Toshiba FDP2 F-PE air conditioner interface Installation and Operating Instructions
Below you will find brief information for air conditioner interface FDP2-F. The FDP2-F is a monitoring and control interface for the Toshiba Digital Inverter, SHRM and SMMS range of air-conditioners. The FDP2 detects all indoor and outdoor faults occurring in Toshiba compatible air-conditioners and reports them to the user. The FDP2 can be used in various configurations, including fault monitoring, preset control and group control. In addition, the FDP2 can be connected to a Building Management System through the FDP2-BMS interface, enabling more sophisticated control.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
RBC-FDP2-F-PE Interface
Installation and Operating Instructions
13.00
20.00
26.00
Fault
No Fault
FDP2-F
Fault Interface
ON
SW1
TCC-NET
A B D1
D-BUS
D2 C
ON
SW7
RELAY
R1 R2
RealTime Control Systems Ltd
FDP2 Model 9410-2-A6
Ø 4.00
72.00
Ø 9.00
63.00
87.00
18.60
ALL DIMENSIONS IN MM NOT TO SCALE
FDP2 Description
The FDP2-F is a monitoring and control interface for the Toshiba Digital
Inverter, SHRM and SMMS range of air-conditioners.
Fault Reporting
The FDP2-F Interface detects all indoor and outdoor faults occurring in
TCC-NET compatible Toshiba air-conditioners and reports them by closing relay contacts R1-R2. The FDP2-F is connected on the TCC-NET network with or without a standard remote controller and detects any faults that can be displayed on the controller for up to 8 units. Red and Green LEDs
Indicate Fault/No Fault state.
Control Functions
GROUP CONTROL. Multiple FDP2 Interfaces can be connected to form large groups of units controlled from a single remote controller.
OPERATION PRESETS. Remote controller operation can be locked and various different preset run conditions can be sent from the FDP2.
DUTY/STANDBY. Pairs of FDPs can operate duty/standby control with 24 hour alternating duty, and changeover on fault.
HARDWIRED CONTROL. In conjuntion with an FDP2-BMS unit control can be achieved through potentiometer and volt-free contact inputs as well as via BMS integration.
CUSTOM CONTROL. FDP2 interfaces can be supplied in custom configurations to suit specific applications.
Warnings and Cautions
Do not exceed the specified fault relay ratings
Mounting
The FDP2 should be mounted using the keyhole mounting points as indicated in the adjacent diagram.
The FDP can be mounted horizontally or vertically.
75.00
Ø 4.00
Ø 9.00
Basic Cable Installation
Cabling should be a minimum 0.75mm
2
throughout. Terminals TCC-NET
A/B connect to the Toshiba TCC-NET. TCC-NET installation should follow
Toshiba installation specifications. Terminals R1-R2 connect to fault monitoring or indication equipment according to the specified rating of the relay. The FDP2 is powered from the TCC-NET and requires no extra power supply.
Indoor Unit
TCC-NET
A
D-BUS
B D1 D2 C
RELAY
R1 R2
TCC-NET
To fault monitoring
A B
Toshiba Remote Controller
LED Functionality
Normal Operation
R
G
Key:
OFF
Power-Up sequence
Factory Configuration
R
G
R
G
Power-Up sequence
Custom Configuration
TCC-NET Holdoff. After power-up and during unit configuration
Error Conditions
R
G
R
G
R
G
FLASHING
R
G
R
G
Device configuration error
D-BUS Communications timeout
ON
No Fault State
Unit Fault
No unit master found on TCC-Net
R
G
Duplicate D-BUS Address detected
Standard Operation
ON
SW1
ON
SW7
FDP2 Configuration Switches
The FDP2 has a number of standard configurations that can be set using switches SW1 to SW7 shown above. Factory configuration is configured with all switches OFF. In this mode the FDP2 operates as a standard fault monitoring device. Additional preset modes are available using SW1 and
SW2 to operate the system in preset Heat, Cool and Auto modes*.
Fault Monitoring
8 Units max
Fault Monitoring + Locked Cooling Preset
18
Fault Monitoring + Locked Heating Preset
23
Fault Monitoring + Locked Auto Preset
21
8 Units max
8 Units max
8 Units max
*Units that do not support specific modes such as cooling-only units will operate in fan-only in unsupported modes.
FDP2 Advanced Operation
ADDRESSING
The FDP2 has the facility to create control groups using multiple FDP2s connected together on the D-Bus network. In standard configuration up to 16 FDP2 devices can be connected together. Each FDP2 is assigned a D-Bus address using the configuration switches SW4 to SW7. Unit addresses are shown below.
ADDRESS 0 ADDRESS 4 ADDRESS 8 ADDRESS 12
ADDRESS 1 ADDRESS 5 ADDRESS 9 ADDRESS 13
ADDRESS 2 ADDRESS 6 ADDRESS 10 ADDRESS 14
ADDRESS 3 ADDRESS 7 ADDRESS 11 ADDRESS 15
Address 0 is the FDP2 MASTER address. Address 1 to 15 are FDP2
SLAVE addresses that can be used to create large control groups.
NETWORK INSTALLATION
The D-Bus network requires a twisted pair cable connecting terminals
D1 and D2 on each FDP2 as shown below. Terminal D1 must be connected to all other D1 terminals. Terminal D2 must be connected to all other D2 terminals. In addition the common terminal C on all devices must be connected together. If a shielded cable is used then the shield can be used for this purpose. The network must be installed as a point to point BUS configuration, Star and Ring connections must NOT be used.
ADDRESS 0 ADDRESS 1
TCC-NET
A
D-BUS
B D1 D2 C
RELAY
R1 R2
TCC-NET
A
D-BUS
B D1 D2 C
RELAY
R1 R2
D1
D2
C
D1
D2
C
SPECIFICATION
Use solid or stranded 24awg shielded or unshielded twisted pair to
Cat3, Cat4 or Cat5 specification. Use a twisted pair for connections
D1,D2 and an extra core for connection C.
NETWORK LENGTH
Standard installation for total network distances of up to 500m can be achieved following the basic daisy-chaining method showed in the above diagram. Network layout should follow a point-to-point connection, ‘T’ and star connections are not supported,
FDP2 Group Control
Group control allows up to 16 FDP2s to be connected on a D-Bus local network. Each FDP2 reports faults for the locally attached units. The
FDP2 with address 0 is a MASTER and determines the settings for all systems connected to FDP2s addressed as slaves. The operating mode of the master is determined by SW1, SW2 as shown in the Standard
Operation configuration instructions overleaf.
LOCAL CONTROL
With SW1 OFF and SW2 OFF the MASTER FDP2 system operates under the control of the attached remote controller. SLAVE FDP2 devices will duplicate these settings to allow large groups to be controlled from one remote controller. Remote controllers on the slave FDP2s are locked and can be omitted if desired.
8 Units max
FDP2 Duty/Standby Operation
Duty/Standby will alternately run two systems on 24 hour alternating run/standby. If a fault occurs on either system then both systems are switched on until the fault is cleared.
SW3 ON for
Duty/standby
Duty/Standby is achieved using two FDP2 devices, one with Address 0 and one with Address 1 with a D-BUS connection between the two. SW3 must be switched ON on both devices to enable the operation.
21
8 Units max
21
Address 0 (MASTER)
DUTY/STANDBY 1 Day 1 Day 1 Day FAULT
8 Units max
Address 0 (MASTER)
8 Units max
D-BUS
16 FDP2 max
Address 1 (SLAVE)
PRESET CONTROL
If the master is configured for Heat, Cool or Auto preset control then the
FDP2 slave units will operate to the same settings as the master. The diagram below shows the system configured for the Cool preset. See overleaf for SW1, SW2 settings for Heat and Auto presets.
18
8 Units max
18
Address 0 (MASTER)
D-BUS
16 FDP2 max
Address 1 (SLAVE)
8 Units max
D-BUS
16 FDP2 max
Address 1 (SLAVE)
The MASTER FDP2 can be configured using SW1 and SW2 to operate using one of the three preset modes Heat, Cool or Auto. Alternatively the
MASTER can be configured for local control, in which case the remote controller attached to the MASTER FDP2 can be used to set the operating settings during master duty.
Advanced control
More sophisticated control con be achieved using the FDP2-BMS interface, this provides a number of inputs that allow external control of unit operation, or connection to Building Management Systems. The
FDP2 interfaces can also be customised for specific operating requirements. Contact Toshiba for details.
Functional Specification
Electrical
Supply
Power
Relay
18V DC from TCC-NET
<1VA
1A, 24VAC max
1A, 30VDC max
Environmental
Temperature
Storage
Operation
Humidity
Mechanical
Dimensions
(mm)
Mounting
H72 x W87 x D19
Protection
EMC Emissions
EMC Immunity
Casing
Weight
Connectors
Two keyhole mounting flanges
Zinc coated mild steel
80g
Rising clamp to 0.75mm
2 cable
-10oC to 50oC
0oC to 50oC
0-90% RH non-condensing
IP30
EN61000-6-1
EN61000-6-3
9570-0 FDP2-F Installation & Operating Instructions issue 1.14.02 Copyright © RealTime Control Systems Limited. 2005
advertisement
Key Features
- Fault monitoring
- Preset control
- Group control
- Building Management System integration
- Multiple configuration options
- LED indicators for fault/no fault state
- Relay contacts for fault reporting
- Duty/Standby operation
- D-Bus network for group control
- TCC-NET connection for power and communication