Technical Specifications Eaton 5SC UPS technical specifications

Technical Specifications Eaton 5SC UPS technical specifications
Technical
Specifications
Eaton 5SC UPS technical specifications*
Model overview
Catalog
Power rating
number
(VA/watts)
5S Tower 120V, 50/60 Hz Models
5SC500
500/350
5SS750
750/525
5SC1000
1000/700
5SSC1500
1440/1080
5S Tower 230V, 50/60 Hz Models
5SC500G
500/350
5SC750G
750/525
5SC1500G
1500/1050
Input
Output
Dimensions
(HxWxD, in.)
Weight (lb.)
5-15P (6 ft)
5-15P (6 ft)
5-15P (6 ft)
5-15P (6 ft)
(4) 5-15R
(6) 5-15R
(8) 5-15R
(8) 5-15R
8.2 x 5.9 x 9.4
8.2 x 5.9 x 13.4
8.2 x 5.9 x 13.4
8.2 x 5.9 x 16.1
15.2
23.1
25.6
34.0
C14
C14
C14
(4) C13
(6) C13
(8) C13
8.2 x 5.9 x 9.4
8.2 x 5.9 x 13.4
8.2 x 5.9 x 16.1
15.0
23.1
33.5
*Due to continuing product improvement programs, specifications are subject to change without notice.
Battery runtimes**
Wattage:
18
28
35
70
105
140
175
210
245
280
315
350
118.0
89.0
64.0
29.0
19.6
16.3
12.1
10.4
8.9
7.1
5.3
4.7
26
42
53
105
158
210
263
315
368
420
473
525
5SC750
120.0
89.0
71.0
36.0
24.0
16.6
12.6
10.6
8.7
7.0
6.0
5.0
5SC750G
124.0
100.0
74.0
38.0
23.0
16.5
12.6
10.7
8.8
7.0
6.0
4.9
35
56
70
140
210
280
350
420
490
560
630
700
111.0
85.0
66.0
35.5
23.0
17.0
12.7
10.6
8.7
7.0
5.9
4.8
54
86
108
216
324
432
540
648
756
864
972
1080
5SC500
Wattage:
Wattage:
5SC1000
Wattage:
5SC1500
136.0
111.0
90.0
40.7
24.9
17.5 12.8
10.5
8.6
6.9
5.9
5.0
5SC1500G
144.0
109.0
90.0
41.0
24.7
17.3 12.7
10.4
8.4
6.8
5.8
4.8
**Runtimes are displayed in minutes. Runtimes are approximate and may vary with equipment, configuration, battery
age, temperature, etc. View interactive runtime graphs at www.eaton.com/5SC.
Additional specifications
General
Graphical LCD
LED
Topology
Configuration
Color
Warranty
Contents (Ships with
the following items)
Graphical display. UPS status in a single view
UPS On LED
Line interactive
Tower
Black
3 years including batteries
•
•
•
•
UPS
Input power cord
User manual, safety instructions and warranty for connected equipment
USB and serial cable and software CD
G-Models only:
• 2 IEC output power cords
• No input power cord
Eaton.com/5SC
TD153004EN
August 2013
Page 2 of 2
Electrical input
Nominal voltage
120V: 100/110/120V
230V (G models): 220/230/240V
Default voltage
Low Voltage: 120V
High Voltage: 230V
120V: 96-144 Vac
230V: 184-276 Vac
50/60 Hz
60 Hz: 55–65 Hz
50 Hz: 45–55 Hz
Input voltage range
Frequency
Frequency range
Electrical output
On utility voltage
regulation
On battery voltage
regulation
Efficiency
Frequency tolerance
Over current
protection
Battery
Battery description
Battery management
Battery replacement
Start on battery
Communications
120V: 108-127 Vac
230V: 207-243 Vac
-10%, +6% of nominal
Normal or line mode: >90% above 50% load, >94% at 100% load
±0.1 Hz
Electronic current limit
Sealed, lead-acid; maintenance free
ABM technology; 3-stage charging extends battery service life by 50% and provides advance
warning for battery replacement
Replaceable internal batteries
(not hot-swappable)
Cold-start enabled; first cold start is always forbidden
User interface
Communication
ports
Power management
software
Environmental & standards
RoHS compliance
Surge protection
EMC compliance
Audible noise
Operating
temperature
Safety Markings
Storage temperature
Relative humidity
Altitude
Eaton.com/5SC
LCD graphical display. UPS status in a single view.
USB port as standard (HID) - USB Cord Included
RJ45 Serial Port – Serial Cord included
IPP / IPM
Yes
IEEE ANSI C62.41 Cat B2
120V: FCC Part 15 subpart B Class A
IEC 62040-2 C1/ EN 55024 / CISPR22 Class B / FCC part 15 Class B
< 40 dB at 1 meter
0° to 35°C (32°F to 95°F)
120V: UL / CE / VCCI / NOM
230V: CE /cTUVus / GHOST
-15°C to 40°C (5°F to 104°F)
0 to 90% non-condensing
Up to 6,500 ft (2000m) without de-rating