Gems SureSite Magnetic Liquid Level Indicator Instruction Bulletin
The Gems SureSite Magnetic Liquid Level Indicator is a shock and vibration-proof device that uses a float and flags to make the liquid level inside a tank visible, even at a distance. The SureSite is designed to work with a variety of liquids and is available in a variety of configurations, including standard, mini, and plastic. The SureSite can be used with a switch module to allow you to control a variety of devices based on the liquid level in the tank.
Advertisement
Advertisement
SureSite
®
Magnetic Liquid Level Indicator
Instruction Bulletin No. 177664-1
(Rev. F)
Section 1: Weldments
Thank you for purchasing the GEMS SureSite Magnetic Level Indicator. Please read this document prior to
installing your SureSite and store it where it may be readily referred to for familiarization and maintenance purposes. If you require any additional information, you are welcome to call GEMS at the number shown below.
1-800-321-6070
(Outside of the Continental U.S., call 860-747-3000)
Record the Part Number of your SureSite here to use when ordering spare or replacement parts:
Part Number:____________________
SureSite Operating Principle
The liquid level of a tank is made visible, even at great distances, through the use of a shock and vibration-proof magnetic level indicator that employs “flags” arranged within a specially constructed external housing: the flag assembly. The two sides of each pivoting flag are marked with contrasting colors. A permanent magnet is encapsulated inside each flag and forms a secure magnetic interlock with the adjacent flags. As the liquid level rises, a float equipped with a permanent magnet causes each of the flags to begin rotating in turn.
This action exposes the contrasting (fluid level indicating) color on the other side of the flag. As the float and liquid level rise, each flag below the level of the float completes a 180 degree rotation, while remaining magnetically interlocked with the other lower flags. Together, the rotated flags display a band or column of color, the height of which corresponds with the liquid level within the tank. An exclusive feature of the SureSite is the magnetic guide that is integrated into the flag assembly. This magnetic attraction ensures that the float is always aligned for optimum performance and exactness, regardless of any shock, vibration, or rapid change to the level of fluid in the tank.
Standard and Mini-SureSites are supplied with the floats packed either separately, or securely strapped to the unit. Top-mounted
SureSites are typically supplied with the floats installed and secured by a support tube. The float supplied with each unit has been designed to the specific gravity of the fluid being monitored, so that the permanent bar magnet will always seek and indicate the fluid surface.
Because of the attraction of the permanent bar magnet in the float and the patented magnetic guide, the SureSite flag assembly can be rotated to a position which will allow for optimum viewing.
Liquid
Flag Channel
Tank
Magnetic Flags
(Plain Side Out)
Magnetic
Float
Magnetic Flags
(Colored
Side Out)
Weldment
(See the Maintenance Section on page 5 for instructions on how to rotate your
SureSite flag assembly.)
- 1 -
Important!
Read the following instructions completely - BEFORE installing the SureSite.
Installation Precautions and Preparation
Failure to observe these precautions could affect the operation of your unit.
1. When locating the tank ports for the SureSite, make sure that no strong magnetic fields or magnetic materials
(such as railings, protective cages, I-beams, etc.) will be any closer than 6 inches (153 mm) from the SureSite.
2. Make necessary efforts to ensure that all tank-side modifications and equipment; i.e., the mating flanges, NPT
ports or shut-off valves (if used) will align properly with the SureSite connections. Improper alignment could
cause distortion and may damage welds and compromise the integrity of the SureSite and/or the tank.
3. After any necessary tank modifications are completed, the tank should be cleaned to remove contaminants. This
will ensure that the installation is free of foreign particles; especially those which could be magnetic and which
could impair the performance of the SureSite.
4. Do not begin the installation of the SureSite until all necessary tools and materials are obtained. (Such as
mating flange gaskets, bolting hardware, etc. )
5. Gasket material typically supplied with the standard SureSite unit is either Viton or nitrile rubber, Garlock 3000
style. Higher pressure units are typically supplied with Flexitallic TM gaskets. For replacement gaskets, please
consult GEMS Sensors for your specific material type.
6. All supplied flag assembly clamps are intended to be installed with a torque on the clamp screw not to exceed
5 lb.-inches.
Installation
Caution
Handle the SureSite with care to avoid damaging the threaded areas, flange surfaces, etc.
Note
If you have a top-mounted alloy or top-mounted plastic SureSite, skip to Page 4 for instructions.
For Standard SureSites (Alloy, Mini and Plastic)
1. Remove the protective packing materials from your SureSite.
2. Position the unit horizontally on a level surface.
3. Unpack the float assembly or, with the aid of a wire-cutter or similar device, remove the strapping that secures
the float to the exterior of the SureSite Unit.
- 2 -
Warning
D0 NOT: 1) Hold the SureSite in a vertical position or 2) Drop the float assembly into the unit. Avoid this or any action which could damage or dent the float. Such damage could cause the float to crush under normal working pressures.
TOP
Float
TOP
Float
Float
Weldment
Weldment
TOP
Flange
Flange
Weldment
Remove Bolts
Standard SureSite
Remove Bolts
Mini SureSite
Threaded
End Cap
Plastic SureSite
4. Remove the end cap or flange attaching bolts, as indicated in the appropriate drawing. Then remove
the end cap or flange.
5. With the unit still in a horizontal position, insert the float assembly into the weldment, with the “TOP” indication
on the float assembly moving in the same direction as the “UP” arrows that are located on each side of the
externally mounted flag assembly.
6. With the gasket or O-ring properly positioned, reassemble the end cap or flange to the weldment. Tighten the
end cap or flange bolts securely, using the proper recommended torque value as supplied in Figure A, page 5.
7. Slowly raise the top end of the SureSite, while the bottom end remains on the level surface, permitting the float
to slowly slide to the bottom, avoiding any sudden impact damage to the float assembly.
8. Move the SureSite to the tank and position the unit with the end marked “TOP” pointing upwards. Install any
necessary mounting gaskets or seals
2
, and align the mating port flanges, NPT’s or connections of the tank with
those of the SureSite. DO NOT ATTEMPT TO FORCE ALIGNMENT. To do so may damage the welds or
compromise the integrity of the SureSite. While following standard practices and procedures, tighten the flange
bolts, NPT’s or connections. Recommended torque values are supplied in Figure A, page 5.
9.
Before Filling the Tank . . . .
Be sure that the installation is free of foreign particles, especially any that are
magnetic. Check that all connections are secure. A hydrostatic pressure test of the complete assembly
is recommended.
NOTE
GEMS recommends that you include at least one support bracket in your installation for SureSite units greater than
10 feet (120 inches, 3048 mm) in length. Depending on the specific installation, a load-bearing support at the base of the SureSite may be beneficial.
______________________________________
2
Gaskets or seals for the port flanges are not supplied with the SureSite.
- 3 -
Installation for Top-Mounted Alloy SureSites
1. After removing any protective packing materials from your
top-mounted SureSite and positioning it horizontally on a level
surface, remove and discard the protective cap from the bottom of
the SureSite and carefully withdraw the cardboard support tube.
2. Slowly raise the top end of the SureSite, while the bottom end
remains on the level surface; permitting the float to slowly slide to
the bottom and avoiding any sudden impact damage to the float
assembly.
3. Position the necessary gasket or O-ring seal
3
on the tank mounting
flange and align the unit so that the bolt holes of the mating flange
match. The indicating face of the flag assembly should be directed
towards your desired point of observation. Do not attempt to force
alignment. To do so may damage the welds or compromise the
integrity of the SureSite.
4. While following standard practices and procedures, tighten the
flange bolts with the recommended torque values as supplied in
Figure A, page 5.
Installation for Top-Mounted Plastic SureSites
1. Remove the threaded stop pin from the bottom of the top-mounted
SureSite and slowly withdraw the support tube. Reinstall the stop
pin.
2. Slowly raise the top end of the SureSite, while the bottom end
remains on the level surface; permitting the float to slowly slide to
the bottom and avoiding any sudden impact damage to the float
assembly.
3. Position the necessary gasket or O-ring seal
3
on the tank mounting
flange and align the unit so that the bolt holes of the mating flange
match. The indicating face of the flag assembly should be directed
towards your desired point of observation. Do not attempt to force
alignment. To do so may damage the welds or compromise the
integrity of the SureSite.
4. While following standard practices and procedures, tighten the
flange bolts with the recommended torque values as supplied in
Figure A, page 5.
_____________________________
3
Gaskets or seals for the port flanges are not supplied with the SureSite.
- 4 -
Float
Float
Chamber
Cardboard
Support Tube
Protective
Cap
Float
Float
Chamber
Cardboard
Support Tube
Stop
Pin
Figure A
(Recommended Torque Values are for Lubricated Threads, Only)
Indicator Type
Fastener
Description
Nominal
Size
Torque Value
Standard Alloy,
Top-Mount Alloy
Standard Plastic,
Top-Mount Plastic
Bolt, Nut
Bolt, Nut
3/8 Inch
1/2 Inch
5/8 Inch
3/4 Inch
7/8 Inch
1 Inch
1-1/8 Inch
70 - 80 Lb.-Inches NTE
(Not to Exceed) 120 Lb.-Inches
30 Lb-Feet
60 Lb-Feet
100 Lb-Feet
150 Lb-Feet
250 Lb-Feet
350 Lb-Feet
15-20 Lb-Feed (Valid for bolts with flat washers under both boltheads and nuts)
Mini
Bolt, Nut
5/16 Inch
70 - 80 Lb-Inches
Flag Installation
General Notes
Under normal circumstances, it should not be necessary to reposition the flag assembly on your SureSite. However, if you find it desirable or necessary to reposition the flag assembly, we strongly recommend that you first mark the distance from the top of the weldment to the top of the flag assembly. Before securing the flag assembly in a new radial position, ensure that the distance from the top of the flag assembly to the top of the weldment is the same as the previously noted dimension. Making a temporary or permanent mark on the weldment can ease the process.
Maintenance
The only maintenance typically required is to ensure that the internal walls of the weldment and the float are free of foreign matter. This may be accomplished by removing the float assembly from the unit and wiping both the float and the inside wall of the float chamber or weldment. Any maintenance interval is to be established by the user of the
SureSite and would depend upon the characteristics of the application. Maintenance could coincide with tank cleaning or flushing.
Float Installation
Mini SureSite Float: (To set magnet position, please go to page 8.)
To accomplish the removal and subsequent reinstallation of the float assembly, follow the appropriate instructions provided on page 6 for the SureSite type and mounting configuration you have selected.
Caution
Make sure that the tank is depressurized and that liquid has been emptied prior to removal of the float assembly.
- 5 -
SureSite with Side Connections (Alloy, Mini and Plastic)
The float assembly can be removed without disturbing the mounting of the SureSite unit to the tank.
1. Carefully remove the end cap (access to the float assembly) which may be retained by bolts, NPT threads
or held in place by setscrews. The float assembly should be resting on the end cap as it is being lowered.
Support the float assembly while setting the end cap aside.
Note: For units supplied with top float access, the float assembly must be extracted from the top of the weldment by engaging the hooking ring provided on the top of the float.
2. Withdraw the float assembly from the unit, exercising caution not to damage the float. Note the “TOP”
indication marking on the float assembly.
3. Wipe down the weldment and the float assembly with a clean, lint-free cloth.
4. Carefully reinsert the float assembly into the weldment, ensuring that the “TOP” indication marking on the
float assembly is positioned in the same manner as when it was removed.
5. Remove the old gasket or O-ring from the end cap assembly and replace it with a new gasket or O-ring.
6. With the new gasket or O-ring properly positioned, reassemble the end cap assembly to the weldment.
Tighten the end cap or secure flange fasteners, using the proper recommended torque value, as supplied
in Figure A -page 5.
SureSite with Top and Bottom Connections (Alloy, Mini and Plastic)
The SureSite unit should be adequately supported when removing it from the tank.
1. Disconnect the top and bottom flange/socket or NPT connections.
2. Remove any other fasteners that retain the unit and/or support bracket(s) to the tank.
3. Remove the SureSite unit from the tank, while avoiding any motion that will cause damage to the float assembly.
4. With the SureSite placed in a horizontal position on a level surface, remove the end cap or flange and withdraw
the float assembly from the unit; noting the relative position of the portion of the float assembly marked “TOP”.
5. Wipe down the weldment and the float assembly with a clean, lint-free cloth.
6. Carefully reinsert the float assembly into the bottom of the float chamber or weldment, ensuring that the “TOP”
indication marking on the float assembly is positioned the same as when it was removed.
7. Remove the old gasket or O-ring from the end cap assembly and replace it with a new gasket or O-ring.
8. With the new gasket or O-ring properly positioned, reassemble the end cap assembly to the bottom of the
weldment. Tighten the end cap or flange bolts securely, using the proper recommended torque value, as
supplied in Figure A, page 5.
9. Complete installation of the unit by following the Installation Instructions for Standard SureSites (Page 3,
Steps 7, 8 and 9).
- 6 -
SureSites Mounted on Top of Tank
The construction of top-mounted SureSites varies with the material selected, and each requires a slightly different procedure than those preceding for “wipe-down”. It is advisable to mark or index mating flanges and other parts so that the relative positions of the components are maintained upon reassembly.
Alloy
1. Remove the attaching bolts that secure the SureSite unit to the top of the
tank. Lift the SureSite vertically from the tank and set it aside on a
level work area, in horizontal position. Exercise caution so that the
float assembly will not be dented or damaged. Remove any gasket
material from the tank and SureSite mounting flanges.
2. Remove the attaching bolts securing the external weldment (with the
attached flag assembly) to the mounting flange that was secured to your
tank, and carefully remove the weldment and gasket from the float
chamber, taking care not to damage the sphere-shaped magnet carrier.
3. While lightly supporting the magnet carrier, remove the upper (first)
cotter pin attaching it to the float rod. Set the magnet carrier and
cotter pin aside.
4. Remove the lower (second) cotter pin from the float rod and set it aside.
5. Withdraw the float and float rod from the bottom of the float chamber.
6. Wipe the inside of the float chamber and the exposed float assembly with
a clean, lint-free cloth.
7. After completing the “wipe-down” cleaning, the unit can be reassembled.
8. Obtain new gaskets for: a) Installation between the weldment and float
chamber
1
, and b) Installation between the mounting flange
2
of your tank
and that of the unit. Obtain new cotter pins for the float rod.
9. Insert the float assembly and rod into the float chamber, passing the float
rod up through the opening in the mounting flange. Secure the rod to the
float chamber by installing a cotter pin in the lower (second) hole and
securing it. Reinstall the magnet carrier to the float rod. Insert and
secure a cotter pin in the upper (first) hole to retain it.
10. Complete the remainder of the reassembly and installation by reversing
the process described in Steps 1 and 2. Refer to Figure A, page 5 for
recommended torque values for bolts. Use a new gasket: a) Between
the weldment and mounting flange of the float chamber, and b) Between
the mounting flange of your tank and that of the SureSite unit.
External
Weldment
Attaching
Bolts
Cotter
Pins
Float
Chamber
Flag
Assembly
Gasket
Magnet
Carrier
Float Rod
Mounting
Flange
Float
Protective
Cap
_____________________________________________
1
Contact Gems Sensors for spare or replacement parts
2
Customer-Supplied
- 7 -
External
Weldment
Mounting
Flange
Float
Chamber
Stop Pin
Flag
Assembly
Magnet
Carrier
Float
Hold the float vertical. A paper clip will attach to the magnet to show its position. Adjust the magnet position by gently tapping the end of the float.
Plastic
1. Remove the attaching bolts that secure the SureSite
unit to the top of the tank and lift the indicator unit
(with its float chamber) vertically from the tank. Set
it aside on a level work area, horizontally. Handle
the float assembly with care to prevent damage.
Remove any gasket material from the tank and
SureSite mounting flanges.
2. Unscrew and remove the stop pin from the bottom of
the float chamber.
3. Carefully withdraw the float, float rod, and attached
magnet assembly from the bottom of the float
chamber.
4. Wipe the inside of the float chamber and the exposed
float assembly with a clean, lint-free cloth.
5. After completing the “wipe-down” cleaning, the unit
can be reassembled. Obtain a new gasket for
installation between the mounting flange of your tank
and that of the SureSite unit. Prepare the mating
surfaces for reassembly.
6. Insert the float assembly and rod into the float
chamber, passing the magnet assembly and float rod
up through the bottom of the float chamber. Secure
the float assembly and rod to the float chamber by
reinstalling the stop pin.
Basic Float Part No. 807100
(Liquid Specific Gravity Range: 0.8 to 1.2)
Float
Part Number
85206
83453
85208
85209
84158
Liquid
Specific
Gravity
0.8
0.9
1
1.2
0.85
“X”
Dimension
5”
4.5”
4”
3.312”
4.75”
Float Part No.
W/Lift Ring
810919
810917
810916
810915
810918
Basic Float Part No. 807200
(Liquid Specific Gravity Range: 1.5 to 3.8)
Float
Part Number
88111
801708
Liquid
Specific
Gravity
1.9
1.5
“X”
Dimension
2”
2.6875”
Float Part No.
W/Lift Ring
810928
810927
TOP
807200
Æ
“X”
Dimension
Æ
Æ
“X” Dimension
Æ
TOP
807100
- 8 -
Condition
No change in Media
Level Indication
Incorrect Fluid Level
Indication
Incorrect Color
Indicating Fluid Level
Troubleshooting
Possible Cause
No Float
Float sticking, due to contamination in the fluid level
Float attracted, due to external ferrous materials within close proximity.
The float is damaged
Port is blocked
Float attracted, due to contamination in the media
Float sticking, due to external ferrous materials within close proximity
The float is damaged
The float is upside down
Flag assembly is upside-down.
(The wrong color is indicating the liquid level)
Solution
Install float
Clean the float and weldment
Remove the ferrous materials from close proximity
Replace the float
Remove blockage
Clean the float and weldment
Remove the ferrous materials from close proximity
Replace the float
Invert the float
Rotate the flag assembly 180 degrees (with the end marked
“TOP” uppermost)
Note: Increased viscosity increases the response time of the SureSite indicator
Warnings/Cautions
1. The SureSite Magnetic Level Indicator must be maintained and installed in strict accordance with this Instruction Bulletin. Failure to observe this warning could result in serious injuries or damages.
2. The liquids to be monitored must be compatible with the materials of construction. Specifications of these materials will be provided upon request.
- 9 -
SureSite
â
Magnetic Liquid Level Indicator
Installation, Operation and Maintenance
Bulletin No. 177664-2 (Rev. B)
Section 2: Switches
Operation
The SureSite Switch Module, available for use with the SureSite Magnetic Liquid Level Indicator, is a sealed assembly containing a magnetically actuated “latching-reed” switch assembly. The reed switch is actuated by the movement of the magnet contained in the SureSite float. The design of the reed switch permits the switch module to perform as either a “normally open” or “normally closed” switch. When installed with the lead wires (or junction box) installed at the top, the switch module is “normally open” and the reed switch will close with the rising fluid level in the tank; remaining closed until a falling fluid level in the tank causes the float to drop below the indicating position, opening the reed switch. When installed with the lead wires (or junction box) at the bottom, the switch module is “normally closed” and the reed switch will open with the rising fluid level in the tank, and remain open until a falling fluid level in the tank causes the float to drop below the indicating position, closing the reed switch. (See sketches below)
For electrical schematics of the switch module, please refer to the Wiring Diagrams, located on pages 5 and 6.
Lead W ires and Junction Box Positioned at T op Lead W ires and Junction Box Positioned at Bottom
Installation
General: The SureSite switch module must be mounted 180 o
opposite the flag assembly of the SureSite Magnetic
Level Indicator and within its operating range. The installation of the switch module varies, depending on the switch module housing and the type of SureSite Magnetic Level Indicator. The chart on the next page is intended to provide an overview of the various switch modules and to indicate which diagram(s) should be referred to for installation instructions.
1 of 6
Installation (Cont.)
If it is necessary to locate two switch-points close together, two switch modules can be positioned side-by-side and located 180 o
opposite of the flag assembly, as shown.
Flag
Assembly
T op V iew
T ype T emp (°F / °C)
Bracket / Spacer
Block
Clamp J-Box
85350
86435
86567
87480
80469
83140
83150
84320
803430
83100*
83110*
83120*
83130*
84330
Standard
Standard
Mini
Mini / Plastic
Plastic
All
All
All
All
All
All
All
All
All
20 VA SPST, N.O. or N.C.
20 VA SPST, N.O. or N.C.
20 VA SPST, N.O. or N.C.
300 / 148
300 / 148
300 / 148
20 VA SPST, N.O. or N.C.
300 / 148
20 VA SPST, N.O. or N.C.
300 / 148
High T emperature
20 VA SPST, N.O. or N.C.
20 VA SPST, N.O. or N.C.
20 VA SPDT, N.O. or N.C.
750 / 398
750 / 398
750 / 398
Incl.
Incl.
Incl.
220 VDC, 5 Amp 750 / 398 Incl.
Explosion-Proof / High T emperature
N/A
N/A
N/A
N/A
N/A
120 VDC, 10 Amp
24 VDC, 10 Amp
20 VA SPST, N.O. or N.C.
20 VA SPST, N.O. or N.C.
20 VA SPDT, N.O. or N.C.
750 / 398
750 / 398
750 / 398
750 / 398
750 / 398
Incl.
Incl.
Incl.
Incl.
Incl.
N/A
Incl.
Incl.
N/A
N/A
N/A
N/A
N/A
Incl.
N/A
N/A
N/A
Incl.
Incl.
Incl.
Incl.
Incl.
Incl.
N/A
N/A
N/A
N/A
N/A
Polysulfone
Polysulfone
Polysulfone
Polysulfone
Polysulfone
Incl.
Incl.
Incl.
Incl.
Incl.
316 SS
316 SS
316 SS
316 SS
316 SS
316 SS
316 SS
316 SS
316 SS
Explosion-proof for Class 1, Division 1, Groups C & D and Class 1, Division 2, Groups B, C & D; Dust ignition proof per Class
2, Division 1, Groups E, F & G and suitable for Class 3, Division 1, Hazardous Location, Indoors (Ref. File #J.I. 0A8A3.AE).
Also CSA certified for Class 1, Division 1, Groups B, C & D (Ref. Files LR22666-22 and LR22666-24).
For Standard Unit installation instructions, see Mounting Diagram “A”
For all other part numbers listed above, see Mounting diagram “B”, “C” or “D”
2 of 6
Standard SureSite
®
Switch Part Numbers
80469, 85350, 86435, 86567, 87480
1. Position the switch module 180° from the flag assembly and within indicating range.
2. Slide the switch clamp between the flag assembly and the weldment of your
SureSite Magnetic Level Indicator.
3. With the switch module located at the desired fluid level, tighten the clamp screw securely; not to exceed a torque of
10 lb-inches.
4. Connect the switch module leads to the load circuit.
1. Position the switch module 180° from the flag assembly and within indicating range.
2. Slide the tabs of the switch clamps between the flag assembly and the weldment of the Mini SureSite Magnetic
Level Indicator; wrapping the retaining screw-end around the upper and lower stem of the switch, as shown.
3. With the switch module located at the desired fluid level, tighten the clamp screw securely; not to exceed a torque of
120 lb-inches.
4. Connect the switch module leads to the load circuit.
Switch
Part Numbers
83100, 83110,
83120, 83130.
83140, 83150,
84320, 84330
Switch
Part Numbers
83150, 84320
Mini SureSite
®
1-1/4”
O.D.
Tubing
Flag
Assembly
ÕÕÕÕÕ
2-1/2”
Ref.
Switch
Module
#24 Clamp
(P/N 85576)
-2 Required
Flag
Assembly
ÕÕÕÕÕ
2-1/2”
Ref.
1-1/4”
O.D.
Tubing
Switch
Module
#24 Clamp
(P/N 85576)
-2 Required
J-Box Not
Included
On Type
83140
3 of 6
Mounting Diagrams (Cont.)
1. Slide the switch into the support bracket.
2. Position the switch module 180° from the flag assembly and within indicating range.
3. Slide the switch clamp between the switch bracket and the stem of the switch, then between the flag assembly and the weldment of your SureSite
Magnetic Level Indicator.
4. With the switch module located at the desired fluid level, tighten this clamp screw securely, not to exceed a torque of 120 lb-inches.
5. Connect the switch module leads to the load circuit.
1. Slide the switch into the plastic spacer block.
2. Position the switch module 180° from the flag assembly.
3. Slide the tabs of the switch clamps between the flag assembly and the weldment of your SureSite Magnetic
Level Indicator, wrapping the retaining screw-ends around the stem of the switch, above and below the spacer block and the desired indication/activation level, as shown.
4. With the switch module located at the desired fluid level, tighten both clamp screws securely, not to exceed a torque of
120 lb-inches.
5. Connect the switch module leads to the load circuit.
Switch
Part Numbers
83100, 83110,
83120, 83130.
83140, 83150,
84320, 84330
Alloy SureSite
®
Tubing or
Pipe
Flag
Assembly
#48 Clamp
(P/N 85577)
J-Box Not
Included
On Type
83140
Switch
Module
Flag
Assembly
Tubing or
Pipe
Switch
Part Numbers
83150, 84320
Switch
Module
Switch
Part Numbers
83100, 83110,
83120, 83130.
83140, 83150,
84320, 84330
#48 Clamp
(P/N 85577)
Plastic SureSite
®
Tubing or
Pipe
Flag
Assembly
#48 Clamp
(P/N 85577)
Switch
Module
P/N 802265
Spacer Block
J-Box Not
Included
On Type
83140
Switch
Part Numbers
83150, 84320
Tubing or
Pipe
Flag
Assembly
#48 Clamp
(P/N 85577)
Switch
Module
P/N 802265
Spacer Block
4 of 6
80469, 87480, 85350, 86435, 86567
R E D
R E D
S P S T, N.O. or N.C. (Dry)
Wiring Diagrams
120 VA C
_
+
- Dry Condition -
Y E L L O W
G R E E N
B L U E
O R A N G E
B R O W N
W H I T E
24 VDC
_
+
Part Number 831
10
- Dry Condition -
83120, 83140, 83150
- Dry Condition -
2-COND.
C A B L E
Y E L L O W
G R E E N
B L U E
O R A N G E
B R O W N
W H I T E
- Dry Condition -
84320, 84330 DPDT
- Dry Condition / J-Box at Top -
3-PIN
T E R M
3-PIN
TERM.
3-COND.
C A B L E
5 of 6
Wiring Diagrams (Cont.)
84320, 84330
- Dry Condition / J-Box at BTM -
3-PIN
TERM.
3-COND.
C A B L E
Switch Module Troubleshooting
Intermittent Switching or
Not Latching
Switch Not Switching
Switch Remains Open or
Closed At All times
Positioned Incorrectly
Switch not in Indicating Range
Incorrect Mounting Hardware
Incorrect Wiring Between
Switch & Load
Positioned Incorrectly
Switch Not in Indicating Range
Incorrect Mounting Hardware
Incorrect Wiring Between
Switch & Load
Switch Rating Exceeded
Reposition Switch Modules
Reposition Switch Modules
See Appropriate Mounting Diagram
Correct Wiring
(See Wiring Diagrams)
Reposition Switch Modules
Reposition Switch Modules
See Appropriate Mounting Diagram
Correct Wiring
(See Wiring Diagrams)
Replace Switch
(See Appropriate Rating Diagram)
6 of 6
SureSite
Magnetic Liquid Level Indicator
Installation, Operation and Maintenance
Bulletin No. 177664-3
Rev. E
Section 3: Transmitters
Operating Principle
The Gems SureSite Transmitter is a 3-wire device, externally mounted on the Gems SureSite Magnetic Level
Indicator. The maximum and minimum level indication position is marked on the transmitter housing. The
maximum indicator mark is red; the minimum indicator mark is blue.
The SureSite Transmitter is a voltage divider which extends the full length of visual indication, consisting of magnetic reed switches tapped in at regular intervals. As the SureSite float moves with the liquid level, it magnetically closes a series of staggered reed switches in a sequence that varies the resistance. A regulated
DC voltage applied to this voltage divider network will result in a proportional voltage output.
Standard
Transmitter
High Temp
EP Transmitter
2-Pc. High Temp
EP Transmitter
Mini
Transmitter
Body Material
Rated Temperature
(Process Media)
Black Polysulfone Plastic
300°F, 148°C
750°F, 398°C
316 SS
300°F, 148°C
Max. Ind. Length
276 “ (701 cm) 120 “ (305 cm)
240 “ (610 cm)
180 “ (457 cm)
Input Voltage
10 - 30 VDC
3/8”
Resolution
Mounting
Location / Position
(From Flag Ass’y
Standard Tubing / 90°
Standard Pipe / 125°
Plastic / 90°
Standard Pipe / Adjacent
180°
Standard Pipe / Adjacent
1234567890123456789012345678901212345678901234567890123456789
1234567890123456789012345678901212345678901234567890123456789
1234567890123456789012345678901212345678901234567890123456789
1234567890123456789012345678901212345678901234567890123456789
1234567890123456789012345678901212345678901234567890123456789
Installation
- Figure A -
Gems SureSite transmitter is typically installed on the SureSite Magnetic Level Indicator at the factory; however, if you purchased your transmitter separately, refer to Figure A above. Read all information carefully, before beginning installation.
*** Warning: To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing.
Standard Transmitter
Rotational Positioning
1. The SureSite transmitter is externally mounted and positioned either to the left or right of the flag
assembly, per Figure A.
2. Using the alignment guide (supplied), determine if the existing flag assembly position can be used or if
the flag assembly needs to be rotated to accommodate the transmitter. (See Figure B)
3. Using the flag assembly as a reference, position the SureSite transmitter using the red (maximum)
and blue (minimum) indication marks. Each indication mark should be placed approximately the same
distance from the top and bottom of the flag assembly.
1 of 6
Rotational Positioning (Cont.)
4. Outline the location of the transmitter and flag assembly on the SureSite
housing.
5. Loosen the clamps around the flag assembly to allow for installation of
the transmitter clamps. The flag assembly clamps should only be
loosened enough to permit the transmitter clamps to be inserted between
the flag assembly and the SureSite housing.
6. Install the transmitter and loosely clamp it in the location
outlined in step 4.
7. Tighten flag assembly clamps. Do not exceed 5 lb-inches.
8. Verify that the red (maximum) and blue (minimum) indication marks are
centrally located between the ends of the flag assembly.
9. Using the alignment guide, verify that the SureSite transmitter is
positioned correctly in relation to the flag assembly. Reposition if necessary.
10. Tighten the transmitter clamps securely. Do not exceed 5 lb-inches.
11. Wire to appropriate signal conditioner/converter or controller.
Note
To ensure continuous electrical output, the transmitter must lay flat against the SureSite housing over the entire length.
90° Must
Be Maintained
Max. Ind.
Mark (Red)
Min. Ind.
Mark (Blue)
- Figure B -
Max. Ind.
Mark (Red)
High Temp/Explosion-Proof Transmitter
Rotational Positioning
1. The high temperature/explosion-proof SureSite transmitter is externally mounted and positioned either to the left or right of the flag assembly, per Figure A.
2. Using the flag assembly as a reference, position the high temperature/explosion-proof SureSite transmitter using the red (maximum) and blue (minimum) indication marks. Each indication mark should be placed approximately the same distance from the top and bottom of the flag assembly.
3. The high temperature/explosion-proof SureSite transmitter is secured to the SureSite Magnetic Level Indicator housing using two mounting clamps. One clamp is positioned at the top of the high temperature/explosion-proof transmitter and the other clamp is positioned at the bottom. Position clamps as shown in the Figure C.
4. Tighten clamps securely.
Min. Ind.
Mark (Blue)
- Figure C -
2 of 6
2-Piece Transmitter - High Temperature/Explosion-Proof
Rotational Positioning
1. The 2-section high temperature/explosion-proof SureSite transmitter is externally mounted to the left
or right of (and adjacent to) the flag assembly and is positioned with the transmitter standoffs against
the SureSite weldment or housing. The lower section mounts to the right of the flag assembly - the
upper section mounts to the left; as indicated in Figure D.
2. Taking the upper section of the high temperature/explosion-proof SureSite transmitter and using the
flag assembly as a reference, position the transmitter section so that the red (maximum) indication
mark is one 1” below and to the left of the top of the SureSite flag assembly.
3. Loosely clamp the upper section of the high temperature/explosion-proof SureSite transmitter by
placing one clamp around the top and bottom of the transmitter section at the same location as the
transmitter standoffs. (See Figure D)
4) Taking the lower section of the high temperature/explosion-proof
SureSite transmitter and using the flag assembly as a reference,
position the transmitter section so that the blue (minimum)
indication mark is 1” above and to right of the bottom of the
SureSite flag assembly.
5. Loosely clamp the lower section of the high temperature/explosion-
proof SureSite transmitter by placing one clamp around the top and
bottom of the transmitter section at the same locations as the
transmitter stand-offs. (See Figure D)
6. If the blue (minimum) indication mark of the upper section and the
red (maximum) indication mark of the lower section (the centered
indication marks) are not aligned as shown in Figure D, reposition
both sections by sliding each section of the transmitter up or down
equally.
7. With the centered indication marks aligned, verify that the red
(maximum) indication mark of the upper section and the blue
(minimum) indication mark of the lower section are centrally
located between the top and bottom of the SureSite flag assembly.
Max. Ind.
Mark (Red)
Min. Ind.
Mark (Blue)
Max. Ind.
Mark (Red)
Note
If the red (maximum) and blue (minimum) indication marks are not centrally located between the top and bottom of the SureSite flag assembly, reposition the transmitter accordingly.
Min. Ind.
Mark (Blue)
- Figure D -
*Reminder*
The centered indication marks must remain aligned as shown for continuous indication.
8. Tighten clamps securely.
9. Wire per supplied diagram. Due to many different wiring combinations for the 2-piece high
temperature/explosion-proof SureSite transmitter, the wiring diagram is supplied with the unit.
If using a Gems explosion-proof SureSite transmitter, use the appropriate wiring method (per
N.E.C. Article 500).
3 of 6
Mini-Transmitter
Rotational Positioning
1. The Mini-SureSite transmitter is externally mounted and
positioned 180° from the SureSite flag assembly, per
Figure E.
2. Before installing the Mini-SureSite transmitter on your
SureSite Magnetic Level Indicator, outline the location of the
flag assembly on the indicator housing.
3. Remove the existing flag assembly clamps from the flag
assembly, one at a time. Replace these clamps with the new
flag assembly/transmitter clamps provided. When replacing
the old flag assembly clamps with the new flag assembly/
transmitter clamps, the Mini-Transmitter should be loosely
clamped 180° from the flag assembly. The new clamp secures
both the Mini-SureSite transmitter and the SureSite flag
assembly.
4. With all the clamps replaced, reposition the flag assembly to
the previously outlined location. Also, vertically position the
Mini-SureSite transmitter so that the red (maximum) and
blue (minimum) indication marks are centrally located
between the top and bottom of the SureSite flag assembly.
5. Verify that the Mini-SureSite transmitter is 180° from the
flag assembly. Reposition as necessary.
6. Tighten the flag assembly/transmitter clamps securely.
Do not exceed 5 lb-inches.
Max. Ind.
Mark (Red)
Min. Ind.
Mark (Blue)
- Figure E -
Service
Because the transmitter is not field-serviceable, the unit must be returned for repair or replacement.
4 of 6
Condition
No Output or
Loss of Signal
Transmitter Troubleshooting
Possible Cause
Positioned Incorrectly
Incorrect Wiring Between
Transmitter & Load
Transmitter Faulty
*
Solution
Reposition Transmitter
(See appropriate installation section)
Correct Wiring
(See wiring diagrams)
Repair or Replace
Transmitter
*
To Determine if Your Transmitter is Faulty:
1. Disconnect the transmitter from the signal conditioner/converter or controller.
2. With an ohmmeter, check the total resistance between the red and black wire of the high temperature/
explosion-proof Suresite transmitter. The resistance should read typically between 1200W and 1600W.
- If the resistance between the red and black wires reads as an open, contact Gems Sensors for
further assistance.
- If the resistance total between the red and black wires is verified, the SureSite float must be
removed from the SureSite magnetic level indicator. If you are unable to remove the float from
your Suresite,you must remove the transmitter from the Suresite housing.
3. With an ohmmeter, check the resistance between the red and white & the black and white wires of the
high temperature/explosion-proof SureSite transmitter. The resistance between both sets of wires should
read
∞
Ω.
If you are reading any resistance across either set of wires other than
∞
Ω,
contact Gems Sensors
for further assistance.
4. If all of the resistance readings and the transmitter’s position are verified as correct, but the SureSite
transmitter is still not operating correctly, contact Gems Sensors for further assistance.
If Your 2-Piece Transmitter is Faulty, Follow the Steps Below to Determine Which Section
to Replace:
1. Disconnect the upper section from the lower section of the 2-piece high temperature/explosion-proof
Suresite transmitter.
2. With an ohmmeter, check the total resistance between the red and black wires of the upper section
of the 2-piece high temperature/explosion-proof SureSite transmitter. The resistance should read
typically between 600 Ω and 800Ω. If the resistance between the red and black wires reads as an open,
contact Gems Sensors for further assistance.
If the resistance total between the red and black wires on the upper section is verified:
3. With an ohmmeter, check the total resistance between the red and black wires of the lower section
of the 2-piece high temperature/explosion-proof SureSite transmitter. The resistance should read
typically between 600
Ω
and 800
Ω
. If the resistance between the red and black wires reads as an
open, contact Gems Sensors for further assistance.
5 of 6
If the resistance total between the red and black wires on the lower section is verified:
4. The SureSite float must be removed from the Suresite magnetic level indicator. If you are
unable to remove the float from your SureSite, you must remove the transmitter from the
SureSite housing.
5. With an ohmmeter, check the resistance between the red & white and the black & white wires of the upper
section of the 2-piece transmitter. The resistance between both sets of wires should read
∞
Ω. If you are
reading any resistance across either set of wires other than
assistance.
∞
Ω, contact Gems Sensors for further
If the resistance total between the red and black wires on the upper section is verified:
6. With an ohmmeter, check the resistance between the red & white and the black & white wires of the lower
section of the 2-piece transmitter. The resistance between both sets of wires should read
∞
Ω. If you are
reading any resistance across either set of wires other than
assistance.
∞
Ω, contact Gems Sensors for further
7. If all of the resistance readings and the transmitter’s position are verified as correct, but the
SureSite transmitter is still not operating correctly, contact Gems Sensors for further assistance.
6 of 6
Bulletin No. 177664-4 (Rev . E)
Signal conditioners provide a regulated output (voltage or current) when used with Gems SureSite transmitters.
The signal conditioner is housed within a junction box with two or three ports. The ports allow for mounting and customer wiring. Your signal conditioner’s part number can be found on the identification plate located on the back of the junction box. Your unit has the operating and electrical characteristics indicated in the chart (for reference purposes) below:
Input V oltage
T ransient V oltage ith T ransmitter
86156
85997
0 to 5 VDC
0 to 12 VDC
8 to 24 VDC
15 to 30 VDC
± 0.4% of Full
Scale or ± 1” -
- Whichever is greater
4K Ohms/V Max
(.25 mA)
Metal Oxide Varistor
Rated @ 30 VDC
2K Ohms/V Max
(.5 mA)
Metal Oxide Varistor
Rated @ 38 VDC
86157
* 0 to 12 VDC
20 to 30 VDC
86158
112300
4 to 20 mA
4 to 20 mA
10 to 40 VDC
± 1.0% of Full
Scale or ± 1” -
- Whichever is greater
Range:
100 - 1200 Ohms
4 to 20 mA
152800
*
Note
1. Lower Alarm Point for P/N 86157 varies. The default setting is 2% to 50% of full scale.
2. Upper Alarm Point for P/N 86157 varies. The default setting is 50% to 98% of full scale.
Metal Oxide Varistor
Rated @ 68 VDC
250 Amps
86158, 1 12300,
SureSite transmitter readings. Converter calibration can be accomplished, using your transmitter or a transmitter simulator.
Calibration is simplified when using a transmitter simulator in place of the SureSite transmitter. Because the output voltage of the signal conditioner is stepped down to a fixed DC voltage, the transmitter and the transmitter simulator act as identical electrical loads, as interpreted by the converter.
For the purpose of calibration, rotating the shaft (wiper) of the transmitter simulator performs the same function as moving the SureSite float up and down inside the weldment.
In each case, the changing resistance will provide the proper output to calibrate the signal conditioner.
A transmitter simulator has been supplied with your converter/signal conditioner.
1 of 7
Minimum Excitation Required for Loop Resistance
40
30
20
10
0
0
200
400 600 800
1000 1200
R (Ohms) Termination Plus DC Loop Resistance
Installation Precautions and Preparations
W ith the exception of P/N 112300, all signal conditioners are typically installed on the SureSite magnetic level indicator at the factory. For those units so designated, the customer will have to provide electrical grounding, with an effective resistance of 1
W or less. Please refer to the Wiring Diagram(s) for your particular signal conditioner part number. Calibration of the signal conditioner can be accomplished using your SureSite transmitter or the transmitter simulator (supplied).
Terminal Blocks
(Ref.)
+8 to 24 VDC
-
+
#2 Rm
#1
Transmitter
Blk
Wht
Red
1 1
Terminal Blocks (Ref.)
+15 to 30 VDC
-
+
#2 Rm
#1
Transmitter
Blk
Wht
Red
1 1
#1: Remove wire from terminal 9 and connect it to
terminal 8 to provide “full” reference of the system.
#2: Output signal loading (Rm): 4K Ohms/V Max
(.25 mA)
#1: Remove wire from terminal 9 and connect to
terminal 8 to provide “full” reference of the system.
#2: Output signal loading (Rm): 2K Ohms/V Max (.5 mA)
The signal conditioner is typically installed on the SureSite magnetic level indicator at the factory.
If your signal conditioner was purchased separately, you may use one of the ½” FNPT ports for mounting.
None. Both of these units are calibrated at the factory.
2 of 7
This unit contains two relays intended to provide a high and low alarm signal for process control. These relays are
K1 and K2, respectively, in the wiring diagram. Standard alarm functions are K1 (High Alarm) and K2 (Low Alarm).
Other configurations are available upon request. Unless specified otherwise, the trip-point for the Low Alarm relay has been set at 5% of full scale, while that of the High Alarm relay has been set at 95% of full scale.
+20 to 30 VDC
- +
#2 Rm
High
High
Low
Low
High
Low
- W iring Diagram -
Terminal Blocks (Ref.)
K
1A
K
1B
K
1
K
2A
K
2B
K
2
Alarm Contacts Shown
With Relay De-energized
#1
#1: Remove wire from terminal 9 and
connect to terminal 8 to provide
“full” reference of the system.
#2: Output signal loading (Rm):
2K Ohms/V Max (.5 mA)
Transmitter
Blk
Wht
1 1
86157 Signal Conditioner is typically installed on the SureSite magnetic level indicator at the factory. If your signal conditioner has been purchased separately, you may use one of the ½” FNPT ports for mounting.
None. This unit is calibrated at the factory. If it is necessary to change the high and/or low alarm settings, you may follow the procedure provided below.
The alarm trip-points are adjusted by means of two separate twenty-turn potentiometers, through either the upper or lower 50% of the indicated range. The approximate set-point adjustment can be made by counting the number of revolutions from the end-stops of the pots. As a general ‘Rule of Thumb,’ you may expect 2.5% of the indicated range per turn. After you have established the desired trip-point(s) for the alarm relay(s), the adjusting knob(s) may be fixed with a small amount of RTV or other semi- permanent material.
3 of 7
Standard
Transmitter
See
Detail
“A”
V
Span Adjust
Null Adjust
SureSite
V isual Indicator
HEX Nut
#8-32
Flat Washer
P.C. Board
Spacer
Threaded
Rod
Detail “A” - P .C. Board Mounting
(T yp. 3 Places)
Span Adjust
Potentiometer oltage to Current Converter
Null Adjust
Potentiometer
1
2
3
4
5
6
The calibration procedure should be conducted with a potentiometer (transmitter simulator) which has a resistance value of
1.0 k Ohm , minimum, to a maximum of 2.5 k O h m . The transmitter simulator supplied with the signal conditioner has an adjustment range of 0 to 1000 ohms.
Maximum
Indication
Mark (Red)
High T emperature T ransmitter
2. Set and apply the D. C. power supply voltage at 24 VDC, with a 250 Ohm load resistance, as shown.
3. Adjust the span and null potentiometers at approximately mid-range.
4. Set the transmitter/simulator potentiometer adjusting screw to its fully clockwise position, for a maximum
indication on the digital multimeter (DMM).
5. With the span adjust potentiometer (see illustration), set the output current to 20 mA.
6. Turn the transmitter/simulator potentiometer adjusting screw to its fully counter-clockwise position, for a
minimum indication on the DMM.
7. With the null adjust potentiometer, set the output current to 4 mA.
8. Repeat steps #4 through #7 for the final fine adjustment. No further adjustments will be required.
9. After calibration, the converter/signal conditioner can be mated permanently to the transmitter assembly.
Any adjustments for null and span (4mA & 20 ma), due to D. C. loop resistance, are achieved by adjusting
the potentiometer screws
4 of 7
T ransmitter d m m
P
.C. Board
- W iring Diagram -
4-20 mA T
O +V A
V oltage
Installation Specifics
The signal conditioner is typically installed on the Gems SureSite magnetic level indicator at the factory. If your signal conditioner was purchased separately, you may use one of the FNPT ports for mounting.
5 of 7
Signal Conditioner Part Number 1 12300 (4 to 20 mA)
- Panel Mounted V ersion -
This unit incorporates a Linear Voltage to Current Converter.
- T op V
Red
- Calibration Wiring Diagram -
White
1
8
2
Black
P.C.
Board
3
4
5
+V
Source
250
W
DMM
Transmitter
4 to 20 mA
Tank Level Transmitter
Process
Control
Loop
Calibration Requirements
The calibration procedure should be conducted with a potentiometer (transmitter simulator) which has a resistance value of 1.0 k
W
minimum to a maximum of 2.5 k
W
. The transmitter simulator is supplied.
Calibration Procedure
Note: Calibration should be performed with the signal conditioner
disconnected from the SureSite transmitter.
1. Make connections as shown in the Calibration Wiring Diagram with the power supply turned off.
2. Set and apply the D.C. power supply voltage at 24 VDC with a 250
W
load resistance, as
shown in the diagram.
3. Adjust both the span and null potentiometers at approximately mid-range.
4. Set the transmitter/simulator potentiometer adjusting screw to its fully clock-wise position,
for a maximum indication on the digital multimeter (DMM).
5. With the span adjust potentiometer screw (see “Top View” diagram above), set the output
current to 20.00 mA.
6. Turn the transmitter/simulator potentiometer adjusting screw to its fully counter-clock-wise
position, for a minimum indication on the DMM.
7. With the null adjust potentiometer (see “Top View” diagram above), set the output current
to 4.00 mA.
8. Repeat steps 4 through 7 for the final fine adjustment. No further adjustments will be
required.
9. After calibration, the converter/signal conditioner can be installed at the desired location.
Any adjustments for null and span (4.00 & 20.00 mA), due to DC loop resistance, are
achieved by adjusting the potentiometer screws.
6 of 7
Installation Specifics
The panel-mount design of this unit permits remote installation. For mounting purposes, it is possible to remove the body of the unit from the terminal base. This permits the terminal base to be installed on two
3/16” studs or with two 3/16” screws, at the slotted holes provided. After installation of the terminal base, reinstall the body of the unit in its socket.
- Wiring Diagram -
Transmitter
Wht
Red
Blk
1
2
7
8
6
5
4
3
R
L
+ V
Source
4-20 mA Loop
- Signal Conditioner T roubleshooting -
No Output
Loose or Improperly Connected
W ires At Terminal Screws
Incorrect Wiring
Transmitter Positioning Incorrect
High or Low Alarm Points
Not Alarming at Desired
Setpoints
Alarm Setpoints Incorrect
Correct Connections
Correct Wiring (See Wiring Diagrams)
See SureSite Transmitter
Troubleshooting Section
Recalibrate Alarm Setpoints
(See Calibration Procedure)
7 of 7
SureSite
â
Magnetic Liquid Level Indicator
Installation, Operation and Maintenance
Bulletin No. 177664-5
Section 5: Power Supplies
The SureSite power supply is designed to provide regulated DC input voltage when only AC voltage is available.
This DC voltage can be used to supply the required input voltage to the Gems signal conditioner. Designed to accept a nominal 115 VAC or 230 VAC input (depending upon the unit ordered), the power supply’s output is 50 mA at 24
VDC, nominal. The power supply has an operating temperature range of -15°C to +70°C (-5°F to +158°F) and its output is thermally and short circuit protected against damage.
Installation
In most cases, the power supply is attached and wired to the signal conditioner at the Factory; requiring only to be wired to your AC voltage source. You may utilize any of the junction box 1/2” NPT ports to mount the unit in a fixed position.
- T ypical Installation -
1. With the power turned off and the circuit disabled, remove the cover from the junction box housing of the power supply, and remove the thread protector from the port you have selected for wiring. (See Installation Diagram).
Transmitter
4 to20mA Signal Conditioner
Power
Supply
2. Run your voltage source wiring through the appropriate strain relief device
1 junction box.
and into the
1/2” NPT
Nipple
- W iring Diagrams -
In
1 2 3 4
+
Out
In
1
2 3
4
230 VA C
+
Out
115
VA C
Ground
*
Ground
P/N 52560 - 1 15 V A C
P/N 52570 - 230 V A C
*
Negative output is not junction box grounded. A ground may be made, if required.
3. For 115 VAC Input Only
Connect your wiring to terminals 1 and 2 of Terminal Block-1. (See the wiring diagram for your
power supply.)
4. For 230 VAC Input Only
Connect your wiring to terminals 1 and 4 of Terminal Block-1. (See the wiring diagram for your power supply.)
*
1
Not
1 of 2
5. If your power supply is remotely mounted and has not been connected to the signal conditioner: a) Remove the thread protector(s) from the ports b) Connect the lead wires to the power supply output terminals. Run the wires through appropriate strain relief device(s)
1
and into the signal conditioner. (See the “Power Supply to Signal Conditioner” sketch.) c) See the appropriate signal conditioner wiring diagram for proper wiring instructions.
6. Reinstall the cover with its required O-ring on the junction box.
7. Enable the circuit and turn power on.
Signal
Conditioner
Power Supply Troubleshooting
24 VDC
Output Bad
Input Voltage Not Correct
Incorrect Wiring Between Signal
Conditioner and Power Supply
Loose or Improperly Connected
W ires at Terminal Screws
Apply the Proper Input Voltage
- 115 VAC or 230 VA C
Correct Wiring
(See Appropriate Wiring Diagrams)
Correct Connections
Blk
Red
Power
Supply
1
The Strain Relief Device is Not
2of 2
P/N 177664-5
Rev
. B
This Indicating Scale provides a numerical readout of the liquid level in the tank, in addition to the visual level displayed by the flag assembly. The indicating scale is mounted alongside the flag assembly with special clamps. The scale is normally graduated in inches and feet, but may be graduated in other dimensional or volumetric units. Scales that have an overall length of more than 24 inches will be provided in two or more sectional lengths.
Side V iew
Front V iew
Scales ordered with the SureSite Magnetic Level Indicator are factory-installed. If ordered separately, please follow the instructions below.
The scale is simply installed on your SureSite Magnetic Level Indicator using the bracketed clamps supplied.
1. Attach the scale onto the SureSite Magnetic Level Indicator, wrapping the clamps
around the flag assembly and the weldment.
2. Tighten the clamps securely, with a torque not to exceed 5 lb.-inches.
P/N 177664-6
Rev. B
SureSite
Magnetic Liquid Level Indicator
Installation, Operation and Maintenance
Bulletin No. 177664-7 (Rev A)
Section 7: Insulation Blankets
I n s t a l l a t i o n
Insulation Blankets are provided to minimize the possibility of personal injury and heat loss. Blankets have been designed for various SureSite Magnetic Level Indicators and mounting configurations, as indicated below:
Indicator Type
Mini
Mini
Standard
Standard
Standard
Mounting Configuration
Top and Bottom Mount
Side Mount
Top and Bottom Mount
Side Mount
Side Mount with Switches
Description
1-Piece
2-Piece
1-Piece
3-Piece
4-Piece
Cable Tie
Insulation
Blanket
M i n i - S u r e S i t e
- Top and Bottom Mount
(1-Piece Blanket)
The optional Heat Trace cable should be installed according to the supplied instructions prior to wrapping the Insulation
Blanket around the SureSite,as described below:
1. Wrap the long section of the Insulation
Blanket around the SureSite Magnetic
Level Indicator so that the area on either
side of the flag assembly is covered. The
flag assembly alone remains visible.
2. Using non-ferrous lock-wire, secure the
Insulation Blanket to the Mini-SureSite
at intervals of approximately 12 inches
(30 cm), as shown in the illustration.
Twist the wire ends to secure.
(See Figure A)
Heat Portion of Heater
Cable to be approx. XXX from Flag Assembly.
(Either side of flag assembly is fine.)
Cable Tie
Heat Cable
Extended Length
SureSite with
Optional Heat Trace
- Figure A -
1 of 3
SureSite with
Heat Trace & Insulation
M i n i - S u r e S i t e
Side-Mount
(2-Piece Blanket)
The optional Heat Trace Cable should be installed according to the supplied instructions prior to wrapping the insulation blanket around the SureSite, as described in the instructions below:
1. Wrap each of the two long sections of the insulation blanket around half of the SureSite Magnetic Level
Indicator so that the areas between the side connections and the flag assembly are covered. The flag
assembly remains visible.
2. Using non-ferrous lock-wire, secure the insulation blanket to the Mini-SureSite at intervals of
approximately 12 inches (30 cm), as shown in Figure A. Twist the wire ends to secure.
Standard SureSite
Top and Bottom Mount
(1-Piece Blanket)
The optional heat trace Cable should be installed according to the supplied instructions prior to wrapping the insulation blanket around the SureSite, as described below.
1. Wrap the long section of the insulation blanket around the SureSite, so that the area on either side of
the flag assembly is covered. The flag assembly alone remains visible.
2. Using non-ferrous lock-wire, secure the insulation blanket to the SureSite, as shown in the illustration
below (Figure B), at the “hog-ring”locations. Twist the wire ends to secure, drawing the insulation
blanket together, surrounding the flag assembly.
Standard SureSite
Side-Mount
(3-Piece Blanket)
Insulation
Blanket
The optional heat trace cable should be installed according to the supplied instructions prior to wrapping the insulation blanket around the SureSite, as described below:
1. Wrap the long section of the insulation blanket around
the SureSite, between the side connectors and position
the edges so that the flag assembly alone remains visible.
2. Using non-ferrous lock-wire, secure the insulation
blanket to the SureSite, as shown in the Figure B, at the
“hog-ring” locations. Twist the wire ends to secure,
drawing the insulation blanket together, surrounding the
flag assembly.
3. The remaining two pieces (the top and bottom collars) are
to be wrapped around the SureSite, and likewise secured
as in step 2. See Figure B for clarity.
- Figure B -
2 of 3
Standard SureSite
(4-Piece Blanket)
The optional heat trace cable, should be installed according to the supplied instructions prior to wrapping the insulation blanket around the SureSite, as described below:
1. Wrap each of the two long sections of
the insulation blanket around half of
the SureSite, so that the areas
between the side connectors and the
flag assembly are covered. The flag
assembly alone remains visible.
Cable Tie
Insulation
Blanket
2. Using non-ferrous lock-wire, secure
the insulation blanket to the
SureSite,as shown in the Figure C,
at the “hog-ring” locations. Twist the
wire ends to secure, drawing the
insulation blanket together,
surrounding the flag assembly.
Heat Portion of Heater
Cable to be approx. XXX from Flag Assembly.
(Either side of flag assembly is fine.)
3. The remaining two pieces (the top
and bottom collars) are to be wrapped
around the SureSite, and likewise
secured, as in step 2. See Figure C
for clarity.
Cable Tie
Heat Cable
Extended Length
(Coil for Shipping)
- Figure C -
3 of 3
SureSite
Magnetic Liquid Level Indicator
Installation, Operation and Maintenance
Bulletin No. 177664-8 (Rev A)
Section 8: Heat Trace
Operating Principle
The Heat Trace is a self-regulating length of heating cable intended for use with the SureSite Magnetic Level
Indicator. The cable is provided with a nominal six-foot (183 cm) power lead length. The heater cable portion
(or length) is typically rated at 10 Watts per foot, operating at 120 Volts. Power consumption is directly proportional to the length ordered.
Power Lead
Heater Cable
Cable Tie
Heat portion of heater cable to be approx. 90° from flag assembly.
(Either side of flag assembly is fine.)
I n s t a l l a t i o n
The Heat Trace may be installed on either side of the flag assembly.
1. Position the Heat Trace heater cable end at the
top of the SureSite and approximately 90 degrees
from the flag assembly, as shown.
2. Using two cable ties (supplied), attach the Heat
Trace at the top and bottom of the SureSite unit,
as shown.
3. Attach power leads to voltage source.
Cable Tie
Heat Cable Extended Length
SureSite
Magnetic Liquid Level Indicator
Installation, Operation and Maintenance
Bulletin No. 177664-9 (Rev A)
Section 9: Cold Service
I n s t a l l a t i o n
Standard SureSite
Cold service insulation has been completely installed on the SureSite Magnetic Level Indicator at the factory; except for the insulated cap assembly, which must be installed in conjunction with the installation of the Gems
SureSite.
For Top and/or Bottom NPT Connections:
1. Remove the flange and install the float into the unit. Refer
to “Section 1: Weldments” of Instruction Bulletin #177664
for detailed instructions.
2. After the float has been installed, reinstall the flange, using
the gasket and bolts. Refer to the torque chart in the
“Weldments” section for the appropriate torque value for the
bolts.
Lens
Note
The insulated cap assembly must first be
installed on the connecting pipe from the
tank, prior to starting the pipe-joint
connections.
3. Before mating the SureSite Magnetic Level Indicator to your
connecting piping, slide the insulated cap assembly back
(toward the tank), far enough to permit completion of the
pipe joint assembly, using the appropriate pipe thread
sealant.
4. With the top and bottom pipe joint completed, slide the insulated cap assembly until it is flush
with the SureSite insulation, and wrap the circumferential joint with the special tape supplied.
5. Apply an appropriate cold service sealant around the pipe/insulation interface.
1 of 2
For NPT/Flange Side Branch Connections:
1. Remove the flange and install the float into the unit. Refer to Section 1 of this Instruction
Bulletin (“Weldments”) for detailed instructions.
2. After the float has been installed, reinstall the flange, using the gasket and bolts. Refer to the
torque chart in the “Weldments” section for the appropriate torque value for the bolts.
3. Place the insulation end cap assembly over the bottom flange, flush with the SureSite
insulation.
Note
If the top or bottom NPT connection is plugged (i.e., welded cap with plugged NPT), remove the tape from the cap, apply the appropriate pipe thread sealant and complete the pipe joint. Using an appropriate cold service sealant, seal around the pipe and insulation interface.
4. Wrap the circumferential joint with the special tape supplied.
5. Complete the installation of your SureSite Indicator according to the instructions provided,
using an appropriate thread sealant and/or gasket material.
2 of 2
Advertisement
Key features
- Shock and vibration-proof
- Visible at great distances
- Multiple configurations
- Switch module compatible
- Various liquids
- Magnetic float and flags