1.6 Installation
1.3 Panel Function Explanation
PANEL COMPONENT
Alarm Indication LED
(RED)
ELC-GP04
GRAPHIC PANEL SERIES
Instruction Sheet
EXPLANATION
Status 1: When power is on, the LED will flash three times slowly.
Status 2: When there is an abnormal situation, the LED will flash quickly along with an
alarm sound.
RS-232 Indication LED
(Yellow)
It will be flashing when transmitting program and communicating by using RS-232.
RS-485/RS-422
Indication LED (Green)
It will be flashing when communicating by using RS-485/RS-422.
LCD Display Area
Liquid Crystal Module display area used to display current program state.
Escape/Exit
Used to cancel an incorrect input, or to Exit a programming step.
Mounting ELC-GP04 into the opening is done by carefully fitting the unit into the opening and
pressing firmly on all four corners. You could fix it by using the fixed support packaged with
ELC-GP04.
Warning: If you turn the screw exceeds torque: 4-5(kg-cm), ELC-GP04 may be damaged.
(Note the flat surface shoud be a Type 4 “Indoor Use Only” enclosure or equivalent.)
Please leave sufficient space (more than 50mm) around the unit for heat dissipation.
:
Thickness:
0.5~9.0mm
Mounting dimension (unit: mm [inch])
WARNING
Please carefully read this instruction before using the ELC-GP04.
DANGER! DC input power must be disconnected before any maintenance. Do not connect or
50mm
disconnect wires and connectors while power is applied to the circuit. Maintenance must be
performed by qualified technicians.
The ELC-GP04 display panel is waterproof. But please prevent grease, corrosive liquids and
sharp objects from contacting the ELC-GP04.
DANGER! The ELC-GP04 requires 24VDC input power. The 24VDC input power should not
be connected to the RS-485 communication port. The unit may be destroyed or can’t be
repaired if the input power is improperly applied. Please always check the correctly input
power wiring before apply power.
85
[3.35]
UP/Pg Up: Used to increase the value or move up one page.
Pg Dn/DOWN: Used to decrease the value or move down one page.
Arrow Keys
Left: Left direction key. (move curser to left)
Right: Right direction key. (move cursor to right)
135~136.5[5.31~5.37]
Thickness Range 0.5~9mm
Shift Key
Used to select keys F5, F6, F7, F8, F9.
Enter Key
Used to input a value or accept a programming command.
F0/F5: They are used to be constant 0 (F0) and 5 (Shift+F0) when they are in system
F1/F6: They are used to be constant 1 (F1) and 6 (Shift+F1) when they are in system
has been removed. Do not conduct any wiring or investigation on the ELC-GP04 until 1
minute after power has been removed. Do NOT touch terminals when power on.
SPECIFICATION
2.1 Electrical Specification
ITEM
menu and user can define the functions separately when they are in user page.
F2/F7: They are used to be constant 2 (F2) and 7 (Shift+F2) when they are in system
Function Keys
menu and user can define the functions separately when they are in user page.
Function Key/Digital Key
menu and user can define the functions separately when they are in user page.
F4/F9: They are used to be constant 4 (F4) and 9 (Shift+F4) when they are in system
adjusted too tight.
menu and user can define the functions separately when they are in user page.
1.4 Back Panel
Memory Capacity
256K Byte
CPU
Hitachi HD64F3064F
RAM of System
Environment Condition
BATTERY
SWITCH OR
RS-485/422
Division 2.
Storage Temperature for Hardware
5-PIN terminals:
Wire gauge: 12-24 AWG
Torque: 4.5 lb.-inch
WARNING – Explosion Hazard – Do not disconnect equipment unless power has been
switched off or the area is known to be Non – Hazardous.
32K Byte
COM1: RS232; COM2: RS485/RS422(See Section 6)
1.5 Dimension
INTRODUCTION
Front panel (unit: mm [inch])
1.1 Model Explanation
Right side diagram (unit: mm [inch])
CISPR22, Class A
Electrostatic Discharge Immunity
EN61000-4-2/1995
Radiated Immunity
EN61000-4-31995
Electrical Fast Transient
EN61000-4-4/1995
Weight/Dimension
Temperature Code
85.00
[3.35]
℃, relative humidity 20-90% RH (non-condensing)
-20~60℃
Radiated Emission
Cooling Method
97.00
[3.82]
0~50
10G, 11ms, from X, Y, Z three directions and three times for each
direction
Impact
methods, Article 501-4 (b) of the National Electrical Code, NEPA 70,or as specified in Section
18-152 of the Canadian Electrical Code for units installed within Canada, and in accordance
with that location’s authority.
IP65/NEMA4/UL Type 4 (indoor use)
0.5mm displacement, 10-55Hz, X, Y, Z three directions and two hours
for each direction
Vibration
Power, input and output (I/O) wiring must all be in accordance with Class I, Division 2 wiring
Possess extension slot for ELC-GPXFERMOD to copy settings and programs rapidly and save
download time. Built-in variety objects to meet your requirement.
24VDC (-15%~20%) 3.5W MAX.
Waterproof Class of Front Panel
WARNING – Explosion Hazard – Substitution of components may impair suitability for class I,
Thank you for choosing Eaton Logic Controller (ELC) GP Series. The features of ELC-GP04 are:
resolution is 128*64, display 8*4 Chinese characters (max.) and multi-language support. It is built-in
two communication ports (RS-232 and RS-485/RS-422, can be used simultaneously), and Built-in
RTC and communication/alarm indication LED.
F0~F4, ESC, SHIFT, ENTER and ARROW keys
External Input Power
Communication Interface
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or Non-Hazardous
Locations only.
1
ELC-GP04
F3/F8: They are used to be constant 3 (F3) and 8 (Shift+F3) when they are in system
CAUTION! ELC-GP04 may be damaged if the fixed support (shipped with the pack) is
Battery replacement: please use UL component type: CR2032 lithium battery (NOTE: RTC
should be reset after changing battery).
2
menu and user can define the functions separately when they are in user page.
DANGER! An electrical charge will remain on the DC-link capacitors for 1 minute after power
CAUTION! Always ground the ELC-GP04 by using the grounding terminal. Not only this acts
as a safety, but also filter out electrical noise. The ground method must comply with the laws
of the country where the unit is to be installed.
50mm
Hazardous Location rating
0.24kg/147×97×35.5mm (Width × Height × Deep)
Natural Air Cooling
T6
Class I, Division 2, Group A, B, C, and D
2.2 Function Specification
ITEM
1.2 Outline
147.00 [5.79]
Vertical view (Unit: mm)
Display Screen
Screen
Color
Backlight
Resolution
Display Range
Contrast Adjustment
ELC-GP04
STN-LCD
Monochromatic
The back-light automatic turn off time is 1~99 minutes
(0 = do not turn off)
(back-light life is about 50 thousand hours at 25 )
℃
128X64 Points
72mm (W) X 40mm (H); 3.00” (diagonal preferred)
10-step contrast adjustment
IL05003006E.pdf
F1/F6: scrolls in a loop as follows 1 6 G H I J K 1
ASCII: characters
Other: user define
Font
F2/F7: scrolls in a loop as follows 2 7 L M N O P 2
5X 8: 25 words X 8 rows
COMMUNICATION CONNECTION
■ ELC-GP04 may connect to a PC by using cable ELC-CBPCGP3
F3/F8: scrolls in a loop as follows 3 8 Q R S T U V 3
8X8: 16 words X 8 rows
Maximum Words x Rows,
for Each Font Size
6
ELC-CBPCGP3
F4/F9: scrolls in a loop as follows 4 9 W X Y Z 4
8X12: 16 words X 5 rows
ON PC (R S-232)
8X16: 16 words X 4 rows
Font Size
ASCII: 5X8, 8X8, 8X12, 8X16
The steps to Startup the ELC-GP04:
It will be flashing when transmitting program and communicating by using
RS-232.
2. Enter into the startup display,
RS-485/RS-422 Indication
LED (green)
It will be flashing when communicating by using RS-485/RS-422.
Program Memory
256KB flash memory
RS-232
Data length: 7 or 8 bits, Stop bits: 1or 2 bits
Parity: None/Odd/Even,
Transmission speed: 9600bps~115200bps
RS-232: 9 PIN D-SUB male
Serial Communication Port
RS-232 (COM1)
External Interface
HARDWARE OPERATION
1. Power on indication (Flash three times)
2. Flash for communication error or other alarm
3. Special Indication by user programming
Alarm Indication LED
(RED)
RS-232 Indication LED
(Yellow)
5
5
1
6
6
1
5
9
9 PIN D-SUB
9 PIN D-SUB
1. Apply 24V DC power,
PC COM Port
3. Enter the user-designed program,
9 PIN D-SUB female
4. Press Esc key and hold on for 5 seconds to return to system menu.
There are five selections in the system menu and are described below.
SELECTIONS
ON ELC-GP02/04
9
9 PIN D-SUB female
Rx
2
3
Tx
GND
5
5
GND
EXPLANATION
■ ELC-GP04 may connect to a ELC by using cable ELC-CBPCELC3
Use the connection cable (ELC-CBPCGP3) to connect the serial communication port RS-232
Download
Program
of ELC-GP04 to a PC. Then use the ELCSoftGP software to download an application program
to the ELC-GP04.
RS-485/RS-422
Data length: 7 or 8 bits, Stop bits: 1 or 2 bits
Parity: None/Odd/Even
Transmission speed: 9600bps~115200bps
RS-422: 9 PIN D-SUB male
RS-485: 5-Pin removal terminal
Extension Communication
Port RS-422/RS-485
(COM2)
Extension Slot
1. Update program version 2.The slot for program copy card
Battery Cover
DC 3V battery for HMI
5-Pin Removal Terminal
There are DC 24V input and RS-485 input
Use the connection cable (ELC-CBPCGP3) to connect the serial communication port RS-232
Upload Program
of ELC-GP04 to a PC. Then use the ELCSoftGP software to upload an application program
from the ELC-GP04.
PC/HMI COM Port
9 PIN D-SUB female
Transfer a program between two ELC-GP04 units.
Rx
2
GND
7
8
1: transmit programs
1
4
6
2: receive programs
Copy Program
When transmitting programs and data between two ELC-GP04 units. Set one ELC-GP04 to
ELC COM1 Port
8 PIN MINI DIN
2
Rx
4
1,2
GND
5V
5
4
8
7
1
3
6
“Receive Program” mode and the other ELC-GP04 to “Transmit Program” mode. Please use
3
TRANSFER MODULE
twisted pair wires to connect the two units via the RS-485 ports.
There are 8 items that used to modify ELC-GP04 system settings:
The function of transfer module that ELC-GP04 provides to copy user program, system function and
passwords is different from the copy program. It is used to copy the whole HMI environment settings
and application programs to another HMI rapidly. It can save much time and manpower. The
operation is in the following.
1
Turn the switch on the XMOD to GPXMOD
Turn the switch on the XMOD to XMODGP
2
Insert the XMOD into the extension slot of GP
Insert the XMOD into the extension slot of GP
3
Input the power to GP
Input the power to GP
4
It will display “remove XMOD” on the screen and
It will display “remove XMOD” on the screen and
power on again
power on again
RS-232 9 PIN D-SUB male
the communication string for either RS-232 or RS-485.
2. Contrast: Adjust the contrast of LCD screen.
3. Back-light: adjust the automatic turn off time of LCD. Setting range is 00~99 seconds. If
3
Tx
5
GND
set to 00, the LCD Back-light will not turn off.
XMODGP
GPXMOD
RS-232:
1. Communication protocol: Setting the address of ELC-GP04, the control port of ELC, and
Definition: Transfer module (ELC-GPXFERMOD) = XMOD, GP Series = GP
Step
■ The Pin definition of 9 PIN D-SUB
4. Date and Time: It is used to set the ELC-GP04 built-in RTC including year, month, day,
RS-422:
hour, minute, second and week. Also the internal battery capacity display is shown here.
ELC-GP04
Settings
RS-422 9 PIN D-SUB male
5. Buzzer: Used to set the buzzer sound, normal mode or quiet mode.
6
6. Language Setting: Used to set the displayed language. English, Traditional Chinese,
8
9
simplified Chinese or user defined language.
Rx +
Tx +
Tx -
7. Password setting: Used to set, enable, and disable the password function. If the password
function is enabled, it will require the user to input a password before entering any system
HMI display message
■ Switch between RS-422 / RS-485 (by using 8-PIN DIP switch)
menu. The factory password is 1234.
Copy HMI program to XMOD (GPXMOD)
8. Startup display: Used to select the ELC-GP04 startup display. User can select “user
Copy XMOD program to HMI (XMODGP)
If the model type of GP does not correspond with the
If there is no program in XMOD, GP will display “The
model type of program of XMOD, GP will display “GP
XMOD is Empty. XMODGP series is illegal”.
defined” to use the file that designed by ELCSoftGP and download to ELC-GP04.
9. Comm. Indicator : Used to select the communication Indicator enable or disable.
series and XMOD is different. Press Enter to Confirm
There are three methods to connect to ELC:
8-PIN DIP switch
RS-485
RS-422
SW1~SW4
On
Off
SW5~SW8
Off
On
7
BATTERY LIFE AND PRECISION OF CALENDAR TIMER
GP seriesXMOD. Press Esc to Exit”.
Using serial communication port (COM1) RS-232 of ELC-GP04: set 8-pin DIP switch to
GP will display “GP XMOD series Please wait!” during GP will display “XMOD GP series Please wait!”
transmission.
during transmission.
GP will display “Please Remove the XMOD and
GP will display “Please Remove the XMOD and
Reboot !” when completing transmitting.
Reboot !” when completing transmitting.
RS-485 mode and connect the cable (ELC-CBPCELC3) to program communication I/O
RS-232C of ELC.
ELC Connection
1.
2.
Using extension communication port (COM2): set 8-pin DIP switch to RS-422 mode and
If the password is forgotten, the password may be cleared using the following code: 8888. This
connect four pins (6, 7, 8, 9) of 9 PIN D-SUB male to RS-422 of ELC with 4-wire cable.
universal code will clear the password and all internal programs of ELC-GP04. The ELC-GP04
will be re-set to the factory settings.
Execute the internal program that download from ELCSoftGP or transmitted from other
F0~F4 to input the password characters.
F0/F5: scrolls in a loop as follows 0 5 A B C D E F 0
-20
0
20
60
Life (year)
1.972
2.466
2.712
2.835
connect 5-pin removal terminal of extension communication port to RS-485 of ELC with
PASSWORD FUNCTION
Users may use 0~9 and A~Z as characters for the password. Users must use the function keys
°
Temperature ( C)
Using extension communication port (COM2): set 8-pin DIP switch to RS-485 mode and
twisted pair.
4
■ Battery life
Execution
ELC-GP04 units. When entering execution program, you can return to system menu by
pressing Escape/Exit (Esc) key for 5 seconds.
■ Precision of calendar timer(sec)
°
°
At 0 C/32 F, less than –117 seconds error per month.
° °
At 55°C/131°F, less than –132 seconds error per month.
At 25 C/77 F, less than 52 seconds error per month.