ±5, 10, or 20%
Initiate Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 70ms
Reset Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 75ms
Recycle Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 250ms
Time Delay vs Temp. & Voltage . . . . . . . . . . . . ≤±10%
Input
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24/28 or 110VDC; 24, 120, or 230VAC
(DC voltages on DPDT output models only)
Tolerance
24VDC/AC . . . . . . . . -15% - 20%
110 to 230VAC/DC . . . . . . . . -20% - 10%
AC Line Frequency . . . . . . . . . . . . . . . . . . . . . . . 50/60 Hz
Power Consumption . . . . . . . . . . . . . . . . . . . . . . ≤ 3.25W
42
Available Models:
TRB120A1Y240
TRB120A2Y1
TRB120A2Y3
TRB120A2Y30
X
Time Delay*
(seconds)
─1 - 0.05 - 1
─2 - 0.05 - 2
─3 - 0.05 - 3
─5 - 0.1 - 5
─10 - 0.1 - 10
─30 - 1 - 30
─60 - 1 - 60
─120 - 2 - 120
─180 - 2 - 180
─240 - 7 - 240
─300 - 7 - 300
─360 - 7 - 360
─420 - 7 - 420
─480 - 7 - 480
─600 - 7 - 600
Output
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electromechanical relay
Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Isolated SPDT or DPDT
Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10A resistive @ 120/240VAC & 28VDC;
1/3 hp @ 120/240VAC
Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mechanical - 1 x 107; Electrical - 1 x 106
Protection
Insulation Resistance . . . . . . . . . . . . . . . . . . . . . . ≥ 100 MΩ
Isolation Voltage . . . . . . . . . . . . . . . . . . . . . . . . . ≥ 1500V RMS between input to output
Polarity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DC units are reverse polarity protected
Mechanical
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Plug-in socket
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3.62 x 2.39 x 1.78 in (91.6 x 60.7 x 45.2 mm)
Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Octal 8-pin plug-in or 11-pin plug-in
Environmental
Operating / Storage Temperature . . . . . . . . . . -20° to 65°C / -30° to 85°C
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≅ 6 oz (170 g)
www.ssac.com • 800-843-8848 • fax: 605-348-5685