Toshiba FDP2 F-PE air conditioner interface Installation and Operating Instructions

Toshiba FDP2 F-PE air conditioner interface Installation and Operating Instructions

Below you will find brief information for air conditioner interface FDP2-F. The FDP2-F is a monitoring and control interface for the Toshiba Digital Inverter, SHRM and SMMS range of air-conditioners. The FDP2 detects all indoor and outdoor faults occurring in Toshiba compatible air-conditioners and reports them to the user. The FDP2 can be used in various configurations, including fault monitoring, preset control and group control. In addition, the FDP2 can be connected to a Building Management System through the FDP2-BMS interface, enabling more sophisticated control.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Toshiba FDP2 F-PE Installation Instructions | Manualzz

RBC-FDP2-F-PE Interface

Installation and Operating Instructions

13.00

20.00

26.00

Fault

No Fault

FDP2-F

Fault Interface

ON

SW1

TCC-NET

A B D1

D-BUS

D2 C

ON

SW7

RELAY

R1 R2

RealTime Control Systems Ltd

FDP2 Model 9410-2-A6

Ø 4.00

72.00

Ø 9.00

63.00

87.00

18.60

ALL DIMENSIONS IN MM NOT TO SCALE

FDP2 Description

The FDP2-F is a monitoring and control interface for the Toshiba Digital

Inverter, SHRM and SMMS range of air-conditioners.

Fault Reporting

The FDP2-F Interface detects all indoor and outdoor faults occurring in

TCC-NET compatible Toshiba air-conditioners and reports them by closing relay contacts R1-R2. The FDP2-F is connected on the TCC-NET network with or without a standard remote controller and detects any faults that can be displayed on the controller for up to 8 units. Red and Green LEDs

Indicate Fault/No Fault state.

Control Functions

GROUP CONTROL. Multiple FDP2 Interfaces can be connected to form large groups of units controlled from a single remote controller.

OPERATION PRESETS. Remote controller operation can be locked and various different preset run conditions can be sent from the FDP2.

DUTY/STANDBY. Pairs of FDPs can operate duty/standby control with 24 hour alternating duty, and changeover on fault.

HARDWIRED CONTROL. In conjuntion with an FDP2-BMS unit control can be achieved through potentiometer and volt-free contact inputs as well as via BMS integration.

CUSTOM CONTROL. FDP2 interfaces can be supplied in custom configurations to suit specific applications.

Warnings and Cautions

Do not exceed the specified fault relay ratings

Mounting

The FDP2 should be mounted using the keyhole mounting points as indicated in the adjacent diagram.

The FDP can be mounted horizontally or vertically.

75.00

Ø 4.00

Ø 9.00

Basic Cable Installation

Cabling should be a minimum 0.75mm

2

throughout. Terminals TCC-NET

A/B connect to the Toshiba TCC-NET. TCC-NET installation should follow

Toshiba installation specifications. Terminals R1-R2 connect to fault monitoring or indication equipment according to the specified rating of the relay. The FDP2 is powered from the TCC-NET and requires no extra power supply.

Indoor Unit

TCC-NET

A

D-BUS

B D1 D2 C

RELAY

R1 R2

TCC-NET

To fault monitoring

A B

Toshiba Remote Controller

LED Functionality

Normal Operation

R

G

Key:

OFF

Power-Up sequence

Factory Configuration

R

G

R

G

Power-Up sequence

Custom Configuration

TCC-NET Holdoff. After power-up and during unit configuration

Error Conditions

R

G

R

G

R

G

FLASHING

R

G

R

G

Device configuration error

D-BUS Communications timeout

ON

No Fault State

Unit Fault

No unit master found on TCC-Net

R

G

Duplicate D-BUS Address detected

Standard Operation

ON

SW1

ON

SW7

FDP2 Configuration Switches

The FDP2 has a number of standard configurations that can be set using switches SW1 to SW7 shown above. Factory configuration is configured with all switches OFF. In this mode the FDP2 operates as a standard fault monitoring device. Additional preset modes are available using SW1 and

SW2 to operate the system in preset Heat, Cool and Auto modes*.

Fault Monitoring

8 Units max

Fault Monitoring + Locked Cooling Preset

18

Fault Monitoring + Locked Heating Preset

23

Fault Monitoring + Locked Auto Preset

21

8 Units max

8 Units max

8 Units max

*Units that do not support specific modes such as cooling-only units will operate in fan-only in unsupported modes.

FDP2 Advanced Operation

ADDRESSING

The FDP2 has the facility to create control groups using multiple FDP2s connected together on the D-Bus network. In standard configuration up to 16 FDP2 devices can be connected together. Each FDP2 is assigned a D-Bus address using the configuration switches SW4 to SW7. Unit addresses are shown below.

ADDRESS 0 ADDRESS 4 ADDRESS 8 ADDRESS 12

ADDRESS 1 ADDRESS 5 ADDRESS 9 ADDRESS 13

ADDRESS 2 ADDRESS 6 ADDRESS 10 ADDRESS 14

ADDRESS 3 ADDRESS 7 ADDRESS 11 ADDRESS 15

Address 0 is the FDP2 MASTER address. Address 1 to 15 are FDP2

SLAVE addresses that can be used to create large control groups.

NETWORK INSTALLATION

The D-Bus network requires a twisted pair cable connecting terminals

D1 and D2 on each FDP2 as shown below. Terminal D1 must be connected to all other D1 terminals. Terminal D2 must be connected to all other D2 terminals. In addition the common terminal C on all devices must be connected together. If a shielded cable is used then the shield can be used for this purpose. The network must be installed as a point to point BUS configuration, Star and Ring connections must NOT be used.

ADDRESS 0 ADDRESS 1

TCC-NET

A

D-BUS

B D1 D2 C

RELAY

R1 R2

TCC-NET

A

D-BUS

B D1 D2 C

RELAY

R1 R2

D1

D2

C

D1

D2

C

SPECIFICATION

Use solid or stranded 24awg shielded or unshielded twisted pair to

Cat3, Cat4 or Cat5 specification. Use a twisted pair for connections

D1,D2 and an extra core for connection C.

NETWORK LENGTH

Standard installation for total network distances of up to 500m can be achieved following the basic daisy-chaining method showed in the above diagram. Network layout should follow a point-to-point connection, ‘T’ and star connections are not supported,

FDP2 Group Control

Group control allows up to 16 FDP2s to be connected on a D-Bus local network. Each FDP2 reports faults for the locally attached units. The

FDP2 with address 0 is a MASTER and determines the settings for all systems connected to FDP2s addressed as slaves. The operating mode of the master is determined by SW1, SW2 as shown in the Standard

Operation configuration instructions overleaf.

LOCAL CONTROL

With SW1 OFF and SW2 OFF the MASTER FDP2 system operates under the control of the attached remote controller. SLAVE FDP2 devices will duplicate these settings to allow large groups to be controlled from one remote controller. Remote controllers on the slave FDP2s are locked and can be omitted if desired.

8 Units max

FDP2 Duty/Standby Operation

Duty/Standby will alternately run two systems on 24 hour alternating run/standby. If a fault occurs on either system then both systems are switched on until the fault is cleared.

SW3 ON for

Duty/standby

Duty/Standby is achieved using two FDP2 devices, one with Address 0 and one with Address 1 with a D-BUS connection between the two. SW3 must be switched ON on both devices to enable the operation.

21

8 Units max

21

Address 0 (MASTER)

DUTY/STANDBY 1 Day 1 Day 1 Day FAULT

8 Units max

Address 0 (MASTER)

8 Units max

D-BUS

16 FDP2 max

Address 1 (SLAVE)

PRESET CONTROL

If the master is configured for Heat, Cool or Auto preset control then the

FDP2 slave units will operate to the same settings as the master. The diagram below shows the system configured for the Cool preset. See overleaf for SW1, SW2 settings for Heat and Auto presets.

18

8 Units max

18

Address 0 (MASTER)

D-BUS

16 FDP2 max

Address 1 (SLAVE)

8 Units max

D-BUS

16 FDP2 max

Address 1 (SLAVE)

The MASTER FDP2 can be configured using SW1 and SW2 to operate using one of the three preset modes Heat, Cool or Auto. Alternatively the

MASTER can be configured for local control, in which case the remote controller attached to the MASTER FDP2 can be used to set the operating settings during master duty.

Advanced control

More sophisticated control con be achieved using the FDP2-BMS interface, this provides a number of inputs that allow external control of unit operation, or connection to Building Management Systems. The

FDP2 interfaces can also be customised for specific operating requirements. Contact Toshiba for details.

Functional Specification

Electrical

Supply

Power

Relay

18V DC from TCC-NET

<1VA

1A, 24VAC max

1A, 30VDC max

Environmental

Temperature

Storage

Operation

Humidity

Mechanical

Dimensions

(mm)

Mounting

H72 x W87 x D19

Protection

EMC Emissions

EMC Immunity

Casing

Weight

Connectors

Two keyhole mounting flanges

Zinc coated mild steel

80g

Rising clamp to 0.75mm

2 cable

-10oC to 50oC

0oC to 50oC

0-90% RH non-condensing

IP30

EN61000-6-1

EN61000-6-3

9570-0 FDP2-F Installation & Operating Instructions issue 1.14.02 Copyright © RealTime Control Systems Limited. 2005

advertisement

Key Features

  • Fault monitoring
  • Preset control
  • Group control
  • Building Management System integration
  • Multiple configuration options
  • LED indicators for fault/no fault state
  • Relay contacts for fault reporting
  • Duty/Standby operation
  • D-Bus network for group control
  • TCC-NET connection for power and communication

Frequently Answers and Questions

What is the maximum number of units that can be connected to a single FDP2-F interface?
The FDP2-F can connect to up to 8 units on the TCC-NET network.
How do I configure the FDP2-F for different operating modes?
The FDP2-F has configuration switches SW1 to SW7 that allow you to set different operating modes. The factory configuration with all switches OFF sets the FDP2-F to operate as a standard fault monitoring device. You can also select preset Heat, Cool, and Auto modes using SW1 and SW2.
What is the purpose of the D-BUS network?
The D-BUS network allows you to connect multiple FDP2-F interfaces together to create large control groups for multiple units. Each FDP2-F is assigned a D-Bus address using switches SW4 to SW7. The FDP2-F with address 0 acts as the master and controls the settings for all other slave devices.

Related manuals

Download PDF

advertisement