KitchenAid 4KUIS185S Ice Maker User Manual | Manualzz
I
II
CHANGING THE BIN DOOR AND LOWER PANEL
The storage bin door and lower panel are designed to
accept an optional decorative wood panel of your
choice.
The wood panel should be no more than VI inch (6 mm)
thick. Cut it to the same size as the production metal
panel. See Figure 1.
To change the bin door panel:
1. Open the bin door.
DOOR
BIN
11’Y.”
LOWER
PANEL
ll’y,e”
c I-
(285 mm)
(303 mm)
2. Remove the two screws on top of the door which hold
the handle.
WOOD
PANEL
DIMENSIONS
(43 mm)
A
FIGURE 1
3. Remove the handle.
4. Slide the metal panels out.
5. Break off the ribs on the door insulation to allow for
the wood thickness. See Figure 2.
6. Slide the wood panel into the door frame.
7. Replace handle and screws.
To change the lower panel:
1. Remove the two screws at the bottom that hold the
lower panel assembly to the ice maker.
2. Remove the two screws on the top of the panel
assembly.
REMOVE ALL DOOR INSULATION
RIBS TO ACCEPT WOOD PANEL
THICKNESS
FIGURE 2
3. Slide the metal panels and spacers out.
4. Slide the wood panel into the door frame.
5. Replace the top of the panel assembly.
NOTE: Make sure the galvanized panel is replaced in
back of the panel assembly.
THERMOSTAT
CALIBRATIONS
If ice maker is installed above two thousand feet of
altitude, the bin and evaporator thermostats must be
adjusted to a warmer setting. Disconnect electricity,
remove thermostat and follow the directions for turning
the altitude adjustment screw as shown in the label on
each thermostat.
SHIPBOARD
OPERATION
When this ice cube maker is installed aboard a ship,
it will be necessary to purchase and install a water
deflector. This deflector hangs between the lower edge
of the evaporator and the cutter grid. It keeps the water
flowing over the evaporator from spilling into the storage
bin area. Order the necessary parts from your local ice
maker dealer.
2
GENERAL INFORMATION
2 Either a gravity drain system or a sump pump to lift
the water to an existing drain.
3 An electrical branch circuit of 115 Volt, 60 Hz, 1
phase, with a 15 Amp delayed action fuse or circuit
breaker.
. UNPACK
l
INTERIOR
PACKING
LOCATE UNIT
THIS UNIT MUST BE
INSTALLED IN AN
AREA PROTECTED FROM
THE ELEMENTS, SUCH
AS WIND, RAIN, WATER
SPRAY OR DRIP.
OPEN BOTTOM FLAPS
1 BEST
\ RANGE
(21.1%)
70°F
H
CR 66 A
FIGURE 4
FIGURE 3
(32.2%)
90° F
1 Lay carton on rear face and break open bottom flaps.
1 Place unit so the front side will be completely
2 Set carton upright with all four flaps outward. See
Figure 3.
3 Lift carton up and off of machine.
4 Remove all tape and packaging material from the
outside and inside of the cabinet. See Figure 4.
5 Remove the front grill; take out the screws securing
the grill at the bottom and lift it free of cabinet
6 Turn the fan by hand to make certain it moves freely
7 Loosen thumb screws holding cutter grid and water
pan to “thumb tight”
unobstructed to provide proper air flow.
2 Area should be well ventilated with temperature above
55’JF, 12.6% and below llOOF, 43.4OC. Best results
are obtained between 7OOF,21 .lOC and gOOF,32.2OC.
3 Provision for electricity, water and drain connections
should be determined.
4 Tne uni? may be closed in on the iop and three sides,
bu? the front MUST BE unobstructed for air circularion and proper operation. Installation shoti~d be
such that the cabinet can be moved iorward foi :srvicing, if necesczry.
. LEVEL UMZT
. UTILITIES
1 After placing unit in position, check to make certain
ELECTRICITY
OBSERVE LOCAL CODES
Each installation
the unit is level side to side and front to back.
2 Accurate leveling is essential for proper operation.
3 Unit should be shimmed so that it is solid as well
as level. The shims should be of hard permanen?
type material such as masonite.
4 Compliance with National Sanitation Foundation
standards require that this type of product be
sealed to the floor at the bottom rail in order to
prevent contamination from spills or the entrance of
vermin. Therefore, we recommend that when installing this product you seal it to the floor in accordance with those standards. A silicone-type sealer
is recommended.
is unique but will require:
1 A cold water inlet of 114” (6 mm) OD soft copper
tubing and a shut-off valve.
3
FOR THE PLUMBER
. CONNECT TO WATER
. CONDENSATE PUMP
(observe local codes)
1 When drain connection
below the level of the unit
is not available a condensate pump may be used to
lift the water to an available drain.
1 Use l/4” (6 mm) OD soft copper tubing for the cold
water supply.
2
2 Provide a convenient
water line.
manual shut-off valve in the
3 Position the t u b’rng so it can enter the access
located in the right-hand rear of the cabinet.
tubing should extend beyond the cabinet
when the cabinet is pushed back into position.
Figure 5.
Install condensate pump on floor behind ice maker
with discharge tube to the rear. Run drain bin directly
into pump as shown in Figure 5A.
3 Run power cord through hole into unit compartment.
(See Figure 5A)
hole
The
front
See
4 Remove lower grille assembly. (See Figure 58)
5 Remove shunt from receptable and plug in condensate pump. (See Figure 5C)
NOTE:
Always purge the water line before making the final
connection to the inlet of the water valve to prevent
possible water valve malfunction.
Do not discard
After the cabinet is in place, bend the tubing to meet
the connection
at the water valve. The garden hose
threaded compression
fitting is found in the parts
bag. This joint provides a convenient disconnect for
service. Be sure the tubing is clear of compressor,
to prevent rattle.
shunt
that is removed
~~ ‘RESSURE
CONDENSATE
PUMP~~ HAS
I
SWITCH THAT CYCLES ITS PUMP.
from
ADD PLASTIC HOSE
FROM BIN DRAIN
I\
. CONNECT THE DRAIN
(observe local codes)
1 The unit is provided with a gravity drain.
2 The ideal installation has a standpipe l-1/4” (32 mm
minimum) installed directly below the outlet of the drain
tube. Refer to Figure 5 for the proper location of
the standpipe.
3 It may be desirable to insulate drain line thoroughly
up to drain inlet.
RlGHT
4,“”
1,v
IC 11,111,
m-1
END VIEW
THROIIGH
B>ACK VIEW
IE
5
TUBE
-
I
n n
,”
V.Y.
WATER LINE
COMPRESSION
4
I.D. RUBBER DRAIN
TO OPEN DRAIN
l-1/4”
MINIMUM
(32 mm MINIMUM)
HOLE FOR FIELD
BEND FIELD SUPPLIED WATER LINE
TO CONNECT TO WATER VALVE FITTING
RUN
THIS
HOLE
REMOVE
SHUNT
PLUG IN
CONDENSATE
PUMP
-
SCREWS
FIGURE 5C
FIGURE 5B
FOR THE ELECTRICIAN
3-PRONG
GROUNDING TYPE
WALL RECEPTACLE
II
II
ELECTRICAL REQUIREMENTS
A 115 Volt, 60 Hz, AC only, 15 Amp fused electrical supply is required (time delay fuse or circuit breaker is
recommended).
It is recommended that a separate
circuit, serving only this appliance, be provided. DO
NOT use an extension cord.
ELECTRICAL
APPLIANCE.
GROUND IS REQUIRED
ON THIS
RECOMMENDED
GROUNDING METHOD
DO NOT, UNDER ANY CIRCUMSTANCES,
REMOVE
THE POWER SUPPLY CORD GROUND PRONG.
For your personal safety, this appliance must be grounded. This appliance is equipped with a power supply cord
having a 3-prong grounding plug. To minimize possible
shock hazard, the cord must be plugged into a mating
3-prong grounding type wall receptacle, grounded in
accordance with all governing codes and ordinances.
If a mating wall receptacle is not available, it is the
personal responsibility and obligation of the customer
to have a properly grounded 3-prong wall receptacle
installed by a qualified electrician. See Figure 6.
-
POWER SUPPLY
FIGURE 6
ALTERNATE
GROUNDING METHOD
DO NOT, UNDER ANY CIRCUMSTANCES,
REMOVE
THE POWER SUPPLY CORD GROUND PRONG.
If changing and properly grounding the wall receptacle
is impossible and where local codes permit (consult your
5
inspector), a temporary adaptor may be
plugged into the existing 2-prong wall receptacle to mate
with the Bprong power supply cord. See Figure 7. THIS,
HOWEVER, IS NOT RECOMMENDED.
eleCtriCal
NOTE: If this is done, you must connect the grounding
eyelet on the adapter to the wall receptacle cover plate
screw and from this same screw, you must connect a
separate copper ground wire (No. 4 minimum) to a
grounded cold water pipe*. See Figure 7. Do not ground
to a gas supply pipe. Do not connect to electrical supply
until appliance is permanently grounded.
*Cold water pipe must have metal continuity to electrical
ground and not be interrupted by plastic, rubber or other
electrically insulating connectors (including water meter
or pump) without adding a jumper wire at these
connections.
\
GROUND
CLAMP
MUST
BE TIGHT
ON PIPE.’
GROUND
WIRE
ELECTRICALLY
GROUNDEDCOLD
WATER PIPE (REMOVE
PAINT, etc.)
GROUNDING
EYELET
I
0
u
=2
1
CORD
FIGURE 7
6
WHEN THE DESIRED ICE SLAB
THICKNESS IS REACHED, THE
HARVEST CYCLE BEGINS AND THE
FOLLOWING HAPPENS:
l
Evaporator thermostat is satisfied
Compressor keeps running
Condenser fan stops or turns very slowly
Water pump stops
Hot gas solenoid opens
Water inlet valve opens
Excess water is flushed out of the drain pan
Cutter grid is warm to the touch
NOTE:
Normal harvest cycle takes 60 to 120
WHEN THE STORAGE BIN PS FILLED,
BIN THERMOSTAT OPENS.
f
WAL .L RECEPTACLE
SUPPLY
0
..a
0
POWER
0
Compressor runs
Condenser fan runs
Water pump runs (circulates water)
Cutter grid is warm to touch
MACHINE RESUMES FREEZING
AFTER SLAB IS RELEASED FROM
EVAPORATOR AND THE CUTTING
PROCESS BEGINS.
_
il
3-PRONG
GROUNDING
PLUG
0
seconds.
(6’4
SCREW
0
0
0
0
0
0
0
0
GROUND
ASSEMBLY
(ATTACH
TO GROUNDED
COLD IlWTER
PIPE)
\
HOW IT
WORKS
0 Cutter grid remains on
UNIT WIRING DIAGRAM
THINGS TO
REMEMBER
This model operates at 115 volts except for the cutter
grid circuit which operates at 8.5 volts at 1 amp.
0 Water enters only during the defrost cycle. Therefore
the first cycle will be completed without water in the
system.
0 As the room and water temperatures vary, so will the
amount of ice produced. This means that higher
operating temperatures will result in reduced ice
production.
0 The unit will shut off when ice in the storage bin
touches the bin thermostat well and will automatically cycle to keep the bin full.
0 The storage bin is not refrigerated and some
meltage will occur. This, too, varies with the room
temperature.
0 The unit needs good air circulation to perform efficiently. Keep the front grill and the condenser clean.
0 The water system, including filter screen in the water
inlet solenoid valve, needs to be cleaned periodically
for good circulation. Instruction are located on the
inner door panel.
The compressor runs at all times except when the bin
thermostat becomes satisfied and opens up. This deenergizes the system except for the transformer, cutter
grid and bin light.
Under normal operating conditions, when the evaporator
reaches the preset temperature (+ loOF, -12.2OCto -3OF,
-19.4%, depending on thickness of ice) the evaporator
thermostat opens, terminating operation of the fan motor
and pump motor. The hot gas solenoid and the water
valve solenoid are energized at this time and remain so
until the evaporator reaches 380 + 2OF (3.30 + 1%).
OPERATING
INSTRUCTIONS
0 For complete operating information, refer to the Use
and Care Guide.
0 Before starting, wash out interior of cabinet with a
Baking Soda solution (2 tablespoons soda to a quart
of warm water). Rinse thoroughly.
0 Make certain the water is turned on.
0 Turn switch to the “ON” position.
IMPORTANT:
Allow unit to run for 3 hours before expecting ice
and for 24 hours before trying to set the thickness
control.
If installed above 2,000 feet altitude,
thermostat adjustments.
see page 2 for
r----
---------------------j
I
CHECK OPERATION
CUBELET CUTTER GRIDS
Start the unit by turning the service switch to
“ON” and opening the line water valve.
NOTE: Left is “OFF”-Middle
is “ON”--Right
is
“CLEAN.” In “CLEAN” position, only the pump
operates.
19mmx19mm
Check condenser
fan to make sure it is revolving.
Water will not enter pump pan until freezing plate
gets cold and machine goes into a harvest cycle.
Check for even water flow over freezing plate. Unit
must be level for proper operation.
b
Check for desired cube thickness and after 24
hours adjust if necessary. Maximum ice yield
will be obtained with ice thickness at l/2” (12 mm)
to 518” (16 mm).
CUBE CUTTER GRID
Replace grill.
l-114” x l-114” Cube Grid
(32 mm x 32 mm)
‘KitchenAid
Part No. 759080-T
is a registered trademark of KitchenAid,
KitchenAid Canada, Inc. Licensee
KitchenAid
Mississauga,
Canada, Inc.
Ont. L5N 3A7
Inc. U.S.A.
Printed in U.S.A.
Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Download PDF

advertisement