Tyco MX4428 is a fire indicator system, which can be used to create a customized fire detection and alarm system. It can be programmed to meet the specific requirements of a building or site, and can be used to monitor a variety of fire detection devices, including smoke detectors, heat detectors, and manual call points. The MX4428 can also be used to control a variety of fire alarm devices, such as sounders, beacons, and door releases.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Tyco MXP 4428 Fire Alarm Systems Technical Manual | Manualzz

MX4428

MXP ENGINEERING / TECHNICAL MANUAL

MX4428 PRODUCT MANUAL

VOLUME 11

Document Number: LT0273

Issue 1.5; 24 March 2006

- APPROVALS -

AUSTRALIAN STANDARD AS4428.1

- SSL Listing Number ....................................................................................... afp1446

NEW ZEALAND STANDARD NZS4512-1997 (INCL AMDT 1 & 2)

- FPA (NZ) Listing number ................................................................................. VF/117

AS/NZS 3548 1995 CLASS A

The 4100MXP is a product of

Tyco Safety Products

211 Maces Road

Christchurch 8030

NEW ZEALAND

Phone +64-3-389 5096

Fax +64-3-389 5938

COPYRIGHT (C) 2003,2004

Information contained in this document is subject to copyright, and shall not be reproduced in any form whatsoever, without the written consent of Tyco Services Fire & Safety.

Information contained in this document is believed to be accurate and reliable, however Tyco

Services Fire & Safety reserves the right to change the content without prior notice.

MX4428 MXP Engineering /Technical Manual Document: LT0273

NON-DISCLOSURE AGREEMENT

Tyco (THE COMPANY) and the User of this/these document(s) desire to share proprietary technical information concerning electronic systems.

For this reason the company is disclosing to the User information in the form of this/these document(s). In as much as the company considers this information to be proprietary and desires that it be maintained in confidence, it is hereby agreed by the User that such information shall be maintained in confidence by the User for a period of

TEN YEARS after the issue date and only be used for the purpose for which it was supplied.

During this period, the User shall not divulge such information to any third party without the prior written consent of the company and shall take reasonable efforts to prevent any unauthorised disclosure by its employees.

However, the User shall not be required to keep such information in confidence if it was in their possession prior to its receipt from the company; if it is or becomes public knowledge without the fault of the User; or the information becomes available on an unrestricted basis from a third party having a legal right to disclose such information.

The User's receipt and retention of this information constitutes acceptance of these terms.

This information is copyright and shall not be reproduced in any form whatsoever.

END USER LIABILITY DISCLAIMER

The MX4428 Fire Indicator Panel provides a configuration programming facility, which may be accessed via a programming terminal using a password. Because this programming facility allows the user to define in detail the operation of the MX4428 System being customised, changes may be made by the user that prevent this installation from meeting statutory requirements.

The Company, therefore cannot accept any responsibility as to the suitability of the functions generated by the user using this programming facility.

AMENDMENT LOG

21 March 01

24 April 03

11 March 04

28 January 05

28 October 05

24 March 06

Issue 1.0

Issue 1.1

Issue 1.2

Issue 1.3

Issue 1.4

Issue 1.5

Original

Updated DIM800 Compatibility, added VLC800, LPS800, Alarm

Tests

DIM800 with s/c fault option. Added "specs", noted source of

MXPPROG, updated MXP software version history.

Added requirements for AS1670.1. Noted DIM800 supply supervision threshold is not adjustable. Added MIM800 max cable

length on inputs to its specs. Updated Table 3-2. Added 5B,

replaced 814IB with 5BI.

Noted MkII Sounder Base has AS2220 and ISO tones. Added note re acceptable type mismatches. Added reference to software version 1.12.

Added 614CH, 614I, 614P, System Sensor 885WP-B detectors to

Table 3-4.

Added 614T Section 3.20.3. Added 814P Section 3.9, etc. Added

Loop Filter Board, Chapter 10.

TRADEMARKS

VESDA is a registered trademark of Vision Systems.

Page ii 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

TABLE OF CONTENTS

NON-DISCLOSURE AGREEMENT....................................................................................................... II

END USER LIABILITY DISCLAIMER .................................................................................................... II

AMENDMENT LOG .............................................................................................................................. II

TRADEMARKS ..................................................................................................................................... II

CHAPTER 1 INTRODUCTION ...............................................................................1-1

1.1

ABOUT THIS MANUAL......................................................................................................... 1-2

1.2

ASSOCIATED DOCUMENTATION....................................................................................... 1-2

1.2.1

PRODUCT RELATED .................................................................................................... 1-2

1.2.2

STANDARD RELATED .................................................................................................. 1-3

1.3

SPECIFICATIONS ................................................................................................................. 1-3

1.4

TERMINOLOGY..................................................................................................................... 1-4

CHAPTER 2 RESPONDER LOOP DESIGN CONSIDERATIONS .........................2-1

2.1

MXP APPLICATION CONSIDERATIONS ............................................................................ 2-2

2.2

"LOGICAL" RESPONDERS ................................................................................................. 2-3

2.2.1

2.2.2

THEORY......................................................................................................................... 2-3

LOGICAL RESPONDERS.............................................................................................. 2-3

2.2.3

POINT TO CIRCUIT TO ZONE MAPPING .................................................................... 2-5

2.3

IMPLICATIONS TO SYSTEM DESIGN................................................................................. 2-6

CHAPTER 3 DEVICE INFORMATION AND PROGRAMMING..............................3-1

3.1

DEVICE TYPES ..................................................................................................................... 3-2

3.1.1

MX DEVICES.................................................................................................................. 3-2

3.2

DEVICE HANDLING CAPABILITY ....................................................................................... 3-7

3.2.1

OVERVIEW .................................................................................................................... 3-7

3.2.2

3.2.3

3.2.4

DC LOAD........................................................................................................................ 3-8

AC LOADING.................................................................................................................. 3-8

ISOLATOR BASE LOADING.......................................................................................... 3-9

3.2.5

EXAMPLE....................................................................................................................... 3-9

3.3

OUTPUT CONTROL............................................................................................................ 3-10

3.3.1

3.3.2

PROGRAMMING.......................................................................................................... 3-11

OUTPUT STATE UNDER EXCEPTIONAL CIRCUMSTANCES ................................. 3-11

3.4

DETECTOR PARAMETER SETTINGS SUMMARY........................................................... 3-12

3.5

DEVICE INSTALLATION..................................................................................................... 3-13

3.5.1

3.5.2

3.5.3

PRECAUTIONS............................................................................................................ 3-13

MOUNTING .................................................................................................................. 3-13

ADDRESS & LED BLINK PROGRAMMING ................................................................ 3-13

3.6

MX4428 PROGRAMMING................................................................................................... 3-14

3.7

814H HEAT DETECTOR ..................................................................................................... 3-15

3.7.1

3.7.2

GENERAL..................................................................................................................... 3-15

814H SPECIFICATIONS .............................................................................................. 3-15

3.7.3

MX4428 PROGRAMMING OPTIONS - 814H .............................................................. 3-15

3.8

814I IONISATION SMOKE DETECTOR ............................................................................. 3-17

3.8.1

3.8.2

GENERAL..................................................................................................................... 3-17

814I SPECIFICATIONS................................................................................................ 3-17

3.8.3

MX4428 PROGRAMMING OPTIONS - 814I................................................................ 3-17

3.9

814PH PHOTOELECTRIC SMOKE & HEAT DETECTOR & 814P PHOTOELECTRIC

SMOKE ONLY DETECTOR ............................................................................................................ 3-19

3.9.1

GENERAL..................................................................................................................... 3-19

3.9.2

3.9.3

814PH & 814P SPECIFICATIONS............................................................................... 3-19

MX4428 PROGRAMMING OPTIONS - 814PH/814P .................................................. 3-19

3.10

814CH CARBON MONOXIDE + HEAT DETECTOR.......................................................... 3-23

3.10.1

GENERAL..................................................................................................................... 3-23

3.10.2

3.10.3

814CH SPECIFICATIONS ........................................................................................... 3-23

MX4428 PROGRAMMING OPTIONS - 814CH ........................................................... 3-23

Issue 1.5 24 March 2006 Page iii

MX4428 MXP Engineering /Technical Manual Document: LT0273

3.11

MUB UNIVERSAL BASE .................................................................................................... 3-25

3.11.1

GENERAL..................................................................................................................... 3-25

3.11.2

3.11.3

MUB AND 5B WIRING ................................................................................................. 3-25

REMOTE INDICATOR WIRING ................................................................................... 3-25

3.12

5BI ISOLATOR BASE ......................................................................................................... 3-26

3.12.1

GENERAL..................................................................................................................... 3-26

3.12.2

3.12.3

SPECIFICATIONS........................................................................................................ 3-26

WIRING ........................................................................................................................ 3-26

3.13

814RB RELAY BASE .......................................................................................................... 3-28

3.13.1

GENERAL..................................................................................................................... 3-28

3.13.2

3.13.3

SPECIFICATIONS........................................................................................................ 3-28

WIRING ........................................................................................................................ 3-28

3.14

814SB SOUNDER BASE .................................................................................................... 3-30

3.14.1

GENERAL..................................................................................................................... 3-30

3.14.2

3.14.3

SPECIFICATIONS........................................................................................................ 3-30

WIRING ........................................................................................................................ 3-30

3.15

MKII SOUNDER BASE........................................................................................................ 3-31

3.15.1

GENERAL..................................................................................................................... 3-31

3.15.2

3.15.3

SPECIFICATIONS........................................................................................................ 3-31

WIRING ........................................................................................................................ 3-31

3.16

MIM800 AND MIM801 MINI INPUT MODULES .................................................................. 3-32

3.16.1

GENERAL..................................................................................................................... 3-32

3.16.2

3.16.3

MIM800 / MIM801 SPECIFICATIONS ......................................................................... 3-32

FIELD WIRING ............................................................................................................. 3-33

3.16.4

3.16.5

MX4428 PROGRAMMING OPTIONS - MIM800 / MIM801 ......................................... 3-33

MX4428 PROGRAMMING OPTIONS - MIM801.......................................................... 3-34

3.17

CIM800 CONTACT INPUT MODULE.................................................................................. 3-35

3.17.1

GENERAL..................................................................................................................... 3-35

3.17.2

3.17.3

CIM800 SPECIFICATIONS .......................................................................................... 3-35

FIELD WIRING ............................................................................................................. 3-36

3.17.4

MX4428 PROGRAMMING OPTIONS - CIM800 .......................................................... 3-36

3.18

CP820 MANUAL CALL POINT ........................................................................................... 3-38

3.18.1

3.18.2

GENERAL..................................................................................................................... 3-38

MX4428 PROGRAMMING OPTIONS - CP820............................................................ 3-38

3.19

FP0838 / FP0839 MANUAL CALL POINTS ....................................................................... 3-39

3.19.1

GENERAL..................................................................................................................... 3-39

3.19.2

MX4428 PROGRAMMING OPTIONS - FP0838 / FP0839 .......................................... 3-39

3.20

DIM800 DETECTOR INPUT MONITOR .............................................................................. 3-40

3.20.1

GENERAL..................................................................................................................... 3-40

3.20.2

DIM800 SPECIFICATIONS .......................................................................................... 3-41

3.20.3

3.20.4

DIM800 DETECTOR COMPATIBILITY........................................................................ 3-42

MX4428 PROGRAMMING OPTIONS - DIM800 .......................................................... 3-42

3.21

RIM800 RELAY INTERFACE MODULE ............................................................................. 3-43

3.21.1

GENERAL..................................................................................................................... 3-43

3.21.2

3.21.3

RIM800 SPECIFICATIONS .......................................................................................... 3-43

RIM800 FIELD WIRING ............................................................................................... 3-43

3.21.4

MX4428 PROGRAMMING OPTIONS - RIM800 .......................................................... 3-44

3.22

SNM800 SOUNDER NOTIFICATION MODULE ................................................................. 3-45

3.22.1

GENERAL..................................................................................................................... 3-45

3.22.2

3.22.3

3.22.4

SNM800 SPECIFICATIONS......................................................................................... 3-45

SNM800 FIELD WIRING .............................................................................................. 3-46

MX4428 PROGRAMMING OPTIONS - SNM800......................................................... 3-46

3.23

LPS800 LOOP POWERED SOUNDER MODULE.............................................................. 3-47

3.23.1

GENERAL..................................................................................................................... 3-47

3.23.2

3.23.3

LPS800 SPECIFICATIONS.......................................................................................... 3-47

MX4428 PROGRAMMING OPTIONS - LPS800.......................................................... 3-47

3.24

VLC-800MX VESDA LASERCOMPACT............................................................................. 3-49

3.24.1

GENERAL..................................................................................................................... 3-49

3.24.2

3.24.3

VLC800 SPECIFICATIONS.......................................................................................... 3-49

MX4428 PROGRAMMING OPTIONS - VLC800.......................................................... 3-50

3.25

AVF / RAD / SAD / FLOWSWITCH DELAYS ..................................................................... 3-51

3.25.1

AVF/RAD ...................................................................................................................... 3-51

Page iv 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

3.25.2

3.25.3

3.25.4

SAD .............................................................................................................................. 3-51

AVF/SAD ...................................................................................................................... 3-51

FLOWSWITCH ............................................................................................................. 3-51

CHAPTER 4 ANALOGUE LOOP DESIGN CONSIDERATIONS ...........................4-1

4.1

ANALOGUE LOOP CONFIGURATION SELECTION .......................................................... 4-2

4.1.1

LINES & LOOPS ............................................................................................................ 4-2

4.1.2

LOOP FAULT TOLERANCE .......................................................................................... 4-2

4.1.3

4.1.4

AS1670.1 DESIGN REQUIREMENTS........................................................................... 4-2

NZS4512 DESIGN REQUIREMENTS ........................................................................... 4-2

4.2

ANALOGUE LOOP/LINE LAYOUTS .................................................................................... 4-3

4.2.1

4.2.2

4.2.3

4.2.4

LINE MODE .................................................................................................................... 4-3

LOOP DESIGN WITH SHORT CIRCUIT ISOLATORS.................................................. 4-3

STAR CONNECTION OF ANALOGUE LINES .............................................................. 4-5

SPURS ........................................................................................................................... 4-5

4.3

CABLE SELECTION CONSIDERATIONS............................................................................ 4-6

4.4

AC REQUIREMENTS ............................................................................................................ 4-7

4.4.1

GENERAL....................................................................................................................... 4-7

4.5

DC CONSIDERATIONS......................................................................................................... 4-7

4.5.1

GENERAL....................................................................................................................... 4-7

4.6

MECHANICAL CONSIDERATIONS ..................................................................................... 4-7

4.7

NOISE CONSIDERATIONS .................................................................................................. 4-8

CHAPTER 5 MXP CURRENT CONSUMPTION .....................................................5-1

5.1

THEORY ................................................................................................................................ 5-2

5.1.1

ALARM CURRENT......................................................................................................... 5-2

5.1.2

QUIESCENT CURRENT ................................................................................................ 5-3

5.1.3

HEAT LOSS.................................................................................................................... 5-3

CHAPTER 6 EVENT LOG AND STATUS AT MX4428 ..........................................6-1

6.1

RETURNED ANALOG VALUES ........................................................................................... 6-2

6.2

FAULT AND ALARM EVENT LOG....................................................................................... 6-3

CHAPTER 7 MXP TECHNICAL DESCRIPTION ....................................................7-1

7.1

GENERAL.............................................................................................................................. 7-2

7.2

CIRCUIT DESCRIPTION ....................................................................................................... 7-3

7.2.1

BLOCK DIAGRAM.......................................................................................................... 7-3

7.2.2

7.2.3

7.2.4

7.2.5

MICROPROCESSOR & LOGIC CIRCUITRY ................................................................ 7-3

MXP POWER SUPPLY .................................................................................................. 7-4

MX4428 LOOP INTERFACE.......................................................................................... 7-6

ANALOGUE LOOP INTERFACE ................................................................................... 7-7

7.3

MXP ADJUSTMENTS.......................................................................................................... 7-10

7.3.1

40V ISO SUPPLY VOLTAGE ADJUSTMENT ............................................................. 7-10

7.3.2

7.3.3

TX DATA VOLTAGE ADJUSTMENT ........................................................................... 7-10

40V ISO SUPPLY CURRENT LIMIT ADJUSTMENT................................................... 7-10

7.4

MXP LED INDICATIONS ..................................................................................................... 7-11

7.5

PARTS LIST ........................................................................................................................ 7-12

CHAPTER 8 MXP DIAGNOSTIC TERMINAL ........................................................8-1

8.1

MXP DIAGNOSTIC TERMINAL OPERATION...................................................................... 8-2

8.1.1

INTRODUCTION ............................................................................................................ 8-2

8.1.2

8.1.3

MENU OF COMMANDS................................................................................................. 8-2

SELECTING POINTS FOR MONITORING.................................................................... 8-2

8.1.4

8.1.5

8.1.6

8.1.7

8.1.8

DISPLAYING DEVICE ANALOGUE VALUES - CV, TV, ETC ....................................... 8-3

ST (STATUS COMMAND) ............................................................................................. 8-5

ANALOG LOOP DIAGNOSTICS.................................................................................... 8-6

ADVANCED COMMANDS ............................................................................................. 8-8

MX4428 DIAGNOSTICS ................................................................................................ 8-8

Issue 1.5 24 March 2006 Page v

MX4428 MXP Engineering /Technical Manual Document: LT0273

8.1.9

MXP EVENT LOG .......................................................................................................... 8-9

8.2

FLASH PROGRAMMING .................................................................................................... 8-10

8.2.1

8.2.2

FILES REQUIRED........................................................................................................ 8-10

PROCEDURE............................................................................................................... 8-10

CHAPTER 9 DEVICE PROCESSING.....................................................................9-1

9.1

EXPONENTIAL FILTER ........................................................................................................ 9-2

9.2

STEP LIMITING FILTER........................................................................................................ 9-2

9.3

HEAT PROCESSING............................................................................................................. 9-4

9.3.1

CONVERSION OF DETECTOR READING TO

°C........................................................ 9-4

9.4

PHOTO PROCESSING.......................................................................................................... 9-6

9.4.1

9.4.2

SMARTSENSE PROCESSING...................................................................................... 9-6

SMARTSENSE ENHANCEMENT .................................................................................. 9-6

9.4.3

FASTLOGIC PROCESSING .......................................................................................... 9-7

9.5

CO PROCESSING ................................................................................................................. 9-8

9.5.1

9.5.2

CALIBRATION AND TEMPERATURE COMPENSATION ............................................ 9-8

“ENHANCEMENT” ......................................................................................................... 9-8

9.5.3

CO PROCESSING ......................................................................................................... 9-8

9.6

IONISATION PROCESSING ................................................................................................. 9-9

9.7

MIM800 / CIM800 / MIM801 PROCESSING........................................................................ 9-10

9.7.1

ALGORITHM - MIM800, CIM800 ................................................................................. 9-11

9.7.2

ALGORITHM - MIM801 ................................................................................................ 9-11

9.8

DIM PROCESSING.............................................................................................................. 9-12

9.8.1

9.8.2

9.8.3

9.8.4

LOAD GRAPH .............................................................................................................. 9-12

DIM MODEL ................................................................................................................. 9-12

ALGORITHM - DIM800 ................................................................................................ 9-12

SUPPLY MONITORING - DIM800 ............................................................................... 9-13

9.9

RIM PROCESSING.............................................................................................................. 9-13

9.9.1

POSITION MONITORING ............................................................................................ 9-13

9.10

SNM PROCESSING ............................................................................................................ 9-13

9.10.1

PROGRAMMING.......................................................................................................... 9-13

9.10.2

9.10.3

SUPPLY FAULT DETERMINATION ............................................................................ 9-13

EOL AND POSITION MONITORING ........................................................................... 9-13

9.11

LPS PROCESSING ............................................................................................................. 9-14

9.11.1

ELD AND POSITION MONITORING ........................................................................... 9-14

9.12

VLC800 PROCESSING ....................................................................................................... 9-14

9.12.1

GENERAL..................................................................................................................... 9-14

9.13

FILTER STEP LIMITS.......................................................................................................... 9-15

9.14

ZONE ALARM TEST ........................................................................................................... 9-15

9.15

ZONE FAULT TEST ............................................................................................................ 9-15

9.16

AUTOTEST AND SYSTEM TEST ....................................................................................... 9-15

9.17

NON LATCHING TEST MODE............................................................................................ 9-16

9.18

COMMISSION MODE .......................................................................................................... 9-16

9.19

FAST POINT TEST.............................................................................................................. 9-16

9.20

SLOW POINT TEST ............................................................................................................ 9-16

9.21

SUMMARY OF ALL TEST MODES .................................................................................... 9-16

9.22

ANCILLARY FILTERING..................................................................................................... 9-17

9.23

RESET ................................................................................................................................. 9-18

9.23.1

RESET OF ADDRESSABLE DETECTOR ................................................................... 9-18

9.23.2

9.23.3

RESET OF DIM MODULE............................................................................................ 9-18

RESET OF ANCILLARY INPUT DEVICE .................................................................... 9-18

9.23.4

RESET OF ANCILLARY OUTPUT DEVICE ................................................................ 9-18

9.24

DEVICE INITIALISATION AND POLLING.......................................................................... 9-19

9.25

SOFTWARE VERSIONS ..................................................................................................... 9-20

CHAPTER 10 MXP LOOP FILTER BOARD ........................................................10-1

10.1

USE OF MXP LOOP FILTER BOARD ................................................................................ 10-2

10.2

FITTING ............................................................................................................................... 10-2

10.3

DIAGNOSTICS .................................................................................................................... 10-3

Page vi 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Introduction

CHAPTER 1

INTRODUCTION

Issue 1.5 24 March 2006 Page 1-1

MX4428 MXP Engineering / Technical Manual

Introduction

1.1 ABOUT THIS MANUAL

Document: LT0273

This manual (MX4428 Product Manual Volume 11) is intended to provide all information and procedures required to incorporate one or more MXPs within an MX4428 system. It predominantly covers the function and engineering associated with the MXP itself, its impact on the MX4428 Responder Loop and the analogue loop/line(s) to which the compatible devices are connected. It does not duplicate basic MX4428 system engineering information, except at the point of interface (i.e. at the MX4428 Responder Loop), or for clarification as required. It is therefore a supplement to the F4000 Engineering Manual (F4000 Product

Manual, Vol 3), to which the reader is referred for further information.

1.2 ASSOCIATED DOCUMENTATION

The following MX4428/F4000 product manuals are available:

Volume 1,

F4000 Operator's Manual, provides a complete guide to the operation and maintenance of the F4000 FIP and

RDU

panels, with Version 1.X software, according to

Australian Standards AS1603 Part 4. This manual is provided as standard with non-LCD

F4000 FIP panels (LT0057). See Volume 10 for AS4428.1 compliant systems.

Volume 2,

F4000 Technical Manual, provides complete technical details on the F4000 system and Hardware/Software components, according to Australian Standards AS1603

Part 4, for servicing purposes (LT0069).

Volume 3,

F4000 Engineering Manual, provides complete design details for correctly engineering the F4000/MX4428 system to meet customer and standard specifications

(LT0071).

Volume 4,

F4000 Installation Manual, provides complete details for correctly installing and placing into operation the F4000/MX4428 system (LT0070).

Volume 5,

F4000 Programming Manual, provides details for correctly programming the

F4000/MX4428 system to meet the system engineering specifications (LT0072).

Volume 6,

F4000 AAR Technical & Engineering Manuals, Volume 6-1 provides

Technical details on the AAR and Addressable Devices, and Volume 6-2 provides

Engineering Design information for correctly engineering the AAR loop (LT0095/LT0096).

Volume 7,

F4000 LCD Operator's Manual, provides a complete guide to the operation and maintenance of F4000 LCD FIP panels with Version 2.X software, according to

Australian Standards AS1603 Part 4, AS4050(INT), and New Zealand Standard NZS4512.

From Issue 2.35A onwards LT0117 includes networked operation, previously covered in a separate manual LT0150 (LT0117/LT0118). See Volume 10 for AS4428.1 compliant systems.

Volume 8,

F4000 NZ Fire Indicator Panel Technical Manual, provides additional installation and technical information regarding the application of F4000/MX4428 Analogue

Addressable Fire Alarm Systems in New Zealand (LT0126).

Page 1-2 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Introduction

Volume 9,

F4000 MPR Technical & Engineering Manuals, Volume 9-1 provides technical details on the MPR and Addressable devices, and Volume 9-2 provides

Engineering Design information for correctly engineering the MPR loop (LT0139/LT0140).

Volume 10, MX4428 AS4428.1 LCD Operator’s Manual, provides a guide to the operation and maintenance of MX4428 AS4428.1 LCD FIP panels with Version 3.10 software, according to Australian Standard AS4428.1, and New Zealand Standard NZS4512.

This manual (LT0249) is provided as standard with MX4428 panels.

Volume 11, MX4428 MXP Technical / Engineering Manual, (LT0273) provides technical details on the MXP and its addressable devices, and provides engineering design information for correctly engineering the MXP loop.

F4000 Point Text Installation & Operation Manual (LT0228) provides details of the Point

Text expansion option.

SmartConfig User Manual (LT0332) provides details on programming an MX4428 database using the SmartConfig program.

This manual makes reference to the following Australian Standards –

AS1603.4 Automatic Fire Detection and Alarm Systems

Part 4 - Control and Indicating Equipment

AS1670.1 Automatic Fire Detection and Alarm Systems-

System Design, Installation, and Commissioning.

AS1851.8 Maintenance of Fire Protection Equipment

Part 8 - Automatic Fire Detection and Alarm Systems.

AS4428.1 Automatic Fire Detection and Alarm Systems. Control and Indication

Equipment.

This manual makes reference to the following New Zealand Standard –

NZS4512 Automatic Fire Alarm Systems in Buildings.

1.3 SPECIFICATIONS

Inputs / Outputs 1. Standard F4000 / MX4428 Responder Loop.

2. Analogue Loop for up to 200 MX devices, with a maximum output current = 400mA.

Card Size

Supply Voltage

Current Consumption

3. RS232 Diagnostics Port.

194mm * 140mm * 35mm.

17.0VDC to 30.0VDC.

50mA to 1.3A depending on the number and type of

devices connected. Refer to section 5.1.

Operating Temperature Range -5

°C to +50°C, 10% to 93% RH non condensing.

Issue 1.5 24 March 2006 Page 1-3

MX4428 MXP Engineering / Technical Manual

Introduction

1.4 TERMINOLOGY

Document: LT0273

ACZ

ADR

Analogue Loop

ARR

AVF

AZF

CV

Detector

EOL

Evacuation Device

FIP

GLOBAL

HH

HL

LCD

LED

MAF

MIC X

MPR

MXP

MCP

Module

NLR

PCB

Point

PSU

Responder

Responder Loop

ROR

RRM

RZDU

Sensor

SLV

Zone

Page 1-4

Ancillary Control Zone.

Advanced Detector Responder.

The wiring that allows an MXP to communicate with and supply power to the addressable devices it is to monitor.

Advanced Relay (and Detector) Responder, which is an ADR fitted with an RRM.

Alarm Verification Facility, or alarm check.

Alarm Zone Facility, previously referred to as "GROUP".

Current Value (Filtered reading from detector)

Addressable device used to detect fires that interfaces to the

MXP via the Analogue Loop. It contains one or more sensors.

End of Line device.

Sounder for warning of evacuation.

Fire Indicator Panel, as defined by standards.

A function that may affect more than one zone.

History High - the highest value a variable has reached

History Low - the lowest value a variable has reached.

Liquid Crystal Display (usually alphanumeric)

Light Emitting Diode (Visual Indicator).

FIP Master Alarm Facility.

Measure of smoke density used with ionisation smoke detectors.

Multi Protocol Responder.

MX Protocol Responder

Manual Call Point (break glass switch).

Addressable I/O device that interfaces to the MXP via the

Analogue Loop.

Number of logical responders.

Printed Circuit Board.

Any addressable device (detector or module) with a unique address that is connected to the analogue addressable loop.

Power Supply Unit.

A general term for all responder types, e.g. ADR, ARR, MPR,

MXP, AAR and IOR that may be connected to the MX4428

Loop.

A 4 core cable for communication and power to all responders connected to an MX4428 FIP.

Rate of Rise.

Responder Relay Module.

Remote Zone Display Unit.

Part of a detector which senses the environment - smoke or temperature or CO.

Step limited (or slope limited) value.

Fire searchable area of Building.

24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Responder Loop Design Considerations

CHAPTER 2

RESPONDER LOOP DESIGN

CONSIDERATIONS

Issue 1.5 24 March 2006 Page 2-1

MX4428 MXP Engineering / Technical Manual

Responder Loop Design Considerations

Document: LT0273

2.1 MXP APPLICATION CONSIDERATIONS

The inclusion of one or more MXPs in an MX4428 system requires consideration of .....

(i) The definition of zones throughout the area to be protected.

(ii) Assessment of the detectors and other addressable device types and positions required to monitor each zone and interface to external equipment. This will indicate if and where the MXP's addressable devices are most appropriate, for purely functional reasons or for reducing system cost through reduced wiring.

The Design Engineer should be fully familiar with the concept of logical responders,

as described in Section 2.2, before allocating an MXP to monitor multiple alarm

zones.

This process should result in an initial system design defining .....

-

-

-

-

Number and location of all Responders including MXPs.

Number and location of all addressable devices.

Planned cable route for MX4428 Responder Loop.

Planned cable route(s) for MXP Analogue Loop(s).

(iii) Using the design rules given in this manual, analyse each MXP Analogue Loop/Line to confirm .....

- the MXP's current capability is adequate for the proposed devices (see

Section 3.2).

-

the proposed cable has the correct AC characteristics (see Section 4.4).

-

the proposed cable has the correct DC characteristics (see Section 4.5).

(iv) Using Section 5 of this manual, in conjunction with the MX4428 Engineering Manual

(LT0071), analyse the MX4428 responder Loop. This should result in.....

- the type and size of cable to be used for the power and signal portions of the

MX4428 Responder Loop.

- the number and position of Loop Boosters required (if necessary).

(v) The results of (iii) and (iv) indicate whether or not the proposed system design is practical and/or cost-effective. If not, analyse what factors have contributed to the design being impractical, re-design these areas or consider the use of loop boosters and return to step (i).

(vi) Assess and document the programming of the MX4428 Master to support the system design. Programming of the MX4428 is covered in the MX4428 Programming Manual

LT0072, with additional details of using SmartConfig in the SmartConfig user manual

LT0332. The following data must be entered to support MXPs.

-

- information which, when downloaded to the MXP, defines how the MXP is to process the data received from addressable devices on the Analogue

Loop/Line(s), information retained at the Master which defines how it is to process data received from configured MXPs on the MX4428 Loop.

Page 2-2 24 March 2006 Issue 1.5

Document: LT0273

2.2

MX4428 MXP Engineering / Technical Manual

Responder Loop Design Considerations

"LOGICAL" RESPONDERS

2.2.1 THEORY

The MX4428 Master Panel can transfer data to and from up to 127 uniquely addressed

Responders distributed around the MX4428 Responder Loop. Its database is structured to support the 4 circuit inputs and 4 relay outputs associated with the most common responder type, the ADR. Incorporating an MXP, which supports up to 200 input, output, or input / output points, represents a departure from the original ADR / AAR structure, but it is similar to that used for the MPR multiprotocol responder.

To incorporate the MXP, while still preserving the original 1 x MX4428 LOOP ADDRESS

SUPPORTS 4 INPUTS (“CIRCUITS”) AND 4 OUTPUTS (“RELAYS”) database assumption, the concept of "logical responders" is used. A logical responder refers to a single responder loop number, supporting 4 inputs and 4 outputs. An ADR/ARR therefore represents a single logical responder. A responder that supports more than 4 inputs and outputs, such as the

MXP, must therefore occupy multiple responder loop numbers. That is, it is a "multiple logical responder" unit. One MXP may in fact be configured at the MX4428 FIP to be between 1 and 50 logical responders.

Since an MXP can support up to 200 points irrespective of how many logical responders it has been configured to represent, it may be necessary to allocate multiple points to each logical responder circuit input or relay output. This has certain implications described below, the most significant being that it is a logical responder “circuit” which is mapped to a zone, not a point, and it is a logical responder “relay” which is mapped to an ACZ, not a single output point. Thus if multiple devices are allocated to a circuit, they must all be in the same zone, and if multiple outputs are allocated to a relay, they will generally be controlled as one.

2.2.2 LOGICAL RESPONDERS

Points map to logical responder circuits and relays as shown in Table 2-1 for different

numbers of logical responders.

Basically the 200 points are evenly distributed across the number of logical responder circuits/relays (= number of logical responders * 4), with the remainder allocated to the last circuit.

Input devices are map to the circuit. Output devices usually map to the relay, but may map to the circuit by programming.

The 50 logical responder option is the only one that allows unique monitoring and full front panel indication of all 200 individual points without using the MX4428 Point Text expansion option. The 50 logical responder option however, uses 50 of the 127 available MX4428 responder loop addresses and therefore limits the remainder of the MX4428 system.

Figure 2.1 shows an example 3 logical responder MXP, which has a capability of 3 X 4 = 12

circuits (C1/1-1/4, C2/1-2/4, C3/1-3/4) and 12 relays (R1/1-1/4 ..... R3/4).

Splitting up the possible 200 addressable devices equally among the 12 circuits results in each circuit being able to service 200/12 = 16 devices, with 8 left over. Thus devices 1-16 are associated with circuit C1/1, devices 17-32 are associated with C1/2, etc, up to C3/4, which not only handles its own 16 points but also the extra 8 device addresses (193-200) otherwise not catered for. Input devices are mapped to circuits, and output devices are usually mapped to relays but may alternatively be mapped to the circuit.

Issue 1.5 24 March 2006 Page 2-3

MX4428 MXP Engineering / Technical Manual

Responder Loop Design Considerations

Number of Logical

Responders

(NLR)

17

18

19

20

21

22

9

10

11

12

13

14

15

16

5

6

7

8

1

2

3

4

31

32

33

34

35

36

23

24

25

26

27

28

29

30

37

38

39

40

41

42

43

44

45

46

47

48

49

50

Number of Circuits (Relays) available

(NC = 4 * NLR)

68

72

76

80

84

88

36

40

44

48

52

56

60

64

4

8

12

16

20

24

28

32

124

128

132

136

140

144

92

96

100

104

108

112

116

120

148

152

156

160

164

168

172

176

180

184

188

192

196

200

Number of Points per circuit

(relay)

PC = 200/NC

2

2

2

2

2

2

3

3

3

3

5

5

4

4

50

25

16

12

10

8

7

6

1

1

1

1

1

1

1

1

1

1

2

2

2

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

Document: LT0273

Table 2-1 Point Allocation For Various Numbers of Logical Responders

Total Quantity of Points in Last Circuit

21

17

13

9

5

1

53

49

45

41

37

33

29

25

77

73

69

65

61

57

18

10

2

97

93

89

85

81

66

58

50

42

34

26

25

5

28

12

47

35

23

11

50

25

24

20

10

16

11

14

Page 2-4 24 March 2006 Issue 1.5

Document: LT0273

TOTAL OF

200 DEVICES

DEVICE 1-16

DEVICE 17-32

DEVICE 33-48

DEVICE 49-64

DEVICE 65-80

DEVICE 81-96

DEVICE 97-112

MX4428 MXP Engineering / Technical Manual

Responder Loop Design Considerations

F4000 LOOP

ANALOG LOOP

MAPPED

TO

C1/1 R1/1

C1/2 R1/2

C1/3 R1/3

LOGICAL

RESPONDER

#1

C1/4 R1/4

C2/1 R2/1

C2/2 R2/2

C2/3 R2/3

LOGICAL

RESPONDER

#2

C2/4 R2/4

F4000

MASTER

DEVICE 113-128

DEVICE 129-144

DEVICE 145-160

DEVICE 161-176

DEVICE 177-200

C3/1 R3/1

C3/2 R3/2

LOGICAL

RESPONDER

#3

C3/3 R3/3

C3/4 R3/4

ANALOG LOOP

F4000 LOOP

3 LOGICAL RESPONDER MXR

Figure 2.1 Device To Circuit Mapping For 3 Logical Responder MXP

POINT TO CIRCUIT TO ZONE MAPPING 2.2.3

Taking the 3 logical responder example in the previous sections, assume that of the 16 possible device addresses that belong to C1/1, only 10 of these are in fact used, and that 7 are input devices, and the remaining 3 are output devices. Further, assume that the

MX4428 FIP is configured to map C1/1 to ZONE 1.

In this case, an alarm sensed by any of the 7 input devices would put C1/1 into alarm, which in turn would put ZONE 1 into alarm, a condition indicated on the MX4428 Master front panel. However, the MXP also generates what is referred to as an extended event, indicating precisely which of the 7 input devices caused the alarm. This is transmitted to the

MX4428 Master where it is presented on the front panel LCD, entered in the history log and printed on the logging printer (if programmed).

If, for instance, in this example it was input device 6 that caused the ALARM then the extended event would take the form .....

"P1/6 ALARM" where .....

..... P = POINT

1 = BASE ADDRESS OF RESPONDER

6 = DEVICE NUMBER

If the Point Text expansion option is fitted at the MX4428 Master, the event will be associated with a text description of the point.

Issue 1.5 24 March 2006 Page 2-5

MX4428 MXP Engineering / Technical Manual

Responder Loop Design Considerations

Document: LT0273

So far only input devices have been considered. To continue our example for output devices, if the MX4428 Master generated an output command, via output logic, to turn on

R1/1, then the MXP would activate all output devices associated with that relay, that is, in this case, all 3.

2.3 IMPLICATIONS TO SYSTEM DESIGN

The System Designer should be aware of the following MX4428 characteristics before proceeding with the design .....

(i) While the MX4428 with MXP capability can support up to 16 x 200 (3,200) points (i.e. addressable devices), the Master unit has a maximum of 528 zones with which to indicate the status of the system.

The 528 zones may be used to display the status of either an "alarm zone", representing the status of a particular sub-section of the area to be monitored, or an

"ancillary control zone" (ACZ), representing the status of an output controlled by the

MX4428 system.

The Point Text expansion option can be used to extend this capability. Refer to the

F4000 Point Text Installation and Operation Manual (LT0228) for further information.

(ii) FIP zone indicators are controlled according to the zone’s status, which is generated from the mapped circuit status. That is, the 4 circuits monitored by each of the 127 logical responders can control a maximum of 4 x 127 = 508 unique zones.

The point handling capability of an MX4428 system requiring individual LED indicators per monitored point is therefore reduced to 508.

Therefore, the more individual LED indications that the FIP must show for each MXP the more logical responders that MXP must represent.

Every additional 4 zones that must be indicated for the addressable devices on an

MXP incurs a cost of 1 additional logical responder (i.e. MX4428 responder loop address).

(iii) For the same reasons as given in (ii) above, the more individually controllable output devices the MXP must drive and control from logic, the more logical responders the

MXP must represent.

Page 2-6 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

CHAPTER 3

DEVICE INFORMATION AND PROGRAMMING

Issue 1.5 24 March 2006 Page 3-1

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.1 DEVICE TYPES

Document: LT0273

The MXP can communicate with a mix of up to 200 addressable devices, within limits defined by loop size.

MX devices fall into three basic types:

(a) Sensors - Detectors (814PH, 814CH, 814I, 814H, VLC800)

(b) Ancillaries -

-

-

Input (Monitor) (MIM800, MIM801, CIM800, DIM800)

MCP (CP820, FP0838, FP0839)

Output (Control) (RIM800, SNM800, LPS800)

(c) Bases

-

-

-

-

Standard Base (MUB, 5B)

Short Circuit Isolator (5BI)

Relay Base (814RB)

Sounder Base (814SB, MkII Sounder Base)

In addition non-addressable smoke, thermal or flame detectors may be connected to the

MXP loop by means of the DIM800 Detector Input Module.

Code Description

814PH

Output

Photoelectric Smoke + Heat Detector I/O

LED

Y

814CH Carbon Monoxide + Heat Detector I/O

814I Ionisation Detector

Y

VLC800 Vesda Aspirating smoke detector

MIM800 Mini Input Module

MIM801 Mini Input Module normally closed interrupt (FP0837)

CP820 Manual Call Point

FP0838

FP0839

NZ Manual Call Point

CIM800 Contact Input Module

I/O Y

I/O Y

Input

Input

Input

Input

DIM800 Detector Input Module

Input

Input

RIM800 Relay Interface Module (unsupervised load wiring)

Output

SNM800 Sounder Notification Module (relay output with supervised load wiring)

Output

The devices above are addressed by the or by command from the diagnostics terminal of an MXP.

Page 3-2 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

The standard base for use with the 814 detectors is:

MUB Minerva Universal Base (4”)

5B Minerva Universal Base (5”)

The following special purpose bases may also be used.

MkII Sounder Base

(802SB, 812SB, 901SB, and 912SB)

Sounder Base

The 814RB and 814SB may be plugged into an MUB, 5B or a 5BI, or mounted directly on a wall / ceiling.

Note that none of the bases are addressable devices. The functional bases (814RB, 814SB, and MkII Sounder Base) are controlled by the MXP via the detector which is plugged into them.

The devices above marked as “Input/Output” are always inputs, but may also be used as outputs via the Remote Indicator output and the signal to the 814RB, 814SB, and MkII

Sounder Base functional bases. The output functionality is programmable and not necessarily related to the input status.

The devices which have a remote LED output may drive a Tyco E500Mk2 remote LED. The functionality of this LED is programmable and it does not necessarily follow the local LED.

A brief description of the capabilities of each device follows:

a)

814I Analogue Ionisation Smoke Detector

This unit uses an ionisation chamber (with a small radioactive source) to detect airborne particles of combustion products.

b)

814H Analogue Heat Detector

This detector incorporates a temperature sensor. The temperature sensor processing may be programmed as Type A (rate of rise plus fixed temperature = 63

°C), Type B (fixed temperature only = 63

°C), Type C (rate of rise plus fixed temperature = 93°C), or Type D

(fixed temperature only = 93

°C). Type A, B, C or D operation is programmable at the

MX4428 panel.

c) 814PH Analogue Photoelectric Smoke Detector + Heat Detector

This unit uses light scattering to detect airborne particles of combustion products, and in addition incorporates a temperature sensor. The heat function may be programmed in the same way as for the 814H detector.

d) 814P Analogue Photoelectric Smoke Detector

This unit uses light scattering to detect airborne particles of combustion products.

Issue 1.5 24 March 2006 Page 3-3

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

e) 814CH Analogue CO (Carbon monoxide) Detector + Heat Detector

This unit uses a special sensor to detect carbon monoxide, and in addition incorporates a temperature sensor. The heat function may be programmed in the same way as for the

814H detector.

f) Mini Input Module MIM800

This unit has a single input for monitoring clean contacts (e.g. MCPs, flow switches conventional detectors with hard contact outputs, relay contacts, switches). As well as monitoring the state of the contacts the MIM800 can supervise the wiring for open circuit fault and (optionally) short circuit fault.

g) Mini Input Module MIM801

This unit has a single input for monitoring clean contacts (e.g. MCPs, flow switches, conventional detectors with hard contact outputs, relay contacts, switches). As well as monitoring the state of the contacts the MIM801 can supervise the wiring for short circuit fault and (optionally) open circuit fault. The MIM801 is very similar to the MIM800, however it is optimised for normally closed applications and can generate an interrupt on an open circuit. (Interrupt is only used when a fast response is required.) (The MIM800 and CIM800 can also generate interrupts, but only in response to closing contacts.)

h) Contact Input Module CIM800

This unit has two separate inputs for monitoring switch or relay contacts (e.g. MCPs, flow switches, conventional detectors with hard contact outputs, relay contacts, switches). As well as monitoring the state of the contacts the CIM800 can supervise the wiring for open circuit fault and (optionally) short circuit fault. Although there are two separate inputs, both belong to the same point. Either input in alarm will put the point into alarm, and either input in fault will put the point into fault. Unused inputs must be terminated with a 200

Ω resistor.

i) Detector Input Module DIM800

This unit has two separate inputs for monitoring conventional detectors. As well as monitoring the state of the detectors they can supervise the wiring for open circuit faults.

Although there are two separate inputs, both belong to the same point. Either input in alarm will put the point into alarm, and either input in fault will put the point into fault. An external power supply is required. The voltage requirements for some conventional detector types

are very specific. (Refer to section 3.20).

j) Australian Call Point Module CP820

This unit consists of a MIM800 complete with a call point switch and break-glass housing.

k) New Zealand Call Point Module FP0838, FP0839

This unit consists of a MIM801 complete with a call point switch and break-glass housing.

FP0838 is flush mounting while FP0839 is surface mounting.

l) Relay Interface Module RIM800

This unit has voltage free changeover relay contacts rated at 2A 30Vdc for external loads.

No supervision of load wiring is provided. However the relay position is supervised and a

“relay checkback fail” fault will be generated if it does not operate.

Page 3-4 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

m) Sounder Notification Module SNM800

This unit has a relay rated at 2A 30Vdc for switching external loads. Supervision of load wiring and the load supply is provided. The relay position is supervised and a “relay checkback” fault will be generated if it does not operate.

n) Short Circuit Isolator 5BI

This detector base is designed for isolating short circuited sections of the analog loop. For instance it can be used where the loop wiring crosses zone boundaries and it will prevent a short circuit from affecting more than one zone. As well as housing a detector it can be used with no detector inserted.

o) Sounder Base 814SB and MkII Sounder Base

These detector bases are designed as low cost warning devices. The MkII Sounder Base is a newer version of the 814SB. Some variants are loop powered while others are powered by an external supply. The sounder is controlled by the detector which is plugged into the base, but the operation of the sounder can be quite separate from the operation of the detector.

The 814SB can be setup to generate a number of tones (none of which are AS2220 or

ISO8201 compliant), and three sound levels are selectable.

The MkII Sounder Base models can be setup to generate a number of tones including

AS2220 and ISO8201 compliant evacuation tones, and on some models the sound level is continuously adjustable. Currently none of the MkII Sounder Base models are SSL listed.

Note that the current taken by a loop powered sounder base is very much higher than any of the other loop devices (except the LPS800), and the number of sounder bases on a loop is limited by the available current.

This detector base is designed for a low cost output device. It is controlled by the detector which is plugged into it, but the operation of the relay can be quite separate from the operation of the detector. A voltage two pole changeover relay is provided, rated at 1A 30V dc.

q) Loop Powered Sounder LPS800

This device is similar to the SNM800, in that it drives one or more external sounders, however the sounder power comes from the loop rather than an external power supply. The available output current is much lower than that of a SNM800, and as all this current comes from the loop, the number of LPS800s and their load is limited by the available loop current.

The Vision Systems VLC800-MX VESDA Laser COMPACT is an aspirating smoke detector.

It samples the smoke from air which is extracted via piping from a large area of a building.

The sensitivity is adjustable over a wide range at the VLC800 by PC software programme.

The VLC800 requires a 24V power supply.

A summary of the electrical specifications of the various devices is shown in Table 3-1.

Issue 1.5 24 March 2006 Page 3-5

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

All loop devices are rated at a loop voltage of 20Vdc - 40Vdc and a signalling voltage of 2V p-p – 6V p-p. Alarm Currents specified do not include remote indicators. Add 7mA for each remote indicator.

DEVICE FUNCTION

CP820

FP0838, FP0839

RIM800

MkII

Sounder

Bases

814I

814H

814PH

814P

814CH

MIM800

MIM801

CIM800

DIM800

SNM800

LPS800

MUB

5BI

814SB

802SB

812SB

901SB

912SB

814RB

VLC800

Ionisation Smoke Detector

Heat Detector

Photo Smoke + Heat

Detector

Photo Smoke Detector

CO + Heat Detector

Mini Input Module

Mini Input Module

(normally closed interrupt)

Contact Input Module

(Conventional) Detector

Interface Monitor

Call Point

NZ Call Point

Relay Interface Module

Sounder Notification

Module (Supervised relay output)

Loop Powered Sounder

Module

Standard Base

Isolator Base

Loop Powered Sounder

Base

Loop Powered Sounder

Base

Loop Powered Sounder

Base

Externally Powered

Sounder Base

Externally Powered

Sounder Base

Relay Base

Vesda aspirating smoke detector

Requires base

Requires base

Requires base

Requires base

Comments

Requires base

EOL 200

Ω

Alarm R (if used) 100

Ω

Max Wiring R 10

Ω

N/O mode - as MIM800

N/C -

EOL 200

Ω

Max wiring R 50

Ω

EOL 200

Ω

Alarm R (if used) 100

Ω

Max Wiring R 10

Ω

EOL 4k7

Requires separate supply.

2A 30Vdc

2A 30Vdc.

Requires external supply.

Provides 24V at up to 75mA

Selectable tone (not AS2220 or ISO8201)

Adjustable sound level

Selectable tone (Including AS2220 and ISO

8201 Evacuation tone)

Adjustable sound level

Selectable tone (Including AS2220 and ISO

8201 Evacuation tone)

Selectable tone (Including AS2220 and ISO

8201 Evacuation tone)

Adjustable Sound Level.

Requires external 24V

Selectable tone (Including AS2220 and ISO

8201 Evacuation tone)

Requires external 24V

1A 30Vdc

2 pole changeover

Requires external supply. Requires PC to set up.

Table 3-1 Compatible Device Summary

The MXP will allow some alternative devices to be used without generating a fault, where the inserted device can provide all the features of the configured device. This includes an 814PH or 814CH used where an 814H was programmed, a CIM800 used where a MIM800 was programmed, and an 814PH used where an 814P was programmed.

Page 3-6 24 March 2006 Issue 1.5

Document: LT0273

3.2

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

DEVICE HANDLING CAPABILITY

3.2.1 OVERVIEW

The parameters which determine the maximum number of each device type that can be put on a loop are as follows. The column “MAX NO. DEVICES” assumes that all devices are of the same type. If this is not the case, it is necessary to perform the calculations described below.

MIM800

MIM801

RIM800

SNM800

LPS800

VLC800

NO.

DEVICES

200

200

200

200

33 or less, depends on load

814SB 40(Quiet)

30(Medium)

24(Loud)

50 (Loud)

125

Current

Alarm

Current

AC Units

(max 250 total)

IB Units

(max 100 IB units between

Isolator Bases)

1 1.4

1 1

1 1.2

1 1.2

1 1

1 1.5 275uA

275uA

2.8mA (with LED)

275uA (no LED)

2.8mA (with LED)

275uA (no LED)

1 1.5

1

1

1

1

(Loop)

285uA

300uA

2.8mA (with LED)

285uA (no LED)

1 1.5

1 5

450uA 3.0mA (with LED)

450uA (no LED)

1 5

1.5 1

4mA, with minimum of 12mA

400uA 9mA(Quiet)

12mA(Medium)

15mA(Loud)

0.2 N/A

2.4 2.5

0.5 2.5

6.8mA (Loud)

0.5 2.5

200uA 2.5

200uA( 2.5

300uA (no LED)

2.8mA (with LED)

0.3 1.6

2 1

*Models of MkII Sounder Base

Table 3-2 Device Quantities and Loading

The particular combination of device types, external loads, cable length and type may limit the total number of devices. This is calculated in the following sections.

There are two types of load which must be considered - DC and AC. Also if isolator bases are used, the loading between each isolator base must be considered.

Issue 1.5 24 March 2006 Page 3-7

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

It is recommended that the PC program F4000CAL is used for conducting the loop loading calculations. However note that it does not include the isolator base loading, this must be done manually.

The total current available from the MX Loop terminals on the MXP is 400mA DC.

This must supply operating current to all addressable devices an the loop. This not only includes the quiescent current required to power the device electronics, but also the additional current drawn by devices in the ALARM state or by associated ALARM LEDs and other loop powered outputs.

The sum of currents for all devices connected to the loop is calculated using the “alarm

current” values shown in Table 3-2. Note –

1)

2)

The MXP limits the number of Alarm LEDs turned on at any one time to 5

(programmable at MX4428).

Remote LEDs must be allowed for at 7mA each. Remote LEDs programmed to follow

3)

4) the detector LED will be limited by the number of alarm LEDs. However remote LEDs programmed to operate on “Circuit Alarm” or “Relay” will not be limited in any way.

LEDs on relay output devices (SNM800, RIM800, LPS800) will operate when the relay is activated, if the MXP is configured at the MX4428 to flash the LED on Poll

“Global Blink Mode”.

The 814RB, RIM800 and SNM800 relay load current must not be supplied from the analogue loop.

The sum of all currents must not exceed 400mA.

Furthermore, the voltage drop in the cable must not exceed 16.0V, regardless of which end of the loop the cable is driven from. This is in order to ensure that with the minimum 36V voltage available from the MX Loop terminals on the MXP, the minimum voltage at any device will be at least 20V.

If you have any LPS800 devices on the loop, you may need to design for a higher minimum

loop voltage and a lower voltage drop. Refer to section 3.23.2.

Calculate the total of the “AC Units” shown in Table 3-2. The total must not exceed 250.

Also ensure that the cable length does not exceed the values in Table 3-3.

Cable type

MICC 2L1.5, 2L2.5, 1H1.5, 2H2.5

Cable length

1.8 km*

Steel Wire Armour (SWA)

Fire resistant ‘foil and drain wire’, e.g.

Radox FR3013, FP200, Lifeline, Firetuff

BS6883 marine cable

1.8 km*

2 km

2 km

Table 3-3 Maximum Cable Lengths

* Up to 2km of these cable types may be used on condition that the maximum AC loading is restricted to less than 220 AC units per loop.

Page 3-8 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

If isolator bases are being used, calculate the sum of the “IB Units” from Table 3-2 for each

section of cable between isolator bases (or between the last isolator base and the end of a cable spur). Include only one of the detectors at the ends of the section. The sum for any section must not exceed 100.

See also section 4.1.3 for details of AS1670 requirements and section 4.1.4 for details of

NZS4512 requirements.

3.2.5 EXAMPLE

Consider an MXP monitoring 200 * 814PH detectors with 10 814SB Sounder Bases set to

High, on a 1300 metre long loop, using 1.5mm

2

wire. The cable is divided (with 9 Isolator

Bases) into 10 segments with 1 Sounder Base and 20 detectors on each segment.

(i) Calculate DC Load

IA = 195 x 275uA

+ 5 x 3.0mA

(No. of detectors in NORMAL)

(No. of detectors with Alarm LEDs turned on, assume limited to

5 max by MXP)

+ 10 x 15mA (Number of 814SB Sounder Bases)

+ 9 x 80uA (Number of Isolator Bases)

(Ref Table 3-2. Note 1mA = 1000uA)

= 220mA which is well under 400mA

For the voltage drop calculation, assume the worst case in the first instance, i.e. that all devices are at the far end of 1300 metres. The loop resistance of 1.5mm

2

wire is

25

Ω per 1000m and the isolator base resistance is 0.25Ω.

Total R = 25

Ω x 1.3 + 9 x 0.25Ω

Voltage drop = 34.75 x 0.220 = 7.7V, which is well under the maximum allowable of

16V.

(ii)

Calculate AC Load

AC Units =

=

200 x 1 (detectors)

+ 10 x 2.4 (Sounder Bases)

+ 10 x 0.1 (Isolator Bases)

225 which is less than the maximum allowable of 250.

Cable length is well under the limits specified in Table 3-3.

(iii)

Calculate IB Load

IB Units for each section = 20 * 1.2 (814PH) + 1 * 2.5 (814SB)

= 26.5 which is less than 100.

As all parameters are within the specified limits, the design is satisfactory.

Issue 1.5 24 March 2006 Page 3-9

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.3 OUTPUT CONTROL

Document: LT0273

The following “outputs” are available on the Analogue loop –

• Output modules – RIM800, SNM800, and LPS800

• Functional Base outputs of detectors (controlling 814SB, MkII Sounder Base or 814RB)

• Remote LED output of detectors.

Each of these is programmable at the MX4428 for which of 3 sources controls the output.

In all cases the outputs are turned off if the point is isolated.

The 3 selectable sources are as follows –

1. Relay output

The output is controlled by the state of the corresponding relay output as sent to the responder. The relay output state can be controlled directly with a logic equation, be controlled by the state of the ACZ that the relay is mapped to (this also allows supervision fault states on the SNM800 and LPS800 output to be indicated), or be controlled by the test state of the flow switch zone it is mapped to.

The functional bases and remote LED outputs for detectors mapped to circuit X of logical responder R will be controlled by the state of relay X of logical responder R, i.e. the relay with the same number as the detector circuit.

2. Circuit alarm

The output will turn on when the corresponding circuit goes into alarm. If the circuit maps to a latching zone then the output will turn off when the zone alarm is reset. If the circuit does not map to a latching zone the output will turn off when the circuit goes out of alarm. The circuit alarm state is determined by the MXP and so can’t include other responder circuits, nor the state of the zone(s) the circuit maps to. (Use “relay output” if these are needed.)

The functional bases and remote LED outputs for detectors will be controlled by the circuit the detector is mapped to. Output modules mapped to relay X of logical responder R will be controlled by circuit X of logical responder R, i.e. the circuit with the same number as the relay.

WARNING - the output will not be disabled by zone isolate.

3. Point alarm

The output will turn on when that point goes into alarm. If the point maps to a latching zone then the output will stay on until the zone alarm is reset. If the point does not map to a latching zone the output will turn off when the point goes out of alarm.

This option is not available on output modules (RIM800, SNM800, and LPS800).

WARNING - the output will not be disabled by zone isolate.

Page 3-10 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.3.1 PROGRAMMING

The programming of the output functions is done by setting the “mode” value for the RIM800,

SNM800, and 814I, and by one of the 7 device parameters for the 814H, 814PH, and

814CH. The LPS800 is programmed as an SNM800.

For example the following are the settings for the 814I.

Mode Functional Base Control Remote LED Control

0 Circuit Alarm Circuit Alarm

Relay

Point Alarm 2 Circuit Alarm

4 Relay

5 Relay

6 Relay

Relay

8 Point Alarm Circuit Alarm

Relay

Point Alarm 10 Point Alarm

The value must be chosen from the above table to give the desired settings for controlling the functional base and the remote LED.

For the 814PH and 814CH, programming of the “enhancement multiplier” is included in the same parameter. The desired enhancement multiplier must be multiplied by 16 and the

result added to the above numbers. The tables in the sections for these detectors (3.9.3 and

3.10.3) include the result when the default enhancement multiplier is used.

For the 814H detector and for an 814PH or 814CH with enhancement disabled, the

“enhancement multiplier” is irrelevant and therefore the above numbers may be entered directly if desired. The global defaults for parameter 6 for all these detector types should always include the desired enhancement multiplier * 16.

For the SNM800, other options are also included in the mode. Refer to section 3.22.4 for

details.

All outputs retain their state if the MX4428 stops polling the responder (e.g. processing is stopped), or if the MXP stops polling the devices (e.g. due to a new configuration download from the MX4428). If a detector is removed from a relay or sounder base, the relay or sounder output turns off.

If power to the MXP is lost, loop powered sounder bases turn off. RIM800 and SNM800 outputs, relay bases and possibly externally powered sounder bases usually retain their state until MXP power is restored, then turn off when polling resumes (which may take some minutes if the MXP has been off for some hours and lost its configuration), then revert to ON after a few seconds if this is the correct state.

Issue 1.5 24 March 2006 Page 3-11

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

3.4 DETECTOR PARAMETER SETTINGS SUMMARY

The following table gives a summary of the MX4428 default and alternate settings, and approved range, for each detector type.

Detector Default Alternate Range Comments

814PH 12% 8% 8% - 12% Enhancement is optional,

Smoke (80 det units) (37 det units) default off.

Medium N/A 814PH

Smoke

FastLogic

High (all approved with nominal sensitivity =

8%) default off.

814PH Heat component

63 N/A 60 - 65

814CH

CO

814CH Heat component

38ppm

(0.3 MIC X)

(93 det units)

63

66ppm

(1)

(0.6 MIC X)

(160 det units)

N/A

23 - 66ppm

60 - 65

(1)

Type B default.

Type A is option

Off is option.

Enhancement is optional, default off.

(23ppm = 0.15 MIC X

= 60 det units)

Type A default.

Type B is option

Off is option.

814H

VLC800

(66 det units)

63

Fixed at 100

(23 det units)

N/A

0.2 - 0.4 (Aus)

0.2 - 0.6 (NZ)

60 - 93 (Aus)

50 - 80 (NZ)

0.005% / m to

20% / m

0.59 MIC X =130 det units

Type A default. Type B option.

Types C/D by changing temperature to 93.

Note that actual sensitivity is adjusted by

PC connected to the

VLC800.

(1)

66ppm is outside the approved range of the 814CH as an ionisation detector. However it is an accepted value as a CO detector.

Prealarm

The Prealarm default and alternate sensitivities will generally be about 70% - 80% of the corresponding alarm level. Note that Prealarm will also be more sensitive to rapidly changing conditions as it does not go through the step limiting filter.

Conversion

Det Units = Detector Units.

Temperatures are already converted by the MXP to degrees C and do not require conversion.

Page 3-12 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Conversion from detector units to displayed values is by imagining a graph with a series of joined straight lines from (0,0) and passing through each of the above defined points (e.g.

814PH 37 det units = 8%) and extrapolated in a continuing straight line past the highest point if necessary.

For the 814PH detector the displayed values bear little resemblance to the static sensitivity of the detector. They are valid only for the tests done in the SSL smoke room.

3.5

3.5.1 PRECAUTIONS

Observe ESD precautions when installing an MXP responder, or connecting any devices to it. Refer to Product Bulletin PBG0025.

3.5.2 MOUNTING

Detector Bases

Detectors attach to a circular, plastic base which has holes for screw mounting to a flat surface, and screw terminals for connecting the loop wiring. There are various different bases available. Most of the bases may only be mounted as just described, but the 814SB sounder base and the 814RB relay base may be mounted as just described, or may themselves be plugged into one of the other bases, to interpose between it and the detector.

Modules

The Modules are normally mounted within the enclosure of the equipment to which they connect, or in a cabinet, junction box or switch box. They may be mounted on plastic standoffs (4 x HW0130 required) on a gearplate or cabinet, or to a face plate that mounts on a double flush or surface box. A hole may be required for the on-board LED. A standard plate with a hole for the LED and three holes for the Service Tool is available (Ancillary

Cover M520). This fits a plastic surface box K2142.

The MIM800/801 is smaller than the other modules, and is supplied in a plastic housing which has a lug for screw mounting.

3.5.3 ADDRESS & LED BLINK PROGRAMMING

Addresses for MX detectors and modules, and options such as LED blink on poll, are most easily set using the MX Service Tool. These are set by placing the detector onto the Service

Tool, or connecting the module to the Service Tool with the supplied interface lead, and programming as per the MX Service Tool Instructions. (Be careful not to leave the pins in the module when removing the lead).

For all input devices, including detectors, the LED turns on steady when in alarm. For output devices (RIM800, etc) the LED turns on when the device is activated (if Global Blink Mode is enabled for the MXP). To enable a device’s LED to blink on poll, the MXP must have Global

Blink Mode enabled at the MX4428 panel, and the device must have LED Blink enabled.

For a mixed system, i.e. some devices are to blink on poll and some are not, then turn off blink on those devices that are not to blink using the Service Tool, and enable Global Blink

Mode at the MX4428 panel for the MXP.

Issue 1.5 24 March 2006 Page 3-13

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.6 MX4428 PROGRAMMING

Document: LT0273

In the following sections information is given about the programming of each device in the

MX4428. An explanation of the mode and the various parameters is given for each device type, along with the global parameters that affect that device type. It is critical that only the listed mode values are used for each device type, as in many cases the mode value is used to define the actual device type. An incorrect mode value may cause a POINT TYPE

MISMATCH to be generated, or it may just render a device not able to work.

In some of the following sections descriptions are given about changing the sensitivity for a detector by altering the specific parameter for that detector. This is correct (it sets the value for just that individual detector), but in many cases it may be better to adjust the global sensitivity for that device type so that all detectors of that type take on the new value. For example, in NZ mode it is recommended that the global heat alarm temperature be set to

57

°

C for both 814PH and 814CH, rather than setting each specific detector to this value.

Details for NZ mode settings are contained in the F4000 NZ Technical Manual (LT0126).

These details are most relevant when programming the MX4428 from a (dumb) programming terminal. Alternatively you can program with "SmartConfig", which displays and edits functional parameters and takes care of mapping the functional parameters into the appropriate mode and parameter bytes for each device type.

Page 3-14 24 March 2006 Issue 1.5

Document: LT0273

3.7

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

814H HEAT DETECTOR

3.7.1 GENERAL

The 814H is an analogue thermal detector. The detector senses the air temperature and sends this value to the MXP. The MXP makes any decisions as to whether this is an alarm, fault, normal or whatever. The MXP can be programmed (at the MX4428 panel) to interpret the values to implement a Type A, Type B, Type C, or Type D Heat Detector. The integral

LED is turned on by the MXP when an alarm is detected.

The 814H has a temperature sensing range of -25

°C to 95°C. The approved operating temperature range is -10

°C to +70°C. The accuracy of the 814H (as interpreted by the

MXP), within the range 0

°C to 70°C, is typically + / - 2°C.

The remote LED and functional base outputs are programmable for their functionality (refer

to section 3.3).

Line Connections

Supply Voltage:

Supply Current:

Alarm Current:

L(–), L1(+)

20Vdc - 40Vdc

250uA (typical quiescent)

3.0mA (typical)

Remote LED Current:

Dimensions:

7mA (Tyco E500Mk2)

110mm (diameter) x 55mm (including MUB base)

Weight 79g

Base

3.7.3

MUB, 5B, 5BI, 814RB, 814SB, or MkII Sounder Base

MX4428 PROGRAMMING OPTIONS - 814H

The programming values for the 814H are described in the following tables.

“Mode” enables or disables rate of rise processing. Mode = 4 selects type A/C (heat rate of rise enabled), and mode = 5 selects type B/D (heat rate of rise disabled). Only select one of these two values. (Note that when rate of rise is disabled, the parameters relating to rate of rise are ignored - there is no need to adjust them.)

For type C and D operation set the heat fixed temperature alarm threshold (Parameter 1) to

93 (

°C).

Parameter 0 may be adjusted to select a different Pre-Alarm temperature.

For special purposes, the fixed temperature alarm threshold may be set to any value between 60 and 93 for Australia, and between 50 and 80 for New Zealand. In New Zealand also set the global parameter “8XX HEAT SL1” to (the highest alarm temperature - 20) / 10

(rounded up if the result is fractional).

For functional base and remote LED programming set Parameter 6 as per the table. Refer

to section 3.3 for further details.

The remaining parameters should not need changing.

Issue 1.5 24 March 2006 Page 3-15

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

Parameter Description

Mode

P0

P1

Default

4

4 A/C – rate of rise enabled.

5 B/D – rate of rise disabled

Heat fixed temperature pre-alarm threshold

°C 56

Heat fixed temperature alarm threshold

°C

63 (

°C)

P4

63

93 b3:b0 b7:b4

Australian Types A / B

Australian Types C / D

ROR Pre alarm Threshold

ROR Alarm Threshold

Number + 5 gives the

Threshold in

°C/min

P5

P6 Enhancement multiplier (default 12) * 16 plus code below

Control

Remote LED

Control

Final value with default enh multiplier

0

2

Circuit Alarm

Circuit Alarm

4 Relay

Circuit Alarm 192

1 Circuit 193

Point Alarm 194

5 Relay Relay 197

7 (12

°C/min)

9 (14

°C/min)

192

6 Relay

8 Point Alarm Circuit Alarm 200

9 Point 201

10 Point Alarm Point Alarm 202

Note – enhancement multiplier is unused for individual 814H detector settings, but must be retained in MX4428 default settings, as the same defaults are used for the 814H and

814PH.

The following global parameters, which may be set at the MX4428, affect all applicable points on all MXPs.

MX4428 Reference Description

8XX HEAT FD1 Heat FD1 (CV Filter)

8XX HEAT FD2

8XX HEAT SL1

8XX HEAT SL2

Default

4

Heat FD2 (ROR determination) 7

Heat SL1 (Fixed temp step limit,

°C/5sec)

2

Heat SL2 (ROR step limit,

°C/min/5sec)

3

Page 3-16 24 March 2006 Issue 1.5

Document: LT0273

3.8

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

814I IONISATION SMOKE DETECTOR

3.8.1 GENERAL

The 814I is an ionisation smoke detector. The detector senses the amount of smoke present and sends this value to the MXP. The MXP makes any decisions as to whether this is an alarm, fault, normal or whatever. The integral LED is turned on by the MXP when an alarm is detected.

The remote LED and functional base outputs are programmable for their functionality (refer

to section 3.3).

Line Connections

Supply Voltage

Supply Current

Alarm Current

L(–), L1(+)

20Vdc - 40Vdc

330uA (typical quiescent)

3.0mA (typical)

Remote LED Current

Dimensions

7mA (Tyco E500Mk2)

110mm (diameter) x 55mm (including MUB base)

Weight 81g

Base MUB, 5B, 5BI, 814RB, 814SB, or MkII Sounder Base

The programmable values for the 814I are explained in the following table.

Normally only the mode needs to be programmed, and then only if a functional base or

remote LED is required and its operation is different from the default. Refer to section 3.3.

In some cases the alarm sensitivity (Parameter 1) may need to be changed from the default.

The approved range for Australia is 0.22 MIC X (23) to 0.39 MIC X ( 66). The available range is 0.22 MIC X (23) to 0.59 MIC X (130). If the alarm sensitivity is changed, the pre-alarm sensitivity (Parameter 0) should normally be changed to about 75% of the alarm sensitivity.

The remaining parameters should not need changing.

Issue 1.5 24 March 2006 Page 3-17

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Parameter Description

Mode Value Functional Base Control Remote LED Control

0 Circuit Alarm

2 Circuit Alarm

4 Relay

Circuit Alarm

Relay

Point Alarm

5 Relay

6 Relay

8 Point Alarm

Relay

Circuit Alarm

Relay

Point Alarm

P0

P1

10 Point Alarm

Pre Alarm Threshold

Alarm Threshold

Value Threshold

23 0.22 MICX (Alternate)

Document: LT0273

Default

0

50

66

P2

P3

Fault Limit (i.e. values below this are assumed to indicate a detector fault)

Dirty Alert Limit (i.e. a “dirty alert” will be raised if the tracked “clean air” value reaches this limit) b3:b0 Filter Divisor

10

120

P4

P5 b7:b4 Step Limit

Tracking Interval i.e. the interval at which the tracked “clean air” value is adjusted.

Tracking adjustment - fixed at 1 in MXP

3

5

30 (minutes)

P6

Ionisation Upper Tracking Limit

(i.e. the maximum assumed value for clean air)

1

The following global parameters which may be set at the MX4428 affect all applicable points on all MXPs.

MX4428 Reference Description Default

8XXI UPPER

TRACKING LIMIT

120 (MXP

Default)

Page 3-18 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.9 814PH PHOTOELECTRIC SMOKE & HEAT

DETECTOR & 814P PHOTOELECTRIC SMOKE

3.9.1 GENERAL

The 814PH is a photoelectric smoke detector which also includes a temperature sensor. The detector senses the amount of smoke present and the temperature and sends these values to the MXP. The MXP makes any decisions as to whether this is an alarm, fault, normal or whatever, based on the smoke level, temperature, or rate of rise of temperature, and/or a combination of these. The integral LED is turned on by the MXP when an alarm is detected.

Refer to the specifications of the 814H for more details on the heat sensing element of the

814PH.

The 814P is the same as the 814PH, except that it has no temperature sensor.

The remote LED and functional base outputs are programmable for their functionality (refer

to section 3.3).

3.9.2 814PH & 814P SPECIFICATIONS

Line Connections

Supply Voltage

Supply Current

Alarm Current

Remote LED Current

Dimensions

L(–), L1(+)

20Vdc - 40Vdc

275uA (typical quiescent)

3.0mA (typical)

7mA (Tyco E500Mk2)

110mm (diameter) x 55mm (including MUB base)

Weight 76g

Base

3.9.3

MUB, 5B, 5BI, 814RB, 814SB, or MkII Sounder Base

MX4428 PROGRAMMING OPTIONS - 814PH/814P

In the MX4428 programming there are two different device types that use the 814PH/814P detector. Type 16 814PH is used when the 814PH is used with the SmartSense algorithm and type 27 814PHFL is used when the FastLogic algorithm is required. These different device types allow the MX4428 to have separate sensitivity settings for the algorithms and for the sensitivities to be displayed correctly.

However, the mode value actually defines to the MXP which algorithm is to be used.

Mode values 0 – 7 must only be used with a device type of 814PH, and mode values 8 – 15 must only be used with a device type of 814PHFL. Do not use an incorrect mode, as the values displayed at the MX4428 will not match those being used or generated at the MXP.

The 814P must be programmed as an 814PH, with no heat. I.e. only modes 7 and 13 are allowed. The MX4428 will display the point type as 814PH.

The programmable values for the 814PH and 814P are described in the following tables.

Issue 1.5 24 March 2006 Page 3-19

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

The mode selects the detection mode for the detector - smoke only, enhanced smoke, heat enabled or disabled, heat rate of rise enabled or disabled, smoke detection algorithm is

SmartSense or FastLogic, etc. Note that when a particular function is disabled by the setting of the mode, the parameters relating to that function are not used and should therefore be left with their default settings.

Parameter 1 selects the smoke alarm threshold.

With the SmartSense algorithm, the actual alarm threshold is selected as per the table. The approved range is 8%/m (Parameter 1 = 37) to 12%/m (Parameter 1 = 80).

With the FastLogic algorithm Parameter 1 values of 0, 1, or 2 will select Low, Medium, or

High sensitivity respectively. Any other value will select the sensitivity defined in the global parameter 8XXPH FUZZY ALGORITHM. Parameter 1 can usually be left at its default setting for all detectors and those detectors with their mode set to FastLogic will then use the setting in the global parameter 8XXPH FUZZY ALGORITHM. All three FastLogic sensitivities are SSL approved and all have a nominal sensitivity of 8% / m.

Parameter 3 may be adjusted to vary the fixed temperature alarm threshold. It may be set to any value between 60 and 65 in Australia, and between 50 and 65 in New Zealand.

Parameter 2 may be adjusted to select a different Pre-Alarm temperature.

Parameter 6 selects the functional base and remote LED output operation (refer to section

3.3) and the “enhancement multiplier” which should normally be left at the default value (12).

The remaining parameters should not need changing.

Page 3-20 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Parameter Description

Mode

P0

P1

Value Smoke

Algorithm

Enhance smoke sensitivity with heat Rate of

Rise.

Heat Type

A – rate of rise enabled

B – rate of rise disabled

A

B

A

B

4 None

5 None

6

7

SmartSense

SmartSense

Yes

No

8 FastLogic Yes

9 FastLogic Yes

10 FastLogic No

11 FastLogic No

A

B

No heat alarm

No heat alarm *

A

B

A

B

No heat alarm

No heat alarm *

12

13

FastLogic

FastLogic

Yes

No

SmartSense smoke Pre Alarm Threshold

SmartSense smoke Alarm Threshold

Value Threshold

37 8% / m (alternate)

80

FastLogic Sensitivity

12% / m (default)

P2

P3

Default

3

68

80

Value Sensitivity

0 Low

1 Medium

2 High

Any other Global Parameter

“8XXPH Fuzzy Algorithm”

Heat fixed temperature pre-alarm threshold

°C 56

Heat fixed temperature alarm threshold

°C

63 (

°C)

Value Usage

P4

P5

P6

63 b3:b0 ROR Pre alarm Threshold b7:b4

Australian Types A / B

ROR Alarm Threshold

Number + 5 gives the

Threshold in

°C/min b3:b0 Smoke Filter Divisor

7 (12

9 (14

3

4

192

°C/min)

°C/min)

Enhancement multiplier (default 12) * 16 plus value below

Result with

Control Control default enh multiplier

0 Circuit Alarm Circuit Alarm

2 Circuit Alarm

4 Relay

Point Alarm

192

193

194

6 Relay

8 Point Alarm Circuit Alarm

10 Point Alarm Point Alarm

* These are the only modes allowed with the 814P detector.

200

201

202

Issue 1.5 24 March 2006 Page 3-21

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

The following global parameters which may be set at the MX4428 affect all applicable points on all MXPs.

MX4428 Reference

8XXPH UPPER

TRACKING LIMIT

8XXPH DIRTY

ALERT LIMIT

Description

Photo Upper Tracking Limit (i.e. the maximum assumed value for clean air)

Photo Dirty Alert Limit (i.e. a “dirty alert” will be raised if the tracked

“clean air” value reaches this limit)

Default

56 (MXP Default)

56

8XXPH TRACK

INTERVAL

8XXPH FUZZY

ALGORITHM

Photo Tracking Interval i.e. the interval at which the tracked

“clean air” value is adjusted.

Fuzzy Sensitivity if Device Parameter

1 is not 0, 1, or 2

0 = low

1 = medium

2 = high

30 (minutes)

1 (medium)

(MXP also chooses

Medium if this parameter is not 0,

1, or 2)

Page 3-22 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.10 814CH CARBON MONOXIDE + HEAT DETECTOR

3.10.1 GENERAL

The 814CH is a carbon monoxide (CO) detector which also includes a temperature sensor.

The detector senses the amount of CO present and the temperature and sends these values to the MXP. The MXP makes any decisions as to whether this is an alarm, fault, normal or whatever, based on the CO level, temperature, or rate of rise of temperature, and/or a combination of these. The integral LED is turned on by the MXP when an alarm is detected.

Refer to the specifications of the 814H for more details on the heat sensing element of the

814CH.

The remote LED and functional base outputs are programmable for their functionality (refer

to section 3.3).

Line Connections

Supply Voltage

Supply Current

Alarm Current

L(–), L1(+)

20Vdc - 40Vdc

275uA (typical quiescent)

3.0mA (typical)

Remote LED Current

Dimensions

7mA (typical Tyco E500Mk2)

110mm (diameter) x 55mm (including MUB base)

Weight 88g

Base MUB, 5B, 5BI, 814RB, 814SB, or MkII Sounder Base

The programmable values for the 814CH are described in the following tables.

The mode selects the detection mode for the detector - CO only, enhanced CO, heat enabled or disabled, heat rate of rise enabled or disabled, etc. Note that when a particular function is disabled by the setting of the mode, the parameters relating to that function are not used and should therefore be left with their default settings.

Parameter 1 selects the CO alarm threshold. Some possible settings are shown in the table.

Note the alternate setting of 66ppm is not an SSL listed setting for an ionisation detector (the

814CH was SSL tested using the tests for an ionisation detector under AS1603.2, as at the time there was no approved standard for CO detector). Although this setting is acceptable for a CO detector it should only be used for special applications where installation conditions exclude other smoke detectors and yet the background CO level may be higher than normal.

At this sensitivity the background CO level should not exceed 30ppm.

Parameter 3 may be adjusted to vary the fixed temperature alarm threshold. It may be set to any value between 60 and 65 in Australia.

Parameter 2 may be adjusted to select a different Pre-Alarm temperature.

Parameter 6 selects the functional base and remote LED output operation (refer to section

3.3) and the “enhancement multiplier” which should normally be left at the default value (12).

Issue 1.5 24 March 2006 Page 3-23

P4

P5

P6

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

The remaining parameters should not need changing.

Parameter Description

Mode sensitivity with heat

Rate of Rise

Heat Type

A – rate of rise enabled

B – rate of rise disabled

P0

P1

0 Yes

1 Yes

2 No

3 No

6

7

Yes

No

CO Pre Alarm Threshold

A

B

A

B

No heat alarm

No heat alarm

CO Alarm Threshold

Value Threshold

60 23ppm

Document: LT0273

Default

2

80

93

P2

P3

Heat fixed temperature pre-alarm threshold

°C 56

Heat fixed temperature alarm threshold

°C

63 (

°C)

Value Usage

63 b3:b0 ROR Pre alarm Threshold b7:b4

Australian Types A / B

ROR Alarm Threshold

Number + 5 gives the

Threshold in

°C/min b3:b0 CO Filter Divisor b7:b4 CO Step Limit

Enhancement multiplier (default 12) * 16 plus value below

Control

Base Remote LED

Control

Result with default enh multiplier

0 Circuit Alarm Circuit Alarm

Point Alarm

192

193

194 2 Circuit Alarm

4 Relay

5 Relay Relay 197

6 Relay

8 Point Alarm Circuit Alarm

10 Point Alarm Point Alarm

200

201

202

7 (12

°C/min)

9 (14

°C/min)

3

3

192

Page 3-24 24 March 2006 Issue 1.5

Document: LT0273

3.11

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

MUB UNIVERSAL BASE

3.11.1 GENERAL

The MUB accommodates any of the MX 814 series detectors, and may also have an 814RB,

814SB, or MkII Sounder Base plugged into it.

3.11.2 MUB AND 5B WIRING

Figure 3.1 shows the wiring for a MUB and 5B, including optional wiring of a remote

indicator.

-

AR

+

MXP

-

AL

+

L

L1

R

L1

L1

TYCO MUB (M614)

MINERVA

UNIVERSAL

BASE

L2

TYCO 5B

5“ UNIVERSAL

BASE

L

M

L2

L2

+

-

Tyco E500Mk2

Remote Indicator

R

Figure 3.1 MUB and 5B Wiring

A remote indicator may be wired to an MUB, Relay Base, or Sounder Base as shown for

example in Figure 3.1.

A single Remote Indicator may be wired up to a number of detector bases, so that it turns on if any one of the detectors turns it on. The R terminals of the detectors involved should be looped together.

This common group must not include an isolator base or extend across an isolator base.

The brightness may increase slightly if more than one detector turns on the remote indicator.

Issue 1.5 24 March 2006 Page 3-25

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.12 5BI ISOLATOR BASE

Document: LT0273

3.12.1 GENERAL

The 5BI base is designed for isolating short circuited sections of the analog loop. For instance it can be used where the loop wiring crosses zone boundaries to prevent a short circuit from affecting more than one zone. When isolator bases are used, it is strongly recommended that two additional isolator bases (possibly with no detectors inserted) be installed at the start and end of the loop, close to the MXP.

Isolator bases may also be used to join multiple lines together in a single star arrangement, for example when a number of conventionally wired zones are being converted to MX and a loop cannot be wired.

Refer to section 4.1 for more details on the analog loop configuration.

There is a limit to the number of other devices which may be connected on the section of

cable between isolator bases. Calculate the sum of the “IB Units” from Table 3-2 for each

section of cable. The sum for each section must not exceed 100.

A section of cable is the portion between isolator bases or between an isolator base and the

MXP, or if a star configuration or tee is being used, between an isolator base and the end of the cable.

3.12.2 SPECIFICATIONS

Line Connections IN

Line Connections OUT

Remote LED Connection

Supply Voltage

Supply Current

Dimensions

M(–), L1(+)

L2(–), L1(+)

R(–), L1(+)

20Vdc - 40Vdc

80uA (typical quiescent)

110mm (diameter) x 22mm (excluding detector)

Weight 80g

3.12.3 WIRING

Figure 3.2 shows wiring for an 5BI, including connection of an external remote indicator.

Note that a common remote indicator may not be wired to a set of bases which are on different sides of an isolator base.

Page 3-26 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

MXP

AR

-

+

AL

-

+

L 1

L

L1

L1

L1

L

L2

M

L 2 L2

M

R

TYCO 5BI

ISOLATOR

BASE

+

-

Tyco E500Mk2

Remote Indicator

(controlled by MX4428)

TYCO MUB

UNIVERSAL

BASE

M and L2 connections to Isolator Base are symmetrical and can be transposed without affecting operation

Figure 3.2 5BI Wiring

TYCO 5BI

ISOLATOR

BASE

L

R

L1

M

L1

M

L2

L2

Issue 1.5 24 March 2006 Page 3-27

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.13 814RB RELAY BASE

Document: LT0273

3.13.1 GENERAL

The 814RB detector base is designed as a low cost output device. The relay is controlled by the detector which is plugged into the base, but the operation of the relay can be quite

separate from the operation of the detector. (Refer to section 3.3.)

The 814RB Relay Base provides two sets of volt-free, change-over contacts capable of switching ancillary equipment rated at up to 1A resistive @ 30Vdc. One set is labelled NO,

C, NC (for normally open, common, and normally closed.) The other set is labelled 1 for NC,

2 for C, and 3 for NO. The terminals accept a single cable of up to 2.5 sqmm. Relay operation is controlled by the MX4428 via an output from the detector. Hence, a detector

must be fitted to the base in order for the relay to operate as the relay base does not have its own address.

The 814RB may be plugged into a MUB standard base, 5B standard base, or 5BI isolator base, or mounted directly on the ceiling or wall.

3.13.2 SPECIFICATIONS

Line Connections

Remote LED Connection

Supply Voltage

Supply Current

Relays

L(–), L1(+)

R(–), L1(+)

20Vdc - 40Vdc

50uA (typical quiescent)

100uA (output active)

Two changeover volt-free contacts

Switching current: 1A @ 30V dc

Dimensions

Switching time: <10ms

Life expectancy: 100,000 operations

110mm (diameter) x 37mm (excluding detector)

Weight 153g

3.13.3 WIRING

Refer to Figure 3.3 for details of the relay terminals. Loop wiring and remote LED wiring is

the same as the MUB, refer to Figure 3.1. Contact wiring connects to the following terminals

First Pole

C Common

Second Pole 2 Common

Page 3-28 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Figure 3.3 Relay Base

Issue 1.5 24 March 2006 Page 3-29

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.14 814SB SOUNDER BASE

Document: LT0273

3.14.1 GENERAL

The 814SB detector base is designed as a low cost warning device. One of three different tones may be selected (none of which are AS2220 compliant), and three sound levels are selectable. Note that the current taken by a sounder base is very much higher than most other loop devices, and the number of sounder bases on a loop is limited by the available current.

The sounder is controlled by the detector which is plugged into the base, but the operation of

the sounder can be quite separate from the operation of the detector. (Refer to section 3.3.)

The tone switch allows selection of one of three different tones –

1 - continuous tone (825Hz)

2 - fast sweep (saw tooth envelope at 15Hz)

3 - slow sweep (saw tooth envelope at 5Hz) (Factory Setting)

The volume switch provides three different levels of loudness:

1 - 70dB(A) (quiet)

2 - 80 dB(A) (medium)

3 - 90 dB(A) (loud) (Factory Setting)

The 814SB may be plugged into a MUB standard base, 5B standard base, or 5BI isolator base, or mounted directly on the ceiling or wall.

3.14.2 SPECIFICATIONS

Line Connections

Remote LED Connection

Supply Voltage

Supply Current

Dimensions

L(–), L1(+)

R(–), L1(+)

20Vdc - 40Vdc

400uA (typical quiescent)

9mA (active in QUIET setting)

12mA (active in MEDIUM setting)

15mA (active in LOUD setting)

110mm (diameter) x 37mm (excluding detector)

Weight 163g

3.14.3 WIRING

Wiring is the same as the MUB, refer to Figure 3.1.

Page 3-30 24 March 2006 Issue 1.5

Document: LT0273

3.15

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

MKII SOUNDER BASE

3.15.1 GENERAL

The MkII Sounder Base is a range of detector bases which are designed as low cost warning devices, some of which are loop powered and others are externally powered. The sounder is controlled by the detector which is plugged into the base, but the operation of the sounder

can be quite separate from the operation of the detector. (Refer to section 3.3.)

The MkII Sounder Bases cannot be plugged into other bases. They must be mounted directly on the ceiling or wall.

At the time of writing, the MkII Sounder Bases are not SSL approved to AS4428. However they may be used for supplementary local sounders.

3.15.2 SPECIFICATIONS

Line Connections

Remote LED Connection

Supply Voltage

Quiescent Supply Current

Dimensions

L(–), L1(+)

R(–), L1(+)

20Vdc - 40Vdc

200uA (ex MX loop)

110mm (diameter) x 37mm (excluding detector)

Weight 186g

802SB 901SB 812SB 912SB

Power Source

Minimum Volume Current

Consumption

Loop

1.2mA (loop)

24VDC

1.2mA (ext supply)

Loop 24VDC

Adjustable volume Yes No

Volume 68-90dBA 100dBA

N/A

Maximum Volume Current

Consumption

Tone 1

Tone 2

Tone 3

6.8mA (loop) 6.8mA (ext supply)

21mA (loop)

Dutch Slow Sweep (AS2220 Evacuate)

21mA (ext

Supply)

Temporal 4

Slow Sweep

Tone 4

Tone 5

Tone 6

Tone 7

Tone 8

March Time Beep

Fast Sweep

Temporal 3 (ISO8201 Evacuate)

Alternating

Continuous

3.15.3 WIRING

Wiring for the 802SB and 812SB is the same as the MUB, refer to Figure 3.1. The 901SB

and 912SB wiring is similar, but they also require a 24V connection. Refer to the installation sheet supplied with these bases.

For the 901SB and 912SB, it is recommended that the external supply covers only one zone, or the power wiring be arranged so that an open circuit in the power feed cannot affect more than one zone. A loop arrangement with supervision and a reverse-feed relay can be used to achieve this - refer to Product Bulletin PBF0200.

Issue 1.5 24 March 2006 Page 3-31

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

3.16 MIM800 AND MIM801 MINI INPUT MODULES

3.16.1 GENERAL

The MIM800 and MIM801 Mini Input Modules are suitable for interfacing voltage free contacts such as switches, relay contacts, flow switches, or non-indicating detectors.

Dedicated Manual Call Point products are available that have the MIM800 or MIM801

mounted on the back of an MCP. Refer to sections 3.18 and 3.19.

Both the MIM800 and MIM801 may be used in normally open or normally closed configurations, and the normally open configuration may or may not include short circuit fault

monitoring. Refer to Figure 3.4 for wiring topology.

The normal response time to an input change of state is 0 – 5 seconds, as each device is polled at 5 second intervals by the MXP. If faster operation is required, interrupt operation can be enabled. Interrupt operation allows a change to be signalled by the device so that the

MXP detects the change immediately, rather than waiting for the next poll of the device.

To interrupt on closing contacts, the MIM800 is required. To interrupt on opening contacts, the MIM801 is required. An interrupt can be generated on only the transition from normal to alarm, transitions from alarm to normal will always require up to 5 seconds to be recognised.

Fault supervision is provided by a 200

Ω EOL resistor - open circuit fault in a normally open configuration and short circuit fault in a normally closed configuration. In addition the normally open configuration can be programmed to also generate fault on short circuit. In this case only one alarm contact is allowed, a 100

Ω resistor must be wired in series with the alarm contacts, and the fault threshold must be specially programmed. (Set Parameter 2 to

176 for a MIM800 and parameter 5 to 40 for a MIM801).

The input wiring should be limited to less than 10m in length and located well away from all electrical noise sources.

Recognition of a fault condition takes about 30 seconds.

The MIM800 and MIM801 have screw terminals for an Alarm Indicator LED. No series resistor is required. A current of about 2.5mA will be supplied when the LED is on.

WARNING

DO NOT JOIN INPUT WIRING BETWEEN MODULES OR CONNECT TO ANYTHING

OTHER THAN VOLTAGE FREE CONTACTS

3.16.2 MIM800 / MIM801 SPECIFICATIONS

Dimensions Height: 13mm Width: 48mm Depth: 57mm

Weight 22g

Line Connections

Supply Voltage

L-, L+

20V – 40V

Supply Current

Contact Inputs

Standby Current : 275uA (typical)

LED on : 2.8mA (typical)

Monitoring Voltage

Line Resistance (MIM800 and all N/O)

Line Resistance (MIM801 N/C)

5V

10

Ω max

50

Ω max

Page 3-32 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Maximum input cable length

EOL

10m

200

Ω + / - 5%.

100

Ω + / - 5%. (if used)

Sh LL+ LL+ Sh LL+ LL+

Requires Param_2 = 176 (MIM800),

Param_5 = 40 (MIM801)

PREVIOUS

DEVICE

MIM800

Mini Module

IN- IN+ O- O+

NEXT

DEVICE

ANALOG LOOP

PREVIOUS

DEVICE

MIM800

Mini Module

IN- IN+ O- O+

NEXT

DEVICE

ANALOG LOOP

200 ohm

EOL

LED

Normally Open

(default for MIM800, option for MIM801.)

Sh LL+ LL+

PREVIOUS

DEVICE

MIM801

Mini Module

IN- IN+ O- O+

NEXT

DEVICE

ANALOG LOOP

200 ohm

EOL

100 ohm

N/O with S/C fault

(for MIM800 or MIM801)

LED

Inputs must be voltage free.

200 ohm

EOL

LED

Normally Closed

(default for MIM801,option for MIM800)

Figure 3.4 CLEAN CONTACT DEVICE CONNECTION TO MIM800 / MIM801

The mode sets the operating configuration.

For the MIM800 the default value of 4 selects normally open operation with no interrupt. A mode of 6 selects normally open with interrupt on alarm. Changing parameter 2 to 176 enables short circuit fault detection. Setting the mode to 5 enables normally closed operation.

Issue 1.5 24 March 2006 Page 3-33

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

For the MIM801 the default value of 15 selects normally closed operation with interrupt on alarm (e.g. for New Zealand callpoints). Setting the mode to 13 disables interrupt on alarm

(e.g. for heat circuits or other non-immediate alarm conditions). Setting the mode to 12 enables normally open operation and then changing parameter 5 to 40 enables short circuit fault detection.

Normally Open

Parameter Description

Mode

P0

6 Interrupt

Normal to alarm threshold

P1 Normal to o/c threshold

P2 Alarm to s/c threshold

0 No alarm resistor

176

P3

100 ohm alarm resistor

P4

P5

P6

Default

4

122

50

0

Normally Closed

Parameter Description

Mode Change to 5 to select normally closed operation

P0

P1

Normal to s/c threshold

Normal to alarm threshold

P2

P3

P4

P5

P6

Default

4

122

50

Normally Open

Parameter Description

Mode Change to 12 to select normally open operation

P0

P1

P2

P3 Normal to alarm threshold

P4 Normal to o/c threshold

P5 Alarm to s/c threshold

0 No alarm resistor

40

P5

100 ohm alarm resistor

P6

Normally Closed

Parameter Description

Mode Value Description

15

P0

Interrupt, does not use AVF even if enabled

P1

P2

P3

P4

Normal to s/c threshold

Normal to alarm threshold

P5

P6

Page 3-34 24 March 2006

Default

15

110

170

0

Default

15

110

170

Issue 1.5

Document: LT0273

3.17

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

CIM800 CONTACT INPUT MODULE

3.17.1 GENERAL

The CIM800 Contact Input Module is suitable for interfacing voltage free contacts, e.g. switches, relay contacts, flow switches, or non-indicating detectors. It has two inputs, the state of which are ORed together to generate the point status. Therefore unused inputs must be terminated with the EOL resistor.

The CIM800 may be used in normally open or normally closed configurations, and the normally open configuration may or may not include short circuit fault monitoring. Refer to

Figure 3.5 for wiring topology.

The normal response time to an input change of state is 0 – 5 seconds, as each device is polled at 5 second intervals by the MXP. If faster operation is required, interrupt operation can be enabled. Interrupt operation allows a change to be signalled by the device so that the

MXP detects the change immediately, rather than waiting for the next poll of the device.

The CIM800 can only interrupt on “closing” contacts, and interrupt operation is only applicable for normally open contacts. Transitions from closed to open will always require up to 5 seconds to be recognised. Therefore it cannot be used for callpoints on NZ systems.

Fault supervision is provided by default with a 200

Ω EOL resistor - open circuit fault in a normally open configuration and short circuit fault in a normally closed configuration. In addition the normally open configuration can be programmed to also generate fault on short circuit. In this case only one alarm contact is allowed, a 100

Ω resistor must be wired in series with the alarm contacts, and the fault threshold must be specially programmed - set

Parameter 2 to 176.

Recognition of a fault condition takes about 30 seconds.

WARNING

DO NOT JOIN INPUT WIRING BETWEEN INPUTS OR MODULES OR TO ANYTHING

OTHER THAN VOLTAGE FREE CONTACTS

Dimensions Height: 61mm Width: 84mm Depth: 25mm

Weight 100g

Line Connections

Supply Voltage

L-, L+

20V – 40V

Supply Current Standby Current : 275uA (typical)

LED on : 2.8mA (typical)

Contact Inputs Monitoring Voltage 5V

Resistance

EOL 200

Ω + / - 5%.

Issue 1.5 24 March 2006 Page 3-35

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

ANALOG LOOP

PREVIOUS

DEVICE

200 ohm

EOL

NEXT

DEVICE

TB1 TB2

L+ LL+ LA+ AB+ B-

CIM800 CONTACT MODULE

Requires Param_2 = 176

200 ohm

EOL

200 ohm

EOL

ANALOG LOOP

PREVIOUS

DEVICE

NEXT

DEVICE

100 ohm

TB1 TB2

L+ LL+ LA+ AB+ B-

CIM800 CONTACT MODULE

100 ohm

200 ohm

EOL

Normally Open

Normally Open, S/C = Fault

ANALOG LOOP

PREVIOUS

DEVICE

200 ohm

EOL

NEXT

DEVICE

TB1 TB2

L+ LL+ LA+ AB+ B-

CIM800 CONTACT MODULE

200 ohm

EOL

Unused inputs (A or B) must be terminated with a 200 ohm EOL resistor.

A and B inputs must be voltage free.

Normally Closed

Figure 3.5 CLEAN CONTACT DEVICE CONNECTION TO CIM800

3.17.4 MX4428 PROGRAMMING OPTIONS - CIM800

The mode sets the operating configuration. The default value of 8 selects normally open with no interrupts, whereas a value of 10 enables interrupt on alarms.

A mode of 9 selects normally closed operation. Interrupt is not available.

Page 3-36 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Normally Open

Parameter Description

Mode

P0

P1

P2

10 Interrupt

Normal to alarm threshold

Normal to o/c threshold

Alarm to s/c threshold

0

176

P3

P4

P5

P6

Normally Closed

Parameter Description

No alarm resistor

100 ohm alarm resistor

Mode

P0

P1

Change to 9 to select normally closed operation

Normal to s/c threshold

Normal to alarm threshold

P2

P3

P4

P5

P6

Default

8

122

50

0

Default

8

122

50

Issue 1.5 24 March 2006 Page 3-37

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.18

Document: LT0273

CP820 MANUAL CALL POINT

3.18.1 GENERAL

The CP820 Manual Call Point consists of a MIM800 mounted on a Break Glass Switch assembly. The MIM800 is factory programmed with a different type-id to allow the CP820 to be distinguished from a generic MIM800.

The normal response time to an input change of state is 0 – 5 seconds, as each device is polled at 5 second intervals by the MXP. If faster operation is required, interrupt operation can be enabled. Interrupt operation allows a change to be signalled by the device so that the

MXP detects the change immediately, rather than waiting for the next poll of the device.

The CP820 is made without an EOL resistor and no wiring fault monitoring is provided as all the wiring is internal.

The CP820 device processing will not use AVF, even if it is enabled for the circuit the CP820 is allocated to.

The mode determines whether interrupt operation is enabled or not. A value of 0 (default) means interrupt is disabled, while a value of 2 enables interrupt operation.

Parameter Description

Mode

Default

0

P0

2 Interrupt

Normal to alarm threshold

P1

P2

P3

P4

P5

P6

122

Page 3-38 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.19 FP0838 / FP0839 MANUAL CALL POINTS

3.19.1 GENERAL

The FP0838 and FP0839 Manual Call Points consist of a MIM801 mounted on an 1841

Break Glass Switch assembly. They are designed for normally closed contacts as is required in New Zealand.

The normal response time to an input change of state is 0 – 5 seconds, as each device is polled at 5 second intervals by the MXP. As faster operation is required in New Zealand,

interrupt operation should be enabled for the MIM801. Interrupt operation allows a change to be signalled by the device so that the MXP detects the change immediately, rather than waiting for the next poll of the device. Default programming of the MIM801 selects open circuit alarm and interrupt operation.

The FP0838 and FP0839 Call Points include a LED visible from the front. This lights on alarm and can be programmed to blink when the MIM801 is polled. Operation is otherwise as for the MIM801.

These Call Points are programmed as MIM801s. Refer to section 3.16.5.

Issue 1.5 24 March 2006 Page 3-39

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.20

Document: LT0273

DIM800 DETECTOR INPUT MONITOR

3.20.1 GENERAL

The DIM800 Detector Input Module is suitable for interfacing conventional non-addressable detectors e.g. heat detectors, smoke detectors, beam detectors, etc, onto the MXP loop.

Alarm and o/c fault conditions are determined by the MXP. An alarm can be recognised within 5 seconds if AVF is not enabled for the circuit, or 15-20 seconds if AVF is enabled.

Recognition of a fault condition takes about 30 seconds.

The DIM800 has two inputs, the state of which are ORed to generate the point status.

Therefore unused inputs must be terminated with the correct EOL.

The DIM800 provides electrical isolation of the detector circuit(s) from the MXP loop.

The DIM800 requires an external supply to power the detector circuit and the module itself. If external power is not provided the DIM800 will not respond to polls and a NODE FAIL fault will be indicated. The voltage of the external supply at the DIM800 is critical to ensure

compatibility with particular detectors. Refer to Table 3-4.

The external supply cannot be derived from the MXP loop or the MX4428 responder loop, and in some cases cannot be taken from the MX4428 main power supply. Where the voltage range is critical, it is recommended that a dedicated power supply and battery be used. The voltage drop in the wiring from the power supply to the DIM800 must be calculated to ensure the supply voltage at the DIM800 is within specification. If multiple DIM800s are on the same cable, then the maximum current drawn by each DIM800 (e.g. input short circuit) must be used.

The external supply must comply with AS4428.1 and AS4428.5 and should be set to 27.3V by default. The wiring from a common PSU to multiple DIM800 modules must be arranged so that a single open circuit does not prevent alarms from being generated in more than one zone. A loop arrangement with supervision and a reverse-feed relay can be used to achieve this - refer to Product Bulletin PBF0200.

If the detector itself requires a 24V power supply that needs to be switched off to reset the detector, e.g. some beam detectors, refer to Product Bulletin PBF0213 for a suitable arrangement. Do not use the SW+ and SW- terminals available on early DIM800 models.

Field wiring of the DIM800 is shown in Figure 3.6. The wiring instructions for the particular

detector/base must be referred to as some detectors break the negative line, and others the positive line, when the detector is removed.

Page 3-40 24 March 2006 Issue 1.5

Document: LT0273

Conventional

Detectors

(refer appropriate wiring diagrams)

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Unused inputs (A or B) must be terminated with 4k7 EOL.

4k7 EOL 4k7 EOL

+

EXT

PSU

-

Refer text for voltage requirements

ANALOG LOOP

PREVIOUS

DEVICE

L+ LL+ LA+ A- B+ B-

DIM800 DETECTOR

INPUT MONITOR

ANALOG LOOP

NEXT

DEVICE

Figure 3.6 DIM800 Field Wiring

Dimensions Height: 61mm Width: 84mm Depth: 25mm

Weight 100g

Line Connections

Loop Supply Voltage

Loop Supply Current

L-, L+

20V – 40V

Standby/Alarm Loop Current : 100uA (typical)

EOL

Detector Load

External Current (normal)

External Current (shorted)

4k7 + / - 1%.

3.0mA max per circuit

7.5mA (excluding detectors)

30 - 50mA (depends on supply voltage)

External Supply Voltage

Refer to Table 3-4 for each detector.

Maximum Line Resistance 50

Ω (with detectors)

1750

Ω (with hard contacts only)

Short Circuit Fault Option Maximum line resistance 34

Ω

Minimum Detector Alarm Voltage 5.0V

Issue 1.5 24 March 2006 Page 3-41

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

Series

Minerva

Model

614P Photo Detector

614I Ionisation Detector

614CH Carbon Monoxide + Heat Detector

614T Heat Type A, B, C, D

MD614 Heat Detector

MR614 Photo Detector

MR614T HPO Detector

MU614 CO Detector

MF614 Ionisation Detector

T614 Heat Type A, B, C, D

Max Qty External Supply

Voltage at DIM

25

38

32

23

40

22

21

40

30

20.0V – 28.7V

20.0V – 28.7V

20.0V – 28.7V

20.7 – 28.7V

20.7V - 28.7V

20.7V - 28.7V

20.7V - 28.7V

20.7V - 28.7V

20.7V - 28.7V

4098 – 9603EA Ionisation Detector

4098 – 9601EA Photo Detector

Simplex

4098 – 9618EA,-9619EA,-9621EA Heat

Detectors

Olsen

P24B Photoelectric Detector

P29B Photoelectric Detector

C24B Ionisation Detector

C29B (Ex) Ionisation Detector

R23B Flame Detector*

R24B Flame Detector

DO1101 Photo Detector*

DLO1191 Beam Detector*

P136 Duct Sampling Unit

T56B Heat Detector

23

24

24

24

24

20

40

40

20

3

20.7V - 28.7V

20.0V - 28.7V

20.0V - 28.7V

20.0V - 28.7V

20.7V - 24.7V

20.7V - 26.7V

20.7V - 26.7V

20.7V - 26.7V

20.7V - 24.7V

22.7V - 28.7V

16

1

5

40

21.7V - 27.7V

22.7V - 28.7V

20.0V - 28.7V

20.0V - 28.7V

All above Olsen Detectors with Z52B, Z54B,

Z54B Mk2, Z56, Z500 base as appropriate

T56B Heat Detector with

Z52B, Z55B, Z56N, Z500N Base

40 20.0V - 28.7V

System

Sensor

885WP-B Weatherproof Heat Detector

Type B *@

40 20.0V – 28.7V

- Hard Contact Devices (T54B, B111, etc) 40 20.0V - 28.7V

Hard contact devices must be rated for at least 30V and currents up to 50mA.

* Not an SSL Listed combination

@ Remote indicator output cannot be used in common with Tyco 614 series or the

Minerva M614 series (and most other Tyco/Olsen) detectors.

Table 3-4 Conventional Detector Compatibility

3.20.4 MX4428 PROGRAMMING OPTIONS - DIM800

Parameter Description

Mode Value Description

0 Short = Alarm

P1

P2

P3

1 Short = Fault

Normal to Alarm Threshold

Normal to Fault Threshold

Supply Fault Threshold

Default

0

P4

Page 3-42

Alarm to Short Threshold

24 March 2006

51

22

60 (this is MXP default used if

MX4428 value = 0).

On the latest revision of

DIM800, the threshold cannot be usefully varied by changing this parameter.

225 (this is MXP default used if MX4428 value = 0)

Issue 1.5

Document: LT0273

3.21

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

RIM800 RELAY INTERFACE MODULE

3.21.1 GENERAL

The RIM800 Relay Interface Module is suitable for relay outputs which require clean voltage free contacts and no supervision. For example it can be used to signal states to other systems (e.g. BMS or security systems), or to energise loads that do not need to be supervised, e.g. Door Holders.

Dimensions: Height: 61mm Width: 84mm Depth: 25mm

Weight 100g

Line Connections

Supply Voltage

L-, L+

20V – 40V

Supply Current

Contact Rating

Standby Current : 285uA (typical)

LED on : 2.8mA (typical)

2A 30Vdc

0.6A 120Vac (not permitted by AS / NZS standards)

0.3A 240Vac (not permitted by AS / NZS standards)

The field wiring is shown in Figure 3.7.

PSU

Normally

DeEnergised

Load

PREVIOUS

ANALOG LOOP

NEXT

DEVICE

DEVICE

Normally

Energised

Load

L+ LL+ L-

O+ O-

N/O COM N/C

RIM800 RELAY MODULE

Make no connection to O+ and O- terminals

Figure 3.7 RIM800 Field Wiring

Issue 1.5 24 March 2006 Page 3-43

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

3.21.4 MX4428 PROGRAMMING OPTIONS - RIM800

The mode selects the control source for the RIM800 output. By default (mode = 4) the output follows the logical relay. However if the mode is 0 then the output is controlled by the corresponding circuit alarm state.

Parameter Description

Mode Value Description

0

4

P0

Controlled by Circuit Alarm

Controlled by Relay

Default

4

P1

P2

P3

P4

P5

P6

Page 3-44 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.22 SNM800 SOUNDER NOTIFICATION MODULE

3.22.1 GENERAL

The SNM800 Sounder Notification Module is suitable for relay outputs which require supervision of the load wiring and optional supervision of the DC power supply (if any).

When inactive, a reverse polarity supervision voltage is applied to the load wiring. The load devices must therefore have internal or external reverse blocking diodes.

The load supervision can detect short and open circuit states on the load wiring only when the relay is inactive.

The 24V DC supply may be supervised.

The load must be isolated from ground and all voltage sources. All inductive loads (e.g. bells or relays) must have back-emf diodes or other noise clamping devices fitted.

Recognition of a fault condition takes about 30 seconds.

Dimensions Height: 61mm Width: 84mm Depth: 25mm

Weight 100g

Line Connections

Supply Voltage

L-, L+

20V – 40V

Supply Current

Output Circuit EOL

Standby Current : 450uA (typical)

LED On : 3.0mA (typical)

27k ohms, 0.5 watt

Contact Rating 2A 30Vdc

Load must be isolated from ground and all supplies.

Issue 1.5 24 March 2006 Page 3-45

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

27k

0.5W

EOL

ANALOG LOOP

PREVIOUS

DEVICE

+

-

+

-

+

-

L+ LL+ LS+ S- R+ R- I+ II+ I-

SNM800 SOUNDER

NOTIFICATION MODULE

-

+

Power

Supply

Power to next device

ANALOG LOOP

NEXT

DEVICE

Figure 3.8 SNM800 Field Wiring

It is recommended that the external supply covers only one zone, or the power wiring be arranged so that an open circuit in the power feed cannot affect more than one zone. A loop arrangement with supervision and a reverse-feed relay can be used to achieve this - refer to

Product Bulletin PBF0200.

3.22.4 MX4428 PROGRAMMING OPTIONS - SNM800

The mode selects the control source for the SNM800 output, load supervision, and EOL supervision. By default (mode = 15) the output follows the logical relay, the external supply is supervised, and the EOL is supervised.

Parameter Description

Mode Control Monitor

Supply ?

Monitor

EOL ?

Default

15

12 Relay

13 Relay

14 Relay

15 Relay

P0

P1 Normal to o/c fault threshold

P2

P3

Normal to s/c fault threshold

Supply fault threshold

P4

P5

P6

Page 3-46 24 March 2006

No No

No Yes

Yes No

Yes Yes

221

20

200

Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.23 LPS800 LOOP POWERED SOUNDER MODULE

3.23.1 GENERAL

The LPS800 Loop Powered Sounder Module is suitable for 24V DC outputs powered by the

MX Loop. It can supply up to 75mA at 24VDC.

When inactive, a reverse polarity supervision is applied to the load wiring. The load devices must therefore have reverse blocking diodes.

The load supervision can detect short and open circuit states on the load wiring only when the output is inactive.

The load must be isolated from ground and all voltage sources. All inductive loads (e.g. bells or relays) must have back-emf diodes or other noise clamping devices fitted.

Recognition of a fault condition takes about 30 seconds.

Dimensions Height: 87mm Width: 148mm Depth: 14mm

Weight 100g

Line Connections

Supply Voltage

Supply Current

L-, L+

20V – 40V

Standby Current : 450uA (typical)

Operated with load up to 8mA : 12mA.

Operated with load over 8mA : Load current + 4mA

Output Circuit ELD

Output Current Rating

22k ohms, 0.5 watt

75mA@24V nominal.

Voltage Drop 2V max

Note that the LPS800 has a minimum voltage drop of 2V between the line voltage and the output terminals. When the loop voltage is less than 26V, the output voltage may be less than 24V. At the minimum loop voltage of 20V, only 18V will be available for the sounder devices. From this you must subtract the voltage drop in the wiring to the sounder devices to obtain the voltage at the sounder device terminals. You must ensure the sounder devices operate correctly at this voltage.

Alternatively you must design the loop so that the minimum voltage is higher than 20V and

sufficient to give the required voltage at the sounder terminals. Refer to section 3.2.2 for loop

voltage drop calculations.

The load must be isolated from ground and all supplies.

The LPS800 is programmed as an SNM800. Refer to section 3.22.4.

Issue 1.5 24 March 2006 Page 3-47

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

22k

0.5W

ELD

+ +

-

+

-

MX LOOP

PREVIOUS

DEVICE

L+ LL+ LS+ S- R+ R-

LPS800 LOOP POWERED

SOUNDER MODULE

Document: LT0273

MX LOOP

NEXT

DEVICE

Figure 3.9 LPS800 Field Wiring

Page 3-48 24 March 2006 Issue 1.5

Document: LT0273

3.24

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

VLC-800MX VESDA LASERCOMPACT

3.24.1 GENERAL

The VLC800 is a derivative of the standard VESDA LaserCOMPACT product family, with the primary difference that it communicates directly on the MX loop.

VESDA LaserCOMPACT detectors provide very early warning of potential fire conditions by drawing air samples through 25mm pipe up to 80m long. Smoke is sampled through holes in the pipe and transported to the detector by an integrated aspirator or fan. Holes are positioned according to the application and often follow the spacing of standard conventional point detectors. Where necessary, sampling points can be constructed using capillary extensions.

The VLC800 alarm sensitivity can be set to between 0.005% obscuration / m and 20% obscuration / m. A PC plugged into the VLC800 is required to set the sensitivity, to normalise the airflow, and perform other setup functions. The sensitivity is NOT controlled at the

MX4428.

Refer to Tyco Safety Products UK publication 17A-03-VLC for further details on installing, commissioning and servicing the VLC-800.

Environment:

IP Rating:

Operating Temperature:

Detector Ambient:

Indoor Application only

IP30

Sampled Air:

Relative Humidity:

-10°C to +39°C

-20°C to +60°C

10-95% non-condensing

Dimensions:

Height:

Width:

Depth:

225mm

225mm

85mm

Weight: 1.9kg

Sampling Network:

Maximum Area Coverage: 800m

2

Maximum Pipe length:

Pipe Size:

80m with up to 15* holes, or 2 x 50m with up to 9* holes per pipe

ID15 - 21mm

‘*’ more holes may be used on networks designed using the VESDA Aspire pipe modelling software.

External 24V dc:

Supply Voltage:

Current Consumption:

18 to 30V dc

Standby: 225mA

MX Loop:

Normal: 300uA

Non operational (VLC off): 300uA

Alarm:

Alarm with external relay:

300uA dependant on the relay

Alarm with external LED: 3.3mA

Onboard relay: rated 2A @ 30V dc

Issue 1.5 24 March 2006 Page 3-49

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

Document: LT0273

3.24.3 MX4428 PROGRAMMING OPTIONS - VLC800

The only programmable items for the VLC800 are

1. The pre alarm threshold.

2. The source of the remote LED output.

3. The source of the onboard relay output and external relay output (they operate together).

The VLC800 shares default values with the 814H, 814PH, and 814PHFL. However the alarm threshold is fixed at 100 regardless of any default setting. The default pre alarm setting of 68 translates to 68% of the alarm value which although a suitable value, can be changed if required.

Parameter Description Default

P0

P6

Pre Alarm Threshold

192 plus value below

Value Relay Control

0

1

2

4

5

6

8

9

10

Circuit Alarm

Circuit Alarm

Circuit Alarm

Relay Logic

Relay Logic

Relay Logic

Point Alarm

Point Alarm

Point Alarm

Remote LED

Control

Circuit Alarm

Relay Logic

Point Alarm

Circuit Alarm

Relay Logic

Point Alarm

Circuit Alarm

Relay Logic

Point Alarm

AVF may be applied to the circuit the VLC800 point maps to.

Resulting parameter

192

193

194

196

197

198

200

201

202

68

192

Page 3-50 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Device Information and Programming

3.25 AVF / RAD / SAD / FLOWSWITCH DELAYS

AVF/RAD or SAD or FLOWSWITCH or AVF/SAD may be configured for a “circuit” and will apply to all input devices on the circuit except CP820 devices, and MIM801 devices with

“interrupt” enabled.

3.25.1 AVF/RAD

Note that AVF is usually unnecessary on the addressable detectors as the built in filtering already provides significant protection against false alarms. AVF provides an additional time delay to verify that the alarm is still present at the end of the AVF delay. It operates as follows –

Time Action

0

5 seconds

Alarm detected at detector or module - not sent to MX4428.

Reset detectors (remove power) on DIM module.

Do nothing on other modules.

10 seconds

15 seconds

Remove reset to detectors on DIM module (re-apply power), and set alarm count to 0 for DIM module (requiring count up to 6 for alarm recognition).

Resample detector or module, if still in alarm condition then alarm is transmitted to MX4428 immediately.

Immediate recognition of alarm condition and transmission to MX4428. 15 – 135 seconds

135 seconds If no alarm start again.

3.25.2 SAD

All devices on circuits set up as “SAD” at the MX4428 have the “return to normal” signalled to the MX4428 delayed by 60 seconds. If the state goes back into alarm during this time, the timer will be reset.

3.25.3 AVF/SAD

All devices on circuits set up as “AVF/SAD” at the MX4428 delay into alarm as per AVF/RAD and delay out of alarm as per SAD.

3.25.4 FLOWSWITCH

All devices on circuits set up as “Flowswitch” at the MX4428 have the alarm signalled to the

MX4428 delayed by 15, 30, or 60 seconds (depending on the MX4428 programming). If the state goes out of alarm during the delay time, the timer will be reset.

Issue 1.5 24 March 2006 Page 3-51

MX4428 MXP Engineering / Technical Manual

Device Information and Programming

THIS PAGE INTENTIONALLY LEFT BLANK

Document: LT0273

Page 3-52 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Analog Loop Design Considerations

CHAPTER 4

ANALOGUE LOOP DESIGN CONSIDERATIONS

Issue 1.5 24 March 2006 Page 4-1

MX4428 MXP Engineering / Technical Manual

Analog Loop Design Considerations

Document: LT0273

4.1 ANALOGUE LOOP CONFIGURATION SELECTION

4.1.1 LINES & LOOPS

The interface between the MXP and its addressable devices requires two wires.

The MXP has two lines (“left” and “right”) which are designed to be connected in a loop.

The LOOP configuration is generally preferred and indeed will often be mandatory for compliance with standards as discussed below.

However the MXP can be used to connect to multiple lines in a star configuration. Dual line mode is not supported.

4.1.2 LOOP FAULT TOLERANCE

Standards require that a line/loop fault condition cause minimal disruption to the system's ability to detect and transmit alarms to the Fire Panel. The MXP achieves this in the following way .....

The MXP has access to each device from both ends of the loop. The loop is normally sourced from “left” and monitored at the “right” terminals. Disappearance of 40V power at the

“right” end, due to an open circuit FAULT on either the + or – wires, can be detected

(causing a FAULT event to be sent to the MX4428 Master) and corrected by switching the

Line driver onto the “right” terminals. The LOOP mode is therefore inherently fault tolerant to any one open circuit on any one of the 2 wires.

However, a short circuit on the loop will, in general, cause the MXP to loose communication with all devices. Thus it is recommended that isolator bases be used to minimise the loss due to a short.

When designing fire alarm systems, the designer should be aware of any local statutory requirements, as well as those of AS1670.1 and NZS4512.

4.1.3 AS1670.1 DESIGN REQUIREMENTS

Australian Standard AS1670.1 sections 3.1 and 3.2 require the analogue loop to comply with the following:

• The maximum number of actuating devices (i.e. detectors and input modules) in an alarm zone shall not exceed 40.

• A single short circuit shall not disable more than 40 devices connected to the MXP loop/line. This means than if more than 40 devices are to be connected to an MXP, short circuit isolators must be used. The count of 40 includes conventional detectors connected to a DIM800 or other ancillary input device

4.1.4 NZS4512 DESIGN REQUIREMENTS

• Isolator Bases must be fitted between zones (or on the first device either side of a zone boundary) so that a single short circuit or break will affect no more than one zone.

• In many cases the tones produced by the 814SB sounder base are not acceptable.

Refer to NZS4512 for detailed requirements.

Page 4-2 24 March 2006 Issue 1.5

Document: LT0273

4.2

MX4428 MXP Engineering / Technical Manual

Analog Loop Design Considerations

ANALOGUE LOOP/LINE LAYOUTS

The MXP is designed to run in LOOP mode only. The dual line mode of the MPR is not

supported. However a star configuration can be used, refer to section 4.2.3.

DESIGN SHORT CIRCUIT ISOLATORS

There are two main reasons for using isolator bases on the analogue loop.

(i) When the MXP powers up a line/loop, it will only have to power up one section of the line/loop at a time, reducing the power required by the MXP from the MX4428 supply loop during startup.

(ii) If the loop is shorted then the MXP will loose communication with only those devices on the shorted section between 2 isolators. If every detector was mounted on an isolator base, then all detectors would remain functional in the event of a single short circuit.

Refer to Figure 4.1 for an example of loop wiring with Isolator Bases.

Issue 1.5 24 March 2006 Page 4-3

MX4428 MXP Engineering / Technical Manual

Analog Loop Design Considerations

Document: LT0273

MXP

+VE -VE +VE -VE

AL AR

MX DETECTOR LOOP

M

L2

L

L

L

L

L

L

L1

IB

L1 L2

L1

M

L

L1

L

L1

L

L1

L

L1

L

L1

IB

L1 L

L1 L

L1 L

L1 L

L1 L

L1

L

L

L1

L

L1

L

L1

L

L1

L2

M

L

L1

IB

L1

L1

L1

L1

L1

L1

M

L1

L L1 L L1

L2 L1

L2

IB

M

IB

Figure 4.1 Loop with Isolator Bases

Note 1: Although it is not essential to have Isolator Bases between the MXP and the first / last device on the loop, greater protection is provided by doing so. It is recommended that the cable between the MXP line terminals and the adjacent Isolator Bases should be kept as short as possible, and have no devices attached to it. These Isolator Bases could be located at the MXP without detectors plugged into them.

Note 2: The maximum number of devices between Isolator Bases is 100 or less depending

on the devices. Refer to section 3.2.4.

Note 3: The M and L2 connections are interchangeable.

Page 4-4 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Analog Loop Design Considerations

It is not always necessary to connect addressable systems as loops, especially if an existing conventional detector system is being converted to addressable detectors. As the existing detector zone cables probably already terminate at the main panel, it is possible to connect

these in a star connection to the MXP as shown in Figure 4.2.

The two line terminals should be joined together as shown in Figure 4.2. The total length of

cable connected to the MXP should not exceed 2000m.

Because shorting the cable in one line will short out all the other lines connected to the same

MXP, it is recommended that 5BI Isolator Bases be fitted at the start of each line and then

placed every 20 - 40 devices along each line. (Refer to section 3.2.4 for the calculations to

determine where the isolator bases must be positioned.) The cabling from the MXP to the initial Isolator Bases should be as short as possible. In fact 5BI Isolator bases without detectors can be used at the star junction point.

Note: The Star Connection is not recommended for new installations. A loop configuration should be used as it offers open circuit fault protection and with Isolator Bases, short circuit protection.

4.2.4 SPURS

Both the loop topography described in section 4.2.2 and the star topography described in

section 4.2.3 can have "spurs" attached. (Spurs on a spur for the star topography.)

Any such spur should be connected to the loop or its parent spur with an isolator base.

However spurs are not recommended for new installations as an open circuit will disconnect all detectors further away from the MXP than the open circuit, and a short circuit on a spur will disconnect the whole spur.

In any case, to comply with standards, all the detectors on a spur should be in the same zone.

Issue 1.5 24 March 2006 Page 4-5

MX4428 MXP Engineering / Technical Manual

Analog Loop Design Considerations

Document: LT0273

MXP

+VE -VE +VE -VE

AL AR

MX DETECTOR LOOP

L

L

L

M

L2

L

L

L1

M

L2

L1 L

L1

M

L2

L1 L

L1

M

L2

L1 L

L1

L

L1

L

L1

L

L1

L1

4 Isolator

Bases

(with or without detectors)

Universal Bases,

Sounder Bases,

Relay Bases

L1

L1

L1

L

L

L1 L

L1

L1

L1

L

L

L

L1

L1

L1

L

L

L

L1

L1

L L1 L L1 L L1 L

L1

L1

SPUR1

NOTE : Total cable length < 2000m

SPUR2 SPUR3 SPUR4

Figure 4.2 STAR CONNECTION ON MXP

4.3 CABLE SELECTION CONSIDERATIONS

Selection of cable to implement the Analogue Loop requires specification of .....

(i) CABLE TYPE

(i.e. construction and choice of materials)

This is determined from consideration of .....

MECHANICAL -

REQUIREMENTS

For instance, does the application specification, or prevailing standards, call for

fire etc.

Page 4-6 24 March 2006 Issue 1.5

Document: LT0273

ELECTRICAL -

MX4428 MXP Engineering / Technical Manual

Analog Loop Design Considerations

Different construction/materials give different

(i.e. gauge of wire used)

MECHANICAL- Does the application

REQUIREMENTS specification, or prevailing standards, call for a minimum gauge

(AS1670.1 specifies a minimum of .75mm² standard, for instance).

ELECTRICAL - What is the minimum gauge wire that can be

REQUIREMENTS used without exceeding the maximum voltage drop for the number of devices over the required loop length.

The four areas to be considered therefore are requirements

• DC requirements

4.4

4.4.1 GENERAL

All common types of wiring with a total length of up to 2000m may be used. Refer to section

3.2.3.

4.5 DC CONSIDERATIONS

4.5.1 GENERAL

A maximum voltage drop of 17V is allowed on the cable from the MXP to the most distant device. This applies both where

• the cable is driven from the “left” end only.

• the cable is driver from the “right” end only.

Refer to the calculations in section 3.2.2.

4.6 MECHANICAL CONSIDERATIONS

Electrical considerations aside, the system design should take into account mechanical aspects such as .....

• Need for fire rated cable.

• Need for mechanical protection.

Issue 1.5 24 March 2006 Page 4-7

MX4428 MXP Engineering / Technical Manual

Analog Loop Design Considerations

4.7

Document: LT0273

Although the MXP loop has been designed for minimum electrical interference, it is still capable of both picking up and generating electrical interference. The longer the loop the greater the potential problems. Each analogue loop must be considered on its own merits, taking into account possible noise sources along the loop's proposed routing. Normal engineering practice applies, such as keeping the loop wiring separate from other wiring, especially power cables, speaker cables, leaky coaxial cable and noise sensitive cables for audio systems.

In extreme cases it may be necessary to implement the analogue loop as a screened pair, with the screen connected to the metal case at the MXP only.

Page 4-8 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering /Technical Manual

CHAPTER 5

MXP CURRENT CONSUMPTION

Issue 1.5 24 March 2006 Page 5-1

MX4428 MXP Engineering / Technical Manual

MXP Current Consumption

5.1 THEORY

Document: LT0273

The MXP current consumption is considerably higher than that of the other responders (even higher than the MPR, in fact it can be considerably higher than the MPR depending on the sounder load). It must be carefully considered when engineering the MX4428 responder loop.

Use of the F4000CAL PC program is strongly recommended as it performs the following calculations automatically.

A formula for predicting the MXP current is.....

I(mA) = (ITOT(mA) * (40V / VIN) * ( 1 / PCE) ) + (IQ(mA) * (24V / VIN))

Where .....

PCE =

IQ =

Power converter efficiency = 0.80

MXP quiescent current at 24V = 50mA.

ITOT = Total current sourced into the AL and AR terminals, which can

be calculated as shown in Section 3.2.2

VIN = MX4428 Responder Loop voltage

The alarm current calculated for all responders can be calculated and used to ensure that

1) The total current to be sourced from the MX4428 does not exceed 2.0A

2) No responder will see a supply voltage of less than 17V, allowing for the minimum battery voltage at the MX4428 and voltage drops in the responder loop wiring.

Once MXP currents are calculated, the voltage drops around the responder loop can be calculated. This will give a more accurate figure for the operating voltage of each MXP which will result in a slightly different current consumption. The full calculation is an iterative process when performed manually, and it is recommended that the PC program F4000CAL is used.

Taking the example from section 3.2.5, where the alarm current was calculated at 221mA,

the MXP supply current at (22V) will be

I(mA) = (ITOT(mA) * (40V / VIN) * ( 1 / PCE) ) + (IQ(mA) * (24V / VIN))

= (221 * (40 / 22) * (1 / 0.8)) + (50 * (24 / 22))

= 502mA + 55mA

This current, together with the load of other responders on the MX4428 responder loop, can be used to calculate the voltage drops on the responder loop power wiring, and possibly refine the value used for the MXP supply voltage (22V above). The calculations can be performed iteratively until little change is evident.

Page 5-2 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering /Technical Manual

It is of interest to recalculate the current consumption assuming for example the supply voltage is only 17.0V (the minimum operating voltage of the MXP). In this case the consumption is increased to 721mA. It can be seen that if the responder loop power wiring has too much resistance, the voltage to the responders is reduced by their current consumption, which results in them requiring even more current and compounding the problem.

The quiescent current of all responders can be calculated and used to ensure there is enough battery capacity and supply current at the MX4428.

The quiescent current for the MX loop is calculated as in section 3.2.2, but using the

quiescent current instead of the alarm current. Then the MXP supply current can be

calculated as described in section 5.1. Once again iterative calculations may be required to

adjust for the responder loop voltage drop.

The heat loss from the MXP PCB can be calculated as follows –

W = ITOT(mA) * 40V * ( 1 - PCE) / PCE + IQ(mA) * 24V

Where .....

W

PCE

=

=

Heat loss in milliwatts

Power converter efficiency = 0.80

IQ = MXP quiescent current = 50mA at 24V.

ITOT = Total current sourced into the AL and AR terminals, which can

be calculated as shown in Section 3.2.2

Using the above figures, the equation simplifies to

W(mW) = ITOT(mA) * 10V + 1200mW

This can be calculated separately for quiescent and alarm conditions, depending on whether quiescent or alarm figures are used to calculate IQ.

The maximum possible heat loss is 5.2 watts.

Issue 1.5 24 March 2006 Page 5-3

MX4428 MXP Engineering / Technical Manual

MXP Current Consumption

THIS PAGE INTENTIONALLY LEFT BLANK

Document: LT0273

Page 5-4 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Event Log and Status at MX4428

CHAPTER 6

EVENT LOG AND STATUS AT MX4428

Issue 1.5 24 March 2006 Page 6-1

F4000 MXP Engineering / Technical Manual

Event Log and Status at MX4428

6.1

Document: LT0273

RETURNED ANALOG VALUES

The MXP returns up to 4 different analog values per device - CV, TV, HH, and HL. The following table details what each value means for each device type.

Type CV TV HH HL

814H Temperature ROR History History High of

Current Value of Temperature SLV ROR SLV

814PH Smoke CV Smoke TV Temp CV HH percent*

(max% of Temp SLV,

Temp ROR SLV,

Smoke SLV)

814CH

814I

CO CV

Current Value

CO TV HH percent*

(max% of Temp SLV,

Temp ROR SLV,

CO SLV)

Tracked Value History High of SLV

Temp CV

MIM800

MIM801 analog i/p analog i/p

CP820 analog i/p

CIM800 analog i/p 1

DIM800 analog i/p 1

– analog i/p 2 analog i/p 2

History High

History High

History High

Hist High (both)

Hist High (both)

History Low of

SLV

History Low

History Low

History Low

Hist Low (both)

Hist Low (both)

LPS800 Analog i/p 0

(while not operated)

RIM800 –

VLC800 Current Value

Supervision

Analog i/p 1

(while not operated)

Fixed at 12

History High EOL

Supervision

History High of analog i/p 0 (while not operated)

History High %*

History Low EOL

Supervision

History Low of analog i/p 0 (while not operated)

0

*HH percent will indicate whichever of Temperature, Rate of Rise, or Smoke/CO has been highest, in terms of the percentage of its alarm threshold. It will be rounded to the nearest

5%, and the last digit will indicate which type it represents. A last digit of 0 or 5 indicates smoke or CO. A last digit of 1 or 6 indicates temperature, and a last digit of 2 or 7 indicates temperature rate of rise.

For example, 51 will indicate that temperature has been highest at 48-52% of the alarm threshold. 65 will indicate smoke/CO has been highest, at 63-67% of the alarm threshold.

For temperature 20

°C will be 0% and the alarm limit 100%.

All History High and History Low values (where used as maximum and minimum) will be based on Step Limited values i.e. the same values as are used for alarm comparison.

However note that PreAlarm comparisons are performed using “CV”, i.e. values without Step

Limited filtering. Therefore a PreAlarm may occur even though the “History High” value is less than the PreAlarm Threshold.

Page 6-2 24 March 2006 Issue 1.5

Document: LT0273

6.2

MX4428 MXP Engineering / Technical Manual

Event Log and Status at MX4428

FAULT AND ALARM EVENT LOG

The table below lists examples of event log items which are produced at the MX4428 panel.

Circuit / point event logging must be enabled to see the events listed below. Zone events are not shown.

Event on MXP Event Logged

RSP 1 DATABASE TX

Event Logged on return to normal

RSP 1 DATABASE TX Database tx from F4000 to MXP

Point Alarm

Point Fault

CCT 1/1 ALARM

PNT 1/30 ALARM

CCT 1/1 FAULT

PNT 1/20 FAULT

PNT 1/3 PRE-ALARM

CCT 1/1 ALARM CLR

PNT 1/30 ALARM CLR

PNT 1/20 FAULT CLR

CCT 1/1 NORMAL

PNT 1/3 ALARM CLR Point Pre-Alarm

SNM800 wiring o/c or s/c

SNM800 Supply Fail

SNM800 / RIM800 checkback fail

RLY 1/1 FAULT

PNT 1/26 SUPERVISION

PNT 1/26 NORMAL OFF

RLY 1/1 NORMAL

FAULT

RLY 1/1 FAULT PNT 1/26 NORMAL OFF

PNT 1/26 LOAD SUPPLY RLY 1/1 NORMAL

FAIL

RLY 1/1 FAULT

PNT 1/24 CONTROL CB

PNT 1/24 CONTROL CB NML

(RIM800)

DIM800 Supply Low

(SNM800)

RLY 1/1 NORMAL

CCT 1/1 FAULT

PNT 1/25 FAULT

PNT 1/25 FAULT CLR

CCT 1/1 NORMAL

PNT 1/25 LOAD SUPPLY

FAIL

Point scan fail

PNT 1/22 NODE FAIL

CCT 1/1 FAULT

Detector calibration fault CCT 1/1 FAULT

PNT 1/2 FAULT

PNT 1/2 PARAMETER

Loop o/c

PNT 1/22 NODE FAIL CLR

CCT 1/1 NORMAL

CCT 1/1 NORMAL

PNT 1/2 FAULT

ERROR

RSP 1 LOOP OPEN RSP 1 LOOP OPEN CIRCUIT

Loop line A or B short or overload

Type Mismatch

RSP 1 LOOP SHORT RSP 1 LOOP SHORT CIRCUIT

Foreign Device

PNT 1/1 POINT TYPE PNT 1/1 POINT TYPE OK

MISMATCH

PNT 1/3 FOREIGN DEVICE

(note- re-logged after DP command)

System Test or autotest

- device not normal at start

System Test or autotest

- device alarm test fail

PNT 1/2 TEST START NOT NML

CCT 1/1 FAIL SELF TEST 3 1

PNT 1/1 ALARM TEST FAIL

CCT 1/1 FAIL SELF TEST 3 1

Zone alarm test device fail

PNT 1/1 ALARM TEST FAIL

Diagnostic Pollscan result -Correct point found

P1/22 LINE 1 OK LINE 2 OK LED OFF

Diagnostics Pollscan result - point not found

Diagnostic Pollscan result -Type mismatch

P1/100 LINE 1 FAULT LINE 2 FAULT LED

OFF TYPE OK

P1/20 LINE 1 OK LINE 2 OK LED OFF

Note “Type Mismatch” means a different device type was found at an address, from the type programmed in the panel configuration for that address. An example of this would be a

MIM800 found at an address that is configured to have an 814PH. Refer to section 3.1.1 for

details of some device substitutions that are accepted without generating a fault.

Issue 1.5 24 March 2006 Page 6-3

F4000 MXP Engineering / Technical Manual

Event Log and Status at MX4428

THIS PAGE INTENTIONALLY LEFT BLANK

Document: LT0273

Page 6-4 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

MXP Technical Description

CHAPTER 7

MXP TECHNICAL DESCRIPTION

Issue 1.5 24 March 2006 Page 7-1

MX4428 MXP Engineering /Technical Manual

MXP Technical Description

7.1 GENERAL

Document: LT0273

The MXP has two major functions:

(i) To provide an interface to an MX4428 responder (communications/power) loop, via which data gathered by the MXP may be transferred to the MX4428 Master for display, annunciation, and processing as appropriate.

(ii) To provide an interface to the Analogue Loop. Data retrieved from the devices connected to the Analogue Loop is processed to determine the ALARM/NORMAL/

FAULT status of each device, and this data is passed on to the MX4428 Master via the MX4428 Loop Interface. The Analogue Loop interface also allows outputs to be sent to those devices that support them, to initiate device tests, activate relays, etc.

The MXP is implemented as one printed circuit board (1901-213).

Page 7-2 24 March 2006 Issue 1.5

Document: LT0273

7.2

MX4428 MXP Engineering / Technical Manual

MXP Technical Description

CIRCUIT DESCRIPTION

A block diagram of the MXP is given in Figure 7.1.

The MXP can be divided into 4 sections:

(i) The microprocessor and memory. This is the "heart" of the MXP.

(ii) The power supply. The power supply produces the 40V isolated supply for the

Analogue Loop and also the 5V isolated supply for the microprocessor.

(iii) The MX4428 Loop Interface. The Loop Interface contains the connect, disconnect circuitry for the MX4428 Loop Power Supply and also the serial data driver circuits.

(iv) The Analogue Loop Interface. This section contains the Loop Driver/ Receiver circuit and the Loop Isolator circuits.

The MXP is controlled by the 68302 Microprocessor CPU (U1). Connected to the CPU bus is the FLASH (U2) which contains the MXP software, and the RAM (U3 and U4) which is used for storing parameters and data associated with devices on the Analogue Loop.

The 68302 includes a communications processor with 3 serial ports. These are used for the

2 responder loop ports and a diagnostic port.

To reduce the number of components on the PCB, a PAL (Programmable Array Logic) (U5) is used to generate bus signals such as RD-, L WR-, and U WR-. It also drives the status

LED and is used to read some of the DIP switches.

Both the FLASH (U2) and PAL (U5) are factory programmed for use in the MXP. However the FLASH (U2) can easily be reprogrammed in the field.

7.2.2.1 Power On Reset & Watchdog Circuits

The power on reset consists of the DS1232 (U6), which drives the RST signal to the CPU low when the 5V supply is below 4.6 Volts. This ensures that the CPU does not corrupt the

RAM when the 5V supply collapses, and the CPU starts up reliably when the 5V supply turns on. The DS1232 also includes a Watchdog circuit inside, to produce a RESET if the CPU stops running properly.

7.2.2.2 Memory

Memory addresses are decoded by the MC68302. When first powered up the FLASH occupies the bottom 8k bytes. However the software relocates the FLASH so that the memory addressing is as follows -

000000 - 03ffff RAM

400000 - 47ffff FLASH

800000 - 80000f LED and SWITCHES via PAL f00000 - f00fff INTERNAL RAM AND PERIPHERALS

The RAM memory and PAL chip are powered by the +5VB supply, which has a supercap

(C68) to supply power when the MXP is powered down. This allows the MXP to retain its

RAM memory contents for typically 10 hours on MXP power down.

Issue 1.5 24 March 2006 Page 7-3

MX4428 MXP Engineering /Technical Manual

MXP Technical Description

Document: LT0273

Switching PSU

+40V ISO

POWER SUPPLY

24V IN +V

Q22

+VS

U10

Q17

D36

RL3

0V

C65.C66

24V OUT

0V IN

D44

R90

Connect / Disconnect

0V

0V

D37

U7C, U7D

0V OUT

RESPONDER

LOOP

CHNL1

CHNL2

U7A

MIN V

D35

RESPONDER LOOP INTERFACE

OC1

RL3 opto coupler

OC5 opto coupler

Q18, Q20

Line Drivers /

Receivers

U7B opto coupler opto coupler

OC3

OC2

U8

Latching

Relay

Drive

Disconn In -

Q19, Q20 opto coupler

OC4

Isolation Barrier

Watchdog /

Reset

Generator

U6

Data / Address

RAM

64kb / 256kb

Diagnostic

Port

Pseudo RS232

Interface

68302 CPU /

Comms Processor

U3, U4

U1 opto coupler

OC6

FLASH

256kb / 512kB

U2

U11

Feedback

MICROPROCESSOR and MEMORY

+5V ISO

0V ISO

Nosex RX

40VReset

Overload -

AD1..5

5 bit D/A

Convertor

R76-R82

Relay

Drive

Q5, Q6

RL1

RL2

RL1

40V ISO

Overcurrent

Detector /

Shutdown

Q12, Q2, Q1,

Q4, Q13

Modulator

Q14, Q15

0V ISO

RL2

Left

Analog

(NOSEx)

Loop

ANALOG LOOP INTERFACE

Right

Receive

Discriminator

Q3, U13A

0V ISO

Sense

OC7

Return Fault

Figure 7.1 MXP Block Diagram

7.2.3 MXP POWER SUPPLY

The raw power to the board is supplied from the 24VIN terminal (via D36) or the 24VOUT terminal (via D34), or both, depending on the Loop conditions.

This voltage "+V" is smoothed and maintained by reservoir capacitors C65, C66, and C71, which store sufficient charge to maintain the circuitry under transient loop fault conditions.

From "+V" the following supplies are derived:

Page 7-4 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

MXP Technical Description

(i) +VS This is a switched version of "+V", which is switched OFF when the loop supply falls below the voltage required for correct operation of the MXP.

(ii) 40V ISO A regulated, isolated 40V supply used to drive the Analogue

Loop circuitry and addressable devices.

(iii) 24V ISO

(iv) 5V

Derived from 40V ISO to power 24V relays.

Used to power the CPU and logic circuitry.

(v) 5VB Used to power the RAM and PAL. Backed up by supercap

(C68).

Descriptions of the circuitry required to generate these power supplies follow.

The MXP is specified to operate over an MX4428 loop supply range of 17.0V to 30.0V. The

MX4428 loop fault clearing technique relies on the fact that responders that are not powered

up "look like" a high impedance (see Section 7.2.4 for details). The circuitry is therefore

divided up into two sections, a (relatively) high current portion which becomes active only when adequate voltage is available, and a low current portion that is continuously powered up and whose sole purpose is to sense the loop voltage and control the enabling/disabling of the high current circuitry. Loop voltage sensing is performed by comparator U7:C and associated components which, in turn, operate power switch Q22 to feed +VS. Since the voltage regulator draws peak currents up to around 5A, a FET is used for Q22, which gives a low voltage drop for minimal control (gate) current.

D39, R12, R35, R113 ensure that +VS becomes active if the loop supply exceeds 17.0V, with R28, R110, D38 providing about 4V of hysteresis (i.e. once switched on +VS will stay switched on until the supply voltage drops below 13V).

The 40V ISO and 5V ISO supplies are produced using the switch mode power supply controller IC U10, FET Q17, and associated components. The circuit configuration is such that the circuit operates in flyback mode, energy being stored in L1 primary during Q17's ON period and transferred to the two secondary windings during the OFF period.

The current into the diode of optocoupler OC6 increases rapidly as the 40V ISO voltage passes through 40V (adjustable by means of VR1). The optocoupler OC6 controls the feedback to U10 pin 2 which adjusts the duty cycle of the current pulses into L1's primary and maintains regulation of 40V ISO.

R6 and C63 provide stability, essentially coupling the sawtooth from the internal oscillator to the comparator – input, thereby making the + input a much lower gain pulse width control than it would otherwise be. R107, R65, C38 provide over-current protection, while C34 defines the frequency of oscillation (approximately 80KHz). D41 and C77 provide a “soft start” circuit to reduce the current taken during the startup time.

The 40V ISO voltage is regulated by a linear regulator consisting of Q23, D40 and associated components. This supply is only required to supply a low current (about 30mA max) to drive relays. The reference diode (D40) used for the 24V supply is also used as the reference for the 40V supply.

Issue 1.5 24 March 2006 Page 7-5

MX4428 MXP Engineering /Technical Manual

MXP Technical Description

Document: LT0273

7.2.3.4 +5V ISO & +5V Batt

A second L1 secondary winding is used to produce an 8V supply, This 8V supply is poorly regulated and may vary from 7.5V to 10V depending on the 40V ISO load. The 8V supply is regulated by U11 to 5.2V.

This supply is then passed through D32 to produce the 5V supply for the CPU and logic circuitry. The 5.2V supply also passes through D31, to produce +5V Batt, and this supply contains a supercap (C68) which is used to keep this supply up after the power supply has shutdown. R66 is used to limit the charge current to the supercap. This supply is used to power the RAM on the MXP, and retain its contents during short (up to a few hours) power downs.

7.2.4 MX4428 LOOP INTERFACE

7.2.4.1 Loop Disconnect Circuitry

The MXP, like all MX4428 compatible Responders, includes a DISCONNECT relay (RL3) which is used to isolate shorts on the power supply loop.

Normally 24V power passes from one Responder to the next via the 24VIN terminal /

DISCONNECT relay / 24 VOUT terminal path, supplying power to the Responder on the way through. D35, D37, R90 form a diode gate such that a loop short on either 24VIN or

24VOUT applies a low voltage to comparator U7:D. This generates a DISCON IN- signal to the microprocessor which then opens the DISCONNECT relay to isolate the fault.

Depending on the time taken for the shorted section to be isolated, the power output of the

MX4428 panel may collapse completely, removing power from all responders. Therefore it is necessary for them to respond rapidly to the DISCON IN signal and open the DISCONNECT relay in their last dying gasps before their power supplies collapse to zero.

Generally, all Responders on the loop respond in like fashion and break the loop supply.

(Depending on the position of the short, and loop resistances, some may not open their

DISCONNECT relays.) Starting from the Responder nearest the MX4428 Master, each

Responder then makes a decision, based on the value of “MIN V” (refer to Figure 7.1)

whether to re-connect the relay or not. If MIN V is less than +V/2, the loop fault is on one of its 24V terminals, so it will not re-close its DISCONNECT relay. If, however, MIN V is greater than +V/2 the fault lies beyond the next Responder and it can therefore apply power to that Responder.

The newly powered up Responder then makes a similar decision, followed by each successive Responder up to the Responder with the loop fault on its far side which will not close its DISCONNECT relay.

Similarly Responders on the other end of the Responder loop will close their DISCONNECT relays, up to the Responder connecting to the section of the loop with the short circuit.

With a single short circuit, all responders will eventually be powered up (receiving power from one end of the loop or the other), however the two responders on either side of the short will have their DISCONNECT relays open.

7.2.4.2 Disconnect Relay Driver

U8A and U8B with Q10 and Q11 form a bridge circuit to drive DISCONNECT relay RL3.

This is a magnetically latched relay to save power consumption. Its position can be switched by providing a short pulse of voltage, with the polarity of the voltage controlling the position.

Page 7-6 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

MXP Technical Description

In response to DISCON IN– going low, the microprocessor outputs a 10 msec pulse to

DISCON OUT+, which applies “0V” to RL3 pin 16 through D5 and U8 pin 2, and “+24V” through Q11 to RL3 pin 1, thereby setting the relay contacts to their open state. When

DISCON IN+ goes low the microprocessor outputs a 10 msec pulse to CONOUT, which applies “0V” to RL3 pin 1 through D6 and U8 pin 1, and “+24V” through Q10 to RL3 pin 16, thereby re-setting the relay contacts to the closed state.

The DISCON IN– signal is configured as an interrupt signal to the CPU. This allows a very fast response to it going low and ensures the relay is opened immediately. This is necessary as a short anywhere on the responder loop will often result in the responder power collapsing completely and the relay must be opened while sufficient charge remains in capacitors C64, C65, C66, and C59-C62.

When neither DISCON OUT+ nor CONOUT is high, no power is applied to the coil of RL3.

7.2.4.3 MX4428 Communications Circuitry

The duplicated MX4428 communications channels are implemented using serial ports 1 and

2 of the 68302 CPU. The two transmit lines are isolated with optocouplers and buffered with

Darlington drivers. The receive circuits are protected with series resistors and shunt diodes/capacitors, digitised with comparators, and isolated with optocouplers.

Passing messages around the loop is done entirely with software. For details of the MX4428 responder protocol and loop operation, refer to “F4000 Technical Manual - Appendix C,

Responder Communication Protocol”.

7.2.5 ANALOGUE LOOP INTERFACE

The Analog Loop (also known as MXP loop or NOSEx loop) is a two-wire circuit with the

MXP being the master and up to 200 addressable devices which are slaves.

The MXP supplies the loop power (36 - 39V dc) which powers the addressable devices and sounder outputs. The loop + voltage is modulated with a 4V p-p dual frequency sinewave in order to transmit data using the power wire.

Both the MXP and the addressable devices transmit and receive in the same way. The addressable devices normally only transmit immediately after they have been polled by the

MXP, however in special circumstances they can transmit interrupt messages when they have something urgent to send.

An example of a message on the loop is shown in Figure 7.2.

Issue 1.5 24 March 2006 Page 7-7

MX4428 MXP Engineering /Technical Manual

MXP Technical Description

Document: LT0273

Figure 7.2 Analog Loop Typical DC Level and Data Waveform

The current drawn by the analog loop passes through current sense resistors R22 - R26.

When the voltage across these resistors exceeds approximately 0.65 volts (corresponding to a current of just over 400mA), the collector of Q2 begins to conduct. Thermistor RV3 and resistor R119 compensate for the fact that the VBE threshold voltage of Q2 varies with temperature. Q2 conducting pulls the gate of Q12 to +40V and switches off Q12. The drain of Q12 then drops to around 5V or less depending on the load on the analog loop. Q13 is then turned on by the current through R5. Q13 then holds Q12 off even though the overload is now gone and Q2 is no longer conducting.

This “latched” over-current situation can only be reset by the CPU. The CPU senses the absence of 40V through the sense resistors R68 and R67 and the signal OVERLOAD– going to a logic low. The CPU (periodically) tries to reset the over-current latch by applying a short (approx 5 ms) pulse to “40V RESET”. This pulse turns on Q4 and Q1, which turns off

Q13. Q12 will then turn back on and stay hard on as long as there is no over-current.

For the duration of this 5 ms pulse, the latching action of the circuit is disabled, and Q12 will act as a linear current limiter. During this time the dissipation in Q12 can be up to 40V *

400mA i.e. 16 watts. This will be an excessive dissipation for Q12 if it continues indefinitely, which is why the reset pulse is limited to 5 ms, and indeed why the latching action is required in the first place.

Page 7-8 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

MXP Technical Description

Each bit transmitted consists of single cycle of a sinewave of one frequency for a ‘0’ and another frequency for a ‘1’. Each cycle is made up from a number of discreet samples, with a

5uS spacing between samples. For each sample the digitised value is output on the 68302

CPU onto signals AD1, AD2, AD3, AD4, and AD5. These signals are converted to an analog voltage “TXDATA” by resistors R72, R73, R74, R75, R76, R77, R82, R81, R80, and R79, which form a conventional R/2R ladder. Resistor R78 adds a DC offset of about 1.5V to the

TXDATA voltage.

Transistor Q14 is a current sink with the current controlled by the TXDATA voltage. The varying current develops an AC voltage of 4V p-p across R85. This AC voltage is coupled onto the gate of Q15 through C53. Q15 provides the DC power for the loop (R85 is too high a resistance for this purpose). Q15 is a source follower, and its source follows the voltage on its gate. The circuit of R85, Q15 and associated components can be viewed as a circuit with about 2 - 4 volts DC drop (at 0 - 400mA load), but which has a high AC impedance determined by R85. (Somewhat like an inductor in that it has a low DC resistance but high

AC impedance.) This supplies power to the loop but at the same time allows the MXP transmitter (Q14) and the transmitters in the addressable devices to modulate the voltage for data transmission.

The data on the analog loop is filtered by L9, L10, C30, R32, R33 and C39. C37 provides

DC blocking. D2 and D3 with C40 clamp the incoming voltage to 1.2V p-p. The filtered, clamped voltage is amplified by Q3 and then sliced by U13A to form a 0 - 5V square wave from the incoming sinewave. The received data is decoded into 0s and 1s by timing and software within the CPU. Note that the slice level is about 0.6V from the peaks of the AC voltage on the loop and not at the mid point of the AC component.

7.2.5.4 Open Circuit Fault Handling

The loop is normally driven from the AL terminals, and not driven by the AR terminals.

Optocoupler OC7 checks that power is reaching the far end of the loop i.e. the AR terminals.

If this is not the case, the CPU will close relay RL2 so that the loop is driven (power and data) from both ends. Thus a single open circuit will result in all addressable devices still receiving power and still being able to communicate with the MXP. Two open circuits may result in loss of power and communications with some devices.

Periodically (every 30 seconds) when the loop is driven from both ends, the CPU will open the right end relay to check whether the open circuit fault has gone away.

7.2.5.5 Short Circuit Fault Handling

If the CPU finds that the over-current detector described in section 7.2.5.1 is unable to be

reset or is operating repeatedly in a short time, it will try to drive the loop from one end at a time in case the short is present only when driving from one end of the loop. In this case it will drive the loop from the other end only. However it will try the faulty end very briefly once every 30 seconds to see if the fault has gone away.

Note that if there are no isolator bases in the loop, the short will appear from both ends and all devices will be effectively disconnected.

If there are isolator bases, then after an initial overload which will be reset, the isolators will isolate the section of the loop with the short. The loop will then appear to have an open

circuit and will be driven by both ends simultaneously as described in section 7.2.5.4. Only

those devices connected to the shorted section will be disconnected.

Issue 1.5 24 March 2006 Page 7-9

MX4428 MXP Engineering /Technical Manual

MXP Technical Description

Document: LT0273

In the event that there are isolator bases installed, but there is a short on the section of loop between the MXP and the first (or last) isolator, the MXP will detect the short and drive the loop only from the opposite end. Every 30 seconds it will very briefly try reconnecting the faulty end to see if the fault has gone away. This reconnection must be very brief (if the short is still present), as it will cause the loop voltage to collapse, and the voltage must be restored quickly enough so that the addressable devices retain enough charge in their power supply filter capacitors and do not reset.

7.3

None of these adjustments should require changing in the field, unless PCB components have been changed.

Disconnect all circuits from the analog loop terminals. Connect 24V to the responder loop power terminals. Adjust VR1 so that the voltage measured between TP16 “40V ISO” and

TP15 “0V ISO” is 40.0V + / – 0.5V.

7.3.2 TX DATA VOLTAGE ADJUSTMENT

Disconnect all circuits from the analog loop terminals. Adjust VR2 so that the AC signal voltage measured with an oscilloscope between TP3 “LINE” and TP15 “0V ISO” is 4.0V -

4.8V p-p.

Refer to Figure 7.2 for an example waveform. Note that that waveform was captured with an

analog loop and some addressable devices connected and so the measured voltage is slightly less than that specified.

Note that the MXP will need to be connected to an MX4428 FIP, or standalone mode activated, for any data to be transmitted.

7.3.3 40V ISO SUPPLY CURRENT LIMIT ADJUSTMENT

Disconnect all circuits from the analog loop terminals. Connect 24V to the responder loop power terminals. Apply a slowly increasing load current to the loop terminals and check at what current the overload circuit operates (i.e. current and voltage drop to zero before being restored by the software - this may happen repeatedly). The overload should occur at a current of 415mA to 430mA. If it is over this range snip out one of the resistors R22 - R25. If it is under this range, re-insert one of these resistors (R22 and R23 are 22

Ω and R24 and

R25 are 47

Ω). Repeat the procedure as required.

Page 7-10 24 March 2006 Issue 1.5

Document: LT0273

7.4

MX4428 MXP Engineering / Technical Manual

MXP Technical Description

MXP LED INDICATIONS

The status LED (LD1) on the MXP board indicates the following conditions –

Indication Condition

2 quick flashes every 2 The MXP is normal and polled by the MX4428 panel. seconds

1 quick flash every 2 seconds

The MXP is normal apart from NOT being polled by the

MX4428 panel.

7 flashes then a pause, repeating.

Each of the 7 flashes indicates a particular fault is present when the flash is

long, or not present when the flash is short.

Continuous very rapid flashes

1st flash : Device polling is stopped due to a configuration download from the MX4428 panel.

2nd flash : One or more configured devices is not responding.

3rd flash : The MXP is not being polled by the MX4428 panel.

4th flash : The responder loop power relay has been opened due to a short on one side of the MXP.

5th flash : The detector loop is open circuit.

6th flash : The detector loop is shorted on "left" terminals.

7th flash : The detector loop is shorted on "right" terminals.

The MXP has just powered up. This phase should only last a couple of seconds.

Issue 1.5 24 March 2006 Page 7-11

MX4428 MXP Engineering /Technical Manual

MXP Technical Description

7.5

Document: LT0273

PART NUMBER. DESCRIPTION QTY/ASSY REF DESIG

PA0893 PCB ASSY,1901-213,F4000 MXP RESPONDER

CA0001 CAP,CERAMIC,10P,50V 1.0000 C45

CA0002 CAP,CERAMIC,15P,50V 2.0000 C1 C2

CA0004 CAP,CERAMIC,68P,50V 1.0000 C63

CA0005 CAP,CERAMIC,100P,50V 1.0000 C39

CA0009 CAP,CERAMIC,2N2,50V 1.0000 C37

CA0010 CAP,CERAMIC,4N7,50V 2.0000 C69 C70

CA0013 CAP,CERAMIC,22N,40V 2.0000 C41 C42

CA0016 CAP,CERAMIC,47P,50V 1.0000 C43

CA0021 CAP,CERAMIC,1N,100V,P2.54MM 6.0000 C30 C31 C32 C35 C36

C38

CA0022 CAP,CERAMIC,10N,63V,P2.54MM 2.0000 C47 C48

CA0023 CAP,CERAMIC,MONOLITHIC,100N,50V,P2.54MM 23.0000 C3 C5 C6 C7 C8 C9

C10 C11 C12 C13 C14

C15 C16 C17 C18 C19

C20 C21 C22 C23 C24

C25 C26

CA0201 CAP,ELECTRO,RADIAL,1U,50V,D5mm,H12mm,P2mm 1.0000 C40

CA0202 CAP,ELECTRO,RADIAL,2U2,50VMIN,DXL 6.5 X12MM MAX 1.0000 C53

CA0206 CAP,ELECTRO,RADIAL,10U,63V MIN,6.5 x 12 MAX 5.0000 C49 C50 C51 C52 C77

CA0211 CAP,ELECTRO,RADIAL,100U,16V 1.0000 C67

CA0218 CAP,ELECTRO,RADIAL,220U,63V,D10.5MM,H22M,P5MM 4.0000 C59 C60 C61 C62

CA0235 CAP,ELECTRO,RADIAL,470U,35V,D10.5mm,H20mm,P5mm 3.0000 C64 C65 C66

CA0327 CAP,POLYESTER,10%,P5mm,L7.5xT2.5xH6.5mm,10N,100V 3.0000 C44 C54 C57

CA0328 CAP,POLYESTER,10%,P5mm,L7.5xT2.5xH6.5mm,100N,63V 3.0000 C27 C28 C29

CA0330 CAP,POLYESTER,10%,P5mm,L7.5xT2.5xH6.5mm,47N,63V 1.0000 C46

CA0331 CAP,POLYESTER,10%,P5mm,L7.5xT2.5xH6.5mm,1N,100V 1.0000 C34

CA0630 CAP,SUPER CAP,0.22F,5.5V 1.0000 C68

CA0634 CAP,POLYESTER,10%,P5mm,L7.5xT3.5xH8.0mm,10N,400V 1.0000 C72

CA0635 CAP,ELECT,330U,35V,LOW ESR,D10mm,P5mm,H16mm 1.0000 C76

CL0453 COIL,L453,F4000 MXP,ISOLATED PSU,RM8 CORE 1.0000 L1

CN0063 CONNECTOR,IC SOCKET,20 PIN 1.0000 U5

CN0151 CONNECTOR,MOLEX,41761-4,MALE 1.0000 J5

CN0360 CONNECTOR,TERMI-BLOCK,VERT,4.0sqmm,5mm,4 WAY 3.0000 J1 J2 J3

CN0475 CONNECTOR,HEADER,0.1",SIL,6mm PIN,2 WAY 1.0000 LK1

CN0476 CONNECTOR,HEADER,0.1",SIL,6mm PIN,3 WAY 1.0000 LK3

CN0543 CONNECTOR,MINI JUMP WITH TAG,3 AMP 2.0000 LK1 LK3

CR0019 CRYSTAL,16.000MHz,30pF,HC49/4H 1.0000 XT1

DD0003 DIODE,1N4004 5.0000 D7 D8 D9 D35 D37

DD0004 DIODE,1N5404 2.0000 D34 D36

DD0005 DIODE,1N4148 8.0000 D2 D3 D4 D5 D6 D38

D41 D43

DD0027 DIODE,ZENER,0W5,D2.5mm,P10mm,5%,8V2 1.0000 D15

DD0030 DIODE,ZENER,0W5,D2.5mm,P10mm,5%,12V 1.0000 D42

DD0042 DIODE,ZENER,1W0,D3.0mm,P10mm,5%,6V2 1.0000 D33

DD0059 DIODE,SCHOTTKY,BYV10-40,1A,40V 2.0000 D31 D32

DD0060 DIODE,BAT85,SCHOTTKY,200MA,30V 4.0000 D27 D28 D29 D30

DD0061 DIODE,ZENER,HIGH SURGE,3W2,D3.8mm,P10mm,5%,33V 4.0000 D20 D21 D22 D23

DD0062 DIODE,ZENER,1W0,D3mm,P10mm,5%,24V 1.0000 D40

DD0065 DIODE,ZENER,HIGH SURGE,3W2,D3.8mm,P10mm,5%,36V 1.0000 D50

DD0073 DIODE,ZENER,HIGH SURGE,3W2,D3.8mm,P10mm,5%,7V5 1.0000 D19

DD0080 DIODE,BIDIRECTIONAL SUPPRESSOR,BZW04-28B (OR -31B) 3.0000 D16 D17 D18

DD0087 DIODE,MUR115 2.0000 D24 D25

DD0100 DIODE,ZENER,HIGH SURGE,3W2,D3.8mm,P10mm,5%,47V 6.0000 D10 D11 D12 D13 D14

D26

HW0237 HARDWARE,TRACK PIN,T1565-01 17.0000 TP1 TP2 TP3 TP4 TP5

TP6 TP7 TP8 TP9 TP10

TP11 TP12 TP13 TP14

TP15 TP16 TP17

IC0135 IC,7805CT,VOLTAGE REGULATOR,5V 4%,1.5A,TO220 1.0000 U11

IC0258 IC,LM393,OP AMP,DUAL,PRECIS VOLTAGE COMPAR,LOW PWR 1.0000 U13

IC0305 IC,LM385BZ 2.5,MICROPOWER VOLT REF DIODE,2.5V,TO92 1.0000 D39

IC0319 IC,LP339,QUAD COMPARATOR,ULTRA LOW POWER,DIL 2.0000 U7 U8

IC0413 IC,DS1232LP,LOW POWER MICROMONITOR 1.0000 U6

IC0447 IC,LM3578AN,750mA SWITCHING REGULATOR,DIL 1.0000 U10

IC0500 IC,OPTOCOUPLER,SFH608-4,CTR 160% @ 1mA,DIL 7.0000 OC1 OC2 OC3 OC4 OC5

OC6 OC7

LD0021 LED,3MM,RED,HIGH BRIGHT 1.0000 LD1

NT0007 NUT,HEX,M3,ZP 1.0000 Q17

PA0899 PCB ASSY,1901-213,F4000 MXP RESPONDER SMD CMP ONLY 1.0000

PT0020 POT,CERMET,100E,TOP ADJ,1 TURN,SPECTROL,63P 1.0000 VR2

PT0045 POT,CERMET,20K,TOP ADJ,1 TURN,SPECTROL,63P 1.0000 VR1

RL0051 RELAY,OMRON G6BU-1114C,12VDC,LATCHING 1.0000 RL3

Page 7-12 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

MXP Technical Description

RL0052 RELAY,OMRON G6A-274P-24VDC 2.0000 RL1 RL2

RR0001 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1E00 1.0000 R84

RR0013 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,22E0 2.0000 R22 R23

RR0016 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,39E0 1.0000 R92

RR0017 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,47E0 2.0000 R24 R25

RR0022 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,120E 2.0000 R66 R85

RR0023 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,150E 1.0000 R93

RR0027 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,330E 2.0000 R32 R33

RR0029 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,470E 1.0000 R64

RR0032 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,820E 1.0000 R119

RR0033 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1K00 4.0000 R16 R47 R63 R65

RR0034 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1K20 3.0000 R100 R102 R120

RR0037 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,2K20 3.0000 R88 R89 R90

RR0038 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,2K70 2.0000 R8 R10

RR0041 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,4K70 1.0000 R91

RR0043 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,6K8 2.0000 R99 R101

RR0044 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,8K20 3.0000 R7 R9 R98

RR0045 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,10K0 23.0000 R48 R49 R50 R51 R52

R53 R56 R57 R58 R59

R60 R61 R62 R70 R71

R79 R80 R81 R82 R87

R115 R116 R117

RR0047 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,15K0 1.0000 R43

RR0048 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,18K0 3.0000 R67 R78 R94

RR0049 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,22K0 2.0000 R95 R104

RR0051 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,33K0 5.0000 R17 R18 R19 R20 R118

RR0053 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,47K0 1.0000 R54

RR0054 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,56K0 2.0000 R31 R86

RR0056 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,82K0 1.0000 R103

RR0057 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,100K 10.0000 R3 R4 R5 R6 R12 R14

R15 R21 R34 R69

RR0058 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,120K 3.0000 R112 R121 R122

RR0059 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,150K 5.0000 R27 R28 R29 R30 R36

RR0060 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,180K 2.0000 R68 R83

RR0061 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,220K 3.0000 R11 R123 R124

RR0062 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,270K 1.0000 R111

RR0065 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,470K 3.0000 R40 R41 R42

RR0069 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1M00 4.0000 R45 R46 R125 R127

RR0071 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1M50 1.0000 R126

RR0072 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1M80 2.0000 R37 R38

RR0077 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,10M0 1.0000 R1

RR0085 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1E80 1.0000 R26

RR0740 RESISTOR,0.25W,1%,100PPM,D2.5mm,P10mm,20K 6.0000 R72 R73 R74 R75 R76

R77

RR0767 RESISTOR,0.25W,1%,100PPM,D2.5mm,P10mm,62K0 1.0000 R113

RR0775 RESISTOR,0.25W,1%,330K ***** USE RR0063 ***** 2.0000 R35 R110

RR0802 RESISTOR,NETWORK,0.125W,5%,0.1" SIP,9 PIN,8+C,10K 1.0000 RN1

RR0803 RESISTOR,NETWORK,0.125W,5%,0.1" SIP,9 PIN,8+C,100K 1.0000 RN2

RR0810 RESISTOR,2W,5%,D4mm,P15mm,PR02,330E 2.0000 R108 R109

RR0862 RESISTOR,0.6W,1%,50PPM,D2.5mm,P10mm,1M21 1.0000 R39

RR0865 RESISTOR,0.25W,1%,2M20 ***** USE RR0073 ***** 1.0000 R44

RR0887 RESISTOR,THERMISTOR,NTC,0.5W,4K7,-4.9%/K,10% 1.0000 RV3

RR0918 RESISTOR,VARISTOR,130VAC,0.25W 1.0000 RV2

RR0926 RESISTOR,2.5W,10%,200ppm,D6.0mm,P22.5mm,0E03 1.0000 R107

SC0041 SCREW,MACHINE,PH POZI,M3 X 6MM,ZP 1.0000 Q17

SF0243 SOFTWARE, F4000 MXP RESPONDER, V1.00 PAL 1.0000 U5

SU0198 SUNDRY,CHOKE,RF,10%,D4.0mm,P15mm,2U2H,1A 2.0000 L9 L10

SU0204 SUNDRY,CHOKE,RF,10%,D4.0mm,P15mm,4U7H,820mA 7.0000 L2 L3 L4 L5 L6 L7 L8

SW0005 SWITCH,DIL,8P1T 1.0000 SW1

SW0155 SWITCH,PUSHBUTTON,PCB MOUNT,NO,6mm x 6mm,L=5mm 1.0000 SW2

TR0029 TRANSISTOR,BC550 8.0000 Q3 Q4 Q5 Q6 Q7 Q9

Q10 Q11

TR0031 TRANSISTOR,BC557B,PNP,50V,100mA,TO92 5.0000 Q1 Q2 Q8 Q13 Q16

TR0049 TRANSISTOR,MPSA13/14,NPN DARL,30V,0.5A,0.5W,TO92 2.0000 Q18 Q19

TR0074 TRANSISTOR,MPSA63 2.0000 Q20 Q21

TR0075 TRANSISTOR,MTP2955E,MOSFET,P CH,60V,8A,40W,TO220 2.0000 Q12 Q22

TR0083 TRANSISTOR,BST72A,MOSFET,N CH,80V,300MA,.83W,TO92 1.0000 Q24

TR0084 TRANSISTOR,TIP110,NPN DARL,60V,2A,TO220 2.0000 Q14 Q23

TR0085 TRANSISTOR,HEATSINK,TO220,VERTICAL,17degC/W 1.0000 Q17

TR0094 TRANSISTOR,MTP12N10,MOSFET,N CH,100V,12A,79W,TO220 1.0000 Q17

TR0095 TRANSISTOR,RFP15N05L,MOSFET,N CH,15A,50V,60W,TO220 1.0000 Q15

WA0026 WASHER,CRINKLE,STAINLESS STEEL,M3 1.0000 Q17

IC0392 IC,MC68302FC16,uP,132 P PQFP,16MHz,68000+SERIAL PR 1.0000 U1

IC0429 IC,62256,32K X 8 SRAM,70ns,SMT 28PIN SOP,LOW POWER 2.0000 U3 U4

PB0893 PCB BARE,1901-213,F4000 MXP RESPONDER 1.0000

SF0242 SOFTWARE, F4000 MXP RESPONDER, V1.00 FLASH BOOT 1.0000 U2

Issue 1.5 24 March 2006 Page 7-13

MX4428 MXP Engineering /Technical Manual

MXP Technical Description

THIS PAGE INTENTIONALLY LEFT BLANK

Document: LT0273

Page 7-14 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

CHAPTER 8

MXP DIAGNOSTIC TERMINAL

Issue 1.5 24 March 2006 Page 8-1

MX4428 MXP Engineering /Technical Manual

MXP Diagnostic Terminal

Document: LT0273

8.1 MXP DIAGNOSTIC TERMINAL OPERATION

8.1.1 INTRODUCTION

The MXP provides diagnostic functions via its serial port (J5) with a terminal or PC connected. Commands may be entered which :

• Display the analogue values (Raw values, Filtered values, etc) of selected devices.

• Select devices for such display.

• Display and reset error counters.

• Determine all the devices and their types, as seen from each end of the loop.

• Change an addressable device’s address.

• Perform advanced diagnostics.

The MXP diagnostic serial port operates at 19200 baud, 8 data bits, no parity, 1 stop bit. A

3-wire cable is needed and it is wired the same as the MX4428 FIP programming terminal cable. This needs either a DB9 or DB25 connector and can be ordered as fully assembled cables using part numbers LM0042 (DB25) and LM0041 (DB9).

To utilise the colour logging facility an ANSI terminal emulator mode is required. Hyperterm and Accuterm are suitable for Windows and Procomm is suitable for DOS. For simple applications where logging to disk and scroll-back are not required mxpprog32 can be used with Windows and mxpprog can be used with DOS – these are included in SF0250.

8.1.2 MENU OF COMMANDS

To see the menu of commands available, type H <Enter> HE <Enter>or HELP <Enter>.

Currently, this will produce the following-

*** MXP monitor version 1.02 (c)2000 ***

H : this help

AH : advanced help

-------- Point Logging Commands -------------

CO : Colour toggle (requires ANSI terminal emulation)

SP n m : select points n to m, n&m optional

SP : show selected points

SPA : select all points

CP n m : clear points n to m, n&m optional

CPA : clear all points

P : alternate for SP

-------- General Diagnostic Commands --------

ST : Display General Status

STANDALONE n : standalone operation, heat threshold=n

-------- NOSEx loop diagnostics -------------

TC : NOSEx comms error count display

EC n m : NOSEx comms detailed error count display

RS : NOSEx comms error count reset

DP : Do diagnostics poll

CA x y : Change address of device old address x to new address y

8.1.3 SELECTING POINTS FOR MONITORING

Before the MXP can display analog values received from points, the user must select the points to be monitored (i.e. include in the monitoring list). This is done using the following commands –

Page 8-2 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

SPA

SP nnn

Adds all points to the list of points to be monitored.

Adds point nnn to list.

P nnn Adds point nnn to list

SP nnn mmm Adds points nnn to mmm.

P nnn mmm Adds points nnn to mmm.

CPA Clears all points from monitoring list.

CP nnn Clears point nnn from list.

CP nnn mmm Clears points nnn to mmm from list.

SP Displays all points selected to be monitored (i.e. in monitoring list)

The values nnn and mmm must be in the range of 1-200.

Note that if more than about 50 points are monitored at once, the serial output may not be fast enough and some data may be discarded.

If it is not required to monitor any points be sure to deselect all points (CPA).

Monitoring a large number of points may have a detrimental effect on processing time. Therefore enter the CPA command before disconnecting the laptop after monitoring points.

8.1.4 DISPLAYING DEVICE ANALOGUE VALUES - CV, TV, ETC

Once points have been selected for display, the MXP will display at least one line for each selected point, each time the point replies to a poll (or sends an interrupt message).

For those devices with two sensors (814PH, 814CH) with both sensors configured, two lines will be displayed – one line for temperature and another line for smoke or CO.

Colour logging may be selected with the “CO” command to make the displayed log clearer.

Green is used for heat sensors, yellow for photo sensors, magenta for CO sensors, cyan for ionisation sensors, and white for ancillaries. A brown/yellow background is used for values in fault, green background for values in pre-alarm, red background for values in alarm.

An example line of the displayed values is

T=165; P= 2; HEAT= 20; Fl= 20; SL= 20; RoR= 0; SLRoR= 0

T=xxxx refers to the time in seconds. It recycles back to 0 after 4290 seconds.

P=xxx refers to the point number (1 .. 200).

The format is designed to be both human readable and suitable for capturing and importing into a spreadsheet. In the latter case, it is suggested that “delimited” text import is used, with

“=” and “;” being used as delimiters.

The following paragraphs describe the parts of the log specific to each device type.

8.1.4.1 Heat Sensor of 814H, 814PH, and 814CH

T=165; P= 2; HEAT= 20; Fl= 20; SL= 20; RoR= 0; SLRoR= 0

HEAT=xxx gives the raw value received from the detector converted to

°C.

Fl=xxx gives the filtered temperature (CV) in

°C. This is the value which is compared with the threshold to decide if a pre-alarm exists.

SL=xxx gives the filtered and slope limited temperature (SLV) in

°C. This is the value which is compared with the threshold to decide if an alarm exists. This item will not be displayed if there is no fixed temperature alarm configured, e.g. if the heat sensor is used only to enhance the smoke or CO.

Issue 1.5 24 March 2006 Page 8-3

MX4428 MXP Engineering /Technical Manual

MXP Diagnostic Terminal

Document: LT0273

RoR=xx gives the rate of rise in

°C/minute. This is the value which is compared with the threshold to decide if a rate of rise pre-alarm exists, and the value which is used to

“enhance” smoke or CO processing. This item will not be displayed if there is no rate of rise alarm configured and there is no enhancement of smoke or CO.

SLRoR=xx gives the slope limited rate of rise in

°C/minute. This is the value which is compared with the threshold to decide if a rate of rise alarm exists. This item will not be displayed if there is no rate of rise alarm configured.

8.1.4.2 Photo Sensor of 814PH

T=165; P= 1; OPT= 26; Cal= 32; TV= 23; CV-TV= 3; SL-TV= 3

OPT=xxx gives the raw value received from the detector (0 .. 255).

Cal=xxx gives the “calibrated” value (i.e. the raw value adjusted to compensate for the varying outputs of different detectors with the same smoke level).

TV=xxx gives the tracked value (or long term average pedestal), i.e. the value which is assumed to be the output of the detector in clean air.

CV-TV=xxx gives the filtered calibrated value less the clean air value (TV). CV-TV is the value which is compared with the threshold to decide if a pre-alarm exists.

SL-TV=xxx gives the filtered and slope limited value less the clean air value (TV). SL-TV is the value which is compared with the threshold to decide if an alarm exists.

8.1.4.3 Carbon Monoxide Sensor of 814CH

T=165; P= 2; CO= 25; Cal= 25; TV= 30; CV-TV= -4; SL-TV= -4

CO=xxx gives the raw value received from the detector (0 .. 255).

Cal=xxx gives the “calibrated” value (i.e. the raw value adjusted to compensate for the varying outputs of different detectors with the same CO level).

TV=xxx gives the tracked value (or long term average pedestal), i.e. the value which is assumed to be the output of the detector with no CO present. (Note that as this value is measured in the factory and stored in the detector then not subsequently adjusted, it is a constant for each detector.)

CV-TV=xxx gives the filtered calibrated value less the zero CO value(TV). CV-TV is the value which is compared with the threshold to decide if a pre-alarm exists.

SL-TV=xxx gives the filtered and slope limited value less the zero CO value (TV). SL-TV is the value which is compared with the threshold to decide if an alarm exists.

8.1.4.4 814I Ionisation Detector

T=165; P= 20; ION= 74; TV= 74; CV-TV= 0; SL-TV= 0

ION=xxx gives the average of the two raw values received from the detector (0 .. 255).

TV=xxx gives the tracked value (or long term average pedestal), i.e. the value which is assumed to be the average of the two detector sensors in clean air.

CV-TV=xxx gives the filtered calibrated value less the clean air value(TV). CV-TV is the value which is compared with the threshold to decide if a pre-alarm exists.

SL-TV=xxx gives the filtered and slope limited value less the clean air value (TV). SL-TV is the value which is compared with the threshold to decide if an alarm exists.

8.1.4.5 MIM800 Mini Input Module

T=165; P= 21; MIM=100

MIM=xxx gives the raw value received from the module.

8.1.4.6 MIM801 Mini Input Module

T=165; P= 30; MIM801=131

MIM801=xxx gives the raw value received from the module.

Page 8-4 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

8.1.4.7 CP820 Manual Callpoint

T=165; P= 22; CP=0

CP=xxx gives the raw value received from the callpoint.

8.1.4.8 CIM800 Contact Input Module

T=165; P= 23; CIM A= 90, B= 91

CIM A=xxx; B=yyy. xxx gives the raw value relating to the module input A and yyy gives the raw value relating to the module input B.

8.1.4.9 DIM800 Detector Input Module

T=1334; P= 25; DIM A= 26;B= 26; Supply=198

DIM A=xxx;B=yyy; Supply=zzz. xxx gives the raw value relating to the module input A, yyy gives the raw value relating to the module input B, and zzz gives that raw value from supply monitoring.

8.1.4.10 RIM800 Relay Interface Module

T=1334; P= 24; RIM=224

RIM=xxx gives the digital inputs to the module ASIC, converted to a integer. The only bit of use is the least significant bit - the number should be odd if the relay is activated, even otherwise.

8.1.4.11 SNM800 Sounder Notification Module

T=1334; P= 26; SNM=255, 3

SNM=xxx, yyy. xxx gives the raw value relating to the EOL monitoring (when the relay is deactivated), and yyy gives the raw value relating to the power supply monitoring.

8.1.4.12 LPS800 Sounder Notification Module

T=1334; P= 27; LPS=151, 78

LPS=xxx, yyy. xxx relates to the voltage at the + terminal. yyy relates to the voltage at the – terminal.

8.1.4.13 VLC800 Vesda Laser Compact

T=1334; P= 28; VLC= 17; DI=0xe0; Cal= 17; TV= 12; CV-TV= 5; SL-TV=5

VLC=xx gives the analog value received from the VLC800. DI=0xaa : aa gives the digital inputs coded in hexadecimal, where bit 0 = "urgent fault", bit 1 = "any fault", bit 2 = "all faults serviceable", bit 3 = "filter fault", bit 4 = "walk test". Bits 6 and 7 appear to be always 1s.

8.1.5 ST (STATUS COMMAND)

The ST command gives a self explanatory synopsis of the status of the MXP, including the version number and details of the software programmed into the Flash IC.

>>ST

MXP Version 1.02, compiled 15:31:03 May 07 2001

Polling Running

All NOSEx devices responding

Being polled by F4000

Responder Loop Disconnect Relay : Connected (Normal)

NOSEx loop OK

1309 polling cycles since power-up / database load

0 detector/ device leds on

Issue 1.5 24 March 2006 Page 8-5

MX4428 MXP Engineering /Technical Manual

MXP Diagnostic Terminal

Document: LT0273

8.1.6.1 TC Command (Total Counts)

This command gives totals of node failures and powerups on the analog loop. See the EC command to get values broken down to individual devices.

>>tc

Transmit echo reception fail count 5

Total reply fail count 191

Total device powerups 0

“Transmit echo reception fail count” indicates the number of times the MXP has been unable to receive its own transmission on the analog loop. This should normally increment only when the loop is subjected to abnormal events, e.g. shorts. This value is not cleared when the MXP powers up, it is only cleared by the RS command.

“Total reply fail count” increments when a device does not reply to a poll, but has not already been deemed to have failed. When a device is removed this value will increment by 12. This value is not cleared when the MXP powers up, it is only cleared by the RS command.

“Total device powerups” increments when a device powers up. This should normally increment by one for each device when the loop first powers up, and by one each time a detector is plugged into a base with the loop powered up. If it increments at other times it is indicative of a problem which requires investigation. This value is set to zero when the MXP powers up.

8.1.6.2 EC Command (Error Counts)

This command gives total error counts as per the TC command, and then also gives the reply fail counts for individual devices, and an indication of whether each device is deemed to be in “scan fail”. These individual counts are not cleared when the MXP powers up, but are reset by the RS command.

This command is also useful to determine which points are configured and what their type is.

>>ec

Transmit echo reception fail count 5

Total reply fail count 191

Total device powerups 0

Individual reply fail counts...

Point 1 Photo/Heat, 17 Scan Fail

Point 2 CO/Heat, 0

Point 3 Heat Only, 0

Point 20 Ionisation, 0

Point 21 MIM, 0

Point 22 CP, 0

Point 23 CIM, 54

Point 24 RIM, 54

Point 25 DIM, 24

Point 26 SNM, 54

8.1.6.3 RS Command (Reset)

This command resets (sets to zero) all the counters displayed by the TC and EC commands.

Page 8-6 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

8.1.6.4 DP Command (Diagnostic Poll)

This command lists all the devices found (irrespective of the MX4428 programming) by issuing a command to each side of the loop (left and right) which requests all devices to identify themselves. Thus it can be used to find what devices are present on the loop and which devices are found from each end, if the loop is broken or isolator bases have opened.

This can help identify which section of the loop cable is broken or shorted.

It will list devices found with any address including addresses above 200. If two or more devices are present with the same address they will usually be detected, however their replies may collide resulting in neither being detected. Therefore a second attempt is made on each line in order to maximise the chance of locating multiple devices with the same address. On the second attempt, only devices not found on the first attempt are displayed.

This command is a local version of the MX4428 DP command.

>>dp

>>Diagnostic Pollscan line 1

Scan attempt 1

Adr 2 : CO/Heat

Adr 3 : Heat Only

Adr 20 : Ionisation Foreign (not programmed)

Adr 21 : MIM

Adr 22 : CP

Adr 23 : CIM

Adr 24 : RIM

Adr 25 : DIM

Adr 26 : SNM

Scan attempt 2

Diagnostic Pollscan line 2

Scan attempt 1

Adr 2 : CO/Heat

Adr 3 : Heat Only

Adr 20 : Ionisation

Adr 21 : MIM

Adr 22 : CP

Adr 23 : CIM

Adr 24 : RIM

Adr 25 : DIM

Adr 26 : SNM

Scan attempt 2

Diagnostic pollscan complete

The DP command will note as “foreign” any devices which are found but not currently programmed. However it will not display devices which are programmed but not found.

Other messages may be given, e.g. “Duplicate Device”, “Unknown Type”, “Used as Heat only”, “Used as MIM”, “Type Mismatch”.

8.1.6.5 CA Command (Change address)

The change address command may be used to change the address of a single device (the first number) on the analog loop to a new address (the second number). If devices are added one at a time, this command may be used to assign their addresses instead of using the programming tool. New devices from the factory normally have an address of 255.

Both new and old addresses may be any number greater than 0 and up to 255. Addresses between 201 and 255 will be inaccessible to the MX4428.

Issue 1.5 24 March 2006 Page 8-7

MX4428 MXP Engineering /Technical Manual

MXP Diagnostic Terminal

Document: LT0273

>>ca 20 100

Re-address device 20 to 100 ?y

Verify OK

The MX4428 configuration is not altered by this command.

If there is no device with the old address, or if there is already a device with the new address, an error message will be displayed and the change will not be made.

Normal polling resumes when the command is completed.

The following commands are available for specialised purposes. Use these commands only as instructed by Tyco Safety Products Christchurch.

>>ah

Advanced diagnostic commands.

Use these commands only as instructed by Tyco Safety Products

Chrsitchurch

------- General -----------------------------------

RD : relay diagnostics toggle

MEM : memory diagnostics menu

TASK : display task times

STACK : display stack free space

STANDALONE a b : standalone operation, heat threshold=a, step limit=b

------- Point Record diagnostics ------------------

PR n : show point n record

NR : show next record

LR : show last record

AR : show next assigned record

SR : show selected point records

DD : point record description

-------- NOSEx loop/device diagnostics -------------

NC : NOSEx comms log toggle

DR d e : Read eeprom address e from device address d

DW d e x: Write x to eeprom address e of device address d

: d is in decimal, e and x in hexadecimal

FP a b x y: force points a to b analog values x,y

Several commands are available on the MX4428 “Analog Diagnostics” (DG then DA) menu which affect the MXP.

These commands are as follows

FP r p

LN r p

L1 r

Set the LED of point p on responder r to flash when polled.

Turn on steady the LED of point p of responder r.

Poll all points of responder r using line 1 (“left”) only. Any failures to respond will be treated as usual i.e. will generate “node fail” events.

L2 r Poll all points of responder r using line 2 (“right”) only. Any failures to respond will be treated as usual i.e. will generate “node fail” events.

FO, LO, or PO Any of these commands cancels all the above special functions.

Page 8-8 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

DP r

Perform a “diagnostic poll” on responder r. This command initiates a

diagnostic poll, similar to that described in section 8.1.6.4. The results are

displayed automatically on the MXP but not the MX4428. To see the results on the MX4428 use the DR command.

DR r

GH r

GT r

RH r p

RT r p

Display the results from the last DP command on responder r. (Use this command at least 30 seconds after a DP command.)

Reset history of all points on responder r.

Reset tracked values (clean air values) of all points on responder r.

Reset history of point p on responder r.

Reset tracked value (clean air value) of point p on responder r.

The above commands are described in more detail in the F4000 Programming manual.

The remaining commands on the DA menu may display returned values from the MXP, but have no direct affect on the MXP.

Some events at the MXP are logged to the diagnostic terminal regardless of whether any points are selected for display or commands entered at the MXP. These events are generally self explanatory, and include –

• MXP Powering up (logs message and displays diagnostic help menu.)

• MXP Major state change including Initial Powerup state, Sending Learn Information,

Acquiring Database, Normal Running.

• System test and Autotest initiated from MX4428, and result thereof.

• Diagnostic Pollscan initiated from MX4428.

• Pollscan to “Learn” system configuration initiated from MX4428.

Issue 1.5 24 March 2006 Page 8-9

MX4428 MXP Engineering /Technical Manual

MXP Diagnostic Terminal

8.2

Document: LT0273

On occasion, Tyco Safety Products Christchurch may provide a new version of the MXP software. This software is stored in the Flash IC, U2. It can be updated in the field as described below.

The following files will be supplied for a Flash software version update –

MXP.MXP Flash contents in special format

FLASHPGM.S19

MXPPROG.EXE

Flash programming program to run in MXP

Flash programming program to run in PC (for DOS)

MXPPROG32.EXE Flash programming program to run in PC (for WIN32)

All of these files should be in the same drive / directory, on a floppy disk or the hard disk.

8.2.2 PROCEDURE

1. The MXP must be powered up either from the responder loop or an external 24V power supply.

2. Make a note of the current DIP switch settings on the MXP, then set all DIP switches

OFF.

3. Connect the PC to the MXP programming port with an F4000 programming lead.

4. If the PC is running DOS or Windows 3.x run the program MXPPROG from a DOS prompt in the directory with the files. If you are using a COM port other than COM1 include the name of the port on the command line e.g. “MXPPROG COM2”.

5. If the PC is running any 32 bit Windows variant (95, 98, NT, ME, 2000, XP etc) run the program MXPPROG32. (You can do this by typing MXPPROG32 from a command prompt in the directory with the files, or by double clicking MXPPROG32.EXE in

Windows Explorer or My Computer. If you are using a COM port other than COM1 you will need to include the port name on the command line, the easiest way to do this is from a command prompt.)

6. Insert the WRITE ENABLE link (LK1) on the MXP.

7. Press the RESET button on the MXP.

8. The programming procedure is now automatic. A typical screen log of this automatic procedure is shown below –

MXP Terminal / Flash Programmer. Type ESC at any time to exit

To program flash with new version ...

Switch all MXP DIP switches OFF, insert FLASH WRITE ENABLE LINK and press reset

Don't type keys while program is running (except ESC to exit if needed)

To use as a terminal ...

Just type your commands, HE<Enter> for help

=====================================================

MXR Boot ROM V1.01. Address = 127, Switch 8 = 0

Valid application program in flash

BOOT : Waiting for load

********************************************************************************

********************************************************************************

********************************************************************************

***************************************************************

Loaded OK

Running from Start address (8000)

=====================================================

MXR Flash Programmer V1.11.

1 : Erase Entire Flash (all unprotected blocks)

3 : Load MXR Binary File and Program into Flash

Page 8-10 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

005000

006000

007000

008000

009000

00a000

00b000

00c000

00d000

00e000

00f000

010000

011000

012000

013000

4 : Flash Information

1

Erasing, wait

Erase OK

1 : Erase Entire Flash (all unprotected blocks)

3 : Load MXR Binary File and Program into Flash

4 : Flash Information

3

FlashPgm : Waiting for load

0134d0 bytes

000000

001000

002000

003000

004000

Loaded

Checksum is correct

Done, Switch MXP DIP switches normal, remove FLASH WRITE ENABLE LINK and press reset

MXR Flash Programmer V1.11.

1 : Erase Entire Flash (all unprotected blocks)

3 : Load MXR Binary File and Program into Flash

4 : Flash Information

9. If the above does not happen, check that all the required files are present, check the DIP switch settings and WRITE ENABLE link and try starting again from the beginning - exit from the program MXPPROG.EXE or MXPPROG32.exe by typing <ESC> and restart it, the press the MXP RESET button again. If there is still a problem obtain a fresh copy of the files and try again. If the problem persists, note carefully exactly what is displayed on the screen and contact Tyco Safety Products Christchurch.

10. Remove the WRITE ENABLE link, or insert it onto one pin only.

11. Reset the DIP switches to the original settings noted in step 2.

12. Press the reset button.

Issue 1.5 24 March 2006 Page 8-11

MX4428 MXP Engineering /Technical Manual

MXP Diagnostic Terminal

Document: LT0273

13. Check the display on the terminal emulator to ensure the program runs and the new version is installed. An example of the output on power up is shown below. Note that some of this may scroll off the screen, however the “MXP Monitor version x.xx ...” line should be visible and will enable you to verify the new version. If necessary type ST

<Enter> to see the version.

=====================================================

MXR Boot ROM V1.01. Address = 99, Switch 8 = 1

Valid application program in flash

Jumping to application program

**************************************************************

MXP Version 1.02 Powered Up

Address 99

Initial Power Up State

*** MXP monitor version 1.02 (c)2000 ***

(menu follows)

14. Write the new software version (1.02 in this example) on the label of the Flash IC, U2.

Page 8-12 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

CHAPTER 9

DEVICE PROCESSING

Issue 1.5 24 March 2006 Page 9-1

MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

9.1

Document: LT0273

An “exponential filter” is used to smooth values received from all detector types and remove

“noise”.

Value

IN

OUT

Time

This is a kind of moving average of recent samples, with the most recent samples given the most weighting. The output of the filter will exponentially approach the input (like an electronic RC filter).

OUT n

= OUT n-1

+ (IN - OUT n-1

) / FD.

FD is the filter divisor. The bigger FD, the slower the filter.

This filter usually requires calculation using units much smaller than the units being filtered.

For instance it could use floating point arithmetic or integer arithmetic using units of 1/256 of the “detector units”. Conversion from the calculation units back to detector units should use rounding rather than truncation.

9.2

“Step Limiting” is used after the exponential filter on all detector types, to reduce sensitivity to large short term changes in input values which may represent false alarms.

Value

IN

OUT

Page 9-2 24 March 2006

Time

Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

The output of the filter approaches the input with a maximum slope, or maximum step on each sample.

ADJ = IN - OUT n-1

IF ADJ > SL THEN ADJ = SL

IF ADJ < -SL THEN ADJ = -SL

OUT n

= OUT n-1

+ ADJ

SL is the step limit for each sample period. The smaller SL the slower the filter.

Issue 1.5 24 March 2006 Page 9-3

MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

9.3

Document: LT0273

9.3.1 CONVERSION

°C

The temperature readings from the detector (814H or the temperature element of an 814PH or 814CH) are returned from input AI1 of the MX ASIC. These are converted to

°C according to the following table. This gives the closest temperature for each reading.

Rdg

°C

0 Fault

1 Fault

2 Fault

3 Fault

4 Fault

5 0

6 0

7 0

8 0

9 0

10 0

11 0

12 0

13 0

14 0

15 0

16 0

17 0

18 0

19 0

20 0

21 0

22 0

23 0

24 0

25 0

26 0

27 0

28 0

29 0

30 0

31 0

32 1

33 2

34 3

35 3

36 4

37 5

38 5

39 6

Rdg

°C

40 7

41 7

42 8

43 8

44 9

45 9

46 10

47 10

48 11

49 12

50 12

51 13

52 13

53 14

54 14

55 15

56 15

57 16

58 16

59 17

60 17

61 18

62 18

63 19

64 19

65 20

66 20

67 20

68 21

69 21

70 22

71 22

72 23

73 23

74 24

75 24

76 25

77 25

78 25

79 26

133

134

135

136

137

138

139

140

141

142

143

144

145

120

121

122

123

124

125

126

127

128

129

130

131

132

154

155

156

157

158

159

146

147

148

149

150

151

152

153

Rdg

°C

80 26

81 27

82 27

83 28

84 28

85 28

86 29

87 29

88 30

89 30

90 30

91 31

92 31

93 32

94 32

95 32

96 33

97 33

98 34

99 34

100 34

101 35

102 35

103 35

104 36

105 36

106 37

107 37

108 37

109 38

110 38

111 39

112 39

113 39

114 40

115 40

116 40

117 41

118 41

119 42

Rdg

45

45

45

46

46

47

47

48

48

48

°C

42

42

43

43

44

44

44

49

49

50

50

50

51

51

52

52

56

56

57

57

58

58

53

53

53

54

54

55

55

55

Rdg

°C

160 59

161 59

162 60

163 60

164 60

165 61

166 61

167 62

168 62

169 63

170 63

171 64

172 64

173 65

174 65

175 66

176 67

177 67

178 68

179 68

180 69

181 69

182 70

183 70

184 71

185 72

186 72

187 73

188 73

189 74

190 74

191 75

192 75

193 76

194 77

195 77

196 78

197 79

198 79

199 80

Rdg

°C

200 80

201 81

202 82

203 83

204 84

205 85

206 85

207 86

208 87

209 88

210 89

211 90

212 90

213 91

214 92

215 93

216 94

217 95

218 95

219 97

220 98

221 99

222 100

223 102

224 103

225 104

226 105

227 107

228 108

229 109

230 110

231 112

232 114

233 115

234 117

235 119

236 120

237 120

238 120

239 120

Rdg

120

120

120

120

Fault

Fault

Fault

Fault

Fault

°C

120

120

120

120

120

120

120

253

254

255

240

241

242

243

244

245

246

247

248

249

250

251

252

The temperature is then processed according to Figure 9.1 to generate the various alarm

and pre-alarm conditions. The RORCV value is also used for enhancement of the smoke or

CO values when this is enabled.

Page 9-4 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Raw

°C

Raw

Reading Table

Lookup

Exponential

Filter

FD1

Slower

Exponential

Filter

FD2

PreAlarm

Threshold

-

+

Comparator

Fixed Temp PreAlarm

Slope

Limiter

CV

Alarm

Threshold

-

+

SLV

Comparator

Subtractor

+

-

SL1

Multiplier

Fixed Temp Alarm

ROR

PreAlarm

Threshold

-

+

Comparator

Slope

Limiter

RORCV

(°C/min)

ROR PreAlarm

ROR

Alarm

Threshold

-

+

RORSLV

Comparator

ROR

Alarm

SL2

PollsPerMinute

FD2-FD1

Figure 9.1 Heat Processing Diagram

Issue 1.5 24 March 2006 Page 9-5

MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

9.4

Document: LT0273

The smoke reading of the detector is returned as input AI0 from the device ASIC. Figure 9.2

shows a general view of the processing of the values received from the photoelectric sensor.

It is of interest that the value is multiplied by a factor (between 1 and 4) depending on the factory calibration of the sensor, and again multiplied by a factor depending on the temperature rate of rise (when “enhanced” operation is selected). In both cases the “tracked value” is subtracted, the multiplication applied, and the “tracked value” added back in. This is so that all scaling occurs relative to the clean air value.

When the MXP or detector powers up the clean air value or “tracked value” is initially set to the average of the reading from the detector after about 30 seconds and the value stored in the detector EEPROM, and then may continue to track up or down by 1 each poll for the next 3 minutes.

When the “tracked value” is reset manually by command from the MX4428, it is set to a value which will make CV equal to TV. Unless the calibration factor is exactly 1.0, the new

TV is not simply the same as the previous CV.

Subtractor Comparator

Enhancement Factor derived from Heat RORCV

(1 if no enhancement)

+

-

+

-

PreAlarm

Calibration

Adder

Exponential

Filter

Subtractor Adder

PreAlarm Threshold

CVEnh

(CV to FIP)

Slope

Limiter

Raw

Value

Subtractor

+

-

+

-

Smoke Filter

Divisor

Multiplier

Smoke Step

Limit

SLV

TV = Tracked Value = Assumed Clean Air Value

CV

+

-

Subtractor Comparator

+

-

Alarm

Very Slow Slope

Limiter

(1 step per Photo Tracking Interval)

Alarm Threshold

Figure 9.2 Photo Processing Diagram - SmartSense

9.4.2 SMARTSENSE ENHANCEMENT

Figure 9.3 shows the amount by which smoke readings are increased depending on the

temperature rate of rise.

The default enhancement multiplier parameter is 12. The graph (Figure 9.3) shows the effect

of this factor and also the effect of an alternative parameter of 6.

If enhancement is disabled, (or less efficiently if the enhancement multiplier parameter is set to 0) the multiplier is exactly 1.

Page 9-6 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Enhancement Multiplier

3

2.5

2

1.5

1

Param=12

Param=6

0.5

0

0 5 10 15

Temperature Rate of Rise (°C/min)

Figure 9.3 Enhancement of smoke reading for temperature rate of rise

When “FastLogic” is selected, most processing is done within the proprietary “FastLogic” module. The internals of that module are beyond the scope of this manual.

Raw heat value

(direct from detector)

Calibration

PreAlarm

Adder Fuzzy Logic Module

Raw Smoke

Value

Subtractor

+

-

Calibrated

Value

Alarm

TV = Tracked Value = Assumed Clean Air Value

(Average of 1st reading and factory stored pedestal)

Mode

Figure 9.4 Photo Processing Diagram - FastLogic

Issue 1.5 24 March 2006 Page 9-7

MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

9.5

Document: LT0273

The CO reading of the detector is returned as input AI0 of the device ASIC. The CO readings are adjusted depending on a calibration factor set at the factory and stored in

EEPROM.

Figure 9.3 shows the amount by which CO readings are increased depending on the

temperature rate of rise. (This is the same for the CO detector as the Photo detector.)

The default enhancement multiplier parameter is 12. The graph (Figure 9.3) shows the effect

of this factor and also the effect of an alternative parameter of 6.

If enhancement is disabled, (or less efficiently if the enhancement multiplier parameter is set to 0) the multiplier is exactly 1.

Raw

Value

Subtractor

+

-

Calibration

Constant stored in detector eeprom

Adder

Exponential

Filter

CO Filter

Divisor

Enhancement Factor derived from Heat RORCV

(1 if no enhancement)

+

-

Subtractor Comparator

+

-

PreAlarm

Adder

PreAlarm Threshold

CVEnh

(CV to FIP)

Slope

Limiter

Subtractor

+

-

Multiplier

CO Step Limit

SLV

TV = Tracked Value = Zero CO Value

+

-

Subtractor Comparator

+

-

Alarm

Alarm Threshold

Figure 9.5 CO Processing Diagram

Page 9-8 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

9.6

The smoke reading of the detector is returned in two parts as inputs AI0 and AI1 of the device ASIC. In the MXP the average value of AI0 and AI1 is used for all calculations, so that all returned values to the MX4428 lie within the range of 0 – 255. (Note that TEPG literature refers to the sum of the two inputs.)

The processing is shown in Figure 9.6. The tracked value is initialised by setting it to a high

value (100) when the MXP or detector powers up, and allowing the tracked value to increment / decrement by 1 for each of the first 4 minutes.

Subtractor Comparator

+

-

+

-

PreAlarm

PreAlarm Threshold

Raw

Value

Exponential

Filter

Filter Divisor

CV

Slope

Limiter

SLV

+

-

Subtractor

Step Limit

Comparator

+

-

Alarm Threshold

Alarm

TV = Tracked Value

= Assumed Clean Air Value

Very Slow Slope

Limiter

(1 step per Tracking Interval)

Figure 9.6 Ionisation Detector Processing

Issue 1.5 24 March 2006 Page 9-9

MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

Document: LT0273

9.7 MIM800 / CIM800 / MIM801 PROCESSING

The MIM800 and CIM800 return a value which depends on the external resistance across the contact terminals and which can be modelled by the equation –

VALUE = 226 * (150 + 3) / (150 + Rext + 3)

The MIM801 returns a value which depends on the external resistance across the contact terminals and which can be modelled by the equation –

VALUE = 226 * (Rext + 3) / (150 + Rext + 3)

(unless Rext is open circuit, then value = 255)

(Note 150 represents an internal 150

Ω resistor, 3 represents a 3Ω FET on resistance, and

226 represents (3.3V - DIODEV) / 3.3V * 255

Graphs of these values are show in Figure 9.7. Also shown are the default thresholds, and

the interpretations of the input ranges between the thresholds.

160

140

120

100

240

220

200

180

80

60

40

20

N/C:

O/C Fault

40

N/O : Optional S/C Fault

176

N/O : Alarm

122

N/O :

Alarm

110

N/C : S/C Fault

N/O :

Optional S/C Fault

MIM801

Normal

Normal

MIM800

170

N/O :

O/C Fault

N/C :

Alarm

50

N/O :

O/C

Fault

N/C :

Alarm

0

0 50 100 150 200 250 300 350 400 450 500 550 600

R

No alarm resistor

(Default)

Figure 9.7 MIM800 / MIM801 Reading versus resistance

The usual parameters are as follows –

MIM800 / CIM800 MIM801

P0 P1 P2 P3 P4 P5

122 50 0 110 170 0

With alarm resistor

176 40

Page 9-10 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

These are designed for the following configurations–

Device Mode Contact R

MIM800

CIM800

N/O

EOL R Max Wiring R

N/O Not

Ω 50Ω

100

Ω 200Ω 10Ω

MIM801

N/C 200

Ω 50Ω

N/O Not

Ω 50Ω

N/O

100

Ω 200Ω 10Ω

N/C 200

Ω 50Ω

Parameters for alternative contact and EOL resistors could be derived from the graphs in

Figure 9.7.

9.7.1 ALGORITHM - MIM800, CIM800

The unverified input condition is evaluated according to the following table, depending on the mode (N/O or N/C) and the values of parameters P0, P1, and P2.

P2=0 P2 not = 0 N/O N/C

P0<=reading<=255 P0<=reading<P2 Alarm

P1<=reading<P0 P1<=reading<P0 Normal

Short

Normal

0<=Reading < P1 0<=Reading < P1 Open circuit fault

Changes in these states are verified as described in section 9.22.

Alarm

For the CIM800, if either input is in fault, the point will be in fault. If either input is in alarm, the point will be in alarm. It may therefore be in fault and alarm at the same time.

9.7.2 ALGORITHM - MIM801

The unverified input condition is evaluated according to the following table, depending on the mode (N/O or N/C) and the values of parameters P0, P1, and P2

P5=0 P5 not = 0 N/O N/C

circuit Alarm

Normal

Short circuit fault

P3<=reading<P4 P3<=reading<P4 Normal

0<=Reading < P3 P5<=Reading < P3 Alarm

0<=Reading < P5 Short circuit fault

Changes in these states are verified as described in section 9.22.

Issue 1.5 24 March 2006 Page 9-11

MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

9.8

Document: LT0273

Figure 9.8 shows the V / I characteristics for the DIM detector terminals, together with the

fault and alarm thresholds when using the default parameters. The shaded areas show the region of uncertainty.

Three lines are shown for three supply voltages.

4k7 EOL

30

25

20

15

10

5

0

0

A

F

L

U

T

N

O

R

M

A

L

10

A

L

A

R

M

19V

24V

28V

20 30

Load Current (mA)

Figure 9.8 DIM LoadLine Characteristics

40 50

The reading from the DIM module can be modelled using the following method.

Calculate “R” from a point on the load line = Load Voltage / Load Current.

Reading = 137000 / (560 + R)

For example take the point where the 4k7 EOL resistor crosses the 24V line.

R = 20.8 / .0044

Reading = 137000 / (560 + 4700)

Note that for a given “R”, the reading is independent of the supply voltage.

9.8.3 ALGORITHM - DIM800

The unverified input condition is evaluated according to the following table, depending on the values of parameters P1, P2, and P4. (if P4 is 0, assume it is 225).

Input

P4 <= reading <= 255

Condition (Mode 0) Condition (Mode 1)

Alarm Short

P1 <= reading < P4

P2 <= reading < P1

Alarm

Normal

Alarm

Normal

0 <= reading < P2 Open circuit fault Open circuit fault

Changes in these states are verified as described in section 9.22.

Page 9-12 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

9.8.4 SUPPLY MONITORING - DIM800

The DIM800 supply is monitored with input AI3 of the device ASIC. If the supply voltage is less than 18V, a SUPPLY FAIL fault is generated. (The threshold can be changed with parameter 3 if needed.) If the supply fails completely, a DIM800 with revision less than 10 will stop responding to polls and a NODE FAIL fault is generated.

9.9

Correct Relay state

Not activated

DI0 Condition

0 OK

Activated

1 OK

Changes in these states are verified as described in section 9.22. Verified faults

representing a “relay stuck” condition are logged as CONTROL CB FAIL at the MX4428, with the return to normal event logged as CONTROL CB NML.

9.10

9.10.1 PROGRAMMING

Supply Monitoring Required DO6

No 1

Yes 0

Input AI1

AI1 > P3

AI1 <= P3

Condition

Supply Fault

Supply OK

Note that Parameter 3 cannot reliably be adjusted to monitor supplies of different voltages.

9.10.3 EOL AND POSITION MONITORING

Correct Relay Position

Not activated

AI0

P1 < AI0 <= 255

P2 <= AI0 <= P1

0 <= AI0 < P2

Condition

Open circuit fault

Normal

Short circuit fault

Activated

Any

P1 <= AI0 < 255

0 <= AI0 < P1

Changes in these states are verified as described in section 9.22.

No Open Circuit Fault

No Short Circuit Fault

No Relay Stuck Fault

Relay Stuck Fault

Issue 1.5 24 March 2006 Page 9-13

MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

Document: LT0273

Both short circuit faults and open circuit faults will be logged as SUPERVISION FAULT, and relay stuck faults will be logged as CONTROL CB FAIL. Only the first fault will be logged.

When all relay faults go away, the event logged at the MX4428 will be NORMAL OFF or

NORMAL ON as the case may be, regardless of the original fault logged.

9.11 LPS PROCESSING

9.11.1 ELD AND POSITION MONITORING

Correct Relay Position

Not activated

AI0, AI1

AI0 > 200 AND AI1 < 50

50 < AI0 <= 110

Condition

Open circuit fault

Short circuit

0 <= AI0 <=50 Relay fault

Otherwise Normal

AI0 > 50

AI0 <= 50 AND AI1 <= 50

Relay Fault

Short circuit Activated

AI0 <= 50 AND 50 < AI1 <= 200 Relay Fault

Otherwise Normal

Changes in these states are verified as described in section 9.22.

Both short circuit faults and open circuit faults will be logged as SUPERVISION FAULT, and relay stuck faults will be logged as CONTROL CB FAIL. Only the first fault will be logged.

When all relay faults go away, the event logged at the MX4428 will be NORMAL OFF or

NORMAL ON as the case may be, regardless of the original fault logged.

9.12

9.12.1 GENERAL

The VLC800 is processed like an 814PH, with the following parameters.

Tracked Value is fixed at 12.

Alarm Threshold is fixed at 100. (Corresponding to a raw value of 112).

Filter Divisor is fixed at 3.

Step Limit is 255 (so essentially there is no step limit).

PreAlarm is adjustable at the MX4428.

So the only filtering is the exponential filter with a filter divisor of 3. This gives some filtering, but with a minimal delay.

As the alarm threshold is always 100, the current level (CV-TV) is an indication of the smoke level in terms of % of the alarm threshold programmed into the VLC800 itself.

Page 9-14 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

9.13 FILTER STEP LIMITS

Note that Step Limits are always expressed as “Units per 5 seconds”. This differs from MPR where heat units are “units per 10 seconds”, but smoke limits are “time to alarm” (the inverse). The MXP change results in

• Heat and smoke being consistent with each other.

• Using a constant slope, rather than a constant time to alarm, as the threshold is varied, means that increasing the alarm threshold also means that the minimum time to alarm will be increased which is generally what would be expected. This gave better results with the various sensitivities of the photo detector in the SSL test room, i.e. a constant

Step Limit could be used for all sensitivities.

9.14

A zone alarm test performs a test in the detector for all detectors in a zone which are capable of supporting it viz 814PH, 814CH, and 814I. The Detector LEDs do not operate. No filtering is applied during remote tests and the fuzzy logic is replaced by a simple comparison test. Any devices already in alarm, prealarm or fault, or isolated, do not partake in the test.

Failure of a capable detector to produce the expected output generates an immediate fault.

The actual alarm returned to the MX4428 goes through AVF if programmed.

The MXP does not return “Test Pass” until all alarm-capable devices in the circuit go into alarm.

9.15 ZONE FAULT TEST

No MX detectors are capable of a remote fault test. Therefore with all detectors and devices a fault is simulated in polling software.

“Test Pass” requires all devices in the circuit to pass.

9.16 AUTOTEST AND SYSTEM TEST

The Flash Checksum is checked. (Note also, a checksum fail on power up will result in the

MXP application software not even starting, but the MXP will await a program load via its diagnostic port.)

Specific checking of the configuration RAM is not required as it is being continually checked

(with anomalies resulting in a download request from the MX4428).

For an autotest where remote device testing is enabled in the MX4428, and for all system tests, all detectors which are capable of a remote alarm test are tested. The LEDs do not operate and no alarms caused only by the remote test are returned to the MX4428. A device with an external wiring fault or which is isolated, or in alarm or pre-alarm, is not subject the test and is not reported. A device with a fault, other than external wiring, or which is in scan fail scan fail, or relay checkback fail, or type mismatch, results in failure of the test (abnormal at start). No filtering is applied during remote tests.

Issue 1.5 24 March 2006 Page 9-15

MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

9.17

Document: LT0273

NON LATCHING TEST MODE

In this mode no alarms are latched, and all filtering is bypassed, however detector and device LEDs follow the alarm status. About 10 seconds after a device goes into alarm it is automatically “held in reset” for about 10 seconds, and then sampling starts again from the beginning.

9.18

Filtering is speeded up or bypassed. AVF is bypassed.

9.19 FAST POINT TEST

A point which supports remote test is put into alarm by its remote test facility. A point which does not support remote test is put into alarm by simulating a high reading. Filtering is speeded up or bypassed. AVF is bypassed.

9.20 SLOW POINT TEST

A point which supports remote test is put into alarm by its remote test facility. A point which does not support remote test is put into alarm by simulating a high reading. Filtering and

AVF operate normally.

9.21 SUMMARY OF ALL TEST MODES

Table 9-1 shows the features of the various alarm tests which may be applied to detectors

and input ancillary devices.

Note that there is no remote test facility on a 8xxH heat detector or on the heat component of a 8xxPH or 8xxCH detector. On MX4428 there is no way to specify an alarm test on the heat component of an 8xxPH or 8xxCH detector.

Page 9-16 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

Detector test applied

Circuit / zone goes into alarm

Yes - but zone isolated at

FIP

No

Mode

FastLogic

Filter Divisor

Switches to SmartSense

2 on Smoke / CO

As cfgd on heat

1 (bypassed)

Enhancement None

Step Limit Bypassed

None

Bypassed

As cfgd on DIM.

N/A Bypassed on analog detectors

Detector / Anc

LED operates

Yes

Alarm

Test test.

Auto test with test fire

Fast

Point

Test

Yes on smoke / CO

(Alarm result simulated on 8xxH ie Heat only detector and on ancillary input modules)

When

ALL points in alarm

No Yes

Slow Point Test

Yes on smoke / CO.

Simulated 100

°C on 8xxH.

Simulated alarm on ancillaries.

As cfgd

As cfgd

As cfgd

As cfgd

Yes

Point alarm generates event

History high, low updated

Tracking updated

FIP CV

Updated

Reset terminates test

No effect at MXP Yes

Yes

No

No

Yes

Yes

Table 9-1 Test Modes Summary

9.22

Normal

No

As cfgd

As cfgd

As cfgd

As cfgd

When alarm condition reached

Yes

Yes

Yes

Yes

N/A

If a poll returns the alarm state, then up to 5 immediate re-polls are made. If all these are still in the alarm state then an alarm is generated. If one of the succeeding polls is not in the alarm state, then immediate re-polling stops, but an up-down counter will be retained for the next poll. This counter counts up when an alarm condition is measured, and down when a non-alarm condition is measured. So if there are 5 polls in the alarm state then 1 non alarm the counter will be left at 4. On the next scheduled poll the counter starts from the value it had previously, so only 2 successive polls returning the alarm condition will be required to reach the alarm condition.

The up-down counter always counts up and down (between 0 and 6) depending on whether an alarm condition or not is read from the detector. When the counter reaches 6 a filtered alarm state is generated. When the counter reaches 0 a filtered non-alarm condition is determined. An immediate re-poll is done if the last poll is in the opposite state to the filtered state.

Ancillary faults are filtered in the same way, except that only 4 polls are needed rather than

6, and there is no immediate re-polling, 4 polls 5 seconds apart are required.

Issue 1.5 24 March 2006 Page 9-17

MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

9.23 RESET

Document: LT0273

9.23.1 RESET OF ADDRESSABLE DETECTOR

For about 20 seconds after reset is applied to an addressable detector, the exponential filter and slope limiting filter are disabled if their input values are less than their output values. In other words their outputs will follow their inputs downwards with no filtering. However increases in input values will be filtered as usual.

If the LED is latched on due to a previous alarm it will be turned off.

The state of any AVF applied to the detector is reset to the “no-alarm” quiescent state.

RESET has no effect on 814PH detectors operating in “FastLogic” mode.

9.23.2 RESET OF DIM MODULE

Power is removed from the attached conventional detectors for about 5 seconds. Then power is re-applied, and sampling resumes 5 seconds later.

If the DIM module LED is latched on due to a previous alarm it will be turned off.

The state of any AVF applied to the detector is reset to the “no-alarm” quiescent state.

9.23.3 RESET OF ANCILLARY INPUT DEVICE

If the LED is latched on due to a previous alarm it will be turned off.

The state of any AVF applied to the detector is reset to the “no-alarm” quiescent state.

9.23.4 RESET OF ANCILLARY OUTPUT DEVICE

No action.

Page 9-18 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

9.24 DEVICE INITIALISATION AND POLLING

The following actions are taken for each device when it powers up or when the MXP powers up. One action is performed on (or instead of) each 5 second poll.

• If fault bit was received, use HEALTH command to verify that fault was caused by powerup.

• Use READEE command to check type.

• Send SETALL command to select which values are returned, to set the interrupt thresholds (if any), set the Digital Outputs required for correct operation and set the status register for LED blink if required.

• Use READEE command to get factory calibration value for Photo and CO devices.

• Use READEE command to get factory “clean air” value for Photo and CO devices.

• Use READEE command to get the stored LED blink bit. This may require the SETALL command to be sent again.

Once this is complete FASTAV commands will be used to read the analog inputs (FASTDI command for RIM) on each poll, except for the occasional use of the SETOUT command to

Reset / unreset the DIM detectors and as a background refresh of digital outputs.

SETOUT commands to set changed digital outputs will be interspersed between polls, with no request to return data.

GLOBADR commands are used to find all devices during a “Learn” initiated by the MX4428 and “Diagnostic Pollscan” initiated by the MX4428 or MXP diagnostic terminal.

(Refer to the “NOSEx SPECIFICATION” document for more details of the above commands.)

Issue 1.5 24 March 2006 Page 9-19

MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

9.25

Document: LT0273

The following software versions have been released for general use.

Version Features

1.03 First full release

1.04

(Limited

Release)

1.05

(Limited

Release)

1.06

Fixed failure of photo self test when using fuzzy logic with some detectors.

Fixed standalone mode did not work if no valid database.

Added "typewrite" command to easily reprogram CO self test pulse length.

Fixed failure of CO self test with new detectors, and subsequent other faults due to the detector powering down.

Fixed failure of photo self test when using fuzzy logic with some detectors.

Fixed standalone mode did not work if no valid database.

Added "typewrite" command to easily reprogram CO self test pulse length.

Fixed failure of CO self test with new detectors, and subsequent other faults due to the detector powering down.

Added automatic detection of CO detectors with insufficient self test pulse length (as stored in detector eeprom), and correction thereof.

Fixed threshold used for remote test of photo detector using fuzzy logic with individual sensitivity.

Fixed reporting of scan-fail (problem introduced in 1.05).

Changed version returned to MX4428 from c0 to c6.

1.07

1.09

1.10

1.11

1.12

Implemented fast and slow point test, commission mode.

Fixed no scan fail fault on CH detector (introduced in V1.06)

Added support for LPS800. (Programmed as SNM800)

Changed version returned to MX4428 to c7.

Added support for Vesda VLC800.

Amended 814I remote test decision to prevent some detectors from incorrectly failing a remote test.

Changed version returned to MX4428 to c9.

Fixed CO detector processing. Versions 1.07 to 1.09 inclusive did not apply the "calibration factor" stored in the detector eeprom, meaning that most detectors were less sensitive than they should have been (possibly outside the SSL limits of +/- 50%).

VLC800 self test - moved decision point to the third poll after the "stimulus".

(The data at the previous decision point was not necessarily valid.)

Reprogrammed the eeprom containing the pulse length to the length required for the self test

MX4428 Analog diagnostics AO command did not always cancel AS and AQ commands. (PR was workaround.) AO now fixed.

Changed version returned to MX4428 to $ca.

DIM800 now has an option for short circuit fault

Fixed the problem that where there was only one DIM800 on the loop, and it was the only device on the loop, it did not get processed.

Fixed the 814PHFL Fastlogic modes, in particular smoke only actually selected heat only.

Changed version returned to MX4428 to $cb.

Fixed continual transmission of global maintenance alert on then off when a

“dirty” point was isolated. Changed version returned to MX4428 to $cc.

Page 9-20 24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

CHAPTER 10

MXP LOOP FILTER BOARD

Issue 1.5 24 March 2006 Page 10-1

MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

10.1

Document: LT0273

USE OF MXP LOOP FILTER BOARD

Some field problems have occurred with the MXP detector loop picking up interference from adjacent or nearby wiring, resulting in faults and possibly prealarms. The “MXP Loop Filter board” (part number PA1038) is now available and it can easily be fitted to an MXP in order to remove the interference and restore normal operation.

One or more of the following symptoms may be evident –

1. Intermittent “scan fail” faults.

2. Intermittent unexpected Prealarms.

3. The MXP diagnostic port “Total reply fail count” is much higher than expected

(normally you should get less than 1 per hour).

4. The above problems occur in time with some external event e.g. lift motors running, radio transmitters operating etc.

Note that symptoms 1 – 3 above can also be caused by other factors e.g. the loop has too many devices connected or is too long. The MXP Loop Filter board will not help if this is the case.

10.2 FITTING

Remove the loop wiring from the MXP. Fit the filter board in the loop wiring terminals of the

MXP. Then fit the loop wiring to the filter board. Refer to Figure 10.1.

Page 10-2

Figure 10.1 MXP Loop Filter Board Fitted to an MXP

24 March 2006 Issue 1.5

Document: LT0273 MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

Note – if you are fitting the board to an MXP in a responder box, you may need to tip the underside of the plastic standoffs inwards to get the board to fit into the MXP board connector easily – it will help if you rotate each standoff so that its plastic latch is pointing away from the edge of the board. Once the board is inserted you can straighten the standoffs before tightening the screws on the MXP loop wiring terminals.

Be sure to check that the system is operating normally, and that the problem you started with is solved.

10.3 DIAGNOSTICS

Connect a terminal or laptop running a terminal emulator program to the MXP diagnostics port using LM0041. Select baud 19200, no parity, 8 databits, 1 stop bit.

Enter the command RS. This will reset the error counters. Wait a few minutes. Enter TC. The

“Total reply fail count” count should be zero. Keep checking it periodically. It should not increase by more than about 1 per hour. If there is a problem the count may increase every few seconds. To try to correlate the errors/retries with other events you can keep typing TC

(or Control-R to repeat the last command) and see when the errors are occurring.

Alternatively to try to correlate the errors/retries with other external events you can enter the command NC (Nosex comms log toggle) so that the Nosex comms log is enabled. Then you will see activity on the screen in real time every time a device does not reply. (Note - one device that should not be present is polled every 5 seconds, it should not reply and this lack of reply is displayed on the screen). Be sure to type NC again so that the Nosex Comms log is disabled before disconnecting the terminal.

Issue 1.5 24 March 2006 Page 10-3

MX4428 MXP Engineering / Technical Manual

MXP Loop Filter Board

THIS PAGE INTENTIONALLY LEFT BLANK

Document: LT0273

Page 10-4 24 March 2006 Issue 1.5

advertisement

Key Features

  • Complies with Australian Standard AS4428.1 and New Zealand Standard AS/NZS 3548 1995 Class A
  • Can be used to create a customized fire detection and alarm system
  • Can be programmed to meet the specific requirements of a building or site
  • Can be used to monitor a variety of fire detection devices
  • Can be used to control a variety of fire alarm devices

Frequently Answers and Questions

What is the purpose of the MX4428?
The MX4428 is a fire indicator panel that can be used to create a customized fire detection and alarm system.
What are the benefits of using the MX4428?
The MX4428 can help to protect people and property from fire by providing early warning of a fire and by activating fire alarm devices.
How do I use the MX4428?
The MX4428 should be installed and programmed by a qualified electrician or fire alarm technician.