Delivery�programme Contactor,�4p,�4kW/400V/AC3 Part�no.  DILEM4-G(24VDC)

Delivery�programme Contactor,�4p,�4kW/400V/AC3 Part�no.  DILEM4-G(24VDC)

Delivery�programme

Product range

Application

Subrange

Utilization category

Contactor,�4p,�4kW/400V/AC3

Part�no. 

Article�no. 

Catalog�No. 

DILEM4-G(24VDC)

012701

XTMF9A00TD

 

 

 

 

Connection technique

Pole

Rated�operational�current

AC-3

380 V 400 V

AC-1

Conventional free air thermal current, 3 pole, 50 - 60 Hz

Open at 40 °C

Max.�rating�for�three-phase�motors,�50�-�60�Hz

AC-3

220 V 230 V

380 V 400 V

660 V 690 V

AC-4

220 V 230 V

380 V 400 V

660 V 690 V

Contact sequence

 

 

 

 

 

I e

 

 

 

I th

=I e

 

P

P

 

P

P

P

 

P

 

 

 

 

 

 

A

 

 

 

A

 

 

 

 

  kW kW kW

  kW kW kW

 

 

22

 

 

 

9

3

3

 

1.5

4

4

 

2.2

Contactors

Mini Contactors for Motors and Resistive Loads

DILEM contactors

AC-1: Nicht induktive oder schwach induktive Last, Widerstandsöfen

AC-3: Käfigläufermotoren: Anlassen, Ausschalten während des Laufes

AC-4: Käfigläufermotoren: Anlassen, Gegenstrombremsen, Reversieren, Tippen

 

Screw terminals

4 pole

For use with

Actuating voltage

Voltage AC/DC

Technical�data

General

Standards

Maximum operating frequency

Mechanical electrical (Contactors without overload relay)

Climatic proofing

Ambient temperature

Open

Enclosed

Mounting position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

  …DILEM

…DILE

24 V DC

DC operation

 

°C

°C

°C

 

 

  IEC/EN 60947, VDE 0660, CSA, UL

   

Ops./h 9000

 

Page 05/070

Damp heat, constant, to IEC 60068-2-78

Damp heat, cyclic, to IEC 60068-2-30

- 25 - 50

- 25 - 40

As required, except vertical with terminals A1/A2 at the bottom

02/13/2015 012701 - HPL-ED2014 V9.0 EN 1 / 12

Mounting position    

Mechanical shock resistance (IEC/EN 60068-2-27)

Half-sinusoidal shock, 10 ms

Basic unit without auxiliary contact module

Main contacts, make contacts

Basic unit with auxiliary contact module

Main contacts make contact

Make

Auxiliary contacts Make/break contacts

Degree of Protection

Protection against direct contact when actuated from front (EN 50274)

Weight

Terminal capacity of auxiliary and main contacts

Screw terminals

Solid

Flexible with ferrule

Solid or stranded

Terminal screw

Pozidriv screwdriver

Standard screwdriver

Max. tightening torque

Main�conducting�paths

Rated impulse withstand voltage

Overvoltage category/pollution degree

Rated insulation voltage

Rated operational voltage

Safe isolation to EN 61140 between coil and contacts between the contacts

Making capacity (cos ϕ to IEC/EN 60947)

Breaking capacity

220 V 230 V

380 V 400 V

500 V

660 V 690 V

Short-circuit protection maximum fuse

Type “2” coordination

Type “1” coordination

AC

AC-1

Rated operational current

Conventional free air thermal current, 3 pole, 50 - 60 Hz

Open at 40 °C at 50 °C

02/13/2015

U imp

 

U i

U e

 

 

 

 

 

 

 

 

 

  gL/gG gL/gG

 

 

 

 

I th

=I e

I th

=I e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

012701 - HPL-ED2014 V9.0 EN

V AC

 

V AC

V AC

A

A

 

A

 

V AC

V AC

A

A

A

 

A

 

 

 

 

A

A mm

2

 

AWG

Size mm

  kg

 

 

  mm

2 g g

  g

  g

 

 

Nm

 

10

 

 

 

 

10

20 / 20

IP20

Finger and back-of-hand proof

 

0.17

 

1 x (0.75 - 2.5)

2 x (0.75 - 2.5)

1 x (0.75 - 1.5)

2 x (0.75 - 1.5)

18 - 14

M3.5

2

0.8 x 5.5

1 x 6

1.2

6000

III/3

690

690

90

64

 

90

 

300

300

110

10

20

 

42

 

 

 

 

22

20

2 / 12

at 55 °C enclosed

Notes

Conventional free air thermal current, 1 pole

Notes open enclosed

AC-3

Rated operational current

Open, 3-pole: 50 – 60 Hz

Notes

220 V 230 V

240 V

380 V 400 V

415 V

440V

500 V

660 V 690 V

Motor rating

220 V 230 V

240V

380 V 400 V

415 V

440 V

500 V

660 V 690 V

AC-4

Rated operational current

Open, 3-pole: 50 – 60 Hz

Notes

220 V 230 V

240 V

380 V 400 V

415 V

440 V

500 V

660 V 690 V

Motor rating

220 V 230 V

240 V

380 V 400 V

415 V

440 V

500 V

660 V 690 V

DC

Rated operational current open

DC - -1

12 V

24 V

60 V

110 V

220 V

DC - 3

02/13/2015

P

P

P

P

P

P

P

P

I e

I e

I e

I e

I e

 

I e

 

 

I e

 

P

P

P

P

P

P

I e

P

P

 

I e

 

 

 

I th

I th

I th

=I e

 

I th

 

 

I e

I e

I e

I e

I e

 

I e

I e

I e

I e

 

 

I e

012701 - HPL-ED2014 V9.0 EN

 

20

20

20

20

 

 

20

6.6

6.6

6.6

5

3.4

3

3

3.1

3.3

 

1.5

1.8

3

19

16

At maximum permissible ambient air temperature.

 

At maximum permissible ambient air temperature.

60

50

 

 

 

At maximum permissible ambient air temperature.

9

9

9

9

9

6.4

4.8

 

4

4.6

4

 

2.2

2.5

4

4.3

 

 

At maximum permissible ambient air temperature.

6.6

6.6

A

A

A

A

A

A kW kW

  kW kWh kW kW kW kW

 

A

 

 

A

 

 

 

A

A

 

 

 

 

A

A

A

A

A

A

A

A kW kW kW kW kWh kW kW kW

 

A

A

A

A

 

 

A

3 / 12

12 V

24 V

60 V

110 V

220 V

DC - 5

12 V

24 V

60 V

110 V

220 V

Current heat losses (3- or 4-pole) to I th

Magnet�systems

Voltage tolerance

DC operated

 

 

Pick-up voltage

Power consumption

DC operation

Power consumption Pick-up = Sealing

Notes

Duty factor

Switching times at 100 % U c

Make contact

Closing delay

Closing delay min.

Closing delay max.

Opening delay

Opening delay min.

Opening delay max.

Closing delay with top mounting auxiliary contact

Reversing contactors

Changeover time at 110 % U c

Changeover time min.

 

Changeover time max.

Arcing time at 690 V AC

Auxiliary�contacts

Positive operating contacts to EN 60947-5-1 appendix L, including auxiliary contact module

 

 

Rated impulse withstand voltage

 

U imp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overvoltage category/pollution degree

Rated insulation voltage

Rated operational voltage

Safe isolation to EN 61140 between coil and auxiliary contacts between the auxiliary contacts

Rated operational current

AC-15

220 V 240 V

380 V 415 V

500 V

 

U e

 

U i

 

 

 

 

I e

I e

I e

 

DC L/R 15 ms

Contacts in series:

1

 

24 V

I e

I e

 

I e

I e

I e

I e

I e

I e

I e

I e

02/13/2015

A

A

A

A

 

W

A

A

 

A

A

A

A

2.5

2.5

2.5

1

 

4.7

3

1

 

2.5

8

8

4

Yes

 

 

 

6

 

300

300

3

1.5

6000

III/3

690

600

 

2.5

 

A

A

 

A

A

 

 

A

 

V AC

V AC

V AC

 

V AC

V AC ms ms ms ms ms ms ms

 

  ms ms ms ms

 

 

 

 

 

 

VA/W

 

% DF

15

25

 

35

 

 

26

 

  max. 70

 

 

 

0.85   1.1

 

 

2.6

Smoothed DC voltage or three-phase bridge rectifier

100

40

50 max. 12

012701 - HPL-ED2014 V9.0 EN 4 / 12

2

3

3

Conv. thermal current

Control circuit reliability

Component lifespan at U e

= 240 V

AC-15

DC current

L/R = 50 ms: 2 contacts in series at I e

= 0.5 A

Notes

Short-circuit rating without welding

Maximum overcurrent protective device

Short-circuit protection only

Short-circuit protection maximum fuse

500 V

500 V

Current heat loss at a load of I th

per contact

Data�for�design�verification�according�to�IEC/EN�61439

Technical data for design verification  

Rated operational current for specified heat dissipation I n

Heat dissipation per pole, current-dependent

Equipment heat dissipation, current-dependent

Static heat dissipation, non-current-dependent

Heat dissipation capacity

IEC/EN 61439 design verification

10.2 Strength of materials and parts

10.2.2 Corrosion resistance

10.2.3.1 Verification of thermal stability of enclosures

10.2.3.2 Verification of resistance of insulating materials to normal heat

10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects

10.2.4 Resistance to ultra-violet (UV) radiation

10.2.5 Lifting

10.2.6 Mechanical impact

10.2.7 Inscriptions

10.3 Degree of protection of ASSEMBLIES

10.4 Clearances and creepage distances

10.5 Protection against electric shock

10.6 Incorporation of switching devices and components

10.7 Internal electrical circuits and connections

10.8 Connections for external conductors

10.9 Insulation properties

10.9.2 Power-frequency electric strength

10.9.3 Impulse withstand voltage

10.9.4 Testing of enclosures made of insulating material

10.10 Temperature rise

 

 

 

 

 

P vid

P vid

 

P vs

P diss

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.11 Short-circuit rating

10.12 Electromagnetic compatibility

10.13 Mechanical function

 

 

 

 

 

 

W

W

 

 

 

 

 

 

W

W

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60 V

100 V

220 V

I th

Failure rate λ

A

A

A

A

Operations

Operations

2.5

1.5

0.5

10

 

<10

-8

(at U e

, < one failure at 100 million operations

= 24 V DC, U min

= 17 V, I min

= 5.4 mA)

 

  x 10

6 0.2

  x 10

6

 

0.15

 

 

Switch-on and switch-off conditions based on DC-13, time constant as specified

 

 

 

 

A gG/gL 6

A fast 10

W

 

PKZM0-4

0.3

 

22

0.68

0

2.6

0

 

 

Meets the product standard's requirements.

Meets the product standard's requirements.

Meets the product standard's requirements.

Meets the product standard's requirements.

Meets the product standard's requirements.

Does not apply, since the entire switchgear needs to be evaluated.

Does not apply, since the entire switchgear needs to be evaluated.

Meets the product standard's requirements.

Does not apply, since the entire switchgear needs to be evaluated.

Meets the product standard's requirements.

Does not apply, since the entire switchgear needs to be evaluated.

Does not apply, since the entire switchgear needs to be evaluated.

Is the panel builder's responsibility.

 

Is the panel builder's responsibility.

Is the panel builder's responsibility.

Is the panel builder's responsibility.

Is the panel builder's responsibility.

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

02/13/2015 012701 - HPL-ED2014 V9.0 EN 5 / 12

Technical�data�ETIM�5.0

Low-voltage industrial components (EG000017) / Magnet contactor, AC-switching (EC000066)

Electric engineering, automation, process control engineering / Low-voltage switch technology / Contactor (LV) / Power contactor, AC switching ([email protected] [AAB718011])

Rated control supply voltage Us at AC 50HZ

Rated control supply voltage Us at AC 60HZ

Rated control supply voltage Us at DC

Voltage type for actuating

Rated operation current Ie at AC-1, 400 V

Rated operation current Ie at AC-3, 400 V

Rated operation power at AC-3, 400 V

Rated operation current Ie at AC-4, 400 V

Rated operation power Ie at AC-4, 400 V

Modular version

Number of auxiliary contacts as normally open contact

Number of auxiliary contacts as normally closed contact

Connection type main current circuit

Number of normally closed contacts as main contact

Number of main contacts as normally open contact  

 

 

 

 

 

A kW

 

A

A kW

V

V

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

4

DC

22

0 - 0

0 - 0

24 - 24

6.6

3

No

0

0

4

0

Screw connection

Approvals

Product Standards

UL File No.

UL Category Control No.

CSA File No.

CSA Class No.

North America Certification

Specially designed for North America

 

 

 

 

 

 

 

 

 

 

 

 

 

  IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking

E29096

NLDX

012528

3211-04

UL listed, CSA certified

No

02/13/2015 012701 - HPL-ED2014 V9.0 EN 6 / 12

Characteristics

1: Overload relay

2: Suppressor

3: Auxiliary contact modules

Enclosure totally insulated

02/13/2015 012701 - HPL-ED2014 V9.0 EN 7 / 12

Squirrel-cage motor

Operating characteristics

Starting:from rest

Stopping:after attaining full running speed

Electrical characteristics

Make: up to 6 x rated motor current

Break: up to 1 x rated motor current

Utilization category

100 % AC-3

Typical applications

Compressors

Lifts

Mixers

Pumps

Escalators

Agitators

Fans

Conveyor belts

Centrifuges

Hinged flaps

Bucket-elevators

Air conditioning system

General drives in manufacturing and processing machines

02/13/2015 012701 - HPL-ED2014 V9.0 EN 8 / 12

Extreme switching duty

Squirrel-cage motor

Operating characteristics

Inching, plugging, reversing

Electrical characteristics

Make: up to 6 x rated motor current

Break: up to 6 x rated motor current

Utilization category

100 % AC-4

Typical applications

Printing presses

Wire-drawing machines

Centrifuges

Special drives for manufacturing and processing machines

02/13/2015 012701 - HPL-ED2014 V9.0 EN 9 / 12

Switching duty for non-motor loads, 3-pole, 4-pole

Operating characteristics

Non-inductive or slightly inductive loads

Electrical characteristics

Make: 1 x rated current

Break: 1 x rated current

Utilization category

100 % AC-1

Typical applications

Electric heat

02/13/2015 012701 - HPL-ED2014 V9.0 EN 10 / 12

Short-time loading, 3-pole

Time interval between two loading cycles: 15 minutes

Dimensions

02/13/2015 012701 - HPL-ED2014 V9.0 EN 11 / 12

2DILE-… + MVDILE + …DILE

2DILE-…-G + MVDILE + …DILE

Additional�product�information�(links)

IL03407009Z�(AWA2100-0882)�Mini�contactor�relay

IL03407009Z (AWA2100-0882) Mini contactor relay

UL/CSA: Approved rating data ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL03407009Z2010_10.pdf

http://de.ecat.moeller.net/flip-cat/?edition=HPLTE&startpage=5.84

02/13/2015 Eaton Industries GmbH http://www.eaton.eu

© 12/2014 by Eaton Industries GmbH

012701 - HPL-ED2014 V9.0 EN

12 / 12