Bulletin No. PAX-M
Drawing No. LP0545
Released 02/13
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
MODEL PAX – 1/8 DIN ANALOG INPUT PANEL METERS
 PROCESS, VOLTAGE, CURRENT, TEMPERATURE, AND STRAIN
GAGE INPUTS
 5-DIGIT 0.56" RED SUNLIGHT READABLE DISPLAY
 VARIABLE INTENSITY DISPLAY
 16 POINT SCALING FOR NON-LINEAR PROCESSES
 PROGRAMMABLE FUNCTION KEYS/USER INPUTS
 9 DIGIT TOTALIZER (INTEGRATOR) WITH BATCHING
 OPTIONAL CUSTOM UNITS OVERLAY W/BACKLIGHT
 FOUR SETPOINT ALARM OUTPUTS (W/OPTION CARD)
 COMMUNICATION AND BUS CAPABILITIES (W/OPTION CARD)
UL
C
 RETRANSMITTED ANALOG OUTPUT (W/OPTION CARD)
US LISTED
R
 CRIMSON® PROGRAMMING SOFTWARE
IND. CONT. EQ.
 NEMA 4X/IP65 SEALED FRONT BEZEL
51EB
GENERAL DESCRIPTION
A linear DC output signal is available as an optional Plug-in card. The card
provides either 20 mA or 10 V signals. The output can be scaled independent of
the input range and can track either the input, totalizer, max or min readings.
Once the meters have been initially configured, the parameter list may be
locked out from further modification in its entirety or only the setpoint values
can be made accessible.
The meters have been specifically designed for harsh industrial environments.
With NEMA 4X/IP65 sealed bezel and extensive testing of noise effects to CE
requirements, the meter provides a tough yet reliable application solution.
The PAX® Analog Panel Meters offer many features and performance
capabilities to suit a wide range of industrial applications. Available in five
different models to handle various analog inputs, including DC Voltage/Current,
AC Voltage/Current, Process, Temperature, and Strain Gage Inputs. Refer to
pages 4 through 6 for the details on the specific models. The optional plug-in
output cards allow the opportunity to configure the meter for present
applications, while providing easy upgrades for future needs.
The meters employ a bright 0.56" LED display. The unit is available with a
red sunlight readable or a standard green LED. The intensity of display can be
adjusted from dark room applications up to sunlight readable, making it ideal
for viewing in bright light applications.
The meters provide a MAX and MIN reading memory with programmable
capture time. The capture time is used to prevent detection of false max or min
readings which may occur during start-up or unusual process events.
The signal totalizer (integrator) can be used to compute a time-input product.
This can be used to provide a readout of totalized flow, calculate service
intervals of motors or pumps, etc. The totalizer can also accumulate batch
weighing operations.
The meters have four setpoint outputs, implemented on Plug-in option cards.
The Plug-in cards provide dual FORM-C relays (5A), quad FORM-A (3A), or
either quad sinking or quad sourcing open collector logic outputs. The setpoint
alarms can be configured to suit a variety of control and alarm requirements.
Communication and Bus Capabilities are also available as option cards.
These include RS232, RS485, Modbus, DeviceNet, and Profibus-DP. Readout
values and setpoint alarm values can be controlled through the bus. Additionally,
the meters have a feature that allows a remote computer to directly control the
outputs of the meter. With an RS232 or RS485 card installed, it is possible to
configure the meter using a Windows® based program. The configuration data
can be saved to a file for later recall.
DIMENSIONS In inches (mm)
MAX
MIN
TOT
8.8.8.8.8
SP1
DSP
SP2
PAR
F1
SP3
SP4
F2
RST
3.80
(96.5)
V
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use this unit to directly command motors, valves, or other actuators
not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the unit.
CAUTION: Risk of Danger
Read complete instructions prior to
installation and operation of the unit.
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is
2.1" (53.4) H x 5.0" (127) W.
1.95
(49.5)
1.75
(44.5)
.10
(2.5)
CAUTION: Risk of electric shock.
4.10
(104.1)
1
12
13
14
15
1 2 3 4
5 6
7
16
17
18
19
8 9 10 11
3.60 (91.4)
20
21
22
23
24
25
1.75
(44.5)
Table Of Contents
Ordering Information . . . . . . . . . . . . . . . . . . . 2
General Meter Specifications . . . . . . . . . . . . . 3
Universal DC Input Panel Meter. . . . . . . . . . . 4
Process Input Panel Meter. . . . . . . . . . . . . . . 4
AC True RMS Voltage and Current Meter. . . . 5
Strain Gage Input Panel Meter. . . . . . . . . . . . 5
Thermocouple and RTD Input Meter . . . . . . . 6
Optional Plug-In Cards . . . . . . . . . . . . . . . . . . 7
Installing the Meter . . . . . . . . . . . . . . . . . . . . . 8
Setting the Jumpers . . . . . . . . . . . . . . . . . . . . 8
Installing Plug-In Cards. . . . . . . . . . . . . . . . . 10
Wiring the Meter . . . . . . . . . . . . . . . . . . . . . . 11
Reviewing the Front Buttons and Display. . . 14
Programming the Meter. . . . . . . . . . . . . . . . . 15
Factory Service Operations . . . . . . . . . . . . . 29
Parameter Value Chart . . . . . . . . . . . . . . . . . 31
Programming Overview . . . . . . . . . . . . . . . . 33
Ordering Information
Meter Part Numbers
PAX
0
0
D - DC Volt/ Current Input
P - Process Input
H - AC True RMS Volt/Current Input *
S - Strain Gage/Bridge Input
T - Thermocouple and RTD Input
0 - Red, Sunlight Readable Display
1 - Green Display
0 - 85 to 250 VAC
1 - 11 to 36 VDC, 24 VAC
* PAXH is only available with 85-250 VAC power supply.
Option Card and Accessories Part Numbers
TYPE
MODEL NO.
PAXCDS
Optional
Plug-In
Cards
Accessories
PAXCDC
DESCRIPTION
PART NUMBER
Dual Setpoint Relay Output Card
PAXCDS10
Quad Setpoint Relay Output Card
PAXCDS20
Quad Setpoint Sinking Open Collector Output Card
PAXCDS30
Quad Setpoint Sourcing Open Collector Output Card
PAXCDS40
RS485 Serial Communications Card with Terminal Block
PAXCDC10
Extended RS485 Serial Communications Card with Dual RJ11 Connector
PAXCDC1C
RS232 Serial Communications Card with Terminal Block
PAXCDC20
Extended RS232 Serial Communications Card with 9 Pin D Connector
PAXCDC2C
DeviceNet Communications Card
PAXCDC30
Modbus Communications Card
PAXCDC40
Extended Modbus Communications Card with Dual RJ11 Connector
PAXCDC4C
Profibus-DP Communications Card
PAXCDC50
PAXCDL
Analog Output Card
PAXCDL10
PAXUSB
PAX USB Programming Card (Not included in PAX product UL E179259 file)
PAXUSB00
CBLUSB
USB Programming Cable Type A-Mini B
CBLUSB01
ICM8
Ethernet Gateway
ICM80000
PAXLBK
Units Label Kit Accessory (Not required for PAXT)
PAXLBK10
SFCRD *
Crimson PC Configuration Software for Windows 98, ME, 2000 and XP
SFCRD200
* Crimson® software is available for free download from http://www.redlion.net/
2
General Meter Specifications
1. DISPLAY: 5 digit, 0.56" (14.2 mm) red sunlight readable or standard green
LEDs, (-19999 to 99999)
2. POWER:
AC Versions:
AC Power: 85 to 250 VAC, 50/60 Hz, 15 VA
Isolation: 2300 Vrms for 1 min. to all inputs and outputs.
DC Versions (Not available on PAXH):
DC Power: 11 to 36 VDC, 11 W
(derate operating temperature to 40° C if operating <15 VDC and three
plug-in option cards are installed)
AC Power: 24 VAC, ± 10%, 50/60 Hz, 15 VA
Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working).
3. ANNUNCIATORS:
MAX - maximum readout selected
MIN - minimum readout selected
TOT - totalizer readout selected, flashes when total overflows
SP1 - setpoint alarm 1 is active
SP2 - setpoint alarm 2 is active
SP3 - setpoint alarm 3 is active
SP4 - setpoint alarm 4 is active
Units Label - optional units label backlight
4. KEYPAD: 3 programmable function keys, 5 keys total
5. A/D CONVERTER: 16 bit resolution
6. UPDATE RATES:
A/D conversion rate: 20 readings/sec.
Step response: 200 msec. max. to within 99% of final readout value
(digital filter and internal zero correction disabled)
700 msec. max. (digital filter disabled, internal zero correction enabled)
PAXH Only: 1 sec max. to within 99% of final readout value (digital filter
disabled)
Display update rate: 1 to 20 updates/sec.
Setpoint output on/off delay time: 0 to 3275 sec.
Analog output update rate: 0 to 10 sec
Max./Min. capture delay time: 0 to 3275 sec.
7. DISPLAY MESSAGES:
“OLOL” - Appears when measurement exceeds + signal range.
“ULUL” - Appears when measurement exceeds - signal range
PAXT: “SHrt” - Appears when shorted sensor is detected. (RTD only)
PAXT: “OPEN” - Appears when open sensor is detected.
“. . . .” - Appears when display values exceed + display range.
“- . . .” - Appears when display values exceed - display range.
“E . . .” - Appears when Totalizer exceeds 9 digits.
“h . . .” - Denotes the high order display of the Totalizer.
8. INPUT CAPABILITIES: See specific product specifications, pages 4-6
9. EXCITATION POWER: See specific product specifications, pages 4-6
10. LOW FREQUENCY NOISE REJECTION: (Does not apply to PAXH)
Normal Mode: > 60 dB @ 50 or 60 Hz ±1%, digital filter off
Common Mode: >100 dB, DC to 120 Hz
11. USER INPUTS: Three programmable user inputs
Max. Continuous Input: 30 VDC
Isolation To Sensor Input Common: Not isolated. (Not PAXH)
PAXH: Isolation to Sensor Input Common: 1400 Vrms for 1 min.
Working Voltage: 125 V
Response Time: 50 msec. max.
Logic State: Jumper selectable for sink/source logic
INPUT STATE
SINKING INPUTS
22 KΩ pull-up to +5 V
SOURCING INPUTS
22 KΩ pull-down
Active
Inactive
VIN < 0.9 VDC
VIN > 3.6 VDC
VIN > 3.6 VDC
VIN < 0.9 VDC
cards installed)
Vibration According to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
direction for 1.5 hours, 2 g.
Shock According to IEC 68-2-27: Operational 25 g (10 g relay), 11 msec in 3
directions.
Storage Temperature Range: -40 to 60°C
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters
16. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File #E179259, UL61010A-1, CSA C22.2
No. 61010-1
PAXT Only: File # E156876, UL873, CSA C22.2 No. 24
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Report #04ME11209-20041018
Issued by Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part I
IP65 Enclosure rating (Face only), IEC 529
IP20 Enclosure rating (Rear of unit), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326:2006: Electrical Equipment for
Measurement, Control and Laboratory use.
Immunity to Industrial Locations:
Electrostatic discharge
EN 61000-4-2 Criterion A
4 kV contact discharge
8 kV air discharge
Electromagnetic RF fields EN 61000-4-3 Criterion A4
10 V/m (80 MHz to 1 GHz)
3 V/m (1.4 GHz to 2 GHz)
1 V/m (2 GHz to 2.7 GHz)
Fast transients (burst)
EN 61000-4-4 Criterion B
2 kV power
1 kV I/O signal
2 kV I/O signal connected
to power
Surge
EN 61000-4-5 Criterion A
power
1 kV L to L, 2 kV L to G
signal
1 kV
RF conducted interference EN 61000-4-6 Criterion A
3 Vrms
Power freq magnetic fields EN 61000-4-8 Criterion A
30 A/m
AC power
EN 61000-4-11
Voltage dip
Criterion A
0% during 1 cycle
40% during 10/12 cycle
70% during 25/30 cycle
Short interruptions
Criterion C
0% during 250/300 cycles
Emissions:
Emissions
EN 55011
Class A
Notes:
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit selfrecovers.
3. Criterion C: Temporary loss of function where system reset occurs.
4. Self-recoverable loss of performance during EMI disturbance at 10 V/m:
Measurement input and/or analog output signal may deviate during EMI
disturbance.
For operation without loss of performance:
Unit is mounted in a metal enclosure (Buckeye SM7013-0 or equivalent)
I/O and power cables are routed in metal conduit connected to earth ground.
Refer to EMC Installation Guidelines section of the bulletin for additional
information.
17. CONNECTIONS: High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gage: 30-14 AWG copper wire
Torque: 4.5 inch-lbs (0.51 N-m) max.
18. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 outdoor use.
IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece
bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and
mounting clip included.
19. WEIGHT: 10.4 oz. (295 g)
12. TOTALIZER:
Function:
Time Base: second, minute, hour, or day
Batch: Can accumulate (gate) input display from a user input
Time Accuracy: 0.01% typical
Decimal Point: 0 to 0.0000
Scale Factor: 0.001 to 65.000
Low Signal Cut-out: -19,999 to 99,999
Total: 9 digits, display alternates between high order and low order readouts
13. CUSTOM LINEARIZATION:
Data Point Pairs: Selectable from 2 to 16
Display Range: -19,999 to 99,999
Decimal Point: 0 to 0.0000
PAXT: Ice Point Compensation: user value (0.00 to 650.00 µV/°C)
14. MEMORY: Nonvolatile E2PROM retains all programmable parameters and
display values.
15. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50°C (0 to 45°C with all three plug-in
3
Model PAXD - Universal DC Input
 FOUR VOLTAGE RANGES (300 VDC Max)
 FIVE CURRENT RANGES (2A DC Max)
 THREE RESISTANCE RANGES (10K Ohm Max)
 SELECTABLE 24 V, 2 V, 1.75 mA EXCITATION
PAXD SPECIFICATIONS
INPUT RANGES:
INPUT
RANGE
ACCURACY*
(18 to 28°C)
0.03% of reading
+0.03 µA
0.03% of reading
±2 mADC
+0.3 µA
0.03% of reading
±20 mADC
+3µA
0.05% of reading
±200 mADC
+30 µA
0.5% of reading
±2 ADC
+0.3 mA
0.03% of reading
±200 mVDC
+30 µV
0.03% of reading
±2 VDC
+0.3 mV
0.03% of reading
±20 VDC
+3 mV
0.05% of reading
±300 VDC
+30 mV
0.05% of reading
100 ohm
+0.03 ohm
0.05% of reading
1000 ohm
+0.3 ohm
0.05% of reading
10 Kohm
+1 ohm
±200 µADC
ACCURACY*
(0 to 50°C)
IMPEDANCE/
COMPLIANCE
0.12% of reading
+0.04µA
0.12% of reading
+0.4 µA
0.12% of reading
+4 µA
0.15% of reading
+40 µA
0.7% of reading
+0.4 mA
0.12% of reading
+40 µV
0.12% of reading
+0.4 mV
0.12% of reading
+4 mV
0.15% of reading
+40 mV
0.2% of reading
+0.04 ohm
0.2% of reading
+0.4 ohm
0.2% of reading
+1.5 ohm
MAX
CONTINUOUS RESOLUTION
OVERLOAD
1.11 Kohm
15 mA
10 nA
111 ohm
50 mA
0.1 µA
11.1 ohm
150 mA
1 µA
1.1 ohm
500 mA
10 µA
0.1 ohm
3A
0.1 mA
1.066 Mohm
100 V
10 µV
1.066 Mohm
300 V
0.1 mV
1.066 Mohm
300 V
1 mV
1.066 Mohm
300 V
10 mV
0.175 V
30 V
0.01 ohm
1.75 V
30 V
0.1 ohm
17.5 V
30 V
1 ohm
* After 20 minute warm-up. Accuracy is specified in two ways:
Accuracy over an 18 to 28°C and 10 to 75% RH environment; and
accuracy over a 0 to 50°C and 0 to 85% RH (non-condensing
environment). Accuracy over the 0 to 50°C range includes the
temperature coefficient effect of the meter.
EXCITATION POWER:
Transmitter Power: 24 VDC, ±5%, regulated, 50 mA max.
Reference Voltage: 2 VDC, ± 2%
Compliance: 1 kohm load min. (2 mA max.)
Temperature coefficient: 40 ppm/°C max.
Reference Current: 1.75 mADC, ± 2%
Compliance: 10 kohm load max.
Temperature coefficient: 40 ppm/°C max.
Model PAXP - Process Input
 DUAL RANGE INPUT (20 mA or 10 VDC)
 24 VDC TRANSMITTER POWER
PAXP SPECIFICATIONS
SENSOR INPUTS:
INPUT
(RANGE)
ACCURACY*
(18 to 28°C)
ACCURACY*
(0 to 50°C)
MAX
IMPEDANCE/
DISPLAY
CONTINUOUS
COMPLIANCE
RESOLUTION
OVERLOAD
20 mA
0.03% of
0.12% of
(-2 to 26 mA) reading +2 µA reading +3 µA
20 ohm
150 mA
1 µA
10 VDC
0.03% of
0.12% of
(-1 to 13 VDC) reading +2 mV reading +3 mV
500 Kohm
300 V
1 mV
* After 20 minute warm-up. Accuracy is specified in two ways: Accuracy over an 18
to 28°C and 10 to 75% RH environment; and accuracy over a 0 to 50°C and 0 to
85%RH (non-condensing environment). Accuracy over the 0 to 50°C range
includes the temperature coefficient effect of the meter.
EXCITATION POWER:
Transmitter Power: 24 VDC, ±5%, regulated, 50 mA max.
4
Model PAXH - AC True RMS Volt
and
Current
 FOUR VOLTAGE RANGES (300 VAC Max)
 FIVE CURRENT RANGES (5 A Max)
 ACCEPTS AC OR DC COUPLED INPUTS
 THREE WAY ISOLATION: POWER, INPUT AND OUTPUTS
PAXH SPECIFICATIONS
INPUT RANGES:
Isolation To Option Card Commons and User Input Commons: 125 Vrms
Isolation To AC Power Terminals: 250 Vrms
INPUT
RANGE
200 mV
2V
20 V
300 V
200 µA
2 mA
20 mA
200 mA
5A
ACCURACY*
0.1% of reading
+0.4 mV
0.1% of reading
+2 mV
0.1% of reading
+20 mV
0.2% of reading
+0.3 V
0.1% of reading
+0.4 µA
0.1% of reading
+2 µA
0.1% of reading
+20 µA
0.1% of reading
+0.2 mA
0.5% of reading
+5 mA
IMPEDANCE
(60 Hz)
MAX
CONTINUOUS
OVERLOAD
686 Kohm
30 V
±10 V
0.01 mV
686 Kohm
30 V
±50 V
0.1 mV
686 Kohm
300 V
±300 V
1 mV
686 Kohm
300 V
±300 V***
0.1 V
1.11 Kohm
15 mA
±15 mA
0.01 µA
111 ohm
50 mA
±50 mA
0.1 µA
11.1 ohm
150 mA
±150 mA
1 µA
1.1 ohm
500 mA
±500 mA
10 µA
0.02 ohm
7 A**
±7 A***
1 mA
*Conditions for accuracy specification:
- 20 minutes warmup
- 18-28°C temperature range, 10-75% RH non-condensing
- 50 Hz - 400 Hz sine wave input with 1.414 crest factor
- 1% to 100% of range
For conditions outside the above listed:
Temperature from 0-18 and 28-50°C: Add 0.1% reading + 20 counts error
Crest factors:
1-3: Add 0.2% reading + 10 counts error
3-5: Add 1% reading
DC component: Add 0.5% reading + 10 counts
20-50 Hz and 400-10 KHz: Add 1% reading + 20 counts error
** Non-repetitive surge rating: 15 A for 5 seconds
*** Inputs are direct coupled to the input divider and shunts. Input signals with
high DC component levels may reduce the usable range.
MAX DC
RESOLUTION
BLOCKING
MAX CREST FACTOR (Vp/VRMS): 5 @ Full Scale Input
INPUT COUPLING: AC or AC and DC
INPUT CAPACITANCE: 10 pF
COMMON MODE VOLTAGE: 125 VAC working
COMMON MODE REJECTION: (DC to 60 Hz) 100 dB
Model PAXS - Strain Gage Input
 LOAD CELL, PRESSURE AND TORQUE BRIDGE INPUTS
 DUAL RANGE INPUT: ±24 mV OR ±240 mV
 SELECTABLE 5 VDC OR 10 VDC BRIDGE EXCITATION
 PROGRAMMABLE AUTO-ZERO TRACKING
PAXS SPECIFICATIONS
SENSOR INPUTS:
MAX
CONTINUOUS RESOLUTION
OVERLOAD
INPUT RANGE
ACCURACY*
(18 to 28 °C)
ACCURACY*
(0 to 50 °C)
IMPEDANCE
±24 mVDC
0.02% of
reading +3 µV
0.07% of
reading +4 µV
100 Mohm
30 V
1 µV
±240 mVDC
0.02% of
reading +30 µV
0.07% of
reading +40 µV
100 Mohm
30 V
10 µV
* After 20 minute warm-up. Accuracy is specified in two ways: Accuracy over an 18
to 28 °C and 10 to 75% RH environment; and accuracy over a 0 to 50 °C and 0 to
85% RH (non-condensing environment). Accuracy over the 0 to 50 °C range
includes the temperature coefficient effect of the meter.
5
CONNECTION TYPE: 4-wire bridge (differential)
2-wire (single-ended)
COMMON MODE RANGE (w.r.t. input common): 0 to +5 VDC
Rejection: 80 dB (DC to 120 Hz)
BRIDGE EXCITATION :
Jumper Selectable: 5 VDC @ 65 mA max., ±2%
10 VDC @ 125 mA max., ±2%
Temperature coefficient (ratio metric): 20 ppm/°C max.
Model PAXT - Thermocouple
and
RTD Input
 THERMOCOUPLE AND RTD INPUTS
 CONFORMS TO ITS-90 STANDARDS
 CUSTOM SCALING FOR NON-STANDARD PROBES
 TIME-TEMPERATURE INTEGRATOR
PAXT SPECIFICATIONS
READOUT:
Resolution: Variable: 0.1, 0.2, 0.5, or 1, 2, or 5 degrees
Scale: F or C
Offset Range: -19,999 to 99,999 display units
THERMOCOUPLE INPUTS:
Input Impedance: 20 MΩ
Lead Resistance Effect: 0.03µV/ohm
Max. Continuous Overvoltage: 30 V
INPUT
TYPE
RANGE
T
-200 to 400°C
-270 to -200°C
1.2°C
**
2.1°C
E
-200 to 871°C
-270 to -200°C
1.0°C
**
2.4°C
J
-200 to 760°C
1.1°C
2.3°C
K
-200 to 1372°C
-270 to -200°C
1.3°C
**
3.4°C
R
-50 to 1768°C
1.9°C
S
-50 to 1768°C
B
N
C
(W5/W26)
ACCURACY* ACCURACY*
STANDARD
(18 to 28 °C) (0 to 50 °C)
RTD INPUTS:
Type: 3 or 4 wire, 2 wire can be compensated for lead wire resistance
Excitation current: 100 ohm range: 165 µA
10 ohm range: 2.6 mA
Lead resistance: 100 ohm range: 10 ohm/lead max.
10 ohm range: 3 ohms/lead max.
Max. continuous overload: 30 V
WIRE COLOR
ANSI
BS 1843
ITS-90
(+) blue
(-) red
(+) white
(-) blue
ITS-90
(+) purple (+) brown
(-) red
(-) blue
ITS-90
(+) white
(-) red
ITS-90
(+) yellow (+) brown
(-) red
(-) blue
4.0°C
ITS-90
no
standard
(+) white
(-) blue
1.9°C
4.0°C
ITS-90
no
standard
(+) white
(-) blue
100 to 300°C
300 to 1820°C
3.9°C
2.8°C
5.7°C
4.4°C
ITS-90
no
standard
no
standard
-200 to 1300°C
-270 to -200°C
1.3°C
**
3.1°C
ITS-90
(+) orange (+) orange
(-) red
(-) blue
0 to 2315°C
1.9°C
6.1°C
ASTM no
E988-90*** standard
INPUT TYPE
(+) yellow
(-) blue
100 ohm Pt
alpha = .00385
100 ohm Pt
alpha = .003919
120 ohm Nickel
alpha = .00672
10 ohm Copper
alpha = .00427
RANGE
ACCURACY*
(18 to 28 °C)
ACCURACY*
(0 to 50 °C)
STANDARD
***
-200 to 850°C
0.4°C
1.6°C
IEC 751
-200 to 850°C
0.4°C
1.6°C
-80 to 260°C
0.2°C
0.5°C
-100 to 260°C
0.4°C
0.9°C
no official
standard
no official
standard
no official
standard
CUSTOM RANGE: Up to 16 data point pairs
Input range: -10 to 65 mV
0 to 400 ohms, high range
0 to 25 ohms, low range
Display range: -19999 to 99999
no
standard
*After 20 min. warm-up. Accuracy is specified in two ways: Accuracy over an 18
to 28 °C and 15 to 75% RH environment; and Accuracy over a 0 to 50 °C and 0 to
85% RH (non condensing) environment. Accuracy specified over the 0 to 50 °C
operating range includes meter tempco and ice point tracking effects. The
specification includes the A/D conversion errors, linearization conformity, and
thermocouple ice point compensation. Total system accuracy is the sum of meter
and probe errors. Accuracy may be improved by field calibrating the meter readout
at the temperature of interest.
** The accuracy over the interval -270 to -200 °C is a function of temperature,
ranging from 1 °C at -200 °C and degrading to 7 °C at -270 °C. Accuracy may be
improved by field calibrating the meter readout at the temperature of interest.
*** These curves have been corrected to ITS-90.
INPUT TYPE
RANGE
ACCURACY*
(18 to 28 °C)
ACCURACY*
(0 to 50 °C)
Custom
mV range
Custom
100 ohm range
Custom
10 ohm range
-10 to 65mV
(1 µV res.)
0 to 400 Ω
(10 MΩ res.)
0 to 25 Ω
(1 MΩ res.)
0.02% of reading
+ 4µV
0.02% of reading
+ 0.04 Ω
0.04% of reading
+ 0.005 Ω
0.12% of reading
+ 5µV
0.12% of reading
+ 0.05 Ω
0.20% of reading
+ 0.007 Ω
Accessories
UNITS LABEL KIT (PAXLBK) - Not required for PAXT
PROGRAMMING SOFTWARE
Each meter has a units indicator with backlighting that can be customized
using the Units Label Kit. The backlight is controlled in the programming.
Each PAXT meter is shipped with °F and °C overlay labels which can be
installed into the meter’s bezel display assembly.
The Crimson software is a Windows based program that allows configuration
of the PAX meter from a PC. Crimson offers standard drop-down menu
commands, that make it easy to program the meter. The meter’s program can
then be saved in a PC file for future use. A PAX serial plug-in card or PAX USB
programming card is required to program the meter using the software. Crimson
can be downloaded at www.redlion.net.
EXTERNAL CURRENT SHUNTS (APSCM)
To measure DC current signals greater than 2 ADC, a shunt must be used. The
APSCM010 current shunt converts a maximum 10 ADC signal into 100.0 mV.
The APSCM100 current shunt converts a maximum 100 ADC signal into 100.0
mV. The continuous current through the shunt is limited to 115% of the rating.
6
Optional Plug-in Output Cards
Adding Option Cards
WARNING: Disconnect all power to the unit before
installing Plug-in cards.
The PAX and MPAX series meters can be fitted with up to three optional plugin cards. The details for each plug-in card can be reviewed in the specification
section below. Only one card from each function type can be installed at one time.
The function types include Setpoint Alarms (PAXCDS), Communications
(PAXCDC), and Analog Output (PAXCDL). The plug-in cards can be installed
initially or at a later date.
SETPOINT CARDS (PAXCDS)
The PAX and MPAX series has 4 available setpoint alarm output plug-in
cards. Only one of these cards can be installed at a time. (Logic state of the
outputs can be reversed in the programming.) These plug-in cards include:
PAXH Isolation Specifications For All Option Cards
Isolation To Sensor Commons: 1400 Vrms for 1 min.
Working Voltage: 125 V
Isolation to User Input Commons: 500 Vrms for 1 min.
Working Voltage 50 V
PAXCDS10 - Dual Relay, FORM-C, Normally open & closed
PAXCDS20 - Quad Relay, FORM-A, Normally open only
PAXCDS30 - Isolated quad sinking NPN open collector
PAXCDS40 - Isolated quad sourcing PNP open collector
COMMUNICATION CARDS (PAXCDC)
DUAL RELAY CARD
Type: Two FORM-C relays
Isolation To Sensor & User Input Commons: 2000 Vrms for 1 min.
Working Voltage: 240 Vrms
Contact Rating:
One Relay Energized: 5 amps @ 120/240 VAC or 28 VDC (resistive load),
1/8 HP @120 VAC, inductive load.
Total current with both relays energized not to exceed 5 amps
Life Expectancy: 100 K cycles min. at full load rating. External RC snubber
extends relay life for operation with inductive loads
A variety of communication protocols are available for the PAX and MPAX
series. Only one of these cards can be installed at a time. When programming
the unit via Crimson, a Windows® based program, the RS232, RS485, or USB
Cards must be used.
PAXCDC10 - RS485 Serial (Terminal)
PAXCDC1C - RS485 Serial (Connector)
PAXCDC20 - RS232 Serial (Terminal)
PAXCDC2C - RS232 Serial (Connector)
PAXUSB00 - USB (Mini B)
PAXCDC30 - DeviceNet
PAXCDC40 - Modbus (Terminal)
PAXCDC4C - Modbus (Connector)
PAXCDC50 - Profibus-DP
QUAD RELAY CARD
Type: Four FORM-A relays
Isolation To Sensor & User Input Commons: 2300 Vrms for 1 min.
Working Voltage: 250 Vrms
Contact Rating:
One Relay Energized: 3 amps @ 240 VAC or 30 VDC (resistive load), 1/10
HP @120 VAC, inductive load.
Total current with all four relays energized not to exceed 4 amps
Life Expectancy: 100K cycles min. at full load rating. External RC snubber
extends relay life for operation with inductive loads
SERIAL COMMUNICATIONS CARD
Type: RS485 or RS232
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V. Not Isolated from all other commons.
Data: 7/8 bits
Baud: 300 to 19,200
Parity: No, Odd or Even
Bus Address: Selectable 0 to 99, Max. 32 meters per line (RS485)
Transmit Delay: Selectable for 2 to 50 msec or 50 to 100 msec (RS485)
QUAD SINKING OPEN COLLECTOR CARD
Type: Four isolated sinking NPN transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V. Not Isolated from all other commons.
Rating: 100 mA max @ VSAT = 0.7 V max. VMAX = 30 V
DEVICENET™ CARD
Compatibility: Group 2 Server Only, not UCMM capable
Baud Rates: 125 Kbaud, 250 Kbaud, and 500 Kbaud
Bus Interface: Phillips 82C250 or equivalent with MIS wiring protection per
DeviceNet™ Volume I Section 10.2.2.
Node Isolation: Bus powered, isolated node
Host Isolation: 500 Vrms for 1 minute (50 V working) between DeviceNet™
and meter input common.
QUAD SOURCING OPEN COLLECTOR CARD
Type: Four isolated sourcing PNP transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V. Not Isolated from all other commons.
Rating: Internal supply: 24 VDC ± 10% , 30 mA max. total
External supply: 30 VDC max., 100 mA max. each output
MODBUS CARD
Type: RS485; RTU and ASCII MODBUS modes
Isolation To Sensor & User Input Commons: 500 Vrms for 1 minute.
Working Voltage: 50 V. Not isolated from all other commons.
Baud Rates: 300 to 38400.
Data: 7/8 bits
Parity: No, Odd, or Even
Addresses: 1 to 247.
Transmit Delay: Programmable; See Transmit Delay explanation.
ALL FOUR SETPOINT CARDS
Response Time: 200 msec. max. to within 99% of final readout value (digital
filter and internal zero correction disabled)
700 msec. max. (digital filter disabled, internal zero correction enabled)
LINEAR DC OUTPUT (PAXCDL)
Either a 0(4)-20 mA or 0-10 V retransmitted linear DC output is available
from the analog output plug-in card. The programmable output low and high
scaling can be based on various display values. Reverse slope output is possible
by reversing the scaling point positions.
PROFIBUS-DP CARD
Fieldbus Type: Profibus-DP as per EN 50170, implemented with Siemens
SPC3 ASIC
Conformance: PNO Certified Profibus-DP Slave Device
Baud Rates: Automatic baud rate detection in the range 9.6 Kbaud to 12 Mbaud
Station Address: 0 to 125, set by rotary switches.
Connection: 9-pin Female D-Sub connector
Network Isolation: 500 Vrms for 1 minute (50 V working) between Profibus
network and sensor and user input commons. Not isolated from all other
commons.
PAXCDL10 - Retransmitted Analog Output Card
ANALOG OUTPUT CARD
Types: 0 to 20 mA, 4 to 20 mA or 0 to 10 VDC
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V. Not Isolated from all other commons.
Accuracy: 0.17% of FS (18 to 28 °C); 0.4% of FS (0 to 50 °C)
Resolution: 1/3500
Compliance: 10 VDC: 10 KΩ load min., 20 mA: 500 Ω load max.
Powered: Self-powered (Active)
Update time: 200 msec. max. to within 99% of final output value (digital
filter and internal zero correction disabled)
700 msec. max. (digital filter disabled, internal zero correction enabled)
PAXUSB PROGRAMMING CARD
Type: USB Virtual Comms Port
Connection: Type mini B
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V. Not Isolated from all other commons.
Baud Rate: 300 to 19.2k
Unit Address: 0 to 99; only 1 meter can be configured at a time
7
1.0 Installing
the
Meter
Installation
While holding the unit in place, push the panel latch over the rear of the unit
so that the tabs of the panel latch engage in the slots on the case. The panel
latch should be engaged in the farthest forward slot possible. To achieve a
proper seal, tighten the latch screws evenly until the unit is snug in the panel
(Torque to approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.
The PAX meets NEMA 4X/IP65 requirements when properly installed. The
unit is intended to be mounted into an enclosed panel. Prepare the panel cutout
to the dimensions shown. Remove the panel latch from the unit. Slide the panel
gasket over the rear of the unit to the back of the bezel. The unit should be
installed fully assembled. Insert the unit into the panel cutout.
Installation Environment
The unit should be installed in a location that does not exceed the maximum
operating temperature and provides good air circulation. Placing the unit near
devices that generate excessive heat should be avoided.
The bezel should be cleaned only with a soft cloth and neutral soap product.
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate
the aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the
keypad of the unit.
PANEL
BEZEL
LATCHING
SLOTS
PANEL
LATCH
PANEL CUT-OUT
LATCHING
TABS
3.62 +.03
-.00
(92 +.8
-.0 )
PANEL
GASKET
1.77+.02
-.00
(45 +.5
-.0 )
PANEL
MOUNTING
SCREWS
2.0 Setting
the
Jumpers
The meter can have up to four jumpers that must be checked and / or changed
prior to applying power. The following Jumper Selection Figures show an
enlargement of the jumper area.
To access the jumpers, remove the meter base from the case by firmly
squeezing and pulling back on the side rear finger tabs. This should lower the
latch below the case slot (which is located just in front of the finger tabs). It is
recommended to release the latch on one side, then start the other side latch.
User Input Logic Jumper
This jumper selects the logic state of all the user inputs. If the user inputs are
not used, it is not necessary to check or move this jumper.
PAXH:
Signal Jumper
Input Range Jumper
This jumper is used to select the proper input range. The input range selected
in programming must match the jumper setting. Select a range that is high enough
to accommodate the maximum input to avoid overloads. The selection is different
for each meter. See the Jumper Selection Figure for appropriate meter.
This jumper is used to select the signal type. For current signals, the jumper
is installed. For voltage signals, remove the jumper from the board. (For 2 V
inputs, this removed jumper can be used in the “2 V only” location.)
Excitation Output Jumper
This jumper is used for AC / DC couple. If AC couple, then the jumper is
removed from the board. If DC couple is used, then the jumper is installed.
Couple Jumper
If your meter has excitation, this jumper is used to select the excitation range
for the application. If excitation is not being used, it is not necessary to check or
move this jumper.
PAXD Jumper Selection
Input Range Jumper
One jumper is used for voltage/ohms or current input ranges. Select the proper input range high
enough to avoid input signal overload. Only one jumper is allowed in this area. Do not have a jumper
in both the voltage and current ranges at the same time. Avoid placing the jumper across two ranges.
JUMPER SELECTIONS
The
Main
Circuit
Board
indicates factory setting.
JUMPER
LOCATION
VOLT/
OHM
8
CURRENT
JUMPER
LOCATION
EXCITATION
USER INPUT
PAXP Jumper Selection
Main
Circuit
Board
JUMPER SELECTIONS
The
indicates factory setting.
USER INPUT LOGIC JUMPER
SINK
SOURCE
REAR TERMINALS
USER INPUT
JUMPER
LOCATION
PAXH Jumper Selection
CAUTION: To maintain the electrical safety of the meter, remove
unneeded jumpers completely from the meter. Do not move the
jumpers to positions other than those specified.
JUMPER SELECTIONS
The
indicates factory setting.
INPUT RANGE
Main
Circuit
Board
2 V ONLY
200 mA
20 mA
2 mA
200 µA
SIGNAL
VOLTAGE: OFF
CURRENT: ON
COUPLE
AC: OFF
DC: ON
SOURCE
Jumper
Locations
RANGES
CURRENT
VOLTAGE
SINK
2 V ONLY
300 V
20 V
.2V/2V
CURR/VOLT
SIGNAL
AC/DC COUPLE
USER INPUT
USER INPUT
REAR TERMINALS
Input Range Jumper
For most inputs, one jumper is used to select the input range. However, for
the following ranges, set the jumpers as stated:
5 A: Remove all jumpers from the input range.
2 V: Install one jumper in “.2/2V” position and one jumper in “2 V only”.
All Other Ranges: One jumper in the selected range only.
Do not have a jumper in both the voltage and current ranges at the same time.
Avoid placing a jumper across two ranges.
Signal Jumper
One jumper is used for the input signal type. For current signals, the jumper
is installed. For voltage signals, remove the jumper from the board. (For 2 V
inputs, this removed jumper can be used in the “2 V only” location.)
Couple Jumper
One jumper is used for AC / DC couple. If AC couple is used, then the jumper
is removed from the board. If DC couple is used, then the jumper is installed.
PAXS Jumper Selection
Bridge Excitation
One jumper is used to select bridge excitation to allow use of the higher sensitivity 24 mV input
range. Use the 5 V excitation with high output (3 mV/V) bridges. The 5 V excitation also reduces
bridge power compared to 10 V excitation.
A maximum of four 350 ohm load cells can be driven by the internal bridge excitation voltage.
Main
Circuit
Board
JUMPER SELECTIONS
The
BRIDGE
EXCITATION
5V
10V
indicates factory setting.
INPUT RANGE
±24mV
±240mV
USER INPUT
JUMPER
LOCATION
SINK
SOURCE
BRIDGE
JUMPER
LOCATION
USER INPUT
INPUT RANGE
REAR TERMINALS
9
PAXT Jumper Selection
RTD Input Jumper
One jumper is used for RTD input ranges. Select the proper range to match
the RTD probe being used. It is not necessary to remove this jumper when
not using RTD probes.
Main
Circuit
Board
JUMPER SELECTIONS
The
JUMPER
LOCATION
RTD INPUT JUMPER
JUMPER
LOCATION
RTD
INPUT
100 ohms
10 ohms
indicates factory setting.
USER INPUT LOGIC JUMPER
SINK
SOURCE
USER INPUT
REAR TERMINALS
3.0 Installing Plug-In Cards
To Install:
The plug-in cards are separately purchased optional cards that perform
specific functions. These cards plug into the main circuit board of the meter. The
plug-in cards have many unique functions when used with the PAX.
1. With the meter removed from the case, locate the plug-in card connector for
the card type to be installed. The types are keyed by position with different
main circuit board connector locations. When installing the card, hold the
meter by the rear terminals and not by the front display board.
If installing the Quad sourcing Plug-in Card (PAXCDS40), set the jumper for
internal or external supply operation before continuing.
CAUTION: The plug-in card and main circuit board contain static
sensitive components. Before handling the cards, discharge static
charges from your body by touching a grounded bare metal
object. Ideally, handle the cards at a static controlled clean
workstation. Also, only handle the cards by the edges. Dirt, oil or
other contaminants that may contact the cards can adversely
affect circuit operation.
Alignment
Slots
Main
Circuit
Board
Internal Supply
(18 V unregulated)
External Supply
(30 V max )
TOP VIEW
2. Install the plug-in card by aligning the card terminals with the slot bay in the
rear cover. Be sure the connector is fully engaged and the tab on the plug-in
card rests in the alignment slot on the display board.
3. Slide the meter base back into the case. Be sure the rear cover latches fully
into the case.
4. Apply the plug-in card label to the bottom side of the meter in the designated
area. Do Not Cover the vents on the top surface of the meter. The surface of
the case must be clean for the label to adhere properly.
Analog Output
Card
Connectors
Serial
Communications
Card
Finger
Tab
Setpoint
Output
Card
Finger
Tab
10
4.0 Wiring
the
Meter
WIRING OVERVIEW
4. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
5. Signal or Control cables within an enclosure should be routed as far away as
possible from contactors, control relays, transformers, and other noisy
components.
6. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional
protection. Install line filters on the power input cable to the unit to suppress
power line interference. Install them near the power entry point of the
enclosure. The following EMI suppression devices (or equivalent) are
recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC #FCOR0000)
TDK # ZCAT3035-1330A
Steward #28B2029-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC #LFIL0000)
Schaffner # FN670-1.8/07
Corcom #1VR3
Note: Reference manufacturer’s instructions when installing a line filter.
7. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
8. Switching of inductive loads produces high EMI. Use of snubbers across
inductive loads suppresses EMI.
Snubber: RLC#SNUB0000.
Electrical connections are made via screw-clamp terminals located on the
back of the meter. All conductors should conform to the meter’s voltage and
current ratings. All cabling should conform to appropriate standards of good
installation, local codes and regulations. It is recommended that power supplied
to the meter (DC or AC) be protected by a fuse or circuit breaker.
When wiring the meter, compare the numbers embossed on the back of the
meter case against those shown in wiring drawings for proper wire position.
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed (stranded
wires should be tinned with solder). Insert the lead under the correct screwclamp terminal and tighten until the wire is secure. (Pull wire to verify
tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).
EMC INSTALLATION GUIDELINES
Although this meter is designed with a high degree of immunity to ElectroMagnetic Interference (EMI), proper installation and wiring methods must be
followed to ensure compatibility in each application. The type of the electrical
noise, its source or the method of coupling into the unit may be different for
various installations.Listed below are some EMC guidelines for successful
installation in an industrial environment.
1. The meter should be mounted in a metal enclosure, which is properly
connected to protective earth.
2. With use of the lower input ranges or signal sources with high source
impedance, the use of shielded cable may be necessary. This helps to guard
against stray AC pick-up. Attach the shield to the input common of the meter.
Line voltage monitoring and 5A CT applications do not usually require
shielding.
3. To minimize potential noise problems, power the meter from the same power
branch, or at least the same phase voltage as that of the signal source.
2
Terminal 1: +VDC
Terminal 2: -VDC
DC-
1
DC Power
DC+
Terminal 1: VAC
Terminal 2: VAC
AC
AC Power
AC
4.1 POWER WIRING
1
2
+
-
4.2 INPUT SIGNAL WIRING
PAXD INPUT SIGNAL WIRING
Before connecting signal wires, the Input Range Jumper and Excitation Jumper should be verified for proper position.
+
-
300VDC MAX.
5
+24V
2 WIRE
2A DC MAX.
- TRANSMITTER
+
11
Terminal 3: +VDC (signal)
Terminal 5: -VDC (common)
Terminal 6: +Volt supply
Excitation Jumper: 24 V
+24 V EXC.
6
Voltage Signal (3 wire
requiring excitation)
COMM.
5
Terminal 4: +ADC (signal)
Terminal 5: -ADC (common)
Terminal 6: +Volt supply
Excitation Jumper: 24 V
20 mA
4
Load
Current Signal (3 wire
requiring excitation)
10 V
COMM.
-
+24 V EXC.
5
4
Terminal 4: -ADC
Terminal 6: +ADC
Excitation Jumper: 24 V
COMM.
4
+
Current Signal (2 wire
requiring excitation)
CURRENT
3
Terminal 4: +ADC
Terminal 5: -ADC
COMM.
CURRENT
VOLT/OHM
Terminal 3: +VDC
Terminal 5: -VDC
Current Signal
(self powered)
CURRENT
Voltage Signal
(self powered)
3
4
5
6
Vout
Iout
COMM.
3 WIRE TRANSMITTER
+Vs
6
1.75 mA
REF.
10K MAX.
+EXCITATION
5
COMM.
+EXCITATION
4
Terminal 3: Wiper
Terminal 5: Low end of pot.
Terminal 6: High end of pot.
Excitation Jumper: 2 V REF.
Input Range Jumper: 2 Volt
Module 1 Input Range: 2 Volt
Note: The Apply signal scaling style
should be used because the signal
will be in volts.
CURRENT
COMM.
3
Potentiometer Signal
(3 wire requiring excitation)
VOLT/OHM
CURRENT
Terminal 3: Resistance
Terminal 5: Resistance
Terminal 6: Jumper to
terminal 3
Excitation Jumper:
1.75 mA REF.
VOLT/OHM
Resistance Signal
(3 wire requiring
excitation)
3
4
5
6
2V
INPUT
2V REF.
Rmin=1KΩ
CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safety of the meter application, the sensor input
common must be suitably isolated from hazardous live earth referenced voltages; or input common must be at protective earth ground potential. If not,
hazardous live voltage may be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the
potential of the user input common with respect to earth common; and the common of the isolated plug-in cards with respect to input common.
PAXP INPUT SIGNAL WIRING
+
+
-
-
6
LOAD
10 VDC MAX.
Terminal 3: +VDC (signal)
Terminal 5: -VDC (common)
Terminal 6: +Volt supply
+24V
20 mA DC MAX.
-
2 WIRE
TRANSMITTER
+24 V EXC.
5
COMM.
4
Voltage Signal (3 wire
requiring excitation)
20 mA
5
Terminal 4: +ADC (signal)
Terminal 5: -ADC (common)
Terminal 6: +Volt supply
10 V
4
+24 V EXC.
5
COMM.
COMM.
4
Current Signal (3 wire
requiring excitation)
Terminal 4: -ADC
Terminal 6: +ADC
CURRENT
20 mA
3
Current Signal (2 wire
requiring excitation)
Terminal 4: +ADC
Terminal 5: -ADC
COMM.
10 V
Terminal 3: +VDC
Terminal 5: -VDC
Current Signal
(self powered)
20 mA
Voltage Signal
(self powered)
3
4
5
6
Vout
Iout
COMM.
3 WIRE TRANSMITTER
+Vs
+
CAUTION: Sensor input common is NOT isolated from user input common. In order to preserve the safety of the meter application, the sensor input
common must be suitably isolated from hazardous live earth referenced voltages; or input common must be at protective earth ground potential. If not,
hazardous live voltage may be present at the User Inputs and User Input Common terminals. Appropriate considerations must then be given to the
potential of the user input common with respect to earth common; and the common of the isolated plug-in cards with respect to input common.
PAXH INPUT SIGNAL WIRING
Before connecting signal wires, the Signal, Input Range and Couple Jumpers
should be verified for proper position.
4
Neutral
300V MAX. AC
Load
Line (Hot)
5A AC MAX.
CURRENT
3
COMM.
COMM.
6
Current Signal (Milliamps)
4
5
Neutral
5 AMP
5
Neutral
VOLT
4
Line (Hot)
CURRENT
Current Signal (Amps)
COMM.
Voltage Signal
CAUTION: Connect only one input signal range to the
meter. Hazardous signal levels may be present on
unused inputs.
Load
Line (Hot)
CAUTION: The isolation rating of the input common of the
meter with respect to the option card commons and the
user input common Terminal 8 (If used) is 125 Vrms; and
250 Vrms with respect to AC Power (meter Terminals 1 &
2). To be certain that the ratings are not exceeded, these
voltages should be verified by a high-voltage meter before
wiring the meter.
200mA AC MAX.
CAUTION:
1. Where possible, connect the neutral side of the signal (including current shunts) to the input common of the meter. If the input signal is sourced from
an active circuit, connect the lower impedance (usually circuit common) to the input signal common of the meter.
2. For phase-to-phase line monitoring where a neutral does not exist, or for any other signal input in which the isolation voltage rating is exceeded, an isolating potential
transformer must be used to isolate the input voltage from earth. With the transformer, the input common of the meter can then be earth referenced for safety.
3. When measuring line currents, the use of a current transformer is recommended. If using external current shunts, insert the shunt in the neutral return line. If the
isolation voltage rating is exceeded, the use of an isolating current transformer is necessary.
12
PAXS INPUT SIGNAL WIRING
Before connecting signal wires, the Input Range Jumper should be verified for proper position.
4-Wire Bridge Input
+EXC
+SIG
-SIG
COMM.
+EXC
5
COMM.
COMM
4
-SIG
- SIG
3
3
4
5
6
3
4
5
6
+SEN
+EXC.
-
+
6-Wire Bridge Input
+SIG
+ SIG
2-Wire Single
Ended Input
+EXC.
+SIG.
-SIG.
+SIG.
-EXC.
-SIG.
-SEN
-EXC.
DEADLOAD COMPENSATION
BRIDGE COMPLETION RESISTORS
In some cases, the combined deadload and liveload output may exceed the
range of the 24 mV input. To use this range, the output of the bridge can be offset
a small amount by applying a fixed resistor across one arm of the bridge. This
shifts the electrical output of the bridge downward to within the operating range
of the meter. A 100 K ohm fixed resistor shifts the bridge output approximately
-10 mV (350 ohm bridge, 10 V excitation).
Connect the resistor between +SIG and -SIG. Use a metal film resistor with
a low temperature coefficient of resistance.
For single strain gage applications, bridge completion resistors must be
employed externally to the meter. Only use metal film resistors with a low
temperature coefficient of resistance.
Load cells and pressure transducers are normally implemented as full
resistance bridges and do not require bridge completion resistors.
PAXT INPUT SIGNAL WIRING
3-Wire RTD
RTD
TC+
COMM.
5
COMM.
COMM.
4
TC+
TC+
3
3
4
5
3
4
5
-
+
2-Wire RTD
RTD
RTD
Thermocouple
Sense Lead
Sense Lead
RTD (Excitation)
Jumper
CAUTION: Sensor input common is NOT isolated
from user input common. In order to preserve the
safety of the meter application, the sensor input
common must be suitably isolated from hazardous
live earth referenced voltages; or input common
must be at protective earth ground potential. If not,
hazardous live voltage may be present at the User
Inputs and User Input Common terminals.
Appropriate considerations must then be given to the
potential of the user input common with respect to
earth common; and the common of the isolated plugin cards with respect to input common.
4.3 USER INPUT WIRING
USER COMM.
USER1
USER2
USER3
Terminal 8-10: + VDC thru external switching device
Terminal 7: -VDC thru external switching device
7
8
9
10
In this logic, the user inputs of the meter are
internally pulled down to 0 V with 22 K
resistance. The input is active when a voltage
greater than 3.6 VDC is applied.
-
USER3
}
Connect external switching device between
appropriate User Input terminal and User Comm.
In this logic, the user inputs of the
meter are internally pulled up to +5 V
with 22 K resistance. The input is active
when it is pulled low (<0 .9 V).
USER2
Sourcing Logic
Terminal 8-10:
Terminal 7:
USER1
Sinking Logic
USER COMM.
Before connecting the wires, the User Input Logic Jumper should be verified for proper position. If not using User
Inputs, then skip this section. Only the appropriate User Input terminal has to be wired.
7
8
9
10
+
V SUPPLY (30V max.)
13
10
11
USER3
9
In this logic, the user inputs of the meter are
internally pulled down with 22 K resistance.
The input is active when a voltage greater
than 3.6 VDC is applied.
USER2
USER3
8
Terminals 9-11:
+ VDC through external switching device
Terminal 8:
-VDC through external switching device
USER1
USER2
In this logic, the user inputs of the
meter are internally pulled up to +5 V
with 22 K resistance. The input is
active when it is pulled low (<0 .9 V).
Sourcing Logic
USER1
}
Terminals 9-11 Connect external
switching device between
Terminal 8
appropriate User Input
terminal and User Comm.
USER COMM
Sinking Logic
USER COMM
PAXH ONLY
8
9
10
11
-
+
V SUPPLY (30V max.)
4.4 SETPOINT (ALARMS) WIRING
4.5 SERIAL COMMUNICATION WIRING
4.6 ANALOG OUTPUT WIRING
5.0 Reviewing
Display
Readout
Legends*
MA X
MI N
T OT
the



See appropriate plug-in card bulletin for details.
Front Buttons
and
Optional Custom
Units Overlay
A
S P1
DSP
S P2
PAR
S P3
S P4
F2
RST
F1
Display
Setpoint Alarm
Annunciators
KEY
DISPLAY MODE OPERATION
PROGRAMMING MODE OPERATION
DSP
Index display through max/min/total/input readouts
Quit programming and return to display mode
PAR
Access parameter list
Store selected parameter and index to next parameter
F1
Function key 1; hold for 3 seconds for Second Function 1**
Increment selected parameter value
F2
Function key 2; hold for 3 seconds for Second Function 2**
Decrement selected parameter value
RST
Reset (Function key)**
Hold with F1, F2 to scroll value by x1000
* Display Readout Legends may be locked out in Factory Settings.
** Factory setting for the F1, F2, and RST keys is NO mode.
14
6.0 Programming
OVERVIEW
DISPLAY
MODE
MAIN MENU
PROGRAMMING
MENU
PAR
NO
Pro
Meter
the
Signal
Input
Parameters
User Input/
Function
Key
Parameters
Display/
Program
Lock-out
Parameters
Secondary
Function
Parameters
Totalizer
(Integrator)
Parameters
Setpoint*
(Alarm)
Parameters
Serial*
Communication
Parameters
Analog*
Output
Parameters
Factory
Service
Operations
F1/F2
Keys
PAR
1-INP
PAR
2-FNC
PAR
3-LOC
PAR
PAR
4-SEC
5-tOt
PAR
6-SPt
PAR
7-SrL
PAR
8-Out
PAR
9-FCS
* Only accessible with appropriate plug-in card.
STEP BY STEP PROGRAMMING INSTRUCTIONS:
DISPLAY MODE
The meter normally operates in the Display Mode. In this mode, the meter
displays can be viewed consecutively by pressing the DSP key. The annunciators
to the left of the display indicate which display is currently shown; Max Value
(MAX), Min Value (MIN), or Totalizer Value (TOT). Each of these displays can
be locked from view through programming. (See Module 3) The Input Display
Value is shown with no annunciator.
PROGRAMMING MODE ENTRY (PAR KEY)
The Programming Mode is entered by pressing the PAR key. If this mode is
not accessible, then meter programming is locked by either a security code or a
hardware lock. (See Modules 2 and 3 for programming lock-out details.)
MODULE ENTRY (ARROW & PAR KEYS)
PROGRAMMING MODE
Upon entering the Programming Mode, the display alternates between 
and the present module (initially ). The arrow keys (F1 and F2) are used
to select the desired module, which is then entered by pressing the PAR key.
Two programming modes are available.
Full Programming Mode permits all parameters to be viewed and modified.
Upon entering this mode, the front panel keys change to Programming Mode
operations. This mode should not be entered while a process is running, since
the meter functions and User Input response may not operate properly while
in Full Programming Mode.
Quick Programming Mode permits only certain parameters to be viewed and/
or modified. When entering this mode, the front panel keys change to
Programming Mode operations, and all meter functions continue to operate
properly. Quick Programming Mode is configured in Module 3. The Display
Intensity Level “” parameter is available in the Quick Programming
Mode only when the security code is non-zero. For a description, see Module
9—Factory Service Operations. Throughout this document, Programming
Mode (without Quick in front) always refers to “Full” Programming Mode.
PARAMETER (MODULE) MENU (PAR KEY)
Each module has a separate parameter menu. These menus are shown at the
start of each module description section which follows. The PAR key is pressed
to advance to a particular parameter to be changed, without changing the
programming of preceding parameters. After completing a module, the display
will return to  . From this point, programming may continue by selecting
and entering additional modules. (See MODULE ENTRY above.)
PARAMETER SELECTION ENTRY (ARROW & PAR KEYS)
For each parameter, the display alternates between the parameter and the
present selection or value for that parameter. For parameters which have a list
of selections, the arrow keys (F1 and F2) are used to sequence through the
list until the desired selection is displayed. Pressing the PAR key stores and
activates the displayed selection, and also advances the meter to the next
parameter.
PROGRAMMING TIPS
The Programming Menu is organized into nine modules (See above). These
modules group together parameters that are related in function. It is
recommended to begin programming with Module 1 and proceed through each
module in sequence. Note that Modules 6 through 8 are only accessible when
the appropriate plug-in option card is installed. If lost or confused while
programming, press the DSP key to exit programming mode and start over.
When programming is complete, it is recommended to record the meter settings
on the Parameter Value Chart and lock-out parameter programming with a User
Input or lock-out code. (See Modules 2 and 3 for lock-out details.)
NUMERICAL VALUE ENTRY (ARROW, RST & PAR KEYS)
For parameters which require a numerical value entry, the arrow keys can be
used to increment or decrement the display to the desired value. When an arrow
key is pressed and held, the display automatically scrolls up or scrolls down.
The longer the key is held, the faster the display scrolls.
The RST key can be used in combination with the arrow keys to enter large
numerical values. When the RST key is pressed along with an arrow key, the
display scrolls by 1000’s. Pressing the PAR key stores and activates the
displayed value, and also advances the meter to the next parameter.
FACTORY SETTINGS
Factory Settings may be completely restored in Module 9. This is a good
starting point if encountering programming problems. Throughout the module
description sections which follow, the factory setting for each parameter is
shown below the parameter display. In addition, all factory settings are listed on
the Parameter Value Chart following the programming section.
PROGRAMMING MODE EXIT (DSP KEY or PAR KEY at 
ALTERNATING SELECTION DISPLAY
In the module description sections which follow, the dual display with
arrows appears for each programming parameter. This is used to illustrate the
display alternating between the parameter (top display) and the parameter's
Factory Setting (bottom display). In most cases, selections or value ranges for
the parameter will be listed on the right.
Indicates Program Mode Alternating Display
Parameter
 


)
The Programming Mode is exited by pressing the DSP key (from anywhere
in the Programming Mode) or the PAR key (with   displayed). This will
commit any stored parameter changes to memory and return the meter to the
Display Mode. If a parameter was just changed, the PAR key should be pressed
to store the change before pressing the DSP key. (If power loss occurs before
returning to the Display Mode, verify recent parameter changes.)
Selection/Value
15
6.1 MODULE 1 - Signal Input Parameters ()
1-INP
PAX PARAMETER MENU
PAXH
ONLY
PAR
rAN6E
COUPL
dECPt
round
FILtr
Input
Range
Input
Couple
Display
Decimal Point
Display
Rounding
Filter
Setting
bANd
Pro
PtS
Filter
Band
StYLE
INP x
dSP x
Scaling
Style
Input x
Value
Display x
Value
Scaling
Points
PAXT PARAMETER MENU
1-INP
Pro
PAR
tYPE
SCALE
dECPt
Input
Type
Temperature
Scale
Display
Decimal Point
round
Display
Rounding
OFFSt
FILtr
bANd
ICE
Display
Offset
Filter
Setting
Filter
Band
Ice Point
Slope
Refer to the appropriate Input Range for the selected
meter. Use only one Input Range, then proceed to Display
Decimal Point.
SELECTION






RANGE
RESOLUTION
SELECTION
±200.00 µA






±2.0000 mA
±20.000 mA
±200.00 mA
±2.0000 A
±200.00 mV
 
 
RANGE
RESOLUTION
±20.000 V
 
 
100.00 ohm
1000.0 ohm
10000 ohm
20.000 mA
10.000 V
RANGE
SELECTION
RESOLUTION
RANGE
SELECTION
RESOLUTION
200.00 mV
2.0000 V
20.000 V
300.0 V
200.00 µA




TYPE








C TC
E TC
J TC
K TC
R TC
S TC
B TC
N TC
RTD platinum 385
RTD platinum 392
RTD nickel 672
RTD copper 10 Ω
Custom TC
Custom RTD High
Custom RTD Low


DISPLAY DECIMAL POINT
 










or
SELECTION
T TC
Select the temperature scale. This selection applies for Input, MAX, MIN,
and TOT displays. This does not change the user installed Custom Units
Overlay display. If changed, those parameters that relate to the temperature
scale should be checked. This selection is not available for custom sensor types.
2.0000 mA
20.000 mA
200.00 mA
5.000 A
PAXH INPUT COUPLE

TYPE








 


Select the input range that corresponds to the external signal. This selection
should be high enough to avoid input signal overload but low enough for the
desired input resolution. This selection and the position of the Input Range
Jumper must match.
 


SELECTION
PAXT TEMPERATURE SCALE
PAXH INPUT RANGE





±24 mV
±240 mV


Select the input type that corresponds to the input sensor. For RTD types,
check the RTD Input Jumper for matching selection. For custom types, the
Temperature Scale parameter is not available, the Display Decimal Point is
expanded, and Custom Sensor Scaling must be completed.
Select the input range that corresponds to the external signal.
 


RANGE
RESOLUTION
SELECTION
PAXT INPUT TYPE
±300.00 V
RANGE
RESOLUTION


Display x
Value
±2.0000 V
PAXP INPUT RANGE
SELECTION
Scaling
Input x
Points
Value
Custom Scaling Only
Select the input range that corresponds to the external signal. This selection
should be high enough to avoid input signal overload but low enough for the
desired input resolution. This selection and the position of the Input Range
Jumper must match.
Select the input range that corresponds to the external signal. This selection
should be high enough to avoid input signal overload but low enough for the
desired input resolution. This selection and the position of the Input Range
Jumper must match.
 
 
dSP x
PAXS INPUT RANGE
PAXD INPUT RANGE
 
 
INP x
PtS
For the PAXT, these are only
available with Custom Scaling.

Select the decimal point location for the Input, MAX and MIN displays. (The
TOT display decimal point is a separate parameter.) This selection also affects
,  and  parameters and setpoint values.
The input signal can be either AC coupled (rejecting the DC components of
the signal) or DC coupled (measures both the AC and DC components of the
signal). The coupling jumper and the setting of this parameter must match.
16
DISPLAY ROUNDING*




SCALING POINTS*
 






 




 to 
Linear - Scaling Points (2)
These bottom selections are not
available for the PAXT.
For linear processes, only 2 scaling points are necessary. It is recommended
that the 2 scaling points be at opposite ends of the input signal being applied.
The points do not have to be the signal limits. Display scaling will be linear
between and continue past the entered points up to the limits of the Input Signal
Jumper position. Each scaling point has a coordinate-pair of Input Value ()
and an associated desired Display Value ().
Rounding selections other than one, cause the Input Display to ‘round’ to the
nearest rounding increment selected (ie. rounding of ‘5’ causes 122 to round to
120 and 123 to round to 125). Rounding starts at the least significant digit of
the Input Display. Remaining parameter entries (scaling point values, setpoint
values, etc.) are not automatically adjusted to this display rounding selection.
Nonlinear - Scaling Points (Greater than 2)
For non-linear processes, up to 16 scaling points may be used to provide a
piece-wise linear approximation. (The greater the number of scaling points
used, the greater the conformity accuracy.) The Input Display will be linear
between scaling points that are sequential in program order. Each scaling point
has a coordinate-pair of Input Value () and an associated desired Display
Value (). Data from tables or equations, or empirical data could be used to
derive the required number of segments and data values for the coordinate pairs.
In the SFPAX software, several linearization equations are available.
PAXT: TEMPERATURE DISPLAY OFFSET*
 


 to 
The temperature display can be corrected with an offset value. This can be
used to compensate for probe errors, errors due to variances in probe placement
or adjusting the readout to a reference thermometer. This value is automatically
updated after a Zero Display to show how far the display is offset. A value of
zero will remove the affects of offset.
SCALING STYLE
This parameter does not apply for the PAXT. Scaling values for the
PAXT must be keyed-in.
FILTER SETTING*
 


 
 
 to  seconds
FILTER BAND*
INPUT VALUE FOR SCALING POINT 1
 to  display units
  
 
The digital filter will adapt to variations in the input signal. When the
variation exceeds the input filter band value, the digital filter disengages. When
the variation becomes less than the band value, the filter engages again. This
allows for a stable readout, but permits the display to settle rapidly after a large
process change. The value of the band is in display units. A band setting of ‘0’
keeps the digital filter permanently engaged.
 to 
For Key-in (), enter the known first Input Value by using the arrow keys.
The Input Range selection sets up the decimal location for the Input Value. With
0.02A Input Range, 4mA would be entered as 4.000. For Apply (), apply
the input signal to the meter, adjust the signal source externally until the desired
Input Value appears. In either method, press the PAR key to enter the value
being displayed.
Note:  style - Pressing the RST key will advance the display to the next
scaling display point without storing the input value.
For the PAXT, the following parameters only apply to Custom
Sensor Scaling.
DISPLAY VALUE FOR SCALING POINT 1
PAXT: ICE POINT SLOPE
 
 
key-in data
apply signal
If Input Values and corresponding Display Values are known, the Key-in
() scaling style can be used. This allows scaling without the presence or
changing of the input signal. If Input Values have to be derived from the actual
input signal source or simulator, the Apply () scaling style must be used.
After using the Apply () scaling style, this parameter will default back to
 but the scaling values will be shown from the previous applied method.
The input filter setting is a time constant expressed in tenths of a second. The
filter settles to 99% of the final display value within approximately 3 time
constants. This is an Adaptive Digital Filter which is designed to steady the
Input Display reading. A value of ‘0’ disables filtering.
 




  
 
 to  µV/°C
 to 
Enter the first coordinating Display Value by using the arrow keys. This is
the same for  and  scaling styles. The decimal point follows the 
selection.
This parameter sets the slope value for ice point compensation for the
Custom TC range () only. The fixed thermocouple ranges are
automatically compensated by the meter and do not require this setting. To
calculate this slope, use µV data obtained from thermocouple manufacturers’
tables for two points between 0°C and 50°C. Place this corresponding µV and
°C information into the equation:
slope = (µV2 - µV1)/(°C2 - °C1).
Due to the nonlinear output of thermocouples, the compensation may show
a small offset error at room temperatures. This can be compensated by the offset
parameter. A value of 0 disables internal compensation when the thermocouple
is externally compensated.
INPUT VALUE FOR SCALING POINT 2
  
 
 to 
For Key-in (), enter the known second Input Value by using the arrow
keys. For Apply (), adjust the signal source externally until the next
desired Input Value appears. (Follow the same procedure if using more than 2
scaling points.)
* Factory Setting can be used without affecting basic start-up.
17
DISPLAY VALUE FOR SCALING POINT 2
  
 
4. The maximum scaled Display Value spread between range maximum and
minimum is limited to 65,535. For example using +20 mA range the
maximum +20 mA can be scaled to is 32,767 with 0 mA being 0 and Display
Rounding of 1. (Decimal points are ignored.) The other half of 65,535 is for
the lower half of the range 0 to -20 mA even if it is not used. With Display
Rounding of 2, +20 mA can be scaled for 65,535 (32,767 x 2) but with even
Input Display values shown.
5. For input levels beyond the first programmed Input Value, the meter extends
the Display Value by calculating the slope from the first two coordinate pairs
( /  &  / ). If  = 4 mA and  = 0, then 0 mA
would be some negative Display Value. This could be prevented by making
 = 0 mA /  = 0,  = 4 mA /  = 0, with  = 20 mA /
 = the desired high Display Value. The calculations stop at the limits of
the Input Range Jumper position.
6. For input levels beyond the last programmed Input Value, the meter extends
the Display Value by calculating the slope from the last two sequential
coordinate pairs. If three coordinate pair scaling points were entered, then the
Display Value calculation would be between  /  &  / .
The calculations stop at the limits of the Input Range Jumper position.
 to 
Enter the second coordinating Display Value by using the arrow keys. This
is the same for  and  scaling styles. (Follow the same procedure if
using more than 2 scaling points.)
General Notes on Scaling
1. Input Values for scaling points should be confined to the limits of the Input
Range Jumper position.
2. The same Input Value should not correspond to more than one Display Value.
(Example: 20 mA can not equal 0 and 10.)
This is referred to as read out jumps (vertical scaled segments).
3. The same Display Value can correspond to more than one Input Value.
(Example: 0 mA and 20 mA can equal 10.)
This is referred to as readout dead zones (horizontal scaled segments).
6.2 MODULE 2 - User Input and Front Panel Function Key
Parameters ()
2-FNC
Pro
PARAMETER MENU
PAR
USr-1
USr-2
USr-3
F1
F2
USER INPUTS
rSt
Sc-F1
Sc-F2
FUNCTION KEYS
The three user inputs are individually programmable to perform specific
meter control functions. While in the Display Mode or Program Mode, the
function is executed the instant the user input transitions to the active state.
The front panel function keys are also individually programmable to perform
specific meter control functions. While in the Display Mode, the primary
function is executed the instant the key is pressed. Holding the function key for
three seconds executes a secondary function. It is possible to program a
secondary function without a primary function.
In most cases, if more than one user input and/or function key is programmed
for the same function, the maintained (level trigger) actions will be performed
while at least one of those user inputs or function keys are activated. The
momentary (edge trigger) actions will be performed every time any of those
user inputs or function keys transition to the active state.
ZERO (TARE) DISPLAY
 
 

 

The Zero (Tare) Display provides a way to zero the Input Display value at
various input levels, causing future Display readings to be offset. This function
is useful in weighing applications where the container or material on the scale
should not be included in the next measurement value. When activated
(momentary action),  flashes and the Display is set to zero. At the same
time, the Display value (that was on the display before the Zero Display) is
subtracted from the Display Offset Value and is automatically stored as the new
Display Offset Value (). If another Zero (tare) Display is performed, the
display will again change to zero and the Display reading will shift accordingly.
Note: In the following explanations, not all selections are available for both
user inputs and front panel function keys. Alternating displays are shown
with each selection. Those selections showing both displays are available for
both. If a display is not shown, it is not available for that selection. 
will represent all three user inputs.  will represent all five function keys.
RELATIVE/ABSOLUTE DISPLAY
NO FUNCTION
 



 
 
 

This function will switch the Input Display between Relative and Absolute.
The Relative is a net value that includes the Display Offset Value. The Input
Display will normally show the Relative unless switched by this function.
Regardless of the display selected, all meter functions continue to operate based
on relative values. The Absolute is a gross value (based on Module 1 DSP and
INP entries) without the Display Offset Value. The Absolute display is selected
as long as the user input is activated (maintained action) or at the transition of
the function key (momentary action). When the user input is released, or the
function key is pressed again, the input display switches back to Relative
display.  (absolute) or  (relative) is momentarily displayed at transition
to indicate which display is active.
No function is performed if activated. This is the factory setting for all user
inputs and function keys. No function can be selected without affecting basic
start-up.
PROGRAMMING MODE LOCK-OUT
 
 
 
 
Programming Mode is locked-out, as long as activated
(maintained action). A security code can be configured to
allow programming access during lock-out.
18
HOLD DISPLAY
RESET MAXIMUM
 
 
The shown display is held but all other meter functions
continue as long as activated (maintained action).
 
 
The meter disables processing the input, holds all display
contents, and locks the state of all outputs as long as activated
(maintained action). The serial port continues data transfer.
When activated (momentary action),  flashes and
the Maximum resets to the present Input Display value. The
Maximum function then continues from that value. This
selection functions independent of the selected display.

 

HOLD ALL FUNCTIONS
RESET, SELECT, ENABLE MAXIMUM DISPLAY
When activated (momentary action), the Maximum value
is set to the present Input Display value. Maximum continues
from that value while active (maintained action). When the
user input is released, Maximum detection stops and holds its
value. This selection functions independent of the selected display. The DSP key
overrides the active user input display but not the Maximum function.
 
 
SYNCHRONIZE METER READING
 
 
The meter suspends all functions as long as activated
(maintained action). When the user input is released, the
meter synchronizes the restart of the A/D with other
processes or timing events.
SELECT MINIMUM DISPLAY
 
 
STORE BATCH READING IN TOTALIZER
 
 

 

The Input Display value is one time added (batched) to the Totalizer at
transition to activate (momentary action). The Totalizer retains a running sum of
each batch operation until the Totalizer is reset. When this function is selected,
the normal operation of the Totalizer is overridden.
RESET MINIMUM
When activated (momentary action),  flashes and
the Minimum reading is set to the present Input Display
value. The Minimum function then continues from that value.
This selection functions independent of the selected display.
SELECT TOTALIZER DISPLAY
 
 
The Totalizer display is selected as long as activated
(maintained action). When the user input is released, the
Input Display is returned. The DSP key overrides the active
user input. The Totalizer continues to function including
associated outputs independent of being displayed.
When activated (momentary action), the Minimum value
is set to the present Input Display value. Minimum continues
from that value while active (maintained action). When the
user input is released, Minimum detection stops and holds
its value. This selection functions independent of the selected display. The DSP
key overrides the active user input display but not the Minimum function.
 
 
 
 
When activated (momentary action),  flashes and the Totalizer resets to
zero. The Totalizer then continues to operate as it is configured. This selection
functions independent of the selected display.
RESET MAXIMUM AND MINIMUM
 
 
RESET AND ENABLE TOTALIZER
 
 
CHANGE DISPLAY INTENSITY LEVEL
 
 
The Totalizer continues to operate as long as activated
(maintained action). When the user input is released, the
Totalizer stops and holds its value. This selection functions
independent of the selected display.
 
 
When activated (momentary action), the display intensity changes to the next
intensity level (of 4). The four levels correspond to Display Intensity Level
() settings of 0, 3, 8, and 15. The intensity level, when changed via the
User Input/ Function Key, is not retained at power-down, unless Quick
Programming or Full Programming mode is entered and exited. The meter will
power-up at the last saved intensity level.
SELECT MAXIMUM DISPLAY
 
 

 

When activated (momentary action),  flashes and the Maximum and
Minimum readings are set to the present Input Display value. The Maximum and
Minimum function then continues from that value. This selection functions
independent of the selected display.
When activated (momentary action),  flashes and
the Totalizer resets to zero. The Totalizer continues to
operate while active (maintained action). When the user
input is released, the Totalizer stops and holds its value. This
selection functions independent of the selected display.
ENABLE TOTALIZER
 
 

 

RESET, SELECT, ENABLE MINIMUM DISPLAY
RESET TOTALIZER
 
 
The Minimum display is selected as long as activated
(maintained action). When the user input is released, the
Input Display is returned. The DSP key overrides the active
user input. The Minimum continues to function independent
of being displayed.
The Maximum display is selected as long as activated
(maintained action). When the user input is released, the
Input Display returns. The DSP key overrides the active
user input. The Maximum continues to function independent
of being displayed.
19
SETPOINT SELECTIONS
PRINT REQUEST
The following selections are accessible only with the Setpoint plug-in card
installed. Refer to Module 6 for an explanation of their operation.
Setpoint
Card
Only
ì
í
î
 
 
 - Select main or alternate setpoints
 - Reset Setpoint 1 (Alarm 1)
 - Reset Setpoint 2 (Alarm 2)
 - Reset Setpoint 3 (Alarm 3)
 - Reset Setpoint 4 (Alarm 4)
 - Reset Setpoint 3 & 4 (Alarm 3 & 4)
 - Reset Setpoint 2, 3 & 4 (Alarm 2, 3 & 4)
 - Reset Setpoint All (Alarm All)
6.3 MODULE 3 - Display
 
 
The meter issues a block print through the serial port when activated. The
data transmitted during a print request is programmed in Module 7. If the user
input is still active after the transmission is complete (about 100 msec), an
additional transmission occurs. As long as the user input is held active,
continuous transmissions occur.
and Program
Parameters
Lock-out
()
PARAMETER MENU
3-LOC
Pro
PAR
HI
LO
Max Display
Lock-out
Min Display
Lock-out
tOt
Total Display
Lock-out
SP-1
SP-2
SP-3
SP-4
CodE
Setpoint 1
Access
Setpoint 2
Access
Setpoint 3
Access
Setpoint 4
Access
Security
Code
MAXIMUM DISPLAY LOCK-OUT*
MINIMUM DISPLAY LOCK-OUT*
TOTALIZER DISPLAY LOCK-OUT*
Module 3 is the programming for Display lock-out and “Full” and “Quick”
Program lock-out.
When in the Display Mode, the available displays can be read consecutively
by repeatedly pressing the DSP key. An annunciator indicates the display being
shown. These displays can be locked from being visible. It is recommended that
the display be set to  when the corresponding function is not used.
SELECTION



DESCRIPTION
Not visible in Display Mode
 
 
Program Lock-out status. It is suggested to lock-out the display if it is not needed.
The associated function will continue to operate even if its display is locked-out.
SP-1 SP-2 SP-3 SP-4 SETPOINT ACCESS*
 
 
DESCRIPTION
 
 
 
 
 
 
The setpoint displays can be programmed for ,  or  (See the
following table). Accessible only with the Setpoint plug-in card installed.
Visible but not changeable in Quick Programming Mode




 

These displays can be programmed for  or . When programmed for
, the display will not be shown when the DSP key is pressed regardless of
Visible in Display Mode
“Full” Programming Mode permits all parameters to be viewed and
modified. This Programming Mode can be locked with a security code and/or
user input. When locked and the PAR key is pressed, the meter enters a Quick
Programming Mode. In this mode, the setpoint values can still be read and/or
changed per the selections below. The Display Intensity Level ()
parameter also appears whenever Quick Programming Mode is enabled and the
security code is greater than zero.
SELECTION
 

Visible and changeable in Quick Programming Mode
Not visible in Quick Programming Mode
PROGRAM MODE SECURITY CODE*
 


* Factory Setting can be used without affecting basic start-up.
 to 
By entering any non-zero value, the prompt   will appear when trying
to access the Program Mode. Access will only be allowed after entering a
matching security code or universal code of . With this lock-out, a user input
would not have to be configured for Program Lock-out. However, this lock-out
is overridden by an inactive user input configured for Program Lock-out.
PROGRAMMING MODE ACCESS
SECURITY
CODE
USER INPUT
CONFIGURED
USER INPUT
STATE
WHEN PAR KEY IS
PRESSED
“FULL” PROGRAMMING MODE ACCESS
0
not
————
“Full” Programming
>0
not
————
Quick Programming w/Display Intensity
After Quick Programming with correct code # at  prompt.
Active
Quick Programming w/Display Intensity
After Quick Programming with correct code # at  prompt.
Not Active
“Full” Programming
Immediate access.
Active
Quick Programming
No access
Not Active
“Full” Programming
Immediate access.
>0
>0
0
0






Immediate access.
Throughout this document, Programming Mode (without Quick in front) always refers to “Full” Programming (all meter parameters are accessible).
20
6.4 MODULE 4 - Secondary Function Parameters ()
PARAMETER MENU
4-SEC
PAXS
ONLY
PAR
HI-t
Max. Capture
Delay Time
LO-t
dSP-t
Min. Capture
Delay Time
PAXS
ONLY
At-t
Auto-Zero
Tracking Delay
Time
Display Update
Time
At-b
Auto-Zero
Tracking Band
NOT
PAXT
b-LIt
OFFSt
Units Label
BackLight
Display Offset
Value
 
 
 to  sec.
When the Input Display is above the present MAX value for the entered
delay time, the meter will capture that display value as the new MAX reading.
A delay time helps to avoid false captures of sudden short spikes.



 
 

updates/sec.
PAXT: ICE POINT COMPENSATION*
PAXS: AUTO-ZERO TRACKING
 


 to  sec.


This parameter turns the internal ice point compensation on or off. Normally,
the ice point compensation is on. If using external compensation, set this
parameter to off. In this case, use copper leads from the external compensation
point to the meter. If using Custom TC range, the ice point compensation can
be adjusted by a value in Module 1 when this is yes.
PAXS: AUTO-ZERO BAND
 
 
 to 
Unless a Zero Display was performed or an offset from Module 1 scaling is
desired, this parameter can be skipped. The Display Offset Value is the
difference from the Absolute (gross) Display value to the Relative (net) Display
value for the same input level. The meter will automatically update this Display
Offset Value after each Zero Display. The Display Offset Value can be directly
keyed-in to intentionally add or remove display offset. See Relative / Absolute
Display and Zero Display explanations in Module 2.
This parameter determines the rate of display update. When set to 20
updates/second, the internal re-zero compensation is disabled, allowing for the
fastest possible output response.
 



This parameter does not apply for the PAXT.
DISPLAY UPDATE RATE*


DISPLAY OFFSET VALUE*
 to  sec.
When the Input Display is below the present MIN value for the entered delay
time, the meter will capture that display value as the new MIN reading. A delay
time helps to avoid false captures of sudden short spikes.
 


ICE
Ice Point
Compensation
The Units Label Kit Accessory contains a sheet of custom unit overlays
which can be installed in to the meter’s bezel display assembly. The backlight
for these custom units is activated by this parameter.
MIN CAPTURE DELAY TIME*
 


Pro
UNITS LABEL BACKLIGHT*
MAX CAPTURE DELAY TIME*
 


PAXT
ONLY
 to 
The meter can be programmed to automatically compensate for zero drift.
Drift may be caused by changes in the transducers or electronics, or
accumulation of material on weight systems.
Auto-zero tracking operates when the readout remains within the tracking
band for a period of time equal to the tracking delay time. When these
conditions are met, the meter re-zeroes the readout. After the re-zero operation,
the meter resets and continues to auto-zero track.
The auto-zero tracking band should be set large enough to track normal zero
drift, but small enough to not interfere with small process inputs.
For filling operations, the fill rate must exceed the auto-zero tracking rate.
This avoids false tracking at the start of the filling operation.
Fill Rate ≥ tracking band
tracking time
Auto-zero tracking is disabled by setting the auto-zero tracking parameter = 0.
* Factory Setting can be used without affecting basic start-up.
21
6.5 MODULE 5 - Totalizer (Integrator) Parameters ()
5-tOt
Pro
PARAMETER MENU
PAR
dECPt
tbASE
Totalizer
Decimal Point
Totalizer
Time Base
SCFAC
Totalizer
Scale Factor



Totalizer Low
Cut Value
Totalizer Power
Up Reset
When the total exceeds 5 digits, the front panel annunciator TOT flashes. In
this case, the meter continues to totalize up to a 9 digit value. The high order 4
digits and the low order 5 digits of the total are displayed alternately. The letter
“” denotes the high order display. When the total exceeds a 9 digit value, the
Totalizer will show “E . . .” and will stop.
TOTALIZER BATCHING
The Totalizer Time Base and scale factor are overridden when a user input or
function key is programmed for store batch (). In this mode, when the user
input or function key is activated, the Input Display reading is one time added
to the Totalizer (batch). The Totalizer retains a running sum of each batch
operation until the Totalizer is reset. This is useful in weighing operations, when
the value to be added is not based on time but after a filling event.
TOTALIZER DECIMAL POINT*

P-UP
TOTALIZER HIGH ORDER DISPLAY
The totalizer accumulates (integrates) the Input Display value using one of
two modes. The first is using a time base. This can be used to compute a timetemperature product. The second is through a user input or function key
programmed for Batch (one time add on demand). This can be used to provide
a readout of temperature integration, useful in curing and sterilization
applications. If the Totalizer is not needed, its display can be locked-out and this
module can be skipped during programming.
 
 
Locut

For most applications, this matches the Input Display Decimal Point
(). If a different location is desired, refer to Totalizer Scale Factor.
TOTALIZER USING TIME BASE
Totalizer accumulates as defined by:
TOTALIZER TIME BASE
 


Input Display x Totalizer Scale Factor
Totalizer Time Base
 - seconds (÷ 1)  - hours (÷ 3600)
 - minutes (÷ 60)  - days (÷ 86400)
Where:
Input Display - the present input reading
Totalizer Scale Factor - 0.001 to 65.000
Totalizer Time Base - (the division factor of
This is the time base used in Totalizer accumulations. If the Totalizer is being
accumulated through a user input programmed for Batch, then this parameter
does not apply.
Example: The input reading is at a constant rate of 10.0 gallons per minute. The
Totalizer is used to determine how many gallons in tenths has flowed.
Because the Input Display and Totalizer are both in tenths of gallons, the
Totalizer Scale Factor is 1. With gallons per minute, the Totalizer Time Base
is minutes (60). By placing these values in the equation, the Totalizer will
accumulate every second as follows:
TOTALIZER SCALE FACTOR*
 
 
 to 
10.0 x 1.000 = 0.1667 gallon accumulates each second
60
This results in:
10.0 gallons accumulates each minute
600.0 gallons accumulates each hour
For most applications, the Totalizer reflects the same decimal point location
and engineering units as the Input Display. In these cases, the Totalizer Scale
Factor is 1.000. The Totalizer Scale Factor can be used to scale the Totalizer to
a different value than the Input Display. Common possibilities are:
1. Changing decimal point location (example tenths to whole)
2. Average over a controlled time frame.
Details on calculating the scale factor are shown later.
If the Totalizer is being accumulated through a user input programmed for
Batch, then this parameter does not apply.
TOTALIZER SCALE FACTOR CALCULATION EXAMPLES
1. When changing the Totalizer Decimal Point () location from the
Input Display Decimal Point (), the required Totalizer Scale Factor is
multiplied by a power of ten.
Example:
Input () = 0
Input () = 0.0 Input () = 0.00
TOTALIZER LOW CUT VALUE*
 
 
Scale
Factor
Totalizer


Scale
Factor
0.0
10
0.00
10
0.000
10
0
1
0.0
1
0.00
1
x10
0.1
0
0.1
0.0
0.1
x100
0.01
x10
0.01
0
0.01
x1000
0.001
x100
0.001
x10
0.001
(x = Totalizer display is round by tens or hundreds)
2. To obtain an average reading within a controlled time frame, the selected
Totalizer Time Base is divided by the given time period expressed in the same
timing units.
Example: Average temperature per hour in a 4 hour period, the scale factor
would be 0.250. To achieve a controlled time frame, connect an external timer
to a user input programmed for . The timer will control the start (reset)
and the stopping (hold) of the totalizer.
TOTALIZER POWER UP RESET*


Scale
Factor
Totalizer

Totalizer
 to 
A low cut value disables Totalizer when the Input Display value falls below
the value programmed.
 


)
Do not reset buffer
Reset buffer
The Totalizer can be reset to zero on each meter power-up by setting this
parameter to reset.
* Factory Setting can be used without affecting basic start-up.
22
6.6 MODULE 6 - Setpoint (Alarm) Parameters () Ñ
PARAMETER MENU
6-SPt
PAR
SPSEL
ACt-n
Setpoint
Select
Setpoint
Action
SP-n
HYS-n
Setpoint
Value
Setpoint
Hysteresis
tON-n
tOF-n
out-n
rSt-n
On Time
Delay
Off Time
Delay
Output
Logic
Reset
Action
 
 



brn-n
Setpoint
Annunciators
Burn-out
Action
 
 












Enter the setpoint (alarm output) to be programmed. The  in the following
parameters will reflect the chosen setpoint number. After the chosen setpoint is
completely programmed, the display will return to  . Repeat step for
each setpoint to be programmed. The  chosen at  will return to  .
The number of setpoints available is setpoint output card dependent.
Setpoint Alarm Figures
With reverse output logic
Standby
Operation
LIt-n






Enter the action for the selected setpoint (alarm output). See Setpoint Alarm
Figures for a visual detail of each action.
SETPOINT SELECT
 


Stb-n
SETPOINT ACTION
Ñ - A setpoint card must be installed in order to access this module.
Depending on the card installed, there will be two or four setpoint outputs
available. For maximum input frequency, unused Setpoints should be configured
for  action.
The setpoint assignment and the setpoint action determine certain setpoint
feature availability.
Pro
PAXT
ONLY
=
Setpoint always off, (returns to SPSEL NO)
=
Absolute high, with balanced hysteresis
=
Absolute low, with balanced hysteresis
=
Absolute high, with unbalanced hysteresis
=
Absolute low, with unbalanced hysteresis
=
Deviation high, with unbalanced hysteresis *
=
Deviation low, with unbalanced hysteresis *
=
Outside band, with unbalanced hysteresis *
=
Lower Totalizer absolute high, unbalance hysteresis**
=
Upper Totalizer absolute high, unbalance hysteresis**
* Deviation and band action setpoints are relative to the value of setpoint 1.
It is not possible to configure setpoint 1 as deviation or band actions. It is
possible to use setpoint 1 for an absolute action, while its value is being used
for deviation or band.
** The lower Totalizer action  allows setpoints to function off of the
lower 5 digits of the Totalizer. The upper Totalizer action  allows
setpoints to function off of the upper 4 digits of the Totalizer. To obtain
absolute low alarms for the Totalizer, program the  or  output
logic as reverse.
, the below alarm states are opposite.
SP1 + SPn
SP
Hys
Hys
SP - ½Hys
ALARM
STATE
SP
OFF
ON
OFF
ALARM
STATE
Hys
OFF
ON
OFF
ALARM
STATE
OFF
TRIGGER POINTS

ON
OFF
OFF
ON
TRIGGER POINTS
Absolute Low Acting (Unbalanced Hys) =
Band Outside Acting =


SP1
SP1 + SPn
SP + ½Hys
Hys
SP
Hys
SP1 + (-SPn)
Hys
SP1
SP - ½Hys
OFF
ON
OFF
ALARM
STATE
OFF
ON
ALARM
STATE
OFF
ON
TRIGGER POINTS
TRIGGER POINTS
Absolute Low Acting (Balanced Hys) =

SP
Deviation High Acting (SP > 0) =
OFF
ON
TRIGGER POINTS
Deviation High Acting (SP < 0) =


SP1
Hys
SP - Hys
ALARM
STATE
SP1
SP1 - SPn
TRIGGER POINTS
Absolute High Acting (Balanced Hys) =
ALARM
STATE
Hys
SP + Hys
SP + ½Hys
Hys
SP1 - SPn
OFF
ON
OFF
TRIGGER POINTS
Absolute High Acting (Unbalanced Hys) = 
This is also for Totalizer alarms: , 
Hys
SP1 - (-SPn)
ALARM
STATE
OFF
ON
OFF
SP1
ALARM
STATE
ON
OFF
ON
TRIGGER POINTS
TRIGGER POINTS
Deviation Low Acting (SP > 0) =
23

Deviation Low Acting (SP < 0)=

maintained), the corresponding “on” alarm output is reset immediately and
remains off until the trigger point is crossed again. (Previously latched alarms
will be off if power up Display Value is lower than setpoint value.)
 = Latch with delay reset action; This action latches the alarm output
on at the trigger point per the Setpoint Action shown in Setpoint Alarm
Figures. Latch means that the alarm output can only be turned off by front
panel function key or user input manual reset, serial reset command or meter
power cycle. When the user input or function key is activated (momentary or
maintained), the meter delays the event until the corresponding “on” alarm
output crosses the trigger off point. (Previously latched alarms are off if
power up Display Value is lower than setpoint value. During a power cycle,
the meter erases a previous Latch 2 reset if it is not activated at power up.)
SETPOINT VALUE
 
 

to

Enter desired setpoint alarm value. These setpoint values can also be entered
in the Display Mode during Program Lock-out when the setpoint is programmed
as  in Parameter Module 3. When a setpoint is programmed as deviation or
band acting, the associated output tracks  as it is changed. The value entered
is the offset, or difference from .
HYSTERESIS VALUE
 
 

to
STANDBY OPERATION

 


Enter desired hysteresis value. See Setpoint Alarm Figures for visual
explanation of how setpoint alarm actions (balance and unbalance) are affected
by the hysteresis. When the setpoint is a control output, usually balance
hysteresis is used. For alarm applications, usually unbalanced hysteresis is used.
For unbalanced hysteresis modes, the hysteresis functions on the low side for
high acting setpoints and functions on the high side for low acting setpoints.
SETPOINT ANNUNCIATORS
 
 
ON TIME DELAY

to
to
 
 



Hys
SP - Hys
ALARM
STATE
RESET ACTION


SP
Enter the output logic of the alarm output. The  logic leaves the output
operation as normal. The  logic reverses the output logic. In , the alarm
states in the Setpoint Alarm Figures are reversed.
 
 

MANUAL
RESET
OUTPUT LOGIC


Enter the probe burn-out action. In the event of a temperature probe failure,
the alarm output can be programmed to go on or off.
 sec.
Enter the time value in seconds that the alarm is delayed from turning off after
the trigger point is reached. A value of 0.0 allows the meter to update the alarm
status per the response time listed in the Specifications. When the output logic
is , this becomes on time delay. Any time accumulated at power-off resets
during power-up.
 
 

PROBE BURN-OUT ACTION (PAXT ONLY)
OFF TIME DELAY


The  mode disables display setpoint annunciators. The  mode
displays the corresponding setpoint annunciators of “on” alarm outputs. The
 mode displays the corresponding setpoint annunciators of “off” alarms
outputs. The  mode flashes the corresponding setpoint annunciators of
“on” alarm outputs.
 sec.
Enter the time value in seconds that the alarm is delayed from turning on after
the trigger point is reached. A value of 0.0 allows the meter to update the alarm
status per the response time listed in the Specifications. When the output logic
is , this becomes off time delay. Any time accumulated at power-off resets
during power-up.
 



When , the alarm is disabled (after a power up) until the trigger point is
crossed. Once the alarm is on, the alarm operates normally per the Setpoint
Action and Reset Mode.
Note: Hysteresis eliminates output chatter at the switch point, while time delay
can be used to prevent false triggering during process transient events.
 



OFF
OFF
ON
ON
OFF
ON
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
( Auto)
(LAtC1)
OFF (LAtC2)
Setpoint Alarm Reset Actions

Alternate Setpoints
Enter the reset action of the alarm output.
 = Automatic action; This action allows the alarm output to automatically
reset off at the trigger points per the Setpoint Action shown in Setpoint Alarm
Figures. The “on” alarm may be manually reset (off) immediately by a front
panel function key or user input.The alarm remains reset off until the trigger
point is crossed again.
 = Latch with immediate reset action; This action latches the alarm
output on at the trigger point per the Setpoint Action shown in Setpoint Alarm
Figures. Latch means that the alarm output can only be turned off by front
panel function key or user input manual reset, serial reset command or meter
power cycle. When the user input or function key is activated (momentary or
An Alternate list of setpoint values can be stored and recalled as needed. The
Alternate list allows an additional set of setpoint values. (The setpoint numbers
nor rear terminal numbers will change in the Alternate list.) The Alternate list
can only be activated through a function key or user input programmed for 
in Module 2. When the Alternate list is selected, the Main list is stored and
becomes inactive. When changing between Main and Alternate, the alarm state
of Auto Reset Action alarms will always follow their new value. Latched “on”
alarms will always stay latched during the transition and can only be reset with
a user input or function key. Only during the function key or user input
transition does the display indicate which list is being used.
24
6.7 MODULE 7 - Serial Communications Parameters () Ñ
PARAMETER MENU
7-SrL
PAR
bAUd
dAtA
Baud
Rate
Data
Bit
PAr
Parity
Bit
Addr
Abrv
Meter
Address
Abbreviated
Printing
OPt
Print
Options
PAXS
ONLY
PAXS
ONLY
6roSS
tArE
Gross
Tare
Pro
INP
Ñ - A communication card must be installed in order to access this
module.




 




 
 




PRINT OPTIONS
PARITY BIT

to
Select abbreviated transmissions (numeric only) or full field transmission.
When the data from the meter is sent directly to a terminal for display, the extra
characters that are sent identify the nature of the meter parameter displayed. In
this case, select . When the data from the meter goes to a computer, it may be
desirable to suppress the node address and mnemonic when transmitting. In this
case, set this parameter to .

Select either 7 or 8 bit data word lengths. Set the word length to match that
of other serial communication equipment. Since the meter receives and
transmits 7-bit ASCII encoded data, 7 bit word length is sufficient to request
and receive data from the meter.
 
 

ABBREVIATED PRINTING
DATA BIT

SPNt
Print Max
Print Setpoint
& Min Values
Values
Enter the serial node address. With a single unit on a bus, an address is not
needed and a value of zero can be used (RS232 applications). Otherwise, with
multiple bussed units, a unique address number must be assigned to each meter.
The node address applies specifically to RS485 applications.

Set the baud rate to match that of other serial communications equipment.
Normally, the baud rate is set to the highest value that all of the serial
communications equipment is capable of transmitting.
 


HILO
Print Total
Value
METER ADDRESS
BAUD RATE
 
 
tot
Print Input
Value
 
 



 - Enters the sub-menu to select those meter parameters to appear in the
block print. For each parameter in the sub-menu select  for the parameter to
appear with the block print, and  to disable the parameter.
*Setpoints 1-4 are setpoint plug-in card dependent.
Set the parity bit to match that of the other serial communications equipment
used. The meter ignores the parity when receiving data, and sets the parity bit
for outgoing data. If no parity is selected with 7-bit word length the meter
transmits and receives data with 2 stop bits. (For example: 10 bit frame with
mark parity)
Gross Value (PAXS Only)
Tare Value (PAXS Only)
Input Value
Max and Min Values
Total Value
Setpoint values*
25
6roSS
tArE
















Sending Commands and Data
Register Identification Chart
When sending commands to the meter, a string containing at least one
command character must be constructed. A command string consists of a
command character, a value identifier, numerical data (if writing data to the
meter) followed by a the command terminator character * or $.
Command Chart
Command Description
N
T
V
R
P
Notes
Address a specific meter. Must be followed by
one or two digit node address. Not required
when node address = 0.
Read a register from the meter. Must be
Transmit Value (read)
followed by register ID character.
Write to register of the meter. Must be
Value change (write) followed by register ID character and numeric
data.
Reset a register or output. Must be followed
Reset
by register ID character
Node Address
Specifier
Block Print Request
(read)
Value Description
A
Input
INP
T, P, R
B
Total
TOT
T, P, R
C
Max Input
MAX
T, P, R
D
Min Input
MIN
T, P, R
E
Setpoint 1
SP1
T, P, V, R
F
Setpoint 2
SP2
T, P, V, R
G
Setpoint 3
SP3
T, P, V, R
H
Setpoint 4
SP4
T, P, V, R
AOR
T, V
CSR
T, V
I
Initiates a block print output. Registers are
defined in programming.
Register
Applicable Commands/Comments
ID
ID
J
L
Q
Analog Output
Register
Control Status
Register
Absolute (gross)
input display value
Offset/Tare (PAXS)
ABS
T, P
GRS †
OFS
T, P, V
TAR †
(Reset command [Ver2.5+]
zeros the input [“REL” or Tare])
(Reset command resets total to
zero)
(Reset command resets MAX to
current reading)
(Reset command resets MIN to
current reading)
(Reset command resets the
setpoint output)
(Reset command resets the
setpoint output)
(Reset command resets the
setpoint output)
(Reset command resets the
setpoint output)
(Applies to manual mode)
(Ver 2.5+)
† -Register ID for the PAXS.
Command String Construction
Command String Examples:
The command string must be constructed in a specific sequence. The meter
does not respond with an error message to illegal commands. The following
procedure details construction of a command string:
1. Node address = 17, Write 350 to Setpoint 1, response delay of 2 msec min
String: N17VE350$
2. Node address = 5, Read Input value, response delay of 50 msec min
String: N5TA*
1. The first 2 or 3 characters consist of the Node Address Specifier (N) followed
by a 1 or 2 character node address number. The node address number of the
meter is programmable. If the node address is 0, this command and the node
address itself may be omitted. This is the only command that may be used in
conjunction with other commands.
2. After the optional address specifier, the next character is the command character.
3. The next character is the register ID. This identifies the register that the
command affects. The P command does not require a register ID character. It
prints according to the selections made in print options.
4. If constructing a value change command (writing data), the numeric data is
sent next.
5. All command strings must be terminated with the string termination
characters * or $. The meter does not begin processing the command string
until this character is received. See timing diagram figure for differences of *
and $ terminating characters.
3. Node address = 0, Reset Setpoint 4 output, response delay of 50 msec min
String: RH*
Sending Numeric Data
Numeric data sent to the meter must be limited to 5 digits (-19,999 to 99,999).
If more than 5 digits are sent, the meter accepts the last 5. Leading zeros are
ignored. Negative numbers must have a minus sign. The meter ignores any
decimal point and conforms the number to the scaled resolution. (For example:
the meter’s scaled decimal point position = 0.0 and 25 is written to a register.
The value of the register is now 2.5 In this case, write a value = 25.0).
Note: Since the meter does not issue a reply to value change commands, follow
with a transmit value command for readback verification.
Receiving Data
The end of the response string is terminated with a carriage return <CR> and
<LF>. When block print is finished, an extra <SP><CR> <LF> is used to
provide separation between the blocks.
Data is transmitted by the meter in response to either a transmit command (T),
a print block command (P) or User Function print request. The response from
the meter is either a full field transmission or an abbreviated transmission. In this
case, the response contains only the numeric field. The meter response mode is
established in programming.
Abbreviated Transmission
Byte
Full Field Transmission
Byte
Description
1, 2
3
4-6
2 byte Node Address field [00-99]
<SP> (Space)
3 byte Register Mnemonic field
12 byte data field; 10 bytes for number, one byte for sign, one byte for
decimal point (The T command may be a different byte length)
<CR> carriage return
<LF> line feed
<SP>* (Space)
<CR>* carriage return
<LF>* line feed
7-18
19
20
21
22
23
Description
13
12 byte data field, 10 bytes for number, one byte for sign,
one byte for decimal point
<CR> carriage return
14
<LF> line feed
15
<SP>* (Space)
16
<CR>* carriage return
17
<LF>* line feed
1-12
* These characters only appear in the last line of a block print.
The abbreviated response suppresses the node address and register ID,
leaving only the numeric part of the response.
Meter Response Examples:
* These characters only appear in the last line of a block print.
The first two characters transmitted are the node address, unless the node address
assigned =0, in which case spaces are substituted. A space follows the node address
field. The next three characters are the register ID (Serial Mnemonic).
The numeric data is transmitted next. The numeric field is 12 characters long
(to accommodate the 10 digit totalizer), with the decimal point position floating
within the data field. Negative value have a leading minus sign. The data field
is right justified with leading spaces.
1. Node address = 17, full field response, Input = 875
17 INP
875 <CR><LF>
2. Node address = 0, full field response, Setpoint 2 = -250.5
SP2
-250.5<CR><LF>
3. Node address = 0, abbreviated response, Setpoint 2 = 250, last line of block
print
250<CR><LF><SP><CR><LF>
26
SERIAL COMMANDS FOR PAX SOFTWARE
(CSR) Control Status Register
Examples:
The Control Status Register is used to both directly control the meter’s
outputs (setpoints and analog output), and interrogate the state of the setpoint
outputs. The register is bit mapped with each bit position within the register
assigned to a particular control function. The control function are invoked by
writing to each bit position. The bit position definitions are:
1. Set manual mode, turn all setpoints off:
7 6 5 4 3 2 1 0:bit location
VJ<30>* or VJ0*
ASCII 0 = 0 0 1 1 0 0 0 0 or <30>
V is command write, J is CSR and * is terminator.
bit 0: Setpoint 1 Output Status
0 = output off
1 = output on
bit 1: Setpoint 2 Output Status
0 = output off
1 = output on
bit 2: Setpoint 3 Output Status
0 = output off
1 = output on
bit 3: Setpoint 4 Output Status
0 = output off
1 = output on
bit 4: Manual Mode
0 = automatic mode
1 = manual mode
bit 5: Always stays 0, even if 1 is sent.
bit 6: Sensor Status (PAXT only)
0 = sensor normal
1 = sensor fail
bit 7: Always stays 0, even if 1 is sent.
2. Turn SP1, SP3 outputs on and SP2, SP4 outputs off:
7 6 5 4 3 2 1 0:bit location
VJ<35>* or VJ5*
ASCII 5 = 0 0 1 1 0 1 0 1 or <35>
3. Select Automatic mode:
7 6 5 4 3 2 1 0:bit location
VJ<40>* or VJ@*
ASCII @ = 0 1 0 0 0 0 0 0 or <40>
Note: Avoid writing values <0A> (LF), <0D> (CR), <24> ($) and <2E> (*)
to the CSR. These values are interpreted by the meter as end of command
control codes and will prematurely end the write operation.
(AOR) Analog Output Register
The Analog Output Register controls the analog output of the meter. The
manual mode must first be engaged by setting bit 4 of the Control Status
Register. The range of values of this register is 0 to 4095, which corresponds to
0 mA, 0 V and 20 mA, 10 V; respectively. The table lists correspondence of the
output signal with the register value.
Register Value
Although the register is bit mapped starting with bit 7, HEX < > characters
are sent in the command string. Bits 7 and 5 always stay a zero, even if a “1” is
sent. This allows ASCII characters to be used with terminals that may not have
extended character capabilities.
Writing a “1” to bit 4 of CSR selects manual mode. In this mode, the setpoint
outputs are defined by the values written to the bits b0, b1, b2, b3; and the
analog output is defined by the value written to the AOR. Internal control of
these outputs is then overridden.
In automatic mode, the setpoint outputs can only be reset off. Writing to the
setpoint output bits of the CSR has the same effect as a Reset command (R). The
contents of the CSR may be read to interrogate the state of the setpoint outputs
and to check the status of the temperature sensor (PAXT only).
Output Signal*
I (mA)
V (V)
0
0.000
0.000
1
0.005
0.0025
2047
10.000
5.000
4094
19.995
9.9975
4095
20.000
10.000
*Due to the absolute accuracy
rating and resolution of the output
card, the actual output signal may
differ 0.15% FS from the table
values. The output signal
corresponds to the range selected
(20 mA or 10 V).
Writing to this register while the meter is in the manual mode causes the
output signal to update immediately. While in the automatic mode, this register
may be written to, but the output will not update until the meter is placed in
manual mode.
Examples:
1. Set output to full scale:
VI4095*
2. Set output to zero scale:
VI0*
Command Response Time
At the start of the time interval t1, the computer program prints or writes the
string to the com port, thus initiating a transmission. During t1, the command
characters are under transmission and at the end of this period, the command
terminating character (*) is received by the meter. The time duration of t1 is
dependent on the number of characters and baud rate of the channel.
The meter can only receive data or transmit data at any one time (half-duplex
operation). The meter ignores commands while transmitting data, but instead
uses RXD as a busy signal. When sending commands and data to the meter, a
delay must be imposed before sending another command. This allows enough
time for the meter to process the command and prepare for the next command.
t1 = (10 * # of characters) / baud rate
At the start of time interval t2, the meter starts the interpretation of the
command and when complete, performs the command function. This time
interval t2 varies from 2 msec to 50 msec. If no response from the meter is
expected, the meter is ready to accept another command.
If the meter is to reply with data, the time interval t2 is controlled by the use
of the command terminating character. The standard command line terminating
character is ‘*’. This terminating character results in a response time window of
50 msec minimum and 100 msec maximum. This allows sufficient time for the
release of the sending driver on the RS485 bus. Terminating the command line
with ‘$’ results in a response time window (t2) of 2 msec minimum and 50 msec
maximum. The faster response time of this terminating character requires that
sending drivers release within 2 msec after the terminating character is received.
At the beginning of time interval t3, the meter responds with the first
character of the reply. As with t1, the time duration of t3 is dependent on the
number of characters and baud rate of the channel. t3 = (10 * # of characters) /
baud rate. At the end of t3, the meter is ready to receive the next command.
The maximum serial throughput of the meter is limited to the sum of the
times t1, t2 and t3.
NO REPLY FROM METER
Ready
Command
String
Transmission
Meter
Response
Time
t1
t2
Ready
RESPONSE FROM METER
Ready
t1
t2
Command
Terminator
Received
First
Character
of Reply
t3
Ready
Reply
Transmission
Time
Timing Diagram Figure
27
Communication Format
LOGIC
INTERFACE STATE
RS232*
Stop bit
Start bit
Data is transferred from the meter through a serial communication channel.
In serial communications, the voltage is switched between a high and low level
at a predetermined rate (baud rate) using ASCII encoding. The receiving device
reads the voltage levels at the same intervals and then translates the switched
levels back to a character.
The voltage level conventions depend on the interface standard. The table
lists the voltage levels for each standard.
0 b0 b1 b2 b3 b4 b5 b6 b7 1
IDLE
IDLE
(8 data, no parity, 1 stop)
IDLE
0 b0 b1 b2 b3 b4 b5 b6 P 1
IDLE
(7 data, parity, 1 stop)
IDLE
RS485*
0 b0 b1 b2 b3 b4 b5 b6 1 1
1
mark (idle)
TXD,RXD; -3 to -15 V
a-b < -200 mV
(7 data, no parity, 2 stop)
0
space (active)
TXD,RXD; +3 to +15 V
a-b > +200 mV
Note: b0- b 7 is ASCII data.
* Voltage levels at the Receiver
IDLE
Character Frame Figure
Data is transmitted one byte at a time with a variable idle period between
characters (0 to ∞). Each ASCII character is “framed” with a beginning start bit,
an optional error detection parity bit and one or more ending stop bits. The data
format and baud rate must match that of other equipment in order for
communication to take place. The figures list the data formats employed by
the meter.
Parity bit
After the data bits, the parity bit is sent. The transmitter sets the parity bit to
a zero or a one, so that the total number of ones contained in the transmission
(including the parity bit) is either even or odd. This bit is used by the receiver
to detect errors that may occur to an odd number of bits in the transmission.
However, a single parity bit cannot detect errors that may occur to an even
number of bits. Given this limitation, the parity bit is often ignored by the
receiving device. The PAX meter ignores the parity bit of incoming data and
sets the parity bit to odd, even or none (mark parity) for outgoing data.
Start bit and Data bits
Data transmission always begins with the start bit. The start bit signals the
receiving device to prepare for reception of data. One bit period later, the least
significant bit of the ASCII encoded character is transmitted, followed by the
remaining data bits. The receiving device then reads each bit position as they are
transmitted. Since the sending and receiving devices operate at the same
transmission speed (baud rate), the data is read without timing errors.
Stop bit
The last character transmitted is the stop bit. The stop bit provides a single bit
period pause to allow the receiver to prepare to re-synchronize to the start of a
new transmission (start bit of next byte). The receiver then continuously looks
for the occurrence of the start bit.
6.8 MODULE 8 - Analog Output Parameters () Ñ
PARAMETER MENU
8-Out
PAR
tYPE
ASIN
Analog
Type
Analog
Assignment
AN-LO
AN-HI
Analog Low
Scale Value
Analog High
Scale Value
Ñ - An analog output card must be installed in order to access this
module.
 
 
Analog
Update Time
 
 
RANGE
0 to 20 mA



udt
0 to 10 V
 





to

to

Enter the analog output update rate in seconds. A value
of 0.0 allows the meter to update the analog output at a
rate of 20/sec.
PROBE BURN-OUT ACTION (PAXT ONLY)
Enter the source for the analog output to retransmit:
 = Display Input Value
 = Maximum Display Input Value
 = Minimum Display Input Value
 = Totalize Display Value

to

 


ANALOG LOW SCALE VALUE
 
 

Enter the Display Value that corresponds to 20 mA (0-20
mA) , 20 mA (4-20 mA) or 10 VDC (0-10 VDC).
ANALOG UPDATE TIME
ANALOG ASSIGNMENT

Burn-out
Action
4 to 20 mA
Enter the analog output type. For 0-20 mA or 4-20 mA
use terminals 18 and 19. For 0-10 V use terminals 16 and
17. Only one range can be used at a time.
 
 
burn
ANALOG HIGH SCALE VALUE
ANALOG TYPE
SELECTION
Pro
PAXT
ONLY

Enter the Display Value that corresponds to 0 mA (0-20
mA) , 4 mA (4-20 mA) or 0 VDC (0-10 VDC).
28


Enter the probe burn-out action. In the event of a
temperature probe failure, the analog output can be
programmed for low or high scale.
6.9 MODULE 9 - Factory Service Operations ()
Pro
9-FCS
PARAMETER MENU
PAR
d-LEV
COdE
Display
Intensity Level
Factory
Service Code
DISPLAY INTENSITY LEVEL
 


PAXP - Input Calibration
Enter the desired Display Intensity Level (0-15) by
using the arrow keys. The display will actively dim or
brighten as the levels are changed. This parameter also
appears in Quick Programming Mode when enabled.
WARNING: Calibration of this meter requires a signal source with an
accuracy of 0.01% or better and an external meter with an accuracy
of 0.005% or better.
The meter has been fully calibrated at the factory.
Scaling to convert the input signal to a desired display
value is performed in Module 1. If the meter appears to be
indicating incorrectly or inaccurately, refer to
Troubleshooting before attempting to calibrate the meter.
When recalibration is required (generally every 2 years), it should only be
performed by qualified technicians using appropriate equipment. Calibration
does not change any user programmed parameters. However, it may affect the
accuracy of the input signal values previously stored using the Apply ()
Scaling Style.
Calibration may be aborted by disconnecting power to the meter before
exiting Module 9. In this case, the existing calibration settings remain in effect.
Before starting, verify that the precision signal source is connected to the
correct terminals and ready. Allow a 30 minute warm-up period before
calibrating the meter.  and PAR can be chosen to exit the calibration mode
without any changes taking place.
Then perform the following procedure:
1. Use the arrow keys to display   and press PAR.
2. Choose the range to be calibrated by using the arrow keys and press PAR.
( and PAR can be chosen to exit the calibration mode without any changes
taking place.)
3. When the zero range limit appears on the display, apply the appropriate:
- Voltage range: dead short applied
- Current range: open circuit
4. Press PAR and  will appear on the display for about 10 seconds.
5. When the top range limit appears on the display, apply the appropriate:
- Voltage range: 10 VDC
- Current range: 20 mADC
6. Press PAR and  will appear on the display for about 10 seconds.
7. When  appears, press PAR twice.
8. If the meter is not field scaled, then the input display should match the value
of the input signal.
9. Repeat the above procedure for each input range to be calibrated.
PAXD - Input Calibration
PAXH - Input Calibration
RESTORE FACTORY DEFAULTS
 


Use the arrow keys to display   and press PAR.
The meter will display  and then return to  .
Press DSP key to return to Display Mode. This will
overwrite all user settings with the factory settings.
CALIBRATION
 


WARNING: In the PAXH, DC signals are used to calibrate the AC
ranges. Calibration of the PAXH requires a DC voltmeter with an
accuracy of 0.025% and a precision DC signal source capable of:
WARNING: Calibration of this meter requires a signal source with an
accuracy of 0.01% or better and an external meter with an accuracy
of 0.005% or better. Resistance inputs require a resistance
substitution device with an accuracy of 0.01% or better.
1. +1% of full scale, DC
2. -1% of full scale, DC
3. +100% of full scale, DC; (300 V range = +100 V calibration)
4. -100% of full scale, DC; (300 V range = -100 V calibration)
Before starting, verify that the Input Ranger Jumper is set for the range to be
calibrated. Also verify that the precision signal source is connected and ready.
Allow a 30 minute warm-up period before calibrating the meter.  and PAR
can be chosen to exit the calibration mode without any changes taking place.
Then perform the following procedure:
1. Use the arrow keys to display   and press PAR.
2. Choose the range to be calibrated by using the arrow keys and press PAR.
3. When the zero range limit appears on the display, apply the appropriate:
- Voltage ranges: dead short applied
- Current ranges: open circuit
- Resistance ranges: dead short with current source connected
4. Press PAR and  will appear on the display for about 10 seconds.
5. When the top range limit appears on the display, apply the appropriate:
- Voltage ranges: top range value applied (The 300 V range is the exception.
It is calibrated with a 100 V signal.)
- Current ranges: top range value
- Resistance ranges: top range value (The ohms calibration requires
connection of the internal current source through a resistance substitution
device and the proper voltage range selection.)
6. Press PAR and  will appear on the display for about 10 seconds.
7. When  appears, press PAR twice.
8. If the meter is not field scaled, then the input display should match the value
of the input signal.
9. Repeat the above procedure for each input range to be calibrated.
Before starting, verify the Input Range and Signal Jumpers are set for the
range to be calibrated and the Couple jumper is installed for DC. Also verify the
DC signal source is connected and ready. Allow a 30 minute warm-up period
before calibrating the meter.  and PAR can be chosen to exit the calibration
mode without any changes taking place.
Then perform the following procedure:
1. Press the arrow keys to display   and press PAR.
2. The meter displays . Use the arrow keys to select the range that matches
the Signal Jumper setting. Press PAR.
3. Apply the signal matching the meter prompt.
4. Press PAR and  will appear on the display, wait for next prompt.
5. Repeat steps 3 and 4 for the remaining three prompts.
6. When  appears, press PAR twice.
7. If the meter is scaled to show input signal, the Input Display should match
the value of the input signal in the Display Mode.
8. Repeat the above procedure for each range to be calibrated or to recalibrate
the same range. It is only necessary to calibrate the input ranges being used.
9. When all desired calibrations are completed, remove the external signal
source and restore original configuration and jumper settings. If AC is being
measured, continue with AC Couple Offset Calibration.
29
100 OHM RTD Range Calibration
AC Couple Offset Calibration - PAXH
1. Set the Input Range Jumper to 100 ohm.
2. Use the arrow keys to display   and press PAR. Then choose 
and press PAR.
3. At  , apply a direct short to input terminals 3, 4 and 5 using a three wire
link. Wait 10 seconds, then press PAR.
4. At  , apply a precision resistance of 300 ohms (with an accuracy of
0.01% or better) using a three wire link, to terminals 3, 4 and 5. Wait 10
seconds, press PAR.
5. Connect the RTD, return to the Display Mode and verify the input reading
(with 0 Display Offset) is correct. If not correct repeat calibration.
It is recommended that Input Calibration be performed first.
1. With meter power removed, set the Input Range Jumper for 20 V, the Couple
Jumper for DC, and set the Signal Jumper for voltage by removing the jumper.
2. Connect a wire (short) between Volt (terminal 6) and COMM (terminal 4).
3. Apply meter power.
4. In Module 1, program as follows: Range: ; Couple: ; Decimal Point:
; Round: ; Filter: ; Band: ; Points: ; Style: ; INP1: ; DSP1:
; INP2: ; DSP2: 
5. In Module 4, program as follows: Hi-t: ; Lo-t: 
6. Press PAR then DSP to exit programming and view the Input Display.
7. The readout displays the DC coupled zero input, record the value.
8. Remove the meter power and set the Couple Jumper to AC by removing the
jumper.
9. Maintaining the short between terminals 4 and 6, reapply the meter power.
10. Keeping all programming the same, view the Input Display.
11. The readout now displays the AC coupled zero input, record the value.
12. In Module 9, Use the arrow keys to display   and press PAR.
13. Press the down arrow key twice to  and press PAR.
14. Calculate the offset  using the following formula:
 = AC coupled reading (step 11) - DC coupled reading (step 7)
15. Use the arrow keys to enter the calculated .
16. Press PAR three times, to exit programming.
17. Remove the meter power and remove the short from terminals 4 and 6.
18. Restore the original jumper and configuration settings.
THERMOCOUPLE Range Calibration
1. Use the arrow keys to display   and press PAR. Then choose  and
press PAR.
2. At  , apply a dead short or set calibrator to zero to input terminals 4 and
5. Wait 10 seconds, then press PAR.
3. At  , apply 50.000 mV input signal (with an accuracy of 0.01% or
better) to input terminals 4 and 5. Wait 10 seconds, then press PAR.
4. Return to the Display Mode.
5. Continue with Ice Point Calibration.
ICE POINT Calibration
1. Remove all option cards or invalid results will occur.
2. The ambient temperature must be within 20°C to 30°C.
3. Connect a thermocouple (types T, E, J, K, or N only) with an accuracy of 1°C
or better to the meter.
4. Verify the readout Display Offset is 0, Temperature Scale is °C, Display
Resolution is 0.0, and the Input Range is set for the connected thermocouple.
5. Place the thermocouple in close thermal contact to a reference thermometer
probe. (Use a reference thermometer with an accuracy of 0.25°C or better.)
The two probes should be shielded from air movement and allowed sufficient
time to equalize in temperature. (A calibration bath could be used in place of
the thermometer.)
6. In the Normal Display mode, compare the readouts.
7. If a difference exists then continue with the calibration.
8. Enter Module 9, use the arrow keys to display   and press PAR. Then
choose  and press PAR.
9. Calculate a new Ice Point value using: existing Ice Point value + (reference
temperature - Display Mode reading). All values are based on °C.
10. Enter the new Ice Point value.
11. Return to the Display Mode and verify the input reading (with 0 Display
Offset) is correct. If not correct repeat steps 8 through 10.
PAXS - Input Calibration
WARNING: Calibration of this meter requires a signal source with an
accuracy of 0.01% or better and an external meter with an accuracy of
0.005% or better.
Before starting, connect -SIG (terminal 4) to COMM (terminal 5).
This allows a single ended signal to be used for calibration. Connect the
calibration signal to +SIG (terminal 3) and -SIG (terminal 4). Verify the Input
Range jumper is in the desired position. Allow a 30 minute warm-up period
before calibrating the meter.  and PAR can be chosen to exit the calibration
mode without any changes taking place. Perform the following procedure:
1. Press the arrow keys to display   and press PAR.
2. Choose the range to be calibrated by using the arrow keys and press PAR.
3. When the zero range limit appears on the display, apply 0 mV between +SIG
and -SIG.
4. Press PAR and ---- will appear, wait for next prompt.
5. When the top range limit appears on the display, apply the corresponding
+SIG and -SIG voltage (20 mV or 200 mV).
6. Press PAR and ---- will appear, on the display for about 10 seconds.
7. When  appears, press PAR twice to exit programming.
8. Repeat the above procedure for each range to be calibrated or to recalibrate
the same range. It is only necessary to calibrate the input ranges being used.
9. When all desired calibrations are completed, remove -SIG to COMM
connection and external signal source.
10. Restore original configuration and jumper settings.
ANALOG OUTPUT CARD CALIBRATION
Before starting, verify that the precision voltmeter (voltage output) or current
meter (current output) is connected and ready. Perform the following procedure:
1. Use the arrow keys to display   and press PAR.
2. Use the arrow keys to choose  and press PAR.
3. Using the chart below, step through the five selections to be calibrated. At
each prompt, use the PAX arrow keys to adjust the external meter display to
match the selection being calibrated. When the external reading matches, or
if this range is not being calibrated, press PAR.
PAXT - Input Calibration
SELECTION
Warning: Calibration of this meter requires precision instrumentation
operated by qualified technicians. It is recommended that a
calibration service calibrates the meter.
EXTERNAL METER
ACTION
0.00
Adjust if necessary, press PAR

4.00
Adjust if necessary, press PAR

20.00
Adjust if necessary, press PAR

0.00
Adjust if necessary, press PAR

10.00
Adjust if necessary, press PAR

4. When  appears remove the external meters and press PAR twice.
Before selecting any of the calibration procedures, the input to the meter
must be at 0 mV or 0 ohms. Set the digital filer in Module 1 to 1 second. Allow
a 30 minute warm-up period before calibrating the meter. The  and PAR can
be chosen to exit calibration mode without any changes taking place.
10 OHM RTD Range Calibration
1. Set the Input Range Jumper to 10 ohm.
2. Use the arrow keys to display   and press PAR. Then choose 
and press PAR.
3. At  , apply a direct short to input terminals 3, 4 and 5 using a three wire
link. Wait 10 seconds, then press PAR.
4. At  , apply a precision resistance of 15 ohms (with an accuracy of 0.01%
or better) using a three wire link, to input terminals 3, 4 and 5. Wait 10
seconds, then press PAR.
5. Connect the RTD, return to the Display Mode and verify the input reading
(with 0 Display Offset) is correct. If not correct repeat calibration.
30
TROUBLESHOOTING
PROBLEM
REMEDIES
NO DISPLAY
CHECK: Power level, power connections
PROGRAM LOCKED-OUT
CHECK: Active (lock-out) user input
ENTER: Security code requested
MAX, MIN, TOT LOCKED-OUT
CHECK: Module 3 programming
INCORRECT INPUT DISPLAY VALUE
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level,
Module 4 Display Offset is zero, press DSP for Input Display
PERFORM: Module 9 Calibration (If the above does not correct the problem.)
“OLOL” in DISPLAY (SIGNAL HIGH)
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
“ULUL” in DISPLAY (SIGNAL LOW)
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
JITTERY DISPLAY
INCREASE: Module 1 filtering, rounding, input range
CHECK: Wiring is per EMC installation guidelines
MODULES or PARAMETERS NOT ACCESSIBLE
CHECK: Corresponding plug-in card installation
ERROR CODE (Err 1-4)
PRESS: Reset KEY (If cannot clear contact factory.)
DISPLAY ZERO’S AT LEVELS BELOW 1% OF RANGE
PROGRAM: Module 4 as Hi-t: 0.0 LO-t: 3271.1 (to disable zero chop feature)
For further assistance, contact technical support at the appropriate company numbers listed.
PARAMETER VALUE CHART Programmer ________________ Date ________
PAX MODEL NUMBER ________ Meter# _____________ Security Code __________

Signal Input Parameters
FACTORY
SETTING
DISPLAY
PARAMETER












 
 
 
 
 
 
 
 
 
 
MODEL DEPENDENT
PAXT: INPUT TYPE
PAXT: TEMPERATURE SCALE
PAXH: INPUT COUPLE
* DISPLAY RESOLUTION
DISPLAY ROUNDING INCREMENT
PAXT: DISPLAY OFFSET
FILTER SETTING
-
PAXH
FILTER ENABLE BAND - PAXH
PAXT: ICE POINT SLOPE
SCALING POINTS
SCALING STYLE - NOT PAXT
* INPUT VALUE 1
* DISPLAY VALUE 1
* INPUT VALUE 2
* DISPLAY VALUE 2
* INPUT VALUE 3
* DISPLAY VALUE 3
* INPUT VALUE 4
* DISPLAY VALUE 4
* INPUT VALUE 5
* DISPLAY VALUE 5


USER SETTING





















* Decimal point location is model and programming dependent.
31
DISPLAY
PARAMETER






















* INPUT VALUE 6






















* DISPLAY VALUE 6
* INPUT VALUE 7
* DISPLAY VALUE 7
* INPUT VALUE 8
* DISPLAY VALUE 8
* INPUT VALUE 9
* DISPLAY VALUE 9
* INPUT VALUE 10
* DISPLAY VALUE 10
* INPUT VALUE 11
* DISPLAY VALUE 11
* INPUT VALUE 12
* DISPLAY VALUE 12
* INPUT VALUE 13
* DISPLAY VALUE 13
* INPUT VALUE 14
* DISPLAY VALUE 14
* INPUT VALUE 15
* DISPLAY VALUE 15
* INPUT VALUE 16
* DISPLAY VALUE 16
FACTORY
SETTING






















USER SETTING

User Input and Function Key Parameters
DISPLAY
PARAMETER








USER INPUT 1

FACTORY
SETTING








USER INPUT 2
USER INPUT 3
FUNCTION KEY 1
FUNCTION KEY 2
RESET KEY
2nd FUNCTION KEY 1
2nd FUNCTION KEY 2
Display and Program Lockout Parameters
FACTORY
SETTING
DISPLAY
PARAMETER








MAX DISPLAY LOCKOUT

Secondary Function Parameters
DISPLAY








USER SETTING








MIN DISPLAY LOCKOUT
TOTAL DISPLAY LOCKOUT
SETPOINT 1 ACCESS
SETPOINT 2 ACCESS
SETPOINT 3 ACCESS
SETPOINT 4 ACCESS
SECURITY CODE
MAX CAPTURE DELAY TIME
MIN CAPTURE DELAY TIME
DISPLAY UPDATE TIME
PAXS: AUTO-ZERO DELAY
PAXS: AUTO-ZERO BAND
DISPLAY OFFSET - NOT PAXT
PAXT: ICE POINT COMPENSATION

Totalizer (Integrator) Parameters
DISPLAY
PARAMETER





* TOTALIZER DECIMAL POINT

Serial Communication Parameters
USER SETTING








Setpoint (Alarm) Parameters
* TOTALIZER LOW CUT VALUE
TOTALIZER POWER-UP RESET
DISPLAY
PARAMETER


SETPOINT ACTION
* SETPOINT VALUE (main)
* SETPOINT VALUE (alternate) 








* SETPOINT HYSTERESIS
ON TIME DELAY
OFF TIME DELAY
OUTPUT LOGIC
RESET ACTION
STANDBY OPERATION
SETPOINT ANNUNCIATORS
PAXT: PROBE BURN-OUT ACTION











USER SETTING
FACTORY
USER SETTING
SETTING
DISPLAY
PARAMETER












BAUD RATE
PARITY BIT
METER ADDRESS
ABBREVIATED PRINTING
ENTER PRINT OPTIONS
PAXS: PRINT GROSS OFFSET
PAXS: PRINT TARE OFFSET
PRINT INPUT VALUE
PRINT TOTAL VALUE
PRINT MAX & MIN VALUES
PRINT SETPOINT VALUES
Analog Output Parameters
FACTORY
USER SETTING
SETTING
PARAMETER






ANALOG TYPE
* ANALOG LOW SCALE VALUE
* ANALOG HIGH SCALE VALUE
ANALOG UPDATE TIME
PAXT: PROBE BURN-OUT ACTION
Factory Setting Parameters
FACTORY
USER SETTING
SETTING
PARAMETER

DISPLAY INTENSITY LEVEL












 Select alternate list to program these values.
* Decimal point location is model and programming dependent.
32






ANALOG ASSIGNMENT
DISPLAY
FACTORY
SETTING












DATA BIT
DISPLAY

FACTORY
SETTING
USER SETTING





TOTALIZER SCALE FACTOR


FACTORY
SETTING
TOTALIZER TIME BASE

FACTORY
SETTING
PARAMETER
UNITS LABEL BACKLIGHT - PAXT
USER SETTING

USER SETTING


FACTORY
SETTING











USER SETTING

FACTORY
SETTING











USER SETTING
33
9-FCS
8-Out
7-SrL
6-SPt
5-tOt
4-SEC
HI
3-LOC
CodE
Factory
Service Code
d-LEv
Display
Intensity
Level
ASIN
Analog
Assignment
tYPE
Data
Bit
Analog
Type
dAtA
Baud
Rate
Setpoint
Action
Setpoint
Select
bAUd
ACt-n
Totalizer
Time Base
SPSEL
tbASE
Totalizer
Decimal Point
Min. Capture
Delay Time
LO-t
Min. Display
Lock-out
LO
USER INPUTS
USr-2
dECPt
Max. Capture
Delay Time
HI-t
Max. Display
Lock-out
USr-1
SCALE
Temperature
Scale
Input
Type
Input
Couple
tYPE
COUPL
Input
Range
PAXH
ONLY
rAN6E
2-FNC
PAXT 1-INP
ONLY
1-INP
F1/F2 Keys
Pro
Analog Low
Scale Value
AN-LO
Parity
Bit
PAr
Setpoint
Value
SP-n
Totalizer
Scale Factor
SCFAC
Display
Update
Time
dSP-t
Total Display
Lock-out
tOt
USr-3
Display
Decimal Point
dECPt
Display
Resolution
dECPt
Analog High
Scale Value
AN-HI
Meter
Address
Addr
Setpoint
Hysteresis
HYS-n
At-b
P-UP
Abrv
burn
Probe
Burn-out
Action
udt
PAXT ONLY
Print
Options
OPt
Off Time
Delay
Print Gross
Value
ICE
PAXT
ONLY
Print Tare
Value
Print Input
Value
INP
Standby
Operation
Stb-n
LIt-n
Display x
Value
dSP x
Display x
Value
dSP x
Print Total
Value
tot
Setpoint
Annunciators
INP x
Ice Point
Compensation
tarE
PAXS
ONLY
PAXS
ONLY
6roSS
Reset
Action
rSt-n
Display
Offset
Value
Output
Logic
out-n
CodE
Security
Code
OFFSt
PtS
Input x
Value
INP x
Scaling
Input x
Points
Value
Custom Scaling Only
Sc-F2
NOT
PAXT
n= Setpoint Selected
Analog
Update
Time
Abbreviated
Printing
SP-4
Setpoint 4
Access
Units Label
BackLight
ICE
Scaling
Style
StYLE
Ice Point
Slope
Sc-F1
Filter
Band
b-LIt
tOF-n
Totalizer
Power Up
Reset
SP-3
Setpoint 3
Access
PtS
Scaling
Points
bANd
FUNCTION KEYS
rSt
Filter
Setting
Auto-Zero
Tracking
Band
On Time
Delay
Filter
Band
bANd
FILtr
PAXS
ONLY
tON-n
Totalizer Low
Cut Value
Locut
Auto-Zero
Tracking Delay
Time
At-t
PAXS
ONLY
SP-2
Setpoint 2
Access
SP-1
F2
Display
Offset
OFFSt
Filter
Setting
FILtr
Setpoint 1
Access
F1
Display
Rounding
round
Display
Rounding
round
SPNt
Print Setpoint
Values
HILO
Print Max
& Min
Values
Burn-out
Action
brn-n
PAXT
ONLY
Pro
PAX PROGRAMMING QUICK OVERVIEW
This page intentionally left blank.
34
This page intentionally left blank.
35
LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and workmanship
for a period limited to two years from the date of shipment, provided the products have been stored,
handled, installed, and used under proper conditions. The Company’s liability under this limited
warranty shall extend only to the repair or replacement of a defective product, at The Company’s
option. The Company disclaims all liability for any affirmation, promise or representation with
respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against
damages, claims, and expenses arising out of subsequent sales of RLC products or products
containing components manufactured by RLC and based upon personal injuries, deaths, property
damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be
to any extent liable, including without limitation penalties imposed by the Consumer Product Safety
Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty
Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except
those expressly contained herein. The Customer acknowledges the disclaimers and limitations
contained herein and relies on no other warranties or affirmations.
Red Lion Controls
Headquarters
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
Red Lion Controls
Europe
Softwareweg 9
NL - 3821 BN Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India
201-B, 2nd Floor, Park Centra
Opp 32 Mile Stone, Sector-30
Gurgaon-122002 Haryana, India
Tel +91 984 487 0503
Red Lion Controls
China
Unit 302, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113 3688
Fax +86 21 6113 3683

advertisement