CB series CMOS IC Time Delay Relay

Add to my manuals
2 Pages

advertisement

CB series CMOS IC Time Delay Relay | Manualzz

Timing Modes

Delay on operate – Delay period begins when input voltage is applied. At the end of the delay period, the relay will operate and will not release until input voltage is removed. Reset occurs when input voltage is reapplied.

INPUT

VOLTAGE

ON

OFF

N.O. RELAY

CONTACTS

ON

OFF

TIME

Delay on release – Input voltage must be applied continuously to operate the internal relay. When the control switch is closed, the relay energizes.

When the control switch is opened, timing begins. When timing is complete, the relay will de-energize. Time may be reset to zero during timing by closing the control switch.

CONTROL

SWITCH

N.O. RELAY

CONTACTS

ON

OFF

ON

OFF

TIME

Interval on (without control switch) – The relay energizes and timing begins when input voltage is applied. At the end of the time delay period the relay will de-energize. Reset is accomplished by removing, then reapplying, the input voltage.

INPUT

VOLTAGE

ON

OFF

Catalog 1308242

Issued 3-03

CB

series

CMOS IC Time Delay Relay

Choice of timing modes

– Delay on operate

– Delay on release

– Interval on with or without control switch

Knob adjustable

10A output relay with SPDT or DPDT contacts

Various models time from 0.1 sec. to 100 min.

P&B

File E22575

File LR15734

Users should thoroughly review the technical data before selecting a product part number. It is recommended that user also seek out the pertinent approvals files of the agencies/laboratories and review them to ensure the product meets the requirements for a given application.

Contact Data @ 25

°

C

Arrangements: 2 Form C (DPDT), except 8-pin delay on release model has 1 Form C (SPDT).

Material: Silver-cadmium oxide alloy.

Rating: 10A @ 30VDC or 277VAC, resistive; 1/2 HP @ 250VAC;

1/3 HP @ 120VAC.

Expected Mechanical Life: 10 million operations.

Expected Electrical Life: 100,000 operations, min., at rated load.

Initial Dielectric Strength

Between Open Contacts: 500V rms, 60 Hz.

Between All Other Conductors: 500V rms, 60 Hz.

Input Data @ 25

°

C

Voltage: 24 and 120VAC, and 12 and 24VDC.

Power Requirement: AC Types: Typically less than 3 VA.

DC Types: Typically less than 3 W.

Transient Protection: Yes.

Reverse Voltage Protection: Yes.

Input Voltages & Limits @ 25

°

C

Voltage

Type

Nominal

Voltage

Minimum

Voltage

Maximum

Voltage

N.O. RELAY

CONTACTS

ON

OFF

TIME

Interval on (with control switch) – Input voltage must be applied continuously to operate the internal relay. The relay energizes and timing begins when the external switch is closed. At the end of the time delay period the relay will de-energize. Reset is accomplished by opening and reclosing the control switch.

AC

DC

24

120

12

24

20

105

11

20

Note: DC voltage must be filtered (5% p-p ripple max. at nom. voltage).

AC models will operate on 50 or 60 Hz.

28

130

13

32

CONTROL

SWITCH

ON

OFF

N.O. RELAY

CONTACTS

ON

OFF

TIME

Timing Specifications

Timing Ranges: From 0.1 to 1.0 sec. through 10 to 100 min.

Timing Adjustment: Knob adjustable.

Tolerance (for AC units add

±

1/2 cycle 60 Hz.):

Knob Adj. Types: –0, +30% of max. specified at high end of timing range; min. specified, or less, at low end.

Fixed Types:

±

10%.

Res. Adj. Types:

±

10% at high end of timing range; min. specified, or less, at low end.

Delta Time (for AC units add

±

1 cycle 60 Hz.):

±

10%.

Repeatability (for AC units add

±

1 cycle 60 Hz.):

±

2%.

Release Time: 60 ms, typ.; 100 ms, max.

Recycle Time: 60 ms, typ.; 100 ms, max.

1228

Dimensions are shown for reference purposes only.

Dimensions are in inches over

(millimeters) unless otherwise specified.

Environmental Data

Temperature Range: Storage: -55

°

C to +85

°

C.

Operating: -10

°

C to +55

°

C.

Mechanical Data

Termination: 8- or 11-pin octal style plug.

Enclosure: White plastic case. Knob adjustable types have dial scale for reference only.

Sockets: Models with 8-pin base fit either 27E122 or 27E891 (snap-on) screw terminal sockets. 11-pin types fit either 27E123 or

27E892 (snap-on) screw terminal sockets.

Weight: 6 oz. (170g) approximately.

Specifications and availability subject to change.

www.tycoelectronics.com

Technical support:

Refer to inside back cover.

Catalog 1308242

Issued 3-03

Ordering Information – Authorized distributors are more likely to stock boldface items listed below.

Delay on Operate Models

Voltage

24VAC

120VAC

12VDC

24VDC

Time

0.1 to 10 Sec.

1.8 to 180 Sec

0.1 to 1 Sec.

0.1 to 5 Sec.

0.1 to 10 Sec.

0.6 to 60 Sec.

1.8 to 180 Sec.

1 to 10 Min.

10 to 100 Min.

0.1 to 10 Sec.

0.1 to 1 Sec.

0.1 to 10 Sec.

0.6 to 60 Sec.

1.8 to 180 Sec.

Adjustment

Knob

Knob

Knob

Knob

Wiring Dia.

Part Number

1 CB-1041B-30

CB-1042B-30

1

1

1

CB-1001B-70

CB-1002B-70

CB-1003B-70

CB-1004B-70

CB-1005B-70

CB-1006B-70

CB-1007B-70

CB-1047D-20

CB-1026D-30

CB-1028D-30

CB-1029D-30

CB-1030D-30

Delay on Release Models

Voltage

24VAC

120VAC

24VDC

Time

0.1 to 10 Sec.

1.8 to 180 Sec

0.1 to 10 Sec.

0.1 to 10 Sec.

0.6 to 60 Sec.

1.8 to 180 Sec.

0.1 to 10 Sec.

1.8 to 180 Sec.

Interval on Models

Voltage

24VAC

120VAC

24VDC

Time

0.1 to 10 Sec.

0.1 to 5 Sec.

0.1 to 10 Sec.

1 to 10 Min.

0.1 to 5 Sec.

1.8 to 180 Sec.

Adjustment

Knob

Knob

Knob

Adjustment

Knob

Knob

Knob

P&B

Wiring Dia.

Part Number

3 CB-1045B-38

CB-1046B-38

3

3

3

5

3

CB-1021B-78

CB-1022B-78

CB-1023B-78

CB-1024B-78

CB-1038D-38

CB-1039D-38

Wiring Dia.

Part Number

1 CB-1043B-39

1

1

1

1

CB-1011B-79

CB-1014B-79

CB-1018B-79

CB-1034D-39

CB-1036D-39

Outline Dimensions

2.406 MAX.

(61.1)

.60

(15.2)

2.937 MAX.

(74.6)

.56

(14.2)

1.781 MAX.

(45.2)

Wiring Diagrams - Bottom Views (pins numbered clockwise from keyway)

EXTERNAL

CONTROL

SWITCH*

EXTERNAL

CONTROL

SWITCH*

+

_

INPUT (DC POLARITY

INDICATED)**

Fig. 1

8 Pin

+

_

CONTINUOUS

SUPPLY

INPUT

(DC POLARITY INDICATED)**

Fig. 3

11 Pin

+

_

CONTINUOUS

SUPPLY

INPUT

(DC POLARITY INDICATED)**

Fig. 5

8 Pin

* If control switch is closed when power is applied, relay will immediately energize. A 50 millisecond minimum switch closure is required. IMPORTANT: A dry circuit switch is recommended. A

“dry circuit” switch is one rated to reliably switch currents of less than 50mA. Use of a switch rated for other than dry circuit may result in failure of the time delay relay to function properly.

** Note: Input polarity for DC operation. For most reliable operation on AC, connect high side to “+” and low side to “–”.

Dimensions are shown for reference purposes only.

Dimensions are in inches over

(millimeters) unless otherwise specified.

Specifications and availability subject to change.

www.tycoelectronics.com

Technical support:

Refer to inside back cover.

1229

advertisement