Lighting Contactors Class 8903

Lighting Contactors Class 8903

Lighting Contactors

Class 8903

CONTENTS

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page

Product Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 modifications (Forms) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Multipole Lighting Contactors (50-60 Hz)

Contact

Ampere

Ratings

No.

of

Poles

NEMA Type 1

General Purpose

Enclosure

Type

Electrically Held

c

30 p

6

8

10

2

3

4

12

Mechanically Held

c

LG20 t

LG30 t

LG40 t

LG60 t

LG80 t

LG1000 t

LG1200 t

NEMA Type 1

Flush Mounting

General Purpose

Enclosure with

Plaster Adjustment

Type

LF20 t

LF30 t

LF40 t

LF60 t

LF80 t

LF1000 t

LF1200 t

NEMA Type 3R

Rainproof

Enclosure

Type

LH20 t

LH30 t

LH40 t

LH60 t

LH80 t

LH1000 t

LH1200 t

NEMA Type 4 & 4X

Watertight, Dusttight and Corrosion-

Resistant Glass-

Polyester Enclosure

Type

LWW20 t

LWW30 t

LWW40 t

LWW60 t

LWW80 t

LWW1000 t

LWW1200 t q

NEMA Type 4 & 4X

Watertight, Dusttight

Brushed Stainless

Steel Enclosure

Type

LW20 t

LW30 t

LW40 t

LW60 t

LW80 t

LW1000 t

LW1200 t

NEMA Type 12 u

Dusttight and

Driptight Industrial

Use Enclosure

Type

LA20 t

LA30 t

LA40 t

LA60 t

LA80 t

LA1000 t

LA1200 t

Open Type k

Type

LO20 t

LO30 t

LO40 t

LO60 t

LO80 t

LO1000 t

LO1200 t

30 p

6

8

10

2

3

4

12

LXG20

LXG30

LXG40

LXG60

LXG80 t t t t t

LXG1000

LXG1200 t t

LXF20

LXF30

LXF40

LXF60

LXF80 t t t t t

LXF1000

LXF1200 t t

....

....

....

....

....

....

....

LXWW20

LXWW30

LXWW40

LXWW60

LXWW80 t t t t t

LXWW1000

LXWW1200 t t

LXW20

LXW30

LXW40

LXW60

LXW80 t t t t t

LXW1000

LXW1200 t t

LXA20

LXA30

LXA40

LXA60

LXA80 t t t t t

LXA1000

LXA1200 t t

LXO20

LXO30

LXO40

LXO60

LXO80 t t t t t

LXO1000

LXO1200 t t u k q t p c

NEMA Type 12 enclosures may be field modified for outdoor applications. For details, see the Class 9991 section in Catalog 9999CT9701.

Separate enclosures are available for these devices. It may be possible to improve delivery by ordering an open type contactor and separate Class 9991 enclosure.

For electropolished finish, specify Form

G16

.

Coil voltage code must be specified to order this product. Refer to standard voltage codes listed below.

Factory conversion of N.O. contacts to N.C., order by description. There is a maximum of eight N.C. poles for Type L and a maximum of six N.C. poles for Type LX contactors (field conversion only).

Versions are available with up to 12 N.C. poles (factory only).

All lighting contactors are provided with separate control as standard.

Power Poles for Type L or LX

The kits below are used to add 30 Ampere power poles to existing Type L contactors when additional circuits are required. Type L lighting contactors are supplied with mounting brackets, so that adder poles may be mounted from the front by a single captive screw.

Adder poles are supplied standard with N.O. contacts which are convertible to N.C.

Power Pole Adder Kit

Class 8903 Type

Single Pole

Can Only Be Added to Contactor Type

Power Pole Adder Kit

Class 8903 Type

Double Pole

Can Only Be Added to Contactor Type

L1L

L1R

LO60

LO80

LXO60

LXO80

L3L

L3R

LO80

LO1000 a

LXO80

LXO1000 a a

Single-pole power pole must be removed before double-pole power pole can be installed.

Coil Voltage Codes

Voltage

Code

60 Hz

24

120

208

240

277

480

Specify

50 Hz

...

110

...

220

...

440

Specify

V01

V02

V08

V03

V04

V06

V99

2

© 1998 Square D All Rights Reserved

1/98

Lighting Control

Multipole Lighting Contactors, Type S – Class 8903

Features

• Electrically and mechanically held

• 30 - 800 Amp lighting ratings

• 2 thru 5 pole versions (5 poles thru 200 Amps)

• UL Listed short-circuit rating up to 100,000 Amperes

• Mixed load ratings (lighting and motor)

• Factory wired controls and clearly marked termination points

• Quick ship on most items in 5-7 days

File E78427

CCN NRNT

File LR60905

(Open Devices Only)

Class 3231 01

Multipole Lighting Contactors – Type S (50-60 Hz)

Contact

Ampere

Ratings

No.

of

Poles

NEMA Type 1

General Purpose

Enclosure

NEMA Type 1

Flush Mounting

General Purpose

Enclosure with

Plaster Adjustment

NEMA Type 3R

Rainproof

Enclosure

NEMA Type 4 & 4X

Watertight, Dusttight and Corrosion-

Resistant Glass-

Polyester Enclosure

NEMA Type 4 & 4X q

Watertight and

Dusttight Enclosure

NEMA Type 12 u

Dusttight and

Driptight Industrial

Use Enclosure

Open Type

Type Type

Rainproof Enclosure

Type

Type Type Type Type

Electrically Held

p

30

60

100

200

300

400

600

800 c c c

4

5

2

3

4

5

2

3

4

5

2

3

4

5

2

3

2

3

2

3

2

3

2

3

Mechanically Held

p

SMG1 t

SMG2 t

SMG3 t

SMG4 t

SPG1 t

SPG2 t

SPG3 t

SPG4 t

SQG1 t

SQG2 t

SQG3 t

SQG4 t

SVG1 t

SVG2 t

SVG3 t

SVG4 t

SXG1 t

SXG2 t

SYG1 t

SYG2 t

SZG1 t

SZG2 t

SJG1 t

SJG2 t

SMF1 t

SMF2 t

SMF3 t

SMF4 t

SPF1 t

SPF2 t

SPF3 t

SPF4 t

SQF1 t

SQF2 t

....

....

....

....

....

....

....

....

....

....

....

....

....

....

SMH1 t

SMH2 t

SMH3 t

SMH4 t

SPH1 t

SPH2 t

SPH3 t

SPH4 t

SQH1 t

SQH2 t

SQH3 t

SQH4 t

SVH1 t

SVH2 t

....

....

....

....

....

....

....

....

....

....

SMW21 t

SMW22 t

SMW23 t

SMW24 t

SPW21 t

SPW22 t

SPW23 t

SPW24 t

SQW21 t

SQW22 t

....

....

....

....

....

....

....

....

....

....

....

....

....

....

SVW1 t

SVW2 t

SVW3 t

SVW4 t

SXW1 t

SXW2 t

SYW1 t

SYW2 t

SZW1 t

SZW2 t

SJW1 t

SJW2 t

SMW1 t

SMW2 t

SMW3 t

SMW4 t

SPW1 t

SPW2 t

SPW3 t

SPW4 t

SQW1 t

SQW2 t

SQW3 t

SQW4 t

SVA1 t

SVA2 t

SVA3 t

SVA4 t

SXA1 t

SXA2 t

SYA1 t

SYA2 t

SZA1 t

SZA2 t

SJA1 t

SJA2 t

SMA1 t

SMA2 t

SMA3 t

SMA4 t

SPA1 t

SPA2 t

SPA3 t

SPA4 t

SQA1 t

SQA2 t

SQA3 t

SQA4 t

30

60

100

200

300

400

600

800

2

3

4

4

5

2

3

4

5

2

3

4

5

2

3

2

3

2

3

2

3

2

3

SMG10 t

SMG11 t

SMG12 t

SMG13 t

SPG10 t

SPG11 t

SPG12 t

SPG13 t

SQG10 t

SQG11 t

SQG12 t

SQG13 t

SVG10 t

SVG11 t

SVG12 t

SXG13 t

SXG14 t

SYG16 t

SYG17 t

SZG18 t

SZG19 t

SJG10 t

SJG11 t

SMF10 t

SMF11 t

SMF12 t

SMF13 t

SPF10 t

SPF11 t

SPF12 t

SPF13 t

SQF10 t

SQF11 t

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

SMW31 t

SMW32 t

SMW33 t

SMW34 t

SPW31 t

SPW32 t

SPW33 t

SPW34 t

SQW31 t

SQW32 t

....

....

....

....

....

....

....

....

....

....

....

....

....

SMW10 t

SMW11 t

SMW12 t

SMW13 t

SPW10 t

SPW11 t

SPW12 t

SPW13 t

SQW10 t

SQW11 t

SQW12 t

SQW13 t

SVW10 t

SVW11 t

SVW12 t

SXW13 t

SXW14 t

SYW16 t

SYW17 t

SZW18 t

SZW19 t

SJW10 t

SJW11 t

SMA10 t

SMA11 t

SMA12 t

SMA13 t

SPA10 t

SPA11 t

SPA12 t

SPA13 t

SQA10 t

SQA11 t

SQA12 t

SQA13 t

SVA10 t

SVA11 t

SVA12 t

SXA13 t

SXA14 t

SYA16 t

SYA17 t

SZA18 t

SZA19 t

SJA10 t

SJA11 t u

NEMA Type 12 enclosures may be field modified for outdoor applications or NEMA Type 3R separate enclosures can be ordered. See the Class 9991 Section in Catalog 9999CT9701.

k

Separate enclosures are available for these devices. It may be possible to improve delivery by ordering an open type contactor and separate Class 9991 enclosure.

q

NEMA Type 4 & 4X enclosures are brush finished stainless steel for contactors sized 30 Amp thru 300 Amp. Sizes 400 Amp thru 800 Amp are painted sheet steel.

For electropolished finish, specify Form G16.

c

Form F4T is provided as standard; include line voltage when ordering. Control voltage is 120-60.

t

Voltage code must be specified to order this product. Refer to standard voltage codes below.

p

All lighting contactors are provided with separate control as standard.

SMO10 tk

SMO11 tk

SMO12 tk

SMO13 tk

SPO10 tk

SPO11 tk

SPO12 tk

SPO13 tk

SQO10 tk

SQO11 tk

SQO12 tk

SQO13 tk

SVO10 t

SVO11 t

SVO12 t

SXO13 t

SXO14 t

SYO16 t

SYO17 t

SZO18 t

SZO19 t

SJO10 t

SJO11 t

SVO1 t

SVO2 t

SVO3 t

SVO4 t

SXO1 t

SXO2 t

SYO1 t

SYO2 t

SZO1 t

SZO2 t

SJO1 t

SJO2 t

SMO1 tk

SMO2 tk

SMO3 tk

SMO4 tk

SPO1 tk

SPO2 tk

SPO3 tk

SPO4 tk

SQO1 tk

SQO2 tk

SQO3 tk

SQO4 tk

Coil Voltage Codes

60 Hz

24 f

120

208

240

277

480

Specify

Voltage

50 Hz

...

110

...

220

...

440

Specify

Code

V01

V02

V08

V03

V04

V06

V99 f

24 volt coils are not available for 200 Amp thru 800 Amp devices. Contact local Square D Field Sales Office for additional information.

Poles for Type S Only

A single-pole or double-pole kit can be added to any 2 or 3 pole 30 or 60 Ampere

Type S lighting contactor to make a 4 or 5 pole device. Factory assembled 4 and 5 pole contactors utilize the basic 3 pole device with a single or double-pole kit installed. Only one power pole can be added per contactor. Sufficient room is provided in all enclosure styles for the addition of a power pole kit.

Ampere

Rating

30

60

Description

One N.O.

One N.C.

One N.O. and One N.C.

Two N.O.

Two N.C.

One N.O.

One N.C.

One N.O. and One N.C.

Two N.O.

Two N.C.

Class

9999

Type

SB6

SB7

SB8

SB9

SB10

SB21

SB22

SB23

SB24

SB25 a a a a a

When power pole is added to 60 A contactor, a 4-pole coil is also required. Order from Coil Table in Catalog 9999CT9701. 60 A power poles are suitable for use with copper or aluminum wire.

3

1/98

© 1998 Square D All Rights Reserved

Lighting Control

Class 8903 – Combination Lighting Contactors, Type S

Features

The features include: disconnect switch and circuit breaker versions; rugged flange-mounted handle; easy installation; occupation of less space; increased operator protection; room to spare for modifications; Class R fuse clips standard; electrically and mechanically held; 30–600 Amperes.

It is desirable to install the branch-circuit protective device and lighting contactor, combining switching and over-current protection, in one enclosure.

Combination lighting contactors are well suited for industrial, highway and area lighting applications, or where a lighting circuit may have to be disconnected for periodic maintenance. They may also be used for resistance heating loads.

Fusible or Non-Fusible Disconnect Switch (3-Pole, 50-60 Hz)

Contactor

Ampere

Rating

Fuse

Clip

Size

(Amps)

Fuse

Clip

Spacing

(Volts)

NEMA Type 1

General

Purpose

Enclosure

Type

NEMA Type 4 & 4X q

Watertight and

Dusttight Enclosure

Stainless Steel

Type

Electrically Held

c

30

None

30

30

60

100

200

300

None

60

60

None

100

100

None

200

200

None

400

400

Mechanically Held

c

30

None

30

30

60

100

None

60

60

None

100

100

200

300

None

200

200

None

400

400

....

600

250

....

600

250

....

600

250

....

600

250

....

600

250

....

600

250

....

600

250

....

600

250

....

600

250

....

600

250

SMG70 t

SMG71 t

SMG72 t

SPG70 t

SPG71 t

SPG72 t

SQG70 t

SQG71 t

SQG72 t

SVG70 t

SVG71 t

SVG72 t

SXG70 t

SXG71 t

SXG72 t

SMG60 t

SMG61 t

SMG62 t

SPG60 t

SPG61 t

SPG62 t

SQG60 t

SQG61 t

SQG62 t

SVG60 t

SVG61 t

SVG62 t

SXG60 t

SXG61 t

SXG62 t

SMW70 t

SMW71 t

SMW72 t

SPW70 t

SPW71 t

SPW72 t

SQW70 t

SQW71 t

SQW72 t

SVW70 t

SVW71 t

SVW72 t

SXW70 t

SXW71 t

SXW72 t

SMW60 t

SMW61 t

SMW62 t

SPW60 t

SPW61 t

SPW62 t

SQW60 t

SQW61 t

SQW62 t

SVW60 t

SVW61 t

SVW62 t

SXW60 t

SXW61 t

SXW62 t

NEMA Type 12 u

Dusttight, Oiltight

Driptight, Industrial

Use Enclosure

Type

SMA60 t

SMA61 t

SMA62 t

SPA60 t

SPA61 t

SPA62 t

SQA60 t

SQA61 t

SQA62 t

SVA60 t

SVA61 t

SVA62 t

SXA60 t

SXA61 t

SXA62 t

SMA70 t

SMA71 t

SMA72 t

SPA70 t

SPA71 t

SPA72 t

SQA70 t

SQA71 t

SQA72 t

SVA70 t

SVA71 t

SVA72 t

SXA70 t

SXA71 t

SXA72 t and

File E16151

CCN NRNT

Coil Voltage Codes

Voltage

60 Hz 50 Hz

24 l

120

208

240

277

480

Specify

...

110

...

220

...

440

Specify

Code

V01

V02

V08

V03

V04

V06

V99 l

24 volt coils are not available for

200 Amp devices. Contact local

Square D Field Sales Office for additional information.

Circuit Breaker (3-Pole, 50-60 Hz)

Contactor

Ampere

Rating

Circuit Breaker

Electrically Held

c

Ampere

Rating

Maximum

Volts

30

30

30

600

240

60

100

200

300

400 f

600 f

Mechanically Held

c

30

30

30

60

60

60

100

200

300

400

600

60

60

100

600

240

600

600

600

600

600

600

240

600

240

600 100

200

300

400

600

200

300

400

600

600

600

600

600

NEMA Type 1

General

Purpose

Enclosure

Type

SMG81

SMG82

SPG81

SPG82

SQG81

SVG81 t

SXG81 t

SYG81 t

SZG81 t

SMG91

SMG92

SPG91

SPG92

SQG91 t t t t t t t t t t

SVG91 t

SXG91 t

SYG91 t

SZG91 t

NEMA Type 4 & 4X q

Watertight and

Dusttight Enclosure

Stainless Steel

(30-300 Amp)

Type

SMW81

SMW82

SPW81

SPW82

SQW81 t t t t t

SVW81 t

SXW81 t

SYW81 t

SZW81 t

SMW91

SMW92

SPW91

SPW92

SQW91 t t t t t

SVW91 t

SXW91 t

SYW91 t

SZW91 t

NEMA Type 12

SMA81

SMA82

SPA81

SPA82

SQA81

SVA81 t

SXA81 t

SYA81 t

SZA81 t

SMA91

SMA92

SPA91

SPA92

SQA91 t t t t t t t t t t

SVA91 t

SXA91 t

SYA91 t

SZA91 t u

Dusttight, Oiltight,

Driptight, Industrial

Use Enclosure

Type f

Form F4T is standard; Include line voltage when ordering. Control voltage is 120V/60 Hz.

q

For NEMA Type 4 & 4X Watertight, Dusttight and Corrosion-Resistant Glass-Polyester enclosure pricing, multiply stainless steel enclosed price by 1.25 and add Form G18 (limited to 100 Amp max.). 400 & 600 Amp enclosures are painted sheet steel (NEMA Type 4 & 4X).

u

NEMA Type 12 enclosures may be field modified for outdoor applications. See the Class 9991 section in Catalog 9999CT9701.

c

All lighting contactors are provided with separate control as standard.

t

Coil voltage codes must be specified to order this product. Refer to standard voltage codes shown to the left.

4

© 1998 Square D All Rights Reserved

1/98

C

®

Long Version

Short Version

UL Approved for

Service Entrance

and

File E16151

CCN NRNT

Lighting Control

NIGHT-MASTER

Combination Lighting Contactors – Class 8903

NIGHT-MASTER Outdoor Combination Lighting Contactors offer disconnecting means, overcurrent protection and a lighting contactor in one NEMA Type 3R Rainproof enclosure. These combination units satisfy requirements of the National

Electrical Code and UL 508 for service entrance equipment.

Features:

• Solid neutral standard

• Grounding lug standard

• Padlocking provisions

• Short and long versions available

• Electrically held Type S lighting contactor

• Eliminates the need for separate time clocks and safety switches

Disconnect Switch Type

p

(3-Pole)

Contactor

Ampere

Rating

30

60

100

200

Fuse Clip

Size

(Amperes)

100

100

200

200

30

30

60

60

Fuse Clip

Spacing

(Volts)

600

250

600

250

600

250

600

250

Short Version

Class 8903

Type

SMC61 t

SMC62 t

SPC61 t

SPC62 t

SQC61 t

SQC62 t

SVC61 t

SVC62 t

Long Version

Class 8903

Type

SMC63 t

SMC64 t

SPC63 t

SPC64 t

SQC63 t

SQC64 t

SVC63 t

SVC64 t

Circuit Breaker Type

p

(3-Pole)

Contactor

Ampere

Rating

30

60

100

200

Ampere

Rating

Circuit Breaker

30

60

100

200

Maximum

Volts

600

600

600

600

Short Version

Class 8903

Type

SMC81 t

SPC81 t

SQC81 t

SVC81 t

Long Version

Class 8903

Type

SMC83 t

SPC83 t

SQC83 t

SVC83 t p

All lighting contactors are provided with separate control as standard.

t

Coil Voltage codes must be specified to order this product. Refer to standard voltage codes listed below.

NIGHT-MASTER Combination Lighting Contactors

The Class 8903 NIGHT-MASTER Outdoor Combination Lighting Contactor is the only product on the market that is UL

Listed for Service Entrance. This allows the contactor to be pole mounted when used to control lighting in remote locations such as parks, monuments, group sports facilities, and streets and highways.

Factory modifications such as photocells, time switches, key operated selector switches, and the combination of photocells and time switches (photocell on, time switch off) allow the NIGHT-MASTER to be located in applications where manual operation of lights is not practical.

NIGHT-MASTER comes in long and short versions in sizes 30 through 200 Amperes. Most common modifications can be provided from the factory, or added in the field to pre-drilled and pre-tapped panels.

Coil Voltage Codes

60 Hz

24 q

120

208

240

277

480

Specify

Voltage

50 Hz

...

110

...

220

...

440

Specify

Code

V01

V02

V08

V03

V04

V06

V99 q

24 volt coils are not available for 200 Amp devices.

Contact local Square D Field Sales Office for additional information.

5

1/98

© 1998 Square D All Rights Reserved

Lighting Control

Class 8903 – Panelboard Lighting Contactors, Type PB

General Information

Panelboard Lighting Contactors, sometimes called remote control switches, are designed for use with lighting panelboards and motor control centers where either panel or bus mounting is desirable. Type PB lighting contactors can be used in a retrofit or new project without increasing the panelboard depth. They can be used to directly replace many inoperative existing switches.

The features include: mechanically held; compatible with Square D panelboards; short-circuit ratings to 100 KA; compact arc suppression; bus or panel mounted; fits in standard-depth lighting panelboards; easy manual operation; standard coil clearing contacts; and the ability to operate in any position.

File E78427

CCN NRNT

LR 60905

Class 3231 01

Class 8903 Type PB Lighting Contactors

Amp Size

30

60

75

100

150

200

225

Description

Poles

2

3

2

3

2

3

2

3

2

3

2

3

2

3

Bus Mount

Type

PBM 10B t

PBM 11B t

PBP 10B t

PBP 11B t

PBN 10B t

PBN 11B t

PBQ 10B t

PBQ 11B t

PBR 10B t

PBR 11B t

PBV 10B t

PBV 11B t

PBW 10B t

PBW 11B t

Panel Mount

Type

PBM 10 t

PBM 11 t

PBP 10 t

PBP 11 t

PBN 10 t

PBN 11 t

PBQ 10 t

PBQ 11 t

PBR 10 t

PBR 11 t

PBV 10 t

PBV 11 t

PBW 10

PBW 11 t t t

Voltage code must be specified to order this product. Refer to standard voltage codes listed below.

AC Coil Voltage Codes

60 Hz

120/208

240/277

480

Voltage Code

V38

V39

V28

Maximum Wire Size

Current Range

30-100 Amps

150-225 Amps

Power Wire

(CU/AL)

1/0 Max.

350 MCM Max.

Factory Modifications

Form

X11

X22

Description

(1) Auxiliary Contacts SPDT

(2) Auxiliary Contacts SPDT

Control Wire

(CU Only)

#18 - #10

#18 - #10

Short-Circuit Ratings

RMS Sym.

Current (Amp)

100,000

22,000

65,000

Max. Volts

600

600

240

Short Circuit

Protection Device Recommended

Class J Fuses

Circuit Breaker - Square D - Type LHL

Circuit Breaker - Square D - Type LHL

Wire Gauge

AWG

#14

#12

#10

120V

550

900

1425

208V

1650

2700

4275

Distance (feet)

240V

2200

3600

5700

277V

2925

4700

7550

480V

8800

14400

22800

Dimensions (Panel Mount)

Amps

30-

100

150-

225

H

11.75

(298)

14.50

(368)

W

7.50

(191)

7.50

(191)

Dimensions Inches (mm)

D A B

3.88

(98)

3.88

(98)

2.25

(57)

2.88

(73)

7.38

(187)

8.50

(216)

C

2.25

(57)

3.00

(76)

E

9.25

(234)

10.50

(266)

Dimensions (Bus Mount)

Amps

30-

100

150-

225

H

8.31

(211)

9.50

(241)

Dimensions Inches (mm)

W

7.50

(191)

7.50

(191)

D

3.38

(86)

3.38

(86)

A

2.25

(57)

2.88

(73) a

B

7.38

(187)

8.50

(216) a

Slotted mounting holes suitable for 2.88 to 3.19 in. (73 to 81 mm) mounting centers.

6

© 1998 Square D All Rights Reserved

1/98

Lighting Control

Lighting Transfer Switches, Type REQ – Class 8903

REQ 2815-G2

Open Type Only

File E78401

CCN WPWR 2

Electrically Held

f

Amperes Poles

Open Type

Catalog Number

30

60

100

150

2 pole / 2 pole

3 pole / 3 pole

4 pole / 4 pole

2 pole / 2 pole

3 pole / 3 pole

4 pole / 4 pole

2 pole / 2 pole

3 pole / 3 pole

4 pole / 4 pole

2 pole / 2 pole

3 pole / 3 pole

4 pole / 4 pole

8903REQ2814-G1

8903REQ2814-G2

8903REQ2814-G3

8903REQ2815-G1

8903REQ2815-G2

8903REQ2815-G3

8903REQ2816-G1

8903REQ2816-G2

8903REQ2816-G3

8903REQ2817-G1

8903REQ2817-G2

8903REQ2817-G3 f

UL Recognized as “Components – Automatic Transfer Switches For Use In Option Stand – By Systems” only.

j

NEMA Type 1 devices are not UL1008 Recognized.

Mechanically Held

q

Amperes Poles

Open Type

Catalog Number

30

60

100

150

2 pole / 2 pole

3 pole / 3 pole

4 pole / 4 pole

2 pole / 2 pole

3 pole / 3 pole

4 pole / 4 pole

2 pole / 2 pole

3 pole / 3 pole

4 pole / 4 pole

2 pole / 2 pole

3 pole / 3 pole

4 pole / 4 pole

8903REQ2814-G4

8903REQ2814-G5

8903REQ2814-G6

8903REQ2815-G4

8903REQ2815-G5

8903REQ2815-G6

8903REQ2816-G4

8903REQ2816-G5

8903REQ2816-G6

8903REQ2817-G4

8903REQ2817-G5

8903REQ2817-G6

225

260

400

600

2 pole / 2 pole

3 pole / 3 pole

2 pole / 2 pole

3 pole / 3 pole

2 pole / 2 pole

3 pole / 3 pole

2 pole / 2 pole

3 pole / 3 pole

8903REQ2818-G1

8903REQ2818-G2

8903REQ2819-G1

8903REQ2819-G2

8903REQ2820-G1

8903REQ2820-G2

8903REQ2821-G1

8903REQ2821-G2

800

2 pole / 2 pole

3 pole / 3 pole

8903REQ2822-G1

8903REQ2822-G2 q

UL Recognized as “Components – Automatic Transfer Switches For Use In Option Stand – By Systems”.

j

NEMA Type 1 devices are not UL1008 Recognized.

NEMA Type 1

j

Enclosed Catalog

Number

8903REQ2814-G7

8903REQ2814-G8

8903REQ2814-G9

8903REQ2815-G7

8903REQ2815-G8

8903REQ2815-G9

8903REQ2816-G7

8903REQ2816-G8

8903REQ2816-G9

8903REQ2817-G7

8903REQ2817-G8

8903REQ2817-G9

NEMA Type 1

j

Enclosed Catalog

Number

8903REQ2814-G10

8903REQ2814-G11

8903REQ2814-G12

8903REQ2815-G10

8903REQ2815-G11

8903REQ2815-G12

8903REQ2816-G10

8903REQ2816-G11

8903REQ2816-G12

8903REQ2817-G10

8903REQ2817-G11

8903REQ2817-G12

8903REQ2818-G3

8903REQ2818-G4

8903REQ2819-G3

8903REQ2819-G4

8903REQ2820-G3

8903REQ2820-G4

8903REQ2821-G3

8903REQ2821-G4

8903REQ2822-G3

8903REQ2822-G4

7

1/98

© 1998 Square D All Rights Reserved

Lighting Control

Class 8903 – Modifications (Forms)

Description

Form

Letter

“On-off” (momentary contact) push button

“On-off” push button (with holding circuit interlock)

“HAND-OFF-AUTO” selector switch. For key operator, add

Form C33, i.e. CC33

“On-off” selector switch. For key operator, add Form C33, i.e.

C6C33

Control circuit fuse (1 fuse)

Control circuit fuses (2 fuses)

Control circuit transformer standard capacity 50/60 Hz

Primary (Fuses) Secondary

2 100 VA Add.

Cap. 0

,

➃ for 300 A

2 100 VA Add.

Cap. 1 ➂ , ➃ for 300 A

2 100 VA Add. Cap. 1

➃ for 200 and 300 A

2 200 VA Add. Cap. 1

➃ for 100, 200 and 300 A

2 300 VA Add. Cap. 1

➃ for 30 to 300 A

Noise reduced enclosure and shock mounted panel

Addition of photoelectric receptacle

Addition of photoelectric receptacle with photo-cell

Addition of photoelectric receptacle and relay (R6)

With photo-cell installed

Addition of terminal blocks (other than standard).

“xx” Represents the number of terminals needed.

(PER TERMINAL PRICE)

(PER TERMINAL PRICE)

WIRED

UNWIRED

Bracketing for internally mounted pilot device

Addition of 24 hour time clock (120-277v only)

Addition of 24 hour time clock w/day omission (120-277v)

Addition of 7 day time clock (120-277v)

Addition of 8865 TC12 lighting controller to lighting contactors of any size. REQUIRES A 24V 60 Hz CONTROL CIRCUIT.

Addition of 24 hour time clock (120-277v only)

Addition of 24 hr time clock w/skip day (120-277v)

Addition of 7 day time clock (120-277v)

Addition of solid neutral terminal block

Red Pilot Light

Two or more lights

(each)

Red Push To Test Pilot Light

Interlock necessary for pilot light one needed for each additional pilot light

Two Wire Interface for Mechanically held

Three wire control for long distance applications.

Auxiliary contacts (specify number of N.O. + N.C.)

Addition of DC coil to Type L (7 poles max)

Auxiliary electrical interlock installed on disconnect switch or circuit breaker operating mechanism

Coil Transient suppressor (120Vac Only)

Coil Transient suppressor (120Vac Only)

Addition of lightning arrestor

Substitute copper only lugs for standard

Substitute Anderson VC crimp style lugs for standard – per lug adder – specify lug

Addition of under and overvoltage relay

Multiple contactors in common enclosure “xx” = number of contactors needed

➄ t

Available.

NIGHT-MASTER maximum 200 Amps, minimum 30 Amps.

DO NOT use Form X for any interlock which is wired in series with pilot light, but DO specify how pilot light and interlock are to be wired into the circuit.

Not required on 400 A through 800 A electrically held versions only, which have a control circuit requiring a 120V secondary; therefore, a transformer is supplied. The transformer comes wired to L1 and L2 unless Form “S” is called for. It is supplied with two primary and one secondary fuse.

Single primary voltage must be specified using the codes shown below:

Voltage 60 Hz Code

120-24

208-120

240-24

240-120

277-120

480-24

480-120

480-240

600-120

V89

V84

V82

V80

V85

V83

V81

V87

V86

Limited to 16 contactors thru 60 Amps, 4 contactors thru 200 Amps.

R6

R62

X ➆

Y48

Y74

Y145

Y145

Y1532

Y157

Y1574

Y449

G53

K14

K141

K142

K143

K14

K141

K142

N

P1

P

P21

,

Y10XX

F4T

FF4T

FF4T11

FF4T12

FF4T13

G4

G10

G101

G10R6

G101R6

G50xx

A3

A3

A12

C

C

C6

C6

F

F4

Any

Any

Any

Any

Any

Any

Any

Any

3R, 4, 12

Any

Any

Any

Any

1, 4, 12

1, 4, 12

1, 4, 12

1, 4, 12

3R

3R

3R

1, 4, 12

Any

Any

Any

1, 4, 12

Any

Any

Any

Any

Any

Any

1, 3R, 12

1, 3R, 12

1, 12

1, 12

Any

NEMA

Enclosure

Type

1

3R, 4, 12

Any

1

3R, 4, 12

1

3R, 4, 12

Any

Any t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t

Elec.

Held

Std.

Mech.

Held t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t

Used On

Combo

Elec.

Held

Mech.

Held t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t t

NIGHT-

MASTER

®

➀ t t t t t t t t t

Std.

t t t t t t t t t t t t t t t t t t t t

For electrically-held enclosed devices, the first pilot is wired in parallel with the coil. Operating interlocks are required for all additional pilot lights.

Mechanically held devices require operating interlocks for all pilot lights.

Electrically held 20 Amp multipole contactors cannot add interlocks. Additional poles can be used for the same function, however. Mechanically held

(Type LX) provide one double throw auxiliary (or status) contact as standard.

Order Example

You have previously selected a Class 8903SMG2V02. V02 means that you need a coil voltage of 120-60/110-50 wired for separate control. You would like to add form FF4T with the transformer voltages being 480 volt primary, 120 volt secondary.

The new and complete Class, Type, Voltage Code and

Form number:

Class Type

8903 SMG2

VoltageCode

V81

Form f

FF4T f

Form numbers should always be shown in alphabetical order.

8

© 1998 Square D All Rights Reserved

1/98

1/98

Lighting Control

Field Modifications – Class 8903

Description

Types L & LX

30 Amp

Kit

30 Amp

Kit

60 Amp

Kit

100 Amp

Kit

Type S

200 Amp

Kit

300 Amp

Kit

400, 600,

800 Amp

Kit

AUXILIARY CONTACTS

1 N.O. LH or RH Mounting

1 N.C. LH or RH Mounting

1 N.C. & 1 N.O. Isolated LH or RH

1 N.O. Overlapping LH or RH

1 N.C. Overlapping LH or RH

CONTROL CIRCUIT

FUSE HOLDER

Single Fuse Unit

Two Fuse Unit

.......

.......

.......

.......

.......

9999 LLX and

9999 SFR3

9999 SX6

9999 SX7

9999 SX8

9999 SX9

9999 SX10

9999 SFR3

9999 SX6

9999 SX7

9999 SX8

9999 SX9

9999 SX10

9999 SFR3

9999 SX6

9999 SX7

9999 SX8

9999 SX9

9999 SX10

9999 SFR3

9999 SX6

9999 SX7

9999 SX8

9999 SX9

9999 SX10

9999 SFR3

9999 SFR4

9999 SX6

9999 SX7

9999 SX8

9999 SX9

9999 SX10

9999 SFR3

9999 SX6

9999 SX7

9999 SX8

9999 SX9

9999 SX10

9999 SFR3

9999 LLX and

9999 SFR4 9999 SFR4 9999 SFR4 9999 SFR4 9999 SFR4 9999 SFR4

TRANSFORMERS (For Prices

See Class 9070 Section)

OVERSIZED ENCLOSURES

(Non-Combo)

NEMA 1

NEMA 4

NEMA 12

STANDARD ENCLOSURES

NEMA 1 – Surface Mount

NEMA 3R

NEMA 4 – Standard

NEMA 4 – With 2 Cover

Mtd. Closing Plates

NEMA 4X – Glass Polyester

NEMA 12

NEMA 1 – Flushmount – Complete

NEMA 1 – Flush Mount Parts

FLUSH PARTS

Standard – Elec. held

Standard – Mech. held

Mounting Strap

Pull Box

Internal Operator

Mounting Bracket

Solid Neutral

(Combination Lighting Contactor

Disconnect Interlock Kit)

Breaker Type

1 Pole

2 Pole

Disconnect Type

1 Pole

2 Pole

Lightning Arrestor 175Vac to Ground Max 2 or

3 wire Grounded

650Vac to Ground Max

3 or 4 wire

Grounded

Hardware 2 Pole

Hardware 3 Pole

Hardware 4 Pole

Versa Crimp Lugs

Range #8-1/0 AL/CU

Range #1-2/0 AL/CU

Range 2/0-4/0 AL/CU

Range 4-300 MCM AL/CU

Range 2/0-500 MCM AL/CU

Range 400-600 MCM AL

Range 400-500 MCM CU

Range 500-750 MCM AL

Range

Range

Range

Range

Range

500 MCM CU

400-600 MCM AL

400-500 MCM CU

500-750 MCM AL

500 MCM CU

Relay Under and Over Voltage

9070 T50

9991 SDG3

9991 SDW3

9991 SDA3

9991 LXG1

9991 SDH1

9991 SDW1

9991 SDW11

9991 SDW20

9991 SDA11

.......

.......

.......

9991 SDF13

9991 SDF13

9991 SDF2

9991 SDF1

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

8430 DWU

9070 T100

9991 SCW20

9991 SCA11

.......

.......

.......

9991 SCF11

9991 SCF13

9991 SCF2

9991 SCF1

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

8430 DWU

9070 T100

9991 SDG7

9991 SDH1

9991 SDW1

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

9991 SDW11

8430 DWU

9070 T300

9991 SFG8

9991 SEH1

......

9991 SEW11

9070 T300 9070 T500 9070 T750

30102-159-01 30102-159-01 30102-159-01 30102-159-01 30102-159-01 30102-159-01 30102-159-01

9999 SN1

.......

.......

.......

.......

J9200-10

J9200-9A

.......

.......

.......

.......

9991 SDG3

9991 SDW3

9991 SDA3

9991 SCG7

9991 SCH2

9991 SCW1

9999 SN1

9999 R26

9999 R27

9999 R45

9999 R46

J9200-10

J9200-9A

.......

.......

.......

.......

9991 SCW11

9991 SDG3

9991 SDW3

9991 SDA3

9991 SDW20

9991 SDA11

.......

.......

.......

9991 SDF11

9991 SDF13

9991 SDF2

9991 SDF1

9999 SN1

9999 R26

9999 R27

9999 R43

9999 R44

J9200-10

J9200-9A

.......

.......

.......

.......

.......

.......

.......

.......

9991 SEA11

9991 SEF11

.......

.......

.......

.......

.......

.......

9999 SN1

9999 R26

9999 R27

9999 R41

9999 R42

J9200-10

J9200-9A

.......

.......

.......

.......

9991 SFH1

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

9999 SN2

9999 R26

9999 R27

9999 R8

9999 R9

J9200-10

J9200-9A

.......

.......

.......

9991 SGG8

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

9999 SN2

9999 R26

9999 R27

9999 R35

9999 R36

J9200-10

J9200-9A

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

9999 SN3

9999 R26

9999 R27

9999 R26

9999 R27

J9200-10

J9200-9A

Not Needed

.......

9999 AL 13

9999 AL 14

9999 AL 15

.......

9999 AL 11

9999 AL 11

.......

VCEL02114S1

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

VCEL022516H1

VCEL024516H1

VCEL030516H1

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

VCEL05012H1

VCEL06012H1

VCEL06012H1

VCEL07512H1

VCEL07512H1

.......

.......

.......

.......

8430 DWU 8430 DWU 8430 DWU

9999 AL 12

9999 AL 12

.......

.......

.......

.......

.......

.......

.......

.......

.......

.......

VCEL06012H2

VCEL06012H2

VCEL07512H2

VCEL07512H2

8430 DWU

For electrically held only.

One or two lugs may be mounted on each terminal. Limited to 400 and 600 Amp versions. 800 Amp is factory modification only.

Limited to 400 and 600 Amp versions. 800 Amp is a factory modification only.

Form

No.

X

F

F4

T

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

....

G53

N

Y74

Y1532

Y449

9

© 1998 Square D All Rights Reserved

Lighting Control

Class 8903 – Field Modifications

TYPE L & LX TYPE S

Description 30 Amp 30 Amp 60 Amp

Kit

9001KA2 &

9999SA3 q

9001KA2

9999SA3 q

100 Amp

Kit

9001KA2 &

9999SA3 q

9001KA2

9999SA3 q

200 Amp

Kit

9001KA2 &

9999SA3 q

9001KA2

9999SA3 q

300 Amp

Kit

9001KA2 &

9999SA3 q

9001KA2

9999SA3 q

400, 600,

800 Amp

Kit

9001KA2 &

9999SA3 q

9001KA2

9999SA3 q

Form

No.

PUSH BUTTON (ON-OFF)

NEMA Type 1 Enclosure

NEMA Type 3R, 4 or 12

Enclosure

SELECTOR SWITCH

(2 POSITION)

NEMA Type 1 Enclosure

NEMA Type 3R, 4 or 12

Enclosure

SELECTOR SWITCH

(3 POSITION)

NEMA 1 Enclosure

(MUST INCLUDE TWO WIRE

CONTROL RELAY (Form R6)

NEMA Type 3R, 4 or 12

Enclosure

TWO WIRE CONTROL

RELAY (Form R6)

PILOT LIGHTS (RED)

NEMA Type 1 Enclosure

NEMA Type 3R, 4 or 12

Enclosure

PUSH BUTTONS

k

NEMA Type 1 Enclosure

NEMA Type 3R, 4 or 12

Enclosure

SELECTOR SWITCH

(2 POSITION)

NEMA Type 1 Enclosure

NEMA Type 3R, 4 or 12

Enclosure

SELECTOR SWITCH

(3 POSITION)

NEMA Type 1 Enclosure

NEMA Type 3R, 4 or 12

Enclosure

Kit

9999BLX &

9999LXPB

9001KA2

9999SA3 q

9999BLX &

9999LXS

9001KN244

9001KS11BH1

9999BLX &

9999SC2

9001KN260 &

9001KS46BH2

9999RLX

CA2SK11_

9999SP28R

9999BLX &

9999SA10

9999SA3

9999BLX &

9999SC22

9001KN244 &

9001KS11BH1

9999BLX &

9999SC2

9999SC8

Kit t

9001KA2

9999SA3 q

9001KN244 &

9001KS11BH1

9001KN244

9001KS11BH1

9001KN260 &

9001KS46BH2

8501X011

9999SP2R

9999SP28R

9999SA10

9999SA3

9999SC22

9001KN244 &

9001KS11BH1

9999SC2

9999SC8

9001KN244 &

9001KS11BH1

9001KN244

9001KS11BH1

9001KN260 &

9001KS46BH2

8501X011

9999SP3R

9999SP28R

9999SA10

9999SA3

9999SC22

9001KN244 &

9001KS11BM1

9999SC2

9999SC8

9001KN244 &

9001KS11BH1

9001KN244

9001KS11BH1

9001KN260 &

9001KS46BH2

8501X011 f

9999SP14R

9999SP28R

9999SA3

9999SA3

9999SC22

9001KN244 &

9001KS11BH1

9999SC2

9999SC8

9001KN244 &

9001KS11BH1

9001KN244

9001KS11BH1

9001KN260 &

9001KS46BH2

8501X011 a

9999SP28R

9999SP28R

9999SA3

9999SA3

9001KN244 &

9001KS11BH1

9001KN244 &

9001KS11BH1

9999SC8

9999SC8

9001KN244 &

9001KS11BH1

9001KN244

9001KS11BH1

9001KN260 &

9001KS46BH2

8501X011 a

9999SP28R

9999SP28R

9999SA3

9999SA3

9001KN244 &

9001KS11BH1

9001KN244 &

9001KS11BH1

9999SC8

9999SC8

9001KN244 &

9001KS11BH1

9001KN244

9001KS11BH1

9001KN260 &

9001KS46BH2

8501X011

9999SP28R

9999SP28R

9999SA3

9999SA3

9001KN244 &

9001KS11BH1

9001KN244 &

9001KS11BH1

9999SC8

9999SC8

A3

C6

C

R6

P1

A12

C6

C t

No field installed kit available.

q

Mechanically-held contactors need two distinct signals to operate. If is necessary to add a N.O. contact block to the Class 9999 Type SA3 push button kit.

f

Selection for 2 or 3 pole only; for 4 or 5 pole use Class 9999 SP15R. a

The coil voltage must be the same as the pilot light rating. Kit contains one (1) Class 9001, Type KP1R6 120V/60Hz red pilot light control unit. For other voltages, refer to the Class 9001, Type KP Control Section.

k

Requires holding circuit interlock or additional power pole on 20 Amp size.

10

© 1998 Square D All Rights Reserved

1/98

1/98

Application of Lighting Contactors

Lighting contactors have evolved from the need for more than just simple on-off manual control of lights.

Today’s requirements call for the development of new and varied types of control. Often the application will call for remote control of lighting from some distant location. This control may or may not be in addition to a master control station at a central location. Certain applications include the use of automatic control by time clocks or photelectric cells. Whatever the need may be, applications are increasing, and lighting contactors are designed to meet the ever-changing requirements.

Square D lighting contactors offer a time-proven design for better electrical and mechanical performance. They are used wherever reliable, convenient and economical control of indoor and outdoor lighting is required. Typical installations include:

• parking lots

• industrial plants

• office buldings

• theaters and auditoriums

• hospitals and institutions

• shopping centers

• stadiums

• airports

Tungsten Lamp Loads

Tungsten lamps have a positive resistance characteristic (resistance to the flow of electric current increases as its operating temperature increases), thus exhibiting an increase in resistance when the lamp is energized. Therefore, these lamps have a high inrush current of up to 18 times normal current resulting from the low cold resistance of the tungsten. Examples of tungsten lamps include incandescent lamps, iodine lamps, quartz-iodine lamps and infrared lamps.

Ballast Lighting Loads

A ballast lighting load consists of electric discharge

(vapor) lamps. All types of vapor lamps possess a negative resistance characteristic. The resistance within the lamp decreases with an increase in current and vice-versa. Without some form of current limiting device in the electric circuit, the current would rise quickly until lamp failure occured. This current limiting element is known as the ballast. A ballast is an impedance used to stabilize the current in a vapor lamp.

It has the property of increasing in resistance as current through it increases and decreasing in resistance as current decreases. Thus it tends to maintain a constant current through it. Types of ballast lighting include high intensisty discharge (HID) lamps – mercury vapor, metal halide and high pressure sodium – and flourescent lamps.

Resistance Loads

Square D lighting contactors are fully rated for resistance loads up to 600 volts. They can be used on resistance-type boilers, electric furnaces, electric water heaters and snow melting cables and panels.

Lighting Control

Application Data – Class 8903

Motor Loads

These loads consist of motors having an inrush current, or locked-rotor current, of approximately six times the full-load current. Square D Type S lighting contactors are fully rated for motor loads and have a horsepower rating equal to the equivalent NEMA-Size motor contactor.

Lighting Contactors for Energy Management

Lighting contactors should be an integral part of any

Energy Management System. They help conserve energy consumption and reduce utility bills by providing three types of control.

Lighting contactors offer both centralized and remote control of lighting. Cirucits can be turned on and off from a number of remote locations in addition to a master control station.

They also offer selective switching of lights.

Selective switching is the control of one or more individual lighting circuits, independent of the other circuits. This design allows the potential for turning on only the amount of lighting that is actually needed.

Lighting contactors can provide automatic control to insure that lights will be turned off when not needed.

There are a number of devices that, when used with lighting contactors, offer a convenient and reliable method of automatically controlling lighting loads: program time clock, photoelectric cell, programmable controller and demand controller.

Installation of Lighting Contactors

For new installations, lighting contactors can either be installed right in the lighting panelboard, or in their own enclosure next to or remote from the panelboard.

In existing applications where the lighting control system is being updated, lighting contactors can be installed in their own enclosure next to a lighting panelboard.

Compression Lugs

Square D Versa-Crimp

compression lugs for Type S lighting contactors,

100–800 ampers, are available factory installed (Form Y157-4) or as a field modification kit (see table on page 9).

They are suitable for both copper and aluminum wire.

One VCEL lug (one or two on the

400 and 600 amperes devices) is required for each line or load terminal.

Each Class 9999 Type AL hardware kit includes mounting hardware for 3 terminals, line or load side.

EXAMPLE: To install compression lugs on a 300 ampere 3 pole device, line and load sides, order six (6)

VCEL-060-12H1 lugs and two (2)

Class 9999 Type AL11 hardware kits.

11

© 1998 Square D All Rights Reserved

Lighting Control

Class 8903 – Application Data

Maximum Voltage Rating

When selecting lighting contactors, the maximum voltage rating of the device must be considered in addition to its current rating. The table below lists the maximum ac voltage ratings of the Types L and S lighting contactors for ballast, tungsten and resistance loads. Lighting contactors also have dc ratings which are shown below.

Current Ratings

All Class 8903 lighting contactors are fully rated for tungsten, ballast and resistance loads. This means that a contactor can be used to control a load up to its full nameplate rating. Derating of the contactor is not necessary, as is the standard practice with circuit breakers and fuses.

AC Voltage Ratings

Tungsten

Ballast

Resistance

Type of Load

Control Circuit (Coil)

Voltage

When

Types L & LX

30 Amperes

Connected

1 Pole to Load

When Connected

2 Poles to Load on 1PH and 3 Poles to Load on 3PH

20 Amp 277 Vac

277 Vac q

480 Vac

480 Vac q

600 Vac 600 Vac

Type L 12-600 Vac; 24, 32, 48,

115/125, 230/250 Vdc

Type LX 24-600 Vac

When

Connected

Type SM

30 Amperes

1 Pole to Load

When Connected

2 Poles to Load on 1PH and 3 Poles to Load on 3PH

277 Vac

347 Vac

600 Vac

480 Vac

600 Vac

600 Vac

6-600 Vac

Types SP, SQ, SV & SX

60-300 Amperes

When

Connected

1 Pole to Load

When Connected

2 Poles to Load on 1PH and 3 Poles to Load on 3PH

277 Vac

347 Vac

480 Vac

600 Vac

600 Vac 600 Vac

6-600 VacType SP

24-600 VacTypes SQ & SV

120-600 VacType SX

Types SY, SZ & SJ

400-800 Amperes

When

Connected

1 Pole to Load

When Connected

2 Poles to Load on 1PH and 3 Poles to Load on 3PH

. . . .

347 Vac

600 Vac

. . . .

600 Vac

600 Vac

120-600 Vac q

Types L and LX contactors also have a ballast lamp rating of 15 Amperes 347 Vac when connected 1 Pole to Load and 600Vac when connected 2 Poles to Load on 1PH and 3 Poles to Load on 3PH.

NOTE: 600 Ampere devices are derated to 540 Amperes for resistance heating loads when aluminum wire is used.

DC Voltage Ratings for Tungsten Lamp or Resistance Loads Only

Table 2 — Motor Load Ratings

Type of

Load

Types

L &LX

20 Amperes

Type SM

30 Amperes

Types

SP, SQ, SV

& SX

60-300

Amperes

Types

SY, SZ,

& SJ

400-800

Amperes

Lighting Contactor

Size

DC with 2 Poles in Series

DC with 3 Poles in Series

125 Vdc

250 Vdc

125 Vdc

250 Vdc

250 Vdc

250 Vdc

UL Listed Short-Circuit Rating

Contactors Protected by Fusible Disconnect Switches

. . . .

. . . .

30 Amperes

60 Amperes

100 Amperes

200 Amperes

300 Amperes

400 Amperes

600 Amperes

800 Amperes

Table 3 — Mixed Load Ratings

Has Same HP Ratings

As Equivalent

NEMA Size Contactor

NEMA Size 1

NEMA Size 2

NEMA Size 3

NEMA Size 4

NEMA Size 5

NEMA Size 6

NEMA Size 7

Contactors Protected by Circuit Breakers

Contactor

Continuous

Rating

Amps

20

20

30

30

60

60

100

100

200

200

300

400

600

Contactor

Continuous

Rating

Amps

20, 30

60

100

200

300

400

Table 1 — Kilowatt Ratings

t

Voltage

200 Vac

230 Vac

380 Vac

460 Vac

575 Vac

30 Amp 60 Amp

10.3

11.9

19.7

23.9

30.0

Maximum

Class RK5

Fuse Rating

Maximum

Circuit Breaker

Rating Amps

25

25

40

40

80

90

125

125

250

225

400

800

800

20.7

23.9

39.4

47.8

60.0

30

60

100

200

400

400

Maximum

Voltage

Recommended

Square D

Circuit Breaker

Types

EH-EHB, FH-FHL

EH-EHB, FA-FAL,

FH-FHL

FA-FAL, FH-FHL

IF-IFL

FH-FHL

IF-IFL

KA-KAL, KH-KHL

IK-IKL

LA-LAL, LH-LHL

IK-IKL

LA-LAL, LH-LHL

MA-MAL, MH-MHL

MA-MAL, MH-MHL

100

Amp

Lighting Contactor Size

200

Amp

300

Amp

400

Amp

34.6

39.8

65.8

79.6

99.0

69.2

79.6

131.6

159.3

199.0

103.9

119.5

197.4

239.0

299.0

138.5

159.3

263.2

318.6

398.4

t

Resistance heating only (three phase system).

600

600

600

480

600

600

Available Amperes

(RMS Sym.)

100,000

100,000

100,000

100,000

100,000

100,000

Maximum

Voltage

240

480

600

480

600

480

600

480

600

480

600

600

600

600

Amp

207.8

239.0

394.9

478.0

597.6

Available

Amperes

(RMS Sym.)

22,000

14,000

10,000

100,000

18,000

100,000

10,000

100,000

14,000

100,000

22,000

22,000

22,000

800

Amp

277.1

318.7

526.5

637.4

796.7

Motor

Voltage and

PH p

200 V

3PH

230 V

3PH

380 V

3PH

460-

575 V

3PH

115 V

Single

PH

230 V

Single

PH

Contactor

Ampere

Rating

30

60

100

200

300

400

600

800

30

60

100

200

300

400

600

800

30

60

100

30

60

100

30

60

100

200

300

400

600

800

30

60

100

200

300

400

600

800

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Max.

Non-

Motor

Amp

0%

Max.

Motor

HP

Percent Lighting (and/or Resistive) Load

25% 50%

Max.

Non-

Motor

Amp

Max.

Motor

HP

Max.

Non-

Motor

Amp

Max.

Motor

HP

Max.

Non-

Motor

Amp

75%

Max.

Motor

HP

0

0

0

0

0

0

7

1

/

2

10

25

40

75

125

150

250

7

1

/

2

15

30

50

100

150

200

300

10

25

50

75

150

250

300

400

10

25

50

100

200

300

400

600

2

7

3

1

/

2

7

3

1

15

/

2

7.5

15

25

50

75

100

150

200

7.5

15

25

50

75

100

150

200

7.5

15

25

50

75

100

150

200

7.5

15

25

50

75

100

150

200

7.5

15

25

7

20

1

/

2

40

75

150

200

250

350

7

1

/

2

20

40

100

150

200

350

500

1

3

1

/

2

5

7.5

15

25

5

10

20

40

75

100

150

200

7

1

/

2

10

25

50

75

100

150

200

2

5

15

15

30

50

100

150

200

300

400

15

30

50

100

150

200

300

400

15

30

50

100

150

200

300

400

15

30

50

100

150

200

300

400

15

30

50

15

30

50

3

7

1

100

125

3

15

30

50

60

3

10

15

30

50

75

100

150

7

1

15

/

2

30

60

100

125

150

250

7

1

20

30

75

100

150

200

300

/

2

3

4

2

5

10

/

2

/

2

22.5

45

75

150

226

300

450

600

22.5

45

75

150

226

300

450

600

22.5

45

75

150

226

300

450

600

22.5

45

75

150

226

300

450

600

22.5

45

75

22.5

45

75

1

3

/

/

2

4

2

3

/

2

4

3

3

10

15

30

50

75

100

150

1

3

1

/

2

5

15

20

30

50

60

2

3

7

1

/

2

15

25

30

50

75

3

7

1

10

30

40

60

75

125

/

2 p

Select lighting contactor on basis of rated motor voltage, whether non-motor load is connected line-to-line or line-to-neutral.

12

© 1998 Square D All Rights Reserved

1/98

5/04

Lighting Control

Lighting Transfer Switch Specifications – Class 8903

Coil Information (120 Volts, 60 Hertz)

Amperes Poles Ohms

30 to 60

100

200

300

3

3

3

3

17.80

8.48

3.57

0.95

p

Worst case; all others are mean values.

Maximum Voltage Ratings

30 - 300 Amperes

Henries

0.110

0.048

0.032

0.013

Type of Load

When connected

1

φ

pole to load

Tungsten

Ballast

277 Vac

277 Vac

When connected

2

φ

poles to load on

1

φ

and 3

φ

poles to load on 3

φ

480 Vac

480 Vac

Inrush

VA

311

700

1185

2970

Power Factor

0.46 p

Henries

1.000

0.46

p

0.764

0.37

0.490

0.23

0.187

Normal

Source

Sealed

VA

37

46

85

212

Power Factor

0.28 p

0.23

0.13

Alternate

Source

400 - 800 Amperes

Type of Load

When connected

1

φ

pole to load

Tungsten

Ballast

277 Vac

277 Vac

2

When connected

φ

poles to load on

1

φ

and 3

φ

poles to load on 3

φ

480 Vac

480 Vac

Transfer

Switch

Lighting

The automatic transfer switch, as part of the emergency lighting system, provides the important function of switching an essential electrical load from the normal source of lighting supply to an alternate source of supply.

Wiring Terminals

Ampere

Rating

30

Power Terminals On Contactor

Type of

Lug

Wire Size

Min. - Max.

#14 - # 8 copper o r aluminum

Control Terminals On All Contactors

Type of

Lug

Wire Size

Min. - Max.

#16 - #12 copper

60 #14 - #2 copper o r aluminum #16 - #12 copper

100 #14 - # 2/ 0 copper o r aluminum #16 - #12 copper

200 #6 350 KCMIL copper or aluminum #16 - #12 copper

300

Screw Lug one #4 - 600 KCMIL or

Two #0 - 250 KCMIL or aluminum

Clamp

#16 - #12 copper

400

600

800

One or two

#6 - 250 KCMIL copper or aluminum

One or two

#6 - 600 KCMIL copper or aluminum

One, two or three

#3/0 - 750 KCMIL copper or aluminum

Elec. Held: #16 - #14 copper

Mech. held: #16 - #12 copper

Elec. Held: #16 - #14 copper

Mech. held: #16 - #12 copper

Elec. Held: #16 - #14 copper

Mech. held: #16 - #12 copper

13

© 1998 Square D All Rights Reserved

Lighting Control

Class 8903 – Approximate Dimensions

B

C

MTG.

D F

MTG.

D

A

Mtg.

2.25

57

Open Type L & LX

A

E

E

Open Type

Ampere

Rating

30

30

60

100

200

300

400

600

800

Type

LO

SMO

SPO

SQO

SVO

SXO

SYO

SZO

SJO

2-4

Electrically Held

Number of Poles

A

2.88

(73)

B

5

(127)

Dimensions p

C D

4.62

(117)

....

6

8-12

4.25

(108)

5.63

(143)

5

(127)

5

(127)

4.62

(117)

4.62

(117)

....

....

2-3

4-5

2-3

4-5

4.34

(110)

4.34

(110)

5.33

(135)

6.22

(158)

3.22

(82)

4.25

(108)

4.31

(110)

5.61

(143)

4.22

(107)

4.22

(107)

4.94

(125)

4.94

(125)

....

....

2-3

4-5

2-3

4 & 5

2-3 c

7.09

(180)

7.82

(199)

9.14

(232)

9.14

(232)

12.31

(313)

5.45

(139)

9.75

(248)

6.00

(152)

9.75

(248)

8.66

(220)

6.50

(165)

6.50

(165)

6.50

(165)

6.50

(165)

8.74

(222)

....

....

....

2-3

2-3

....

....

12.33

(313)

12.33

(313)

9.00

(229)

11.94

(303)

....

....

c

5 pole, electrically-held only.

p

Dimensions are in inches (millimeters).

C

B

Open Type S

NEMA Type 1 Flush Mounted

Ampere

Rating

30

30

60

Type Form(s)

Standard, F, Y48, R6

LF

LXF

SMF

SPF

A3, A12, C, C6,

T, P

Electrically

Held

Std., A12,

C, C6, P, X

Mechanically

Held

Electrically

Held

Std., X

T, N

Mechanically

Held

Electrically

Held

Mechanically

Held

Electrically

Held

Mechanically

Held

A3, C, C6,

T, N, P, R6

Std., A12,

C, C6, P, X

Std., X

T, N

A3, C, C6,

T, N, P, R6

A

15.19

(386)

Dimensions in inches (millimeters)

B C D E F

8.94

(227)

7.63

(194)

12.88

(327)

5.44

(138)

10.94

(278)

G

5.13

(130)

24.00

(610)

13.44

(341)

24.00

(610)

15.19

(386)

24.00

(610)

17.50

(445)

7.19

(183)

17.50

(445)

8.94

(227)

17.50

(445)

15.00

(381)

5.88

(149)

15.00

(381)

7.63

(194)

15.00

(381)

19.25

(489)

11.13

(283)

19.25

(489)

12.88

(327)

19.25

(489)

7.12

(181)

4.75

(121)

5.75

(146)

5.44

(138)

5.75

(146)

100 SQF With or without any forms

31.00

(787)

16.75

(425)

14.25

(362)

26.25

(667)

8.00

(203)

...

9.19

(233)

...

4.50

(114)

10.94

(278)

5.13

(130)

...

...

...

...

...

...

A

B

H

C30054-333-A

E

Enclosure

D

H

G

Saddle

F

C

E

3.12

(79)

3.12

(79)

3.12

(79)

....

....

....

....

Type

LXO

....

....

....

SVO

....

27.78

(706)

42.70

(1085)

SXO

SYO

SZO

SJO

7.15

(182)

7.15

(182)

8.25

(210)

8.70

(221)

A

2.88

(73)

4.25

(108)

5.63

(143)

10.13

(257)

10.56

(268)

11.35

(293)

11.55

(293)

12.31

(313)

....

....

5.94

(151)

9.75

(248)

6.00

(152)

9.75

(248)

8.66

(220)

3.79

(96)

4.54

(116)

4.61

(117)

5.90

(150)

Mechanically Held

Dimensions p

B C

....

....

D

8.81

(224)

....

....

....

....

8.81

(224)

8.81

(224)

4.68

(119)

4.68

(119)

5.23

(133)

5.23

(133)

....

....

6.72

(171)

6.72

(171)

6.72

(171)

6.72

(171)

10.50

(267)

....

....

....

8.66

(220)

8.66

(220)

10.50

(267)

11.94

(303)

....

....

....

....

....

....

....

21.00

(533)

35.35

(898)

E

3.25

(83)

3.25

(83)

3.25

(83)

F

7.70

(196)

7.70

(196)

7.70

(196)

....

....

....

....

....

....

....

NEMA Type 1 Enclosure (Non-Combination)

Electrically and Mechanically Held

Ampere

Rating

30

30

30

60

100

200

300

Type

LG,

LXG

SMG

SPG

SQG

SVG

SXG

Number of Poles

Any

2-5

2-5

2-5

2-5

2 & 3

4 & 5

All

All

Form(s)

Standard, A3, A12, C, C6,

F, R6, Y48

P, T

K14, K141, K142

16.00

(406)

Electrically Held Std., A12, C, C6, P, X

6.00

Mechanically Held Std., X

(152)

Electrically Held

T

6.34

(161)

N

T, N, R6

14.88

(378)

Mechanically Held

Electrically Held

A3, C, C6, P

Std., A12, C, C6, P, X

8.12

(206)

7.81

(198)

Dimensions p

Width Height Depth

7.81

(198)

11.88

(302)

12.69

(322)

11.88

(302)

6.03

(153)

7.44

(189)

22.00

(559)

7.13

(181)

10.00

(254)

15.88

(403)

14.12

(359)

14.12

(359)

12.69

(322)

14.12

(359)

14.12

(359)

5.28

(134)

5.19

(132)

7.56

(192)

Electrically Held &

Mechanically Held

T, N, R6

Mechanically Held Std., A3, C, C6, P, X

14.88

(378)

8.12

(206)

Electrically Held

Std., A12, C, C6, F,

P, X, T

11.25

(286)

Mechanically Held Std., F, X, T

Electrically Held N, R6, T, T10-T13, t

Mechanically Held

Electrically Held

A3, C, C6, N, R6, T,

T10-T13, t

Std., A12, C, C6, F,

P, X

Std., F, X

18.15

(461)

11.25

(286)

Mechanically Held

Electrically Held

Mechanically Held t

A3, C, C6, t

18.15

(461)

Electrically Held

Mechanically Held

N, R6, T, T10-T13

22.15

N, R6, T, T10-T13

(563)

25.15

(639)

29.15

(740)

25.15

(639)

29.15

(740)

39.15

(994)

9.73

(247)

6.03

(153)

7.56

(192)

9.73

(247)

8.99

(288)

9.24

(234)

8.99

(288)

9.24

(234)

10.24

(260)

Electrically and

Mechanically Held

Electrically and

Mechanically Held

Standard and

All Forms

Standard and

All Forms

22.15

(563)

17.21

(437)

39.15

(994)

44.21

(1123)

10.24

(260)

12.83

(325)

400 and

600

SYG

&

SZG

All

Electrically and

Mechanically Held

Standard and

All Forms

20.21

(513)

65.75

(1670)

13.10

(333)

800 SJG 2-3 With or without any forms

34.50

(876)

93.00

(2362)

23.50

(597) t

All “Type K” Forms.

p

Dimensions are in inches (millimeters).

14

© 1998 Square D All Rights Reserved

1/98

200 SVH All

Lighting Control

Approximate Dimensions – Class 8903

NEMA Type 3R

Amps Type

Number of Poles

30 SMH All

A B C

8.83

(224)

12.30

(312)

7.12

(181)

30

60

LH

SPH

All

9.83

(250)

16.30

(414)

8.62

(219)

D1

1.39

(35)

1.39

(35)

D2

1.44

(37)

1.44

(37)

E

6.00

(152)

F

7.50

(191)

7.00

(178)

11.50

(292)

G1

2.64

(67)

2.64

(67)

G2

2.16

(55)

2.16

(55)

H1

2.08

(53)

2.08

(53)

H2

2.62

(66)

J

14.28

(363)

2.62

(66)

16.78

(426)

K

1.37

(35)

1.31

(33)

L

1.37

(35)

1.75

(44)

M

1.88

(48)

2.13

(54)

N

4.38

(111)

4.88

(124)

P

1.83

(46)

1.83

(46)

100 SQH All

12.83

(326)

25.30

(643)

8.62

(219)

1.39

(35)

1.44

(37)

10.00

(254)

20.50

(521)

2.64

(67)

2.16

(55)

2.08

(53)

2.62

(66)

19.78

(502)

1.31

(33)

1.94

(49)

2.44

(62)

6.38

(162)

1.83

(46)

12.83

(326)

40.30

(1024)

9.12

(232)

1.39

(35)

1.44

(37)

10.00

(254)

35.50

(902)

2.64

(67)

2.16

(55)

2.08

(53)

2.62

(66)

20.28

(515)

1.31

(33)

2.31

(59)

2.69

(68)

6.38

(162)

1.83

(46)

K.O.

X

1

3

/

/

2

1

4

1

1

1

/

4

1

1

/

2

1

1

1

/

4

2

2

1

/

2

1

1

1

/

4

2

2

1

/

2

K.O.

Y

1

3

/

/

2

1

4

1

3

/

/

2

4

1

3

/

/

2

4

1

3

/

/

2

4

NEMA Type 4 and 4X

Ampere

Rating

30

30

60

100

200

300

Type

LW

LXW

SMW

SPW

SQW

SVW

SXW

Number of

Poles

Any

2-5

2-5

2 & 3

4 & 5

All

All

Form(s)

Standard, F, R6, Y48

A3, A12, C, C6, P, T

Electrically Held

Mechanically Held

Electrically Held

Electrically Held

Mechanically Held

Electrically Held

Mechanically Held

Electrically Held

Mechanically Held

Electrically Held

Mechanically Held

Electrically Held

Mechanically Held

Electrically Held

Mechanically Held

Electrically and

Mechanically Held

Electrically and

Mechanically Held

A

8.13

(206)

12.62

(321)

Std., A12, C, C6, P, X

Std., F, X

6.38

(162)

T

12.63

(321)

N, R6

A3, C, C6, T, N, P, R6

Std., A12, C, C6, P, X

Std., A3, C, C6, P, X

T, N, R6

A3, C, C6, T, N, P, R6

Std., A12, C, C6, F,

N, R6, P, T, T10-13, X

Std., A3, C, C6, F, N,

P, R6, T, T10-13, X

14.88

(378)

8.13

(206)

14.88

(378)

18.15

(461)

Std., A12, C, C6, F, P, a 18.15

Std., A3, C, C6, P, a

(461)

N, R6, T, T10-13

N, R6, T, T10-13

22.15

(563)

Standard and

All Forms

Standard and

All Forms

22.15

(563)

17.21

(437)

B

7.88

(200)

7.81

(198)

7.13

(181)

7.11

(181)

7.25

(184)

7.88

(200)

7.25

(184)

8.77

(223)

8.77

(223)

9.77

(248)

9.77

(248)

12.63

(321)

C

16.19

(411)

14.69

(373)

13.19

(351)

14.69

(373)

16.31

(414)

16.19

(411)

16.31

(414)

32.21

(818)

32.21

(818)

42.21

(1072)

42.21

(1072)

47.21

(1199)

Dimensions in inches (millimeters)

D

1.56

(40)

2.56

(65)

1.56

(40)

2.56

(65)

2.56

(65)

1.56

(40)

2.56

(65)

3.08

(78)

3.08

(78)

E

5.00

(127)

7.50

(191)

3.25

(83)

7.50

(191)

9.75

(248)

5.00

(127)

9.75

(248)

12.00

(305)

12.00

(305)

F

15.00

(381)

13.50

(343)

12.00

(305)

13.50

(343)

15.00

(381)

15.00

(381)

15.00

(381)

30.50

(775)

30.50

(775)

3.08

(78)

16.00

(406)

3.08

(78)

4.11

(104)

16.00

(406)

9.00

(229)

40.50

(1029)

40.50

(1029)

46.00

(1168)

G

0.60

(15)

0.63

(16)

0.63

(16)

0.63

(16)

0.63

(16)

0.60

(15)

0.63

(16)

0.61

(15)

0.61

(15)

0.61

(15)

0.61

(15)

0.61

(15)

H

1.94

(49)

3.38

(86)

1.91

(30)

3.19

(81)

3.19

(81)

1.94

(49)

3.88

(98)

3.67

(93)

3.67

(93)

3.67

(93)

3.67

(93)

4.59

(117)

I

14.75

(375)

18.44

(468)

11.81

(300)

18.50

(470)

20.88

(530)

14.75

(375)

20.88

(530)

26.71

(678)

26.71

(678)

31.71

(805)

31.71

(805)

28.32

(719)

J

2.00

(51)

1.69

(43)

1.63

(41)

1.64

(42)

2.06

(52)

2.00

(51)

2.06

(52)

2.58

(66)

2.58

(66)

K

2.63

(67)

2.31

(59)

2.31

(59)

2.31

(59)

2.63

(67)

2.63

(67)

2.63

(67)

3.19

(81)

3.19

(81)

2.33

(59)

2.33

(59)

3.11

(79)

2.88

(73)

2.88

(73)

5.75

(146)

L

0.31

(8)

0.31

(8)

0.31

(8)

0.31

(8)

0.31

(8)

0.31

(8)

0.31

(8)

0.44

(11)

0.44

(11)

400 &

600

SYW

&

SZW

All

Electrically and

Mechanically Held

Standard and

All Forms

20.21

(513)

12.13

(308)

65.21

(1656)

4.11

(104)

12.00

(305)

64.00

(1626)

0.61

(15)

4.59

(117)

30.82

(783)

2.67

(68)

4.50

(114)

800 SJW 2-3 With or without any forms

34.50

(876)

23.50

(597)

101.00

(2565)

Floor Mounting c

X hub is

1

/

4 in. left of center. W hub shown is another X hub. K dimension is distance between two X hubs. Actual W hub is located 3

3

/

16 in. to the right of X hub shown.

a

All “K” forms.

0.56

(14)

0.44

(11)

0.44

(11)

0.56

(14)

Bottom

Hub

Only

W

3

/

4

in.

3

/

4

in.

3

/

4

in.

3

/

4

in.

3

/

4

in.

3

3

3

/

/

/

4

4

4

in.

in.

in.

3

/

4

in.

3

/

4

in.

3

/

4

in.

3

/

4

in.

3

/

4

in.

c

D1

N

A

E D2

C

P

D

A

E D G B

G1

F

C

F B

Top &

Bottom

Hub

X

1

1

/

2

in.

1 in.

1 in.

1 in.

1

1

/

2

in.

1

1

/

2

in.

1

1

/

2

in.

2

1

/

2

in.

2

1

/

2

in.

2

1

/

2

in.

2

1

/

2

in.

3

1

/

2

in.

Two

3 in. c

G

(4) L. Dia. Mtg. Holes

C30054-260-A

G2

(4) .36 Dia. Mtg. Holes

(3) Closing Plates

D30060-118-D

J

H1

H2

X

M

M

X

Y K

L

NEMA Type 3R

I

W X

J

H

K

NEMA Type 4 and 4X

15

1/98

© 1998 Square D All Rights Reserved

Lighting Control

Class 8903 – Approximate Dimensions

NEMA Type 12

Ampere

Rating

Type

Number of Poles

Form(s)

Standard, F, R6, Y48

30

30

60

100

200

300

400 &

600

800

LA

LXA

SMA

SPA

SQA

SVA

SXA

SYA

&

SZA

SJA

Any

2-5

2-5

2 & 3

4 & 5

All

All

All

A3, A12, C, C6, P, T

Electrically Held

Mechanically Held

Std., A12, C, C6, P, X

Std., F, P, X

Electrically Held

Electrically Held

Mechanically Held

Electrically Held

Mechanically Held

Electrically Held

Mechanically Held

Electrically Held

Mechanically Held

Electrically Held

Mechanically Held

Electrically Held

Mechanically Held

Electrically and

Mechanically Held

Electrically and

Mechanically Held

T

N, R6

A3, C, C6, T, N, P, R6

Std., A12, C, C6, P, X

Std., A3, C, C6, P, X

T, N, R6

A3, C, C6, T, N, P, R6

Std., A12, C, C6, F,

N, R6, P, T, T10-13, X

Std., A3, C, C6, F, N,

P, R6, T, T10-13, X

Std., A12, C, C6, F, N, P, a

Std., A3, C, C6, P, a

N, R6, T, T10-13, a

N, R6, T, T10-13, a

Standard and

All Forms

Standard and

All Forms

Electrically and

Mechanically Held

Standard and

All Forms

2-3 With or without any forms p

See Figure 1 for all dimensions except 800A; for 800A dimensions, see Figure 2.

a

All Type “K” Forms using Class 9001 Type K Control Units.

A

8.13

(206)

11.88

(302)

6.38

(162)

11.88

(302)

14.88

(378)

8.13

(206)

14.88

(378)

18.15

(461)

22.15

(563)

22.15

(563)

17.21

(437)

20.21

(513)

93.00

(2362)

B

8.50

(216)

7.75

(197)

8.53

(217)

7.75

(197)

7.88

(200)

9.28

(236)

7.88

(200)

9.24

(234)

10.24

(260)

10.24

(260)

13.33

(339)

13.00

(330)

34.50

(876)

C

15.75

(400)

13.50

(343)

12.75

(324)

13.50

(343)

16.00

(406)

16.00

(406)

15.75

(400)

31.50

(800)

41.50

(1054)

41.50

(1054)

47.00

(1193)

65.00

(1651)

23.50

(597)

3.08

(78)

3.08

(78)

3.08

(78)

4.11

(104)

4.11

(104)

Dimensions in inches (millimieters) p

D E F G

1.56

(40)

3.81

(97)

5.00

(127)

4.25

(108)

15.00

(381)

12.75

(324)

0.31

(8)

0.38

(10)

1.56

(40)

2.56

(65)

2.56

(65)

3.25

(83)

6.75

(171)

9.75

(248)

12.00

(305)

12.75

(324)

15.00

(381)

0.38

(10)

0.38

(10)

0.50

(13)

1.56

(40)

2.56

(65)

5.00

(127)

9.75

(248)

15.00

(381)

15.00

(381)

0.50

(13)

0.38

(10)

12.00

(305)

16.00

(406)

16.00

(406)

9.00

(229)

12.00

(305)

NIGHT-MASTER Outdoor Lighting Contactors (Short Version) – NEMA Type 3R

Ampere

Rating

Description Type Number A B C D E F G H

Cond.

J

30

60

100

200

Disconnect Switch & Circuit

Breaker Types

SMC61, 62 & 81

Disconnect Switch & Circuit

Breaker Types

SPC61, 62 & 81

Disconnect Switch & Circuit

Breaker Types

SQC61, 62 & 81

Disconnect Switch Type

Circuit Breaker Type

SVC61 & 62

SVC81

23.50

(597)

34.53

(877)

48.37

(1229)

15.00

(381)

20.00

(508)

19.00

(483)

8.42

(214)

8.42

(214)

9.12

(232)

10.50

(267)

10.50

(267)

10.53

(267)

19.00

(483)

22.38

(568)

30.04

(763)

44.00

(1118)

33.41

(849)

47.25

(1200)

7.00

(178)

7.00

(178)

7.00

(178)

2.18

(55)

2.18

(55)

2.18

(55)

1.50

(38)

2.0

(2.50)

2.50

(64)

K

2.13

(54)

2.68

(68)

2.68

(68)

NIGHT-MASTER Outdoor Lighting Contactors (Long Version) – NEMA Type 3R

Ampere

Rating

Description Type Number A B C D E F G H

Cond.

J

30

60

100

200

Disconnect Switch & Circuit

Breaker Types

SMC63, 64 & 83

Disconnect Switch & Circuit

Breaker Types

SPC63, 64 & 83

Disconnect Switch & Circuit

Breaker Types

SQC63, 64 & 83

Disconnect Switch Type

Circuit Breaker Type

SVC63 & 64

SVC83

38.88

(987)

42.53

(1080)

56.37

(1432)

15.00

(381)

20.00

(508)

19.00

(483)

8.42

(214)

8.42

(214)

9.12

(232)

10.42

(265)

10.42

(265)

10.53

(267)

34.38

(873)

37.76

(959)

38.04

(966)

52.00

(1321)

41.41

(1052)

55.25

(1403)

7.00

(178)

7.00

(178)

7.00

(178)

2.18

(55)

2.18

(55)

2.18

(55)

1.50

(38)

2.0

(2.50)

2.50

(64)

K

2.13

(54)

2.68

(68)

2.68

(68)

30.50

(775)

L

2.13

(54)

2.68

(68

2.68

(68)

L

2.13

(54)

2.68

(68)

2.69

(68)

0.50

(13)

M

2.13

(54)

3.44

(87)

3.44

(87)

M

H

2.13

(54)

4.94

(125)

3.56

(90)

3.66

(93)

3.66

(93)

3.66

(93)

3.66

(93)

3.67

(93)

40.50

(1029)

40.50

(1029)

46.00

(1168)

64.00

(1625)

0.50

(13)

0.50

(15)

0.50

(13)

0.50

(13)

Floor Mounting

3.67

(93)

3.67

(93)

4.59

(117)

5.31

(135)

N

2.13

(54)

0.50-

0.75

3.44

(87)

3.44

(87)

0.50-

0.75

0.50-

0.75

1.-1.25

1.50

1.-1.25

2.-2.50

1.-1.25

2.-2.50

I

14.75

(375)

18.12

(460)

12.50

(318)

18.12

(460)

21.25

(540)

15.38

(391)

21.25

(540)

26.71

(678)

31.71

(805)

31.71

(805)

28.32

(719)

30.87

(784)

0.44

(11)

N

0.50-

0.75

Knockouts

P

1.-1.25

1.50

Q

0.50-

0.75

0.50-

0.75

0.50-

0.75

1.-1.25

2.-2.50

1.-1.25

2.-2.50

0.50-

0.75

1.-1.25

1.5-2.0

1.-1.25

1.5-2.0

0.44

(11)

0.44

(11)

0.56

(14)

0.69

(18)

J

0.31

(8)

0.31

(8)

0.31

(8)

0.31

(8)

0.31

(8)

0.31

(8)

0.31

(8)

1.-1.25

1.5-2.0

1.-1.25

1.5-2.0

Knockouts

P Q

D

A

E D

G

B

C

(4) .44 Dia. Mtg. Holes

11

G

J

D

H

F

C

E

F

A

G

(4) J Dia. Mtg. Holes

C30054-251-B

B

A

I

16

H

Figure 1: NEMA Type 12 (30-600A)

2142-C48

Figure 2: NEMA Type 12 (800A)

© 1998 Square D All Rights Reserved

B

C

L M

N P Q K

Figure 3: NIGHT-MASTER

1/98

Lighting Control

Approximate Dimensions – Class 8903

L

A

D

M

K

HANDLE

SWING

L C

Y

N

O

E B

Y

F

J

COVER

OPEN 90

°

(4) .31 DIA. MTG.HOLES (FOR SIZE 0, 1, & 2)

8

(4) .44 DIA. MTG. HOLES (FOR SIZE 3 & 4)

11

(4) .56 DIA. MTG. HOLES LOCATED ON

14 EXTERNAL FLANGES (FOR SIZE 5)

W X W

G

C30053-173I

H

I

Combination Lighting Contactors – NEMA Type 1 Enclosure

Ampere

Rating

30

60

Type

SMG6– & 8–

SMG7– & 9–

SPG6– & 8–

SPG7– & 9–

A

9.50

(241)

13.75

(349)

10.50

(267)

15.00

(381)

B

22.50

(572)

23.00

(584)

26.00

(660)

28.75

(730)

C D

8.37

(213)

6.38

(162)

8.36

(212)

9.62

(244)

9.62

(244)

10.63

(270)

7.37

(187)

11.62

(295)

Dimensions in inches (millimeters) t

(see Figure 1)

E F G H I J K

20.50

(521)

21.00

(533)

24.00

(610)

26.25

(667)

14.68

(373)

20.07

(510)

17.00

(432)

21.50

(546)

1.81

(46)

1.87

(47)

2.12

(54)

2.18

(55)

1.69

(43)

1.88

(48)

2.00

(51)

2.00

(51)

3.37

(86)

3.76

(96)

4.00

(102)

4.00

(102)

3.38

(86)

2.06

(52)

2.06

(52)

2.56

(65)

1.06

(27)

L

3.25

(83)

M

2.18

(55)

1.06

(27)

3.25

(83)

2.18

(55)

1.06

(27)

1.31

(33)

3.25

(83)

3.25

(83)

2.18

(55)

2.18

(55)

N

1.25

(32)

1.25

(32)

1.25

(32)

1.25

(32)

O

0.87

(22)

0.87

(22)

0.87

(22)

0.87

(22)

Top & Bot.

Sides

W X Y

0.50-

0.75

0.50-

0.75

0.50-

0.75-

1.0

0.50-

0.75-

1.0

1.0-

1.25

1.0-

1.25

0.50-

0.75

0.50-

0.75

.50

.50

.50

.50

Figure 1

NEMA Type 1 Enclosure

NEMA Type 1 Enclosure

G

N

O

Ampere

Rating

100

200

200

Type

SQG6– & 7–

SQG81 & 91

SVG6– & 7–

SVG81 & 91

SXG6– & 7–

F

K

COVER

OPEN 90

°

(4) .31 DIA. MTG.HOLES (FOR SIZE 0, 1, & 2)

8

(4) .44 DIA. MTG. HOLES (FOR SIZE 3 & 4)

11

(4) .56 DIA. MTG. HOLES LOCATED ON

14 EXTERNAL FLANGES (FOR SIZE 5)

W X W

J

C30053-173 I

H

I

Figure 2

NEMA Type 1 Enclosure

400

600

Ampere

Rating

SXG81 & 91

SYG81 & 91

SZG81 & 91

Type

36.00

(914)

90.00

(2286)

17.00

(432)

NEMA Type 4 & 4X Enclosure

L

A

D

A

F

E

B

HANDLE

SWING

L C

E

H

D

HANDLE

SWING

G C

Y

Y

B

COVER OPEN 90

°

(4) .31 DIA. MTG.HOLES (FOR SIZE 0, 1, & 2)

8

(4) .44 DIA. MTG. HOLES (FOR SIZE 3 & 4)

11

(4) .56 DIA. MTG. HOLES LOCATED ON

14 EXTERNAL FLANGES (FOR SIZE 5)

C30053-173 I

W X

J

I

K

Figure 3

NEMA Type 4 Enclosure

30

60

100

200

300

400

600

SQW6– & 7–

SQW81 & 91

SVW6– & 7–

SVW81 & 91

SYW81 & 91

SZW81 & 91

A

15.25

(387)

39.50

(1003)

16.00

(406)

20.00

(508)

B

50.00

(1270)

75.00

(1905)

20.00

(508)

63.00

(1600)

C

10.60

(269)

10.68

(271)

14.37

(365)

14.37

(365)

D

Dimensions in inches (millimeters) t

(see Figure 2)

E F G H I J K

9.25

(235)

3.00

(76)

22.68

(576)

41.00

(1041)

2.69

(68)

5.38

(137)

2.83

(72)

3.74

(95)

L

5.00

(127)

10.00

(254)

12.00

(305)

12.00

(305)

3.00

(76)

4.00

(102)

4.00

(102)

23.68

(601)

51.50

(1308)

2.69

(68)

29.43

(748)

77.00

(1956)

3.19

(81)

27.43

(697)

65.00

(1651)

3.19

(81)

5.38

(137)

...

...

2.83

(72)

3.52

(89)

3.52

(89)

3.74

(95)

7.00

(178)

7.00

(178)

5.00

(127)

9.25

(235)

5.00

(127)

SMW6–& 8–

SMW7– & 9–

SPW6– & 8–

SPW7– & 9–

SXW6– & 7–

SXW81 & 91

15.00

(381)

15.25

(387)

16.00

(406)

20.00

(508)

20.00

(508)

A

9.50

(241)

13.75

(349)

10.50

(267)

36.00

(914)

9.61

(244)

10.60

(269)

10.56

(268)

14.21

(361)

14.21

(361)

B

8.36

(212)

8.36

(212

9.61

(244)

17.71

(450)

3.25

(83)

5.00

(127)

5.00

(127)

9.25

(235)

5.00

(127)

D

3.25

(83)

3.25

(83)

3.25

(83)

31.01

(788)

41.76

(1061)

52.26

(1327)

78.12

(1984)

66.12

(1679)

C

24.76

(629)

25.26

(642)

28.26

(718)

98.00

(2489)

5.38

(137)

2.50

(64)

2.50

(64)

4.00

(102)

4.00

(102)

E

2.50

(64)

4.75

(121)

2.50

(64)

Floor Mounting Enclosure

Dimensions in inches (millimeters) t

F G H I J

4.50

(114)

4.25

(108)

23.50

(597)

24.00

(610)

0.63

(16)

0.63

(16)

3.00

(76)

5.25

(133)

1.62

(41)

1.62

(941)

5.50

(140)

4.25

(108)

10.25

(260)

11.00

(279)

12.00

(305)

12.00

(305)

27.00

(686)

29.75

(756)

40.50

(1028)

51.00

(1295)

77.00

(1956)

65.00

(1651)

0.63

(16)

0.63

(16)

0.63

(16)

0.63

(16)

0.56

(14)

0.56

(14)

3.00

(76)

5.88

(149)

3.24

(82)

3.24

(82)

4.77

(121)

4.77

(121)

2.96

(75)

2.96

(75)

2.00

(51)

2.00

(51)

2.61

(66)

2.61

(66)

Floor Mounting Enclosure

M

...

...

...

...

2.63

(67)

3.19

(81)

3.19

(81)

3.50

(89)

3.50

(89)

K

2.31

(59)

2.31

(59)

2.63

(67)

N

1.21

(31)

1.21

(31)

...

...

21.06

(535)

22.18

(563)

23.00

(584)

29.43

(748)

27.43

(697)

L

14.31

(363)

20.14

(512)

16.56

(421)

O

0.90

(23)

0.90

(23)

...

...

Top & Bot.

Sides

W X Y

1.-1.25

2.-2.50

2.50

0.50-

0.75

0.50-

0.75

.50

.50

0.50-

0.75

0.50-

0.75

3.00

3.00

...

...

...

W

...

...

X

...

...

0.75 Hub 1.0 Hub

0.75 Hub 1.0 Hub

0.75 Hub 1.50 Hub

0.75 Hub 1.50 Hub

0.75 Hub 2.50 Hub

0.75 Hub 2.50 Hub

0.75 Hub 3.50 Hub

0.75 Hub 3.50 Hub t

Dimensions are the same for Form F4T (standard control transformer), Form F4T11 (100 VA extra capacity) and Form F4T12 (200 VA extra capacity).

A

F E

H

D

HANDLE

SWING

B

G C

(4) .31 DIA. MTG.HOLES (FOR SIZE 0, 1, & 2)

8

(4) .44 DIA. MTG. HOLES (FOR SIZE 3 & 4)

11

(4) .56 DIA. MTG. HOLES LOCATED ON

14 EXTERNAL FLANGES (FOR SIZE 5)

C30053-175J

I

Figure 4

NEMA Type 12 Enclosure

NEMA Type 12 Enclosure

Ampere

Rating

30

60

100

200

300

400

600

Type

SMA6– & 8–

SMA7– & 9–

SPA6– & 8–

SPA7– & 9–

SQA6– & 7–

SQA81 & 91

SVA6– & 7–

SVA81 & 91

SXA6– & 7–

SXA81 & 91

SYA81 & 91

SZA81 & 91

15.00

(381)

15.25

(387)

16.00

(406)

20.00

(508)

20.00

(508)

A

9.50

(241)

13.75

(349)

10.50

(267)

36.00

(914)

B

8.36

(212)

10.10

(257)

9.61

(244)

10.98

(279)

10.59

(259)

10.52

(267)

14.21

(361)

14.21

(361)

17.71

(450)

C

24.26

(616)

24.76

(629)

27.76

(705)

30.51

(775)

42.00

(1067)

52.50

(1334)

78.00

(1981)

66.00

(1676)

90.00

(2286)

Dimensions in inches (millimeters) t

D E F G

3.25

(83)

3.25

(83)

3.25

(83)

3.25

(83)

5.00

(127)

5.00

(127)

9.25

(235)

5.00

(127)

2.50

(64)

4.75

(121)

2.50

(64)

5.38

(137)

3.00

(76)

3.00

(76)

4.00

(102)

4.00

(102)

4.50

(114)

4.25

(108)

5.50

(140)

4.25

(108)

9.25

(235)

10.00

(254)

12.00

(305)

12.00

(305)

23.50

(597)

24.00

(610)

27.00

(686)

29.75

(756)

41.00

(1041)

51.50

(1308)

77.00

(1956)

65.00

(1651)

H

0.38

(10)

0.38

(10)

0.38

(10)

0.38

(10)

0.50

(13)

0.50

(13)

0.50

(13)

0.50

(13)

Floor Mounting Enclosure

I

3.25

(83)

5.50

(140)

3.25

(83)

6.13

(156)

3.75

(95)

3.75

(95)

7.75

(197)

7.75

(197)

23.43

(595)

22.31

(567)

23.00

(584)

29.43

(748)

27.43

(697)

J

14.31

(363)

22.00

(559)

16.56

(421) t

Dimensions are the same for Form F4T (standard control transformer), Form F4T11 (100 VA extra capacity) and Form F4T12 (200 VA extra capacity).

17

1/98

© 1998 Square D All Rights Reserved

Lighting Control

Class 8903 – Approximate Dimensions

Class 8903 REQ Open Type

Electrically Held

Figure Device Poles Mounting

2P – 2P (4) #10

1

30 A

60 A

100 A

150 A

3P – 3P

4P – 4P

2P – 2P

3P – 3P

4P – 4P

2P – 2P

3P – 3P

4P – 4P

2P – 2P

3P – 3P

4P – 4P

(4) #10

(4) #10

(4) #10

(4) #10

(4) #10

(4) 5/16

(4) 5/16

(4) 5/16

(4) 5/16

(4) 5/16

(4) 5/16

A

12.13

(308)

12.72

(323)

12.72

(323)

21.71

(551)

14.21

(361)

12.13

(308)

13.27

(337)

12.13

(308)

12.13

(308)

13.27

(337)

14.21

(361)

21.71

(551)

B

6.75

(171)

7.97

(202)

7.97

(202)

8.96

(228)

8.96

(228)

6.75

(171)

6.75

(171)

6.75

(171)

6.75

(171)

6.75

(171)

8.96

(228)

8.96

(228)

E

6.25

(159)

7.00

(178)

7.00

(178)

8.00

(203)

8.00

(203)

6.25

(159)

6.25

(159)

6.25

(159)

6.25

(159)

6.25

(159)

8.00

(203)

8.00

(203)

D

11.63

(295)

11.75

(299)

11.75

(299)

20.75

(527)

13.25

(337)

11.63

(295)

11.63

(295)

11.63

(295)

11.63

(295)

11.63

(295)

13.25

(337)

20.75

(527)

C

6.03

(153)

7.00

(178)

7.00

(178)

7.00

(178)

7.00

(178)

6.03

(153)

6.03

(153)

6.03

(153)

6.03

(153)

6.03

(153)

7.00

(178)

7.00

(178)

F

A

D

H

I

C

G

H

0.50

(13)

0.48

(122)

0.48

(122)

0.48

(122)

0.48

(122)

0.50

(13)

0.50

(13)

0.50

(13)

0.50

(13)

0.50

(13)

0.48

(122)

0.48

(122)

J

0.25

(6)

0.49

(12.5)

0.49

(12.5)

0.48

(122)

0.49

(12.5)

0.25

(6)

0.25

(6)

0.25

(6)

0.25

(6)

0.25

(6)

0.49

(12.5)

0.48

(122)

I

0.25

(6)

0.48

(122)

0.48

(122)

0.48

(122)

0.48

(122)

0.25

(6)

0.25

(6)

0.25

(6)

0.25

(6)

0.25

(6)

0.48

(122)

0.48

(122)

E B

J

Figure 1

18

© 1998 Square D All Rights Reserved

1/98

1/98

Lighting Control

Approximate Dimensions – Class 8903

Class 8903 REQ Open Type

Mechanically Held

Figure Device Poles Mounting

2P – 2P (4) #10

2

3

30 A

60 A

100 A

150 A

3P – 3P

4P – 4P

2P – 2P

3P – 3P

4P – 4P

2P – 2P

3P – 3P

4P – 4P

2P – 2P

3P – 3P

4P – 4P

(4) #10

(4) #10

(4) #10

(4) #10

(4) #10

(4) 5/16

(4) 5/16

(4) 5/16

(4) 5/16

(4) 5/16

(4) 5/16

A

12.13

(308)

12.98

(330)

12.98

(330)

21.71

(551)

14.21

(361)

12.13

(308)

13.27

(337)

12.13

(308)

12.13

(308)

13.27

(337)

14.21

(361)

21.71

(551)

B

8.53

(217)

10.50

(267)

10.50

(267)

10.93

(278)

10.93

(278)

8.53

(217)

8.53

(217)

8.53

(217)

8.53

(217)

8.53

(217)

10.93

(278)

10.93

(278)

D

11.63

(295)

11.75

(299)

11.75

(299)

20.75

(527)

13.25

(337)

11.63

(295)

11.63

(295)

11.63

(295)

11.63

(295)

11.63

(295)

13.25

(337)

20.75

(527)

C

6.31

(160)

7.22

(183)

7.22

(183)

7.22

(183)

7.22

(183)

6.31

(160)

6.31

(160)

6.31

(160)

6.31

(160)

6.31

(160)

7.22

(183)

7.22

(183)

E

6.25

(159)

7.00

(178)

7.00

(178)

8.00

(203)

8.00

(203)

6.25

(159)

6.25

(159)

6.25

(159)

6.25

(159)

6.25

(159)

8.00

(203)

8.00

(203)

F

8.13

(207)

8.13

(207)

8.13

(207)

8.13

(207)

8.13

(207)

8.13

(207)

G

9.31

(237)

9.31

(237)

9.31

(237)

9.31

(237)

9.31

(237)

9.31

(237)

H

0.50

(13)

0.48

(122)

0.48

(122)

0.48

(122)

0.48

(122)

0.50

(13)

0.50

(13)

0.50

(13)

0.50

(13)

0.50

(13)

0.48

(122)

0.48

(122)

J

2.03

(51.6)

3.02

(76.7)

3.02

(76.7)

2.45

(62.2)

2.45

(62.2)

2.03

(51.6)

2.03

(51.6)

2.03

(51.6)

2.03

(51.6)

2.03

(51.6)

2.45

(62.2)

2.45

(62.2)

I

0.25

(6)

0.48

(122)

0.48

(122)

0.48

(122)

0.48

(122)

0.25

(6)

0.25

(6)

0.25

(6)

0.25

(6)

0.25

(6)

0.48

(122)

0.48

(122)

A

D

I

H

F

G

Figure 2

J

E

B

C

A

D

H

I

E

B

J

Figure 3

C

19

© 1998 Square D All Rights Reserved

Square D Company

8001 Hwy 64 East

Knightdale, NC 27545

(919) 266-3671

Square D and are registered trademarks of Square D Company.

® is a registered trademark of Underwriter’s Laboratories, Inc.

is a registered trademark of Canadian Standard Association.

VERSA-CRIMP is a registered trademark of Hubbell Incorporated.

NIGHT-MASTER is a trademark of Square D Company

Catalog No. 8903CT9701 January 1998 © 1998 Square D All Rights Reserved.