Toshiba 4200FA Power Supply User Manual

U
NINTERRUPTIBLE
P
OWER
S
YSTEM
THREE-PHASE 15/ 25/ 30/ 33/ 50 kVA UPS
4200
FA
USER'S MANUAL
MANUFACTURED IN THE U.S.A.
Document Number: 53878-004
Date: April 2005
0
TOSHIBA
4200FA
THREE PHASE- 15/25/30/33/50 kVA
UNINTERRUPTIBLE POWER SYSTEM
OPERATION MANUAL
FOR MODELS
T42F3F150X#MBN
T42F3F150F#MBN
T42#3#150##MXN
T42F3F250X#MBN
T42F3F250F#MBN
T42#3#250##MXN
T42F3F300X#MBN
T42F3F300F#MBN
T42#3#300##MXN
T42F3F330X#MBN
T42F3F330F#MBN
T42#3#330##MXN
T42F3F500XAMBN
T42F3F500F#MBN
T42#3#500##MXN
TOSHIBA INTERNATIONAL CORPORATION
INDUSTRIAL DIVISION
13131 West Little York Rd., Houston, Texas 77041
1
TOSHIBA
Notice
These Instructions are not intended to cover all of the details or variations in equipment, nor to provide for every possible contingency to be met in connection with installation, operation, or maintenance. This manual may change without notice. Contact your local Toshiba sales office to verify that this is the latest revision. Should further information be desired or should particular problems arise which are not covered sufficiently, the matter should be referred to your local Toshiba sales office.
The contents of this instruction manual shall not become a part of or modify any prior or existing equipment, commitment, or relationship. The sales contract contains the entire obligation of Toshiba International
Corporation’s UPS Division. The warranty contained in the contract between the parties is the sole warranty of Toshiba International
Corporation’s UPS Division, and any statements contained herein do not create new warranties or modify the existing warranty.
Any Electrical or mechanical modifications to this equipment, without prior written consent of Toshiba International Corporation, will void all warranties and may void UL/CUL listing. Unauthorized modifications also can result in personal injury, death, or destruction of the equipment.
UNINTERRUPTIBLE POWER SUPPLY
Complete the information below for the UPS system received.
Unless otherwise specified on the warranty card, the warranty period for the UPS or UPS part is 36 months from the shipment date (see TIC bill of lading).
Unless otherwise specified on the warranty card, the warranty period for a UPS battery is 24 months from the shipment date (see TIC bill of lading).
Please complete the following information and retain for your records.
Job Number:
Model Number:
Serial Number:
Application:
Date of Installation:
Inspected By:
2
TOSHIBA
Manual’s Purpose and Scope
This manual provides information on how to safely install, operate, and maintain your TIC power electronics product. This manual includes a section of general safety instructions that describes the warning labels and symbols that are used throughout the manual. Read the manual completely before installing, operating, or performing maintenance on this equipment.
This manual and the accompanying drawings should be considered a permanent part of the equipment and should be readily available for reference and review. Dimensions shown in the manual are in metric and/or the English equivalent.
Toshiba International Corporation reserves the right, without prior notice, to update information, make product changes, or to discontinue any product or service identified in this publication.
TOSHIBA is a registered trademark of the Toshiba Corporation. All other product or trade references appearing in this manual are registered trademarks of their respective owners.
Toshiba International Corporation (TIC) shall not be liable for direct, indirect, special, or
consequential damages resulting from the use of the information contained within this manual.
This manual is copyrighted. No part of this manual may be photocopied or reproduced in any form without the prior written consent of Toshiba International Corporation.
© Copyright 2005 Toshiba International Corporation.
All rights reserved.
Printed in the U.S.A.
Contacting Toshiba’s Customer Support
Center
Toshiba’s Customer Support Center can be contacted to obtain help in resolving any
Uninterruptilbe Power Supply system problems that you may experience or to provide application information.
The center is open from 8 a.m. to 5 p.m. (CST), Monday through Friday. The Support Center’s toll free number is US (800) 231-1412/Fax (713) 466-8773.
You may also contact Toshiba by writing to:
Toshiba International Corporation
13131 West Little York Road
Houston, Texas 77041-9990
Attn: UPS Product Manager.
For further information on Toshiba’s products and services, please visit our website at
www.tic.toshiba.com
.
3
TOSHIBA
General Safety Instructions
DO NOT attempt to install, operate, maintain or dispose of this equipment until you have read and understood all of the product safety information and directions that are contained in this manual.
Safety Alert Symbol
The Safety Alert Symbol indicates that a potential personal injury hazard exists. The symbol is comprised of an equilateral triangle enclosing an exclamation mark.
Signal Words
Listed below are the signal words that are used throughout this manual followed by their descriptions and associated symbols. When the words DANGER, WARNING and CAUTION are used in this manual they will be followed by important safety information that must be carefully adhered to.
The word DANGER preceded by the safety alert symbol indicates that an imminently hazardous situation exists that, if not avoided, will result in death or serious injury to personnel.
DANGER
The word WARNING in capital letters preceded by the safety alert symbol indicates that a potentially hazardous situation exists that, if not avoided, could result in death or serious injury to personnel.
WARNING
The word CAUTION in capital letters preceded by the safety alert symbol indicates that a potentially hazardous situation exists which, if not avoided, may result in minor or moderate injury.
CAUTION
The word CAUTION or ATTENTION in capital letters without the safety alert symbol indicates a potentially hazardous situation exists which, if not avoided, may result in equipment and property damage.
CAUTION/ATTENTION
4
TOSHIBA
Special Symbols
To identify special hazards, other symbols may appear in conjunction with the DANGER,
WARNING and CAUTION signal words. These symbols indicate areas that require special and/or strict adherence to the procedures to prevent serious injury to personnel or death.
Electrical Hazard Symbol
A symbol which indicates a hazard of injury from electrical shock or burn. It is comprised of an equilateral triangle enclosing a lightning bolt.
Explosion Hazard Symbol
A symbol which indicates a hazard of injury from exploding parts. It is comprised of an equilateral triangle enclosing an explosion image.
5
TOSHIBA
Equipment Warning Labels
DO NOT attempt to install, operate, maintain, or dispose of this equipment until you have read and understood all of the product warnings and user directions that are contained in this instruction manual.
Shown below are examples of warning labels that may be found attached to the equipment. DO NOT remove or cover any of the labels. If the labels are damaged or if additional labels are required, contact your Toshiba representative for additional labels.
Labels attached to the equipment are there to provide useful information or to indicate an imminently hazardous situation that may result in serious injury, severe property and equipment damage, or death if the instructions are not followed.
6
TOSHIBA
7
TOSHIBA
TABLE OF CONTENTS
1.0 Product Description ................................................................................................ 13
1.1
Theory of Operation............................................................................................................................ 13
1.2
Application and Use............................................................................................................................ 13
1.3
Power Backup .................................................................................................................................... 13
1.4
Power Conditioning ............................................................................................................................ 13
2.0 Uncrating/Inspection/Storage/Disposal................................................................. 14
2.1
Uncrating the new UPS equipment 15/25/30/33kVA: ........................................................................ 14
2.2
Uncrating the new UPS equipment 50kVA: ....................................................................................... 15
2.3
Inspection of the new UPS equipment ............................................................................................... 15
2.3
Inspection of the new UPS equipment ............................................................................................... 16
2.4
Storage of UPS equipment................................................................................................................. 16
2.5
Disposal.............................................................................................................................................. 16
3.0 Installation Precautions .......................................................................................... 17
3.1
Equipment Placement ........................................................................................................................ 17
3.2
System Preparation (Pre-Power) ....................................................................................................... 18
3.3
Operating Precautions........................................................................................................................ 18
4.0 UPS Connections .................................................................................................... 19
4.1
Power Connections 15/25/30/33 kVA with Internal Batteries............................................................. 19
4.1.1
Power Connections 15/25/30/33kVA with Internal Transformer ................................................. 19
4.1.1
Power Connections 15/25/30/33kVA with Internal Transformer ................................................. 20
4.1.2
Recommended Wire Size and Torque Requirements................................................................. 21
4.1.3
Power Connection Cable Routing and Conduit Placement ........................................................ 22
4.2
Control Circuit and External Battery Interface Connections 15/25/30/33 kVA ................................... 23
4.2.1
Recommended Wire Size and Torque Requirements................................................................. 23
4.3
Power Connections 50 kVA................................................................................................................ 24
4.3.1
Recommended Wire Size and Torque Requirements For UPS Input and Output Terminals..... 25
4.3.2
Power Connection Cable Routing ............................................................................................... 26
4.4
Control Circuit and External Interface Connections ........................................................................... 27
4.4.1
Recommended Wire Size and Torque Requirements................................................................. 27
4.5
Communication Interface ................................................................................................................... 28
4.5.1
Remote Contact........................................................................................................................... 28
4.5.2
RS-232C...................................................................................................................................... 29
4.5.3
UPS Shutdown (via RS-232C) .................................................................................................... 29
5.0 Technical Data ......................................................................................................... 30
5.1
4200FA 15 / 25kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries................................... 30
5.2
4200FA 15/ 25kVA w/Internal Transformer ........................................................................................ 31
5.3
4200FA 30 / 33kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries................................... 32
5.4
4200FA 30/ 33kVA w/Internal Transformer ........................................................................................ 33
5.5
4200FA 50kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries.......................................... 34
5.6
4200FA 50kVA w/Internal Transformer .............................................................................................. 35
5.7
Operating the UPS ............................................................................................................................. 36
5.7.1
AC Input Mode (Normal Operation)............................................................................................. 36
5.7.2
Bypass Mode............................................................................................................................... 36
5.7.3
Battery Backup Mode .................................................................................................................. 37
5.8
Battery Backup Time and Discharge Process.................................................................................... 38
5.9
Battery Low Voltage Tolerances ........................................................................................................ 38
5.10
Battery Recharging............................................................................................................................. 39
5.11
Front Panel Layout (All Units) ............................................................................................................ 40
5.12
EPO (Emergency Power Off) Function .............................................................................................. 40
5.13
Audible Alarm Functions .................................................................................................................... 40
5.14
LED (Light Emitting Diode) Functions ................................................................................................ 42
5.14.1
LED (Light Emitting Diode) System Status ................................................................................. 42
8
TOSHIBA
5.15
LCD (Liquid Crystal Display) Functions.............................................................................................. 43
5.15.1
Line-1 System Messages ............................................................................................................ 43
5.15.2
Line-2 System Fault Messages ................................................................................................... 43
5.15.3
Line-3 System Messages ............................................................................................................ 43
5.15.4
Line-4 System Messages ............................................................................................................ 44
5.16
Initial Battery Charge .......................................................................................................................... 45
5.17
Start-up Procedure ............................................................................................................................. 46
5.18
Shutdown Procedure .......................................................................................................................... 47
5.19
Maintenance Bypass Procedure ........................................................................................................ 48
5.20
Keypad Overview ............................................................................................................................... 49
5.21
Key Functions..................................................................................................................................... 50
5.21.1
MONI ........................................................................................................................................... 50
5.21.2
IN ................................................................................................................................................. 50
5.21.3
OUT ............................................................................................................................................. 50
5.21.4
BATT Key .................................................................................................................................... 51
5.21.5
MENU, F1, ENTER, UP, & DOWN Keys .................................................................................... 51
5.21.6
BATT TEST Key .......................................................................................................................... 51
5.21.7
BUZZ STOP Key ......................................................................................................................... 52
5.21.8
RESET Key ................................................................................................................................. 52
5.22
Menu Data Screens............................................................................................................................ 53
5.22.1
Settings for Calendar and Clock.................................................................................................. 53
5.22.2
Adjusting the Buzzer Volume ...................................................................................................... 53
5.22.3
Settings for Display Duration....................................................................................................... 53
5.22.4
Run Switch Select ....................................................................................................................... 54
5.22.5
Serial Com Station Address ........................................................................................................ 54
5.22.6
Output Voltage Adjustment ......................................................................................................... 55
5.22.7
Charge Mode Select.................................................................................................................... 55
5.22.8
Reset to Default Settings............................................................................................................. 56
5.23
Overload Operation ............................................................................................................................ 56
5.24
Backup History and Fault History ....................................................................................................... 57
6.0 UPS Protection System .......................................................................................... 59
6.1
System Protection Features ............................................................................................................... 59
6.2
System Protection Functions.............................................................................................................. 59
7.0 Authorized Factory Service .................................................................................... 60
7.1
Start-up............................................................................................................................................... 60
7.2
Preventive Maintenance ..................................................................................................................... 60
7.3
Parts Replacement ............................................................................................................................. 61
8.0 External Layouts / Dimensions / Weights.............................................................. 62
8.1
External Dimensions 15/25/30/33kVA................................................................................................ 62
8.2
External Dimensions 50kVA............................................................................................................... 63
8.3
Shipping Dimensions and Weights..................................................................................................... 64
9
TOSHIBA
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during the installation, maintenance, and operation of the UPS and its batteries to assure safe and proper operation
1. Turn off, lockout, and tagout all power sources before connecting the power wiring to the equipment or when performing maintenance.
2. Hardwire type UPS units are not equipped with an over-current protection device, nor do they have an output disconnect for the ac output. Therefore, a user-installed circuit breaker should be provided between the UPS output and the load input.
3. Battery servicing should be performed by a qualified Toshiba Representative only.
4. Unauthorized personnel should not service batteries.
5. Contact your nearest Toshiba authorized service center for battery replacement.
Qualified Personnel ONLY!
Qualified Personnel is one that has the skills and knowledge relating to the construction, installation, operation, and maintenance of the electrical equipment and has received safety training on the hazards involved (Refer to the latest edition of NFPA 70E for additional safety requirements).
Qualified Personnel shall:
1. Have read the entire operation manual.
2. Be trained and authorized to safely energize, de-energize, ground, lockout and tag circuits and equipment, and clear faults in accordance with established safety practices.
3. Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves, hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety practices.
4. Be trained in rendering first aid.
5. Be knowledgeable of batteries and the required handling and maintenance precautions.
For further information on workplace safety visit www.osha.gov.
Refer to the Battery System Manual for details on operating and maintaining the battery units for each system.
UPS System’s output is not equipped with an over-current protection device, or an output disconnect for the
AC output; therefore, a circuit breaker should be provided, by the user, between the UPS output and the critical load input. This device should be rated as follows:
Rated Output
15 kVA
Rating
25 kVA
Rating
208/120 VAC 240V, 60A 240V, 90A
220/127 VAC 240V, 50A 240V, 90A
30 kVA
Rating
33 kVA
Rating
240V, 110A 240V, 120A
240V, 110A 240V, 120A
50 kVA
Rating
240V, 175A
240V, 175A
240
380/220
480/277
600
240V, 50A 240V, 80A
480V, 30A 480V, 50A
480V, 25A
600V, 20A
480V, 40A
600V, 35A
240V, 90A 240V, 100A
480V, 60A
480V, 50V
600V, 40A
480V, 70A
480V, 50A
600V, 40A
240V, 175A
480V, 100A
480V, 80A
600V, 70A
10
TOSHIBA
The maximum ambient temperatures in which the Uninterruptible Power System (UPS) should be operated is
104
°F (40°C) or 89° F (32°C) if the battery cabinet is subject to the same ambient.
The nominal battery voltage for all internal battery models is 288VDC. The nominal battery voltage for all external battery models is 288VDC.
An Authorized Toshiba Service Representative who is knowledgeable of batteries and the required precautions should perform service on the batteries. Keep unauthorized personnel away from batteries.
Refer to the Battery System Manual, when scheduling maintenance or battery replacement.
WARNING
Misuse of this equipment could result in injury and equipment damage. In no event will Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that may result from the misuse of this equipment.
CAUTION
Do not dispose of the batteries in a fire. The batteries may explode.
CAUTION
Do not open or mutilate the batteries. Released electrolyte is harmful to the eyes and skin and could also be toxic.
WARNING
Failure to replace a battery before it becomes exhausted may cause the case to crack, possibly releasing electrolytes from inside the battery, and resulting in secondary faults such as odor, smoke, and fire.
7)
8)
9)
10)
11)
5)
6)
1)
2)
3)
4)
12)
WARNING
Personnel knowledgeable of batteries and the required precautions should perform installation and servicing of batteries. Keep
Unauthorized personnel away from the batteries.
WARNING
A qualified service technician must do proper maintenance to the battery system of this unit. This is essential for the safety and reliability of your
UPS system. Refer to service manual.
DANGER
A battery can present a risk of electrical shock and high short circuit current.
The following precautions should be observed when working with batteries.
Verify that the “UPS” is off and that the Input Circuit Breaker is in the off position.
Remove watches, rings or other metal objects.
Use tools with insulated handles to prevent accidental shorts.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Determine if the battery is grounded. If grounded, remove source of the ground.
Contact with any part of a grounded battery can result in an electrical shock.
Electrical shock will be reduced if grounds are removed during installation and maintenance.
Verify circuit polarities prior to making connections.
Disconnect charging source and load prior to connecting or disconnecting terminals.
VRLA batteries contain an explosive mixture of hydrogen gas. Do not smoke; create a flame or a spark in the immediate area of the batteries. This includes static electricity.
Do not attempt to open the batteries in order to add water or sample the specific gravity of the electrolyte. The batteries are valve regulated lead acid type and such servicing is not possible without damaging the battery.
Use proper lifting means when moving batteries and wear all appropriate safety clothing and equipment.
Dispose of lead acid batteries through proper channels in accordance with Local, State and Federal EPA Regulations.
11
TOSHIBA
To be performed by Qualified Personnel only.
1) Verify that the UPS is off and that the power cord is disconnected from the power source.
2) Remove watches, rings or other metal objects.
3) Use tools with insulated handles to prevent inadvertent shorts.
4) Wear rubber gloves and boots.
5) Do not place tools or any metal parts on top of batteries.
6) Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground.
Contact with any part of a grounded battery can result in electrical shock.
The likelihood of shock will be reduced if such grounds are removed prior to installation or maintenance.
INSTRUCTIONS IMPORTANTES CONCERNANT
LA SÉCURITÉ
CONSERVER CES INSTRUCTIONS
Cette notice contient des instructions importantes concernant la sécurté
Un battery puet présenter un risque de choc électrique, de brûlure
ATTENTION
par transfert d’ énergie.
ATTENTION
Por le replacement, utiliser le même nombre de batteries du modéle suivant.
ATTENTION
L’élimination des batteries est règlementèe. Consultar les codes locaux à cet effet.
12
TOSHIBA
1.0 Product Description
1.1 Theory of Operation
An Uninterruptible Power Supply (UPS) is a system that is installed between the commercial power and the critical load. The UPS provides steady AC output power during commercial power fluctuations and interruptions.
During “Normal Operation” the UPS utilizes commercial AC power and removes high voltage spikes and transients caused by switching and faults on the utility. The result of this process is maximum power conditioning and regulation.
If the AC power supplied to the UPS drops below a specified voltage level, the unit's batteries automatically begin supplying power instead of receiving it. This insures that the loads connected to the UPS continue to receive power without interruption. This power is provided for a long enough time so that the load can be shut down in an orderly fashion. This prevents loss of data and possible damage to both hardware and software.
When the AC input power becomes available again, the operation returns to normal and the batteries begin to recharge for the next power interruption.
1.2 Application and Use
Toshiba's 4200FA On-Line, Uninterruptible Power Systems (UPS) provide continuous computer grade isolated AC power in a compact, efficient, high performance unit. The UPS assures safe, reliable operation of critical office equipment, ranging from personal computers to mini-computers to local area networks (LAN). All units feature an audible alarm that sounds if the battery voltage drops below the standard during use. This is an additional aid to help in retaining valuable data and equipment. All units are capable of interfacing to a computer network.
During an electrical power failure the UPS batteries automatically supply DC power to the inverter that supports the load equipment, without interruption. For example, when used to support a computer, the UPS’s back up assures additional time to complete your activity, store data and initiate an orderly shutdown after a power failure occurs.
While commercial power is present, the UPS supplies conditioned power to the load while maintaining its batteries in a charged condition. The UPS protects the connected load against the normal, everyday problems associated with heavy use of raw commercial power, including power sags, surges, signal interference, and spikes. In addition, the models with transformers provide total isolation to reduce the common and normal mode noises. This adds further protection to keep power-line problems from reaching your load, where it can cause equipment to operate erratically, or damage hardware and software.
13
TOSHIBA
2.0 Uncrating/Inspection/Storage/Disposal
2.1 Uncrating the new UPS equipment 15/25/30/33kVA:
Upon receipt of the UPS, a careful inspection for shipping damage should be made. Units shipped within North America are shrink-wrapped, those outside North America are crated.
1. Remove packing material.
1a. For international units, remove the screws that attach the shipping crate to the pallet.
Remove the crate and foam packing material.
2. Unbolt the rails from both the unit and the shipping pallet. Place the rails on the front of the pallet. Use the four
½x3” bolts to secure the rails to the shipping pallet. Attach the rails as shown to the front of the pallet.
3. Place the tie brackets in the slots at the lower end of the ramps. SLOWLY roll the unit down the ramp.
DANGER
TOP HEAVY EQUIPMENT. IMPROPER LIFTING CAN RESULT IN INJURY OR
DEATH. LIFT AND MOVE CAREFULLY AND ONLY WITH ADEQUATE
EQUIPMENT AND TRAINED PERSONNEL. THIS EQUIPMENT WILL TIP OVER
EASILY UNTIL FIXED IN PLACE.
14
TOSHIBA
2.2 Uncrating the new UPS equipment 50kVA:
Upon receipt of the UPS, a careful inspection for shipping damage should be made. Units shipped within North America are shrink-wrapped, those outside North America are crated.
1. Remove packing material.
1a. For international units, remove the screws that attach the shipping crate to the pallet. Remove the crate and foam packing material.
2. Unbolt the rails from both the unit and the shipping pallet. Place the rails on the front of the pallet. Use the six ½x3” bolts to secure the rails to the shipping pallet.
Attach the rails as shown to the rear of the pallet.
2.3
3. Place the tie brackets in the slots at the lower end of the ramps. SLOWLY roll the unit down the ramp.
DANGER
TOP HEAVY EQUIPMENT. IMPROPER LIFTING CAN RESULT IN INJURY OR DEATH.
LIFT AND MOVE CAREFULLY AND ONLY WITH ADEQUATE EQUIPMENT AND TRAINED
PERSONNEL. THIS EQUIPMENT WILL TIP OVER EASILY UNTIL FIXED IN PLACE.
15
TOSHIBA
Inspection of the new UPS equipment
After Uncrating:
1) Check the unit for loose, broken, bent or other damaged parts. If damage has occurred during shipment, keep all original crating and packing materials for return to the shipping agent. The equipment warranty will not apply to units that are damaged during shipment.
2) Check to see that the rated capacity and the model number specified on the nameplate conform to the order specifications.
2.4 Storage of UPS equipment
If the UPS equipment is to be subject to long or short-term storage, the following guidelines should be used.
Avoid:
1) Storage in sites subject to extreme changes in temperature or high humidity.
2) Storage in sites subject to exposure of high levels of dust or metal particles.
3) Storage on inclined floor surfaces or in sites subject to excessive vibration.
Before storing:
1) Charge the system's batteries.
2) Perform a complete system shutdown as described in section 5.18
of this manual.
Storing:
1) Store within a temperature range of - 4° to 104° F (-20° to 40° C).
2) For best results, store the UPS in the original shipping container and place on a wood or metal pallet.
3) The optimum storage temperature is 70° F (21° C). Higher ambient temperatures cause UPS batteries to need recharging more frequently.
4) If stored in an ambient temperature under 68° F (20° C), recharge the batteries every 9 months.
5) If stored in an ambient temperature of 68° to 86° F (20° to 30° C), recharge the batteries every 6 months.
6) If stored in an ambient temperature of 86° to 104° F (30° to 40° C), recharge the batteries every 3 months.
2.5 Disposal
Please contact your state environmental agency for details on proper disposal of electrical components and packaging in your particular area.
ATTENTION
It is ILLEGAL to dump lead-acid batteries in landfills or dispose of
improperly. Please help our Earth by contacting the environmental protection agencies in your area, the battery manufacturer, or call Toshiba toll-free at (800) 231-1412 for more information about recycling batteries.
16
TOSHIBA
3.0 Installation Precautions
Based on the 4200FA UPS external dimensions and the way the outer panels are removed; minimum amounts of unobstructed space around the unit are necessary for ventilation and maintenance access. Figure 3.1 shows the minimum clearances required for proper UPS site installation.
1) Do not install the UPS on an inclined surface, or areas that are subject to frequent vibrations or jolting. This could damage UPS circuits.
2) Do not allow liquids or foreign objects to get inside the UPS.
3) Allow at least 20” (500 mm) on the front side and 6" (152 mm) on the rear and sides of the
UPS unit for air ventilation and maintenance access.
4) Do not install the UPS in a location that is subject to high humidity. Also, do not install the unit in areas that are exposed to direct sunlight, or contaminated areas subject to high levels of airborne dust, metal particles, or flammable gasses.
5) Verify the ventilation and air conditioning system at the site is capable of removing the heat generated by the UPS.
Ambient temperature range for operating the UPS is 32° – 104°F (0° – 40°C); 77°F (25°C) is the
recommended operating temperature for
maximum battery life.
6) Avoid installation near sources of electrical noise. Always make sure that the unit's ground is intact to prevent electrical shock and help prevent electrical noise.
7) This UPS generates and radiates radiofrequency energy during operation. Although
RFI noise filters are installed inside the unit there is no guarantee that the UPS will not influence some sensitive devices, which are operating in near proximity. If such interference occurs, the UPS should either be installed farther away from the affected equipment and/or powered from a different source than the affected equipment.
LEFT
6” (152mm)
REAR
6” (152mm)
FRONT
20” (500mm)
RIGHT
6” (152mm)
17
TOSHIBA
Before connecting the UPS to a power source; move the Circuit Breakers (ON/OFF), on the front panel, to the OFF position and move the operation STOP/RUN key switch, on the front panel, to the STOP position.
1) The UPS should not be powered up until the entire operation manual has been reviewed, and understood.
2) The input power source voltage must be within +10% to -15% (to start UPS) of the rated input voltage. The input frequency must be within the rated input frequency range.
Voltages and frequencies outside of the permissible range may cause internal protection devices to activate.
3) The UPS should not be used with a load whose rated input is greater than the rated UPS output.
4) Do not use the UPS to provide power to motors that require high starting current or a long starting time such as vacuum cleaners and machine tools.
5) Do not insert metal objects or combustible materials in the unit's ventilation slots.
6) Do not place, hang, or paste any objects on the top or on the exterior surfaces of the UPS.
18
TOSHIBA
4.0 UPS Connections
4.1 Power Connections 15/25/30/33 kVA with Internal Batteries
The following illustrates the wiring connections from the power distribution panel (not part of the UPS) to the terminal block of the 15/25/30/33 kVA UPS Models
4.1.1
CUSTOMER-PROVIDED AC DISTRIBUTION PANEL
TB1
INPUT GROUND RESISTANCE
LESS THAN 10 OHMS
Optional Bypass Input:
3-phase, 3-Wire
*208V requires 3-phase,
4-Wire Wye
TB4
19
TO BATTERY SYSTEM GND
TOSHIBA
Power Connections 15/25/30/33kVA with Internal Transformer
The following illustrates the wiring connections from the power distribution panel (not part of the UPS) to the terminal block of the 15/25/30/33 kVA UPS Models
CUSTOMER-PROVIDED AC DISTRIBUTION PANEL
TB1
INPUT GROUND RESISTANCE
LESS THAN 10 OHMS
Optional Bypass Input:
3-Phase, 3-Wire
*208V requires 3-Phase,
4-Wire Wye
TB4
20
TOSHIBA
4.1.2 Recommended Wire Size and Torque Requirements
UPS Input and Output Terminals
Minimum Wire Size and Torque Requirements
UPS Input and Output Terminals 15/25/30/33 kVA
(USE MINIMUM 75° C INSULATED COPPER WIRING)
Phase: (A) (B) (C) 15 kVA 25 kVA 30/33 kVA
Input: (H1) (H2) (H3)
AWG Torque AWG Torque AWG
Torque
208
220
240
380
400
415
480
600
10 35 in-lbs. 8 51 in-lbs.
10
10 35 in-lbs. 8 51 in-lbs.
10
35 in-lbs.
35 in-lbs.
8
8
51 in-lbs.
51 in-lbs.
6
6
6
6
10 35 in-lbs. 10 35 in-lbs. 10
All wire sizes are per the NEC. Maximum Wire Size is 2 AWG.
51 in-lbs.
51 in-lbs.
51 in-lbs.
51 in-lbs.
35 in-lbs.
Output:
(L1) (L2) (L3)
(N)
AWG
(L1)-
(L3)
15 kVA
AWG
(N)
Torque
(inch-lbs.)
(L1)-(L3) (N)
AWG
(L1)-
(L3)
25 kVA
AWG
(N)
Torque
(inch-lbs.)
(L1)-(L3) (N)
AWG
(L1)-
(L3)
30/33 kVA
AWG
(N)
Torque
(inch-lbs.)
(L1)-(L3) (N)
240 8 N/A 51 N/A 4 N/A 51 N/A 2 N/A 87 N/A
600 10 N/A 35
Neutral Conductors are rated @ 1.73 or 200% of phase conductors, per NEC. Maximum Wire Size is 2
AWG.
15 kVA 25 kVA 30/33kVA
Input/ Output (GND)
AWG Torque AWG
Torque
AWG Torque
35 in-lbs. 8 51 in-lbs. 6 51 in-lbs. (G) 10
Maximum Wire Size is 2 AWG.
Minimum Wire Size and Torque Requirements
UPS Optional Separate Bypass Input “TB4” 15 / 25kVA
(USE MINIMUM 75° C INSULATED COPPER WIRING)
Phase: (A) (B) (C) 15 kVA 25 kVA 30/33 kVA
Input: (H1) (H2) (H3)
AWG Torque AWG
Torque AWG
Torque
208
220
240
380
400
10 35 in-lbs. 8 51 in-lbs.
10 35 in-lbs. 8 51 in-lbs.
6
6
415
480
10
10
35 in-lbs.
35 in-lbs.
8
8
51 in-lbs.
51 in-lbs.
6
6
600 10 35 in-lbs. 10 35 in-lbs. 10
Maximum Wire Size is 2 AWG.
51 in-lbs.
51 in-lbs.
51 in-lbs.
51 in-lbs.
35 in-lbs.
21
TOSHIBA
The following illustrates the proper cable routing that should be followed during the power connection process of the 15/25/30/33 kVA.
CONDUIT MOUNTING PANEL INPUT CONDUIT OUTPUT CONDUIT BATTERY CONDUIT
Note:
1) Input and Output conductors shall be installed in separate conduits, and installed in accordance with the latest edition of NEC and the Local Authority having jurisdiction.
2) Battery conductors shall be installed in a separate conduit and be of low resistance type.
22
TOSHIBA
4.2 Control Circuit and External Battery Interface Connections 15/25/30/33 kVA
The following illustrates the wiring connections of the Control Circuits, and Battery Interface
Circuits.
(3) Fault
Battery Connection
(+) Positive
(-) Negative
(3) Battery Shunt Trip
(4) Battery Shunt Trip
(5) Battery Aux.
(6) Battery Aux.
(7) P24A3
(9) P24A3
(10) Remote Stop
(11) Bypass
(12) GND
(13) EPO
(14) EPO
4.2.1 Recommended Wire Size and Torque Requirements
UPS Control and Battery Interface 15/25/30/33kVA
Minimum Wire Size and Torque Requirements
UPS Control and Battery Interface Circuits
USE MINIMUM 75° C COPPER WIRING
15/25/30/33 kVA
TERMINAL
(TERMINAL #)
AWG
TIGHTENING
TORQUE
UPS CONTROL CIRCUITS
(1-24)*
BATTERY CONTROL
CIRCUITS (3-6)*
BATTERY
(+/-)
*Indicates Class 1 wiring methods is to be used. Maximum Wire Size for Control Circuits is 12 AWG.
Maximum for Battery is 2 AWG.
23
TOSHIBA
4.3 Power Connections 50 kVA
The following illustrates the wiring connections from the power distribution panel (not part of the UPS) to the terminal block of the 50 kVA UPS Model
(H1) (H2) (H3) (N) (L1) (L2) (L3) (N) (+) (-)
INPUT: 3-phase, 3-wire
208V requires 3-phase, 4-wire
OUTPUT: 3-phase (4-wire)
(H1) (H2) (H3) (N)
Optional: Bypass Input:
3-phase, 3-wire
208V requires 3-phase,
4-wire
24
TOSHIBA
4.3.1 Recommended Wire Size and Torque Requirements For UPS Input and Output Terminals
Minimum Wire Size and Torque Requirements
UPS Input and Output Terminals 50 kVA
(USE MINIMUM 75° C INSULATED COPPER WIRING)
(H1) (H2) (H3)
INPUT:
AWG NEUTRAL
AWG
(L1)(L2)(L3)
OUTPUT:
AWG NEUTRAL
AWG
250MCM
4/0
N/A
1/0
1/0
1
2
N/A
Tightening
Torque
200 in-lbs.
200 in-lbs.
200 in-lbs.
200 in-lbs.
200 in-lbs.
200 in-lbs.
200 in-lbs.
200 in-lbs.
All wire sizes are per the NEC. Maximum Wire Size for Input and Output is 1/0 AWG.
Neutral Conductors are rated @ 1.73 or 200% of phase conductors, per NEC. Maximum Wire Size for Neutral is 250MCM.
Input/ Output (GND)
AWG
50 kVA
Tightening Torque
Battery (+) / (-)
(+) (-)
AWG
250MCM
50 kVA
Tightening Torque
200 in-lbs.
Maximum Wire Size for Battery is 250MCM.
Minimum Wire Size and Torque requirements
UPS Optional Bypass Input Terminals TB4 50 kVA
(USE MINIMUM 75° C INSULATED COPPER WIRING)
Phase: (A) (B) (C)
Input: (H1) (H2) (H3)
AWG
50 kVA
NEUTRAL AWG Tightening Torque
220 1/0 in-lbs.
200 in-lbs.
415 4 1 200
480 6 2 200
Maximum Wire Size for Input is 1/0 AWG. Maximum Wire Size for Neutral is 250MCM.
25
TOSHIBA
4.3.2 Power Connection Cable Routing
The following illustrates the proper cable routing that should be followed during the power connection process for the 50kVA.
Removable cover for conduit access
Bottom Conduit Entry
26
TOSHIBA
4.4 Control Circuit and External Interface Connections
The following illustrates the wiring connections of the Control Circuits, and Battery Interface
Circuits for the 50kVA.
(3) Fault
(3) Battery Shunt Trip
(4) Battery Shunt Trip
(5) Battery Aux.
(6) Battery Aux.
(7) P24A3
(9) P24A3
(10) Remote Stop
(11) Bypass
(12) GND
(13) EPO
(14) EPO
4.4.1 Recommended Wire Size and Torque Requirements
UPS Control and Battery Interface 50 kVA
Minimum Wire Size and Torque Requirements
UPS Control and Battery Interface Circuits
USE MINIMUM 75° C COPPER WIRING
TERMINAL
(TERMINAL #)
50 kVA
TIGHTENING
TORQUE AWG
UPS CONTROL CIRCUITS
(1-24)*
BATTERY CONTROL
CIRCUITS (3-6)*
*Indicates Class 1 wiring methods is to be used. Maximum Wire Size is 12 AWG.
27
TOSHIBA
4.5.1 Remote Contact
This interface is a standard feature and is available as dry switch contacts through a DB9 male connector located on the front of the UPS. The following schematic shows the contact state and pin assignment for each signal and the associated DB9 connector pin-out.
5 System Common
6 Bypass Active
DB9 Male Connector Outline
(Facing Connector)
7 Battery Voltage Low
8 UPS On-line
9
4
Battery Discharge
1 2 3 4 5
6 7 8 9
1
2
Fault Signal Detect
Notes:
1) Pin “switches” are shown in their inactive states. Example: (if battery voltage is low, pin 7 will be connected to System Common).
2) Contacts are rated at 30 VDC, 0.1 amps; 125 VAC, 3 amps.
3) Pin number “3” is not used.
28
TOSHIBA
4.5.2 RS-232C
The RS-232C serial communication interface is available through a DB9 female connector located on the backside of the UPS. This interface allows control of the UPS from a computer network running Toshiba RemotEyeII
™ software. The computer and the UPS are connected through a serial RS-232C communication port. The available data from the UPS, via the RS-
232C communication link, is shown below:
Operating Conditions
Input Voltage
Input Frequency
Battery Voltage
Output Voltage
Output Frequency
Output Current
UPS Operating Status
(Described as “yes or “no”)
Fault Details
(Described as “occurred” or “not occurred”)
Utility Power OK
Low Battery Voltage Detected
UPS in BYPASS Mode
UPS in NORMAL Mode
Input and Output Frequency Synchronized
UPS FAULT Occurred
DC Bus Over-Current
DC Bus Over-Voltage
DC Bus Under-Voltage
Input Over-Current
Overheat
Overload Being Timed
Overload (allowable time exceeded)
Output Over-Voltage (during Normal Mode)
Output Under-Voltage (during Normal Mode)
The connector pin assignment and female connector outline are illustrated below.
DB9 Female Connector Outline
(facing connector)
Pin I/O Symbol Description
1 This pin is not used
3 Output TXD Transmit
4 Output DTR Data Terminal Ready
5 - SG Signal
6 Input DSR Data Set Ready
7
8
9
Output
Input
RTS
CTS
Request To Send
Clear To Send
This pin is not used
5
9
4 3 2 1
8 7 6
4.5.3 UPS Shutdown (via RS-232C)
When the UPS is operating from its internal batteries, a 'shutdown' order can be sent to the
UPS instructing it to turn OFF after a user-specified amount of time. This function can allow you to stop discharging the UPS batteries after an orderly system shutdown has been completed. The UPS can be programmed to turn OFF up to 8 minutes after the 'shutdown' command is given. This command can be cancelled before the specified time has elapsed by following the directions listed on the RS-232C screen.
29
TOSHIBA
5.0 Technical Data
Input
Battery
Output
5.1 4200FA 15 / 25kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries
Model Number
T42F3F150XAMBN
T42F3F150##MBN
T42F3F250XAMBN
T42F3F250##MBN
Rated Output Capacity
External Dimensions
W x D x H (mm)
Rated Voltage
Voltage Variation
Rated Frequency
Input Cables required
Dual Input Option Cables required
* Power Factor
Required Input kVA
Walk-in Function
Inrush Current
Current Limit
* Harmonic Currents
DC Nominal (Voltage Range)
Float Charge (Regulation)
Ripple Voltage
**Rated Back-up Time
Rated Charge Current
Rated Voltage
Rated Current
Rated Power Factor
Output Cables Required
Voltage Regulation (phase-phase)
Voltage Adjustment Range
Phase Displacement
Rated Frequency
Frequency Regulation
Frequency Synchronous
Frequency Slew Rate
Voltage Transients
(Recovery time: 50 msec)
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Neutral Line Conductor
Harmonic Voltage Distortion
15 kVA 25 kVA
20” x 36.25” x 59.85”
508mm x 90.75mm x 1520.2mm
208 VAC
+10% to -30%; (-15% to -30%)
50 / 60 Hz
3
∅; 4 Wire + GND
3
∅; 4 Wire
Greater than 0.98 when in inverter mode
16.5 27.5
From 20% to 100% over 5 seconds
Less than 8 times the rated current under synchronous operation
115% maximum
Less than 3% THD
288 VDC (216 to 332 VDC)
324.0 VDC (
± 2%)
2% R.M.S.
7 min at full load 5 min at full load
4.0 Amps
208 / 120 VAC
42.0 Amps 69.5 Amps
0.8 lagging
3
∅; 4 Wire + GND
± 2% (0-100% balanced load); ± 3% (0-100% unbalanced load)
± 5V Manually from the key pad
± 2° (0–100% balanced load); ± 4° (unbalanced load)
50 / 60 Hz
± 0.1% in free running mode
± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.) switch selectable by qualified technician
1 Hz/s to 3Hz/s (in 0.5 Hz steps)
± 5% (100% load step change); ± 3% (loss or return of input voltage);
± 8% (transfer of bypass to inverter)
125% 90 sec; 150% 30 sec
1000% 10 msec; 125% 10 min.
2.5–3.0 within the kW range
1.73 (200%) times line rating
1.5% max (linear load)
Inrush Current protection Automatic Transfer to bypass, then retransfer to inverter
Environment Efficiency AC/DC/AC: 86%; DC/AC: 90%
Heat loss to be removed 5733 BTU/hr (1445kcal/hr) 9554 BTU/hr (2407kcal/hr)
Audible Noise
Operating Temperature
Operating Humidity
Altitude ***
60dB (A) at 1 meter from the front of the unit
32
°–104° F (0°–40° C); optimal temperature is 77° F (25° C)
30–90% RH (non condensing)
Less than 2000 meters
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).
30
TOSHIBA
5.2 4200FA 15/ 25kVA w/Internal Transformer
T42#3*150#AMXN T42#3*250#AMXN
Rated Output Capacity
Input
Battery
Output
Environment
External Dimensions
W x D x H (mm)
Rated Voltage
Voltage Variation
Rated Frequency
Input Cables Required
Dual Input Option Cables required
* Power Factor
Required Input kVA
Walk-in Function
Inrush Current
Current Limit
* Harmonic Currents
DC Nominal (Voltage Range)
Float Charge (Regulation)
Ripple Voltage
**Rated Back-up Time
Rated Charge Current
Rated Voltage
Rated Current
Rated Power Factor
Output Cables Required
Voltage Regulation (phase-phase)
Voltage Adjustment Range
Phase Displacement
Rated Frequency
Frequency Regulation
Frequency Synchronous
Frequency Slew Rate
Voltage Transients
(Recovery time: 50 msec)
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Neutral Line Conductor
Harmonic Voltage Distortion
Inrush Current protection
15 kVA 25 kVA
20” x 36.25” x 59.85”
508mm x 90.75mm x 1520.2mm
208; 220; 240; 380; 400; 415; 480; 600 VAC
(Determined by Input Transformer internal to the unit)
+10% to -30%; (-15% to -30%)
50/60 Hz
3
∅; 3 Wire + GND
3
∅; 4 Wire
Greater than 0.98 when in inverter mode
16.5 27.5
From 20% to 100% over 5 seconds
Less than 12 times the rated current under synchronous operation
115% maximum
Less than 3% THD
288 VDC (216 to 332 VDC)
324.0 VDC (
± 2%)
2% R.M.S.
Refer to Battery System Manual
10.0 Amps
(Determined by Output Transformer internal to the unit)
VA / Nominal Output Voltage / 1.73
0.8 lagging
3
∅; 4 Wire + GND
± 5% (0–100% balanced load); ± 6% (0-100% unbalanced load)
± 5V Manually from key pad
± 2° (0–100% balanced load); ± 4° (unbalanced load)
50 / 60 Hz
± 0.1% in free running mode
± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.) switch selectable by qualified technician
1 Hz/s to 3Hz/s (in 0.5 Hz steps)
± 5% (100% load step change); ± 3% (loss or return of input voltage);
± 8% (transfer of bypass to inverter)
125% 90 sec; 150% 30 sec
1000% 10msec; 125% 10 min.
2.5–3.0 within the kW range
1.73 (200%) times line rating
1.5% max (linear load)
Automatic Transfer to bypass, then retransfer to inverter
Efficiency AC/DC/AC: 84%; DC/AC: 88%
Heat loss to be removed
Audible Noise
Operating Temperature
Operating Humidity
Altitude ***
60dB (A) at 1 meter from the front of the unit
32
°–104° F (0°–40° C); optimal temperature is 77° F (25° C)
30– 90% RH (non condensing)
Less than 2000 meters
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).
31
TOSHIBA
Input
Battery
Output
5.3 4200FA 30 / 33kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries
Model Number
T42F3F300XAMBN
T42F3F300##MBN
T42F3F330XAMBN
T42F3F330##MBN
Rated Output Capacity
W x D x H (mm)
Rated Voltage
Voltage Variation
Rated Frequency
Input Cables required
Dual Input Option Cables required
* Power Factor
Required Input kVA
Walk-in Function
Inrush Current
Current Limit
* Harmonic Currents
DC Nominal (Voltage Range)
Float Charge (Regulation)
Ripple Voltage
**Rated Back-up Time
Rated Charge Current
Rated Voltage
Rated Current
Rated Power Factor
Output Cables Required
Voltage Regulation (phase-phase)
Voltage Adjustment Range
Phase Displacement
Rated Frequency
Frequency Regulation
Frequency Synchronous
Frequency Slew Rate
Voltage Transients
(Recovery time: 50 msec)
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Neutral Line Conductor
Harmonic Voltage Distortion
Inrush Current protection
30 kVA 33 kVA
20” x 36.25” x 59.85”
508mm x 90.75mm x 1520.2mm
208 VAC
+10% to -30%; (-15% to -30%)
50 / 60 Hz
3
∅; 4 Wire + GND
3
∅; 4 Wire
Greater than 0.98 when in inverter mode
33.0 36.0
From 20% to 100% over 5 seconds
Less than 8 times the rated current under synchronous operation
115% maximum
Less than 3% THD
288 VDC (216 to 332 VDC)
324.0 VDC (
± 2%)
2% R.M.S.
4 min at full load 3.5 min at full load
4.0 Amps
208 / 120 VAC
83.4 Amps 90 Amps
0.8 lagging
3
∅; 4 Wire + GND
± 2% (0–100% balanced load); ± 3% (0–100% unbalanced load)
± 5V Manually from the key pad
± 2° (0–100% balanced load); ± 4° (unbalanced load)
50 / 60 Hz
± 0.1% in free running mode
± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.) switch selectable by qualified technician
1 Hz/s to 3Hz/s (in 0.5 Hz steps)
± 5% (100% load step change); ± 3% (loss or return of input voltage);
± 8% (transfer of bypass to inverter)
125% 90 sec; 150% 30 sec
1000% 10 msec; 125% 10 min.
2.5–3.0 within the kW range
1.73 (200%) times line rating
1.5% max (linear load)
Automatic Transfer to bypass, then retransfer to inverter
Environment Efficiency AC/DC/AC: 86%; DC/AC: 90%
Heat loss to be removed 9108 BTU/hr (2295kcal/hr) 9829 BTU/hr (2477kcal/hr)
Audible Noise
Operating Temperature
Operating Humidity
Altitude ***
60dB (A) at 1 meter from the front of the unit
32
°–104° F (0°–40° C); optimal temperature is 77° F (25° C)
30–90% RH (non condensing)
Less than 2000 meters
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).
32
TOSHIBA
5.4 4200FA 30/ 33kVA w/Internal Transformer
T42#3*300#AMXN T42#3*330#AMXN
Rated Output Capacity
Input
Battery
Output
Environment
External Dimensions
W x D x H (mm)
Rated Voltage
Voltage Variation
Rated Frequency
Input Cables Required
Dual Input Option Cables required
* Power Factor
Required Input kVA
Walk-in Function
Inrush Current
Current Limit
* Harmonic Currents
DC Nominal (Voltage Range)
Float Charge (Regulation)
Ripple Voltage
**Rated Back-up Time
Rated Charge Current
Rated Voltage
Rated Current
Rated Power Factor
Output Cables Required
Voltage Regulation (phase-phase)
Voltage Adjustment Range
Phase Displacement
Rated Frequency
Frequency Regulation
Frequency Synchronous
Frequency Slew Rate
Voltage Transients
(Recovery time: 50 msec)
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Neutral Line Conductor
Harmonic Voltage Distortion
Inrush Current protection
30 kVA 33 kVA
20” x 36.25” x 59.85”
508mm x 90.75mm x 1520.2mm
208; 220; 240; 380; 400; 415; 480; 600 VAC
(Determined by Input Transformer internal to the unit)
+10% to -30%; (-15% to -30%)
50/60 Hz
3
∅; 3 Wire + GND
3
∅; 4 Wire
Greater than 0.98 when in inverter mode
34 37.5
From 20% to 100% over 5 seconds
Less than 12 times the rated current under synchronous operation
115% maximum
Less than 3% THD
288 VDC (216 to 332 VDC)
324.0 VDC (
± 2%)
2% R.M.S.
Refer to Battery System Manual
10.0 Amps
(Determined by Output Transformer internal to the unit)
VA / Nominal Output Voltage / 1.73
0.8 lagging
3
∅; 4 Wire + GND
± 5% (0-100% balanced load); ± 6% (0-100% unbalanced load)
± 5V Manually from key pad
± 2° (0–100% balanced load); ± 4° (unbalanced load)
50 / 60 Hz
± 0.1% in free running mode
± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.) switch selectable by qualified technician
1 Hz/s to 3Hz/s (in 0.5 Hz steps)
± 5% (100% load step change); ± 3% (loss or return of input voltage);
± 8% (transfer of bypass to inverter)
125% 90 sec; 150% 30 sec
1000% 10msec; 125% 10 min.
2.5–3.0 within the kW range
1.73 (200%) times line rating
1.5% max (linear load)
Automatic Transfer to bypass, then retransfer to inverter
Efficiency AC/DC/AC: 84%; DC/AC: 88%
Heat loss to be removed 11174 BTU/hr (2815kcal/hr) 12062 (3038kcal/hr)
Audible Noise
Operating Temperature
Operating Humidity
Altitude ***
60dB (A) at 1 meter from the front of the unit
32
°–104° F (0°–40° C); optimal temperature is 77° F (25° C)
30–90% RH (non condensing)
Less than 2000 meters
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).
33
TOSHIBA
5.5 4200FA 50kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries
Input
Battery
Output
Environment
Model Number
Rated Output Capacity
W x D x H (mm)
Rated Voltage
Voltage Variation
Rated Frequency
Input Cables Required
Dual Input Option Cables required
* Power Factor
Required Input kVA
Walk-in Function
Inrush Current
Current Limit
* Harmonic Currents
DC Nominal (Voltage Range)
Float Charge (Regulation)
Ripple Voltage
**Rated Back-up Time
Rated Charge Current
Rated Voltage
Rated Current
Rated Power Factor
Output Cables Required
Voltage Regulation (phase-phase)
Voltage Adjustment Range
Phase Displacement
Rated Frequency
Frequency Regulation
Frequency Synchronous
Frequency Slew Rate
Voltage Transients
(Recovery time: 50 msec)
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Neutral Line Conductor
Harmonic Voltage Distortion
T42F3F500XAMBN
T42F3F500##MBN
50 kVA
35.6” X 38.9” X 59.4”
(904mm x 970mm x 1509mm)
208 VAC
+10% to -30%; (-15% to -30%) ****
50 / 60 Hz
3
∅; 4 Wire + GND
3
∅; 4 Wire + GND
Greater than 0.98 when in inverter mode
55.0
From 20% to 100% over 5 seconds
Less than 12 times the rated current under synchronous operation
115% maximum
Less than 3% THD
288 VDC (216 to 332 VDC)
324.0 VDC (
± 2%)
2% R.M.S.
5 min. at full load
11.5 Amps
208 / 120 VAC
138.9 Amps
0.8 lagging
3
∅; 4 Wire + GND
± 2% (0–100% balanced load); ± 3% (0–100% unbalanced load)
± 5V Manually from key pad
± 2° (0–100% balanced load); ± 4° (unbalanced load)
50 / 60 Hz
± 0.1% in free running mode
± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.) switch selectable by qualified technician
1 Hz/s to 3Hz/s(in 0.5 Hz steps)
± 5% (100% load step change); ± 3% (loss or return of input voltage);
± 8% (transfer of bypass to inverter)
125% 90 sec; 150% 30 sec
1000% 10 msec; 125% 10 min.
2.5–3.0 within the kW range
1.73 (200%) times line rating
1.5% max (linear load)
Inrush Current protection Automatic Transfer to bypass, then retransfer to inverter
Efficiency AC/DC/AC: 88%; DC/AC: 89%
Heat loss to be removed
Audible Noise
Operating Temperature
Operating Humidity
Altitude ***
17,743BTU/hr (4,472kcal/hr)
~65dB @ 1 meter from the front of the unit
32
°–104° F (0°–40° C); optimal temperature is 77° F (25° C)
30–90% RH (non condensing)
Less than 2000 meters
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).
(****) Prolonged operation at this level requires some derating of the output capacity.
34
TOSHIBA
5.6 4200FA 50kVA w/Internal Transformer
T42#3*500#AMXN
Rated Output Capacity
External Dimensions
W x D x H (mm)
Input
Rated Voltage
Voltage Variation
Rated Frequency
Input Cables Required
Dual Input Option Cables required
* Power Factor
Required Input kVA
Walk-in Function
Inrush Current
Current Limit
* Harmonic Currents
Battery
Output
Environment
DC Nominal (Voltage Range)
Float Charge (Regulation)
Ripple Voltage
**Rated Back-up Time
Rated Charge Current
Rated Voltage
Rated Current
Rated Power Factor
Output Cables Required
Voltage Regulation (phase-phase)
Voltage Adjustment Range
Phase Displacement
Rated Frequency
Frequency Regulation
Frequency Synchronous
Frequency Slew Rate
Voltage Transients
(Recovery time: 50 msec)
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Neutral Line Conductor
Harmonic Voltage Distortion
Inrush Current protection
50 kVA
35.6” X 38.9” X 59.4”
(904mm x 970mm x 1509mm)
208 VAC
+10% to -30%; (-15% to -30%) ****
50 / 60 Hz
3
∅; 3 Wire + GND
3
∅; 4 Wire + GND
Greater than 0.98 when in inverter mode
55.0
From 20% to 100% over 5 seconds
Less than 12 times the rated current under synchronous operation
115% maximum
Less than 3% THD
288 VDC (216 to 332 VDC)
324.0 VDC (
± 2%)
2% R.M.S.
Refer to Battery System Manual
11.5 Amps
(Determined by Output Transformer internal to the unit)
VA / Nominal Output Voltage / 1.73
0.8 lagging
3
∅; 4 Wire + GND
± 2% (0–100% balanced load); ± 3% (0–100% unbalanced load)
± 5V Manually from key pad
± 2° (0–100% balanced load); ± 4° (unbalanced load)
50 / 60 Hz
± 0.1% in free running mode
± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.) switch selectable by qualified technician
1 Hz/s to 3Hz/s(in 0.5 Hz steps)
± 5% (100% load step change); ± 3% (loss or return of input voltage);
± 8% (transfer of bypass to inverter)
125% 90 sec; 150% 30 sec
1000% 10 msec; 125% 10 min.
2.5–3.0 within the kW range
1.73 (200%) times line rating
1.5% max (linear load)
Automatic Transfer to bypass, then retransfer to inverter
Efficiency AC/DC/AC: 88%; DC/AC: 89%
Heat loss to be removed 17,743BTU/hr (4,472kcal/hr)
Audible Noise
Operating Temperature
Operating Humidity
Altitude ***
~65dB @ 1 meter from the front of the unit
32
°–104° F (0°–40° C); optimal temperature is 77° F (25° C)
30–90% RH (non condensing)
Less than 2000 meters
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).
(****) Prolonged operation at this level requires some derating of the output capacity.
35
TOSHIBA
Operating the UPS
5.7 Operating the UPS
5.7.1 AC Input Mode (Normal Operation)
The following illustration shows circuit power flow when the UPS is operating normally in the
AC Input Mode. The rectifier includes a boost chopper circuit that converts the AC input power into DC power. The boost chopper circuit maintains a constant voltage with current limiting abilities for charging the batteries. The rectifier supplies a DC voltage of the proper level to the inverter section. The inverter section generates a high quality sine wave output voltage. The batteries are maintained in a constantly charged state when the UPS is in the “Normal
Operation Mode.”
MBS
Input
Power
Input
Power
Isolation
Transformer
Model
Bypass
Converter Inverter
MCCB
Output
Power
Chopper
Batteries
Power flow in AC Input Mode
If the UPS unit is severely overloaded or develops an internal fault, power flow is automatically switched from the main circuit to the Bypass circuit. Power flow through the bypass is shown in the following illustration. This changeover occurs automatically in less than 4 milliseconds in phase (Make-Before-Break). If the power flow is transferred to the Bypass circuit because of an overload and that overload condition ends within a specified period of time, then the power flow will "re-transfer" to the AC Input Mode (Normal Operation) automatically. If the power
flow is transferred to the Bypass circuit due to a fault condition, then the power flow must be transferred manually from the UPS's Bypass circuit back to the Inverter circuit
after repairing the fault (see "Start-up Procedure"). If the power flow is transferred to the
Bypass circuit due to an overload condition, then the power flow will automatically transfer from the UPS's Bypass circuit back to the Inverter circuit after removing the
overload (see "Overload Operation").
MBS
Isolation
Transformer
Model
Bypass
Converter Inverter
MCCB
Output
Power
Chopper
Batteries
Power flow in Bypass mode
5.7.2.1 Bypass Mode for Optional Alternate Input Models
36
TOSHIBA
Bypass
Power
Isolation
Transformer
Model
MBS
Bypass
Converter Inverter
MCCB
Input
Power
Output
Power
Chopper
Batteries
Input
Power
Power flow in Bypass mode for the Alternate Input Models
5.7.3 Battery Backup Mode
The following illustration shows power flow during the battery backup mode. When commercial AC power failures occur, the batteries instantly begin supplying DC voltage to the main inverter circuit. This circuit inverts (hence; Inverter) the DC power into AC power. The AC power is available at the output. This back-up process will continue until the battery voltage drops below a specific minimum level. When this occurs, the batteries will stop supplying power to the load. This minimum level is the rated minimum voltage (V min).
MBS
Bypass
Isolation
Transformer
Model
MCCB Converter Inverter
Output
Power
Chopper
Batteries
Power flow in battery backup mode
37
TOSHIBA
5.8 Battery Backup Time and Discharge Process
The UPS system, when used in conjunction with a Toshiba designed Battery System, is designed to provide several minutes of back-up time (Refer to the Battery System Manual for back-up times). These times are valid when the unit is operating under full load. When these models are operating at half load, the batteries can provide approximately 2 times the specified value. The exact length of these times will depend on the UPS model used, condition of the batteries, amount and type of load, temperature and other variables.
CAUTION
Contact Toshiba when using other than Toshiba designed Battery Systems to determine proper compliance. Using other systems could void Warranty and or
Safety Certifications.
The following illustration graphically shows the battery discharge process at full load conditions.
5.9 Battery Low Voltage Tolerances
Excessive discharge will cause the UPS battery voltage to drop bellow tolerable levels. The chart shown below lists the voltage level at which each UPS unit's low-voltage alarm will sound, and also at what level the low-voltage condition will cause the unit to automatically shut down.
Models
Nominal Voltage
Alarm Voltage
Shutdown Voltage min.
15/25/30/33/50 kVA
288 VDC
252 VDC
216 VDC
38
TOSHIBA
The illustration below shows a graphical representation of the UPS battery recharge process after a full discharge.
The recharge process usually consists of three steps. During the first step, the charging current is maintained at approximately 4.0 amperes for the 15/25/30/33kVA and approximately 11.5 amperes for the 50 kVA. This current is the maximum value that can be used to charge the batteries (for minimal recharge time) while assuring safety and long battery life. In the second step, constant-voltage control starts and current gradually decreases as the batteries charge to their normal fully charged state. In the third step, a slight "trickle" current continues to flow into the batteries to keep them fully charged and "floating" at the normal DC Voltage level. A full recharge usually requires approximately 24-72 hours (90% recharge in 10 hours) after a complete discharge.
The following chart shows the rated maximum and minimum battery voltages, and the charge current for each of the sizes while the unit is maintained in a 75°F (24
° C) ambient.
Rated Battery Voltages
Model
V float
V min
I charge
15/25/30/33
Internal
Battery
324.0 VDC
252 VDC
4.0 A
Internal
Transformer
324.0 VDC
252 VDC
10.0 A
Internal
Battery
50kVA
Internal
Transformer
324.0 VDC
252 VDC
11.5 Amps
39
TOSHIBA
5.11 Front Panel Layout (All Units)
Refer to the following illustration for the entire UPS front panel operating procedures.
4-line liquid crystal display screen (see
Section 6.9)
Emergency power off switch
(see Section 6.6)
STOP/RUN key switch line-1 line-2 line-3 line-4
AC IN INV BYP BATT
FAULT
MONI
BATT F1
IN
BUZZ
STOP
MENU ENTER
RESET
OUT
BATT
TEST
EPO
STOP
UPS
RUN
4200 Series
ON-LINE
UNINTERRUPTIBLE POWER SYSTEM
Green light emitting diodes (LED)
(see Section 6.8)
12-key Data entry keypad (see
Section 6.14)
Red light emitting diode (LED)
(see Section 6.8)
5.12 EPO (Emergency Power Off) Function
These units are equipped with terminals for receiving an EPO (Emergency Power Off) "closed contact" switch command from two locations: (1) a remote location and (2) from a front panel mounted EPO switch. This safety feature enables quick shutdown of the UPS AC output and battery circuits. Usually the EPO switch is installed in a central location that is easily accessible to personnel concerned with the operation of the UPS and the equipment connected to it. The EPO function is initiated by pressing the switch to the closed "shutdown" position. The effect of using the EPO switch is the same whether the UPS is in the AC Input
Mode, Battery Backup Mode, or the Bypass Mode. See 'EMERGENCY OFF' screen. The following figure shows the UPS condition after application of the EPO switch. Use the Start-
up Procedure for restarting the unit.
MBS
Input
Transformer
Model
TRIPPED
MCCB
OFF
Converter
Bypass
OFF
Inverter
Input
Power
Output
Power
OFF
Chopper
Batteries
5.13 Audible Alarm Functions
Audible alarms will sound when the UPS is in the Battery Backup Mode, has a fault, is at the low battery voltage, or is in an overload condition. The following chart shows the audible alarm
40
TOSHIBA
pattern duration for each condition. Time intervals are shown in seconds. The audible alarm can be silenced, by pressing “BUZZ STOP” on the keypad.
Condition Audible pattern
UPS in Battery Backup Mode
(Battery Voltage 100-92%)
7 S 1 S
UPS Low Battery
(Battery Voltage < 92%)
1 S 1 S
Overload
.5 S .5 S
Fault
.5 S .5 S
41
TOSHIBA
5.14 LED (Light Emitting Diode) Functions
The following list describes the conditions necessary for each LED lamp to be "on."
AC IN
GREEN
This green LED lamp is "on" when the UPS is operating normally within specifications. If there is no power failure and the input voltage is in an under-voltage condition, the AC IN lamp will be "off." If there is no power failure and the input voltage is in an over-voltage condition, the
INV
GREEN
AC IN lamp will flicker on and off rapidly (0.4 sec "on" and 0.4 sec "off").
This green LED lamp is "on" when the UPS inverter is operating.
BYP
GREEN
BATT
GREEN
This green LED lamp is "on" when the UPS is in the static Bypass Mode.
This green LED lamp is "on" when the UPS is in the Battery-Discharge Mode. If the battery is low during a battery discharge, the BATT lamp will flicker on and off slowly (1.2 sec "on" and
1.2 sec "off"). The BATT lamp will go "off" if the battery voltage reaches the shutdown level during the Battery-Discharge Mode.
FAULT
RED
This red LED lamp is "on" when the UPS is in a fault condition.
5.14.1 LED (Light Emitting Diode) System Status
The following chart shows the UPS system status that can be determined by decoding the "on" and "off" condition of the LED lamps. It should be used in conjunction with the LCD display and the audible alarms for total system monitoring.
LED ON/OFF STATUS LED ON/OFF STATUS
Normal UPS Operation
(UPS On-Line, no abnormal conditions)
AC IN
INV
BYP
BATT
FAULT
ON
ON
OFF
OFF
OFF
Bypass Operation; UPS Fault
AC IN
INV
BYP
BATT
FAULT
ON
OFF
ON
OFF
ON
Battery Back-up; (Battery Voltage Low)
AC IN
INV
BYP
BATT
FAULT
OFF
ON
OFF
ON (Blinking)
OFF
Output Shutdown
(After EPO received (Emergency Power Off ))
AC IN
INV
BYP
BATT
FAULT
OFF
OFF
OFF
OFF
OFF
Fatal Communication Error
(Display to Control Interface)
AC IN
INV
BYP
BATT
FAULT
ALL ON OR FLICKERING
RAPIDLY
42
TOSHIBA
5.15 LCD (Liquid Crystal Display) Functions
The LCD screen is a 4-line by 20-character wide display. The LCD display contains information about the operation of the UPS. It should be used in conjunction with the LED display and the audible alarms for total system monitoring. The LCD displays certain information only on specific lines of the display. The UPS operating mode and conditions determines the information shown. These messages are shown in the following line message charts.
5.15.1 Line-1 System Messages
Line-1 messages are based on the operating mode. The following chart shows all allowable Line-1 messages, which occur while starting up and while in main monitor
(MONI) screen mode.
Display Message
- UPS START UP -
LINE-1 MESSAGES
Translation
Displayed when UPS is in the start-up condition
- BYPASS OPERATION -
or display board is resetting.
Displayed when the UPS is in Bypass
Operation.
- UPS ON-LINE -
- BATTERY DISCHARGE -
- OUTPUT SHUTDOWN -
- BATTERY BACKUP -
Displayed when the inverter is running, and no
Utility abnormality exists.
Displayed during abnormal Utility occurrences; inverter is supplying power from batteries. (UPS shuts down after V (min.) is reached.
Displayed during power failure if V (min.) is reached, an EPO is received, or after completion of Start-Up Sequence of the Inverter and Bypass is not available.
Displayed during input power failure.
5.15.2 Line-2 System Fault Messages
Line-2 fault messages are automatically displayed when a system fault is detected.
LINE-2 MESSAGES
Display Message Translation
5.15.3 Line-3 System Messages
Line–3 messages show load current information, and user selected instructions.
43
TOSHIBA
5.15.4 Line-4 System Messages
Line-4 messages reflect the UPS operating conditions. Warning messages will be displayed when an abnormal operating condition occurs. The following chart shows the allowable Line-4 messages.
Line-4 Messages
Displayed Message Translation
PHEI
I/O NOT SYNCHRONIZE
* AUTOTRANSFER *
* LOW BATTERY *
* UPS OL: REDUCE LOAD *
* DCOC *
* DCOV *
* DCUB *
* OL *
* FUSE *
* INOV *
* INUV *
* BATT. OH *OR MCCB-B OPEN
* MM/DD/YY (DAY) HH:MM *
* TRANSFER INHIBITED *
* ENTER FOR DETAILS *
Displayed when Input Phase rotation has been wired in a counter-clockwise rotation.
Displayed when input and output frequencies are not synchronized. (Abnormal)
Displayed when Auto-transfer to Bypass is active (i.e. current limit reached). (Abnormal)
Displayed when battery voltage is low (abnormal) or the UPS batteries have failed self-diagnostic test.
(Abnormal)
Displayed when UPS has tripped due to an overload condition. (Abnormal)
Displayed when the UPS has an internal failure.
(Abnormal)
Displayed when the UPS has an internal DC bus over-voltage. (Abnormal)
Displayed when the UPS has an internal DC bus unbalance referenced to Neutral. (Abnormal)
Displayed when UPS has tripped due to an overload condition. (Abnormal)
Displayed when an internal transistor fuse opens.
Displayed when inverter output over-voltage has occurred. (Abnormal)
Displayed when inverter output under-voltage has occurred. (Abnormal)
Displayed when the optional battery over-temp sensor has activated, or if the external battery disconnect is open. (Verify TB3-5, 6)
Displayed when none of the above abnormal conditions are present. (Normal)
Displayed when key switch position is changed and frequency is not synchronized. (Abnormal)
Displayed when a Fault or Faults have occurred.
(Abnormal)
Note:
1) Line-4 will be blank when the BATT key is pressed during Battery Backup Mode with normal battery voltage.
2) The # symbol signifies numerical values or other information supplied by the UPS.
44
TOSHIBA
5.16 Initial Battery Charge
The UPS Battery System must be charged before it is used for the first time or when the unit has not been used (AC power source removed) for more than 10 days. Use the following procedure to recharge the UPS Battery System:
1) Switch on power at the UPS input distribution panel, and battery disconnects.
2) Move the UPS MCCB1 (Circuit Breaker 1) power switch on the rear panel to
"on." The UPS battery charging circuit is now activated. The AC IN lamp will be
"on." The LCD screen should display the following message:
- UPS START UP -
> PLEASE WAIT
3) With the key switch in the STOP position, the AC IN and the BYP lamp will be
"on" and the LCD screen should display the following message:
- BYPASS OPERATION -
OUTPUT VOLTAGE=208V
>CURRENT 100/100/100%
(DATE) DAY (TIME)
4) Turn the Key Switch to “RUN” and the UPS automatically performs a controlled system battery test. (Note: The Automatic Battery Test is performed only when the software is enabled for this function. The standard default is set to disable.)
(Allow 24-72 hours for the batteries to fully charge).
When automatic battery test fails and the “LOW BATTERY” message is displayed use the following procedure:
1) Turn the key switch to STOP.
2) Allow 24-72 hours for the batteries to charge and then move the Circuit Breaker to "off."
3) Repeat Initial Battery Charge procedure. (A failure indicates battery replacement may be necessary).
45
TOSHIBA
The UPS batteries must be charged before the UPS is used for the first time or if the unit has not been used (AC power source removed) for more than 10 days.
If the batteries are charged then use the following start-up procedure:
1) Verify that all power switches are off, and that the "STOP/RUN” Switch on the UPS is in the “STOP” position.
2) Switch on the power at the Customer Provided UPS input distribution panel.
3) Move the UPS Circuit Breakers to "on." The AC IN lamp will be "on." The LCD screen should display the following message:
- UPS START UP -
> PLEASE WAIT
With the key switch in the “STOP” position, both the AC IN and the BYP lamp will be "on" and the LCD screen should display the following message:
- BYPASS OPERATION –
OUTPUT VOLTAGE=207V
>CURRENT 100/80/90%
DATE (DAY) TIME
The UPS battery charging circuit is now activated. Move the “STOP/RUN” key switch to the
“RUN” position. The inverter will then start and the UPS will transfer to the Normal Operating
Mode. Both the AC IN and the INV lamp will be "on." The following system message is an example of the main MONI (monitor) screen for standard operation:
- UPS ON-LINE -
OUTPUT VOLTAGE=208V
>CURRENT 100/80/90%
DATE (DAY) TIME
If a fault occurs during start-up, the red FAULT lamp will be "on" and the LCD screen will display a FAULT(s) DETECTED at start-up message such as the following:
UPS FAULT (BYPASS ON)
(DESCRIPTION)
PRESS DOWN TO DETAIL
> ENTER FOR DETAILS
Refer to the "Line-2 System Fault Messages" section for details.
46
TOSHIBA
When turning off the UPS, the following shutdown procedure should be used:
Move the “STOP/RUN” key switch, located on the front panel, to “STOP." Operation of the inverter stops. Output power is now provided to the load through the unit's Bypass circuit.
While in this state of operation; if a power failure occurs in the commercial power source, the
UPS will lose power. Power to the critical load device will be interrupted. The battery charging circuit and chopper circuit remains active.
Do not touch the UPS terminals even though the operation switch has
DANGER
been moved to the STOP position. The UPS may be supplying power through the Bypass circuit.
The green AC IN lamp is "on" and the green BYP lamp is "on." The LCD screen shows the following message:
OUTPUT VOLTAGE=207V
>CURRENT 100/100/100%
DATE (DAY) TIME
Move the Circuit Breaker to the "off" position. Power is removed from the UPS and to any
attached loads. All lamps are "off" and the LCD screen shows the following message as long as sufficient power remains to display it:
- OUTPUT SHUT DOWN -
OUTPUT VOLTAGE= 0V
CURRENT=LOW/LOW/LOW%
When the EPO (Emergency Power Off) switch, located on the front panel (or from a remote located EPO switch) is pushed, the Circuit Breaker is tripped and power is removed from the
UPS and to any attached loads. All LED lamps are "off" and the LCD screen will display the following message:
- OUTPUT SHUT DOWN -
OUTPUT VOLTAGE= 0V
CURRENT=LOW/LOW/LOW%
47
TOSHIBA
5.19 Maintenance Bypass Procedure
When operating the Maintenance Bypass, the following operation procedure should be used:
WARNING
Failure to adhere to the following instructions could result in damage to your equipment and/or you risk removal of power to any equipment attached to the UPS.
From UPS to Maintenance Bypass
1) Move the “STOP/RUN” key switch, located on the front panel, to “STOP."
Operation of the UPS inverter stops. Output power is now provided to the load through the Bypass circuit. While in this mode, if a power failure occurs on the
commercial power source, the UPS will lose power. Power to the critical
load device will be interrupted. The battery charging circuit and chopper circuit remains active.
2) Verify that step one above is followed, and that the Bypass light indicator on the front panel is lit.
3) Locate the Maintenance Bypass Rotary Switch (middle front panel of the UPS); slowly rotate the Cam Switch clockwise until “BYPASS MODE” Position is reached.
4) Turn off MCCB1 breaker labeled “MAIN POWER SWITCH."
The unit is now in the Maintenance Bypass mode and may be serviced. For units with an internal isolation transformer, the transformer is still active.
From Maintenance Bypass to UPS
1) Verify that the “STOP/RUN” switch is in the “STOP” position. Turn on MCCB1
“MAIN POWER SWITCH."
2) Wait until the output fans turn on (This is a good indication that the unit is in the
Bypass mode), and that the Bypass indicator light on the front panel is lit.
3) For units with an external battery cabinet, turn on MCCB1 “BATTERY CABINET."
4) Locate the Maintenance Bypass Switch (Middle front panel of the UPS) slowly rotate the Cam Switch counter-clockwise until “UPS MODE” Position is reached.
5) Rotate the “STOP/RUN” switch to the “RUN” position.
6) Verify that the Inverter indicator light on the front panel is lit.
The unit is now back On-Line and supplying conditioned power to the load.
48
TOSHIBA
The following illustrates the 12-key data entry pad with each key functionally labeled.
MONI BATT F1
IN OUT
TEST
BUZZ
STOP
MENU ENTER
RESET
MONI
BATT
F1
IN
Press to display system-monitoring screens.
Press to display UPS battery conditions.
Press to change settings of various menus.
Press to display UPS input conditions.
OUT
BATT
TEST
BUZZ
STOP
MENU
Press to display UPS output conditions.
Press to execute On-Line Battery test.
Press to stop the audible alert buzzer.
Press to display the main user-selection menu.
ENTER
Press to confirm user-selected command or action.
RESET
Press to reset UPS panel’s message-display area.
Press to forward through display data values or to forward through menus.
Press to reverse through display data values or to reverse through menus.
49
TOSHIBA
5.21.1 MONI
After the UPS has been successfully started, the system will be in the normal 'AC
Input Mode' of operation. The LCD screen will automatically display the main MONI
(monitor) function. If the MONI key is pressed at this time the screen output will not change. The MONI function automatically monitors the entire UPS system. The LCD screen will automatically switch "off" after a period of keypad inactivity and switch
"on" if any key is pressed. It will switch "on" automatically during battery discharge or if an abnormality develops in the system (see "Settings for LCD Display Duration").
All system 'line' messages will be displayed from MONI mode when abnormal operating problems are detected. If AC input power is available and the UPS is operating normally, the following system message is displayed:
- UPS ON-LINE -
OUTPUT VOLTAGE= 208V
CURRENT=100/100/99%
DATE (DAY) TIME
If an AC input power failure occurs, and no abnormal operating conditions are present, the UPS switched to standard 'Battery Backup Mode'. The following system message is displayed:
- BATTERY BACKUP –
OUTPUT VOLTAGE = 208V
CURRENT=100/100/99%
DATE (DAY) TIME
5.21.2 IN
When the IN key is pressed during normal 'AC Input Mode' of operation, the LCD screen displays details about the unit's input voltage. The following system message is displayed:
- UPS ON-LINE -
INPUT Vab = 96%
VOLTAGE Vbc = 96%
Vca = 96%
The Bypass Input Voltages, Frequencies / Sync Mode, and Converter Current can be monitored by pressing the "UP/DOWN" keys.
5.21.3 OUT
When the OUT key is pressed during normal ‘AC Input Mode’ of operation, the LCD screen displays details about the output voltage, current, and frequency. The following system message is displayed:
- UPS ON-LINE -
OUTPUT Ia = 101%
CURRENT Ib = 100%
Ic = 100%
The Output Line Voltages (phase-neutral, and phase to phase),
Frequencies / Sync Mode, Inverter Output Power, and Power factor can be monitored by pressing the "up/down" keys.
50
TOSHIBA
When the BATT key is pressed during normal 'AC Input Mode' of operation, the LCD screen displays details about the battery capacity. The following system message is displayed:
- UPS ON-LINE -
BATTERY VOLTAGE=324V
CHARGE CURR.=0%
If an AC input power failure occurs, and no abnormal operating conditions are present, the UPS will switch to standard 'Battery Backup Mode'. The following system message is displayed when the BATT key is pressed:
- BATTERY BACKUP –
BATTERY VOLTAGE=324V
DISCHARGE CURR. =76%
5.21.5 MENU, F1, ENTER, UP, & DOWN Keys
When the MENU key is pressed during normal ‘AC Input Mode’ of operation, a menu of user adjustable data screens are available. Press 'up' arrow key to scroll up through the available data screens. Press 'down' arrow key to scroll down through the available data screens. Pressing the F1 key changes to the adjustment screen for that menu item. Press 'up' arrow to move display to previously available item. Press
'down' arrow to move display to next available item. From the adjustment screen, if the MENU key is pressed any changes are discarded and the display returns to the regular menu screen with the previous data values shown. If the “ENTER” key is pressed from the adjustment screen, the changes are saved. After pressing the
“ENTER” key, the display screen will return to the regular menu screen with the new data values shown (see "Menu Data Screens").
5.21.6 BATT TEST Key
When the BATT TEST key is pressed during normal 'AC Input Mode' of operation, the LCD screen displays details about the battery back-up capacity. The following system message is displayed:
- BATTERY TEST –
BATTERY VOLTAGE=324V
> F1+ENTER TO BEGIN
Press the F1+ ENTER keys at the same time to begin the battery test and to display the following screen while batteries are tested:
- BATTERY TEST -
BATTERY VOLTAGE=324V
## MINS ## SECS
> PLEASE WAIT
51
TOSHIBA
When the battery test is completed, the previous operation will be resumed and the main system MONI screen will be displayed. If the battery test detects a low DC battery voltage, then the message screen will display:
- UPS ON-LINE -
OUTPUT VOLTAGE=208V
CURRENT=38/55/48%
* LOW BATTERY *
If the battery test passes then the following screen message will be displayed:
- UPS ON-LINE -
OUTPUT VOLTAGE=208V
CURRENT=38/55/48%
DATE (DAY) TIME
If the inverter is not operating when the BATT TEST key is press then the function will be inhibited and the following screen message will be displayed:
- BATTERY TEST -
BATTERY VOLTAGE=324V
BATT. TEST INHIBITED
NOTE:
After start-up, the battery test function is inhibited for 20-min. (only one battery test can be done approximately every 20-min.).
5.21.7 BUZZ STOP Key
The “BUZZ STOP” key has no effect on the LCD screen display. However if the UPS alarm buzzer is on, pressing this key will silence it. If the alarm buzzer is not on, pressing this key has no effect.
The RESET key function is used to 'Reset' the LCD display board software should a system lock-up occur. The reset does not reset the variables in the memory. Use of
the RESET function is very important when a fatal communication error has occurred.
Press and hold the RESET key for a period of at least five seconds to reset the display software. The 'display board' to 'main board' interface will begin a new communication sequence. If a communication response is not received by the
'display board' from the 'main board' within 15 seconds, a fatal time-out occurs and the following system message displays:
- DISPLAY ERROR -
MAIN COMM. ERROR
PRESS & HOLD RESET KEY
If the 'Reset' function is successful then the display will begin from the 'Start-up screen' and then change to the 'main monitor' screen.
52
TOSHIBA
5.22 Menu Data Screens
5.22.1 Settings for Calendar and Clock
Press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the present date and time adjustment screen:
CALENDER / CLOCK
DATE (DAY) TIME
>*F1: DATA SET MODE
>
∆/∇ PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
CALENDER / CLOCK
DATE (DAY) TIME
>
∆/∇ : UP/DOWN
>ENTER:NEXT DATA
Press the "up/down" arrows to increment or decrement the character(s) above the flashing cursor.
Press the ENTER key to advance the cursor.
5.22.2 Adjusting the Buzzer Volume
Press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the present buzzer volume adjustment screen display:
BUZZER VOLUME ADJUST
<LOUD> MEDIUM SOFT
>*F1: DATA SET MODE
>
∆/∇:PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
BUZZER VOLUME ADJUST
<LOUD> MEDIUM SOFT
>
∆/∇: CHANGE DATA
>ENTER:ACCEPT CHANGE
Press the 'up' or 'down' arrow key to move the marker between the three buzzer volume levels. Press ENTER key to confirm the change or press MENU key to discard any changes and return to the menu data screen.
5.22.3 Settings for Display Duration
The LCD display is designed to automatically switch off after a user-designated period of inactivity. When setting this feature, press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the LCD-Idle Mode
Select screen display:
DISPLAY DURATION SET
<3 MIN> 30 MIN
>F1: DATA SET MODE
>
∆/∇:PRV/NEXT SCREEN
53
TOSHIBA
Press the F1 key to display the LCD-Idle mode setting adjustment screen:
DISPLAY DURATION SET
<3 MIN> 30 MIN
>
∆/∇: CHANGE DATA
>ENTER:ACCEPT CHANGE
Press the 'up' or 'down' arrow key to move the marker between the two available idle mode times. Press the ENTER key to save the change or press the MENU key to exit to the main menu and discard the change.
Note: If any of the following conditions occur, the LCD-Idle Mode will be inhibited and the LCD will remain on continuously:
1) The UPS has received an EPO command.
2) The UPS is in Battery-Discharge Mode.
3) A fault has been detected in the main unit.
4) The UPS is in an overload condition.
5.22.4 Run Switch Select
Press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the “Run Switch Select” setting screen display:
RUN SWITCH SELECT
<LOCAL> REMOTE
>*F1: DATA SET MODE
>
∆/∇: PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
RUN SWITCH SELECT
<LOCAL> REMOTE
>
∆/∇: CHANGE DATA
>ENTER:ACCEPT CHANGE
Press the 'up' or 'down' arrow key to move the marker between the two "RUN
SWITCH" selections Press the ENTER key to save the change or press the MENU key to exit to the main menu and discard the change. (Must have Remote Control option.)
5.22.5 Serial Com Station Address
Press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the “Serial Comm Station Address” setting screen display:
SER COM STATION ADDR
STATION ADDRESS: 31H
>*F1: DATA SET MODE
>
∆/∇: PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
SER COM STATION ADDR
STATION ADDRESS: 31H
>∆/∇: CHANGE DATA
>ENTER: ACCEPT CHANGE
54
TOSHIBA
5.22.6 Output Voltage Adjustment
When the MENU key is pressed and held 3-4 seconds during normal 'AC Input Mode' of operation, the LCD screen displays the output voltage on the present output voltage adjust screen:
OUTPUT VOLT. ADJUST
OUTPUT VOLTAGE.=###%
>F1:DATA SET MODE
>
∆/∇ :PREV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
OUTPUT VOLT. ADJUST
REFERENCE ADJUST: ##
>
∆/∇ :CHANGE DATA
>ENTER: ACCEPT CHANGE
The locations marked ## will show the numerical value of the allowable voltage adjustment parameter values. Press the 'up' and 'down' arrow keys to adjust the setting from between
±5 volts. This will cause the unit's output voltage to adjust to within
±2% of its nominal value.
If the inverter is not running, and the output voltage cannot be adjusted; the following message will be displayed:
OUTPUT VOLT. ADJUST
ADJUST PROHIBITED
DATA CANNOT CHANGE
>
∆/∇:PRV/NEXT SCREEN
Pressing the F1 key will have no effect on this display screen
5.22.7 Charge Mode Select
Press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the “Charge Mode Select” adjustment screen display:
CHARGE MODE SELECT
EQUAL CHARGE>OFF ON
>F1:DATA SET MODE
>
∆/∇:PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
CHARGE MODE SELECT
EQUAL CHARGE>OFF ON
>
∆/∇:CHANGE DATA
>ENTER:ACCEPT CHANGE
Note: Please consult with the factory when using this option. DAMAGE to the battery system will occur if this is used improperly.
55
TOSHIBA
5.22.8 Reset to Default Settings
Press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the original factory 'default settings' adjustment screen display:
MENU DATA RESET
DATA INITIALIZATION
>F1: TO ACCESS RESET
>
∆/∇:PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
MENU DATA RESET
DATA INITIALIZATION
> MENU: NO DATA RESET
>ENTER: ACCEPT CHANGE
When the ENTER key is pressed the following factory defaults are reset:
1) Resets the voltage-reference setting to +0
2) Resets the buzzer volume to 'loud'
3) Resets the serial station address to 31h
4) Resets the idle mode to 3 minutes
Press the MENU key to abandon the operation and return to the menu data screen.
When the UPS is operating and an overload condition is first detected, the following “Overload
Warning” screen is displayed.
- UPS ON-LINE -
OUTPUT VOLTAGE= ###V
OUTPUT CURRENT= ###%
* UPS OL: REDUCE LOAD *
After a period of time, if the overload is still not reduced and the STOP/RUN key switch is in the
RUN position, the UPS will automatically transfer to Bypass. If the overload condition is still present, the following screen will be displayed:
- BYPASS OPERATION -
OUTPUT VOLTAGE=208
CURRENT= 114/116/114%
* UPS OL: REDUCE LOAD *
If the STOP/RUN key switch is in the STOP position; the UPS is in the Bypass Mode and, if the overload condition is still present, the following screen will be displayed:
- BYPASS OPERATION -
OUTPUT VOLTAGE=208
CURRENT= 114/116/114%
* UPS OL: REDUCE LOAD *
56
TOSHIBA
After the load is reduced, if the STOP/RUN key switch is in the RUN position, the UPS will automatically return to 'Inverter Operation’ after a period of time. During this wait, the following screen will be displayed:
- BYPASS OPERATION -
OUTPUT VOLTAGE=208V
CURRENT= 100/100/100
>PLEASE WAIT
Or if the UPS is waiting and the STOP/RUN key switch is switched to the STOP position while the UPS is waiting, the following screen will be displayed:
- BYPASS OPERATION -
OUTPUT VOLTAGE=208V
CURRENT= 100/100/100
>PLEASE WAIT
If the STOP/RUN key switch remains in the STOP position when the UPS's 'wait' period is complete, then the following screen will be displayed:
- BYPASS OPERATION -
OUTPUT VOLATAGE=###V
CURRENT=100\100\100%
DATE (DAY) TIME
If the STOP/RUN key switch remains in the RUN position when the UPS's 'wait' period is complete, then the following screen will be displayed:
- UPS ON-LINE -
OUTPUT VOLTAGE= 208V
CURRENT=100/100/99%
DATE (DAY) TIME
5.24 Backup History and Fault History
Pressing the MONI and F1 keys simultaneously, for a few seconds will cause the Battery
Discharge Count screen to be displayed.
BATT DISCHARGE COUNT
# TIMES
> F1: FOR DETAILS
>
∆/∇: TO SCROLL
Press the F1 key to display the record relating to the first discharge event.
BACKUP HISTORY ( 1)
#MIN##SEC VB=324V
BT *PF OL
>
∆/∇: EXIT F1: NEXT
57
TOSHIBA
Press the F1 key again to display the record relating to each subsequent discharge event.
BACKUP HISTORY ( #)
#MIN##SEC VB=324V
BT *PF OL
>
∆/∇: EXIT F1: NEXT
Press the ‘up’ or ‘down’ arrow keys to return to the Battery Discharge Count screen.
BATT DISCHARGE COUNT
# TIMES
> F1: FOR DETAILS
>
∆/∇: TO SCROLL
Press the ‘up’ or ‘down’ arrow keys to display the Fault Count screen.
TOTAL FAULT COUNT
## TIMES
> F1: FOR DETAILS
>
∆/∇: TO SCROLL
Press the F1 key to display the record relating to the first fault.
FAULT HISTORY ( 1)
Date Time fault code
>
∆/∇: EXIT F1: NEXT
Press the F1 key again to display the record relating to each subsequent fault.
FAULT HISTORY ( #)
Date Time fault code
>
∆/∇: EXIT F1: NEXT
Press the ‘up’ or ‘down’ arrow keys to return to the Fault Count screen.
TOTAL FAULT COUNT
## TIMES
> F1: FOR DETAILS
>
∆/∇: TO SCROLL
58
TOSHIBA
6.0 UPS Protection System
6.1 System Protection Features
The preceding one-line schematic illustrates the electrical locations of the protection devices on all UPS models.
Input
Abnormal
MBS
Overheat
Bypass
Overload
Isolation
Transformer
Model
Converter Inverter
MCCB
Input
Power
Output
Power
Chopper
Over-voltage/
Under-voltage
Overcurrent
Batteries
Low Battery
Protection Item
LCD Message
Cause
Operation Mode after Fault
Audible Alarm
Visible Alarm
Relay Contact
Alarm
Auto-Retransfer
6.2 System Protection Functions
The following chart shows the built-in UPS fault protection functions on all models.
Built-in UPS Fault Protection Functions
Inverter Over-voltage
(IVOV)
Inverter Under-voltage
(IVUV)
UPS Overload
INVERTER
OVERVOLTAGE
INVERTER
UNDERVOLTAGE
Control Malfunction; Feedback Error
OUTPUT OVERLOAD
Bypass Operation; Chopper and Inverter Stopped
Overload or short circuit at the load.
Inverter Overload: Transfer to bypass; Inverter stopped.
Bypass Overload: Inverter, Chopper, and Bypass stopped.
Red Fault Lamp “on”
Yes: See Audible Alarm Functions
Inverter OL: No Fault Lamp
Bypass OL: Fault Lamp “on”
Fault Relay closed; Bypass Relay closed
No
Inverter OL: Bypass Relay closed
Bypass OL: Bypass Relay open and Fault relay closed
Inverter OL: Yes, if bypass ok
Bypass OL: No
Protection Item
LCD Message
Cause
Operation Mode after Fault
Audible Alarm
Visible Alarm
Relay Contact
Alarm
Auto-Retransfer
Low Battery Voltage
(Level-1)
Line-4 will read
“BATTERY LOW”
Low Battery Voltage
(Level-2)
DC UNDERVOLTAGE
Inverter Output Current Limit
OUTPUT OVERLOAD
Battery Discharge
Battery Discharge
Battery Lamp Flickers
Low Battery Relay closed
No
Battery Shutdown Level reached
Shutdown:
No Output
Load Inrush current
If Bypass ok, transfer to bypass; if not, current-limit mode
Yes: See Audible Alarm Functions
NO NO
Bypass Relay closed
Yes, if bypass ok
59
TOSHIBA
Protection Item
LCD Message
Cause
Operation Mode after Fault
Audible Alarm
Visible Alarm
Relay Contact
Alarm
Auto-Retransfer
Memory error (EERR)
Internal overheat
(OH)
MAIN EEPROM ERROR OVERHEAT; INTERNAL
Control board chip error Fan failure; high ambient
Start is inhibited
DC circuit overvoltage (DCOV)
DC OVERVOLTAGE
Chopper malfunction
DC circuit overcurrent
(DCOC)
DC OVERCURRENT
Inverter / chopper fault
Bypass operation; chopper and inverter are stopped
Yes; continuous buzzer
RED fault lamp “ON”
Fault relay closed; bypass relay closed
NO
7.0 Authorized Factory Service
7.1 Start-up
The startup of the UPS equipment is broken up in several steps. These steps are as follows:
1. Initial Condition: This is where the service technician checks the unit for physical damage and verifies the installation of the UPS (electrically).
2. Static Checks: This step verifies the proper settings within the UPS logic.
3. Wiring Check: The wiring to (power cables) and from (control wires) the battery cabinet.
4. Main Voltage Check: The input voltages are checked to verify they are within the range.
5. Energizing the UPS: This step begins the internal self-checks within the processor logic.
6. Output Voltage Check: The output voltages are checked to verify they are within range.
7. EPO (Emergency Power Off): The EPO is operated to verify its operation in case of an emergency.
8. Load Testing: Performed if load is available.
9. Generator Testing: Performed if Generator is available.
10. Internal Maintenance Bypass: This verifies the operation of the Maintenance Bypass.
Toshiba's 4200FA Uninterruptible Power Systems have been designed to provide years of trouble-free operation requiring a minimum of preventive maintenance.
The best preventive measure that the UPS user can take is to keep the area around the unit, particularly the air inlet vents, clean and free of moisture and dust accumulations. If the atmosphere of the installation site is very dusty, use a vacuum cleaner to periodically remove dust accumulations from the system. Schedule authorized Toshiba service centers to perform internal parts inspections annually.
CAUTION
Before performing any maintenance the technician should be familiar with and follow the important safety instructions within this manual.
WARNING
Proper maintenance of the battery system of this unit by a qualified service technician is essential to the safety and reliability of your UPS system. Refer to service manual.
60
TOSHIBA
The following list shows intervals for periodic maintenance and replacement of certain UPS parts.
1) Batteries: VRLA (Valve Regulated Lead Acid) batteries do not require the adding of water or electrolyte. The charging voltage, temperature, performance and connection resistance must be monitored periodically. Necessary corrective maintenance must be made in order to assure the UPS supplies safe reliable power. These items affect the life of batteries, so replacement should be once every 3 to 5 years as a minimum. All of the batteries must be replaced at the same time to eliminate the possibility of multiple failures due to resistances of the batteries.
Quarterly Maintenance
A. Visual Checks
1) Leakage
2) Corrosion on positive terminal
B. Check battery temperature at the negative terminal
C. Measure and record the system float charging voltage.
D. Measure and record the individual unit’s float charging voltage.
Semi-Annual maintenance
A. Repeat the quarterly checks.
B. Perform a 10-second high rate (e.g. 100 amp) load test on the individual batteries.
C. Optionally test for the purpose of trending the battery over time.
D. Re-torque all inter-battery connecting hardware (if applicable).
E. Perform inter-battery connector resistance checks.
3) Fuses: Replace once every 7 years.
4) Cooling fan: Replace once every 3 years.
61
TOSHIBA
8.0 External Layouts / Dimensions / Weights
8.1 External Dimensions 15/25/30/33kVA
62
8.2 External Dimensions 50kVA
TOSHIBA
63
TOSHIBA
8.3 Shipping Dimensions and Weights
Models
15 kVA
25/30/33 kVA
50 kVA
Shipping Dimensions
W” x D” x H” (WmmxDmmxHmm)
36.5” x 43.0” x 69.5”
(927mm x 1092mm x 1765mm)
36.5” x 43.0” x 69.5”
(927mm x 1092mm x 1765mm)
55.0” x 44.5” x 69.5”
(1397mm x 1130mm x 1765mm)
Internal Model
Battery
Transformer
Battery
Transformer
Battery
Transformer
Shipping Weights
Lbs. (kg)
1,303 lbs. (591 kg)
1,260 lbs. (572 kg)
1,321 lbs. (599 kg)
1,275 lbs. (579 kg)
2,548 lbs. (1156 kg)
2,523 lbs. (1144 kg)
64
TOSHIBA
TOSHIBA INTERNATIONAL CORPORATION
INDUSTRIAL DIVISION
13131 West Little York Road, Houston, Texas 77041
Tel: (713) 466-0277 Fax: (713) 896-5212 Telex: 762078
E-mail: [email protected]
Printed in the U.S.A.